Tender BOQ CIVIL ITEMS

advertisement

TENDER AND CONTRACT DOCUMENT

Name of Work:-“Construction and Development of Agri Food Cluster Campus of

National Agri Food Biotechnology Institute (NABI) at Mohali

(Punjab)”

Tender No. : RITES/CP/TC/ROC-II/NABI/Agri Food Cluster Campus/2013

PART 2

FINANCIAL BID

SCHEDULE (BILL) OF QUANTITIES

Name of the work :Construction and Development of Agri-Food Cluster Campus of National

Agri Food Biotechnology Institute(NABI) at Mohali(Punjab).

Tender No.:RITES/CP/TC/ROC-II/NABI/Agri Food Cluster Campus/2013

Sch.

No.

PARTICULARS

ABSTRACT SHEET

Estimated Cost

(In Rs.)

Quoted % above/below in

Figures & Words

Quoted Amount in Rs.

DSR BASED ITEMS

A

Civil Works

(Based on DSR-2012)

868052208.67

C

Electrical Works

(Based on DSR-2012)

23138745.65

E

HVAC WORK

(Based on DSR-2012)

MARKET BASED ITEMS

B

Civil Works

(Based on Market Rate Items)

635997.50

D

Electrical Works

(Based on Market Rate Items)

F

HVAC WORK

(Based on Market Rate Items)

Total amount

Un conditional Rebate if any

Amount after rebate in figure

Amount after rebate in Words

Name of the work :Construction and Development of Agri-Food Cluster Campus of National Agri Food

Biotechnology Institute(NABI) at Mohali(Punjab).

DSR SCHEDULE ITEMS(CIVIL) SCHEDULE-A

DSR

Item No.

1.1

S.

No.

1.00

1.01

Description of Items

CARRIAGE OF EARTH

Carriage of materials by mechanical transport including loading, unloading and stacking - for 5km.

1.1.2

2.31

a

2.00

2.01

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Earth

EARTH WORK

Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.

Cum

100 Sqm

14,093.22 125.92

119.83

482.00

1,774,618.26

57,758.06

2.8

2.02

Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.

2.8.1

2.7

a

2.03

All kinds of soil.

Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5m, disposed earth to be levelled and neatly dressed.

Cum 566.94 130.80 74,155.75

2.7.1

2.6

a

2.04

Ordinary rock

Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth.

1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

Cum 710.45 197.75 140,491.49

2.6.1

2.10

a

2.05

All kinds of soil

Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m including getting out the excavated soil, and then returning the soil as required, inlayers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m :

Cum 42,508.65 129.35 5,498,621.40

2.10.1

2.10.1.1

2.10.1.2

2.10.1.3

2.11

a ai

All kinds of soil

Pipes, cables etc, not exceeding 80 mm dia. aii aiii

2.06

Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.

Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.

Extra for excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over corresponding basic item for depth up to 1.5 metre).

metre

metre

709.20 101.40

metre 1,296.26 165.60

575.19 258.55

metre 1,617.08 136.89

71,912.88

214,660.66

148,715.37

221,362.08

2.12

2.16

2.07

2.08

Extra for excavating trenches for pipes, cables, etc, in all kinds of soil for depth exceeding 3 m in depth, but not exceeding 4.5 m.

(Rate is over corresponding basic item for depth up to 1.5 metre).

Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. Measurements to be taken of the face area timbered.

metre 1,246.85 351.86 438,714.15

2.16.1

a Depth not exceeding 1.5 m.

Sqm 1,400.61 101.85 142,652.13

DSR

Item No.

2.16.2

S.

No.

b

Description of Items

Depth exceeding 1.5 m but not exceeding 3 m.

2.16.3

2.17

c

2.09

Depth exceeding 3 m but not exceeding 4.5 m.

Close timbering in case of shafts, wells, cesspits, manholes and the like including strutting, shoring and packing cavities

(wherever required) etc. complete.(Measurements to be taken of the face area timbered).

Unit Quantity Rate

(Rs.)

Sqm 1,608.51 106.20

Sqm 929.54 115.95

Amount

(Rs.)

170,823.76

107,780.16

2.17.1

2.17.2

2.17.3

2.24

2.24.1

2.24.2

2.25

2.33.1

2.33.2

2.33.3

2.33.4

2.34

2.34.1

2.35

2.27

2.3

2.3.1

2.33

2.35.1

c

2.10

a a b b

2.11

Depth not exceeding 1.5 m.

Depth exceeding 1.5 m but not exceeding 3 m.

Sqm 1,391.81 104.90

Sqm 1,460.61 114.15

Sqm 1,061.54 123.85

146,000.87

166,728.63

131,471.73

Depth exceeding 3 m but not exceeding 4.5 m.

Extra rates for quantities of works, executed:

In or under water and/or liquid mud, including pumping out water as required.

Metre Depth 875.92 70.37

In or under foul position, including pumping out water as required.

Metre Depth 729.62 87.96

Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.

Cum 22,231.32 83.80

61,639.89

64,180.66

1,862,984.62

2.12

2.13

Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete.

Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m :

Cum 3,446.68 749.30 2,582,597.32

a

2.14

a d

2.15

b c a

2.16

a

All kinds of soil

Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.

Beyond 30 cm girth up to and including 60 cm girth

Beyond 60 cm girth up to and including 120 cm girth

Beyond 120 cm girth up to and including 240 cm girth

Above 240 cm girth

Supplying chemical emulsion in sealed containers including delivery as specified.

Chlorpyriphos/ Lindane emulsifiable concentrate of 20%

Diluting and injecting chemical emulsion for POST-

CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :

Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres/ sqm of the vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall & rodding etc. complete:

Cum

litre

40,118.83 181.25

Each

Each

Each

Each

66.00 148.20 9,781.20

63.00 654.95

35.00 3,026.30

26.00 6,071.30

41,261.85

105,920.50

157,853.80

11,189.75 185.95

7,271,537.94

2,080,734.01

2.35.1.1

2.38

ai With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration.

2.17

Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed

15 cm), with intermediate layer of compacted earth (Soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer in- charge, including compacting each layer by rolling/ ramming and watering , all complete as per drawing and direction of

Engineer -in - charge.

metre 1,270.30 11.80 14,989.54

Cum 3,950.49 83.80 331,051.06

3.00

CONCRETE WORK

DSR

Item No.

4.1

S.

No.

3.01

Description of Items

Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :

4.1.3

a 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size).

4.1.8

4.5

b

3.02

1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate

40mm nominal size).

Providing and fixing up to floor five level precast cement concrete string or lacing courses, copings, bed plates, anchor blocks, plain window sills, shelves, louvers, steps, stair cases, etc. including hoisting and setting in position with cement mortar 1:3 (1 Cement

: 3 coarse sand), cost of required centering complete.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Cum 521.52 4,514.05 2,354,167.36

Cum 1,723.65 3,593.30 6,193,591.55

4.5.1 a

4.12

4.17

3.03

3.04

1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate

20mm nominal size). Cum 258.13 5,525.20 1,426,219.88

Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer’s specifications.

Per 50KG

Cement

7,514.27 35.35 265,629.44

Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand including finishing the top smooth.

Sqm 1,408.35 338.75 477,078.56

5.1.1

5.1.2

5.9

5.9.1

5.9.2

5.9.3

5.9.5

5.9.6

5.9.7

5.9.14

5.10

5.1

5.10.1

5.10.2

5.10.3

5.10.4

5.11

5.11.1

4.00

4.01

REINFORCED CEMENT CONCRETE WORK

Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level.

a b

4.02

d e f g

4.03

a b c

1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate 20 mm nominal size).

1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate

20 mm nominal size).

Centering and shuttering including strutting, propping etc. and removal of form for :

Foundations, footings, bases of columns, etc. for mass concrete.

Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

Suspended floors, roofs, landings, balconies and access platform.

Lintels, beams, plinth beams, girders, bressumers and cantilevers.

Columns, Pillars, Piers, Abutments, Posts and Struts.

Stairs, (excluding landings) except spiral-staircases.

Extra for shuttering in circular work (20% of respective centering and shuttering items).

Providing and fixing tie bolt, spring coil and plastic cone in wall shuttering complete as per the direction of Engineer-in-charge.

Cum

Cum

Sqm

Sqm

Sqm

Sqm

Sqm

Sqm

Sqm

405.71 6,333.40

81.60 5,094.85

32,443.17 166.90

17,248.69 285.15

41,039.80 311.20

2,569,523.71

415,739.76

5,414,765.07

4,918,463.95

12,771,585.76

26,165.63 262.25 6,861,936.47

18,097.71 365.60 6,616,522.78

1,900.97 326.30 620,286.51

1,597.29 57.03 91,093.45

c d a b

4.04

a

12 mm dia. & 100 mm length.

12 mm dia. & 150 mm length.

20 mm dia. & 150 mm length.

20 mm dia.& 225 mm length.

Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of deshuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).

Each Set 425.00 125.95

Each Set 345.00 139.85

Each Set 475.00 153.80

Each Set 315.00 174.70

53,528.75

48,248.25

73,055.00

55,030.50

Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).

Sqm 21,320.48 121.65 2,593,636.39

DSR

Item No.

5.18

S.

No.

4.05

Description of Items

Providing precast cement concrete Jali 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6mm nominal size) reinforced with 1.6 mm dia mild steel wire including centering and shuttering, roughening cleaning, fixing and finishing in cement mortar 1:3 (1 cement: 3 fine sand) etc. complete excluding plastering of the jambs, sills and soffits.

5.18.1

5.22

a

4.06

5.22.6

5.22 A

5.22.6

5.30

5.33

a

4.07

a

4.08

4.09

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

50 mm thick.

Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.

Thermo-Mechanically Treated bars.

Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.

Thermo-Mechanically Treated bars.

Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.

Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.

(Note :cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/recoverable separately).

Sqm

Kg

1,312.13 598.15

1,144,927.36 62.25

784,850.56

71,271,728.16

Kg 1,860,243.33 62.25

metre 8,118.62 22.25

115,800,147.29

180,639.30

5.33.1

5.33.2

5.34

5.34.1

5.35

5.38

a b

4.10

a

All works upto plinth level

All works above plinth level upto floor V level

Extra for providing richer mixes at all floor levels.

Note:- Excess/less cement over the specified cement content used is payable /recoverable separately.

Providing M-30 grade concrete instead of M-25 grade BMC/RMC.

(Note:- Cement content considered in M-30 is @ 340 kg/cum)

4.11

4.12

Cum

Cum

10,467.82 5,242.15

14,210.25 5,781.50

Cum 2,491.93 63.20

Add for using extra cement in the items of design mix over and above the specified cement content therein.

Quintal

Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof. Cum

176.15 589.80

2,701.99 151.00

54,873,882.61

82,156,560.38

157,489.98

103,893.27

408,000.49

DSR

Item No.

S.

No.

DSR

Supplemen tary 5.44

4.13

Description of Items

Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor / floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components.

System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer's pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self -centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge . (Material shall confirm to ASTM 6063.)

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

5.44.2

a

DSR

Supplemen tary 5.45

4.14

Floor Joint of 150 mm gap

Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of

Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221-02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint

System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to

ASTM 6063).

metre 497.93 6,998.60 3,484,812.90

5.45.2

6.1

6.1.1

6.3

a

5.00

5.01

a

5.02

Wall Joint of 150 mm gap.

BRICK WORK

Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 75 in foundation and plinth in:

Cement mortar 1:4 (1 cement : 4 coarse sand).

Brick work with common burnt clay machine moulded perforated bricks of class designation 12.5 conforming to IS: 2222 in superstructure above plinth level up to floor five level in cement mortar 1:6 (1 cement : 6 coarse sand) :

metre

Cum

317.40 5,488.65 1,742,097.51

7,973.68 3,508.25 27,973,662.86

6.3.1

6.4

6.4.2

6.5

6.34

6.34.2

a

5.03

a

5.04

5.05

a

With F.P.S. (non-modular) bricks

Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in :

Cement mortar 1:6 (1 cement : 6 coarse sand)

Extra for brick work / AAC block masonry / Tile brick masonry in superstructure above floor V level for each four floors or part thereof by mechanical means.

Brick work with non modular fly ash lime bricks (FALG Bricks) conforming to IS:12894-2002, class designation 10 average compressive strength in super structure above plinth level up to floor V level in :

Cement mortar 1:6 (1 cement : 6 Coarse sand).

Cum

Cum

100.00 4,593.40

456.84 3,876.15

Cum 1,001.24 250.45

459,340.00

1,770,780.37

250,760.56

Cum 3,681.11 3,978.50 14,645,296.14

DSR

Item No.

6.38

S.

No.

5.06

Description of Items

Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position

2 Nos 8 mm dia M.S. bars at every third course of masonry work.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Cum 2,817.27 4,508.30 12,701,098.34

6.45

5.07

Half brick masonry with non modular fly ash lime Gypsum bricks

(FALG bricks) class designation 10, conforming to IS : 12894, in super structure above plinth and upto floor V level.

6.45.2

6.14

7.23

a

5.08

Cement mortar 1 : 4 (1 cement : 4 coarse sand).

Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means.

Sqm 7,483.07 503.10 3,764,732.52

Sqm 2,757.83 22.20 61,223.83

6.00

6.01

STONE WORK

Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade :

(To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately):

7.23.2

a

7.23.2.5

7.25

ai

6.02

Red sand stone - Exposed face machine cut and table rubbed with rough backing.

30 mm thick.

Providing and fixing stainless steel cramps of required size and shape for anchoring stone wall lining to the backing or securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the necessary chases in stone and holes in walls wherever required.

Sqm 4,589.55 2,236.00 10,262,233.80

Kg 22,947.76 524.10 12,026,921.02

7.27

8.2

8.2.1

8.2.1.1

8.2.1.2

8.2.2

8.2.2.1

8.2.2.2

8.3

8.3.1

8.3.2

6.03

7.00

7.01

Providing and fixing copper pins 7.5 cm long 6 mm diameter for securing adjacent stones in stone wall lining in cement mortar 1:2

(1 cement : 2 coarse sand), including making the necessary chases.

MARBLE & GRANITE WORK

Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over

20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.

Each 18,358.21 27.40 503,014.95

a b bi ai aii bii

7.02

a b

Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble.

Area of slab upto 0.50 sqm.

Area of slab over 0.50 sqm.

Granite of any colour and shade.

Area of slab upto 0.50 sqm.

Area of slab over 0.50 sqm.

Providing edge moulding to 18mm thick marble stone counters,

Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-

Charge.

Marble work.

Granite work.

Sqm

Sqm

353.22 1,894.75

Sqm 2,261.18 1,980.10

Sqm 516.13 3,041.15

5,064.71 3,083.40

669,263.60

4,477,362.52

-

1,569,628.75

15,616,526.81

metre

metre

5,696.71 105.70 602,142.25

7,978.67 178.75 1,426,187.26

DSR

Item No.

8.4

S.

No.

7.03

Description of Items

Extra for fixing marble /granite stone over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive including cleaning etc.

complete.

8.5

7.04

Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform, vanity counters and similar location in marble/Granite/stone work including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.

8.6

7.05

Mirror polishing on marble work/ Granite work/ stone work where ever required to give high gloss finish complete.

Unit

metre

Each

Quantity Rate

(Rs.)

1,786.04 185.80

604.00 281.10

Amount

(Rs.)

331,846.23

169,784.40

Sqm 7,629.53 163.10 1,244,376.34

8.8

7.06

Providing and fixing expansion hold fasteners on C.C.

/R.C.C./Brick masonry surface backing including drilling necessary holes and the cost of bolt etc complete.

8.8.1

8.8.1.1

8.8.1.3

8.9

a ai aii

7.07

Wedge expansion type.

Fastener with threaded dia 6 mm.

Fastener with threaded dia 12 mm.

Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and cement slurry

@ 3.3 kg/sqm including pointing in white cement complete.

Each

Each

410.00 22.05 9,040.50

399.00 38.95 15,541.05

8.9.1

8.9.1.1

8.9.1.2

aii

DSR

Supplemen tary 8.12

7.08

a ai

8mm thick.

Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble.

Granite of any colour and shade.

Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing

, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.

Sqm

Sqm

1,091.18 1,207.90 1,318,036.32

317.39 1,606.70 509,950.51

8.10

8.10.2

9.12

9.20

9.20.2

9.22

a

7.09

Flamed finish granite stone slab Jet Black, Cherry Red, Elite

Brown, Cat Eye or equivalent.

Providing and fixing stone slab table rubbed, edges rounded and polished of size 75x50 cm deep and 1.8 cm thick fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6mm nominal size) as per direction of Engineerin-charge and finished smooth.

Sqm 310.73 2,667.60 828,903.35

a Granite Stone of approved shade.

Sqm 129.44 2,942.05 380,818.95

8.00

8.01

WOOD AND PVC WORK

Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).

Sqm 1,086.77 5.80 6,303.27

8.02

Providing and fixing ISI marked flush door shutters conforming to

IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.

a

8.03

30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws.

Extra for Providing and fixing flush doors with decorative veneering instead of non decorative ISI marked flush door shutters conforming to IS: 2202 (Part I).

Sqm 2714.420

1984.800

5387580.816

0

DSR

Item No.

9.22.1

9.23

8.04

S.

No.

a On one side only.

Description of Items

Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).

9.70

8.05

Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete :

9.70.1

9.70.2

9.70.3

9.84

a b c

8.06

125 x 64 x 1.90 mm.

100 X 58 X 1.90 mm.

75 x 47 x 1.80 mm.

Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS :

3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.

Unit

Sqm

Sqm

Quantity

1014.000

2275.030

Rate

(Rs.)

371.700

325.200

Each 553.00 981.75

Amount

(Rs.)

376903.8

739839.756

Each

Each

Each

117.00 57.65 6,745.05

62.00 50.60

289.00 34.30

3,137.20

9,912.70

542,907.75

9.113

8.07

Providing and fixing bright finished 100mm mortice lock with 6 levers without pair of handles for aluminium door with necessary screws etc complete (Best make of approved quality) as per direction of Engineer-in-charge.

Each 73.00 410.00 29,930.00

9.114

8.08

Providing and fixing magnetic catcher in cupboard / ward robe shutters including fixing with necessary screws etc. complete .

9.114.1

9.114.2

9.132

9.136

a b

8.09

Triple strip vertical type.

Double strip (horizontal type).

Providing and fixing aluminum U beading of required size to Prelaminated/ flush door shutter including fixing etc. complete as per direction of Engineer-in-charge.

8.10

Each

Each

Kg

83.00 21.90

83.00 18.45

4,640.99 400.75

Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I.sheet (zinc coating not less than 120gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge(Dash fastener to be paid for separately).

metre 445.96 1,161.45

1,817.70

1,531.35

1,859,876.74

517,960.24

9.137

8.11

Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II) tested and certified as per laboratory approved by Engineer-incharge with suitable mounting on doorframe, consisting of vertical styles, lock rail, top rail 100mm wide, bottom rail200mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/sqm duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in charge(pannelling to be paid for separately).

Sqm 254.72 5,727.20 1,458,832.38

9.138

9.138.1

8.12

Providing and fixing glazing in fire resistant door shutters, fixed panels, ventilators and partitions etc., with G.I. beading of appropriate size made out of 20 SWG G.I.sheet (zinc coating not less than 120 gm/sqm sealant, including applying a coat of approved fire resistant primer on G.I. beading etc. complete all as per direction of Engineer-in-charge. a With clear fire resistant glass panes 6mm thick of approved brand, having minimum 60 minutes fire resistance. Sqm 110.40 25,435.15 2,808,040.56

DSR

Item No.

9.139

S.

No.

8.13

Description of Items

Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineerin- charge, all complete.

9.124 8.14 Providing and fixing factory made 30 mm thick door shutter made of solid PVC foam profile. The styles & rails shall be of size 75 mm x 30 mm having wall thickness 5 mm. The styles, top & bottom rails shall have one side wall thickness of 15 mm integrally extruded on the hinge side of the profile for better screw holding power. The styles and rails shall be reinforced with M.S. tubes of size 33 mm x 17 mmx 1 mm, painted with primer , all four corners of reinforcement to be welded or sealed. Solid PVC extruded bidding (push fit type) will be set inside the styles and the rails with a cavity, to receive single piece extruded 5 mm PVC sheet as panel. The styles and rails will be mitred cut and joint with the help of PVC solvent cement & self driven self tapping screws. Single piece extruded solid PVC lock rail of size 100 mm x 30 mm with wall thickness 5 mm & 15 mm integrally extruded in the middle of the lock rail & fixed with styles with the help of PVC solvent cement & self driven self tapping screws of size 100 mm x 8 mm complete as per manufacturer's specifications and direction of Engineer-in-charge.

Unit Quantity Rate

(Rs.)

Each 73.00 5,873.25

Amount

(Rs.)

428,747.25

9.124.1

9.124.2

9.140

a b

8.15

Non decorative finish.

Decorative finish (both side wood grained finish).

Providing and fixing plain lining with necessary screws/nuts & bolts/ nails, including a coat of approved primer on one face, and fixed on wooden /steel frame work, complete as per direction of

Engineer-incharge (Frame work shall be paid for separately).

Sqm

Sqm

201.00 2,609.55

219.00 3,050.90

524,519.55

668,147.10

9.140.1

a 12mm thick commercial ply conforming to IS : 1328 BWR type

Sqm 947.97 861.05 816,249.57

10.1

10.2

10.25

10.25.1

9.00

9.01

9.02

9.03

STEEL WORK

Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.

Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.

Structural steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.

a In stringers, treads, landings etc. of stair cases including use of chequered plate wherever required, all complete.

10.25.2

10.28

b

9.04

In gartings, frames, guard bar, ladder, railings, brackets, gates and similar works.

Providing and fixing stainless steel ( Grade 304) railing made of

Hollow tubes, channels, plates, sheets, pipes, angles, clamps etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of

Engineer-in-charge, ( for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc).

kg

kg

kg

kg

40,673.42 59.90

94,759.04 66.50

60,798.42 67.20

148,200.27 77.90

2,436,337.86

6,301,476.16

4,085,653.82

11,544,801.03

Kg 19,691.18 558.00 10,987,678.44

DSR

Item No.

10.6

S.

No.

9.05

Description of Items

Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 part 1 and M.S. top cover of required thickness for rolling shutters.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

10.6.1

10.8

10.8.1

10.8.2

10.9

10.17

a

9.06

a

80 x 1.25 mm M.S. laths with 1.25 mm thick top cover.

Extra for providing mechanical device chain and crank operation for operating rolling shutters.

Exceeding 10.00 sqm and upto 16.80 sqm in the area. b

9.07

Exceeding 16.80 sqm in area.

Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by

Engineer-in- charge, (area of grill to be measured).

Sqm

Sqm

Sqm

140.00 627.35 87,829.00

99.90 662.20 66,153.78

Sqm

239.90 1,840.85

134.90 261.35

441,619.92

35,256.12

9.08

Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S.

bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete.

Each 835.00 106.30 88,760.50

11.4

10.00

FLOORING

10.01

52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume,. hardening compound mixed @ 2 litre per 50kg of cement or as per manufacturers specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.

Sqm 3,087.76 420.55 1,298,557.47

11.6

11.6.1

11.8

11.23

10.02

Cement plaster skirting (up to 30 cm height) with cement mortar

1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement. a 18 mm thick.

10.03

Extra for making chequers of approved pattern on cement concrete floors, steps, landing, pavements etc.

10.04

Marble stone flooring with 18mm thick marble stone (sample of marble shall be approved by Engineer-in-charge) over 20 mm

(average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry including rubbing and polishing complete with :

Sqm

Sqm

309.73 258.20 79,972.29

3,087.76 24.10 74,415.02

11.23.3

11.23.4

11.23.5

11.24

11.25

11.26

11.26.1

a b

Agaria White

Black Zebra. c Udaipur green marble

10.05

Extra for pre finished nosing to treads of steps of marble stone.

10.06

Extra for marble stone flooring in treads of steps and risers using single length up to 2.00 metre .

10.07

Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : a 25 mm thick.

Sqm

Sqm

Sqm

Sqm

286.32 1,993.30 570,721.66

600.92 1,165.15 700,161.94

1,547.59 1,418.95 2,195,952.83

1,548.92 197.75 306,298.93

Sqm 1,926.92 230.55 444,251.41

Sqm 2,847.91 945.70 2,693,268.49

DSR

Item No.

11.27

S.

No.

Description of Items

10.08

Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

11.29

10.09

40 mm thick fine dressed stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement : 5 coarse sand), including pointing with cement mortar 1:2 (1 cement : 2 stone dust) with an admixture of pigment to match the shade of stone.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Sqm 1,511.61 954.10 1,442,227.10

11.29.1

11.30

11.30.1

11.30.2

11.31

11.32

11.45

a Red sand stone.

10.10

40 mm thick rubbed stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement :5 coarse sand) with joints

3 mm thick, side buttered with cement mortar 1:2 (1 cement : 2 stone dust) admixed with pigment to match the shade of stone and pointing with same mortar.

a b

Red sand stone.

White sand stone.

10.11

Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.

10.12

Extra for Kota stone/ sand stone in treads of steps and risers using single length up to 1.05 metre .

10.13

Providing and laying 500x500x40 mm thick Turf paver (Turfpave

XD) on 150 mm thick sub grade of compacted bed of 20 mm thick nominal size stone aggregate and base course and filling with 150 mm thick jamuna sand, including spreading, well ramming, consolidating and finishing smooth etc. all complete as per direction of Engineer-in-charge.

Sqm 1,710.31 538.30 920,659.87

Sqm

Sqm

metre

3,784.00 591.40

200.00 610.55

2,237,857.60

122,110.00

392.48 52.45 20,585.58

Sqm

Sqm

943.25 12.10

2,109.00 1,651.20

11,413.33

3,482,380.80

11.41

11.41.2

11.41.4

11.47

10.14

Providing and laying vitrified floor tiles in different sizes

(thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.

a b

Size of Tile 600x600 mm.

Size of Tile 1000x1000 mm.

10.15

Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than

0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).

Sqm 17,420.13 1,337.10 23,292,455.82

Sqm 2,236.39 2,246.10 5,023,155.58

11.47.2

11.48

a Size of Tile 600x600 mm.

10.16

Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of

Engineer-in-charge.

Sqm 8,868.55 1,503.90 13,337,412.35

11.48.2

11.36

a Size of Tile 600x600 mm.

10.17

Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineerin-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete.

Sqm 2,189.39 164.10 359,278.90

Sqm 2,385.73 724.25 1,727,864.95

DSR

Item No.

11.37

S.

No.

Description of Items

10.18

Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as

White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4

Coarse sand), including pointing the joints with white cement and matching pigment etc, complete.

Unit Quantity Rate

(Rs.)

Sqm 864.74 764.55

Amount

(Rs.)

661,136.97

DSR

Supplemen tary Items

No 11.54

10.19

Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings,as specified and as directed by Engineer-incharge consisting of :

(a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and

25mm outer diameter, fully welded on to the G.I. Base plate of size 100mmx100mmx3mm at the bottom of the pedestal tube,

G.I. pedestal head of size 75mmx75mmx3.5mm welded with GI fully threaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug.

Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings,as specified and as directed by Engineer-incharge consisting of :

(b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge.

(c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of

800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of

64 hemispherical cones. The top and bottom plates of Steel

Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip non-combustible Portland cementitious core mixed with lightweight foaming compound.

The access floor shall be factory finished with Anti-static High

Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The

panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and

Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineerincharge. All specification must be printed on the side of the panel to ensure the quality of the product.

11.54.2

a 450 mm Finished Floor Height

11.00

ROOFING

Sqm 334.98 3,917.75 1,312,367.90

DSR

Item No.

12.56

S.

No.

Description of Items

11.01

Providing and laying roof insulation with 40 mm thick impervious sprayed, closed cell free Rigid Polyurethane foam over deck insulation conforming to IS - 12432 Pt. III (density of foam being

40-45 kg/ cum), over a coat of polyurethane primer applied @ 6-8 sqm per litre, laying 400 G polythene sheet over PUF spray and providing a wearing course of 40 mm thick cement screed 1: 2 : 4

(1 cement :2 coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish, in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the joints with polymerized mastic, all complete as per direction of Engineer-in-

Charge.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Sqm 4,337.11 1,077.15 4,671,718.04

12.53

11.02

Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture spintone/cosmos / Hexa or equivalent of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main 'T' runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross "T" of size 24x28 mm made out of

0.33 mm (Minimum) sheet, 1200 mm long spaced between main'T' at 600 mm centre to centre to fometre a grid of 1200x600 mm and secondary cross 'T' of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture (Spintone / Cosmos/hexa) in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main 'T' runners to be suspended from ceiling using G.I.

slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main 'T' , bottom exposed with

24 mm of all T-sections shall be pre-painted .

12.54

11.03 Providing and fixing GI Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing 'C' wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of GI steel

0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring 'T' with :

Sqm 7,493.22 1,566.00 11,734,382.52

12.54.1

12.54.2

a GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G

I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.

Sqm 489.09 1,559.45 b GI Metal Ceiling Clip in plain Beveled edge global white olor tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G

I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation.

Sqm 140.00 1,680.30

762,711.40

235,242.00

DSR

Item No.

12.26

S.

No.

Description of Items

11.04

Providing and fixing plain Multipurpose Cement board ( High

Pressure steam cured ) as per IS : 14862, with suitable screws for fibre cement board in ceiling etc. complete (frame work to be paid separately) :

12.26.1

a 6 mm thick cement board.

12.28

11.05

Extra for providing and fixing ceiling to curved surfaces in narrow widths

12.31

11.06

Providing 10 mm thick plaster of Paris (gypsum anhydrous) ceiling up to a height of 5 m above floor level, over first class kail wood strips 25x6 mm with 10 mm gap in between and reinforced with rabbit wire mesh fixed to wooden frame (frame work to be paid separately) :

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Sqm 2,063.80 395.30 815,820.14

Sqm 652.97 124.05 81,000.93

12.31.1

12.41

a Flat surfaces

11.07

Providing and fixing on wall face unplasticised-Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring confirming to IS:5382,leaving 10 mm gap for thermal expansion .(i) Single Socketed pipes.

Sqm 684.45 676.15 462,790.87

12.41.1

12.41.2

12.42

a 75 mm diameter.

b 110 mm diameter.

11.08

Providing & fixing wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type-A, including jointing with seal ring confirming to IS:5382, leaving 10 mm gap for thermal .

metre

metre

1,130.00 124.90

1,620.00 206.90

12.42.1

12.42.1.1

12.42.1.2

12.42.5

12.42.5.1

12.42.5.2

13.16

aii b bi bii a ai

Coupler

75 mm

110 mm

Bend 87.5 Degree

75 mm bend

110 mm bend

12.00

FINISHING

12.01

6 mm cement plaster of mix :

13.16.1

13.4

a

12.02

1:3 (1 cement: 3 fine sand).

12 mm cement plaster of mix:

13.4.1

13.5

13.5.1

13.72

a 1:4 (1 cement: 4 coarse sand).

12.03

15 mm cement plaster on rough side of single or half brick wall of mix : a 1:4 (1 cement: 4 coarse sand).

12.04

Washed stone grit plaster on exterior walls height upto 10 metre above ground level, in two layers, under layer 12 mm cement plaster 1:4 (1 cement : 4 coarse sand ), furrowing the under layer with scratching tool, applying cement slurry on the under layer @

2 Kg of cement per square metre, top layer 15 mm cement plaster

1:1/ 2:2 (1 cement: 1/2 coarse sand : 2 stone chipping 10 mm nominal size), in panels with groove all around as per approved pattern, including scrubbing and washing the top layer with brushes and water to expose the stone chippings ,complete as per specification and direction of Engineer-in- charge (payment for providing grooves shall be made separately).

each

each

each

each

Sqm

Sqm

Sqm

Sqm

186.00 97.60

128.00 130.25

13.00 104.55

20.00 156.95

21,351.18 101.00

25,926.59 132.10

32,735.94 153.60

9,537.50 417.35

18,153.60

16,672.00

1,359.15

3,139.00

2,156,469.18

141,137.00

335,178.00

3,424,902.54

5,028,240.38

3,980,475.63

13.73

12.05

Forming groove of uniform size in the top layer of washed stone grit plaster as per approved pattern using wooden battens, nailed to the under layer, including removal of wooden battens, repair to the edges of panels and finishing the groove complete as per specifications and direction of the Engineer-in-charge :

13.73.1

13.74

a 15 mm wide and 15 mm deep groove.

12.06

Extra for washed grit plaster on exterior walls of height more than

10 m from ground level for every additional height of 3 m or part thereof.

metre 5,837.61 23.65

Sqm 5,524.10 65.85

138,059.48

363,761.99

DSR

Item No.

13.19

S.

No.

Description of Items

12.07

Rough cast plaster upto 10m height above ground level with a mixture of sand and gravel or crushed stone from 6mm to 10mm nominal size, dashed over and including the fresh plaster in two layers, under layer12mm cement plaster 1:4 (1 cement: 4 coarse sand) and top layer 10mmcement plaster 1:3 (1 cement: 3 fine sand) mixed with 10% finely grounded hydrated lime by volume of cement.

13.19.1

13.22

13.23

13.23.1

13.26

13.37

13.37.1

13.60

13.60.1

13.43

13.43.1

13.45

13.45.1

13.47

13.47.1

13.51

13.51.2

13.80

13.61

13.61.1

15.3

15.2

15.2.2

15.7

15.7.4

a Ordinary cement finish using ordinary cement.

12.08

Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.

12.09

Extra for plastering on circular work not exceeding 6 m in radius: a In one coat.

12.10

Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.

12.11

White washing with lime to give an even shade: a New work (three or more coats).

12.12

Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : a Two or more coats on new work.

12.13

Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : a Water thinnable cement primer.

12.14

Finishing walls with textured exterior paint of required shade : a New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @2.20kg/10 sqm.

12.15

Finishing walls with Premium Acrylic Smooth exterior paint with

Silicone additives of required shade : a New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/

10 sqm)

12.16

Painting with silicon & acrylic emulsion based water thinnable sealer of approved brand and manufacture on wet or patchy portion of plastered surfaces: a Two coats

12.17

Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.

12.18

Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: a Two or more coats on new work.

13.00

DISMENTLING & DEMOLISHING

13.01

Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - incharge.

13.02

Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.

a Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix).

13.03

Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-incharge.

a In cement mortar

Unit

cum 80.00 978.95 78,316.00

cum 35.00 413.65 14,477.75

cum

Quantity Rate

(Rs.)

Amount

(Rs.)

Sqm 1,584.05 315.30 499,450.97

Sqm 1,232.38 28.85 35,554.16

Sqm 50.00 13.65 682.50

Sqm 21,802.10 83.80 1,827,015.98

Sqm 4,533.77 11.75 53,271.80

Sqm 73,060.75 60.25 4,401,910.19

Sqm 73,060.75 27.55 2,012,823.66

Sqm 5,098.61 117.70

Sqm 9,249.68 80.45

Sqm 180.00 77.85 14,013.00

Sqm 54,515.28 76.05 4,145,887.04

Sqm 47,000.00 53.85 2,530,950.00

300.00 566.60

600,106.40

744,136.76

169,980.00

DSR

Item No.

15.12

S.

No.

Description of Items

13.04

Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc.

complete and stacking within 50 metres lead :

15.12.1

15.12.2

15.25

16.3

16.3.9

16.68

a Of area 3 sq. metres and below.

b Of area beyond 3 sq. metres.

13.05

Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead.

14.00

ROAD WORK

14.01

Supplying and stacking at site.

a Good earth.

14.02

Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of

Engineer-in-charge.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Sqm

Sqm

40.00 101.70 4,068.00

25.00 139.85 3,496.25

Sqm 180.00 73.70 13,266.00

Cum 14,093.22 260.70 3,674,102.45

Sqm 15,718.98 536.65 8,435,590.62

16.69

14.03

Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge

(length of finished kerb edging shall be measured for payment).

(Precast C.C. kerb stone shall be approved by Engineer-incharge).

Cum 1,483.93 5,046.80 7,489,097.92

Supply

DSR 2012

Item 16.89

14.04

Providing and laying matt finished vitrified tile of size 300 x 300 x

9.8mm having with water absorption less than 0.5% and confometreing to IS: 15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar

1:4 (1cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.

Sqm 162.00 899.65 145,743.30

Supply

DSR 2012

Item

No.16.91

14.05

Providing and laying factory made coloured chamfered edge

Cement Concrete paver blocks of required strength, thickness & size/shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of fine sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with jamuna sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand in footpath, parks, lawns, drive ways or light traffic parking etc. complete as per manufacturer's specifications & direction of Engineer-in-Charge. 60mm thick C.C.

paver block of M-35 grade with approved colour, design & pattern.

Sqm 11,331.00 703.80 7,974,757.80

16.1

14.06

Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of

22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres.

Sqm 20,607.00 61.25 1,262,178.75

16.2

16.3

16.3.1

16.3.2

14.07

Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density).

14.08

Supplying and stacking at site.

a 90 mm to 45 mm size stone aggregate b 63 mm to 45 mm size stone aggregate

Cum 3,297.12 7.75 25,552.68

Cum 985.07 1,010.75

-

995,659.50

Cum 811.71 1,100.80 893,530.37

DSR

Item No.

16.79

S.

No.

Description of Items

14.09

Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm) to wet mix macadam

(WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

Cum 5,700.85 1,960.60 11,177,086.51

16.80

14.10

Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to

IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineer-incharge.

Cum 2,060.70 2,896.15 5,968,096.31

16.42

16.43

14.11

Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) in pavements, laid to required slope and camber in panels as required including consolidation finishing and tamping complete.

Cum 1,545.53 4,502.55 6,958,826.10

14.12

Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints ( 10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately).

Note:- Cement content considered in M-30 is @ 340 kg/cum.

Excess/ less cement used as per design mix is payable/ recoverable separately.

16.43.1

16.44

16.45

16.46

16.46.1

16.47

a Cement concrete prepared with batch mixing machine

14.13

Extra for providing and mixing hardening compound of approved quality as per manufacturer's specification in cement concrete.

Cum 2,060.70 5,619.50 11,580,103.65

Litre 4,121.40 43.00 177,220.20

14.14

Providing and fixing in position pre-moulded joint filler in expansion joints.

per cm depth per cm width per m length

19,200.00 2.40

14.15

Providing and laying in position bitumen hot sealing compound for expansion joints etc.

per cm depth per cm width per m length a Using grade 'A' sealing compound.

19,200.00 1.65

14.16

Painting runway/taxi track/apron marking with adequate nos of coats to give uniform finish with road marking paint of superior make as approved by the Engineer-in-charge, i/c cleaning the surface of all dirt, scales, oil, grease and other foreign material etc. and lining out complete.

46,080.00

31,680.00

16.47.1

a New work (Two or more coats).

Sqm 1,030.35 94.90 97,780.22

DSR

Item No.

16.60

S.

No.

Description of Items

14.17 Manufacturing, supplying and fixing retro reflective overhead signage boards made up of 2 mm thick aluminium sheet, face to be fully covered with high intensity and encapsulated lens type heat activated retro reflective sheeting conforming to type - III of

ASTM-D-4956-01 as approved by Engineer-in-charge, letters, borders etc. as per IRC : 67-2001 in silver white with blue colour back ground and with high intensity grade, pasted on substrate by pressure sensitive adhesive backing which shall be activated by applying pressure conforming to class II of ASTM-D-4956-01 and fixing the same to the plate of structural frame work by means of suitable sized aluminium alloys, rivets or bolts & nuts @ 300 mm centre to centre all along the periphery as well as in two vertical rows along with theft resistant measures, including the cost of painting with two or more coats of epoxy paint in grey colour on the back side of aluminium sheet including appropriate priming coat. The rate includes the cost of rounding off the corners, lowering down the structural frame work from the gantry, fixing and erecting the same in position all complete as per drawings, specification and direction of the engineer-in-charge. (Structural frame work including M.S. plate to be provided separately.

Rectangular area of the sheet only shall be measured for payment).

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

16.60.1

16.62

a Overhead informatory road signage

14.18

Providing and applying 2.5 mm thick road marking strips

(retroreflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour ,T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications.

Sqm 84.00 4,516.50

Sqm 1,030.35 505.80

379,386.00

521,151.03

16.65

17.31

17.32

14.19

Providing and fixing post delineators made of ABS round body fitted with 2 nos 100 mm dia high reflective reflectors and mounted on MS pipe of 65 mm dia duly powder coated anti-rust and anti theft steel to be installed as per direction of Engineer-incharge.

15.00

SANITARY INSTALLATION

15.01

Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

15.02

Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :

Each 10.00 562.55 5,625.50

each 103.00 674.05 69,427.15

17.32.3

17.32.4

17.10

a b

Oval shape 450x350 mm (outer dimensions).

Rectangular shape 1500x450 mm.

15.03

Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making goodthe walls wherever required :

each

each

24.00 642.80 15,427.20

65.00 1,211.00 78,715.00

17.10.1

17.10.1.1

17.10.2

17.10.2.2

17.70

a ai

Kitchen sink with drain board.

510x1040 mm bowl depth 250 mm.

b bi

Kitchen sink without drain board.

610 X 460 MM bowl depth 200mm.

15.04

Providing and fixing PTMT Bottle Trap for Wash basin and sink.

17.70.2

a Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms.

each

each

each

58.00 6,743.55 391,125.90

10.00 3,702.00 37,020.00

68.00 435.80 29,634.40

17.35

15.05

Providing and fixing soil, waste and vent pipes:

DSR

Item No.

17.35.2

S.

No.

a 75 mm dia.

17.35.2.2

ai

Description of Items

Centrifugally cast (spun) iron socketed pipe as per IS: 3989:

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

metre 1,245.00 744.50 926,902.50

17.35.1

17.35.1.2

17.65

17.65.2

17.65.1

b bi

100 mm dia.

Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per

IS: 3989:

15.06

Painting sand cast iron / centrifugally acst (spun) iron soil, waste vent pipes and fittings with paint of any colour such as chocolate grey, or buff etc. over a coat of primer (of approved quality) for new work: a b

75 mm dia.

100 mm dia.

17.39

17.39.2

17.39.2.2

17.39.1

17.39.1.2

15.07

Providing and fixing plain bend of required degree: a ai b bi

75 mm dia.

Sand cast iron S&S as per IS - 3989.

100mm dia.

Sand cast iron S&S as per IS - 3989.

17.43

17.43.1

17.43.1.2

15.08

Providing and fixing single equal plain junction of required degree with access door, insersion rubber washer 3 mm thick, bolts and nuts complete. a ai

100x100x100 mm.

Sand cast iron S&S as per IS - 3989.

17.44

15.09

Providing and fixing single equal plain junction of required degree:

17.44.1

17.44.1.2

17.44.2

17.44.2.2

17.56

17.56.1

17.56.1.2

17.56.2

17.56.2.2

17.58

a ai

100x100x100 mm.

Sand cast iron S&S as per IS - 3989.

b bi

75x75x75mm.

Sand cast iron S&S as per IS - 3989.

15.10

Providing and fixing terminal guard: a 100 mm.

ai b

Sand cast iron S&S as per IS - 3989.

75 mm bi Sand cast iron S&S as per IS - 3989.

15.11

Providing lead caulked joints to sand cast iron/ centrifugally cast

(spun) iron pipes and fittings of diameter:

metre 3,995.00 857.30 3,424,913.50

metre

metre

1,245.00 22.00 27,390.00

3,895.00 28.75 111,981.25

each

each

each

each

each

each

each

205.00 221.95

1,242.00 296.35

1,140.00 579.75

72.00 522.85

40.00 378.75

116.00 244.10

57.00 221.95

45,499.75

368,066.70

660,915.00

37,645.20

15,150.00

28,315.60

12,651.15

17.58.1

17.58.2

17.59

17.59.1

17.59.2

17.6

a 100mm b 75mm

15.12

Providing and fixing M.S stays and clamps for sand cast iron /

Centrifugally Cast (Spun) Iron Pipes iron pipes of diameter.

a b

100 mm dia

75 mm dia

15.13

Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete including cost of cutting and making good the walls and floors.

each

each

1,600.00 207.85

590.00 176.50

332,560.00

104,135.00

each

each

2,175.00 61.70 134,197.50

800.00 52.35 41,880.00

17.60.1

a

17.60.1.1

ai

100 mm inlet and 100 mm outlet.

Sand cast iron S&S as per IS:3989

16.00

WATER SUPPLY

each 446.00 801.70 357,558.20

DSR

Item No.

18.8

S.

No.

Description of Items

16.01

Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all

CPVC plain and brass threaded fittings including fixing the pipe with clamps at 1.00 M spacing. This include jointing of pipes & fitting with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in charge.

Concealed work including cutting chases and making good the walls etc.

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

18.8.1

18.8.2

18.8.3

18.8.4

18.7

a 15 mm nominal outer dia pipes b c

20 mm nominal outer dia pipes

25 mm nominal outer dia pipes d 32 mm nominal outer dia pipes

16.02

Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all

CPVC plain and brass threaded fittings including fixing the pipe with clamps at 1.00 M spacing. This include jointing of pipes & fitting with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in charge.

Internal work - Exposed on walls.

metre

metre

metre

metre

3,085.00 219.55

1,905.00 243.95

677,311.75

464,724.75

190.00 298.85 56,781.50

725.00 359.80 260,855.00

18.38.1

18.38.2

18.38.3

18.38.4

18.38.5

18.38.6

18.7.1

18.7.2

18.7.3

18.7.4

18.7.5

18.7.6

18.10

18.10.1

18.10.2

18.10.3

18.10.4

18.10.5

18.10.6

18.38

a b

15 mm nominal outer dia pipes

20 mm nominal outer dia pipes

metre

metre

40.00 133.95 5,358.00

40.00 157.15 6,286.00

c d e

25 mm nominal outer dia pipes

32 mm nominal outer dia pipes

40 mm nominal outer dia pipes

metre

metre

40.00 197.90

40.00 252.65

7,916.00

10,106.00

f 50 mm nominal outer dia pipes

16.03

Providing and fixing of GI pipe complete with GI fiitings and clamps, including cutting and making good the wall as per direction of Engineer in Charge.

Internal Work - Exposed on wall a 15 mm dia nominal bore

metre

metre

45.00 348.25

135.00 514.35

15,671.25

69,437.25

metre 130.00 161.60 21,008.00

b 20 mm dia nominal bore

metre 615.00 188.05 115,650.75

c 25 mm dia nominal bore

metre 630.00 243.15 153,184.50

d 32 mm dia nominal bore

metre 2,270.00 296.50 e 40 mm dia nominal bore

metre f 50 mm dia nominal bore

metre e f c d

16.04

Painting GI Pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work: a b

15 mm diametre pipe

20 mm diametre pipe

metre

25 mm diametre pipe

32 mm diametre pipe

40 mm diametre pipe

50 mm diametre pipe

metre

metre

metre

metre

metre

874.00 364.10

688.00 453.65

130.00 7.35

615.00 8.65

630.00 11.40

1,520.00 13.45

730.00 16.00

330.00 18.80

673,055.00

318,223.40

312,111.20

955.50

5,319.75

7,182.00

20,444.00

11,680.00

6,204.00

18.12.2

18.12.3

18.12.4

18.12.5

18.12.6

18.12.7

18.12.8

18.13

DSR

Item No.

18.53

S.

No.

Description of Items

16.05

Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore.

18.21

18.21.1

16.06

Providing & Fixing uplasticised PVC connection pipe with brass unions: a 30 cm length.

18.21.1.1

ai 15 mm nominal bore.

18.49

18.49.1

18.40

16.07

Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931:

15 mm nominal bore a

16.08

Painting GI pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality.

18.40.4

18.40.5

18.40.6

18.12

18.13.1

18.13.2

18.35

a b

32 mm diameter pipe.

40 mm diameter pipe.

c 50 mm diameter pipe.

16.09

Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. (External work): a d e b c f g

20 mm nominal bore.

25 mm nominal bore.

32 mm nominal bore.

40 mm nominal bore.

50 mm nominal bore.

65 mm nominal bore.

80 mm nominal bore.

16.10

Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : a b

16.11

25 to 40 mm nominal bore.

50 to 80 mm nominal bore.

Constructing masonry Chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and

RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :

Unit

each

each

each

metre

metre

metre

Each

Each

Quantity Rate

(Rs.)

996.00 449.35

Amount

(Rs.)

447,552.60

996.00 51.35 51,144.60

51.00 397.50 20,272.50

750.00 7.80

144.00 8.90

5,850.00

1,281.60

358.00 10.55 3,776.90

metre

metre

metre

metre

metre

metre

metre

1,420.00 161.25

445.00 209.40

65.00 248.55

45.00 294.25

65.00 355.95

228,975.00

93,183.00

16,155.75

13,241.25

23,136.75

45.00 453.55

820.00 573.40

20,409.75

470,188.00

10.00 277.35

20.00 630.15

2,773.50

12,603.00

18.35.1

18.41

18.41.2

18.41.3

18.41.4

18.41.5

18.41.6

18.41.7

18.41.8

18.41.9

18.46

a With common burnt clay F.P.S.(non modular) bricks of class designation 75.

16.12

Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work : a b c d

20 mm nominal bore.

25 mm nominal bore.

32 mm nominal bore,

40 mm nominal bore.

g h e f

50 mm nominal bore.

65 mm nominal bore.

80 mm nominal bore.

100 mm nominal bore.

16.13

Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :

Each 5.00 12,492.70 62,463.50

metre

metre

metre

metre

metre

metre

metre

metre

1,420.00 55.50 78,810.00

445.00 56.95 25,342.75

65.00 58.45 3,799.25

45.00 59.20 2,664.00

65.00 61.40 3,991.00

45.00 96.95 4,362.75

820.00 99.90 81,918.00

1,570.00 105.80 166,106.00

-

19.6.2

19.6.3

19.6.4

19.6.5

19.6.6

19.6.7

19.6.9

19.7

DSR

Item No.

18.46.2

18.46.3

18.46.4

18.46.5

18.46.6

18.46.7

18.46.8

18.60

S.

No.

a b c

Description of Items

20 mm nominal bore.

25 mm nominal bore.

32 mm nominal bore, f g d e

40 mm nominal bore.

50 mm nominal bore.

65 mm nominal bore.

80 mm nominal bore.

16.14

Providing and fixing enclosed type water meter (bulk type) conformingto IS : 2373 and tested by Municipal Board complete with bolts,nuts, rubber insertions etc. (The tail pieces if required will be paid separately) :

18.60.1

18.60.2

19.4

a b

80 mm dia nominal bore.

100 mm dia nominal bore.

17.00

DRAINAGE

17.01

Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight

C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than

2.70 kg as per standard design :

19.4.1

19.4.1.1

19.6

a 100 x 100 mm size P type ai With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.02

Providing and laying non-pressure NP2 class (light duty) R.C.C.

pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :

Unit

Each

Each

Each

Each

Each

Each

Each

Quantity Rate

(Rs.)

Amount

(Rs.)

20.00 142.85 2,857.00

20.00 154.45

30.00 189.30

10.00 229.95

20.00 307.70

20.00 551.60

10.00 656.15

3,089.00

5,679.00

2,299.50

6,154.00

11,032.00

6,561.50

Each

Each

2.00 2,880.60

1.00 4,329.20

5,761.20

4,329.20

Each 30.00 1,258.05 37,741.50

c d a b e

150 mm dia R.C. C. pipe.

250 mm dia R.C. C. pipe.

300 mm dia R.C. C. pipe.

450 mm dia R.C. C. pipe.

500 mm dia R.C. C. pipe.

f g

600 mm dia R.C. C. pipe.

800 mm dia R.C. C. pipe.

17.03

Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement: 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2coarse sand : 4 graded stone aggregate 20 mm nominal size),foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 gradedstone aggregate 40 mm nominal size), inside plastering 12 mm thickwith cement mortar 1:3 (1 cement :

3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mmnominal size) finished with a floating coat of neat cement complete as per standard design :

metre

metre

metre

metre

metre

metre

metre

420.00 254.50

1,205.00 342.45

1,025.00 422.90

400.00 620.85

1,320.00 722.20

106,890.00

412,652.25

433,472.50

248,340.00

953,304.00

340.00 1,084.25 368,645.00

1,250.00 1,415.70 1,769,625.00

19.7.1

a Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :

19.7.1.1

19.7.2

ai With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.04

Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :

Each 35.00 7,061.70 247,159.50

19.7.2.1

19.8

19.8.1

a With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.05

Extra depth for manholes a Size 90x80 cms

Each 45.00 15,223.25 685,046.25

DSR

Item No.

19.8.1.1

19.8.2

19.8.2.1

19.9

S.

No.

ai b

Description of Items

With common burnt clay F.P.S. (non modular) bricks of class designation 75.

Size 120x90 cms bi With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.06

Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete

1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

Unit

metre

Quantity Rate

(Rs.)

25.00 4,061.70

Amount

(Rs.)

101,542.50

metre 13.00 4,866.75 63,267.75

19.9.1

a 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S.

12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand

: 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and

12mm thick cement plaster at the external surface shall be paid for separately) :

19.9.1.1

19.10

19.10.1

19.11

ai With common burnt clay F.P.S. (non modular) bricks of class designation 75

17.07

Extra depth for circular type manhole 0.91m internal dia (at bottom) beyond 0.91m to 1.67m

a With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.08

Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement

:4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement :

2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

Each 80.00 7,033.25

metre 77.00 3,498.25

562,660.00

269,365.25

19.11.1

a 1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S.

12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand :

4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :

19.11.1.1

19.12

19.12.1

19.13

ai With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.09

Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m : a With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.10

Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement

: 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement :

2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

Each

metre

142.00 12,969.25 1,841,633.50

352.00 4,522.30 1,591,849.60

DSR

Item No.

19.13.1

S.

No.

a

Description of Items

2.30 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S.

12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and

12 mm thick cement plaster at the external surface shall be paid for separately) :

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

19.13.1.1

19.14

19.14.1

19.15

ai

17.11

With common burnt clay F.P.S. (non modular) bricks of class designation 75

Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m : a With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.12

Providing M.S. foot rests including fixing in manholes with

20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design :

19.15.1

19.15.2

19.16

a b

With 20x20 mm square bar.

With 20 mm diameter round bar.

17.13

Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS : 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as

165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.

Each

metre

Each

Each

Each

35.00 26,906.05

25.00 10,643.40

3,200.00 258.70

941,711.75

266,085.00

400.00 228.85

2,800.00 194.00

91,540.00

543,200.00

827,840.00

19.27

17.14

Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including

500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design :

19.27.1

19.18

19.18.2

21.1

a With common burnt clay F.P.S. (non modular) bricks of class designation 75.

17.15

Supplying and fixing C.I. cover without frame for manholes : a 500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg.

18.00

ALUMINIUM WORK

18.01

Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required

EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of

Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :

Each 325.00 3,215.00 1,044,875.00

Each 5.00 2,624.65 13,123.25

21.1.1

21.1.1.1

21.1.1.2

a ai aii

For fixed portion

Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC

15.)

Powder coated aluminium (minimum thickness of powder coating

50 micron).

Kg 2,118.09 358.30 758,911.65

Kg 72,955.10 387.60 28,277,396.76

DSR

Item No.

21.1.2

S.

No.

b

Description of Items

For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately).

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

21.1.2.1

21.1.2.2

21.18

bi Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC

15).

bii Powder coated aluminium (minimum thickness of powder coating

50 micron).

18.02

Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately).

Kg

Kg

2,275.68 406.50

91,565.33 436.35

Sqm 155.42 4,430.80

925,063.92

39,954,531.75

688,634.94

21.3

21.3.2

21.3.3

21.4

18.03

Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): a b

With float glass panes of 5.50 mm thickness.

With float glass panes of 8 mm thickness.

18.04

Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg., for doors, including cost of cutting floors ,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-incharge.

Sqm 6,065.63 905.75 5,493,944.37

Sqm 718.39 726.90 522,197.69

21.4.1

21.11

a With stainless steel cover plate minimum 1.25 mm thickness.

18.05

Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineer-in-charge complete.

Each 70.00 1,953.10 136,717.00

21.11.1

21.11.3

21.8

a b

205 X 19 mm.

355 X 19 mm.

18.06

Filling the gap in between aluminium frame & adjacent RCC/

Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete.

Each 219.00 205.40

Each 57.00 284.40

44,982.60

16,210.80

21.8.1

21.9

21.9.1

21.9.2

a Upto 5mm depth and 5 mm width.

18.07

Extra for applying additional anodic coating AC 25 instead of AC

15 to aluminium extruded sections.

metre 10,014.06 75.10 a b

For fixed portion.

For shutters of doors, windows & ventilators.

19.00

WATER PROOFING

Kg

Kg

2,209.86 11.60

2,390.38 11.60

752,055.91

25,634.38

27,728.41

DSR

Item No.

22.7

S.

No.

Description of Items

19.01

Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75

kg/sqm. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto300mm height including cleaning the surface before treatment. b)Laying brick bats with mortar using broken bricks/brick bats 25 mm to115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)admixed with water proofing compound conforming to IS :

2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with waterproofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c)After two days of proper curing applying a second coat of cement slurry using 2.75kg/ sqm of cement admixed with water proofing compound conforming to

IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement mortar of mix1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.

All above operations to be done in order and as directed and specified by the Engineer-in-Charge :

Unit Quantity Rate

(Rs.)

Amount

(Rs.)

22.7.1

24.1

a With average thickness of 120mm and minimum thickness at khurra as 65 mm.

20.00

RAIN WATER HARVESTING & TUBEWELLS

20.01

Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level.

Sqm 7,481.76 786.70 5,885,900.59

24.1.1

24.1.1.1

24.2

a ai

All types of soil

300 mm dia

20.02

Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre

& upto 150 metre depth below ground level.

metre 360.00 358.95 129,222.00

24.2.1

24.2.1.1

24.2.1.3

24.3

a All types of soil ai 300 mm dia aii 400 mm dia

20.03

Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.

metre

metre

240.00 418.75

225.00 628.15

24.3.2

24.3.3

24.4

24.4.2

a b

20.04

Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.

a

150 mm nominal size dia

200 mm nominal size dia

150 mm nominal size dia

metre

metre

metre

600.00 539.20

150.00 975.45

600.00 545.00

100,500.00

141,333.75

323,520.00

146,317.50

327,000.00

DSR

Item No.

24.4.3

24.5

24.6

S.

No.

Description of Items b 200 mm nominal size dia

20.05

Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge.

20.06

Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in equired thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge

Unit

metre

cum

cum

Quantity Rate

(Rs.)

300.00 981.80

Amount

(Rs.)

294,540.00

96.00 459.05 44,068.80

96.00 828.45 79,531.20

24.7

24.8

20.07

Supplying, filling, spreading & leveling coarse sand of size range

1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer

-in-charge.

20.08

Gravel packing in tubewell construction in accordance with IS:

4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge.

cum

cum

96.00 799.40 76,742.40

36.85 842.80 31,057.18

24.9

20.09

Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size

1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineer-in-charge.

each 30.00 897.10 26,913.00

24.10

20.10

Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/ plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge.

24.10.3

24.11

a 200 mm nominal size dia having minimum wall thickness 5.40

mm

20.11

Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted

(having slot of size 1.6/3.2 mm) mild steel threaded and socketed

/ plain bevel ended pipe (type A) of required dia, conforming to

IS:8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of

Engineer -in-charge.

metre 150.00 1,555.10

24.11.3

24.12

a 200 mm nominal size dia

20.12

Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge.

metre

hour

150.00 1,625.30

240.00 549.10

233,265.00

243,795.00

131,784.00

24.13

24.13.2

24.13.3

24.14

20.13

Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: a b

150 mm dia

200 mm dia

20.14

Providing and fixing M.S. clamp of required dia to the top of casing/housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete

Each

Each

4.00 182.95 731.80

15.00 219.50 3,292.50

DSR

Item No.

24.14.2

24.14.3

24.15

S.

No.

a b

150 mm clamp

200 mm clamp

Description of Items

20.15

Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I).

Unit

Each

Each

Quantity Rate

(Rs.)

Amount

(Rs.)

4.00 1,033.10

15.00 1,173.25

4,132.40

17,598.75

24.15.2

24.15.3

a b

150 mm dia

200 mm dia

Total Cost of DSR item(Civil) of Schedule-A

Each

Each

4.00 206.10 824.40

15.00 240.95 3,614.25

868052208.67

Name of the work :Construction and Development of Agri-Food Cluster Campus of National Agri Food Biotechnology Institute(NABI) at

Mohali(Punjab).

DSR SCHEDULE ITEMS (ELECTRICAL) SCHEDULE-C

DSR Item

No.

Sr.No.

1.10

1.10.1

1.10.2

1.11

1.18

1.18.2

1.18.3

1.14

1.14.1

1.14.2

1.14.3

1.14.4

1.14.9

1.14.10

1.19

1.21

1.21.1

1.21.2

1.21.3

1.24

1

3 a b a b c d e f a b c a b

2

4

5

6

7

Description of Items

Sub Head (A): ELECTRICAL WORKS

CIRCUIT CUM POINT WIRING

Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR

PVC insulated copper conductor single core cable in surface / recessed medium class

PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.

Group A

Group B

Wiring for twin control light point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.

Supplying and drawing following pair 0.5 sq mm FR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.

2 Pair

4 Pair

Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR

PVC insulated copper conductor, single core cable in surface/ recessed medium class

PVC conduit as required

2 x 1.5 Sq.mm. + 1 x 1.5 Sq.mm. earth wire

2 x 2.5 Sq.mm. + 1 x 2.5 Sq.mm. earth wire

2 x 4 Sq.mm. + 1 x 4 Sq.mm. earth wire

2 x 6 Sq.mm. + 1 x 6 Sq.mm. earth wire

4 x 6 Sq.mm. + 2 x 6 Sq.mm. earth wire

4 x 10 Sq.mm. + 2 x 10 Sq.mm. earth wire

Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor

PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.

Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.

20 mm

25 mm

32 mm

Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.

Unit

Point 1,682.00 462.00

Point 4,855.00 544.00

777,084.00

2,641,120.00

Point 135.00 710.00 95,850.00

metre metre metre metre metre metre metre metre metre metre metre metre

Quantity Rates (Rs.) Amount (Rs.)

27,999.00 15.50

664.00 24.00

433,984.50

15,936.00

200.00 107.00

5,278.00 131.00

250.00 162.00

3,951.00 206.00

6,941.00 358.00

150.00 562.00

21,400.00

691,418.00

40,500.00

813,906.00

2,484,878.00

84,300.00

11,378.00 22.00 250,316.00

13,151.00 56.50

22,441.00 64.50

700.00 80.50

743,031.50

1,447,444.50

56,350.00

1.24.6

a Telephone Socket Outlet Each 985.00 89.00 87,665.00

DSR Item

No.

1.24.7

Sr.No.

b TV Antenna Socket Outlet

Description of Items Unit Quantity Rates (Rs.) Amount (Rs.)

Each 325.00 93.00 30,225.00

DSR Item

No.

Sr.No.

1.25

8

1.26

1.27

1.27.1

1.27.2

1.27.3

1.27.4

1.27.5

1.27.6

1.31

1.32

1.33

1.38

1.41

1.45

1.50

1.50.1

1.51

2.7

9

10 d e f a b c

11

12

13

14

15

16

17 a

18

19

Description of Items Unit Quantity Rates (Rs.) Amount (Rs.)

Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.

Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.

Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.

1 or 2 Module (75 mm x 75 mm)

3 Module (100 mm x 75 mm)

4 Module (125 mm x 75 mm)

6 Module (200 mm x 75 mm)

8 Module (125 mm x 125 mm)

12 Module (200 mm x 150 mm)

Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).

Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.

Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.

Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.

Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required.

Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.

Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.

Upto 450 mm Sweep

Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.

DISTRIBUTION BOARD, MCCB,MCB&RCCB

Supplying and fixing following way prewired SP&N MCB distribution board of steel sheet for 240 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required. (But without

MCB/ RCCB/ Isolator)

Each 339.00 322.00 109,158.00

Each 321.00 22.00 7,062.00

Each 2,474.00 142.00

Each 958.00 154.00

Each 137.00 173.00

Each 1,686.00 221.00

Each 198.00 255.00

Each 18.00 344.00

351,308.00

147,532.00

23,701.00

372,606.00

50,490.00

6,192.00

Each 3,182.00 288.00 916,416.00

Each 1,241.00 366.00 454,206.00

Each 329.00 34.00 11,186.00

Each 156.00 54.50 8,502.00

Each 4,403.00 69.50 306,008.50

Each 339.00 99.00 33,561.00

Each 206.00 163.00 33,578.00

Each 206.00 68.50 14,111.00

DSR Item

No.

2.7.4

2.7.5

2.7.6

Sr.No.

a b c

2.8

2.8.6

2.8.7

2.8.8

2.9

2.9.5

2.9.6

2.9.7

2.9.8

2.10

2.10.1

2.10.4

2.11

2.14

2.14.1

2.14.2

2.15

2.15.1

2.15.2

2.15.3

20 a b

23 a b c d a b c a b c

21

22

24 a b

25

Description of Items

2 + 4 Way, Double Door

2 + 8 Way, Double Door

2 + 12 Way, Double Door

Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/

RCCB/ Isolator)

6 Way (4 + 18), Double Door

8 Way (4 + 24), Double Door

12 Way (4 + 36), Double Door

Supplying and fixing following way prewired vertical type TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, terminal connectors for all incoming and outgoing circuits, duly prewired with adequate size of FR PVC insulated copper conductor upto the terminal connector/ neutral link, earthing etc as required (But without MCB/ RCCB/ Isolator). (Note : Prewired vertical type MCB TPDB is normally used where 3 phase outlets are required.)

4 Way Double Door

6 Way Double Door

8 Way Double Door

12 Way Double Door

Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.

Single Pole

Triple Pole

Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.

Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.

25 Amps

40 Amps

Three Phase Residual Current Circuit Breaker

Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.

25 Amps

40 Amps

63 Amps

Unit Quantity Rates (Rs.) Amount (Rs.)

Each 109.00 2,152.00

Each 22.00 2,572.00

Each 7.00 3,108.00

234,568.00

56,584.00

21,756.00

Each 31.00 8,197.00

Each 26.00 8,984.00

Each 57.00 11,042.00

254,107.00

233,584.00

629,394.00

Each 12.00 6,816.00

Each 7.00 8,810.00

Each 6.00 9,606.00

Each 1.00 12,762.00

81,792.00

61,670.00

57,636.00

12,762.00

Each 4,010.00 141.00

Each 59.00 562.00

Each 516.00 5.50

565,410.00

33,158.00

2,838.00

Each 130.00 1,318.00

Each 180.00 1,394.00

171,340.00

250,920.00

Each 10.00 1,679.00

Each 75.00 1,703.00

Each 41.00 1,965.00

16,790.00

127,725.00

80,565.00

DSR Item

No.

Sr.No.

2.18

2.19

26

27

Description of Items

SPN Industrial Type Socket Outlet

Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.

Supplying and fixing 20 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required

2.20

28

Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required

Unit Quantity Rates (Rs.) Amount (Rs.)

Each 359.00 693.00 248,787.00

Each

Each

100.00 1,718.00 171,800.00

20.00 1,983.00 39,660.00

DSR Item

No.

Sr.No.

4.1

4.1.1

4.1.2

4.1.4

4.1.7

4.1.15

5.4

5.6

5.8

5.9

5.10

5.11

5.14

5.15

5.18

5.17

6.1

29 a b c d e

30

31

32

33

34

35

36

37

38

39

40

Description of Items

CABLE TRAYS AND ACESSORIES:

Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.

100 mm width X 50 mm depth X 1.6 mm thickness

150 mm width X 50 mm depth X 1.6 mm thickness

300 mm Width x 50 mm Depth x 1.6 mm Thickness

600 mm Width x 50 mm Depth x 1.6 mm Thickness

750 mm width X 75 mm depth X 2.0 mm thickness

EARTHING INSTALLATION

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt

& spring washer spaced at 50mm)

Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and refilling etc. as required.

Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and refilling etc. as required.

Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.

Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.

Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable s required.

Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.

LIGHTNING CONDUCTOR

Providing and fixing of lightning conductor finial, made of 25 mm dia 300mm long, copper tube, having single prong at top, with 85 mm dia 3mm thick copper base plate including holes etc. complete as required.

Unit metre metre metre metre metre

Each

Each metre metre metre metre metre metre metre metre

Quantity Rates (Rs.) Amount (Rs.)

100.00 405.00

404.00 464.00

255.00 677.00

65.00 1,210.00

325.00 1,507.00

40,500.00

187,456.00

172,635.00

78,650.00

489,775.00

24.00 3,996.00

95,904.00

6.00 8,559.00

51,354.00

500.00 680.00

340,000.00

970.00 97.50 94,575.00

60.00 962.00 57,720.00

240.00 364.00 87,360.00

300.00 766.00 229,800.00

530.00 120.00 63,600.00

4,478.00 19.50 87,321.00

300.00 87.50 26,250.00

Each 22.00 701.00 15,422.00

DSR Item

No.

Sr.No.

6.4

41

6.7

6.8

6.12

6.14

42

43

44

45

Description of Items Unit Quantity Rates (Rs.) Amount (Rs.)

Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.

Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)

Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)

Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.

Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.

Each metre metre

Each metre

10.00 60.50

1,445.00 58.00

1,020.00 81.50

20.00 58.50

700.00 125.00

605.00

83,810.00

83,130.00

1,170.00

87,500.00

DSR Item

No.

Sr.No.

5.4

7.8

7.8.1

7.8.2

7.8.3

7.8.4

9.1

9.1.21

9.1.22

9.1.23

9.1.24

9.1.25

9.1.26

9.1.27

9.1.30

9.1.32

9.1.33

9.1.34

7.1

7.1.1

7.1.2

7.1.3

7.1.4

7.2

7.2.1

7.2.2

7.2.3

7.2.4

7.5

46

48 d e f a b c j i g h k

49 a b c d

47 a b c d

50 a b c d

51

Description of Items Unit Quantity Rates (Rs.) Amount (Rs.)

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

CABLES, MAINS AND SUB MAINS

Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

Upto 35 Sq.mm (Clamped with 1 mm thick saddle)

Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp).

Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

3½ X 35 sq. mm (32mm)

3½ X 50 sq. mm (35mm)

3½ X 70 sq. mm (38mm)

3½ X 95 sq. mm (45mm)

3½ X 120 sq. mm (45mm)

3½ X 150 sq. mm (50mm)

3½ X 185 sq. mm (57mm)

3½ X 300 sq. mm (70mm)

4 X 10 sq. mm (25mm)

4 X 16 sq. mm (28mm)

4 X 25 sq. mm (28mm)

TOTAL OF SUB HEAD (A)

SUB HEAD(B): ELECTRICAL HIGH END EQUIPMENTS & DG SETS (UTILITY-1&2)

HT & LT Cables

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

Upto 35 sq. mm

Above 35 sq. mm and upto 95 sq. mm

Above 95 sq. mm and upto 185 sq. mm

Above 185 sq. mm and upto 400 sq. mm

Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.

Upto 35 sq. mm

Above 35 sq. mm and upto 95 sq. mm

Above 95 sq. mm and upto 185 sq. mm

Above 185 sq. mm and upto 400 sq. mm

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

Set 34.00 3,996.00 135,864.00

metre metre metre

5,590.00 16.50

880.00 38.50

710.00 47.50

92,235.00

33,880.00

33,725.00

metre 22.00 72.50 1,595.00

each each each each each each each each each each each metre metre metre metre metre metre metre metre

38.00 223.00

6.00 262.00

32.00 297.00

14.00 366.00

10.00 383.00

18.00 458.00

16.00 616.00

2.00 867.00

120.00 146.00

4.00 188.00

24.00 192.00

397.50

72.60

189.00 179.00

895.80 196.00

662.50

121.00

167.00

173.00

115.00

121.00

315.00 127.00

1,493.00 144.00

8,474.00

1,572.00

9,504.00

5,124.00

3,830.00

8,244.00

9,856.00

1,734.00

17,520.00

752.00

4,608.00

19,656,926.00

66,382.50

12,559.80

33,831.00

175,576.80

76,187.50

14,641.00

40,005.00

214,992.00

DSR Item

No.

7.5.1

7.5.2

7.5.3

7.5.4

7.8

7.8.1

7.8.2

Sr.No.

a b c d

52 a b

7.8.3

7.8.4

7.10

10.4

10.4.4

9.1

9.1.23

9.1.26

9.1.29

9.1.30

9.1.31

9.1.21

9.1.34

4.1

4.1.2

4.1.4

4.1.15

2932

2933 c d

53

54 a

55 e f c d g a b

56 a b c

57

58

Description of Items

Upto 35 sq. mm

Above 35 sq. mm and upto 95 sq. mm

Above 95 sq. mm and upto 185 sq. mm

Above 185 sq. mm and upto 400 sq. mm

Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

Upto 35 sq. mm (clamped with 1mm thick saddle)

Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm

MS flat clamp)

Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.

H.T POWER CABLE END TERMINATION

Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories includind lugs suitable for following size of 3 core XLPE aluminium conductor cable of 11 kV grade asquired.

300 sq. mm

L.T POWER CABLE END TERMINATION

Cable end temetreination of the following PVC insulated sheathed PVC/XLPE aluminium

/ copper conductor ametreoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc. complete as required.

3.5 core 70 sq.mm

3.5 core 150 sq.mm

3.5 core 240 sq. mm

3.5 core 300 sq.mm

3.5 core 400 sq.mm

3.5 core 35 sq. mm

4 core 25 sq. mm

CABLE TRAYS AND ACESSORIES:

Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.

150 mm width X 50 mm depth X 1.6 mm thickness

300 mm Width x 50 mm Depth x 1.6 mm Thickness

750 mm width X 75 mm depth X 2.0 mm thickness

BATTERY & BATTERY CHARGER

Providing & fixing HT danger notice plate of 250 mm x 200mm, made of mild steel sheet of minimum 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.

Supply & fixing MV danger notice plate of 200 mm x 150mm, made of mild steel sheet of minimum 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required.

SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF EXTERNAL

LIGHTING FIXTURES.

Unit metre metre metre metre metre metre

132.50

24.20

16.50

38.50

2,186.25

931.70

metre 63.00 47.50 metre 289.60 72.50

2,992.50

20,996.00

Each

Each each each each each each each each metre metre metre

Each

Each

Quantity Rates (Rs.)

132.50

24.20

12.00

18.50

63.00 25.00

298.60 44.00

1,590.00

447.70

1,575.00

13,138.40

20.00 244.00

Amount (Rs.)

16.00 6,881.00 110,096.00

4.00

12.00

16.00

34.00

8.00

2.00

20.00

297.00

458.00

771.00

867.00

1,109.00

223.00

192.00

1,188.00

5,496.00

12,336.00

29,478.00

8,872.00

446.00

3,840.00

150.00

400.00

500.00

464.00

677.00

1,507.00

69,600.00

270,800.00

753,500.00

8.00

6.00

47.25

36.75

4,880.00

378.00

220.50

DSR Item

No.

Sr.No.

1.14

1.14.1

1.14.2

1.14.3

7.1

7.1.1

7.2

7.2.1

5.4

5.6

1.17

1.17.2

1.20

1.20.1

1.20.2

1.20.3

64 a

65 a b c

59 a b c

60 a

61 a

62

63

Description of Items

Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR

PVC insulated copper conductor, single core cable in surface/ recessed medium class

PVC conduit as required

2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire

2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire

2 X 4 sq. mm + 1 X 4 sq. mm earth wire

Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

Upto 35 sq. mm

Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.

Upto 35 sq. mm

EARTHING INSTALLATION (SUB STATION)

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

TOTAL OF SUB HEAD (B)

Sub- Head (C): FIRE FIGHTING SYSTEM

Supply and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel conduit as required.

2X1.5 sqmm

Supply and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface , or cutting the wall and making good the same in case of recessed conduit ar required.

20mm dia

25mm dia

32mm dia

TOTAL OF SUB HEAD(C)

Total Cost of DSR items(Electrical) of Schedule-C

Unit meter meter meter metre metre

Set

Set metre metre metre metre

Quantity Rates (Rs.) Amount (Rs.)

350.00

300.00

100.00

107.00

131.00

162.00

37,450.00

39,300.00

16,200.00

120.00 167.00

20,040.00

680.00 115.00

78,200.00

24.00 3,996.00

95,904.00

18.00 8,559.00

154,062.00

7,000.00

2,390,319.65

33.50

234,500.00

2,000.00

4,000.00

200.00

123.00

143.00

195.00

246,000.00

572,000.00

39,000.00

1,091,500.00

23,138,745.65

DSR Item

No.

Sr.No.

5.18

7.8

7.8.1

7.8.2

7.8.4

9

9.1.33

9.1.34

9.2.19

9.2.20

9.2.26

4.1

4.1.7

4.1.4

4.1.2

5.18

1

3 a b c d e

2 a b c

4 a b c

5

Description of Items

DSR SCHEDULE ITEMS (HVAC WORK) SCHEDULE-E

SUB HEAD (A): -LABORATORY

Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.

Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

RM

Upto 35 Sq.mm (Clamped with 1 mm thick saddle)

Above 35 Sq.mm & Upto 95 Sq.mm (Clamped with 25 X 3mm MS Flat Clamp)

Above 185 Sq.mm & Upto 400 Sq.mm (Clamped with 40 X 3mm MS Flat Clamp)

RM

RM

RM

END TERMINATION OF CABLES

Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

4 Core 16 Sq.mm. (Copper armoured Cable)

4 Core 25 Sq.mm. (Aluminium armoured Cable)

3.5 Core 50 Sq.mm. (Aluminium armoured Cable)

3.5 Core 70 Sq.mm. (Aluminium armoured Cable)

3.5 Core 240 Sq.mm. (Aluminium armoured Cable)

CABLE TRAY & ACCESSORIES

Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.

No.

No.

No.

No.

No.

600 mm Width x 50 mm Depth x 2 mm Thickness

300 mm Width x 50 mm Depth x 1.6 mm Thickness

150 mm Width x 50 mm Depth x 1.6 mm Thickness

TOTAL OF SUB HEAD(A)

Sub- Head (B): ANIMAL HOUSE

Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.

RM

RM

RM

RM

Unit Quantity Rates (Rs.) Amount (Rs.)

500.00 19.50 9,750.00

986.00 16.50 16,269.00

60.00 38.50 2,310.00

35.00 72.50 2,537.50

28.00 188.00 5,264.00

2.00 192.00 384.00

4.00 601.00 2,404.00

6.00 664.00 3,984.00

20.00 1,137.00 22,740.00

50.00 1,210.00 60,500.00

120.00 677.00 81,240.00

810.00 464.00 375,840.00

583,222.50

200.00 19.50 3,900.00

7.8

7.8.1

4.1

4.1.1

7 a

6 a

Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

Upto 35 Sq.mm (Clamped with 1 mm thick saddle)

CABLE TRAY & ACCESSORIES

Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.

RM

150 mm Width x 50 mm Depth x 1.6 mm Thickness RM

TOTAL OF SUB HEAD (B)

Total cost of DSR Items-HVAC WORK of Schedule-E

150.00 16.50 2,475.00

100.00 464.00 46,400.00

52,775.00

635,997.50

Name of work: Construction and Development of Agri- Food Cluster Campus of National Agri Food

Biotechnology Institute ( NABI) at Mohali ( Punjab)

NON SCHEDULE ITEMS ( CIVIL) SCHEDULE-B

S.

No.

1

Description of Item

EARTH WORK

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5 m in width as well as

10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift from 1.5m to 3m, disposed earth to be levelled and neatly dressed.

Unit Quantity Rate in

Fig.( Rs.) a

2 a

4 a

3

All kinds of soil.

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5 m in width as well as

10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift from 3m to 4.5m, disposed earth to be levelled and neatly dressed.

Cum 9812.51

All kinds of soil.

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5 m in width as well as

10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift from 4.5m to 6m, disposed earth to be levelled and neatly dressed.

Cum 3533.65

All kinds of soil.

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5 m in width as well as

10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift from 6m to 7.5m, disposed earth to be levelled and neatly dressed.

Cum 2685.93

a

6 a

5

7

8

All kinds of soil.

Earth work in excavation by mechanical means

(Hydraulic excavator) / manual means over areas

(exceeding 30cm in depth. 1.5 m in width as well as

10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift from 7.5m to 9m, disposed earth to be levelled and neatly dressed.

All kinds of soil.

Diluting and injecting chemical emulsion for PRE-

CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) at plinth and foundation level treatment of soil using chemical emulsion @ 5 litres/ sqm of the horizontal surface of the substructure with Chlorpyriphos/ Lindane E.C.

20% with 1% concentration. Only Plan area shall be measured and paid.

Cum 2685.93

Cum 2327.81

Sqm 16091.89

Laying, spreading and compacting stone aggregate of specified sizes of 90 to 45mm & 63 to 45mm in uniform thickness, hand picking, rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity in stages to proper grade of coarse aggregate and compacting.

REINFORCED CEMENT CONCRETE WORK

Charges for making holes in RCC walls, slabs or any other RCC member by core cutting machine of Hilti /

Fischer/ Mungo including disposing the debris.

Measurement will be taken for the depth of holes in running meter for specified diameter. For disposal of the debris specification of relevant items shall be followed. For all floors/ all heights.

Cum 8341.16

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

a d

9 b c

Description of Item Unit

upto 100mm dia

From 101 to 200mm dia

From 200 to 300mm dia.

metre metre

From 301 to 450mm dia.

Providing and laying in position PVC sleeves of 6kg/ cm2 UPVC pipes of approved make of different diameters for taking out service pipelines, cables etc.

as per required beam/wall thickness for all floors / all levels / all heights. metre metre

Quantity

91.00

119.00

61.00

53.00

Rate in

Fig.( Rs.) a b c

50mm Diameter.

75mm Diameter .

110mm Diameter.

d e

160mm Diameter.

225mm Diameter.

10 Deduct for using of PPC cement in any work instead of OPC cement.

BRICK WORK

11 Providing and fixing hexagonal chickenmesh of size

20mm x 20mm of 22 gauge at junction of concrete and brick work or between different materials etc. as directed by Engineer-in- Charge.

each each

71.00

each 120.00

each 172.00

each 141.00

83.00

Tonne 30315.55

Sqm 3050.11

FLOORING

12 Formation of roughened strip 2.5 cm wide to form antiskid surface on floors & steps as per design including forming straight deep curved gishi (groove)

6 mm wide & 4 mm deep on two sides of the roughened area, chiseling, polishing the edges, sides and bottom of gishis etc. complete as per sample approved by Engineer-in- Charge..

metre 3175.15

13 Providing & laying sandwich platform comprising of a)

Sandwich of 18 mm thick single side polish Granite of approved size, shade and sample on top and 25 mm thick polished kota in bottom with 25mm thick Cement mortar 1:4 (1 cement : 4 Coarse sand) in between b)

At centre vertical sandwich supports of 25 mm thick two kota stone on sides and 10mm thick Cement mortar 1:4 (1 cement : 4 Coarse sand) in between with finished groove and at both end walls vertical supports of 18 mm thick double side granite. c) 75 mm raised platform at bottom with kota on top and

75mm Cement mortar 1:4 (1 cement : 4 Coarse sand) at bottom, kota stone skirting as per design and approved sample.

The rate includes rounding, champhering and mirror polishing of edges, facias of granite and bonding with necessary bonding adhesive

. Rate shall be also inclusive of making holes & cutouts for SS sink, Oval wash basin, Piller tap / Bib tap etc.

as directed by Engineer- in-Charge. (Only plan area shall be measured & paid for and exclusive of MS works).

Sqm 104.8

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

14 Providing & laying water trough of 75 mm thick sandwich granite of any size, shade and sample at outside skirts supported on 18mm thick granite rested on 40mm thick kota stone at bottom with skirting/ dado of 18mm thick granite on wall including average

35mm Cement mortar 1:6 (1 cement : 6 Coarse sand) in between sandwich and wall fixing with cement mortar 1:2 (1cement:2coarse sand) of 18mm thick granite as per design and approved sample for all floors / all levels / all heights. The rate shall be inclusive of rounding, champhering and mirror polishing of edges, facias of granite, making holes & cutouts for sink, ovel wash basin, piller tap, bib tapcouplin etc. including necessary bonding adhesive as per approved make. (Only plan area shall be measured and paid for).

Unit

Sqm

15 Providing & laying china mosaic flooring for plain and curved surfaces at floor, dado, otta etc. comprising of

20 to 25 mm size broken pieces of ceramic/ glazed tiles laid over cement mortor 1:6 (1cement:6 coarse sand) bedding including applying cement slurry at the rate of 2.75 kg per sqm on plain or sloped surfaces and filling joints with white cement. The flooring/ dado shall be tampered with wooden rammer not exceeding

2 Kg in weight to bring the mortar up to the surface including rounding of the junctions and extending them upto 15 cm along the parapet wall. The rate shall include any type of bands, vata, any colour i/c curing, cleaning with water and oxalic acid etc.

complete as sample approved by Engineer-in-Charge.

(Only plan area shall be measured including vata upto

150mm height).

16 Providing & laying average 25 mm thick machined cut green rough kota of approved quality, selected and sorted for uniform color & texture in floor, otta, sill, skirting, tread, riser etc., in required sizes upto 600 mm as per design normal pattern (straight or staggered joint with square or rectangular shaped stone) and drawings (with grooves of 10mm wide or without grooves). Kota stone is to be laid over cement mortar 1:6 (1 cement:6 coarse sand) bedding of average 40mm thickness with joints, pointing and finishing and filling the grooves with cement mortar

1:2 ( 1cement:2 coarse sand) as sample approved including curing and cleaning with wire brush to remove excess cement on the sides of stone upto the satisfaction of the Engineer-in- Charge complete.

Sqm

Sqm

17 Providing, fixing and laying PVC (Poly Vinyl Chloride) flexible and conductive single layer homogeneous antistatic flooring roll/ tile/ plank approved shade, pattern as per design with veined surface pattern and non directional chip texture as per EN649, protect surface treatment of approved color & shade of wearing resistance 0.15mm as per EN 660.1 and EN-

649 and sample approved by Engineer-in-Charge. The sheet would have of thickness of average 2 mm, width of 1.5 m to 2 m & length between 15 m to 25 m & newly improved Continious Graphite Backing for better flow of charges till the earthling points. Thermal

Welding: The joints must be welded by the heat fusion process to get a seamless floor. The joints in the flooring should be sealed by using a PVC welding bar of matching colour to be supplied by the manufacturer, using a hot air gun for fusion of welding bar with flooring. The sheet should have residual indentation of 0.06mm as per EN 433, the color fastness > 6 as per ISO105-B02, vertical resistance <

1X106 Ohm as per EN1081

Quantity

63.00

6985.78

1377.40

Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item and the static electric charge < 2 kV as per EN1815.

The product should also confirm to class Bfl - s1 inflammability test as per EN 13501-1, slip resistance of R10 as per BGR 181, dynamic coefficient of friction with class DS as per EN13893. The wear group of sheet is P as per EN 649. The application should also include coving, capping & welding wherever required.

Adhesive shall be used as per manufacturer’s specification .Flooring rolls/ sheets are to be fusion welded of matching color and should not appear visually. The rate includes making seamless joints, cleaning the flooring, welding rods, coving, wall capping as per manufacturer specification, taking precautionary measures till handing over to client etc.

complete as directed by Engineer-in-Charge .

Unit Quantity

Sqm 587.66

18 Providing & laying at least 3 mm thick self leveling compound to achieve 0-0 leveled surface for vinyle as per manufacturer specification which is suitable to PVC flooring in all manner. Adhesive to be used as per manufacturers recommendation.

FINISHING

19 Providing and applying 1 coat of primer and 2 coat of anti-fungal, anti-bacterial and anti-microbal paint for interior use of any color , at any height/ any floor/ any level which is not only water proof and washable but also covers hairline cracks and provides protection against bacteria that promotes better hygiene and health for interior walls and ceilings as per manufacturer's specifications and as directed by

Engineer-in-Charge.

20 Providing and fixing of 12mm thick Cement Bonded

Particle Board over MS/SS member Structure to form a parapet/ Railing including providing, cutting boards, fixing boards to MS/SS Structure with SDST countersunk screws or company manufactured screws with spacing not more than 20cms, finishing of joints and both side painting of boards with external "Apex" paint with miniumum three coats etc. complete

(Board area shall be measured for payment.MS/SS members shall be paid separetly).

Sqm 729.56

Sqm 1023.16

Rate in

Fig.( Rs.)

Sqm 994.26

ALUMINIUM WORK

21 Extraover on each section bending charges for any diameter of circular window as suggested and directed by Engineer -in-Charge.

22 Extra Charges for providing frosted glass.

23 Extra Charges for providing toughened glass.

24 Providing and fixing 6mm thick Wired Glass with 1 mm thick Stainless steel ( SS304 grade) wire @ every 1 cm horizontal & vertical of any size, any shape in frame and shutter work with necessary cutting of glass including providing and fixing with EPDM quality rubber/ silicon sealant/ structural sealant /3M tape on the periphery of the glass as per the required thickness etc. complete at all floors/ all levels/ all heights as per the directions of Engineer-in-Charge.

Actual installed quantity shall be measured and paid. each

Sqm

Sqm

46.00

2304.82

3908.61

 

Sqm 6138.47

25 Providing and fixing 6mm thick Compact Sheet of any size, any shape, any color for providing in aluminium frame and shutter work with necessary cutting of sheet, single side, double side coloured including providing and fixing EPDM quality rubber/ silicon sealant/ 3M tape/ screwing on the periphery of the sheet as per the required thickness etc. complete at all floors/ all levels/ all heights as directed by

Engineer- in- Charge . Cut edges of the compact sheet shall be provided with masking tape. Actual installed quantity shall be measured and paid.

Sqm 6382.55

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

26 Extra charges for machined Perforation in compact sheet ( The area of sheet on which perforations made shall be measured.Perforations shall be of area size 1 sqcm to 5 sqcm)

Unit Quantity Rate in

Fig.( Rs.)

Sqm 611.53

27 Providing & fixing 2mmx2mm x18 gauge Stainless steel (SS304 grade) wire mesh with screw & fixing assembly in aluminium section for doors, windows, ventilators, partition, cabinets as approved by

Engineer - in- Charge.

28 Providing and fixing Stainless Steel ( SS 304 grade)

Mosquito Net of 1.5mm x 1.5mmx 27 Gauge of any size, any shape, any color in Aluminium frame / shutter work as directed by Engineer -in - Charge.

Sqm 273.68

Sqm 1400.11

29 Providing and fixing of 30micron anodised aluminium fixed horizontal louvers as per manufacturer's specifications and their established system ( of unit wt. 0.514 Kg/m @ 8cm centre to centre)of any size , any colour,any pattern, i/c required accessories and fixtures complete as approved by Engineer-in-Charge.

Work to be done by specilized agency mentioned in list of approved makes.

Sqm 2855.42

30 Providing and fixing of 30micron anodised aluminium adjustable openable louvers as per manufacturer's specifications and thier established system( of unit wt.

0.80Kg/m @ 6cm centre to centre) of any size,any colour, any pattern i/c required accessories and fixtures complete as approved by Engineer-in-

Charge.Work to be done by specilized agency mentioned in list of approved makes.

Sqm 389.45

31 Providing & fixing heavy duty "Europrofile Mortise

Deadlock" (12.6cm 1CK brass) with minimum 6 keys in door/ window with necessary screws complete as approved by Engineer-in-Charge.

32 Providing & fixing Stainless steel ( SS 304 grade)

Baby latch "Door Bolt" size of 3.5" with indicator hair line finish in door/ window with necessary s.s. screws complete as approved by Engineer -in-Charge.

each 885.00

each 395.80

33 Providing and fixing "Sliding lock with auto locking " for sliding door/ window with necessary s.s. screws complete as approved by Engineer -in-Charge.

34 Providing & fixing heavy quality Stainless steel AISI

316 grade "Butt Hinge with 4 Bearing" of 102 X 76 X

3mm of brush/ satin finish with necessary s.s. screws complete as approved by Engineer-in-Charge.

each 846.00

each 3115.00

35 Providing & fixing heavy quality Stainless steel AISI

316 grade Butt Hinge without Bearing of brush/ satin finish with necessary s.s.screws

approved by Engineer-in-Charge. complete as

36 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body

/ plate with double spring mechanism and capable of taking door weight from 126 to 180 Kg (extra heavy duty ) for doors, including cost of cutting floors

,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. each 213.00

each 50.00

37 Providing & fixing Stainless steel (SS 304 grade) of brush/ satin finish specified size Tower Bolt in door/ window with necessary screws complete as approved by Engineer -in-Charge.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

a

Description of Item

18" x 10mm (square)

38 b 4" x 10mm (square)

Providing & fixing Stainless steel AISI 316 grade glossy/ satin finish specified size Push-Pull Handle in pairs in door/ window with necessary screws complete as approved by Engineer -in-Charge.

Unit Quantity each 1361.00

each 505.00

a 32mm (diameter) x 2400mm

Pair 19.00

b c

22mm (diameter) x 300mm

19mm (diameter) x 250mm

Pair

Pair

387.00

206.00

d 19mm (diameter) x 150mm

Pair 703.00

39 Providing and fixing Satin nickle finish BRASS ALDROP of size 100MM X 45MM with 25mm x 45mm counter with necessary screws complete as approved by

Engineer -in-Charge.

each 1095.00

40 Providing & fixing 3" PVC Nylon Buffer in door/ window with necessary screws complete as approved by Engineer -in-Charge.

each 1404.00

41 Providing & fixing Stainless steel (SS 304 grade)

1"series of Ball Bearing for sliding door/ window with necessary screws complete as approved by Engineer in-Charge.

each 2021.00

42 Providing & fixing Stainless steel AISI 316 grade glossy/ satin finish of specified size 10mm X 128mm

(C/R-type) Handles in door/ window/ cabinet with necessary screws complete as approved by Engineer in-Charge.

each 310.00

43 Providing & fixing Stainless steel AISI 316 grade glossy/ satin finish of specified size 10mm X 96mm

(C/R-type) Handles in door/ window/ cabinet with necessary screws complete as approved by Engineer in-Charge.

each 182.00

44 Providing & fixing Stainless steel (SS 304 grade )

Medium Magnetic Catcher for door/ window/ cabinet with necessary screws complete as approved by

Engineer -in-Charge.

each 903.00

45 Providing & fixing Stainless Steel (SS304 grade )

10”x14mm rectangle type Aldrop with necessary screws complete as approved by Engineer -in-

Charge.

Pair 1171.00

46 Automatic sliding Door:-

Providing , fixing and commissioning Double Leaf

Sliding door of approved make in curved/ plain opening with glass partition of size 6350 mm (W) *

3450 mm (H) made from 6mm clear glass encased in heavy duty aluminium section duly powder coated (

50 micron)consisting of 2 sliding glass leaves( 10mm toughened glass) of size 1500mm (W) * 2400mm (H) each as specified by manufacturer with fitting accessories, electromechanical lock with manual release device, digital programmer switch, back up battery etc complete all with Double leaf sliding door operator, with built ‐ in photocells and a pair of microwave radar complete.

each 1.00

Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

47

Description of Item

Providing, fixing & designing of Curtain Wall with DGU system at all levels/ all heights/ all floors through designing and selection of aluminum profiles (

Aluminium sections will be for outer frame

131.16mm*38.5mm*2.00 mm thick, mullion will be

131.16 mm*67*2.00 mm thick and transim will be

81.16mm*67mm *2.00mm

thick) by minimum anodizing of 50 microns of approved color/ standard with necessary corrosion resistance accessories/ fittings, specially extruded EPDM gaskets, specially selected fittings for their fixing on the structure depending on the structural conditions, functional and statistical load requirements. System should provide proper rebate areas for air pressure compensation and water drainage at the required stages. Selection of glazing to be made as per structural stability, panel size, wind load before execution. Transom fixing shall be by overlapping joint. Transom screwing shall be able to bear the dead load of the any type of infill.

Unit Quantity Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.)

For higher field weights, additional transom fixing with aluminum connecting brackets and subsequent transom assembly shall be provided.

Vertical connections shall have vertical expansion joints.

Pressure compensation and drainage from open rebates of transom sections in mullion channel shall be up to the base point.

Supporting shims shall be laid on aluminum shims for load denudation. Thermal Break shall be provided by the contractor. Incase of openable panel handle and curtain wall arm shall be provided. Friction Hinges/

Parallel hinges shall be SS 316 of approved make. All sections and accessories shall have to be approved by

Engineer-in-Charge before execution. Rates shall be inclusive of providing 8mm thick rough ground ( 8 mm thick water proof ply) with sealant, 8mm thick colored structural sealant of approved make for joints between two DGU panels, anodizing, approved quality anchor fasteners of size and diameter for fixing of DGU aluminium sections with adjacent wall / RCC elements and making the entire system air and water tight, treatment of spendral portion and providing of smoke seal. Test certificates for SHGC & U-value to be submitted to Engineer-in-Charge for verification.

Contractor to submit certificate of origin & shop drawings to Engineer-in-Charge for any approval before procurement of materials. DGU Panels should be factory fabricated and should be as per approved manufacturers specifications.DGU Glass system shall be 6 mm reflective toughened glass + 10 to 12 mm air gap between filled with inert gas and hermtically sealed + 6 mm toughened glass which will take care of SGHC= 0.25, U value= 0.58 BTU/hr.sqft. Deg F or

3.30 W/sqm K. Contractor shall submit manufacturer's data sheet before placing of the order to confirm it technical data to Engineer-in-Charge. Work to be done by specilized agency mentioned in list of approved makes.

Note:- 1. For The purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places.

Note:-2. The following performance test are to be conducted on structural glazing system from the certified laboratories accreditated by NABL(National

Accreditation Board for Testing and Calibration

Laboratories), Department of Science & Technologies,

India. Cost of testing is included in this rate.

Performance Testing of Structural glazing system Tests to be conducted in the NBL

Certified laboratories:

S.

No.

Description of Item

1. Performance Laboratory Test for Air Leakage Test (-

50pa to –300pa) & (+50pa to +300pa) as per ASTM E-

283-04 testing method for a range of testing limit 1 to

200 mVhr”

2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME-331-09 testing method for a range up to

2000 ml.”

3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto

2000 ml”

4. Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm”

5. Seismic Movement Test (upto 30 mm) as per AAMA

501.4-09 testing method for Qualitative test” Tests to be conducted on site

6. Onsite Test for Water Leakage for a pressure range

50 kpa to 240 kpa (35psi) upto 2000ml”.

Unit Quantity Rate in

Fig.( Rs.)

Sqm 2014.24

48 Providing, making and fixing storage units of depth of

450 mm in position comprising of following:

1) Box work, shutters and shelves shall be made from

19 mm thick BWR ply. Total number of shelves inside shall be 2 .

2) Backing of boxwork shall be made from 12mm thick

BWR ply.

3) Laminate of 1.0 mm thickness approved make and shade on both sides of shelves, both sides of shutters and exposed visible sides of ply of box work.

4) Teak wood - Best quality Ghana Teak Wood frame work 75mm X 25mm size and 6 mm thick lipping on all ply edges. 19mm x 75 mm thick base .

5) Polishing: Lacquer polish on wooden and ply surfaces other than laminated surface.

6) Hardware: - Hinges: SS 304 grade Butt hinges of

75 mm x 40mm for openable shutters of approved make for openable shutters - 4 hinges per shutter .

- Tower bolt: Brass satin finish nickel plated or SS

304 (150 mm long)for upper shutters and 100 mm long for bottom shutters.

- Handle: 150 mm long Solid rod "D" shaped handle of SS 304 grade

- Magnet Catcher- of approved make 2 nos per active shutter

- One multipurpose lock per active shutter of approved make

- Adjustable shelves shall be fixed by 25mm x 25 mm x 3mm powder coated MS angles.

7) Onsite measurement for wardrobes, storages, etc. shall be taken before manufacturing and it shall be

6mm less from all sides adjacent to wall or ceiling.

Gaps shall be filled silicon sealant of approved make and shade.

The work shall be done as per sample approved and as directed by Engineer-in-charge. The rate shall be for complete item inclusive of all material, labour, wastages, necessary tools & tackles,adhesives, consumable hardwares & required SS 304 grade hardware/accessories for all floors, all heights.

Rate in Words

( Rs.)

Amount

(Rs.)

49 Automatic Entance Gate:-

Providing & fixing double leaf Swing gate actuator, comprising of the drive unit, integral electronic control unit with key selector, Pair of Photocells with anodised aluminium vertical mountings , Flashing light

,additional key selector, back up battery kit mounted out side control panel, electrically operated lock ( double cylinder) complete work as per manufacturer's specifications.

Sizes : (3750 + 3750)mm width & height 1800 mm

Sqm each

403.12

1.00

S.

No.

Description of Item

50 Supplying and fixing modular storage facility for kitchen of approved make , specifications and tender drawings inclusive of necessary hardware, fixing accessory, finishing as approved by Engineer-in-

Charge . One mockup has to prepared and approved by Engineer-in-Charge before ordering .

Unit Quantity Rate in

Fig.( Rs.) a

Class III - Modular Kitchen ( as per tender drawing No.

NA_A4_MK_III-L_03) b

Class IV - Modular Kitchen ( as per tender drawing

No. NA_A4_MK_IV-L_05) c

Class IV - Modular Kitchen with Soft Close (as per tender drawing No. NA_A4_MK_IV-H_04) d e

Class V - Modular Kitchen with Soft Close ( as per tender drawing No. NA_A4_MK_V-H_01)

Director Bunglows & Guest House - Modular Kitchen ,

Soft Close and chimney ( as per tender drawing No.

NA_A4_MK_D-H_02)

51 Powder Coated Galvenised Iron(PCGI) Wall Panels :

Providing and fixing of pre- fabricated insulated sandwich panels made up of 0.8 mm Galvanised Plain

Skin Pass (GPSP) GI Sheet with epoxy polyester powder coating & Insulation of PUF with density 40±2

Kg /M3 as per specifications. Overall thickness of the panel will be 80 mm . Rate includes cut out of all type, any size, any numbers , sealing the joints with suitable adhesive with all finishing . each each each each each

Sqm

52 Cladding Panels:

Providing and fixing of pre- fabricated insulated sandwich panels made up of 0.8 mm Galvanised Plain

Skin Pass (GPSP) GI Sheet on both side with epoxy polyester powder coating & Insulation of PUF with density 40±2 Kg /M3 as per specifications.Overall

thickness will be 44 mm .Rate includes cut out of all type, any size, any numbers , sealing the joints with suitable adhesive with all finishing .

3.00

550.00

8.00

9.00

9.00

8.00

Sqm

53 Non Walkable Ceiling Panels:

Providing and fixing of pre- fabricated insulated sandwich panels Made up of 0.8 mm Galvanised Plain

Skin Pass (GPSP) GI Sheet on both side with epoxy polyester powder coating & Insulation of PUF with density 40±2 Kg /M3 overall to fit within each other with Self Supported systemthickness will be 44 mm

.Panel designed to fit within each other with Self

Supported system. Rate includes cut out of all type, any size, any numbers , sealing the joints with suitable adhesive with all finishing .

Sqm

54 Providing and fixing pre-coated Aluminium Coving having thickness 0.5 mm at junction of wall and floor having radius 50/65mm to match with the existing surafces material.

55 Providing and Fixing of Aluminium Corner Coving (

3D).

56 Providing and Fixing of Aluminium Coving corner 2D.

metre

Nos

Nos

487.00

689.55

960.00

127.00

48.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

57 Clean Room Door:

Providing and fixing of door fit to flush into the wall panels. Shutter sheet thickness will be 0.8mm and

Frame will be 1.2mm thick made up of GPSP GI sheet with epoxy polyester powder coating. Leaf thickness will be 44mm and infill will be PUF with density 40±2

Kg /M3 .

a Single leaf door size 1000*2100mm

Nos of Door Accessories included as per instruction of

Engineer-in-Charge:

SS Ball bearing hinges

D handle single side

One Side push plate

Door closer TS-68 STD arm

Kick plate 0.8mm thick upto 300mm one side

Drop seal

Door seal

Door Stopper

Dead Lock with both side key operation

Toughened glass of 400*800mm b Double leaf door size 1800*2100mm

Door Accessories included as per instruction of

Engineer-in-Charge.

SS Ball bearing hinges

D handle single side

One Side push plate

Door closer TS-68 STD arm

Kick plate 0.8mm thick upto 300mm one side

Drop seal

Door seal

Door Stopper

Dead Lock with both side key operation

Flush bolt for Double leaf door

Toughened glass of 400*800mm

58 Epoxy flooring:

Providing & laying 4mm avg. thick self levelling Epoxy flooring ( 2mm epoxy screed + 2mm epoxy self levelling ), including levelling, cleaning of the bed surface, treating contraction and expansion joints by filling with approved filler, applying primer coat, etc.

.

The finished floor display good abrasion resistant &

Monolithic Jointless surface.

Unit Quantity Rate in

Fig.( Rs.)

Nos

Nos

25.00

1.00

Sqm 689.55

59 EPOXY COVING : 75mm X 75mm

Providing, laying and fixing epoxy coving at all required junction i.e wall/floor, wall/ceiling, Wall/wall which shall be constructed with solvents very high abrasion resistant aggregates.

Coving shall be impermeable with water & flush with wall/floor/ceiling

& with proper levelling at all floor, all levels, all height.

metre 207.50

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

SANITARY INSTALLATION

Note: i) Detail of Sanitary fixture are for the information of the Contractor, however model / makes of all sanitary fixture shall be selected by

Engineer Incharge / Interior designer / client and the same shall be binding for execution.

ii) No additional all fixing cost shall be paid for change in type of sanitary fixture or fitting.

iii) Provision of extension pieces, chairs, brackets, nuts, bolts and all accessories as required for final connection of CP fittings shall be supplied and installed by the contractor accordingly (as required).

60 Providing, Fixing & Testing of white vitreous China wall mounting cascade type water closet with CP bolts, nuts, CI chair hanging arrangements, bakelite seat & cover with CP hinges & rubber buffers, CP brass screw, washer with all accessories with WC connector with

Rubber Lip / Buffer and side gap filled with silicon sealant wherever required with chrome finished brass

Concealed type dual flush valve (suitable for shaft / wall) fittings push button arrangement. Including

32/40 mm dia C.P. flush pipe with clamp and adapter, rubber joint, C.P. brass wall flange, elbow complete with all other accessories including cutting, making good the walls, floors, slab wherever required as per direction of Engineer-in-Charge.

Unit Quantity Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.) a b c d e f g

Type-1-WC

Hindware - WC - 20061 with seat cover or CERA 2036

(carat series) with seat cover (carina) or SOMANY

(MIDO) 120515 with seat cover 120678 and Hindware -

Flush valve - 850022 or CERA-CM 102 or Somany

250002.

Type-1-WC

Hindware - WC - 20061 with seat cover or CERA 2036

(carat series) with seat cover (carina) or SOMANY

(MIDO) 120515 with seat cover 120678 and flush valve of Jaquar - 1093 or CERA- 102 or Somany-

250002.

Type-2-WC

Jaquar-CNS-WHT-WS01( CONTINENTAL) with seat cover or Kohler Patio K-18131-0 with seat cover and flush valve of Jaquar - FLV - 1085 or ROCA of dual flush fitting, of flushing capacity 3 litre/ 6 litre .

each each each

Type-3-WC

Jaquar-Florentine - FLS-WHT-0111 with seat cover or

ROCA-NEXO with seat cover and flush valve of Jaquar -

FLV - 1085 or ROCA of dual flush fitting, of flushing capacity 3 litre/ 6 litre .

Type-4-WC

Jaquar SLS-WHT-0117(SOLO) or Kohler-K-8752-

0(ODEON) with seat cover-K-8752K-S-0 or ROCA-

Sidney with seat cover and flush valve of Jaquar - FLV -

1085 or ROCA of dual flush fitting, of flushing capacity

3 litre/ 6 litre .

Type-5-WC

Cera- Compact-2837 with seat cover 2330 or

Hindware-Studio-Cat.No.-20061 with PVC seat cover premium with steel hinges or Somany 120501 D'ORO with PVC seat cover and flush valve of

Jaquar - FLV - 1085 or ROCA of dual flush fitting, of flushing capacity 3 litre/ 6 litre .

each each each

Providing, fixing & testing of jet spray consisting of jet spray, triangular spacer attached with toilet seat hinges, C.P. brass angle valve & C.P brass flexible pipe, wall flange complete .

each

63.00

129.00

56.00

23.00

2.00

10.00

10.00

S.

No.

Description of Item

61 Supply, fixing & Testing of C.P. hand spray with lever control (health faucet) and flexible hose 1 m long connection with C.P. holder for hand spray complete in all respects as per direction of Engineer-in-Charge.

Unit Quantity Rate in

Fig.( Rs.) a Somany - 250013 or CERA - CG 106 or Hindware

F160023, ABS with required accessories complete all.

b each

Jaquar - ALD-CHR-573 or CERA - CG 106 or Hindware

F160023, ABS with required accessories complete all.

each

62 Supply, fixing &Testing of white vitreous china flat back wash basin with CP brass waste assembly, CP cast brass bottle trap with CP extension piece, 450mm long CP copper connections pipes, wall flanges and rubber adapters for waste connection complete including CI/MS brackets and duly painted, wall flange and union complete, including nuts, washers and vitreous china for wash basin complete recessed at the back for the reception of pipes and fittings including cutting and making good the walls floors wherever required as per direction of Engineer-in-

Charge: a b c d

Type-1-WB

Hindware - 10038 with full pedestal or CERA - Casino

1023 with full pedestal or Somany - Uniek 110107 with full Pedestal 110206 and

Waste coupling - Hindware- F850001 or CERA CM 103 or Somany 250008 and

Bottle Trap - Hindware- F850015 or CERA CM 104a or

Somany 250006.

Type-1-WB

Hindware - Sola 10007 with full pedestal or CERA -

Casino 1023 with full pedestal or Somany - Uniek

110107 with full Pedestal 110206 and

Waste coupling - Jaquar ALD- 709 full thread or CERA

CM 103 or Somany 250008 and

Bottle Trap - Jaquar ALD 769 or CERA CM 104a or

Somany 250006.

Type-2-WB

Jaquar: SLS-WHT-0611, with half pedestal SLS-WHT-

1505(SOLO) or Kohler K-11341-1-0 with half pedestal

(FOLIO) or ROCA ( GIRALDA) with half pedestal and and

Waste Coupling - Jaquar ALD-709 full thread or Kohler

K-9031 IN-CP and

Bottle Trap - JaquarALD-769 or Kohler K-16407 IN-CP. each each

Type-3-WB

Jaquar: SLS-WHT-0610(OPAL), with half pedestal OPS-

WHT-1504 or Kohler K-11341-1-0, with half pedestal

(FOLIO) or ( ROCA)Giralda with half pedestal and

Waste Coupling - Jaquar ALD-709 full thread or Kohler

K-9031 IN-CP and

Bottle Trap - JaquarALD-769 or Kohler K-16407 IN-CP. each e f

Type-4-WB

Jaquar: JDS-WHT-0542 (JDR-Counter Top) or ROCA

(FONTANA- Counter Top) and

Waste Coupling - Jaquar ALD-709 full thread or Kohler

K-9031 IN-CP and

Bottle Trap - JaquarALD-769 or Kohler K-16407 IN-CP. each each

Type-5-WB

Cera: Canon-1012 or Hindware: Compact- 10004 or

Somany: 110142 Lux and

Waste Coupling - CERA CM 103 full thread or Hindware

F850001 full thread or Somany 250008 full thread and

Bottle Trap - CERA - CM104A or Hindware F850015 or

Somany - 250006.

each

63.00

220.00

63.00

129.00

56.00

23.00

2.00

15.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

63 Supply, fixing & Testing of C.P. brass Wash Basin mixer with C.P. flange, overhead spout complete as required as per direction of Engineer-in-Charge:

Unit Quantity Rate in

Fig.( Rs.) a b c

Jaquar : CON-CHR-167KNB or CERA:CP 115 or

Somany:ECHO 221012.

Jaquar: FLR-5001B (Florentine) or Kohler K-8620IN-

ND-CP (EOLIA) single lever or ROCA Attic - Monoblock.

each each

Jaquar: FLR-5233K single lever (Florentine) or Kohler

K-660IN-ND-CP (Candide) single or ROCA loft elite.

each

64 Supply, fixing & Testing of 15mm Diameter C.P brass pillar Cock with heavy CP wall Flange etc complete as per direction of Engineer-in-Charge.

a Cera - CP 109A or Hindware F290001 or Somany

220901 (AAHA).

65 Supply, fixing & Testing of C.P. brass wall mounted sink mixer with C.P. wall flange, overhead swinging spout complete as required and making good Including necessary wall cutting / chasing complete as per direction of Engineer-in-Charge.

a Jaquar - 23309 or Cera-Cl-119 or Johnson.

each each b Jaquar - CON-CHR-319KN, KOHLER-SIROCCO-8616IN-

1A-CP.

66 Supply, fixing & Testing of CP Brass Shower Mixer with provision of over head shower with 115mm long bend pipe, in built spout, spout/shower selector with wall flange complete with all accessories complete as required and making good the walls:Cera - CP 112 or

Hindware: F280018 or Somany: ECHO (221021).

each each

67 Supply, fixing & testing of CP Brass 115mm long

Shower Arm with wall flange and pressure adjustable

Shower Rose complete with all accessories as required and making good the walls wherever required.

181.00

85.00

4.00

17.00

19.00

50.00

107.00

a Cera - CP 140 shower with shower arm or Somany

ECHO 221027 with shower arm or Hindware F160004 with shower arm.

b c

Jaquar: OHS-1989 with shower arm( SHA-477) or

Kohler K-16356IN-CP showerhead with shower Arm & flange or ROCA ATTIC showerhead with shower arm & flange.

Jaquar: OHS-1999 SHA-483 shower head with shower arm & flange or Kohler K-16351IN-CP showerhead with shower arm & flange.

68 Supply, fixing & Testing of storage type water heater of approved shade with copper container, glasswool insulation,stove enamelled MS jacket, thermostatically controlled inner heater with pilot neon lamps, angle valve on inlet connection, 15mm dia CP flexible connection pipe in inlet & outlet suitable for working pressure of 5/8 kg/sqcm complete as per direction of

Engineer-in-Charge.

a b

Capacity 15 litres (Racold, A0 Smith).

Capacity 25 litres (Racold, A0 Smith).

each each each each each

107.00

81.00

4.00

244.00

2.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

69 Providing , fixing & testing of white vitrous china flat back urinal with automatic flushing systems comprising of all plumbing, electronic and electrical items. CP brass flush pipe with CP brass elbow, CP brass spreader, CP wall flange, infrared photo cells, eyes electrically operated solenoid valve, step down transformer / equipment and any other item required to provide satisfactory functioning including necessary wall cutting / chasing and making good, as required for urinal flushing complete as mentioned above as per direction of Engineer-in-Charge.

URINAL - Hindware- 60002 or CERA 5001 or Somany

13024 and

FLUSH VALVE Sensotronic Concealed Type for Urinal

Complete Set with Installation Box with Control Cock -

Jaquar- 51087 or equivalent of Parryware and Kohler.

Unit Quantity Rate in

Fig.( Rs.)

78 each

70 Providing & fixing white vitreos chinaware urinal partitions , comprising of necessary wall cutting / chasing and making good, as required for urinal partition complete as mentioned above as per direction of Engineer-in-Charge.

71 Providing & fixing of robe hook.

Hindware-F840007 or Cera CA 105 or Somany 23056.

each each

72 Providing & fixing of soap dish.

Hindware-1137N or Cera 6913 A or Somany 230505.

each

73 Providing & fixing of soap dish.

Jaquar - 1131N or Cera CA 103 .

each

74 Providing & fixing of C.P brass toilet paper holder

Jaquar - 1151N.

each

75 Providing & fixing C.P. brass Towel rod - 600mm long with CP screws. Jaquar - 1111NM or Kohler K-17524-

CP (EOLIA) or ROCA (PLAY).

76 Supply, Fixing of solid state, no touch operting, fully hygienic hand drier of approved make with single blower, with time delay, summer & winter control, music while drying, volume ON/OFF controls including providing necessary brackets, cable from drier to Plug,

Plug top key and lock etc, complete as required.

each each

77 Providing & fixing C.P. brass Towel ring: a Hindware-890003 or Cera CA 102 or Somany 230505.

each b Jaquar - 1121N or Kohler K-17528 (EOLIA) or ROCA

(PLAY).

COLD AND HOT WATER SUPPLY (INTERNAL)

Providing and fixing of GI pipe complete with GI fiitings and clamps, including cutting and making good the wall as per direction of Engineer-in-Charge.

Internal Work - Exposed on wall each a b c d a b

65 mm dia.

80 mm dia.

100 mm dia.

150 mm dia.

79 Providing and laying two coats of Synthetic enamel paint of approved shade on pipes and supports as per pipe colour code over a coat of primer. Including painting of legends with direction arrow as per the approval of Engineer-in-Charge.

65 mm dia.

80 mm dia. metre metre metre metre metre metre

36.00

36.00

63.00

63.00

42.00

93.00

118.00

53.00

63.00

269.00

580.00

285.00

280.00

75.00

580.00

285.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item c d

100 mm dia.

150 mm dia.

80 Providing, Fixing & Testing of nitrle rubber insulation on hot water supply pipes as per direction of Engineerin-Charge.

Unit metre metre

Quantity

280.00

75.00

Rate in

Fig.( Rs.) c d a b e f

15 mm dia (9 mm thickness).

20 mm dia (9 mm thickness).

25 mm dia (9 mm thickness).

32 mm dia (13 mm thickness).

40 mm dia (13 mm thickness).

50 mm dia (13 mm thickness).

g 65 mm dia (13 mm thickness).

81 Providing, Fixing & Testing of full way lever operated forged brass ball valve of brass body with forged brass hard chromeplated steel ball tested to a pressure rating of PN 16 with threaded / flanged joints complete with nuts, bolts, gaskets, washers union etc as per direction of Engineer-in-Charge.

metre metre metre metre metre metre metre

726.00

585.00

120.00

30.00

50.00

30.00

10.00

a 15 mm dia.

d e b c

20 mm dia.

25 mm dia.

32 mm dia.

40 mm dia.

f 50 mm dia.

82 Providing, Fixing & Testing of butterfly valve (Body :

Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). PN 16 Valves. Including flanges, nuts, bolts, washers & painting complete as required.

each each each each each each

65.00

270.00

121.00

232.00

59.00

63.00

a 65 mm dia.

b c

80 mm dia.

100 mm dia.

d 150 mm dia.

83 Providing, Fixing & Testing of high pressure rated

Gun Metal Float Valve with copper ball float and brass rods of required length suitable for test pressure of not less than 10 Kg/sqcm of the following sizes: each each each each

18.00

10.00

7.00

2.00

Rate in Words

( Rs.)

Amount

(Rs.) a b

20 mm dia.

25 mm dia.

84 Providing, Fixing & Testing of CI Air Release valve for cold water supply risers, suitable for pressure not less than 10 Kg/Sq.cm. a 15 mm dia.

85 Providing and fixing in position G.I. vent with brass mosquito proof coupling and air filter including return bend, complete as required. The entire fitting shall be hot dip galvanised.

a 100 mm dia.

86 Providing and fixing M.S. puddle flanges fabricated of

750 mm long pipe pieces to RCC water tanks wall / slab.

The entire fitting shall be hot dipped galvanised(Flanges shall confirming to BS10 Table E). each each each each

4.00

11.00

298.00

53.00

S.

No.

a b

Description of Item

25 mm dia (Screwed ends MS plate 6 mm thick; 125 mm x 125 mm plus dia of pipe).

32 mm dia (Screwed ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

c 40 mm dia (Screwed ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

d e f g

50 mm dia (Screwed ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

65 mm dia (Screwed ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

80 mm dia (Screwed ends MS plate 6 mm thick; 400 mm x 400 mm plus dia of pipe).

100 mm dia (Screwed ends MS plate 6 mm thick; 500 mm x 500 mm plus dia of pipe).

87 h i

150 mm dia (Screwed ends MS plate 6 mm thick; 600 mm x 600 mm plus dia of pipe).

200 mm dia (Screwed ends MS plate 6 mm thick; 600 mm x 600 mm plus dia of pipe).

Providing and fixing HDPE tanks with inlet,outlet nipples and man hole cover.

500 Ltrs.

1000 Ltrs.

a b

INTERNAL DRAINAGE (SOIL, WASTE & VENT)

88 Providing, Fixing & Testing of GI inlet hopper with two or three inlets fittings to receive waste pipes from fixtures waste. The hopper shall be fabricated from

100 mm dia upto 600 mm long GI heavy class pipe and welded GI sockets, fixed to CI trap with lead / drip seal joint and support through galvanized steel support from slab or set in cement concrete mix 1:2:4 complete as required. The hopper shall be hot dip galvanized after fabrication and fixed to CI trap / pipe with drip seal joint.

Unit Quantity Rate in

Fig.( Rs.) each each each each each each each each each each each

60.00

6.00

38.00

48.00

24.00

21.00

42.00

23.00

2.00

3.00

3.00

each 446.00

89 Providing, Fixing, Testing & Commissioning of 100mm x 50mm GI waste with reducing elbow & nipple cutting chases, the floor / slab, repairs complete as required and connection to GI waste pipe.

each 259.00

90 Providing, Fixing, Testing & Commissioning of Heavy class SS grating with Cockroach proof SS strainer of approved design including setting in floor with cement motor to match with floor finish as per Engineer-in-

Charge .

a Size 127 mm x 127 mm.

b Size 150 mm x 150 mm.

91 Providing and fixing Brass floor clean out plug comprising of GI pipe, socket, elbow, extension piece caulked to pipe and cast brass plug with suitable inlet key for opening male threaded joint with GI class C pipe & socket. Including lead / drip seal caulked to CI pipes or CI class LA pipes complete as required including paint.

a 100 mm dia.

each each each

259.00

446.00

32.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

Solar Water Heater System

92 Providing, fixing , Testing and commissioning of Solar

Hot Water indirect heating system using approved type of Heating liquid medium comprising of eight number of flat plate solar panels, including all interconnecting insulated G.I. piping, primary and secondary recirculation pumps, pressure type insulated hot water tank, sacrificial magnesium anode with steel core including electrical heating arrangement, valves on inlet, outlet, Y stainer and a water meter on the inlet, air release valve all mounted on galvanized MS sections complete with connection with the existing piping as directed by Engineer-in-

Charge and comprising of following items:

Unit Quantity Rate in

Fig.( Rs.) a b c d

24 nos of flat plate solar collector panels of 2 m x 1 m size approx. The panels enclosed in insulated collector boxes with single piece toughned glass 4 mm thick and fixed with heat resistant gasket with complete accessories.

1 no of Solar HWH System 3000 lpd of hot water at

55 deg.C Heat Exchanger Capacity - 35,000 BTHU

/Day with complete accessories.

1 no of Solar HWH System 3000 lpd of hot water at 60 degree C with , an insulated storage water tank of dual vessel construction, inner vessel of stainless steel grade 304 OR glass lined MS sheet or copper sheet to withstand a test pressure of 7 kg./sqcm with outer vessel of mild steel sheathing of 3000 ltrs capacity, mounted horizontally, temperature measuring device, thermostats, inlet outlet and drain connections as required with complete accessories.

Providing and fixing horizontal/ vertical monobloc single/multi stage pumping set for hot water pumps with CI body, bronze impellar, stainless steel shaft and bronze shaft sleeve, (suitable for 90 deg. C. hot water flow) connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply having IP 55 protection enclosure, all inter connecting pipe work & valves, pressure gauge etc. vibration eliminating pads etc. complete with base and frame, nuts and bolts fixed over RCC foundations as per requirement complete in all respects. (RCC foundation shall be paid in relevant item)

Hot water recirculation (Cap & head as per manufacturer's approved design)

Primary pump - 2 Nos(1W+1S),

Secondary pumps - 2 Nos(1W+1S),

Recirculation pump - 2 Nos (1W+1S)

Total 6 nos. of pumps as described above:

Solar Water Heater System comprising of all above

EXTERNAL WATER SUPPLY SYSTEM

93 Providing and fixing G.I. pipes complete with G.I.

fittings including trenching and refilling etc. (external work):

System a 100 mm nominal bore.

94 Making connection of G.I. distribution branch with G.I.

main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete

: a 100 to 150 mm nominal bore.

EXTERNAL DRAINAGE SYSTEM metre each

1.00

1570.00

6.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

95 Providing, laying, jointing and testing in position the following IS:14333 HDPE - PE 63 (PN-6.0) Pipes for lab drainage cut to required lengths making proper connections at required depths. Pipe to be laid below ground level in trenches upto required depth including excavation in all kind of soil (hard rock), dewatering, refilling, watering, ramming & removing the surplus excavated material and making good the same complete as required. Cost shall be inclusive of providing protection to pipe all round CC haunches as per specification.

Unit Quantity Rate in

Fig.( Rs.) c d a b e

63 mm dia.

110 mm dia.

160 mm dia.

200 mm dia.

250 mm dia.

metre metre metre metre metre

90.00

150.00

120.00

250.00

225.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

WATER SUPPLY, DRAINAGE, PUMPS &

EQUIPMENT

96 Providing and fixing GI Heavy class header complete for pump suction / discharge manifold comprising of expansion elbows, flanges, unions, check nuts, tee elbow etc. including all flanged connections as per site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as directed by Engineer-In-Charge.

Unit Quantity Rate in

Fig.( Rs.) a b c d e

25 mm dia.

32 mm dia.

40 mm dia.

50 mm dia.

65 mm dia. f g

80 mm dia.

100 mm dia.

97 Providing , fixing & commissioning of full way lever operated forged brass ball valve of brass body with forged brass hard chromeplated steel ball tested to a pressure not less than 15 Kg / sqcm with threaded / flanged joints complete with nuts, bolts, gaskets, washers etc. as per direction of Engineer-in-Charge.

metre metre metre metre metre metre metre a b

25 mm dia. Nominal bore.

32 mm dia. Nominal bore.

c 40 mm dia. Nominal bore.

d 50 mm dia. Nominal bore.

98 Providing & fixing butterfly valve (Body : Grey Cast

Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner

: HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.

each each each each a b

65 mm dia. Nominal bore.

80 mm dia. Nominal bore.

c 100 mm dia. Nominal bore.

99 Providing & fixing gun metal horizontal flap type non return valve conforming to IS 778. Including rubber gasket, flanges, union, nuts, bolts & washers complete as required.

c d a b

40 mm dia.

50 mm dia.

65 mm dia.

80 mm dia.

100 Providing & fixing C.I. `Y' Strainer (screwed/ flanged) with stainless steel fine wire mesh perforated sheet basket with necessary flange/ unions nuts, bolts and washers complete as required (on pump suction)as per direction of Engineer-in-Charge.

each each each

No.

No.

each each

15.00

60.00

60.00

40.00

80.00

80.00

40.00

2.00

2.00

2.00

2.00

20.00

47.00

5.00

1.00

1.00

10.00

12.00

c d a b

50 mm dia.

65 mm dia.

80 mm dia.

200 mm dia.

101 Providing & fixing M.S. puddle flange fabricated of 750 mm long pipe pieces to R.C.C. water tank wall / slab.

The entire fitting shall be hot dipped galvanised

(Flanges shall confirming to BS10 Table E).

each each each

No.

2.00

2.00

7.00

4.00

Rate in Words

( Rs.)

Amount

(Rs.) a 25 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe).

each 22.00

S.

No.

b c d e f g h

Description of Item

40 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe).

50 mm dia (Screwed ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe).

65 mm dia (Flanged ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe).

80 mm dia (Flanged ends MS plate 6 mm thick; 100 mm x 100 mm plus dia of pipe).

100 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

150 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

200 mm dia (Flanged ends MS plate 6 mm thick; 250 mm x 250 mm plus dia of pipe).

102 Providing and fixing electronic type level indicator for water tanks mounting in panel with the following features, level display, alarm when water level is low or high, full range from one level to four level display and manual reset for alarm etc. with electrical wiring conduit supports from wall & ceiling probes and all other accessories complete as required.

Unit Quantity Rate in

Fig.( Rs.) each each each each each each each

2.00

30.00

2.00

9.00

30.00

10.00

2.00

each 8.00

103 Providing and fixing in position GI vent with brass mosquito proof coupling and air filter including return bend complete as required. The entire fitting shall be hot dip galvanised.

a 100 mm dia.

104 Providing ,installation & testing of dial type pressure gauge with pressure scale of 0 to 15 kg / sq.cm.

Provision of isolation cock suitable for maximum pressure of 15 kg / sq.cm shall be included in cost.

each 12.00

each 19.00

105 Providing complete testing kit with all chemicals complete suitable for conducting test on water quality.

The test kit shall be suitable to measure TDS, pH,

Hardness, Iron content and other parametres .

each 2.00

106 Supply, Installation, Testing and Commissioning Of

Compact Self Contained Skid Mounted

Hydropneumatic System as Follows: a. Vertical, In-Line, Multisage, centrifugal pumps with

SS-304 casing and impeller and SS-316 shaft, CI base

& head TEFC motor (with mechanical seal).

b. Vendor to submit performance curves and technical catalog of the proposed model for review & information.

c. The pump shall be selected for performance at best efficiency point. However, the pump selection shall be suitable for perfometreance with set point @ + 20% of the rated head.

d.

External Pump mounted or wall mounted microprocessor PID controller and frequency inverter integrated in a single body or as separate components with pressure sensor transmitter minimum two lined

LCD display, diodes to indicate pump ready, pump running and fault and capable to communicate with other controllers following MODBUS-RTU or BACNET

Class-2 protocall through RS485 port. System should be capable to compensate for frictional losses at lower flows. All alarm should be displayed in the controller.

System should be equiped with dry running protection

- Quantity : 1 each

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item e. Complete (Skid mounted wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring and any other necessary imports etc.

Unit Quantity Rate in

Fig.( Rs.) f. Precharged diaphram pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete.

g. Set of accessories such as pressure switches, pressure transducers, inter connecting power and control cabling etc. complete.

h. Accessories like pressure gauge, MS base frame

(Synthetic enamel painted over a coat of primer).

i. GI suction and delivery header with flanges for inlet connection, common outlet header with flanges for outlet connections as required, and inter connecting piping with flexible connections, eccentric type reducers etc. all necessary indigenous accessories as required to complete the installation.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

Note : Contractor to note that the suction header is required to have inlet connection from the Puddle Flange

@ water tanks and to the pump suction. Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold   /   header   shall   be   provided   as   required.

Unit Quantity Rate in

Fig.( Rs.)

107

Pumps : 2 (1W+1S)

Water Flow Rate : 55 LPM (each)

Head : 45 M

RPM 2900

Purpose : Domestic water supply

Location : Plumbing Plant Room

1 set comprises of Hydropneumatic system as above

Supply, installation, testing and commissioning of continuous duty submersible centrifugal non-clogging drainage pumps complete with 3 phase motor with all necessary protection and mechanical seal etc.

complete with all ancillaries including float type level controllers, electrical control panels fabricatd from 14 gauge CRCA sheet volt metre ammetre with selector switch, TPMCB, 5 VA CL : CTs, phase indicating lamps protected by 2 Amp SP MCB, DOL starter, necessary wiring, cable alleys, earthing, interlocking, starter with

Automatic float type level controller, providion of high level alametre, sequence timer, potential free contact to starter for connection to BAS, both pumps may run simultaneously at pre detemetreind level. (1 Working

+ 1 Standby)

Contractor to submit proposed pump model with duty curve.

Set

108

Flow rate : 360 LPM

Head : 10 Mtrs

Solid Handling : 10-12 MM

Location : Sump of Basement

WATER TREATMENT PLANT

Supplying, installing, testing and commissioning of SS vertical centrifugal pump. each pump shall have TEFC

2900 RPM three phase electric motor. The pump shall have cast iron head, base plate SS Shaft/ Impeller/

Intemetreediate chamber. Pump shall be provided with mechanical seal. The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate with vibration eliminator pads complete as required.(1Working + 1Standby)

Set

2.00

8.00

109

Flow rate :55 LPM each

Head : 35 Mtrs

Required for : Filter feed pump

Providing, fixing, testing & commissioning of vertical

Dual Media FRP filter with adequate dirt holding capacity. The filter shall be complete having PVC frontal piping with 50 mm multiport valve including all supporting structure with initial charge filter media.

The filter shall be provided with set of internals for raw water inlet and bottom collecting system. Velocity in frontal piping and valves shall be 1.50 m/sec.Filter for

Domestic Water services.

Set 2.00

Rate in Words

( Rs.)

Amount

(Rs.) a b

FRP Filter:

Filteration Rate :20000 L/Sqm/Hr

Working pressure: 3 Kg/Sq.cm

Capacity :55 LPM

Activated Carbon Filter:

Filteration Rate :14000 L/Sqm/Hr

Working pressure :3 Kg/Sq.cm

Capacity :55 LPM

No

No

2.00

2.00

S.

No.

110

Description of Item

Providing, fixing, testing & commissioning of FRP water softening plant (suitable for 3 Kg/Sqcm working pressure) complete with initial charge with T-40 NA

Resin, multiport valve with built in ejector for controlling all operations), regeneration system and

HDPE tank, pressure gauge at inlet, outlet and back wash (each with isolation cock), valves, fittings and water hardness testing kit & associated works.

Velocity in frontal piping and valves shall be 1.50

m/sec Softener shall be suitable for the following duty.

Raw water hardness: 400 Mg/L

Treated water hardness: 10 Mg/L

Capacity :55 LPM

Unit Quantity Rate in

Fig.( Rs.)

No 2.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

111

Description of Item

Supplying, installing, testing and commissioning of dosing system (for domestic water treatment plant) consisting of one HDPE tank of 200 litres capacity with a positive displacement diphragm dosing pump having variable flowrate of 0-6 lph. The motor shall be suitable for operation at 240 V/single phase/50 Hz.

Supply. The pump shall be supplied complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall be speed & stroke control Asia LMI / equivalent make.

The cost shall be inclusive of providing salt for the testing and operation of system before handover to the Client.

Unit Quantity Rate in

Fig.( Rs.)

No 2.00

112 Supplying, installing, testing and commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification with level controller (In Raw Water, Treated Water

Tank : High / Low Level Controller) etc with control cabling from field to MCC as required.

The system shall be complete to ensure automatic quotation of pump in accordance to water level in respective tanks.

No 2.00

113

  MAIN   DISTRIBUTION   BOARDS

Supply, Installation, Testing & Commissioning , cubicle type body made out of 2mm thick CRCA sheet,totally enclosed, IP 42, floor mounted with channel base frame, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with extensible busbars on both sides, making interlocking arrangement including control wiring with 2.5 sq mm size wires/cable, interconnection, duly powder coated painting etc.

including supply & installation of following switchgears,metreing accessories as per specifications.

instruments and a) INCOMER

1 each 150 Amp four pole Moulded Case Circuit

Breaker (Ics value 35 KA) with built in thermal based release unit with adjustable setting .

b) BUSBARS

150Amp TPN busbars of high conductivity electrolytic quality aluminium alloy.

c) INSTRUMENTS

1 each digital multifunction metre (Ammetre +

Voltmetre) for 3 phase, 4 wire operation as per specification.

1 Sets of RYB phase indicating lamps controlled by 2 amp MCB.

d) OUTGOING i) 1 Nos. 40 amps TP MCCB (Ics value 35 KA)outgoing feeder to 1 each Domestic Water pump.

ii) 2 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Filter feed pump motor 2 each 5 HP(1working + 1Stand by). each compartment shall contain direct & analogue type

Ammetre , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

iii) 4 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Bore well pump motor 4 each 15 HP (2working + 2Stand by). each compartment shall contain direct & analogue type

Ammetre , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item iv) 4 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Sump pump motor 4 each 3 HP ((2working + 2Stand by).each

compartment shall contain direct & analogue type

Ammetre , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

Unit Quantity Rate in

Fig.( Rs.) v) 8 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to stormwater drainage sump pump motor 8 each 2 HP (4working +

4Stand by). each compartment shall contain direct & analogue type Ammetre , auto / manual selector swtich and indicating / pushbutton lamps with MCB for

ON / OFF / TRIP of motor.Note:All breakers shall be mechanical interlocked with suitable accessories.Separate neutral link shall be provided in all 3 Pole feeders.All breakers breaking capacities shall be ICU=ICS.

Rate in Words

( Rs.)

Amount

(Rs.)

Main Distribution panel consisting of all above No 2.00

S.

No.

114

Description of Item

Fire Fighting System

Supplying, installing, testing & commissioning of electric driven Main Fire & sprinkler Pump suitable for automatic operation complete consisting of the following:

Horizontal split casing centrifugal suction type pump of cast iron body & bronze impeller with stainless steel shaft, mechanical Seal to ensure a minimum pressure

3.5 kg/cm2 at highest and farthest outlet at specified flow of 2280 ltrs./minute against a total head of 70 metres confometreing to IS: 1520.

Unit Quantity Rate in

Fig.( Rs.)

Squirrel cage induction motor suitable for 415 V, ±

10%, 50 Hz, AC supply of suitable rating for the above pump with synchronous speed of 1500 RPM T.E.F.C.

type such as confirming to IP:55 protection for inclosure, horizontal foot mounted type wth Class-'F' insullation, confometreing to IS: 325 and flexible coupling and coupling guard with the pump.

Mild steel fabricated Common bed plate of channel, foundation bolts ect.

Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers with anti vibration pads as required.

115 Supplying, installing, testing & commissioning of

Diesel Engine driven main fire Pump suitable for automatic operation consisting of the following (as per specification).

Horizontal split casing multistage centrifugal suction type pump of cast iron body & bronze impeller with stainless steel shaft, mechanical Seal to ensure a minimum pressure 3.5 kg/cm2 at highest and farthest outlet at specified flow of 2280 ltrs./minute against a total head of 70 metres confirming to IS: 1520.

No 3.00

Suitable HP, 1500 RPM water cooled with radiator,

Diesel Engine confirming to relevent BS & IS standard complete with auto starting mechanisum, 12 volts/24

Volts electric starting equipment i/e suitable maintenance free batteries of 12 V, 180 AH. Diesel tank 400lts. with first charge and manual oil pump set., Exhaust pipe extended upto open top of building as per requirement duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer , instruments and protection as per specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour ect. as required, common bed plate for mounting of engine.

Mild steel fabricated Common bed plate of channel, foundation bolts ect. as required.

Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers with anti vibration pads as required.

116 Providing & fixing, testing and commissioning of electrical driven jockey pump (pressurisation pump) suitable for automatic operation and comprising of following: complete in all respect as required.

Horizontally mounted centrifugal end suction type

Jockey pump complete of cast iron body & bronze impeller with stainless steel shaft, mechanical Seal delivery of 180 ltrs/minute against a total head of 70 metres approx complete with arrangement for testing of the working of the pumping set as required confirming to IS: 1520.

Rate shall also include

Mechanical Seal.

No 2.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

Squirrel cage induction motor T.E.F.C type suitable operation on 415 V ± 10%, 3 phase 50 Hz AC supply wit IP 55 class of protection for encloser, horizontal foot mounted type class - 'F' insulation, confirming to

IS : 325 of suitable rating for the above pump with synchronous speed of 2900 RPM and flexible coupling and coupling guard with the pump.

Unit Quantity Rate in

Fig.( Rs.)

Mild steel fabricated Common bed plate of channel, foundation bolts ect. as required.

Suitable reinforced cement concrete pump foundation including cushy foot mounting, foundation bolts, washers with anti vibration pads as required.

No 2.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

117

Description of Item

Main Distribution Boards (Fire Fighting)

Supply, Installation, Testing & Commissioning , cubicle type body made out of 2mm thick CRCA sheet,totally enclosed, IP 42, floor with channel base frame, dust and vemetrein proof, indoor, compartmentalised extensible segregated hinged lockeble door, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with extensible busbars on both sides, making interlocking arrangement between incomers & buscoupler breakers, including control wiring with 2.5

sq mm size wires/cable, interconnection, duly powder coated painting etc. including supply & installation of following switchgears,metreing accessories as per specifications.

instruments and

Unit Quantity Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.)

INCOMER

1 each 150 Amp four pole Moulded Case Circuit

Breaker (Ics value 50 KA) with built in microprocessor based release unit with adjustable setting .

INSTRUMENTS

2 each digital multifunction metre (Ammetre +

Voltmetre) for 3 phase, 4 wire operation as per specification.

2 Sets of RYB phase indicating lamp scontrolled by 2 amp MCB & with toggle switch

BUSBARS

200Amp TPN busbars of high conductivity electrolytic quality aluminium alloy.

OUTGOING

2 Nos. 125 amps TP MPCB (Ics value 50 KA) with inbuilt thermal magnetic release with all acessories incluidind 1 each Auto DOL starter suitable for 60 HP with, single phase preventor oil relay ammetre with

CTs `ON'/OFF`TRIP' indicating lamp and push bottons, potential free contacts for remote operation in each feeder and auto / manual selector switch complete as required. (out going feeders to Hydrant /

Sprinkler pump motor.)

1 Nos. 40 amps TP MCCB (Ics value 35 KA) with inbuilt thermal magnetic release with all acessories incluidind 1 each Auto DOL starter at 10 HP with, ammetre with CTs `ON'/OFF`TRIP' indicating lamp and push bottons, potential free contacts for remote operation in each feeder and auto / manual selector switch complete out going feeders to Hydrant Jockey/

Sprinkler Jockey pump motor.(2 Sets)

Diesel Engine Control:

Control for Diesel Engine comprising:-

Auto/ Manual selecator switch & 3 attempt strating device, timers and relays as required, push buttons, strat/stop in manual mode.

Indication lamp for High/ Low Lub. Oil pressure, High

Water Temp. and Engine ON Indication.

Battery chrager suitable for 12 V/ 24 V DC with boost and tickle selector switch, 0-30 V DC volt metre, 0-

20A DC Ammetre.

All standard senescing and protection relays and accessories for automatic operation of diesel engine.

System Controller

Designing, Supply, Installation, testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, pressurisation pump, terrace pump in sequence as per specification consisting of relays, timers, sensors, annunciation window for fault indication, complete as per specification

S.

No.

118

Description of Item

Note:

All breakers shall be mechanical interlocked with suitable accessories.

Separate neutral link shall be provided in all 3 Pole feeders.

Spare Feeder & 4 each MPCB

All breakers breaking capacities shall be ICU=ICS

Indication Panel in Fire Control Room

Fabrication, supply, installation, testing & commissioning of wall mounted remote indication panel for fire fighting system fabricated from not less than 1.6 mm. thick CRCA sheet, powder coated of approved shade, complete internal wiring, indicating lamps, relays, accessories, numbering, lettering complete in all respect and consisting of the following as required.

119

ON/OFF indication of main electrical fire pump and

Sprinkler pump, pressurisation pump.

Audio/Visual indication of operation of main electric/diesel fire pump with reset push button.

Pressure indication in fire fighting system (pressure transducer to be installed under separate item.)

Failure of Hydrant pump to start

High level in fire water storage tank compartment

Low level in fire water storage tank compartment

Low level in HSD day tank of the fire pump

Supplying, installation, testing and commissioning of annunciation panel made out of not less 1.6 mm thick

CRCA sheet powder coated in approved colour with locking arrangement, audio and visual indication of fault and operation of automatic sprinkler, system monitoring including providing and fixing the following, connections interconnections etc.

complete as required.

Monitoring 1 Nos. of flow switches.

Moniotoring the open circuit, short circuit & earth fault in control cable between panel and flow switches.

Unit Quantity Rate in

Fig.( Rs.)

No

No

2.00

2.00

Battery charger trickle cum boost to take complete load of annunciation panel complete with indication of low battery voltage, mains failure and other accessories including providing and fixing of 2 No 12 volts 24 AH each sealed maintenance free batteries.

120

Audible alarm.

Supply, installation, testing and commissioning of

Terrace fire pump comprising of the following: a. Horizontal mono-block centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C

supply.

The pump casing shall be CI, shaft shall be CS & impeller / shaft sleeve / casing wearing ring shall be bronze. The system shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side.

(The pump should meet the condition and shall be gotten approved by the Local fire Authority).

b. Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 HZ AC supply for the above pump with speed of

2900 R.P.M. c. Suitable cement concrete foundation with plaster,

(design and drawing to be provided by the Contractor while the foundation will be done by others) complete with Antivibration arrangement of cushy foot mounting.

For pump defined above & of duty as follows :

Flow : 450 LPM

Head : 40 mts

No

No

2.00

1.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

121 Supplying and laying of XLPE insulated PVC stranded aluminium conductor 1.1 kv grade (ametreoured) U.G.

power cable following size on existing cable tray suitably clamped with termination with aluminium lugs at both ends as required conforming to IS : 7098 as amended.

a b

3.5 core 95sq. mm.

3 core 50 sq. mm.

c d

4 core 16 sq. mm.

3 core 16 sq. mm.

122 Supplying of following 1100 volt grade PVC insulated sheathed copper conductor un-armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

Unit metre metre metre metre

Quantity

30.00

30.00

30.00

30.00

Rate in

Fig.( Rs.) a 3 core x 4 sq. mm.

123 Providing, fixing, testing and commissioning of precharged air vessel (size 250 mm dia & 1200 mm height of 8.0 mm thick MS sheet) for pressurization of hydrant / sprinkler system complete with 2 nos pressure switches with vibration dampner, 2 nos

Pressure gauges, 8 nos 15 mm dia SS needle valves , one no 25 mm dia drain valve, air release valve on top and flanged connection to riser with stop cock on the top, 25 mm dia inlet with isolating valve duly painted from inside and outside complete as required.

metre each

124 Supplying, testing, installation & commissioning of pressure switches for Hydrant, Sprinkler, Standby and

Jockey & Booster Pumps, including necessary wiring upto control panel & other materials.

125 Providing and fixing electronic type level indicator for water tanks mounting in panel with the following features, level display, alarm when water level is low or high, full range from one level to four level display and manual reset for Alarm etc. with electrical wiring conduit supports from wall & ceiling probes and all other accessories complete as required.

each

126 Providing & fixing electronic type water level indicator with LED panel mounted as required by the Engineerin-Charge complete with probes & all control wiring etc.

127 Providing, laying, jointing, testing , commissioning and painting with two coats of synthetic enamel paint with primer of following sizes of MS Class "C" pipes conforming to IS-1239 with all accessories like all fittings (standard MS fitting with welded joint shall be used on the pipes) including tees, elbows, headers, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with galvanised clamps,hangers

(using anchor fastners) as per specification. GI pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Engineer-in-

Charge requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwire and then supply of the same shall also be included for rates under this head.

Welding of any kind on the galvanized support / hanger shall not be permitted.

each each

10.00

2.00

10.00

2.00

2.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

i

128 e f g h a b c d

Description of Item

25 mm dia.

32 mm dia.

40 mm dia.

50 mm dia.

65 mm dia.

80 mm dia

100 mm dia.

150 mm dia.

200 mm dia.

Providing, laying, jointing and testing in trenches the following sizes of MS class `C' (heavy class) pipes conforming to IS: 1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers including excavation in all kind of soil, refilling, ramming, shoring, removing the excavated surplus material, providing cement concrete support to the pipe and making good the same complete as required. Rate shall include for dewatering necessary to execute the work. The pipe shall not be laid less than 1.0 m below ground level at any point. Pipes shall be embedded all around 150mm thick compacted silver sand and providing protection to embedded MS pipes and fittings and providing anticorrosive treatment with 4 mm thick coal tar as per IS: 10221 & Specification.

Unit Quantity Rate in

Fig.( Rs.) metre metre metre metre metre metre metre metre metre

1950.00

75.00

815.00

1220.00

320.00

265.00

215.00

1610.00

5.00

a b

129

80 mm dia.

150 mm dia.

Providing, fixing, testing & commissioning of butterfly valve PN 1.6 (Body : Grey Cast Iron, Shaft : SS, Disc :

SG Iron (Rilson coated), Liner : HT - EPDM) (upto

150mm dia with hand lever operation & above with gear box operation).Bronze / Gun metal seal

Including rubber gasket, flanges, nuts, bolts, washers

& painting complete as required.

metre metre

185.00

225.00

a b

130 d

131 a b c a b

132

133

150 mm dia.

200 mm dia (Gear Operated).

Providing, fixing, testing & commissioning of CI wafer type dual plate check valve PN 1.6 including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required.

65 mm dia.

100 mm dia.

150 mm dia.

200 mm dia.

Providing, fixing, testing & commissioning of CI `Y' strainer with bronze perforated sheet basket including rubber gasket, flanges, nuts, bolts and washers, complete as required and suitable for system pressure.

80 mm dia.

200 mm dia.

Providing & fixing dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI. Cost shall be inclusive of providing any short pieces, nipples, elbows, stainless steel 'U' tube & ball valveetc as required.

Providing & fixing gun metal single headed fire hydrant landing valve with flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. CI wheel, GM coupling, blank cap, chain, twist release type lug & all accessories. Conforming to

IS:5290. Including fixing with anchor fastner and flanged tapping from wet riser and providing pressure gauge with gun metal ball valve complete as required.

each each each each each each each each each each

16.00

11.00

3.00

1.00

21.00

3.00

17.00

4.00

6.00

23.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

134

135

Description of Item

Providing & fixing non-percolating rubber reinforced lined (RRL) fire hose pipe (as per IS : 636) of 63 mm dia and 15 metre length. The hose shall be rated for brust pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & rivetted to hose pipe with copper rivets & 1.5 mm copper wire for External fire hydrant.

Providing and Fixing 63 mm dia instantaneous pattern branch short gunmetal pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required.

Unit Quantity Rate in

Fig.( Rs.) each 46.00

each 23.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

136

Description of Item

Providing & fixing Gun Metal fire brigade connection

(suction collecting head) consisting of 4 Nos. 63 mm dia instantaneous type male couplings with built-in check valves, 1 each 150 mm dia sluice valve, (1 each

150 mm dia non-return valve) and 150 mm dia flanged outlet complete with bolts, nuts and rubber insertions as required and as per IS standards.

Unit Quantity Rate in

Fig.( Rs.) each 4.00

137 Providing & fixing Gun Metal fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS standards complete with 100 mm dia GI suction pipe and 100 mm dia foot valve (to be connected to static tank). Provision of GI drop pipe and foot valve shall be made in all the fire water static storage tanks (4 Nos) (GI pipe to be paid separately through appropriate item while cost of foot valve to be included).

138 Providing, fixing, jointing, painting with two coats of synthetic enamel paint i/c primer coat and testing in position the for drainage purpose following medium class (Class B) MS pipes conforming to IS:1239 cut to required lengths including all necessary fittings (All fittings shall confirm to IS:1879 (part 1 to 10) and specials such as bends, tees, unions, Reducers, flanges & plugs etc. fixing at wall / ceiling level supported by clamps, hangers (using anchor fastners) etc. as per specification. Threading / Welding, jointing, and making proper connections, cutting hole in wall / floor / slab and making good the same. PVC pipe sleeves suitable higher size shall be provided wherever the pipes are crossing the fire rated walls / floors slab and sealing the sleeves with glasswool in between and fire sealent compound at either end all as per Engineer-in-Charge. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and the supply of the same shall also be included in rates under this head. each 3.00

Rate in Words

( Rs.)

Amount

(Rs.) a b

50 mm dia.

80 mm dia.

139 Providing & Fixing of Installation Control Valve with turbine type automatic alarm gong to be connected with control valve, drain & test valve and all other necessary components as per manufacturer's specifications complete as required.

metre metre a 150 mm dia.

140 Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows : each

25.00

85.00

2.00

a Spray recessed (adjustable) rossette (68°C) sprinkler quick response pendant / upright type.

141 Providing and Fixing electrically operated water flow switches (Vane type) including tamper switch and accessories, complete with tap off socket arrangement as required, with potential free contact with 2 each

NONC.

a

142

150 mm dia.

Supply, installation, testing and commissioning ISI marked (IS:940) portable chemical fire extinguisher, water (gas pressure) type capacity 9 litres with gun metal cap and nozzle and complete in all respects including initial fill and wall suspension brackets as required as per specifications.

each each each

11945.00

51.00

21.00

S.

No.

143

Description of Item

Supply, installation, testing and commissioning ISI marked (IS:2878) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with

CO2 gas conforming to IS:307-1966 and walll suspension braket as required as per specifications.

Unit Quantity Rate in

Fig.( Rs.) each 21.00

144 Supply, installation, testing and commissioning ABC

(Powder Type) Fire Extinguisher. Mild Steel Cylinders

ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to

IS:1349-1993 as required as per specifications.

a b

145

4 Kg.

9 Kg.

Providing, fixing, testing & commissioning of MS air cushion tank on top of each riser fabricated from 6mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 8mm thick MS plate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25mm dia valve, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS 4736-1968.

(The cushion tank should be suitable for rated working pressure. each each each

21.00

21.00

1.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

146

Description of Item

INTELLIGENT ADDRESSABLE FIRE DETECTION &

ALARM SYSTEM

FIRE ALARM PANELS

Supply, installation, testing and commissioning of the following as per specifications :

UL Listed Microprocessor based analogue addressable

3 Loops fire alarm control panel with minimum 168 characters LCD display. each loop of panel shall have minimum capacity of 250 (125 Detectors + 125

Devices) analogue addressable devices, and shall have provision for 20% spare capacity. The panel shall be

UL 9th Edition listed and shall be in compliance with technical specifications.

Unit Quantity Rate in

Fig.( Rs.)

The panel shall be complete with Integrated 8 channel digital voice evacuation and 2 ways communication

Fire Fighters system capable to supervision of all the speaker circuits with adequate zone control and accessories. The system shall be equipped with necessary Digital Audio Amplifier capable of processing one of 8 audio channels and total wattage as per speakers mentioned in BOQ with necessary enclosures. The DAA shall be fully monitored for fault and alarm reporting. The proposed Digital

Amplifiers shall not be rail mounted / dependant on

Fire Panel CPU for operation. (Failure of Fire Panel CPU shall not result in failure of Amplifier operation).

147

Tenderer to provide interfacing connectivity (BAC Net/

Modbus gateway) in Fire Panel for integrating with building management system, PA system and Music system (for selected zones) complete as per specification.

Fire Detection & Alarm Control Panel.

UL listed Repeater panel for accessing the information from alternate locations. The Repeater Panel shall include a minimum of 168 characters, backlit by a long life, solid state LCD. It shall be equipped with rubberized key pad. The keypad is functional only when an entry is requested by the system. There shall be fixed and soft keys for functional requirements as per technical specifications.

each each

148

149

ALARM INITIATING DEVICES, MODULES &

CONTROLS :

Supplying, installing, testing and commissioning of following items:

UL listed analogue addressable Multi Sensor smoke detector with mounting based LED, Address Switch / electronic way of addressing, complete as per all requirements of technical specifications & contracts works.

UL listed analogue addressable Photoelectric smoke detector with mounting based LED, Address Switch / electronic way of addressing, complete as per all requirements of technical specifications comprising of below :

UL Listed Fixed temperature cum rate of rise heat detector with mounting based LED, Address Switch / electronic way of addressing, as per technical specifications

Analog addressable LPG detector with mounting based

LED, address switch to programme the detectors complete as required.

each each

150 Fault Isolators for isolating shorted, dewired and loose circuits between two successive fault isolators with automatic required.

resetting arrangement complete as

151 Addressable control/relay modules for Hooters,Fire pumps, Elevators and Pressurization Fan complete.

each each

1.00

1.00

55.00

385.00

24.00

42.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

152 Addressable monitor modules for Sprinkler Flow

Switch, Fire doors, magnetic contacts complete.

153 UL listed, dual action (push IN-pull DOWN) Flush or surface mounted Manual Call Point in manufacturers prescribed matching red enamel outlet box complete with key operated test-reset lock. The word FIRE shall appear in front of station as per technical specifications.

154 Fire Fighter's Telephone Jack for 2 way communication as per specifications complete

155

156

157

2 way communication Fire Fighter's Handset.

Fire panel supervised 70db-84db Ceiling Mounted multi tap 2 Watt Speaker as specified & same make as of panel.

EFFULENT TREATMENT PLANT - ETP

A. DESIGN,SUPPLY, INSTALLATION , Testing and commissioning OF EFFLUENT TREATMENT SYSTEM

FOR RECYCLING OF EFFLUENT

Nature of influent - Effluent

Daily average flow - 20 cum/day

Reuse of treated water. Inlet To STP

Supply, installation, testing & commissioning of

Screens:

2 Nos.Stainless Steel Suitable Sized Manually operated Bar Screen made of SS 304 in RCC screen channel as per following specifications.

Cleaning :- Manual Screen

Bar Spacing :- 5 - 6 mm

MOC :- Complete in SS 304

Supply, installation, testing & commissioning of adequate capacities of twin lobe air blower and

Coarse air diffusers in Equalisation tank for providing aeration.(Qty.-1.00 Lot)

Make of diffusers : Micro/Eqv.

Capacity of blower : 30 m3/hr

Head of blower : 5500 mmmwc

Make of blowers : Beta/Eqv.

Supplying, installing, testing, commissioning of Centrifugal Soil Scape Filter Feed pumps

Complete in CI body& CI impeller with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, strainer at suction. The pump shall be suitable for 415±10% volts 3 phase AC supply .

Pumps = 02 Nos.(1w + 1s)

Flow rate (each) = 2.5 m³/hr

Head = 8-10 m

Supply, installation, testing & commissioning of the ecotechnology system complete with

Organotreat™, Specific Plant species, Under

Drain media.(Qty.-2.00 Lot)

Organotreat: specific media for growth of plant and microbial species

Make of organotreat: Trans NV tech

Providing and fixing all piping and isolation control valves for making the system complete.(Qty.-1.00 Lot)

Providing MFM at inlet of the system.(Qty.-1.00 each)

Providing and fixing water meter at outlet of the system. (Qty.-1.00 each)

Providing and fixing pH meter at outlet of the system. (Qty.-1.00 each)

B. ELECTRICALS

Unit Quantity Rate in

Fig.( Rs.) each each each each each

10.00

25.00

8.00

2.00

285.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre fabricated out of 14 gauge CRCA sheet steel. Cable gland plates shall be provided on top as well as at the bottom of the panels.

Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 Nos.

earthing terminals shall be provided for 3 phase,

4 wire, 50 Hz supply system. Panel should be complete with Isolation push button for every equipment and auto manual selection switches,as per complete Job. (Qty.-1.00 Job).

Unit Quantity Rate in

Fig.( Rs.)

Rate in Words

( Rs.)

Amount

(Rs.)

Note:

Realted all SS/MS/CI works such as supply and fixing of handrails, manholes, gratings, grills, vents, footrests and puddle flanges.

Contractor shall ensure submission of detailed GA drawings (Plan & Section), P & I diagram, schematic diagram for the above mentioned components and additional components such as inserts, puddle flanges, vent pipes etc.

if so required for the complete automatic working of the STP and have it approved by the Engineer-in-Charge.

Effluent Treatment Plant - ETP as described above all

158

BORE WELL

(a)Supplying, installing, testing and commissioning submersible type of pump of approved make suitable for tube well with all necessary standard fittings and accessories adequate capacity of motor i/c like base plate, bend, tee etc. and flow control devices, suitable for well dia 150mm and meeting the following requirement all complete as per specification and direction of Engineer-In-Charge.

Discharge - 5 LPS and Head - 110 Meters.

Job

(b) Providing and lowering GI 80mm dia double flanged lowering pipe of suitable size for pumping machinery as approved by the Engineer-in-charge.

Including all C.I specials such as C.I SV, Reflex valve etc. for making connection with the delivery line all complete as per specification and direction of Engineer-

In-Charge. - 95 metre.

(c ) Supply, Installation, Testing and Commissioning of Pressure Gauge all complete as per specifications and direction of Engineer-In-Charge .

each

159

SEWAGE TREATMENT PLANT - STP

A. SEQUENTIAL BATCH REACTOR TECHNOLOGY

Design, supplying, installing, testing & commissioning of Sewage Treatment Plant (SEQUENTIAL BATCH

REACTOR TECHNOLOGY) (including all MS work) for the following duty:

Nature of effluent - Domestic Sewage from toilet, kitchen waste water shall be discharged into the STP.

Design to take consideration of same.

Daily average flow - 350 Cum / Day pH - 7.5 – 8.5

BOD5 - 250 – 400 Mg/L

S. Solids - 200 – 450 Mg/L

COD - 400 – 600 Mg/L

Oil & Grease - 50 Mg / L

Effluent discharge standard after treatment pH - 6.5 – 8.5

BOD5 - Less than 10Mg/L

S. Solids - Less than 10 Mg/L

1.00

4.00

S.

No.

Description of Item

COD - Less than 60 Mg/L

Oil & Grease - Less than 2 Mg / L

Sewage treatment plant shall include the following items:

Grit chamber

Screen Chamber

Sewage equalization tank / sump

Reactor Tank - 2 nos.

Supernatant Tank

Sludge Holding Tank

Filtration through MGF & ACF

UV Unit

Air Blowers, Pumps & equipment

Piping, valves etc

Electrical Panel & Cabling

1. Supply, installation, testing & commissioning of 2

Nos Stainless Steel Perforated, Corrugated Bar Screen with suitable lifting arrangement (size 1000 mm wide x 600 mm high approx). (Qty-1 set)

2. Constructing Grease Trap of suitable size with minimum of 1200 liquid depth in brick work of class 75 with cement mortar 1:6 (1 cement:6 coarse sand), inside plastering 16 mm thick with cement mortar 1:3

(1:cement:3 coarse sand) with floating coat of neat cement and rough plaster on outside. Including SS bucket as per detail to collect the grease. RCC top slab with 500 mm dia medium duty manhole covers with frame (weight of covers 58 Kg & weight of frame 58

Kg), necessary 150 mm thick foundation concrete

1:2:4 (1 Cement:2 coarse sand:4 Aggregate). (Qty-1 no)

3. Supply of MS hot dip galvanized puddle flanges in accordance to BS:10 table D as required to be provided (in the structural slab and wall) of various diameters. Puddle flanges shall be provided for all the structural component of the STP. The installation of the puddle flanges shall be carried out by the Civil contractor in accordance to the Civil GA drawing (to be prepared by the STP contractor) at the required levels

& position; under the supervision of the STP contractor.(Qty-15 Nos.)

Unit Quantity Rate in

Fig.( Rs.)

4. Supply of plastic manhole step/foot rest (@ 300 mm c/c) with polypropelene compound injection molded around 12 mm dia (Fe-415) steel reinforcing bar. Provision of the foot rest is envisaged in various tanks/ components of the STP for the purpose of accessability. The installation of the foot rest shall be done by the civil contractor as per civil GA drawing.(Qty-80 No.)

5. Supply, installation, testing & commissioning of 10 mm thick MS chequered plate rectangular manhole cover with frame for the feasibility of access in the tank with locking arrangement.

Size : 600 x 900 (Qty-6.00 No.)

6. Supply of vent pipes of 100 mm dia with mosquito proof grating suitable for the ventilation purpose of the various tanks.(Qty-8.00 Nos.)

7. Supply, installation, testing & commissioning of displacer type level switch for automatic operation of the system with high / low level alarm complete with auxillary NO/NC contacts for each tank. (Qty-6.00

No.)

8. Supply, installation, testing & commissioning of

Float & Board type level indicator with isolation valve at top / bottom, & making the installation complete.(Qty-1.00 No.)

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

9. Supply, installation, testing & commissioning of non clogging type submersible pumps complete with all accessories, motor of required capacity. Delivery header with isolation valve, pressure gauge on delivery line with isolation cock, level controller (with wiring) to control the level of sump automatically.

Provison shall be kept to run both pumps simultaneously in case of emergency. Pumps shall have following duty:

9.1

EQT Submersible Sump Pumps for EQTconsidering 6 cycles (2 Nos. 1 working & 1 standby)

Unit Quantity Rate in

Fig.( Rs.)

Flow rate (each) = 30 cum/hr

Head = 12 to 15 Mtr

MOC : CI

9.2 Solid handling size for this pump shall be 35-40 mm

Sludge disposal pump (2 Nos - 1 working + 1

Standby)

Flow rate (each) = 9.0 LPS

Head = 15 Mtr

MOC : CI

9.3 Solid handling size for this pump shall be 15 mm

Plant room sump pump (2 Nos - 1 working + 1

Standby)

Flow rate = 6.0 LPS

Head = 15 Mtrs

MOC : SS

(Solid handling size for this pump shall be 15 mm).

Cost shall be inclusive of PVC flexible Hose pipe ( for piping submeged in effluent) with MS epoxy piping

(for piping non-submerged in effluent)

Provision of guide ropes to guide submersible pump from upper level to operational level in sump basin with channels / angle section of MSEP shall be made by the STP contractor.

10. Air diffusion system shall include the following:

10.1 2 Nos. twin type rotary air blowers (1W + 1S) capable of delivering 200 cum/hr of free air at 0.6

kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a TEFC motor of suitable

HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles

A/C supply.

10.2

Air piping shall comprise of pipes droppers / laterals with MS (epoxy coated) Header complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good. Contactor to submit detailed P & I indicating their proposal.(Qty.-1.00 Lot)

10.3 Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen transfer efficiency of 3-4% per/meter water depth. Air dispersion grid shall be assembled in modular form so that they can be replaced / repaired easily from plat form at the top.

(Imported fine bubble membrane diffusers).(Qty.-1.00

Lot)

11.

Bronze Ball valve and air dispersion grid as required for STP as described above.(Qty.-1.00 Lot)

Note : Air dispersion system shall be provided for

Sewage Sump, aeration tank and Sludge Holding

Tank.

12.

Providing and fixing all piping (as described below) and isolation control valves for making the system complete.

SS 304 : Submerged air piping

MS Epoxy : Air piping & pumped effluent riser (nonsubmerged)

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

PVC piping : Pumped effluent (submerged) & tank overflow pipe line

GI (Heavy) : Interconnecting pipe line after delivery header of pump/ filter.

13.

Supply, installing, testing & commissioning of

ultravoilet dis-infection unit. The unit shall have over 99.9 % bacterial reduction from inlet to outlet.

The dis-infection chamber shall be constructed of SS

316L on all welted parts. The UV lamp shall be of low pressure mercury vapour type with hard glass enclosure, the sockets shall be water tight & vibration resistant. The lamp life shall be rated for 6000 hours.

The unit shall be complete with temperature safety control, lamp out alert circuit & UV radiometer with 4

– 20 mA output.

Unit Quantity Rate in

Fig.( Rs.)

The UV unit shall have with reactor, cabinet housing, cabinet cooling, treatment chamber, electrical panel, temperature safety control, lampout alert, UV radiometer along with UV monitoring system and UV monitoring readout panel. The UV Dosage should be >

60,000 uW – Sec / sq.cm. The lamps should be selected based upon the flow requirement of respective unit.

13.1 Flow Rate : 17.5 Cu-m / Hr.(Qty.-1.00 No)

14 Supplying, installing, testing & commissioning of hypochlorite solution doser comprising of 200

Litres capacity FRP tank with inlet / outlet connection, piping & valves alongwith metering (0-12 lph) pump for dosing. (Qty.-1.00 No)

15.

Supplying, installing, testing & commissioning of

Floating type SS304 Decanter System with all required accessories in Reactor tanks. (Qty.2 No)

16.

Supply, installation, testing and commissioning of PLC based Reactor controller in Reactor tank to control the cycle of Reactor system based on time &

Level based flow measurment inbuilt in the controller.

(Qty.-2 No.)

17.

Supplying, installing, testing & commissioning of horizontal centrifugal filter feed water pumps CI

Head & Base, Bronze Impeller along with motor, pressure gauge with isolation cock, Isolation valve,

NRV on delivery line. Isolation valve, stainer (with bypass) at suction. Mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia) for the pump. The pump shall be suitable for 415±10% volts 3 phase AC supply.

17.1 Filter Feed Pumps: (1 working+ 1 Standby)

Capacity : 5.0 LPS each

Head : 30 M

RPM : 2900

17.2 Irrigation pumps: (1 working+ 1 Standby)-

Capacity : 2.0 LPS each

Head : 30 M

RPM : 2900

18.

Providing, fixing, testing & commissioning of vertical MSEP filter with adequate dirt holding

capacity.

Fabricated from MS sheet as per manufacturer's specifications complete with intitial charge filter media including painting inside with two coats of non toxic epoxy and with one coat of zinc chromate two coats of synthetic enamel paint outside.

Including concrete foudation with cement plaster complete as required. The filter shall also be provided with set of internals for raw water inlet and bottom collecting system. Complete with frontal piping

(heavy) and butterfly valves designed on 1.50 m / sec velocity.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

18.1 Filter for Domestic Water services.(Qty-1.00 no.)

Filteration Rate 20000L/Sqm/Hr

Flow Rate : 5.0 LPS

18.2 Activated Carbon Filter :(Qty-1.00 no)

Filteration Rate 14000L/Sqm/Hr

Flow Rate : 5.0 LPS

19.

Supply, installation, testing and commissioning of Hydraulic filter press of Suitable Capacity with CI frame, PP plates complete with filter cloth complete with Filter press feed pump (Screw Type) – 2 No. (1 working + 1 standby) with 1 No. standby stator, interconnecting piping and poly dosing system.

Unit Quantity Rate in

Fig.( Rs.)

20.

Supply, installation, testing & commissioning of

Electro-magnetic type Flow Meter at inlet of reactor tanks of 100 mm size. (Qty-2.00 No)

21. HYDRO-PNEUMATIC SYSTEM

Supply, Installation, Testing And Commissioning Of

Compact Self Contained

Hydropneumatic System As Follows:

Skid Mounted a. Vertical, In-Line, Multisage, centrifugal pumps with

SS-304 casing and impeller and SS-316 shaft, CI base

& head TEFC motor (with mechanical seal)

(Contractor to submit performance curves and technical catalog of the proposed model for review & information)

The pump shall be selected for performance at best efficiency point. However, the pump selection shall be suitable for performance with set point @

+ 20% of the rated head.

b.

External Pump mounted or wall mounted microprocessor PID controller and frequency inverter integrated in a single body or as separate components with pressure sensor transmitter minimum two lined

LCD display, diodes to indicate pump ready, pump running and fault and capable to communicate with other controllers following MODBUS-RTU or BACNET

Class-2 protocall through RS485 port. System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller.

System should be equiped with dry running protection.

Rate in Words

( Rs.)

Amount

(Rs.) c. Complete (Skid mounted wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring ,single VFD and any other necessary imports etc. d. Precharged diaphram pressure vessel with food grade membrane, charging connection, connected to outlet header with necessary flanges, gaskets, isolating valves, nuts/bolts etc complete.

e. Set of accessories such as pressure switches, pressure transducers, inter connecting power and control cabling etc. complete.

f. Accessories like pressure gauge, MS base frame

(Synthetic enamel painted over a coat of primer).

g. GI suction and delivery header with flanges for inlet connection, common outlet header with flanges for outlet connections as required, and inter connecting piping with flexible connections, eccentric type reducers etc. all necessary indigenous accessories as required to complete the installation.

21.1 Flushing hydropneumatic system as follows:

No. of pumps -2 (1 Working + 1 Standby)

Water Flow Rate 7.0 LPS each

Purpose : OHT Filling for phase-1

Head 80 M

RPM 2900

S.

No.

Description of Item

22.

Providing & fixing on line Electro magnetic

type flow meter cum Totaliser for Monitoring the total flow, Flow rate. etc. Including electrical wiring from panel to flow meter. Complete with all type of

Plumbing & Electrical connections, accessories, wiring, conduits & supports complete with all respect.

The signal from read out shall be 4-20 m.amps to be received on BAS.(Qty-1 no.)

Unit Quantity Rate in

Fig.( Rs.)

23.

Providing & fixing level controllers, pressure

swtich and transmitters for water pumps to start/stop the pump at set level. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically.(Qty-4

No)

24.

Providing & fixing on line pH meter digital type for Monitoring the online pH after Tertiary treatmnent & before disposal. Including electrical wiring from panel to flow meter. Complete with all type of Plumbing & Electrical connections, accessories, wiring, conduits & supports complete with all respect.(Qty-1 no.)

25.

Approval from pollution board at initial & various other stages of works including preparation of report / drawings as per pollution board requirement, testing & commissioning. Contractor shall include the cost of all chemicals consumed during testing & commissioning and the cost of such items of works which are not explicitly mentioned above, but are mendatory to have pollution board approval.(Qty-1

Job)

B. ELECTRICAL INSTALLATION FOR SEWAGE

Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre shall be fabricated out of 14 gauge

CRCA sheet steel in form in 3b formation with reinforcement of suitable size angle iron, channel ‘T’ sections irons and /or flats wherever necessary. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 No.

earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel before fabrication. Cadmium

Plated hardware shall be used in fabrication of panels.

Quoted rates shall inclusive of cables, cable trays, control cabling, earthing (in accordance to specification) with earthing from panel to each motor / equipment.

MCC –1 (Sewage Treatment Plant)

Incoming

200 amps TPN MCCB with the following accessories: a. 0-415 volts 96 x 96 mm square voltmeter with selector switch shall be protected by 2 amps TP MCB.

1 Set b. 0-500 amps 96 x 96 mm square ammeter with selector switch and 200/5 amps 10 VA CL:1 CTs.

1 Set c. Phase indicating lamps shall be protected by 2 amp

SP MCB-3 Set

Bus Bar

250 amps TPN (25 KA) aluminium bus bar with heat shrinkable insulation sleeves

Outgoings a. 2 No. suitable rating MPCB for 10.0 KW DOL starter and outgoing feeder to EQT effluent transfer pumps motor - Main (including 1No. standby).

Each compartment shall contain auto / manual selector swtich and indicating / pushbutton lamps with MCB for

ON / OFF / TRIP of motor.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item b. 3 No. suitable rating MPCB for 5.0 KW direct on line starter and outgoing feeder to air blowers (including 1 no.

standby).

Each compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for ‘ON/OFF/TRIP' status of motor

Unit Quantity Rate in

Fig.( Rs.) c. 2 No. suitable rating MPCB for 3.0 KW direct on line starter and outgoing feeders to sludge disposal pump

(including 1 no. standby). Compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for ‘ON/OFF/TRIP’ status of motor d. 2 No. suitable rating MPCB for No. 4.0 KW direct on line starter and outgoing feeders to filter feed pump including future (including 1 no. standby). Each compartment shall contain auto/manual selector switch and indicating lamps with MCB for

‘ON/OFF/TRIP’ status of motor e. 2 No. suitable rating MPCB for No. 3.0 KW direct on line starter and outgoing feeders to irrigation water pump (including 1 no. standby). Each compartment shall contain auto / manual selector switch and indicating lamps with MCB for ‘ON/OFF/TRIP’ status of motor g. 2 No. suitable rating MPCB for 2.2 KW direct on line starter and outgoing feeders to Filter press.

Compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for

‘ON/OFF/TRIP’ status of motor h. 2 No. suitable rating MPCB for 3.0 KW direct on line starter and outgoing feeders to plantroom sump pump

(including 1 no. standby). Compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for ‘ON/OFF/TRIP’ status of motor j. 1 No. suitable rating TPN MCB for 5.0 HP outgoing feeders to flushing water hydropneumatic for Phase 1 k. 2 No. suitable rating MPCB for No. 15 KW star delta starter and outgoing feeders to axial flow fan. Each compartment shall contain auto/manual selector switch and indicating lamps with MCB for ‘ON / OFF /

TRIP’ status of motor.

l. 1 Nos. suitable rating MPCB for 3.0 KW direct on line starter and outgoing feeders to submersible mixer.

Compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for

‘ON/OFF/TRIP’ status of motor m. 2 Nos. suitable rating MPCB for 5.0 KW direct on line starter and outgoing feeders to floating type decanter. Compartment shall contain auto/manual selector switch and indicating lamps with MCB’s for

‘ON/OFF/TRIP’ status of motor n. Spare MCB’s of following capacities: i.

20 amps TPN

2 Nos.

ii 32 amps TPN

MCB’s

MCB’s

2 Nos.

Note : All MCCB's to be suitable for motor duty and shall be of 25 KA breaking capacity.

Provision shall be made for providing potential free contacts to all pumps starters for connection to building automation system.

MCC –1 for STP as described above ( Qty.- 1 Nos.)

Note1: Contractor shall ensure submission of detailed

GA drawings (Plan & Section), P&I diagram, schematic diagram for the above said component and additional component if so required for the complete working of the STP for the full capacity.

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item

Note2: Contractor to note that the suction header is required to have inlet connection from the Puddle

Flange @ water tanks and to the pump suction.

Provision of delivery header is required to have outlet connection from the pumps. Suitable outlet flanges from the delivery mainfold / header shall be provided as required.

Unit Quantity Rate in

Fig.( Rs.)

160

Sewage Treatment Plant -STP( Sqential Batch

Reactor Technology) as described all above

Main Distribution Board for STP: Supply,

Installation, Testing & Commissioning , cubicle type body made out of 2mm thick CRCA sheet,totally enclosed, IP 42, floor mounted with channel base frame, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with extensible busbars on both sides, making interlocking arrangement including control wiring with 2.5 sq mm size wires/cable, interconnection, duly powder coated painting etc.

including supply & installation of following switchgears,metering instruments and accessories as per specifications.

INCOMER

1 No. 150 Amp four pole Moulded Case Circuit Breaker

(Ics value 35 KA) with built in thermal based release unit with adjustable setting .

BUSBARS

150Amp TPN busbars of high conductivity electrolytic quality aluminium alloy.

INSTRUMENTS

1 No. digital multifunction meter (Ammeter +

Voltmeter) for 3 phase, 4 wire operation as per specification.

1 Sets of RYB phase indicating lamps controlled by 2 amp MCB.

OUTGOING a. 1 Nos. 40 amps TP MCCB (Ics value 35 KA)outgoing feeder to 1 no. Domestic Water pump.

b. 2 No. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Filter feed pump motor 2 no. 5 HP(1working + 1Stand by). Each compartment shall contain direct & analogue type

Ammeter , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

c. 4 No. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Bore well pump motor 4 no. 15 HP (2working + 2Stand by). Each compartment shall contain direct & analogue type

Ammeter , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

d. 4 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to Sump pump motor 4 no. 3 HP ((2working + 2Stand by).Each

compartment shall contain direct & analogue type

Ammeter , auto / manual selector swtich and indicating / pushbutton lamps with MCB for ON / OFF /

TRIP of motor.

No 1.00

Rate in Words

( Rs.)

Amount

(Rs.)

S.

No.

Description of Item e. 8 Nos. MPCB with (Ics value 35 KA) DOL starter of suitable rating for outgoing feeder to stormwater drainage sump pump motor 8 no. 2 HP (4working +

4Stand by). Each compartment shall contain direct & analogue type Ammeter , auto / manual selector swtich and indicating / pushbutton lamps with MCB for

ON / OFF / TRIP of motor.

Unit Quantity Rate in

Fig.( Rs.)

Note:

All breakers shall be mechanical interlocked with suitable accessories.

Separate neutral link shall be provided in all 3 Pole feeders.

All breakers breaking capacities shall be

ICU=ICS

Total Cost of NON Schedule items(Civil) of

Schedule-B

No 1.00

Rate in Words

( Rs.)

Amount

(Rs.)

Name of the work :Construction and Development of Agri-Food Cluster Campus of National Agri Food Biotechnology Institute(NABI) at Mohali(Punjab).

NON SCHEDULE ITEMS (ELECTRICAL) SCHEDULE-D f g h j i c d e a b a

2 a

Item

No

1

3

Description of Item Unit Quantity

SUB HEAD (A): ELECTRICAL WORKS

CIRCUIT CUM POINT WIRING

Supply, installation, testing and commissioning of flush mounted outlets wired to T 568 A or B with British style faceplace. The plastic shall be high impact, flame-retardant, UL rate thermoplastic. Dust cover/ blank shall be provided to protect unused fa

Single outlet faceplate with RJ-45 jack

Supply, installation, testing and commissioning of 4 pair Category 6 LAN cable consisting of 24

AWG solid copper conductors and as per the specification.

The cable should have flexibleJacket and ripcord for easy stripability

Each 652.00

metre 7,000.00

Notes:- The rate shall also include the following:

Providing and fixing junction boxes with covers including painting.

Effecting adequate and proper connections at temetreinations.

Providing all fixing accessories such as clamping devices nuts, bolts and screws.

Excavation laying of cable filling of sand, brick protection, back filling of earth, watering, ramming and making good.

Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.

All cable shall be laid with one diameter gap.

All cables shall be IS approved.

Fire retardant paint one meter on both side of wall penetration and at temetreination as per specifications.

Buried LT cables to be laid atleast 750 mm below ground.

All cut-outs/ Sleeves shall be sealed with fire retardant sealant as per specification.

CABLES, MAINS AND SUB MAINS

Supplying of following 1100 volt grade XLPE insulated PVC inner sheathed and HR PVC outer sheathed aluminium conductor ametreoured cables as per specification.

3.5 Core 300 Sq.mm

metre 22.00

metre 195.00

3.5 Core 185 Sq.mm

3.5 Core 150 Sq.mm

3.5 Core 120 Sq.mm

metre 350.00

metre 165.00

metre 270.00

3.5 Core 95 Sq.mm

3.5 Core 70 Sq.mm

3.5 Core 50 Sq.mm

metre 470.00

metre 140.00

metre 800.00

3.5 Core 35 Sq.mm

4 Core 25 Sq.mm

4 Core 16 Sq.mm

metre 600.00

metre 60.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

a b c d e f

5 c d e

6 a b c d e a b

Item

No

4

Description of Item

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

i f g h

Unit Quantity

4 Core 10 Sq.mm

4 Core 6 Sq.mm

4 Core 4 Sq.mm

3 Core 6 Sq.mm

3 Core 4 Sq.mm

2 Core 2.5 Sq.mm. Control Cable (Dual Metering)

metre 1,500.00

metre 490.00

metre 990.00

metre 1,445.00

metre 54.00

metre 320.00

Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc.

complete as required.

4 Core 6 Sq.mm

metre 24.00

4 Core 4 Sq.mm

metre 40.00

3 Core 6 Sq.mm

metre 56.00

3 Core 4 Sq.mm (Copper Unarmoured Cable)

metre 20.00

2 Core 2.5 Sq.mm. Control Cable (Dual Metering)

metre 26.00

Providing and laying 1.6 MM thick GI factory fabricated raceways in partition of the following sizes including providing removable 3 mm thick GI cover knock out holes and fixing accessories earthing with 8 SWG copper earth wire complete required including floor wall supports, bends, access boxes and tap off boxes as per specification and cross over as per site requirement.

300 mm wide x 40 mm deep raceway

metre. 342.00

250 mm wide x 40 mm deep raceway

metre. 176.00

200 mm wide x 40 mm deep raceway

metre. 242.00

150 mm wide x 40 mm deep raceway

metre. 232.00

100 mm wide x 40 mm deep raceway

metre. 275.00

Providing and fixing of 350 x 350 x 40 mm deep (Nominal size) wall junction box including providing 3 mm thick GI steel cover required as per specification.

metre. 50.00

Providing and fixing of 250 x 250 x 40 mm deep (Nominal size) wall junction box including providing 3 mm thick GI steel cover required as per specification.

metre. 40.00

Providing and fixing of 200 x 200 x 40 mm deep (Nominal size) wall junction box including providing 3 mm thick GI steel cover required as per specification.

metre. 40.00

Providing and fixing of 150 x 150 x 40 mm deep (Nominal size) wall junction box including providing 3 mm thick GI cover required as per specification.

metre. 40.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

MAIN DISTRIBUTION PANEL/ SUB DISTRIBUTION PANEL/ METER BOARD PANEL

Unit Quantity

7

8

Design, fabrication, assembling, wiring, testing, supply, forwarding to site, unloading, shifting to location, inspection, installation, testing and commissioning of Main distribution panels/ subdistribution panels/ Meter Board Panels, fabricated out of 14 gauge CRCA sheet steel in cubicle fometreation, compartmentalized, from 3b construction, free standing floor mounted, dust and vemetrein proof with reinforcement of suitable size angle iron, channel, `T’ sections and/ or flats wherever necessary. 16 gauge CRCA sheet steel shall be used for final distribution panels. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 each earthing temetreinals shall be provided for all distribution panels.

Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the fometre of shop drawings before fabrication.

Galvanised hardware with zinc passivation shall be used in fabrication of panels.

MDB-9

Incoming

1 each 800 Amps TPN manually draw out type Air Circuit Breaker (Icu = Ics) with built in microproccessor based realease for short circuit, over current, earth fault protection with adjustable settings, ON/ OFF/ Trip indication lamp including control MCB's with fuse and with following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 800/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

1000 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 125 Amps TPN MCCB - 1 each iii. 100 Amps TPN MCCB - 3 each iv. 63 Amps TPN MCCB - 8 each

Spare

100 Amps TPN MCCB - 2 each

Notes: i. All MCCB's shall be of 35 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-9 as described above

SDB-9.1,10.1&11.1

Incoming

1 each 63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 60/ 5 Amps 15 VA, CL 1 CTs . -1 Set

Set.

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

150 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

9 each of 32 Amps DP MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

9

32Amps DP MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-9.1,10.1&11.1 as described above

SDB-9.2

Incoming

1 each 125 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 120/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 100 Amps TPN MCCB - 1 each ii. 32Amps 4P MCB - 2 each iii. 40 Amps 4P MCB - 3 each

Spare

40 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-9.2 as described above

10 SDB-9.3

Incoming

1 each 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 100/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 63 Amps 4P MCB - 2 each ii. 32Amps 4P MCB - 3 each iii. 40 Amps 4P MCB - 3 each

Spare

40 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-9.3 as described above

Unit

Set.

Set.

Set.

Quantity

3.00

1.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

11 SDB-9.4

Incoming

1 each 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 100/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 63 Amps 4P MCB - 3 each ii. 32Amps 4P MCB - 2 each iii. 40 Amps 4P MCB - 2 each

Spare

40 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-9.4 as described above

12 SDB-9.5

Incoming

1 each 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 100/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 32Amps 4P MCB - 3 each ii. 25 Amps 4P MCB - 1 each iii. 40 Amps 4P MCB - 2 each

Spare

40 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-9.5 as described above

13 MDB-10

Incoming

1 each 1000 Amps TPN manually draw out type Air Circuit ABreaker (Icu = Ics) with built in microproccessor based realease for short circuit, over current, earth fault protection with adjustable settings, ON/ OFF/ Trip indication lamp including control MCB's with fuse and with following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 1000/5 Amps 15 VA, CL 1 CTs . - 1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's with fuse - 6 Sets

Bus Bars - 1

Unit

Set.

Set.

Quantity

1.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

1250 Amps TPN Aluminiun bus bars with heat coloured shrinkable insulation sleeve. - 1 Set

Outgoing i. 200 Amps TPN MCCB -1 each ii. 160 Amps TPN MCCB -3 each iii. 63 Amps TPN MCCB -3 each ii. 125 Amps TPN MCCB -2 each

Spare i. 160 Amps TPN MCCB -1 each ii. 63 Amps TPN MCCB -1 each

Notes:i. All MCCB's shall be of 35 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-10 as described as above.

14 SDB-10.2

Incoming

1 each 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 160/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 100 Amps TPN MCCB - 2 each i. 63 Amps TPN MCB - 2 each iii. 40 Amps 4P MCB - 2 each iv. 32 Amps 4P MCB - 1 each

Spare

40 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-10.2 as described above

15 SDB-10.3

Incoming

1 each 200 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 200/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

300 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 125 Amps TPN MCCB - 1 each i. 100 Amps TPN MCCB - 1 each iii. 40 Amps 4P MCB - 2 each iv. 32 Amps 4P MCB - 1 each

Spare

Unit

Set.

Set.

Quantity

1.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

40 Amps 4P MCB - 1 each

32 Amps 4P MCB - 1 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-10.3 as described above

16 SDB-10.4

Incoming

1 each 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 160/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 100 Amps TPN MCCB - 3 each iii. 63 Amps 4P MCB - 1 each iii. 40 Amps 4P MCB - 1 each iv. 32 Amps 4P MCB - 1 each

Spare

63 Amps 4P MCB - 1 each

40 Amps 4P MCB - 1 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-10.4 as described above

Unit

Set.

Set.

17 SDB-10.5

Incoming

1 each 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 160/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 100 Amps TPN MCCB - 2 each iii. 63 Amps 4P MCB - 2 each iii. 40 Amps 4P MCB - 1 each iv. 32 Amps 4P MCB - 1 each v. 25 Amps 4P MCB - 1 each

Spare

40 Amps 4P MCB - 1 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

Quantity

1.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

SDB-10.5 as described above

Description of Item

18 MDB-11

Incoming

1 each 1600 Amps TPN manually draw out type Air Circuit Breaker (Icu = Ics) with built in microproccessor based realease for short circuit, over current, earth fault protection with adjustable settings, ON/ OFF/ Trip indication lamp including control MCB's with fuse and with following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 1600/5 Amps 15 VA, CL 1 CTs . - 1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's with fuse - 6 Sets

Bus Bars - 1

2000 Amps TPN Aluminiun bus bars with heat coloured shrinkable insulation sleeve. - 1 Set

Outgoing i. 400 Amps TPN MCCB -1 each ii. 200 Amps TPN MCCB -5 each iii. 160 Amps TPN MCCB -1 each iv. 63 Amps TPN MCCB -3 each

Spare i. 160 Amps TPN MCCB -1 each ii. 63 Amps TPN MCCB -1 each

Notes:i. All MCCB's shall be of 35 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-11 as described as above.

19 SDB-11.2

Incoming

1 each 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 400/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

500 Amps TPN Aluminium bus bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 160 Amps TPN MCCB - 2 each ii. 100 Amps TPN MCCB - 3 each iii. 63 Amps 4P MCB - 1 each iv. 40 Amps 4P MCB - 1 each v. 32 Amps 4P MCB - 2 each

Spare i. 63 Amps 4P MCB - 1 each ii. 40 Amps 4P MCB - 1 each

Notes: -

Unit

Set.

Set

Quantity

1.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-11.2 as described above

20 SDB-11.3 & SDB-11.4

Incoming

1 each 200 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 200/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

300 Amps TPN Aluminium bus bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 160 Amps TPN MCCB - 1 each ii. 100 Amps TPN MCCB - 2 each iii. 63 Amps 4P MCB - 2 each iv. 40 Amps 4P MCB - 1 each v. 32 Amps 4P MCB - 1 each

Spare i. 63 Amps 4P MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-11.3 & 11.4 as described above

21 SDB-11.5

Incoming

1 each 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 160/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bus bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 160 Amps TPN MCCB - 1 each ii. 100 Amps TPN MCCB - 1 each iii. 63 Amps 4P MCB - 1 each iv. 40 Amps 4P MCB - 2 each v. 32 Amps 4P MCB - 1 each vi. 25 Amps 4P MCB - 1 each

Spare i. 63 Amps 4P MCB - 1 each ii. 40 Amps 4P MCB - 1 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

SDB-11.5 as described above

Unit

Set.

Set.

Set.

Quantity

1.00

2.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

22 MDB-11.1 (UPS)

Incoming

200 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/ OFF/

Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:- 3 each

VAF digital electronic meter with inbuilt selector switch and 200/ 5 Amps 15 VA, CL 1 CTs . -3

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 9 Set

Bus Bars

500 Amps TPN Cu Bus bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 63 Amps TPN MCCB - 8 each ii. 32 Amps DP MCB - 4 each

Spare i. 63 Amps TPN MCCB - 2 each ii. 32 Amps DP MCB - 1 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-11.1 as described above

Unit

Set.

Quantity

1.00

Rate in figures

(Rs.)

23 MDB-10.1 (UPS)

Incoming

125 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/ OFF/

Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:- 2 each

VAF digital electronic meter with inbuilt selector switch and 125/ 5 Amps 15 VA, CL 1 CTs . -2

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 6 Set

Bus Bars

300 Amps TPN Cu bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 63 Amps TPN MCCB - 8 each ii. 32 Amps DP MCB - 4 each

Spare i. 63 Amps TPN MCCB - 2 each ii. 32 Amps DP MCB - 1 each

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-10.1 as described above

Set.

24 MDB-9.1 (UPS)

Incoming

63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/ OFF/

Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:- 2 each

VAF digital electronic meter with inbuilt selector switch and 60/ 5 Amps 10 VA, CL 1 CTs . -2 Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 6 Set

Bus Bars

1.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

200 Amps TPN Cu bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing i. 40 Amps 4P MCB - 8 each ii. 32 Amps DP MCB - 4 each

Spare i. 32 Amps DP MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-9.1 as described above

Unit

Set.

25 MDB-9.2 (UPS-Emergency)

Incoming

63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/ OFF/

Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:- 2 each

VAF digital electronic meter with inbuilt selector switch and 60/ 5 Amps 15 VA, CL 1 CTs . -2 Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 6 Set

Bus Bars

100 Amps TPN Cu bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

32 Amps DP MCB - 8 each

Spare

32 Amps DP MCB - 4 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

MDB-9.2 as described above

26 Design, fabrication, assembling, wiring, testing, supply, forwarding to site, unloading, shifting to location, inspection, installation, testing and commissioning of Main distribution panels/ subdistribution panels/ Meter Board Panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, from 3b construction, free standing floor mounted, dust and vermin proof with reinforcement of 15 size angle iron, channel, `T’ sections and/ or flats wherever necessary. 16 gauge CRCA sheet steel shall be used for final distribution panels. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 No. earthing terminals shall be provided for all distribution panels.

Panels shall be 15 for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardware with zinc passivation shall be used in

Set.

Quantity

1.00

1.00

Rate in figures

(Rs.)

Incoming

1 No. 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based realease for short circuit, over current, earth fault protection with adjustable settings, ON/

OFF/ Trip indication lamp including control MCB's with fuse and with following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's with fuse - 6 Sets

Bus Bars - 1

500 Amps TPN Aluminiun bus bars with heat coloured shrinkable insulation sleeve. - 1 Set

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

Outgoing

17 Set of (1 No. 40 Amps 4P MCB before energy meter, three phase Electronic energy meter with required number of CT's and 1 No. 40 Amps 4P MCB after energy meter complete with all accessories including wiring etc. as required as per single line diagram.

Spare

40 Amp 4P MCB - 2 No.

63 Amp 4P MCB - 1 No.

Notes:-

All MCCB's shall be of 35 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-2 & MDB-1 as described as above.

27 MDB-5 (Tower 31A)

Incoming

1 No. 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 400/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

500 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

3 No. of 125 Amps TPN MCCB complete with all accessories including wiring etc. as required as per single line diagram.

2 No. of 160 Amps TPN MCCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

125 Amps TPN MCCB - 1 No.

160 Amps TPN MCCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-5 as described above

28 MDB-6 (Tower 31A)

Incoming

1 No. 400 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 400/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

500 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

5 No. of 125 Amps TPN MCCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

125 Amps TPN MCCB - 1 No.

Unit

Set

Set.

Quantity

2.00

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

100 Amps TPN MCCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-6 as described above

29 SDB-5.3, 5.4, 6.5, 6.4, 6.3, 6.2, 6.1 (Tower 31A)

Incoming

1 No. 125 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 125/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

10 No. of 32 Amps DP MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

32Amps DP MCB - 2 No.

40 Amps 4P MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

SDB-5.3, 5.4, 6.5, 6.4, 6.3, 6.2, 6.1 as described above

30 SDB-5.1 (Tower 31A)

Incoming

1 No. 160 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 160/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

10 No. of 32 Amps DP MCB complete with all accessories including wiring etc. as required as per single line diagram.

2 No. of 40 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

1 No. of 63 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

32Amps DP MCB - 1 No.

63Amps 4P MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

Unit

Set.

Set.

Quantity

1.00

7.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit

SDB-5.1 as described above

31 SDB-5.2 (Tower 31A)

Incoming

1 No. 125 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 120/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

9 No. of 32 Amps DP MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

32Amps DP MCB - 2 No.

63Amps 4P MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

SDB-5.2 as described above

Set.

Set.

Quantity

1.00

1.00

Rate in figures

(Rs.)

32 MDB-8 (Guest House)

Incoming

1 No. 250 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 250/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

300 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

5 No. of 32 Amps TPN MCB complete with all accessories including wiring etc. as required as per single line diagram.

5 No. of 40 Amps TPN MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

32Amps TPN MCB - 2 No.

40 Amps TPN MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-8 as described above Set.

1.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

33 Emergency Panel & Common Area 7.3 & 7.4 (Tower 29 & 27A)

Incoming

1 No. 63 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/ OFF/

Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 60/ 5 Amps 15 VA, CL 1 CTs . -1 Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

150 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

3 No. of 32 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

1 No. of 32 Amps DP MCB complete with all accessories including wiring etc. as required as per single line diagram.

1 No. of 40 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

40 Amps 4P MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

Emergency & Common Area Panel 7.3 & 7.4 as described above

Unit

Set.

Quantity

2.00

Rate in figures

(Rs.)

34 MDB-7 (Animal House)

Incoming

1 No. 100 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 100/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

1 No. of 63 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

1 No. of 40 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

8 No. of 40 Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

40 Amps 4P MCB - 1 No.

32 Amps 4P MCB - 1 No.

Notes: -

All MCCB's shall be of 25 kA (Ics) breaking capacity.

All MCB's shall be of 10 kA breaking capacity.

MDB-7 as described above Set.

1.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

35 Director's bunglow 4 way TPN DB (BPU & NABI)

Incoming

1 No. 63 Amps TPN MCB as per specifications & SLD:

Dual Energy (digital) meter with 60/ 5 Amps 15 VA, CL 1 CTs . -1 Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

100 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

2 No. of 40Amps 4P MCB complete with all accessories including wiring etc. as required as per single line diagram.

Spare

40 Amps TP MCB - 2 No.

Notes: -

All MCB's shall be of 10 kA breaking capacity.

Director's bunglow 4 way TPN DB (BPU & NABI) as described above

Unit

Set.

Quantity

2.00

Rate in figures

(Rs.)

36.00 Terminal Box

Incoming

Supplying, installation, testing and commissioning of 250 mm x 400 mm x 150 mm (WxLxD) consolidation ms box, power coated with perforated door and suitable knockouts for conduit entry at top & with lockable cover plate.

Isolators for following Ratings for UPS Incoming

37.00 200 A TPN MCCB

38.00 125 A TPN MCCB

39.00 63 A TPN MCCB

40

LIGHTING FIXTURES AND FANS

SITC of the following lighting fixtures with all fixing accessories etc. as required.

Recessed Type channel office 1x28 WT5 with AL Specular Louvre Batwing. Make: Philips TBX

321 1x28 TL5 EBP M or equivalent as per approved Make. (Labs,Office and Common Areaa

Amenties Alternate-1)

41

42

43

44

45

Recessed mounted 2 x 18 W with fully frosted Glass. Make: Wipro WCP 27 27218 SGW or equivalent as per approved Make.

Recessed Type channel office 1x28 W T5 with Opal diffuser. Make: Philips TBX 311 1 x28 W TL5

EBP O-SAT or equivalent as per approved Make. (Labs,Office and Common Areaa Amenties

Alternate-2)

Surface mounted Fluorescent light fixture 1x28 W/2x28 W with T5 Tube Light.Make:

CromptonType T5JB13228EB9 or equivalent as per approved Make(Parking,Utility, Store &

Electrical Substation)

Surface/ Wall mounted Fluorescent light fixture 1x28 W/1x14W with T5 Tube Light with

Diffuser.Make : Crompton,Type T5LK1128 or equivalent as per approved Make(Toilet Blocks &

Pantry)

Recessed mounted 2 x 36 W compact flourescent tube light with diffuser. Philips FBS 440 2xPL-

L36W SP EBT or equivalent as per approved Make(Conference & Meeting)

46

Recessed mounted 2xPL-L36W EBT D6 DF-WH light fixture with Direct Indirect and Low Glare 3D

OLC Optics.Philips FBS 580 2xPL-L36W SP EBT/ CG CRDIA236EB or equivalent as per approved

Make(Office & Labs).

No.

No.

No.

No.

each each each each each each each

38.00

3.00

3.00

4.00

35.00

30.00

93.00

140.00

281.00

81.00

965.00

Rate in words(Rs.)

Amount (Rs.)

48

49

50

51

Item

No

47

52

53

54

55

56

57

58

59

60

61

62

Description of Item

Reccesed mounted 1x28W/ 1x54W T5 Wall Washer Light. Make: Philips Type TBS 207 1xTLD-

36W HFB A or equivalent as per approved Make(Conference, Meeting Area & Cabins).

Surface mounted 2x18 W T5 CFL with diffuser. Make: Thorn Type: ORBITILITE S/ CG DCR218EB orequivalent as per approved Make (Corridor & Passage).

Bulk Head lighting fixture Philips make FXC-101 1xPL-S/ 2P 9W AC GR or equivalent as per approved Make complete with PL-9 lamp.

Occupancy Sensors complete with all accessories as required. Make: Philips Lmetre 1071 or equivalent as per approved Make (Staircase Lobby/ Foyer)

Aviation obstruction light cluster of LED's with step down transformer Bajaj make or equivalent as per approved Make complete as required.

Surface mounted linear fluorescent light fixture 1x28 W T5 tube light with diffuser. Make: Philips

FWG 300 WALLLIGHT or equivalent as per approved Make(Toilets, Bed Rooms, Living, Dining,

Store, Kitchen, Guest Room)

Wall mounted light fixture 75 W with Halogen lamp. Make:Philips Ledino wall light or equivalent as per approved Make (Bed Rooms)

Wall mounted Fluorescent light fixture 2x36 W with fluorescent lamp. Make : Thorn Avanti

2x55W TC LHF Direct/Indirect head 96004638 or equivalent as per approved Make

(Bedroom/Living).

Surface/ Wall mounted Fluorescent light fixture 1x28 W with T5 Tube Light.Make : Philips Adreno

28W or equivalent as per approved Make( Utility Store, Servant's room, attendant's room)

Surface mounted Fluorescent light fixture 2x9 W with compact fluorescent lamp. Thorn Novello

CNVS 209(LPF) or equilvalent as per approved Make.(Passage betwwen dining and servant's room)

Surface mounted Flourescent downlighter, with acrylic diffuser light fixture, with 2 x 18 W with compact flourescent lamp.Make : Artlite RL 2815 2x18W/ CG DWLDA07IH or equivalent as per approved Make (Passage, Baclony)

Surface mounted Compact fluroscent downlighter with fully frosted glass 2 x 18 W compact flourescent lamp.Make : Artlite RL-2802 / CG CBH13 or equivalent (Main Corridor, living room, balcony, stair landing)

Decorative Suspended lighting fixturep down light fixture with 1 x 42 W compact flourescent lamp.Make: Glacier II 42W CFL large Version with Priamatic Reflector or equivalent as per approved Make (Reception, Living & Private Dining).

Wall mounted upligther mounted at double height fixture with 1 x 150 W/ 70 W CDMT lamp.Make:Philips DCP 731 or equivalent as per approved Make(Enatrance poarch, lobby, waiting).

Wall/Surface mounted linear fluorescent light fixture 1x14 W T5 tube light with diffuser. Make:

Philips Coral WRF81128 SG or equivalent as per approved Make (Servant's toilet, Toilets, Bed

Rooms, Living, Dining, Store, Kitchen, Guest Room).

Wall mounted up and downlight light fixture 1x75 W light. Make: Philips DCP 721 or equivalent as per approved Make (Stair landing).

Unit each

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

each each each each

Quantity

145.00

502.00

22.00

10.00

5.00

177.00

90.00

71.00

76.00

118.00

337.00

518.00

2.00

16.00

44.00

158.00

Rate in figures

(Rs.)

63

Surface / wall mounted linear fluorescent light fixture 1x14 W T5 tube light with diffuser. Make:

Philips Adreno 14 W or equivalent as per approved Make (Toilets, Wash basin)

No.

96.00

64

65

Wall mounted CFL light fixture 1x13 W T5 tube light with diffuser. Make: Reiz 156450 Silver

Finish /CG CBH13 or equivalent as per approved Make(Bedrooms)

Surface / wall mounted linear fluorescent light fixture 1x28 W T5 box tube light with diffuser.

Make: Philips TMS122M 1XTLS 28 W EBE or equivalent as per approved Make (Utylity, store, servant's room)

No.

No.

141.00

28.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit

66

Decorative Suspended lighting fixture up down light fixture with 1 x 36 W compact flourescent lamp. Make: Philips Suspension light QPG304 24W or equivalent (Drawing Room and Dining).

No.

67

Wall mounted water tight fixture with diffuser with 1 x42W CFL lamp. Make: Philips DCP711 2xPL-

C/2P-18W or equivalent as per approved Make (Terrace and External)

No.

68

Foot Light recessed mounting, water tight, with 1x18W lamp. Make: Artlite RL-4120 or equivalent as per approved Make(External)

No.

Quantity

64.00

92.00

29.00

69 Occupancy Sensors complete with all accessories as required. (Staircase Lobby/ Foyer) No.

d e f g h a b c g h a b c d e f

70

71

72

73

Aviation obstruction light cluster of LED's with step down transformer Bajaj make or equivalent as per approved Makecomplete as required

SITC of ceiling fan,including wiring the down rods of standard length (upto 30 cm) with 1.5 sq mm FRLS PVC insulated copper conductor , single core cable ete. As required.

1400 mm Sweep Ceiling Fan

1200 mm Sweep Ceiling Fan

900 mm Sweep Ceiling Fan

300 mm dia Domestic Exhaust Fan

250 mm dia Domestic Exhaust Fan

200 mm dia Domestic Exhaust Fan

225 mm dia Light Duty Trans-air bird screen for protection against birds and foreign matter.

5 Star rated ES-50 Premium White/Brown/Ivory energy saving Fan

ACCESSORIES FOR TELEPHONE/TV NETWORK SYSTEM

Supply, fixing, cable temetreination, testing and commissioning of Tag Blocks of Krone make or equivalent and boxes with lockable doors made out of 1.2 mm CRCA sheet with epoxy polyster coating as required.

10 pair tag box

20 pair tag box

30 pair tag box

40 pair tag box

50 pair tag box

60 pair tag box

100 pair tag box

300 pair tag box

Supply, installation, testing and commissioning of following Telephone cable on existing cable trays. The cable shall be as per the specifications laid down in the tender.

No.

No.

No.

No.

No.

No.

No.

each each

No.

No.

No.

No.

No.

No.

No.

each

104.00

9.00

156.00

149.00

14.00

30.00

27.00

118.00

31.00

5.00

39.00

2.00

1.00

1.00

3.00

1.00

10.00

3.00

Rate in figures

(Rs.) a b

5 pair 0.61mm cable

10 pair 0.61mm cable metre 1,026.00 metre 160.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit Quantity c 20 pair 0.61mm cable d 50 pair 0.61mm cable

UPS

74 30 kVA UPS 3 phase (415 V + 15%) Volts input & 3 phase output (415 V + 1%), 50 Hz, Input hametreonic Current THD 3% typical at 100% load, 6% maximum at 50% load and 10 min battery backup for UPS along with battery cabinet complete in all respect including supporting steel structure for UPS and Battery as required.

75 Dismentalling, shifting & re-installation as per drawing of existing 40 kVA UPS 3 phase (415 V)

Volts input & 3 phase output (415 V), 50 Hz, at 100% load and battery backup (existing) for

UPS along with battery cabinet complete in all respect supporting steel structure etc. for UPS and Battery complete as required.

76 Dismentalling, shifting & re-installation as per drawing of existing 60 kVA UPS 3 phase (415 V)

Volts input & 3 phase output (415 V), 50 Hz, at 100% load and battery backup (existing) for

UPS along with battery cabinet complete in all respect supporting steel structure etc. for UPS and Battery complete as required.

77 120 kVA UPS 3 phase (415 V + 15%) Volts input & 3 phase output (415 V + 1%), 50 Hz, Input hametreonic Current THD 3% typical at 100% load, 6% maximum at 50% load and 10 min battery backup for UPS along with battery cabinet complete in all respect including supporting steel structure for UPS and Battery as required.

78

INVERTER

Supply, installation, testing and commissioning of 1 phase input and 1 phase output inverters of

1.5 kVA rating. Sine wave inverter, including batteries etc as required.

SPLIT AIR CONDITIONING WORK

76 Supply, installing, testing and commissioning of wall mounted AIR COOLED SPLIT AIR

CONDITIONING UNITS as described in specifications. The unit shall be complete with Hi wall

type Indoor unit and external condensing unit, complete in all respects, inclusive of copper refrigerant piping, GI condensate drain piping, valves and insulation. Quoted price shall include cost of thermostat, wiring, control cooling thermostat, wiring, control wiring, and earthing The unit capacities shall be after taking deration into account due to copper piping lengths: metre 149.00 metre 110.00 each each each each

No.

2.00

2.00

2.00

3.00

3

Rate in figures

(Rs.) a b c

77 a

The quoted price shall include the GI frame structure to mount the outdoor unit or to suit the site condition.

2 TR split air conditioning units as described above

1.5 TR split air conditioning units as described above

1 TR split air conditioning units as described above

Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows :

150 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

MECHANICAL VENTILATION WORKS

No.

No.

No.

No.

4.00

29.00

9.00

43.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit Quantity

78.0

a

Supply, installation, testing & commissioning of AXIAL FLOW FAN suitable for installing in any position in Horizontal or vertical and complete with totally enclosed fan cooled motor belt drive, multi sheaved pulley mounted on motor and fan shaft, belt guard, motor mount and vibration isolators. The fan shall be selected for low noise level and low RPM (less than 1000 RPM) Fan motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase power supply with high efficiency,EFF-1 type. The fan shall be equipped with mounting bracket & outlet core required at discharge. Minimum 15 mm (WC) external static pressure after fan outlet. Total static pressure shall be checked by Vendor.

Fan Tag : Space Fed : CFM : Motor HP

Lift Well Pressurization

TAF-1 : Tower - 27 A-Apt Type III & IV : 26000 : 7.5

b c

79.0

TAF-2 : Tower - 29 A-Apt Type IV & V : 26000 : 7.5

TAF-3 : Tower - 31 A : 26000 : 7.5

Note : Lift well Pressurization fan shall be for outdoor application & provided with cannopy of material similar to casing.

AIR DISTRIBUTION

Supply, installation and testing of Factory fabricated GI sheet metal ducts as per SMACNA in accordance with the approved shop drawings and as required by the specifications.

a

80.0

81.0

82.0

24 gauge galvanised sheet steel

Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resin sleeve as per the approved shop drawings.

Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air

Grilles with volume control dampers in accordance with the approved shop drawings and specifications.

Supply, installation, testing and balancing of powder coated extruded aluminium Air Grilles without volume control dampers.

Supply, installation, testing and commissioning of motorized volume control ON /OFF type dampers of extruded aluminium construction in fresh air/return air/exhaust air steams. The damper actuator must accept signal from BMS system. Maximum leakage rate from dampers shall be in accordance with AMCA standard 500 . Quoted price shall also be included control wiring of damper.

Motarised Damper a b Control Panel & Wiring(with actuators)

83 CONTROL PANELS FOR FANS ( TUBE AXIAL FLOW FANS)

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MPCB and copper earthing, in each panel shall be provided by the electrical contractor.

The panel shall include the following components & accessories .

a. MCB / MCCB with built-in overload relay and single phase preventor as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Terminal block for power distribution as required.

c. Contactor, over load relay with built in single phasing protection.

d. Phase indicating lights and indicating light for `ON’ status.

e. 96 mm x 96 mm voltmeter and ammeter.

f. Time delay relay for delayed automatic restart of motor (0-180 sec).

g. The Control panel shall be out door type and shall have potential free contacts for fire alarm integration.

Each 1.00

Each 1.00

Each 1.00

Sqm

Sqm

Sqm

Sqm

150.00

7.00

4.00

Sqm 4.00

Each 3.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit Quantity a

84 a

85 a h. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation.

The number of control panels shall be as follows.

MPCB with DOL starters suitable for 1-7.5 HP motors

CABLES, MAINS AND SUB MAINS

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor un-armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

4 Core 6 Sq.mm

END TERMINATION OF CABLES

Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

4 Core 6 Sq.mm. (Copper Unarmoured Cable)

TOTAL OF SUB HEAD (A)

Each metre 30.00

No.

3.00

6.00

SUB HEAD (B):ELECTRICAL HIGH END -UTILITY-1

SUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF SUB-STATION EQUIPMENT

86 Main 11 kV HT Panel

Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site and supervising the testing & commissioning of 11 kV, 50 Hz 3 phase, 630 Amps indoor drawout type switchboard with 18.4 kA VCB circuit breaker as per specifications with following:

Rate in figures

(Rs.)

Incomer one number consisting of

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A.

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

24 V DC closing coil.

Spring charging motor.

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with inbuilt selector switch.

Digital electronic Voltmeter with inbuilt selector switch.

Digital Frequency Meter with inbuilt selector switch.

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

2 over current & Earth Fault IDMT relay with high set element range 500 – 2000%

3 No. Cast resin CTs of dual ratio 100-200 / 5 Amps CL:1, 5P10, 15 VA.

3 No. Cast resin drawout type PTs 11 kV / √ 3 / 110 √ 3, class 1, 100 VA.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as incoming.

Outgoing two number consisting of:

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

24 V DC closing coil.

Spring charging motor

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with selector switch.

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

2 over current IDMT relay with high set element range 500 – 2000%

3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps CL:1, 5P10, 15 VA.

3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps, 5P10, 15 VA.

12 window alarm annunciator with windows and buzzer, ACK, rest, test push button for each transformer faults and electrical faults in each outgoing panel.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as outgoing.

Main HT Panel described as above

87 11 kV HT Panel

Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site and supervising the testing & commissioning of 11 kV, 50 Hz 3 phase, 630 Amps indoor drawout type switchboard with 18.4 kA VCB circuit breaker as per specifications with following:

Incomer one number consisting of

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A.

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

24 V DC closing coil.

Spring charging motor.

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with inbuilt selector switch.

Digital electronic Voltmeter with inbuilt selector switch.

Digital Frequency Meter with inbuilt selector switch.

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

2 over current & Earth Fault IDMT relay with instantaneous high set element range 500 – 2000%

3 No. Cast resin CTs of dual ratio 100-200 / 5 Amps CL:1, 5P10, 15 VA.

3 No. Cast resin drawout type PTs 11 kV / √ 3 / 110 √ 3, class 1, 100 VA.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as incoming.

Outgoing two number consisting of:

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

24 V DC closing coil.

Spring charging motor

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with selector switch.

Unit

Set

Quantity

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

88

89 a

90

Description of Item Unit Quantity

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

Tripping relay for each type of transformer fault.

Restricted Earth Fault ( CAG - 14 ) relay with CT's.C877

2 over current IDMT relay with instantaneous high set element range 50 – 2000%

3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps CL:1, 5P10, 15 VA.

3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps, 5P10, 15 VA.

12 window alarm annunciator with windows and buzzer, ACK, rest, test push button for each transformer faults and electrical faults in each outgoing panel.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as outgoing.

Main HT Panel described as above

Set 1.00

Supply, installation, testing and commissioning of 1600 kVA 3 phase, 11/ 0.433 kV indoor dry type Transformer copper wound with Dyn 11 connection and neutral brought out for earthing.

The transformer shall be provided with +5 and -10 % On load tap changer on HT side. HT side cable termination box shall be suitable for 11 KV, 3 C x 300 mm 2 XLPE cable and LT side terminal box shall be suitable for termination of 2500 Amps TPN Al. Bus Duct. The transformer shall be supplied with all standard fitting viz thermistors for Alarm and Trip, winding temperature relay unit with Alarm and trip, lifting lugs, earthing studs and marshlling box, etc. complete in all respect as required as per specification.

HT & LT CABLES

Supply, Laying in Open Duct/ Trench and Testing of following sizes of XLPE insulated PVC sheathed aluminium conductor armoured power cable of 11 kV grade (11 kV earthed system).

Set 2.00

3 Core 300 Sq.mm.

Supplying of following 1100 volt grade XLPE insulated PVC inner sheathed and HR PVC outer sheathed aluminium conductor armoured cables as required as per specifications.

metre 800.00

Rate in figures

(Rs.) c d a b e c d e a b f

91

3.5 core 400 sq.mm

3.5 core 300 sq.mm

3.5 core 240 sq.mm

3.5 core 150 sq.mm

3.5 core 70 sq.mm

4 core 25 sq. mm

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

3 core 4 sq. mm

3 core 6 sq. mm

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable metre 530.00 metre 1,144.00 metre 200.00 metre 440.00 metre 110.00 metre 715.00 metre 250.00 metre 250.00 metre 100.00 metre 100.00 metre 100.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

92 a b c d e

93

Description of Item Unit Quantity

Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc.

complete as required.

3 core 4 sq. mm

3 core 6 sq. mm

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable

MAIN LT PANEL CUM CHANGEOVER PANEL

Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Main

LT Panel cum DG Sysnchronizing panel fabricated out of 14 gauge CRCA sheet steel in cubicle compartmentised free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel `T’ section and/ or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panel as per site requirement.Panel shall be treated with all anticorrosive process before powder coating as per specification and final approved shade. 2 No. earthing terminals shall be provided for the panel.

Panel shall be suitable for 433 V, 3 phase, 4 wire, 50 HZ supply system, with extensible busbars on both sides, making suitable electrical/ mechanical interlocking arrangement between incomers & buscoupler breakers, interconnection, duly powder coated painting etc. including supply & installation of following switchgears, metering instruments and accessories as per specifications. (All breakers breaking capacity shall be 50 kA. ICU = ICS). Lifting hooks shall also be provided in the panel). metre 6.00 metre 6.00 each 4.00 each 4.00 each 4.00

Approval shall be taken for the panel in the fometre of shop drawings before fabrication.

Galvanised hardwares with zinc passivation shall be used in fabrication of panel.

Rate in figures

(Rs.)

Section - I

INCOMER - 1 (1600 kVA Transformer)

Incoming for 1 each 1600 kVA Transformer comprises the following and as per single line diagram.

2500 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 2500/5 amps 15VA CTs.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

1 each 2500/1250/ 5, 15 VA dual ratio CT’s shall be provided for APFCR on transformer incomer.

INCOMER - 2 (DG Syn Panel)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

2500 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit , for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Electronic Load manager meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 2500/5 amps 15VA CTs.

VAF digital electronic meter with inbuilt selector switch and 2500/5 Amps suitable VA, CL 1 CTs .

- 1 Set

Phase indicating light shall be protected by 2 Amps MCB - 3 Set

Breaker ON / OFF / TRIP indicating lights with control MCB’s - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

BUSBARS

3200 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING

1000 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting - 2 each

1600 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 1600/5 Amps suitable VA, CL 1 CT - 1 each

1250 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 1250/5 Amps suitable VA, CL 1 CT - 1 each

250 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 250/5 Amps suitable VA, CL 1 CT - 1 each

100 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 100/5 Amps suitable VA, CL 1 CT - 3 each

63 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with

RS 485 port) with 60/5 Amps suitable VA, CL 1 CT - 1 each

Bus Coupler (1 ACB) shall be equipped with the following:

2500A, 4 poles electrically draw out type motor operated air circuit breaker with microprocessor release unit (Type 2A of MG make or equivalent).

24V D C shunt coil.

415 under voltage release.

1 each 230 V A.C closing coil.

Breaker control switch.

On/ Off/ Trip indicating lamps.

Spring charged indication.

Section - II

INCOMER - 1 (1600 kVA Transformer)

Incoming for 1 each 1600 kVA Transformer comprises the following and as per single line diagram.

Unit Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

2500 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 2500/5 amps 15VA CTs.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

1 each 2500/1250/ 5, 15 VA dual ratio CT’s shall be provided for APFCR on transformer incomer.

Unit

INCOMER - 2 (DG Syn Panel)

2500 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit , for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Electronic Load manager meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 2500/5 amps 15VA CTs.

VAF digital electronic meter with inbuilt selector switch and 2500/5 Amps suitable VA, CL 1 CTs .

- 1 Set

Phase indicating light shall be protected by 2 Amps MCB - 3 Set

Breaker ON / OFF / TRIP indicating lights with control MCB’s - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

BUSBARS:

3200 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING:

1000 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting - 1 each

1000 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 1000/5 Amps suitable VA, CL 1 CT - 2 each

1250 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 1250/5 Amps suitable VA, CL 1 CT - 1 each

Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

800 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 800/5 Amps suitable VA, CL 1 CT - 1 each

Unit Quantity

250 amps TPN Electrically Operated Manually draw out type Air Circuit Breaker (Icu = Ics) with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting including dual electronic energy meter (EM

6438 or equivalent with RS 485 port) with 800/5 Amps suitable VA, CL 1 CT - 4 each

94

95

63 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with

RS 485 port) with 60/5 Amps suitable VA, CL 1 CT - 1 each

Main LT Panel cum Changeover Panel as described above.

FEEDER PILLAR (Outdoor type)

Incoming

1 each 125 Amps TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microproccessor based release for short circuit, over current, earth fault protection with adjustable setting, ON/

OFF/ Trip indication lamp including control MCB's with fuse and following accessories as per specifications & SLD:

VAF digital electronic meter with inbuilt selector switch and 125/ 5 Amps 15 VA, CL 1 CTs . -1

Set

Phase indicating light shall be protected by 2 Amps SP MCB's - 3 Set

Bus Bars

200 Amps TPN Aluminium bars with heat coloured shrinkable insulation sleeve - 1 Set

Outgoing

63 Amps TPN MCCB complete with all accessories including wiring etc. as required as per single line diagram - 2 set

63Amps 4P MCB - 2 each

Spare

63Amps 4P MCB - 1 each

63Amps TPN MCB - 2 each

Notes: i. All MCCB's shall be of 25 kA (Ics) breaking capacity.

ii. All MCB's shall be of 10 kA breaking capacity.

Feeder Fillar as described above

400 KVAR CAPACITOR AUTOMATIC CONTROL PANEL

INCOMING

1000 amps TPN manually operated fully drawout type air circuit breaker as per specification and with following accessories:

96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch

Phase indicating light shall be protected by 2 Amps SP MCB’s - 3 Set

Power factor compensating relay (including power factor meter) in 11 steps for automatic cut off or add on capacitor units to keep the power factor at 0.97 with variation of loads. All associated auxiliary contactors/ relays/ timer/ auto manual selector switches to be provided - 1 Set.

each

Set.

1.00

1.00

BUS BARS:

1250 amps TPN Aluminium bus bars with coloured heat Shrinkable insulated sleeves. - 1 set

OUTGOING - I:

Outgoing feeders consisting of following accessories.

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

96

97

98

99

Description of Item

125 amps TPN MCCB - 5 Set

125 amps or capacitor duty 525 volts 50Hz contactors. - 5 Sets

“ON” /”OFF” push buttons and indicating lamps. - 5 Sets

50 KVAR, 525 volts capacitor unit with detune filters as specified - 5 Sets

OUTGOING - II:

Outgoing feeders consisting of following accessories.

80 amps TPN MCCB - 6 Set

80 amps or capacitor duty 525 volts 50Hz contactors. - 6 Sets

“ON” /”OFF” push buttons and indicating lamps. - 6 Sets

25 KVAR, 525 volts capacitor unit with detune filters as specified - 6 Sets

Note:

All MCCB’s shall be of 50 KA breaking capacity.

Fast response time of ‘ON’ capacitors 40-60 miliseconds.

Necessary control and firing card with proper wiring and lugs of the required rating to be provided.

Heavy duty exhaust fans to be provided for cooling Thyristors.

LED indication for number of capacitor banks ‘ON’.

LED indication of Power Factor lagging or leading.

The APFC system shall be provided with following :

Protections : a. Over voltage.

b. Voltage imbalance.

c. Over temperature-system should be in standby mode & automatically restart after above condition restored.

d. Earth leakage.

e. 7% value reactors with iron core.

Capacitor automatic control panel (400 kVAr) as described above.

BATTERY & BATTERY CHARGER

Supply, Installation, Testing and Commissioning of 1 (One) number 24 V Battery Charger & 2

(Two) numbers of 12V 200 AH maintenance free sealed lead acid batteries, Battery Charger shall be solid state, full wave fully controlled bridge, input suitable for single phase 230V AC suppply, conforming to degree of protection IP-42, Sheet steel enclosure 2 mm thick with automatic voltage regulation, current limiting circuitary, auto cut facility, smooth filter circuit switches, Ammeter & voltmeter on DC side, phase indicating lamps (LED type) on AC side complete in all respect with float and boost/ buck charging, switchgear, earthing, powder coated painting etc as required.

Supplying of Rubber hand gloves suitable for 11 kV.

Supplying and fixing of Shock treatment chart both in Hindi & English.

Supply and fixing Carbon dioxide fire extinguishers of 4.5 kg capacity each as per IS : 2878-

1976 and mounting the same on wall by means of suitable hooks.

Unit each

Job

Pair each each

100 Supply and fixing Dry Chemical fire extinguishers 5 kg as per IS : 2171-1976.

101 Supply and fixing of 9 ltr mechanical foam type fire extinguisher

102

Supply and fixing 5No.Fire buckets 9 litre capacity filled with dry sand and fixed MS structure, made out of 40x6mm angle and hange with bracket .

103

Supply of First aid box containing material as prescribed by St. John Ambulance brigade OR

Indian Red Cross complete as required.

each each each each

Quantity

2.00

1.00

2.00

4.00

4.00

2.00

2.00

1.00

2.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit Quantity

104

Supply & fixing of fire retardant/ extinguishing Electrical Insulated synthetic mat of 3.0 mm thick

+/- 10% conforming to latest BIS: DOC NO. ET-02 (5440) meeting requirements of IS 3043, IS

5216 (part-1, 2&3), IS 8437 and IEC 479, suitable for all voltages up to & including 33 kV AC and having minimum width of 1000 mm +/- 20 mm and including supply of required quantity of adhensive / compound and fixing the same at site as per site requirement.

metre 10.00

Rate in figures

(Rs.)

105

106

Supply & fixing of fire retardant / extinguishing Electrical Insulated synthetic mat of 2.0 mm thick + 10% conforming to latest BIS: DOC NO. ET-02 (5440) meeting requirements of IS 3043,

IS 5216 (part-1, 2&3), IS 8437 and IEC 479, suitable for all voltages not exceeding 3.3 kV AC and 220 V DC supply and having minimum width of 1000 mm +/- 20 mm and including supply of required quantity of adhensive / compound and fixing the same at site as per site requirement.

Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete including fixing the same on wall. metre 25.00

Job 2.00 b c d

107 a

108

109

110

111

112

BUS DUCT (IN SANDWICH CONSTRUCTION)

Supply, installation, testing and commissioning of following rating (50 KA for 1 Sec) TPN busduct in sandwich construction of aluminium bus bars with expansion joints, fire barriers including necessary supports and louvers for ventilation, fabricated out of extruded aluminium/

GI sheet painted with approved paint shade as per specification including 2 No. of 50 x 6 mm copper earthing conductor through out the length of the bus duct. (Phase sequence shall be matched).

Note: Degree of protection for outdoor bus duct shall be IP 55 as per IS:13947-1993.

2500 amps TPN bus ducts from Transformer - 1 toLT Cum DG & Tr. Changeover panel including

90 deg bends.

2500 amps TPN bus ducts from Transformer - 2 to LT Cum DG & Tr. Changeover panel including

90 deg bends.

2500 Amps TPN tinned copper flexible braided end connection on Transformer.

2500 Amps TPN tinned copper flexible braided end connection on LT Cum DG & Tr Changeover

Panel.

SUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF EXTERNAL LIGHTING

FIXTURES.

1 X 28W Solar street Light (Philips BRP 402)Fixture with lamp, accessories including MS

Galvanized Tubular Pole 6 meter of Pole icluding panels,battery with all accessories etc as approved by Architect.

1 X 43W Solar street Light (Philips BRP 403)Fixture with lamp, accessories including MS

Galvanized Tubular Pole 6 meter of Pole icluding panels,battery with all accessories etc as approved by Architect.

1 x 102.6 W Street Light fixture (Philips RoadStar GPLS 90W 49WLED 4K LEH2)with lamp, accessories etc as approved by Architect.

1 X 44W Street Light (Philips RoadStar & 40W49LED) Fixture with lamp, accessories etc as approved by Architect.

Poles

8.5 meter high aluminium painted MS pole with 300mmx300mmx5mm thick base plate and cap welded at bottom complete as required with painting of approved colour including erection of

G.I. pole (410-SP 20 as per IS:2713/80)with single arm (7.5 meter above and 1.5 meter)in

1:2:4 cement concrete (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal size) including excavation & refilling etc as required below ground complete as per requirement with all accessories.

metre 10.00 metre 16.00 each 2.00 each 2.00 each each each each each

18.00

15.00

62.00

45.00

52.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

113

Supply of 8.5 metre, surface mounting, swaged, galvanized pole, as per IS: 1239 (Part-1) -

1979 / IS 3601: 1994, with double arm (Metalcoats Make : Swan) bracket, suitable for mounting pendent (hanging) type street lighting cut-off luminaire. The pole shall consists of five sections, made of circular tubes of diameter 165.1 x 3.5mm thick at the bottom section, diameter 139.7 x

3mm thick at the second section, diameter 114.3 x 3mm thick at the third section, diameter

88.9 x 2.5mm thick at the fourth section. Bracket shall be made of circular tubes of diameter

76.1 x 2.5mm thick with overhang length of 1200mm on each side, luminaire mounting tube is internally threaded of designation FP-1. Bracket assembly is secured on to the pole top with allen grub screws. The pole is provided with built-in control box including service door with lock and safety chain, control gear tray prewired with heavy duty 3 phase, 15Amp terminal block for loop-in loop-out arrangement, 10A SP MCB including all accessories complete as required. Base plate of size 300 x 300 x 16 mm (steel of grade Fe - 410 to IS 2062: 1999) having elongated holes for alignment of the pole, welded at the bottom of the pole, 4Nos of M20 x 700mm foundation bolts hot dip galvanized is provided. The pole is coated with epoxy zinc rich primer and finished with polyurethane based black colour paint, ensuring total thickness of 80 microns.

(Metalcoats Make : MC-8269* - Swan Lighting Pole)

Unit each

Quantity

10.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

114

4.5 meter high Aluminium Painted MS pole with 300mmx300mmx5mm thick base plate and cap welded at bottom complete as required including erection of G.I. pole with B class MS pipe (3.6

meter above and 0.9 meter )in 1:2:4 cement concrete (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal size) including excavation & refilling etc as required below ground complete as per requirement with all accessories.

115

Providing, installation of 200 x 150 x 125 mm polycarbonate weather proof (IP-55) junction box and SP MCB’s and terminal block. Supplying and laying cable through GI pipe upto junction box including excavation and back filling, wiring with 2 x 2.5 sq.mm PVC insulated 1100 volts grade copper conductor wires from junction box to lighting fixture complete. each each

45.00

107.00 a b c

116

117

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

3 C x 2.5 Sq. mm

3 C x 4 Sq. mm

3 C x 6 sq.mm

Making end termination of following size PVC insulated copper conductor 1100 V grade armored cable including cost of crimping lugs, insulation tapes, double compression glands etc. complete.

meter 1,125.00 meter 1,800.00 meter 1,200.00

118

3C x 2.5 Sq. mm.

3C x 4 Sq. mm.

3C x 6 Sq.mm

EARTHING INSTALLATION (SUB STATION)

Supply, Testing & Commissioning, fixing of following bare GI tapes/ wires including all necessary fixing accessories and effecting connections as per specifications.

a b

50 x 5 mm thick GI. tape.

50 x 5 mm thick Cu. tape.

SOLAR SYSTEM EQUIPMENT each each each

80.00

100.00

30.00 metre 275.00 metre 585.00

Item

No

Description of Item

119

Supplying installation,testing and commissioning of 15 kWP Solar Photovoltaic system including

PV Modules, module mounting aluminium super structure supported on MS support, string

PCUs,DC DBs arry junction box,main junction boxs, AC DBs with associated copper power cable and control cabling from SPV panel upto ACDB including all accessories as per specification complete in all respect as per site requirement.

TOTAL OF SUB HEAD (B)

120

SUB HEAD (C) ELECTRICAL HIGH END-UTILITY-2

11 kV HT Panel

Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site and supervising the testing & commissioning of 11 kV, 50 Hz 3 phase, 630 Amps indoor drawout type switchboard with 18.4 kA VCB circuit breaker as per specifications with following:

Unit

Set

Quantity

1.00

Rate in figures

(Rs.)

Incomer two number consisting of

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A.

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

24 V DC closing coil.

Spring charging motor.

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with inbuilt selector switch.

Digital electronic Voltmeter with inbuilt selector switch.

Digital Frequency Meter with inbuilt selector switch.

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

2 over current & Earth Fault IDMT relay with high set element range 500 – 2000%

3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps CL:1, 5P10, 15 VA.

3 No. Cast resin drawout type PTs 11 kV / √ 3 / 110 √ 3, class 1, 100 VA.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as incoming.

Outgoing two number consisting of:

MS sheet enclosed cubicle type panel with main bus rated for 630 A and droppers rated for 630

A

630 Amps electrically operated trip free type vacuum circuit breaker at 50 deg.C ambient.

Breaker control switch.

24 V DC tripping coil.

24 V DC closing coil.

Spring charging motor

Set of ON/OFF/TRIP indicating lamps.

Set of Phase indicating lamps.

Clear lamp for trip circuit health supply.

Digital ammeter with selector switch.

Aux. relays for Anti Pumping & indication.

Trip circuit supervision and lock out relay.

Tripping relay for each type of transformer fault.

Restricted Earth Fault ( CAG - 14 ) relay with CT's.

2 over current IDMT relay with instantaneous high set element range 50 – 2000%

3 No. Cast resin CTs of dual ratio 20-40 / 5 Amps CL:1, 5P10, 15 VA.

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

12 window alarm annunciator with windows and buzzer, ACK, rest, test push button for each transformer faults and electrical faults in each outgoing panel.

Suitable space for termination of 1 No. 11 kV, 3 C x 300 sq.mm XLPE cable as outgoing.

121

Main HT Panel described as above

Supply, installation, testing and commissioning of 630 kVA 3 phase, 11/ 0.433 kV indoor dry type Transformer copper wound with Dyn 11 connection and neutral brought out for earthing.

The transformer shall be provided with +5 and -10 % On load tap changer on HT side. HT side cable termination box shall be suitable for 11 KV, 3 C x 300 sqmm XLPE cable and LT side terminal box shall be suitable for termination of 1000 Amps TPN Al. Bus Duct. The transformer shall be supplied with all standard fitting viz thermistors for Alarm and Trip, winding temperature relay unit with Alarm and trip, lifting lugs, earthing studs and marshlling box, etc. complete in all respect as required as per specification.

Unit

Set

Set

Quantity

1.00

2.00

Rate in figures

(Rs.) c d e a b f g

122 a

123

124 a b c

125 a b c

126

HT & LT CABLES

Supply, Laying in Open Duct/ Trench and Testing of following sizes of XLPE insulated PVC sheathed aluminium conductor armoured power cable of 11 kV grade as per IS 7098 and as required as per specifications.

3 Core 300 Sq.mm.

SUPPLY OF 1.1 kV GRADE LT CABLE

Supplying of following 1100 volt grade XLPE insulated PVC inner sheathed and HR PVC outer sheathed aluminium conductor armoured cables as per IS: 7098 and as required as per specifications.

3.5 core 400 sq.mm

3.5 core 300 sq.mm

3.5 core 240 sq.mm

3.5 core 150 sq.mm

3.5 core 70 sq.mm

4 core 25 sq. mm

3.5 core 35 sq. mm

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor ametreoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable

L.T. POWER CABLE END TERMINATION

Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc.

complete as required.

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable

MAIN LT PANEL CUM CHANGEOVER PANEL metre metre metre metre metre metre metre metre metre metre metre each each each

352.00

902.00

210.00

190.00

132.00

310.00

300.00

100.00

100.00

100.00

4.00

4.00

4.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Main

LT Panel cum DG Sysnchronizing panel fabricated out of 14 gauge CRCA sheet steel in cubicle compartmentised free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel `T’ section and/ or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panel as per site requirement. Panel shall be treated with all anticorrosive process before powder coating as per specification and final approved shade. 2 No. earthing terminals shall be provided for the panel.

Panel shall be suitable for 433 V, 3 phase, 4 wire, 50 HZ supply system, with extensible busbars on both sides, making suitable electrical/ mechanical interlocking arrangement between incomers & buscoupler breakers, interconnection, duly powder coated painting etc. including supply & installation of following switchgears, metering instruments and accessories as per specifications. (All breakers breaking capacity shall be 50 kA. ICU = ICS). Lifting hooks shall also be provided in the panel.

Unit

Approval shall be taken for the panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panel.

Section - I

INCOMER - 1 (630 kVA Transformer)

Incoming for 1 No. 630 kVA Transformer comprises the following and as per single line diagram.

1000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 1000/5 amps 15VA CTs.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

1 No. 1000/ 5, 15 VA dual ratio CT’s shall be provided for APFCR on transformer incomer.

BUSBARS

1250 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting- 1 No.

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 400/5 Amps suitable VA, CL 1 CT - 2 No.

630 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 600/5 Amps suitable VA, CL 1 CT - 1 No.

Bus Coupler (1 ACB) shall be equipped with the following:

Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

1000A, 4 poles electrically draw out type motor operated air circuit breaker with microprocessor release unit (Type 2A of MG make or equivalent).

24V D C shunt coil.

415 under voltage release.

1 No. 230 V A.C closing coil.

Breaker control switch.

On/ Off/ Trip indicating lamps.

Spring charged indication.

Section - II

INCOMER - II (630 kVA Transformer)

Incoming for 1 No. 630 kVA Transformer comprises the following and as per single line diagram.

1000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 1000/5 amps 15VA CTs.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

1 No. 1000/5, 15 VA dual ratio CT’s shall be provided for APFCR on transformer incomer.

BUSBARS:

1250 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING:

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting- 1 No.

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 400/5 Amps suitable VA, CL 1 CT - 2 No.

250 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 600/5 Amps suitable VA, CL 1 CT - 1 No.

Main LT Panel cum Changeover Panel as described above.

127 MAIN EMERGENCY PANEL

Section - I

INCOMER - 1 (LT CUM DG CHANGEOVER PANEL)

800 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 800/5 amps 15VA CTs.

Unit each

Quantity

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

INCOMER - II (500 kVA DG Set)

Incoming for 1 No. 500 kVA DG set comprises the following and as per single line diagram.

800 amps 4 Pole electrically operated Manually drawout type air circuit breaker as per specification and with following accessories.

Control wiring from Synchronizing module (PCCM - 3100 or equivalent) at alternator.

Electronic type energy meter (EM-6400 or equivalent with RS-485) of accuracy class 1.0 with 3

Nos. 5 amps secondary CTs

Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.

3 Nos. phase indicating lights with control MCB’s.

Excitor field DC voltmeter and ammeter.

Breaker control switch.

Engine cranking relay.

24 V DC shunt trip.

Emergency stop push button.

Selector switch for Auto / Manual / Test

Selector switch for engine control OFF/ON.

Five push buttons – start, stop, reset, test and accept.

Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.

12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.

Temperature scanner (Messi Bus/Procon)

Phase sequence relay (46 )

BUSBARS

1000 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING

630 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 600/5 Amps suitable VA, CL 1 CT - 1 No.

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 400/5 Amps suitable VA, CL 1 CT - 2 No.

200 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 200/5 Amps suitable VA, CL 1 CT - 1 No.

100 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 100/5 Amps suitable VA, CL 1 CT - 1 No.

Bus Coupler (1 ACB) shall be equipped with the following:

Unit Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

800A, 4 poles electrically draw out type motor operated air circuit breaker with microprocessor release unit (Type 2A of MG make or equivalent).

24V D C shunt coil.

415 under voltage release.

1 No. 230 V A.C closing coil.

Breaker control switch.

On/ Off/ Trip indicating lamps.

Spring charged indication.

Section - II

INCOMER - III (LT CUM DG CHANGEOVER PANEL)

800 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unit (Type 6A of MG make or equivalent), for short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :

Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3

Nos. 800/5 amps 15VA CTs.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Set

Three Phase Under voltage relay MV12 or equivalnt (27) - 1 Set

Three Phase Over voltage relay MV 12 or equivalent (59) - 1 Set

Breaker ON/ OFF/ TRIP indicating lights with control MCB’s. - 1 Set

24 V DC Shunt trip coil. - 1 Set

240 V AC under voltage release. - 1 Set

Auto-manual / test selector / switch - 1 Set

Breaker control switch - 1 Set

Auxiliary contacts required for necessary interlocking of breakers.

Three Phase Voltage sensor relay shall be protected by 2 amps TP MCB’s. - 1 Set

Transient voltage surge supressor with suitable contactor shall be protected by 2 amps TP

MCB’s. - 1 Set

INCOMER - IV (500 kVA DG Set)

Incoming for 1 No. 500 kVA DG set comprises the following and as per single line diagram.

800 amps 4 Pole electrically operated Manually drawout type air circuit breaker as per specification and with following accessories.

Control wiring from Synchronizing module (PCCM - 3100 or equivalent) at alternator.

Electronic type energy meter (EM-6400 or equivalent with RS-485) of accuracy class 1.0 with 3

Nos. 5 amps secondary CTs

Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.

3 Nos. phase indicating lights with control MCB’s.

Excitor field DC voltmeter and ammeter.

Breaker control switch.

Engine cranking relay.

24 V DC shunt trip.

Emergency stop push button.

Selector switch for Auto / Manual / Test

Selector switch for engine control OFF/ON.

Five push buttons – start, stop, reset, test and accept.

Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.

12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.

Temperature scanner (Messi Bus/Procon)

Phase sequence relay (46 )

BUSBARS

1000 Amp TPN busbars of high conductivity electrolytic quality aluminium alloy as per specification.

OUTGOING

Unit Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

128

129

Description of Item

630 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 600/5 Amps suitable VA, CL 1 CT - 1 No.

400 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 400/5 Amps suitable VA, CL 1 CT - 2 No.

250 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 250/5 Amps suitable VA, CL 1 CT - 1 No.

100 Amp TPN Moulded Case Circuit Breaker (Icu = Ics) with built in microprocessor based release unit with adjustable setting including dual electronic energy meter (EM 6438 or equivalent with RS 485 port) with 100/5 Amps suitable VA, CL 1 CT - 2 No.

Main Emergency Panel as described above.

FEEDER PILLARS

Design, Manufacturing, Supply, installation, testing and commissioning of cubicle type totally enclosed free standing, dust free, damp and vermin proof and water proof outdoor (IP 54)

Feeder pillar fabricated out of 2mm thick CRCA sheet duly powder coated and including supply & fixing the following items and interconnections, wiring with suitable size wires/cables and including all civil works like excavation, PCC, brick work pedestal, plastering, refilling etc. and as per specifications as required.

FEEDER PILLAR NO. 1 & 2 (EXTERNAL LIGHTING)

Feeder Pillars for external lighting with IP-54

Incomer : 1 no. 63 A TPN MCCB with 100A 4P insulated AL busbars.

Out going : 24 Nos. 16/20 amps SP MCB as outgoing with 3 nos. 63 amps DP RCCB of 30 mA leakage current plus 1 No. 63 amps DP Contactor controlled through 0-24 hour timer.

Feeder Pillars described as above :

150 KVAR CAPACITOR AUTOMATIC CONTROL PANEL

INCOMING

400 amps TPN MCCB as per specification and with following accessories:

96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch

Phase indicating light shall be protected by 2 Amps SP MCB’s - 3 Set

Power factor compensating relay (including power factor meter) in 8 steps for automatic cut off or add on capacitor units to keep the power factor at 0.97 with variation of loads. All associated auxiliary contactors/ relays/ timer/ auto manual selector switches to be provided - 1 Set.

BUS BARS:

500 amps TPN Aluminium bus bars with coloured heat Shrinkable insulated sleeves. - 1 set

OUTGOING - I:

Outgoing feeders consisting of following accessories.

63 amps TPN MCCB - 4 Set

63 amps or capacitor duty 525 volts 50Hz contactors. - 4 Sets

“ON” /”OFF” push buttons and indicating lamps. - 4 Sets

25 KVAR, 525 volts capacitor unit with detune filters as specified - 4 Sets

OUTGOING - II:

Outgoing feeders consisting of following accessories.

40 amps TPN MCCB - 4 Set

40 amps or capacitor duty 525 volts 50Hz contactors. - 4 Sets

“ON” /”OFF” push buttons and indicating lamps. - 4 Sets

Unit each

Set

Quantity

1.00

2.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

12.5 KVAR, 525 volts capacitor unit with detune filters as specified - 4 Sets

Note:

All MCCB’s shall be of 50 KA breaking capacity.

Fast response time of ‘ON’ capacitors 40-60 miliseconds.

Necessary control and firing card with proper wiring and lugs of the required rating to be provided.

Heavy duty exhaust fans to be provided for cooling Thyristors.

LED indication for number of capacitor banks ‘ON’.

LED indication of Power Factor lagging or leading.

The APFC system shall be provided with following :

Protections : a. Over voltage.

b. Voltage imbalance.

c. Over temperature-system should be in standby mode & automatically restart after above condition restored.

d. Earth leakage.

e. 7% value reactors with iron core.

Capacitor automatic control panel (150 kVAr) as described above.

130

BATTERY & BATTERY CHARGER

Supply, Installation, Testing and Commissioning of 1 (One) number 24 V Battery Charger & 2

(Two) numbers of 12V 200 AH maintenance free sealed lead acid batteries, Battery Charger shall be solid state, full wave fully controlled bridge, input suitable for single phase 230V AC suppply, conforming to degree of protection IP-42, Sheet steel enclosure 2 mm thick with automatic voltage regulation, current limiting circuitary, auto cut facility, smooth filter circuit switches, Ammeter & voltmeter on DC side, phase indicating lamps (LED type) on AC side complete in all respect with float and boost/ buck charging, switchgear, earthing, powder coated painting etc as required.

Unit each

Job

Quantity

2.00

1.00

131 Supplying of Rubber hand gloves suitable for 11 kV.

132 Supplying and fixing of Shock treatment chart both in Hindi & English.

133

Supply and fixing Carbon dioxide fire extinguishers of 4.5 kg capacity each as per IS : 2878-

1976 and mounting the same on wall by means of suitable hooks.

134 Supply and fixing Dry Chemical fire extinguishers 5 kg as per IS : 2171-1976.

135 Supply and fixing of 9 ltr mechanical foam type fire extinguisher

136

Supply and fixing 5No.Fire buckets 9 litre capacity filled with dry sand and fixed MS structure, made out of 40x6mm angle and hange with bracket .

137

138

Supply of First aid box containing material as prescribed by St. John Ambulance brigade OR

Indian Red Cross complete as required.

Supply & fixing of fire retardant/ extinguishing Electrical Insulated synthetic mat of 3.0 mm thick

+/- 10% conforming to latest BIS: DOC NO. ET-02 (5440) meeting requirements of IS 3043, IS

5216 (part-1, 2&3), IS 8437 and IEC 479, suitable for all voltages up to & including 33 kV AC and having minimum width of 1000 mm +/- 20 mm and including supply of required quantity of adhensive / compound and fixing the same at site as per site requirement.

Pair each each each each each each

2.00

4.00

4.00

2.00

2.00

1.00

2.00 meter 10.00

Rate in figures

(Rs.)

139

Supply & fixing of fire retardant / extinguishing Electrical Insulated synthetic mat of 2.0 mm thick + 10% conforming to latest BIS: DOC NO. ET-02 (5440) meeting requirements of IS 3043,

IS 5216 (part-1, 2&3), IS 8437 and IEC 479, suitable for all voltages not exceeding 3.3 kV AC and 220 V DC supply and having minimum width of 1000 mm +/- 20 mm and including supply of required quantity of adhensive / compound and fixing the same at site as per site requirement.

meter 25.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

140

Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete including fixing the same on wall.

Unit

Job

Quantity

2.00

Rate in figures

(Rs.) e f c d

BUS DUCT (IN SANDWICH CONSTRUCTION)

141 Supply, installation, testing and commissioning of following rating (50 KA for 1 Sec) TPN busduct in sandwich construction of aluminium bus bars with expansion joints, fire barriers including necessary supports and louvers for ventilation, fabricated out of extruded aluminium/

GI sheet painted with approved paint shade as per specification including 2 No. of 50 x 6 mm copper earthing conductor through out the length of the bus duct. (Phase sequence shall be matched).

Note: Degree of protection for outdoor bus duct shall be IP 55 as per IS:13947-1993.

a b

1000 amps TPN bus ducts from Transformer - 1 toLT Cum DG & Tr. Changeover panel including

90 deg bends.

1000 amps TPN bus ducts from Transformer - 2 to LT Cum DG & Tr. Changeover panel including

90 deg bends.

800 amps TPN bus ducts from LT Cum DG & Tr Changeover Panel. to Emergency including 90 deg bends.

1000 Amps TPN tinned copper flexible braided end connection on Transformer.

1000 Amps TPN tinned copper flexible braided end connection on LT Cum DG & Tr Changeover

Panel.

800 Amps TPN tinned copper flexible braided end connection on Emergency Panel.

EARTHING INSTALLATION (SUB STATION) metre metre metre each each each

10.00

16.00

28.00

2.00

2.00

2.00 a b fixing accessories and effecting connections as per specifications.

50 x 5 mm thick GI. tape.

50 x 5 mm thick Cu. tape.

DG SETS FOR (UTILITY 1&2)

143 1010 kVA DG Set

Supply, installation, testing and commissioning of 1010 kVA prime rating diesel generating set in acoustic enclosure radiator cooled with with PMG, base frame, Alternator, Static Excitation

System, Lube Oil System, Electronic Governor, Batteries, Instrumentation, day oil fuel tank,

Residential Silencer with Bellows, Alarms, Engine Control Panel (PCC-3.3) AVM Pads, AVR Panel, a

Terminal Arrangements including cable termination box with all associated equipment/work as per specifications. Alternator shall have class H insulation and rated for 808 KW output at 47°C.

Emergency stop push button for individual DG set shall be located at the canopy door. Engine shall not be derated upto 50°C ambient. No deration in DG set capacity shall be accepted on this account.

144 500 kVA DG Set

Supply, installation, testing and commissioning of 500 kVA prime rating diesel generating set in acoustic enclosure radiator cooled with with PMG, base frame, Alternator, Static Excitation

System, Lube Oil System, Electronic Governor, Batteries, Instrumentation, day oil fuel tank,

Residential Silencer with Bellows, Alarms, Engine Control Panel (PCC-3.3 or equivalent) AVM a

Pads, AVR Panel, Terminal Arrangements including cable termination box with all associated equipment/work as per specifications. Alternator shall have class H insulation and rated for 400

KW output at 47°C. Emergency stop push button for individual DG set shall be located at the exit door. Engine shall not be derated upto 50°C ambient. No deration in DG set capacity shall be accepted on this account. Note: Piping between day oil tank & DG set shall be included.

metre 275.00 metre 585.00 each each

3.00

1.00

Rate in words(Rs.)

145 500 kVA DG Set

Amount (Rs.)

Item

No

Description of Item a

146

Dismenteling,shifting, testing, commissioning & reinstallation as per drawing of 500 kVA prime rating existing diesel generating set in acoustic enclosure with PMG, base frame, Alternator,

Static Excitation System, Lube Oil System, Electronic Governor, Batteries, Instrumentation, day oil fuel tank, Residential Silencer with Bellows, Alarms, Engine Control Panel AVM Pads, AVR

Panel, Terminal Arrangements including cable termination box with all associated equipment/work as per existing set complete as required.

Auto Starting, Auto/Manual Synchronizing , Auto load sharing and load managing panel and DG Auxiliary Panel

SECTION I

Incoming -1 for 1 No.1010 KVA DG sets each comprises the following and as per single line diagram.

1600 amps 4P electrically operated fully drawout type air circuit breaker as per specification and with following accessories.

Wiring for Engine Generator control package relay type EGCP - 32 of woodward/ PCC-3.3 of

Cummins or equivalent make at alternator with all accessories.

Each incomer feeder shall be equipped with following accessories.

Electronic type energy meter (EM-6400 or equivalent with RS-485 ) of accuracy class 1.0 with 3

Nos. 5 amps secondary CTs

Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.

3 Nos. phase indicating lights with control MCB’s.

Excitor field DC voltmeter and ammeter.

Breaker control switch.

Differential protection relay (87) (3 Nos. L & T SC14S ) with PS class CT’s on both side of alternator.

Master trip relay.

Trip circuit supervision relay.

Engine cranking relay.

24 V DC shunt trip.

Emergency stop push button.

Selector switch for Auto/ Manual/ Test.

Selector switch for engine control OFF/ ON.

Five push buttons – start, stop, reset, test and accept.

Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start.

12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.

Temperature scanner (Messi Bus/ Procon)

Bus Bar :

4000 A TPN electrolytic Aluminium bus bar with heat shrinkable insulation sleeve.

Outgoings

2500 amps TPN manually operated draw out type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting - 1 No.

Unit each

Bus Coupler

3200 amps 4P electrically operated fully drawout type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting - 1

No.

SECTION II

Incoming -2 for 1 No.1010 KVA DG sets each comprises the following and as per single line diagram.

1600 amps 4P electrically operated fully drawout type air circuit breaker as per specification and with following accessories.

Wiring for Engine Generator control package relay type EGCP - 32 of woodward/ PCC-3.3 of

Cummins or equivalent make at alternator with all accessories.

Each incomer feeder shall be equipped with following accessories.

Quantity

1.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item

Electronic type energy meter (EM-6400 or equivalent with RS-485 ) of accuracy class 1.0 with 3

Nos. 5 amps secondary CTs

Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.

3 Nos. phase indicating lights with control MCB’s.

Excitor field DC voltmeter and ammeter.

Breaker control switch.

Differential protection relay (87) (3 Nos. L & T SC14S ) with PS class CT’s on both side of alternator.

Master trip relay.

Trip circuit supervision relay.

Engine cranking relay.

24 V DC shunt trip.

Emergency stop push button.

Selector switch for Auto/ Manual/ Test.

Selector switch for engine control OFF/ ON.

Five push buttons – start, stop, reset, test and accept.

Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start.

12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.

Temperature scanner (Messi Bus/ Procon)

Incoming - 3 for 1 No.1010 KVA DG sets each comprises the following and as per single line diagram.

1600 amps 4P electrically operated fully drawout type air circuit breaker as per specification and with following accessories.

Wiring for Engine Generator control package relay type EGCP - 32 of woodward/ PCC-3.3 of

Cummins or equivalent make at alternator with all accessories.

Each incomer feeder shall be equipped with following accessories.

Electronic type energy meter (EM-6400 or equivalent with RS-485 ) of accuracy class 1.0 with 3

Nos. 5 amps secondary CTs

Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.

3 Nos. phase indicating lights with control MCB’s.

Excitor field DC voltmeter and ammeter.

Breaker control switch.

Differential protection relay (87) (3 Nos. L & T SC14S ) with PS class CT’s on both side of alternator.

Master trip relay.

Trip circuit supervision relay.

Engine cranking relay.

24 V DC shunt trip.

Emergency stop push button.

Selector switch for Auto/ Manual/ Test.

Selector switch for engine control OFF/ ON.

Five push buttons – start, stop, reset, test and accept.

Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start.

12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.

Temperature scanner (Messi Bus/ Procon)

Bus Bar :

4000 A TPN electrolytic Aluminium bus bar with heat shrinkable insulation sleeve.

Outgoings

2500 amps TPN manually operated draw out type air circuit breaker with microprocessor release unit for short circuit, over current and earth fault protection with adjustable setting - 1 No.

Note:

All outgoing feeders shall have suitable Digital ammeter with selector switch, CTs and phase indicating light protected by 2 amps MCBs.

Unit Quantity

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit

All breakers shall be electrically interlocked as per schematic diagram.

All ACB’s/MCCB’s shall be suitable for 50 KA breaking capacity.

PLC for load management and supervision and D.G. set auxilliary.

Auto starting / Auto synchronizing / Auto load balancing and auto load management panel for 3

No. DG Sets as described above (component A to I complete as per specification) Set

147

HSD SYSTEM FOR DG SETS

S.I.T.C.of 20 KL underground Bulk Storage Tank .Fabrication of 6 mm thick M.S. plate with bracing inside complete with all standard appurtenances/ mountings like manhole of 600 mm dia

& 450 mm dia cover duly hinged, access ladders, lifting lugs, earthing bolts etc. Plane ends of 8 mm thick M.S. sheet, fuel fill pipe 80 mm dia with locking arrangement, vent pipe, outlet pipe

Brass dip stick, with calibrater chart and two level indicators and controller. The tank shall be duly painted with two coats of tank mastic & two of coats of Tar Plastic paints outside of tank

Civil works, tanker, fencing and earthing area not considered.

No.

148

Fuel Transfer gear Pump coupled with single phase flame motor (Set of 2 pumps mounted on common base frame .

For Supply ii i ii

For Return

149 Fuel Piping i

80mm dia MS "C" class pipe

65mm dia MS "C" class pipe iii

50mm dia MS "C" class pipe iv

40mm dia MS "C" class pipe v

25mm dia MS "c" class pipe

150 Wire braided flexible hose 5 meter with brass end fitting

151 Ball Valve - Sant - Brass i

Ball Valve 80 mm ii

Ball Valve 50 mm iii

Ball Valve 40 mm iv

Ball Valve 25 mm

152 Foot Valve 50 mm

153 Pot Stainer 80 mm

154 Y strainer i

Y Strainer 50 mm ii

Y Strainer 40 mm

155 NRV 50mm

156 NRV 40mm

157 Flow Meter - Mechanical Type i

Flow meter 80 mm

158 Flot Valve 50 mm

159 Level Sensor

No.

No.

meter meter meter meter meter

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

Quantity

1.00

2

2

2

11

2

1

5

5

4

10

100

50

50

40

1

2

2

2

2

1

6

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

a b c d

Item

No

Description of Item i

Level Sensor for BMS (Buffer tank) ii

Level Sensor for BMS (Sump Tank)

160 Pressure Gauge with siphon and gauge cook

161 Day oil tank 990 liter

162 Buffer Tank 990 liter

163 Sump Tank 990 liter

164 MCC panel for Fuel system ( Outdoor type )

165

Safety equipment - Fire extinguisher, sand bucket etc. (Considereing 4 nos. 4.5 kg CO2 type fire

Extinguishers, 8 nos. sand Bucket with stand)

166 Statutory approval for Bulk Storage tank from Explosive Department

167

EXHAUST PIPE & CHIMNEY

Supply, installation, testing and commissioning of exhaust pipe fabricated out of 6 mm thick MS pipe class 'C' with all fixing accessories and hardwares. The exhaust pipes shall be insulated with 75 mm thick mineral wool insulation wrapped in chicken mesh and clad with 24 gauge aluminium sheet excluding all support as required.Above item shall be inclusive of all support including angels, channels, ISMC supports, fasteners, bends,including painting etc. as required as per specifications..(Only MS guide support along with wall/shaft considered)

168

Unit

Job

400 mm dia

250 mm dia

200 mm dia

125 mm dia

Supply and fixing of MS steel structure suitable for exhaust pipe fabricated out of 6 mm thick MS pipe. The structure shall be raised above 10 mtr. in height for fire clearance, self standing upto

30 mtr, paint with heat resistant paint with all support, climbing ladder, finials for lightning protection with GI tape and GI earthing station as required.

metre metre metre metre

Kg

No.

No.

No.

Set

No.

No.

No.

No.

Quantity

1

35

20

30

10

5,000.00

1

1

1

1

1

1

4

5

Rate in figures

(Rs.)

169

LT CABLES

Supplying of following 1100 volt grade XLPE insulated PVC inner sheathed and HR PVC outer sheathed aluminium conductor armoured cables as per specification as required as per specifications.

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit a b c a b c a

170

171

172

3.5 core 300 sq.mm

Supplying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable

L.T. POWER CABLE END TERMINATION

Cable end termination of the following PVC insulated sheathed PVC/XLPE aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with earthing facility at both ends of cables etc.

complete as required.

4 core 2.5 sq.mm control cable

7 core 2.5 sq.mm control cable

12 core 2.5 sq.mm control cable

BUS DUCT (IN SANDWICH CONSTRUCTION)

Supply, installation, testing and commissioning of following rating (50 KA for 1 Sec) TPN busduct in sandwich construction of aluminium bus bars with expansion joints, fire barriers including necessary supports and louvers for ventilation, fabricated out of extruded aluminium/

GI sheet painted with approved paint shade as per specification including 2 No. of 50 x 6 mm copper earthing conductor through out the length of the bus duct. (Phase sequence shall be matched).

Note: Degree of protection for outdoor bus duct shall be IP 55 as per IS:13947-1993.

metre metre metre metre each each each a b c

Quantity

2000

300

400

200

10

10

10

2500 amps TPN bus ducts from DG Sync. Panel to DG & Tr. Changeover panel including 90 deg bends.

2500 Amps TPN tinned copper flexible braided end connection on DG Syn Panel. metre 30.00 each 2.00

2500 Amps TPN tinned copper flexible braided end connection on LT Cum DG & Tr Changeover

Pnael.

EARTHING INSTALLATION (SUB STATION) each 2.00

Rate in figures

(Rs.) a fixing accessories and effecting connections as per specifications.

50 x 5 mm thick GI. tape.

metre 1,100.00 b

50 x 5 mm thick Cu. tape.

metre 660.00

TOTAL OF SUB HEAD (C)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item d e b c

174 a

175 a b

SUB HEAD (D):IBMS

CENTRAL CONTROL STATIONS

Supplying, Installing, Testing & Commissioning of the Central Control Stations consisting of the following :

BMS workstation 'Intel 5, 3.2 GHZ Processor

3 GB RAM, 320 GB hard disc

DVD Read & writer, compatible CDROM

Windows XP and shall have MS-Office installed

As per specification

32” LCD screen minimum

A4 laser printer Coloured

Cordless Mouse

Cordless Key board

SOFTWARE

Supply, installation, testing & commissioning of following Software for Building Management

System

Testing and commissioning of the Software for Building Automation System i (Minimum Three user on LAN to be consider)

Developing and commissioning of software interface with 85 No DEM / KWH/MFM/Trivector meters for two way flow of data between central control station and static power meters.The

price shall include the necessary integrator required for integration and also the networking of all load managers include network cabling.All necessary cabling (Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Unit

Lot

Lot

No.

No.

No.

No.

No.

Quantity

1.00

1.00

1.00

1.00

1.00

1.00

1.00

Rate in figures

(Rs.) c

Developing & commissioning of Software interface for 1 No. PLC panel hook up to 3 No.VFD for

Secondary Pump , 19 No for AHU, 6 CT VFD No. via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling. All necessary cabling (Communication / signal & power) from integrator

/ convertor to each equipment shall be included in the scope.

Lot d

Developing & commissioning of Software interface for 3 No. Chiller via communication bus.The

price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling (Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Lot

1.00

1.00

Rate in words(Rs.) e

Developing & commissioning of Software interface for 5 No. DG via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling (Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Lot 1.00 f

Developing & commissioning of Software interface with 9 No. UPS Panel via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling (Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Lot 1.00

Amount (Rs.)

Item

No g h j i

Description of Item

Developing & commissioning of Software interface for VAV integrator (150 VAV) via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling

(Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Developing & commissioning of Software interface with CCTV & Access system via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling

(Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Developing & commissioning of Software interface with 4 No. Water Meter Panel via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling

(Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope.

Developing & commissioning of Software interface with 5 No.PAC unit Panel via communication bus.The price shall include the necessary integrator / gateway required for integration and also the networking of all include network cabling.All necessary cabling (Communication / signal & power) from integrator / convertor to each equipment shall be included in the scope. The quoted price for above shall be inclusive of communication cable in 25 mm dia MS conduit between the

Equipment to Integrators /DDC Panel.

Unit

Lot

Lot

Lot

Lot

Quantity

1.00

1.00

1.00

1.00

Rate in figures

(Rs.)

CONTROLLERS

176 Supply, installation, testing & commissioning of the following: a

Stand alone Intelligent DDC Controllers as per the specifications for I O points. The contractor shall decide upon the number of contollers, depending on his Controller capacity. Expandable modules for Inputs/Outputs are not allowed.Contractor shall furnish quantity and unit rate for each type of controller considered by him. The above shall be housed in a vandal proof, lockable

& secure MS powder coated Cabinets to be supplied along with the Controllers.

b c

System Integration Units consisting of Gateways, Interface units as required The above shall be housed in a vandal proof, lockable & secure MS powder coated cabinets to be supplied along with the Controllers

Supply, installation, testing and commissioning of hand held portable operator terminals.(POT).

These shall be required if the Controllers and Integration Units do not have a built in keypad on the facia .

Lot

Lot

No.

1.00

1.00

1.00

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item iii iv i ii

SENSORS & FIELD DEVICES

177 Supply, installation, testing & commissioning of the following Sensors :

Resistance type immersion temperature sensors for measuring Chilled water, condenser water a supply and return temperature (Range 32-160 deg. F). The accuracy shall be at least ± 0.36

degrees F. The pressure rating shall be 10 kgf/sq cm .

b

Duct Temperature & RH Sensor shall be with rigid stem type. These shall be suitable for duct installation and accuracy shall be at least ± 0.36 degrees F.

c

Duct Mounted Temperature Type

Indoor Wall Mounted Type Temperature Sensor with Display

Duct Mounted Type Temp & RH Sensor

Wall Mounted Type Temp & RH Sensor with LCD display

Outside air temperature & humidity RH sensors for measuring outside air temperature (Range 35-

130 °F). The accuracy of temperature sensor shall be ± 0.36 degrees F and RH sensor is ± 3%.

It should be provided with sun sheild and rain protection.

Unit

No.

No.

No.

No.

No.

No.

d

Pressure transmitters for measuring pressure in water headers (0-16 Kg/sqm).Pressure

transmitters shall be piezo-electric type or diaphragm type.Output shall be 4-20mA or 0-10V

DC.Housing shall be weather proof with IP 65 protection.

Ultrasonic type inline type chiled water flow meter suitable for pipes (300 mm dia) e i1 i2 j l m n o o1 g h i f k

178

Differential pressure switches across the pumps for indicating the pumps status.The set point shall fall in 40-70% of the scale range and shall have differentials adjustable over 10%-30% of the scale range.

Differential pressure switches across the Air Handling Unit filters, for indicating the filter status.

Pressure differential – 2 mm to 15 mm. The switch shall be with connecting tube and metal bends for connections to the duct.

Differential pressure switches across the blowers for indicating blower status. Pressure differential – 10 mm – 125 mm. The switch shall be with connecting tube and metal bends for connections to the duct. The housing shall be IP 54 rated.

Level Switches for indicating Water level in water tanks. It should be of Single / Bi-Level Float

Type/Capacitance type/Conductity type of Stainless steal construction. Housing shall be IP 55 rated and output shall be 2 NO/NC

Single Level Switch

Bi- Level Switch

Level Transmitters for monitoring water level in UG Tanks.

Water Flow Switches shall be paddle type and suitable for the type of liquid flowing in the line. Output shall be 1 NO/ 1NC potential free as per specification

Flame Proof Level Transmitter

Flame proof Bi-level switch

Duct Static Pressure Transmitters

Electronic Water Meter (electromagnetic type) with Rs 485 communication port

<=65 mm dia

VALVES AND ACTUATORS

Supply,and commissioning of motorized ON / OFF butterfly valves (PN16): inclusive of actuators, wiring & power supply.The actuator should accept 4-20 mA or 0-10 V signal from IBMS system & give position fedback to it. IBMS Contractor to check size of Valves and actuator fitting details before installation of following line sizes

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

Quantity

9.00

36.00

6.00

19.00

1.00

1.00

1.00

1.00

17.00

124.00

62.00

6.00

8.00

8.00

7.00

1.00

11.00

19.00

4.00

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Item

No

Description of Item Unit Quantity a b

179

180

181

182

200 mm dia Valves.

No.

3.00

250 mm dia Valves.

No.

9.00

Supplying, installing, testing and commissioning of 2 x 1.0 mm signal / power cables UTP

Armoured as per specification. (per I/O points hard wired to DDC). More than two cables should not be saddled to wall /ceiling.

Supplying, installing, testing and commissioning of communication cables 2 C X 1.5 Sqmm STP

Armoured).

Supplying, installing, testing and commissioning of LAN cable cat 6 in 25 mm dia MS conduit

(complete with all accessories) as per manufacturers recommendation.

Supplying, installing, testing and commissioning of 2 mm thick GI perforated cable trays of the following sizes complete with angle iron supports/hanging arrangement etc.

Per I/O point

780.00 metre metre

9,360.00

50.00

Rate in figures

(Rs.) a

40 x 300 x 40 b

40 x 200 x 40 c

25 x 150 x 25

TOTAL OF SUB HEAD (D)

SUBHEAD(E)- LIFT/ELEVATOR

183 ELEVATOR :Design, manufacture, supply, installation, testing, commissioning and maintenance( each year maintenance price breakup as per Specification) of Machine Room Less

(MRL) Passenger Elevator / Lift as mentioned in relavant BOQ item and as per specificification.

1. Type of elevator: Passenger Elevator / Lift / Service Lift as mentioned in relavant BOQ item.

2. Load carrying capacity: As mentioned in relavant BOQ item

3. Speed: Varies (min 1.0 m / sec)

4. Openings: As mentioned in Drawing / BOQ (Glass Door)

5. Stops / Floors: As mentioned in relavant BOQ item.

6. Door operation: Full automatic power door with center/telescopic opening Glass doors

7. Entrance Position: As specified (Through or Regular Type Car)

8. Finishes of Car wall & ceiling: Brush finished stainless steel, Anti skid granite / stone flooring

9. Operating panel: Stainless steel

10. For car: Call registration high intensity LED indicators with brail button indicator; Attendant operations; Door open/close button; separate fan & light switch; Digital position & direction indicator; visual & audible indication for floors; Lighting of 53.8 lux,S.S. handrail on 3 side wall.

11. Car Door: Fully Automatic Doors S.S. hairline finish

12. Car Door Protection: Multi beam height infra-Red Detection

13. Car Operating Panel: Position indication, Call registration indication by illumination,Pre announcing arrows, Door open button, Door close button.

metre 300.00 metre 150.00 metre 200.00

Rate in words(Rs.)

Amount (Rs.)

a b c d e

Item

No

Description of Item

14. For landings: Call registration high intensity LED indicators; Digital position & direction indicator; Visual & audible signals for call buttons.

15. Landing Operating Panel: Call registration indication by illumination, Car position indication,

Pre-announcing arrows for direction, Overload indication,Full load incation, Fire indication, Out of service indication

16. Lighting: Fluorescent LED lighting at front and rear wall in ceiling

17. Ventilation: Fan

18. Other features: Full length infra light curtain safety for Automatic door; Door nudging operation with buzzer; Built in voltage stabilizer for controller; Adjustable door open time;Battery operated emergency light;Alametre and P&T between car & GF;Handrail on rear wall in car;Full height mirror on rear wall in car; Fireman switch at GF landing door; Intercom from car to controller; Attendant operation;Emergency light in car;Automatic rescue device with maintance free batteries ;Alarm button in car

19. Stainless steel Wall Cladding: At wall (Out side of car - Elevation) as instructed by Architect.

Unit a b c

184

Quantity

Elevator -

G+8, 8 Passenger

Elevator -

G+3, 12 Passenger

Elevator -

G+8, 13 Passenger

TOTAL OF SUB HEAD (E)

SUBHEAD(F)- GAS SUPRESSION

Supply, Installation, Testing and Commissioning of Novec-1230, 34.5 Bar, independent system for following rooms. Each system shall comprises of following system components including but not limited to; gas cylinder(s) with extinguishing agent, cylinder valve assembly, master cylinder kit with electrical actuation valve, manual actuator assembly, braided flexible hoses, warning plates, discharge nozzles, mounting brackets, gas release panel, multicriteria & photoelectric smoke detectors for cross zoning, manual release switch, abort switch, response indicator, fire survival cable, seamless discharge pipe to ASTM A-106, Such A-106 etc. The system shall be complete in all respect with gas qty and flow calculations approvals as required at site.

6 M x 13.08 M Data centre with room void of 3.1 M, Ceiling void of 0.80 M and Floor void of 0.30

M

4.45 M x 9.05 M ICT networking room with room void of 3.1 M, Ceiling void of 0.80 M and Floor void of 0.30 M

5.70 M x 4.15 M UPS-1 with room void of 3.1 M, Ceiling void of 0.80 M and Floor void of 0.30 M

5.50 M x 4.15 M UPS-2 with room void of 3.1 M, Ceiling void of 0.80 M and Floor void of 0.30 M

Each 4.00

Each 5.00

Each 2.00

Each

Each

Each

Each

1

1

1

1

5.75 M x 2.54 M UPS-3 with room void of 3.1 M, Ceiling void of 0.80 M and Floor void of 0.30 M

Each 1

TOTAL OF SUB HEAD (F)

Total cost of NON Schedule Items-Electrical of Schedule-D

Rate in figures

(Rs.)

Rate in words(Rs.)

Amount (Rs.)

Name of Work: Construction and development of Agri food cluster campus of National Agri-Food Biotechnology Institute (NABI) at Mohali(Punjab)

NON SCHEDULE ITEMS (HVAC WORK) SCHEDULE-F

Item

No.

Description of Items

A.

1

LABORATORY

EQUIPMENT

Supplying, installing, testing and commissioning of CENTRIFUGAL WATER CHILLING UNITS each complete with 400 TR capacity (total) Centrifugal compressor with Unit mounted (liquid /air cooled) factory fiited VFD, motor, starter panel machine mounted, water cooled condenser, insulated chiller, flow switch at chiller and condenser, vibration isolators, integral refrigerant piping and power / control cabling from starter to unit, BMS interface unit (Tracer / Microgateway

/ Datalink) grooved/flanged/victolic couplings for condenser and cooler water in/out connections, complete charge of refrigerant and oil, accessories as required and called for, automatic and safety controls mounted in central micro-processor based console panel and all mounted on a steel frame complete as per specifications. Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply and motor cable terminal box shall be suitable to connect Aluminium Cabling.

Refrigerant used shall be Ozone friendly HFC-134a & R410a as detailed in specifications.All chiller shall be factory tested at design conditions at 100%, 75%, 50% and 25% load(To ensure unloading of chillers and surge free operation). The Centrifugal chiller evaporator with secandory variable chilled water pumping system shall be designed to take minimum 40% of designed flow.

The chillers shall be ARI certified.

Unit Qty.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply . Refrigerant used shall be

Ozone friendly HFC(R134a, R410a) as per specification.

Quoted price shall also be inclusive of: a. Unit mounted automatic star delta/ soft starter to ensure that starting current shall not exceed twice the full load current. b. Victolic coupling connection shall be provided for chilled and condensing water pipes. c. Chiller Installation in Basement.

d. Cable termination adopter box.

e. Marine boxes for chiller and condenser.

Chiller

Chiller Water IN.

Chiller Water OUT.

Fouling Factor

54

44

0.0005

°F

°F

FPS

Item

No.

Chilled Water Flow

Condenser

Condenser Water IN.

Condenser Water OUT.

Fouling Factor

Chilled Water Flow

Description of Items

960

88

98

0.001

1200

USGPM

°F

°F

FPS

USGPM

Unit e

2 a b c d

IKW/TR at 100% load ti d

- <0.65

- <0.4

Minimum COP = 6.1

Chilling machines as described above (including one standby)

Supply imported portion of above chiller CIF nearest port and transportation of the same to

Mohali,Chandigarh.

Indicate for all chillers port charges, port handling charges, other local duties, loading, transportation/insurance upto site, octroi charges and all other taxes & incidentals complete till delivered at site.

Custom duty & counterveiling duty against licence for the above imported equipments.

No.

No.

No.

No.

Receiving at site above imported equipment, unloading,storing,handling, hoisting,installing in position, effective connections, anchoring, grouting above equipment including supplying & installing all necessory indageneous accessories to complete the installation.

No.

Indicate for testing and commissioning of above machines.

Supplying, installing, testing and commissioning of CENTRIFUGAL VERTICAL INLINE PUMPS, factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system as per specifications. All pumps shall be aligned properly as required. The pump motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The motor selected shall be energy efficient having efficiency (Class I) at full load ranging between 91.5% to

94% in accordance with motor rating as per specification. Minimum pump efficiency shall be 75%.

The motor of Secandory Variable chilled water pumps shall be suitable for operation on adjustable frequency drive. The quoted price shall include cost of thermal insulation and cladding for item

2A & 2B. Pumps with performance characteristics as given below:

No.

2A Primary Chilled Water Pumps

Water flow rate 960 USGPM

Head 40 Ft. of Water

Maxm. Motor HP 15 HP

Qty.

3

3

3

3

3

3

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Included in item no.1

Included in item no.1

Included in item no.1

Included in item no.1

Included in item no.1

Item

No.

2B

2C

2D

3

Description of Items Unit Qty.

Efficiency 75 % or more

Quantity indicated includes one standby ( PCHWP 1 - 3)

Secondary Chilled Water Pumps

Water flow rate 960 USGPM

Head 80 Ft. of Water

Maxm. Motor HP 30 HP

Efficiency 75 % or more

Quantity indicated includes one standby (SCHWP 1 - 3 )

Hot Water Pumps

Water flow rate 76 USGPM

Head 110 Ft. of Water

Maxm. Motor HP 5HP

Efficiency 75 % or more

Quantity indicated includes one standby (HWP 1 - 3 )

Condenser Water Pumps

Water flow rate 1200 USGPM

Head 70 Ft. of Water

Maxm. Motor HP 30HP

Efficiency 75 % or more

Quantity indicated includes one standby ( CDWP 1-3 )

No.

No.

No.

3

3

3

Supplying, installing, testing and commissioning of VARIABLE SPEED PUMPING SYSTEM consisting of adjustable frequency drive (VFD) for 30 HP -3 Nos. pumps (2W+1SBY), one dedicated microprocessor based pump controller per zone housed within the enclosure of one of the AFD with parallel pumping software duly down loaded and multiple differential pressure sensor / transmitters along with complete control cabling from transmitter to AFD Panel as per the site requirement. The entire system along with primary / secondary pumps as described under item 5 / 9 must be sourced from single manufacturer only, to ensure unit responsibility.

Necessary factory test certificates for entire system shall be submitted along with the equipment.

Sensor / Transmitters as described in specification. System shall be BMS compatible with open protocol communication port, so that complete data can be transported to remote IBMS console.

No. 3

Set 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

4

Description of Items

3(a) Supplying, installing, testing and commissioning of VARIABLE SPEED PUMPING SYSTEM consisting of adjustable frequency drive (VFD) for 5 HP -3 Nos. pumps (2W+1SBY), one dedicated microprocessor based pump controller per zone housed within the enclosure of one of the AFD with parallel pumping software duly down loaded and multiple differential pressure sensor / transmitters along with complete control cabling from transmitter to AFD Panel as per the site requirement. The entire system along with primary / secondary pumps as described under item 5

/ 9 must be sourced from single manufacturer only, to ensure unit responsibility. Necessary factory test certificates for entire system shall be submitted along with the equipment. Sensor /

Transmitters as described in specification. System shall be BMS compatible with open protocol communication port, so that complete data can be transported to remote IBMS console.

Unit Qty.

Supply, installing, testing and commissioning of horizontal FAN COIL UNITS (2 PIPE

SYSTEMS), blow thru type, each complete with 3 rows deep Chilled Water Coil, one or more centrifugal fans, cleanable fabric filters, main condensate extended SS drain pans, RA insulated plenum, as described in specifications, casing, coil piping connections, through copper pipes, condensate drain connections, wiring, control wiring in conduit upto thermostat boxes. Fan coil unit shall be factory fitted with valve package comprising of pressure independent Balancing cum

Control Valve with integrated 2 way motorized actuator in a single body for modulating operation suitable for static pressure of 1600 kPa and actuator shall be capable of withstanding 400 kPa shut off pressure, 24 V AC incoming power supply, ball valve with Y-strainer at inlet & Ball valve at outlet and necessary copper coil piping connections. The actuator of modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA signal from Digital Thermostat.

Set 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

The actuator of the valve shall have necessary torque to overcome pressure differential of 4 bars rating. All fan coil units shall be suitable for 220±6% volts, 50 cycles, single phase power supply.

Fan coil units shall be of following refrigeration capacities as listed.

4(a)

4(b)

5

1.0 TR nominal capacity - 400 CFM

2.5 TR nominal capacity - 1000 CFM

No.

Supplying, installing, testing and commissioning of double skin construction draw thru type AIR

HANDLING UNITS as per specification, each complete with following:

a. Direct drive supply air centrifugal backward curved fan.

b. MERV 8 filters in supply air stream. c. 6 Row deep cooling coil & 2 Row deep heating coil of copper tube and aluminum construction sized at maximum face velocity of 500 fpm.

d. Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency.

e. Vibration isolators.

No.

3

1

Item

No.

Description of Items

f. Fan outlet velocity not exceeding 10 mps. g. Minimum 20 mm (WC) external static pressure after sound attenuators. Total static pressure of AHU shall be checked by Vendor. h. Sound level at 1m distance not exceeding 60 dB in supply and return air stream. Sound attenuators in supply and return air streams shall be provided if required to meet the specified sound level in both supply & return air ducts. i. VFD designed for HVAC applications for supply air fan with built-in PID controller, control panel

(keypad & display) , IP-55 enclosure for use on standard centrifugal fans. The VFDs should not cause any deration of the connected motors and must ensure that class B temperature levels of the connected motors are never exceeded. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have builtin harmonic filters.VFD shall be BMS compatible with open protocol communication port, so that complete data can be transported to remote IBMS console.

Tag No.

5.1

AHU- 1

CFM TR

3500 8.5

5.2

AHU- 2

5.3

AHU- 3

5.4

AHU- 4

5.5

AHU- 5

5.6

AHU- 6

5.7

AHU- 7

Tag No.

5.8

AHU- 8

5.9

AHU- 9

5.10 AHU- 10

5.11 AHU- 11

5.12 AHU- 12

5.13 AHU- 13

5.14 AHU- 14

5.15 AHU- 15

Floor

Ground

Ground

Ground

Ground

Ground

Ground

Ground

Floor

First

Space Type

FB Cabins & CSU

Passage

Plant biotech 2 FMU

NMR & Central

Store

Corridor 1

FMU

CSU

Corridor 1

Corridor 2

CSU

CSU

DH Atrium & FMU

Reception

Space Type

Director's Office CSU

First

First

First

First

First

First

First

Bio Informatics

Plant biotech

Admin & Admin

Staff

Corridor 1

Corridor 2

Corridor 3

Prefunction

Room

FMU

FMU

FMU

CSU

CSU

CSU

CSU

14000 27

15500 31

5000 10

3000

4600

13000 24

6

9

CFM TR

4800 10

16500 37

19500 41

11000 23

3500

4500

6

9

5000 10

1500 4

Unit Qty.

Max Heating

2 3

No. 1

7.5

30

No. 1

7.5

2

No. 1

2 Nil

No. 1

1 Nil

No. 1

2

1

2

2

2 Nil

No. 1

7.5

1

No. 1

Max Heating

2 7

No. 1

7.5

38

10

5

50

13

No. 1

No. 1

Nil

Nil

Nil

Nil

No. 1

No. 1

No. 1

No. 1

No. 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items Unit Qty.

5.16 AHU- 16

5.17 AHU- 17

5.18 AHU- 18

5.19 AHU- 19

First 35 Seater

Conference Room

Second Dean Office

Second Plant Biotech

Second Non Clean Room

Nutrition Btech

CSU

CSU

FMU

CSU

1300

4800

4

10

20500 45

6000 14

1

2

10

2

Nil

7

50

18

No. 1

No. 1

No. 1

No. 1

5.20 AHU- 20 Second Seminar Rooms FMU 12000 27 5 3

No. 1

5.21 AHU- 21 Second

130 Seater

Conference Room

FMU

6000 15 2

9

5.22 AHU- 22

5.23 AHU- 23

5.24 AHU- 24

5.25 AHU- 25

5.26 AHU- 26

5.27 AHU- 27

5.28 AHU- 28

5.29 AHU- 29

5.30 AHU- 30

5.31 AHU- 31

Second Corridor 1

Second Corridor 2

Second Corridor 3

Second High

Tea/Prefunction

Third

Third

Third

Third

Third

Third

Administration

Plant biotech 1

Plant biotech 2

Corridor 1

Corridor 2

Corridor 3

CSU

CSU

CSU

CSU

FMU

FMU

FMU

CSU

CSU

CSU

3500

4500

5000 10

2600

6

9

6

5500 10

21500 50

24000 55

3500 6

5000 10

5200 10

2

2

2

1

2

10

10

2

2

2

Nil

Nil

Nil

Nil

3

35

45

Nil

Nil

Nil

5.32 AHU- 32 Ground Food Biotech FMU 14000 21 7.5

14

Note 1 : AHU No- 1, 2, 3, 7, 8, 9, 10, 11, 17, 18, 19, 20, 21, 26, 27, 28 &32 only to be

6

Note 2 : AHU No- 2, 3, 9, 10, 18, 19, 27,28 & 32 only to be provided with standby fan

Double skin AHU (in Single /double Decker construction) complete with thermal break profile, Fresh air section with Fresh air manual AL damper with double HDPE insect mesh, Filter sections with G-4 filters & F6 /F9 filters (The Velocity across F6 filters not to exceed 500 FPM),

Coil section with CHW coil, PVC Moisture Eliminator,DIDW backward Curved Centrifugal Blower ,

Supply air plenum with Supply air manual AL damper, Return Air plenum with return air manual

AL damper, Differential pressure nozzles, Exhaust air manual AL damper with double HDPE insect mesh, Magnehelic gauges with pvc tubing across all filters & blower, Service windows as per approved design & Motor for Supply air blower.The filter stages shall be as specified in the ahu data sheet.EU 13 filters if specified shall be terminal mounted and rates for the same to be quoted as specified under respective items under filter housing/hooded filters.

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

No. 1

Rate in figures

(Rs.)

Limitswitches in Supply fan section for AHU doors and Inspection lamp, Cushy foot mountings,

Fire proof double canvass connections (Fungal resistant and Lint free) and Standard accessories duly

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

a.6 Row deep cooling coil & 2 Row deep heating coil of copper tube and aluminum construction sized at maximum face velocity of 500 fpm.

b. Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency.

c. Vibration isolators.

d. Fan outlet velocity not exceeding 10 mps.

e. Minimum 60 mm (WC) external static pressure after sound attenuators. Total static pressure of AHU shall be checked by Vendor.

f. Constant Volume Coil Bypass damper of specified bypass air quantity in below mentioned table, to be provided in the AHU's. g. VFD designed for HVAC applications for supply air fan with built-in PID controller, control panel

(keypad & display) , IP-55 enclosure for use on standard centrifugal fans. The VFDs should not cause any deration of the connected motors and must ensure that class B temperature levels of the connected motors are never exceeded. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have builtin harmonic filters.VFD shall be BMS compatible with open protocol communication port, so that complete data can be transported to remote IBMS console.

Unit

Tag No.

Floor Space Type CFM TR Ma x

Mo tor

(H

P)

Bypa ss Air

Qty

(CFM

) humidifi er

Capacity

(Litre/h our)

Heatin g

Capaci ty

(KW)

6.1

6.2

AHU- 32

AHU- 33

Ground

Ground

Clean Labs-

GC,LC-MS erc.

Plant biotech 1

(Clean room)

FMU

FMU

21500 25 30 3600

15000 17 20 4600

5

5

28

20

No.

No.

6.3

AHU- 34 Second Clean Room

Nutrition Btech

FMU 15500 17 20 4600 10 21

Note 1: Other than the heating coil pecified in AHU No.32, there are two duct heaters of 3 KW each required in duct branch feeding area ICP-MS & GC -TOF. The price for the same must be included in the cost of AHU.

Note 2 : All above mentioned AHU's to be provided with addidtional/standby fan arrangement.as

Labs are 24 hours operational.

No.

Qty.

1

1

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

7

Description of Items

Supplying, installing, testing and commissioning of double skin construction draw thru type

TREATED FRESH AIR HANDLING UNITS as per specification, each complete with following :-

Unit

a. Supply air centrifugal Forward curved fan with efficiency >65%

b. MERV 8 filters in supply air stream. c. 8 Row deep cooling coil of copper tube and aluminum construction sized at maximum face velocity of 500 fpm. d. Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency.

e. Vibration isolators.

f. Fan outlet velocity not exceeding 10 mps. g. Minimum 20 mm (WC) external static pressure after sound attenuators. Total static pressure of AHU shall be checked by Vendor.

h. Fan belt drive package

j. All air handling units to be provide with SS-304 end plates for coil.centrifugal fans.

Tag No.

7.1

TFA-1

Floor

Terrace

Space

Radioactivity

CFM

3,000

Motor (HP)

1

7.2

TFA-2

8

Ground

Rooms

Food Biotech Lab 2,500 1

Fresh Air

Supplying, installing, testing and commissioning of AIR HANDLING UNITS ( FAN SECTIONS

ONLY)with double skin construction as per specificatopns, each complete with squirrel cage induction motor (mounted internally), airfoil centrifugal fan belt drive and vibrations isolators.Motors shall be suitable for 415 +- 10% volts, 50 cycles , 3 phase AC supply an static pressure shall be as indicated . Fan-motor assembly (as whole) shall be statically & dynamically balanced to grade G6.3 as per ISO-1940/AMCA 204-3. All AHUS (Fan sections) shall be suitable for outdoor duty and complete with duct flexible connections and volume control damper . In additional all supply fans (SF) shall be provided with prefilter .Minimum 20 mm (WC) external static pressure . Total static pressure of AHU shall be checked by Vendor.

No.

No.

Qty.

1

1

Tag No.

8.1

AHF-1

8.2

AHF-2

8.3

AHF-3

8.4

AHF-4

Floor

Terrace

Terrace

Terrace

Terrace

Space

AHU's Fresh Air

Riser 1

AHU's Fresh Air

Riser 2

AHU's Fresh Air

Riser 3

AHU's Fresh Air

Riser 6

CFM

11600

12800

6100

4700

Motor (HP)

5

5

2

1.5

No.

No.

No.

No.

1

1

1

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items Unit

9.1

9.2

9.3

9.4

9.5

9.6

10

8.5

AHF-5

8.6

AHF-6

Terrace Radioactivity

Room Exhaust

Terrace Toilet Exhaust

3000

3200

1

1

No.

No.

8.7

AHF-7

9

Terrace RNA And Cold 1400 1

Room Exhaust

Supply, installation, testing and commissioning of Electronic Self Balancing Valve pressure independent with independent type dynamic balancing valve for AHUs with integrated 2 way modulating control valves in a single body. The actuator shall be capable of accepting 2-10 VDC /

4-20 mA electric signal and shall provide similar transduced feedback output signal to control system for flow measurement. The minimum close off pressure actuator must be 1.5 times shut off head of pump 5 bars whichever is maximum. The valves shall be suitable for following pipe sizes:

No.

80 mm dia

65 mm dia

50 mm dia

32 mm dia

25 mm dia

20 mm dia

Supply, installation, testing and commissioning of cooling Thermostats for various air handling units and fan coil units.

No.

No.

No.

No.

No.

No.

11

i. Proportional cooling thermostat at AHU.

ii. Proportional cooling thermostat at FCU.

Supplying, installing, testing and commissioning of Smoke extract fans as per specifications.

Fan shall be with direct driven vane axial fan. Fan and casing shall be suitable for smoke exhaust application.Motor shall be mounted inside/outside so that it is not exposed to smoke stream & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] Class-H. Motors shall be suitable for 415+10% volts, 50 cycles , 3 phase AC supply with high efficiency,EFF-2 type and static pressure shall be as indicated.Minimum 20 mm (WC) external static pressure after fan outlet. Total static pressure shall be checked by Vendor.The fan shall be equipped with mounting bracket & outlet core required at discharge.Fan shall be with flexible fire proof connection at inlet and outlet.Cost of spring isolators for the installation of the fans needs to be included.Fan capacity shall be as follows:-

No.

No.

Fan Tag

Descripti on

Space Fed Floor CFM Motor

HP

Qty.

35

4

5

5

7

23

7

10

1

3

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

11.1 VEX-1

11.2 VEX-2

11.3 VEX-3

11.4 VEX-4

11.5 VEX-5

11.6 VEX-6

11.7 VEX-7

11.8 VEX-8

11.9 VEX-9

11.10 VEX-10

11.11 VEX-11

11.12 VEX-12

Description of Items

Exhaust

Air

Clean room Lab Ground 6500

Exhaust

Air

Food Biotech Lab Ground 4500

Exhaust

Air

Plant Biotech Ground 7500

Ground 11000 Exhaust

Air

NMR

Exhaust

Air

Exhaust

Air

Bio Informatics

Lab

Plant Biotech

First

First

12000

7500

Exhaust

Air

Plant Biotech

Exhaust

Air

Plant Biotech 1

Second

Exhaust

Air

Nutrition Biotech Second

Third

14000

5500

14000

Third 13000 Exhaust

Air

Plant Biotech 2

Exhaust

Air

Exhaust

Air

DH Conference

Room

Food Biotech

Second

Ground

10000

6500

1.5

1

1.5

3

3

1.5

3

1.5

3

3

2

1.5

Unit

No.

Qty.

1

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

1

No.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

12

Description of Items

Supply, installation, testing & commissioning of AXIAL FLOW FAN suitable for installing in any position in Horizontal or vertical and complete with totally enclosed fan cooled motor belt drive, multi sheaved pulley mounted on motor and fan shaft, belt guard, motor mount and vibration isolators. The fan shall be selected for low noise level and low RPM (less than 1000 RPM) Fan motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase power supply with high efficiency,EFF-1 type. The fan shall be equipped with mounting bracket & outlet core required at discharge. Minimum 15 mm (WC) external static pressure after fan outlet. Total static pressure shall be checked by Vendor.

Unit Qty.

12.1

12.2

TAF-5 to 7

12.3

Fan Tag

TAF-1 to 4

TAF-8 to 10

12.4

12.5

12.6

13

TAF-11

TAF-12 & 13

Description CFM

Liftwell

Lift Lobby

Staircase

Pressurisation

Plumbing

Plantroom Fresh

LT Panel Room

Fresh & Exhaust

Air

HVAC Plantroom

Exhaust

10000

14000

11500

4000

5500

16000

Motor HP

2

5

3

1

1.5

No.

No.

No.

No.

No.

TAF-14 5

Note : Liftwell,Lift Lobby & Staircase Pressurization fan shall be for outdoor application & provided with cannopy of material similar to casing.

Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply. All units shall be complete with duct flexible connector and volume control damper.

No.

Tag No.

13.1 IF-1

13.2 IF-2

Floor

Ground

Ground

Space

Cold /Dark Room

Fresh Air

Cold /Dark Room

Exhaust Air

CFM

800

800

4

3

3

1

2

1

No. 1

No. 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

14.1

14.2

14.3

14.4

14.5

14.6

14.7

14.8

Item

No.

Description of Items Unit Qty.

13.3 IF-3

14

Ground Autoclave &

Wash Area

750

Exhaust

Supplying, installing, testing and commissioning of Pressure Independent Variable Air Volume

Terminal units, suitable for installtion in horizontal ducts. The casing shall be double skin acoustically lined and constructed with galvanised sheet steel.Should include all accessories such as single / multileaf damper (with equal % characteristics) etc. actuators, control cabling , thermostat , feed back control cabling upto VFD panel / DDC Panel in AHU room and any other ancilary requirement for the functioning of the units. Cost of duct mounted Diff. pressure transmitter with cabling upto VFD panel shall also be included.

No. 1

Rate in figures

(Rs.)

VAV boxes shall be suitable for following air flow capacitties.

No.

No.

No.

No.

No.

No.

No.

No.

Rate in words

(Rs.)

Amount (Rs.)

15

15.1

Item

No.

16

Description of Items

Supply, installation, testing and commissioning of DUAL COIL MICROPROCESSOR BASED

PRECISION A/C UNITS as per the specifications complete with air cooled condenser, chilled water coil and variable speed drive for condenser fan, scroll compressor, evaporator coil with hydrophillic coating, EC brushless motor, backward curved/ direct driven fan, first fill of refrigerent, 24 hrs performance test with necessary hea load, multistage electric heater, variable capacity humidifer ,all valves ,accessories and vibration isolator. Motor shall be suitable for 415 +

10% volts, 50 cycles, 3 phase AC supply and external static pressure shall be 25 Pa. Outdoor unit motor should be with IP-54/55 protection and should be weather proof. PAC shall have bottom throw.Auto sequencing of the unit for equal run time should be integral part of the microprocessor.

Unit

Each unit shall be complete with powder coated electrical panel and double earthing. The cables should be Cross linked polythene insulated, armoured Copper cabling, with a low smoke and flame sheath (XLPE/SWA/LSF) and all termination between main panel and PAC should have double compression gland. Timers shall be provided in Electrical panel for delayed start of units.

It shall be inclusive of copper, drain piping, control & power cabling from MCB to indoor unit & it also includes MCB, GI tray for supporting the refrigerant pipes( whereever exposed to sun) between indoor and outdoor units.

Units shall be equipped with factory integrated 2 way automatic control valve with thermostat. It shall also provided with automatic balancing valve.

The unit capacities shall be after taking deration into account due to copper piping lengths.

Condensers should be adequately sized for high ambient temperatures upto 43.3 Deg C with condensing temperatures not exceeding 56 Deg C.

The unit should include INTEGRATOR for giving industry standard (Modbus / Lon Works / Bacnet) output to BMS system. Mapping shall be required for all points displayed on precision unit microprocessor panel. It shall be inclusive of wiring in MS conduit between integrator and individual PAC panel.

CHW units shall be capable for delivering 8 TR actual sensible capacity at below rated chilled water conditions :

Chilled Water Inlet to PAHU's : 6.7 Deg C (44 Deg F)

Chilled Water Outlet from PAHU's : 12.2 Deg C ( 54 Deg F)

Computerized selection sheet shall be required to be submitted along with the offer and same need to be demonstrated at the time of technical evalution.

The air cooled units shall be complete with copper refrigerant piping with nitrile rubber insulation as per specifications.

8 TR Dual Coil (chilled water & DX air cooled) Microprocessor units for Server Room.

Unit described as above

No.

Qty.

4

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

17

Description of Items Unit

3.5 TR (DX air cooled) Microprocessor units for Network Room.

Supply, installation, testing and balancing of Powder coated extruded aluminum construction jet diffusers/nozzle with volume control dampers as per approved drawings and specifications.

No.

Qty.

2

17.1

300 mm dia.

18 Supplying, installing, testing and commissioning of PRESSURISED chilled& hot WATER

EXPANSION TANK suitable for total volume of water in chilled water/ hot water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and

20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank and air separator must be constructed in accordance with section

VIII of the ASME Boiler and pressure vessel (Unfired)code and stamped 125 PSI working pressure. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures and safety fixtures required for proper functioning of the complete hydronic system.

No.

50

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

19

The total Volume of water in chilled water circuit = 2500 Litres for cooling system and static head of approximate 25 mts to be considered . The contractor shall submit calculations for total system volume and tank sizing calculations.

The total Volume of water in Hot water circuit = 300 Litres and static head of approximate 25 mts to be considered . The contractor shall submit calculations for total system volume and tank sizing calculations.

Supply, installation, testing and commissioning of INDUCED OR FORCED DRAFT COOLING

TOWERS. Fan and motor shall be suitable for VFD. Each tower shall be complete with basin, casing, distribution system, filling, louvers, ladder, fan and motor. Motor shall be suitable for

415±10% volts, 50 cycles, 3 phase power supply, Isolator panel with MCCB at cooling tower and earthing, shall also be included. Tower for airconditioning system shall be selected on the basis of ambient wet bulb 80 Deg F. The tower shall be sized for 10% extra capacity over heat rejection duty specified through water temperature difference and flow rate below :For units with VFD, complete equipment shall be designed to limit THDi to less than 5%.

No.

No.

1

1

Capacity Suitable for 400

TR Machine

Item

No.

Description of Items Unit

20

20.1

20.2

Water flow rate

Water temp.

IN.

Water temp. out

Recommend ed motor rating

Airside pressure

-

-

-

-

-

1200 USGPM

98 °F

88 °F

10 HP X 2 Nos drop

Type of motor

IP55,TEFC

No. of cell 1

Cooling tower as described as above (2 W

& 1SBY)

Note: i. VFD designed for HVAC applications for supply air fan with built-in PID controller, control panel

(keypad & display) , IP-55 enclosure for use on standard centrifugal fans. The VFDs should not cause any deration of the connected motors and must ensure that class B temperature levels of the connected motors are never exceeded. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have builtin harmonic filters.

ii. Each VFD panel to be provided with digital display showing electrical parameters like voltage, current and power consumption.

No.

iii. Each VFD shall be installed in a dedicated external IP-55 enclosure and the inter connecting wires between driver and MCC shall be included.

iv. Colour of cooling tower shall be as per Architect approval.

v. The cooling tower shall be of special design to suite are available at site as per design drawing.

Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather t ti i d F l ti t d El t i l h t i ti h ll b f ll

300 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

No.

No.

Qty.

3

4

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

21

B.

22

Description of Items Unit

Supplying, installing, testing and commissioning of Electrical Hot Water generator of vertical/ horizontal construction equipped with sufficient number of flanges and electrical immersion heaters. The pressure vessel shall be constructed as per ASME standards and insulated on all sides with 100 mm thick fibreglass. The hot water generator shall be equipped with all automatic and safety controls such as manual reset high temperature water outlet, step controller and recycling relay, ON-OFF switch, thermostats, pilot light, ‘ON’ status of individual banks, low water cut off all as per manufacturers recommendations. All basic controls and terminal shall be located in an internal control cabinet, factory wired and tested. The hot water generator shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The entire hot water generator and control cabinet shall be factory assembled on common base and tested, requiring only connection to services.

200 KW Hot Water Generator as described above.

a. Water ‘IN’ temperature : 104 deg F.

b. Water ‘OUT’ temperature : 122 deg F c. Heater Bank to be provided with 4 steps.

TOTAL OF SUB HEAD(A)

PIPING-CHILLED,HOT AND CONDENSER WATER

Providing & fixing the following factory rolled MS pipes with specified wall thickness (as per specifications) cut to required lengths and installed with all welded / grooved joints, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, floor mounted & ceiling/wall hung MS support & sockets for BAS, fabricated to size and shape in workshop or brought out ready made where available of acceptable quality.

No.

Qty.

2 a b c d

23

500mm dia MS pipes

450 mm dia MS pipes

300 mm dia MS pipes

250 mm dia MS pipes

Providing and fixing in position the following MS class ‘C’ pipes cut to required lengths (as per specifications) and installed with all welded joints, providing and fixing in position the necessary fittings like elbows, tees and reducers, mating flanges & sockets for BAS:

RM

RM

RM

RM

200

145

725

500

Rate in figures

(Rs.) c d a b e

200 mm dia MS pipes

150 mm dia MS pipes

125 mm dia MS pipes

100 mm dia MS pipes

80 mm dia MS pipes

RM

RM

RM

RM

RM

410

264

154

935

666

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

e f g h c d k

25 a b

26 a i j b g h i j e f a b c d h i f g j k

24

Description of Items

65 mm dia MS pipes

50 mm dia MS pipes

40 mm dia MS pipes

32 mm dia MS pipes

25 mm dia MS pipes

20 mm dia MS pipes

Providing and fixing in position the following manual butterfly valves (PN 16) :

500 mm dia Valves.

400 mm dia Valves.

300 mm dia Valves.

250 mm dia Valves.

200 mm dia Valves.

150 mm dia Valves.

125 mm dia Valves.

100 mm dia Valves.

80 mm dia Valves.

65 mm dia Valves.

50 mm dia Valves.

Providing and fixing in position the following manual balancing valves (PN 16) :

250 mm dia Valves.

150 mm dia Valves.

125 mm dia Valves.

100 mm dia Valves.

80 mm dia Valves.

65 mm dia Valves.

50 mm dia Valves.

32 mm dia Valves.

25 mm dia Valves.

20 mm dia Valves.

Providing and fixing in position following ball valves (PN 16) :

32 mm dia valves

25 mm dia valves

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

RM

RM

RM

RM

RM

RM

Unit Qty.

259

310

138

799

195

637

18

8

2

9

15

32

22

3

3

3

18

1

1

1

1

1

1

4

1

3

3

No.

No.

48

16

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

27 a b c

28 a b

29 k l i j e f g h c d

Description of Items Unit

20 mm dia valves

Providing and fixing in position the following ‘Y’ Strainers (PN 16) :

250 mm dia Valves.

200 mm dia Valves.

80 mm dia strainers

65 mm dia strainers

50 mm dia valves

32 mm dia valves

25 mm dia valves

20 mm dia valves

Providing and fixing in position the following Non return Valves (PN 16) :

250 mm dia Valves.

200 mm dia Valves.

65 mm dia Valves.

Providing and fixing in position the following Drain Valves :

50 mm dia Valves.

25 mm dia Valves.

Supply, installation, testing and commissioning of flexible connections of suitable pressure rating to be installed at pump suction, discharge and at pipes crossing building expansion joints.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

Qty.

26

9

12

3

10

10

7

23

7

12

9

12

5

8 a b c

30

31

32

33

34

250 mm dia pipes (PN-16)

200 mm dia pipes (PN-16)

65 mm dia pipes (PN-16)

Supplying, installation, testing and commissioning of Auto air vents(PN-16).

Supplying, installation, testing and commissioning of Flow Switches .

No.

Providing and fixing in position SS 304 the industrial dial type pressure gauges with gun metal valves.

Providing and fixing in position SS 304 the mercury-in- glass industrial dial type thermometers.

Supply, installation, testing and commissioning of Magnehelic Gauges 100mm dial, range 0 to

60 Pa with SS box, probes & tubes, at different rooms

No.

No.

No.

No.

No.

No.

No.

12

18

6

15

3

142

118

16

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

b c d

Item

No.

35

36 a b c a b c

C.

37 a e

38

Description of Items Unit Qty.

Providing and fixing in position the following GI class ‘B’ pipes cut to required lengths and installed with all screwed joints, and providing and fixing in position the necessary elbows, tees and reducers as per specifications for AHU / FCU drain.

50 mm dia GI pipes

32 mm dia GI pipes

25 mm dia GI pipes

RM

RM

RM

Providing and fixing in position the following ‘POT’ Strainers :

Suitable for 500 mm dia pipe

Suitable for 450 mm dia pipe

Suitable for 100 mm dia pipe

TOTAL OF SUB HEAD(B)

AIR DISTRIBUTION

No.

No.

No.

Supply, installation and testing of Factory fabricated GI sheet metal ducts as per SMACNA in accordance with the approved shop drawings and as per specifications.

26 gauge galvanised sheet steel (0-750mm)

Sqm

24 gauge galvanised sheet steel (751-1200mm)

Sqm

22 gauge galvanised sheet steel (1201-1800mm)

Sqm

20 gauge galvanised sheet steel (1801-2100mm)

Sqm

18 gauge galvanised sheet steel (2101 & Above)

Sqm

Supply, installation and testing of Factory fabricated Aluminium sheet metal ducts as per

SMACNA in accordance with the approved shop drawings and as required by the specifications.

130

30

20

1

1

1

7,053

2,663

673

933

176 a b a b

39

24 gauge

Sqm

22 gauge

Supply, installation, testing and commissioning of Aluminum Powder Coated Risers with filter fixing arrangement & opening complete with perforated grill & bolts in front.

Sqm

200

63

450mm X 150 mm (3.5m Vertical Length)

450mm X 300 mm (3.5m Vertical Length)

No.

No.

62

24

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

40

41

42

43

44 a b

45

46

47

48

49

50

Description of Items Unit Qty.

Supply, installation, testing and commissioning of Low leak aluminium damper in return air

ducts for rooms of classified areas.

Sqm

Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resin sleeve as per the approved shop drawings.

Sqm

Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air Grilles front fixed type with inner side adjustable/movable type with volume control dampers in accordance with the approved shop drawings and specifications.

Supply, installation, testing and balancing of powder coated extruded aluminium Air Grilles front fixed type with inner side adjustable/movable type without volume control dampers.

Sqm

Sqm

Supply, installation, testing and commissioning of motorised combined smoke & fire damper complete with control panel, inter connecting wiring at locations shown in approved shop drawings and as per specifications.

11

42

16

13

Smoke & Fire Damper

Sqm

Control Panel & Wiring(with actuators)

No.

Supply, installation, testing and balancing of Powder coated extruded aluminium construction

square / round shape supply air diffusers with removable core & anti smudge ring & volume control dampers as per approved drawings and specifications.

Sqm.

Supply, installation, testing and balancing of Powder coated extruded aluminium construction.

Square / round shape return air diffusers with removable core, antismudge ring & without volume control damper as per specifications.

Sqm.

Supply, Installation, Testing and Balancing of Powder coated extruded aluminium construction

Linear Grilles with removable core as per approved drawings and specifications. Quoted price shall be inclusive of volume control damper behind supply air collar.

Sqm.

Supplying & fixing of opposed blade volume control dampers in supply air duct collars as per approved drawings and specifications.

Sqm.

Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. louvers with bird screen for exhaust air as per specifications and approved drawings.

Sqm.

Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. louvers with bird screen for fresh air as per specifications and approved drawings.

Sqm.

32

64

86

88

8

5

4

3

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

51 a b

52 a

D.

53 a

54

Description of Items Unit Qty.

Supply, installation, testing and commissioning of motorized volume control ON /OFF type dampers of extruded aluminium construction in fresh air/return air/exhaust air steams. The damper actuator must accept signal from BMS system. Maximum leakage rate from dampers shall be in accordance with AMCA standard 500 . Quoted price shall also be included control wiring of damper.

Motarised Damper

Sqm

Control Panel & Wiring(with actuators)

Nos.

Hooded Type Terminal Hepa Filter Box with Filter & filter shall be gel seal type & replaceable from Room side, Frame material: Aluminum anodised, Dop efficiency:99.997% down to 0.3

micron with SS Terminal Plate

8

10

Hepa Filter boxes shall be of following sizes.

610 x 610 x 133 (700 CFM)

No.

TOTAL OF SUB HEAD (C)

THERMAL INSULATION

Supply, installation testing and commissioning of acoustic insulation. Material shall be Open cell

Nitrile rubber and all accessories as per specification.

15 mm thick acoustic lining

Supply and installation of External Thermal closed cell crosslinked polyethelene/Nitrile rubber insulation for Class O as per BS 476 Part 6 : 1989 with aluminium foil faced & Self adhesive backing on ducts as per the approved specifications. Quoted price shall be inclusive of UV protective coating over exposed to weather ducts.

Sq.m

.

88

200

Rate in figures

(Rs.) a b

55

13 mm thick insulation for supply & return air ducts

25 mm thick insulation for supply & return air ducts exposed to weather.

Supplying, installing and testing of 25 mm thick (pre-moulded pipe section of T.F. quality expanded polystyrene, 24 Kg / M³) insulation on chilled water and condensate drain piping and fitting like valves, flanges union etc. as per the approved shop drawings and specifications.

Sq.m

.

Sq.m

.

9275

20

Rate in words

(Rs.)

Amount (Rs.) a b c

40 mm dia pipes

32 mm dia pipes

25 mm dia pipes

RM

RM

RM

138

799

195

Item

No.

d e f g

56

Description of Items Unit

20 mm dia pipes

RM

50 mm dia condensate drain pipes

RM

32 mm dia condensate drain pipes

RM

25 mm dia condensate drain pipes.

Supplying, installing and testing of 50 mm thick (pre-moulded pipe section of T.F. quality expanded polystyrene, 24 Kg / M 3 ) insulation on chilled water piping and fitting like valves, flanges union, etc. as per the approved shop drawings and specifications.

RM

Qty.

637

130

30

20 b c d e f a

57

150 mm dia pipes

RM

125 mm dia pipes

RM

100 mm dia pipes

RM

80 mm dia pipes

RM

65 mm dia pipes

RM

50 mm dia pipes

Supplying, installing and testing of 75 mm thick (pre-moulded pipe section of T.F. quality expanded polystyrene, 24 Kg / M 3 ) insulation on chilled water piping and fitting like valves, flanges union, etc. as per the approved shop drawings and specifications.

RM c d a b

450 mm dia pipes

300 mm dia pipes

250 mm dia pipes

200 mm dia pipes

Sqm

RM

RM

TOTAL OF SUB HEAD (D)

RM

204

724

418

385

264

154

935

666

259

310

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

E.

58

Description of Items

ELECTRICAL PANELS

MOTOR CONTROL CENTRE FOR AIR CONDITIONING EQUIPMENT

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type

2 mm thick sheet steel enclosed separate compartment for each feeder, front operated, rear connections indoor type LT motor control panel, dust and vermin proof, drawout/hinged and lockable doors, complete with internal wiring, colour coding with ferrules, cable glands, bonding to earth and painting. Quoted price for each panel & motor control centre shall include all power cabling & earthing over MS Powder coated cable trays upto various equipment/motor and all associated control wiring.

Unit Qty.

iii iv i ii v vi vii.

viii

All outgoing shall be provided with Stop/Manual/ Auto/selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

Motor Control Centre 415V consisting of

Incoming

2 No. 1250 Amps 4 pole electrically operated fully drawout type air circuit breaker with

ON/OFF/TRIP indicating lumps with MCB's and over current short circuit and earth fault microprocessor releases (Type 2A of MG or equivalent make) .

Digital VAF meter with 3 No.1250/5 amps 15VA CTs with inbuilt slector switch.

Phase indicating light shall be protected by 2 amps MCB’s. - 3 Sets

ON / OFF indicating lights with control MCB’s. - 1 Set.

Under voltage release - 1 Set

24 V DC Shunt trip coil. - 1 Set

Auto-manual / test selector / switch - 1 Set

Digital electronic Demand controller (EM 3460 with RS-485 ) suitable for metering class CT’s

Auxiliary contacts required for necessary interlocking of breakers.

Bus Bars

1600 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set.

Bus Coupler

1250 Amps 4 pole electrically operated fully drawout type air circuit breaker without release with

ON / OFF indicating lamps with control MCB’s and breaker control switch etc. complete as required. - 1 Set

Outgoing

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

3 No. 800 amps TPN MCCB as outgoing for 3 No. 260 KW starter of chilling unit compressor motor . The MCCB compartment shall contain CT operated digital ammeter of 0-800 amps range with selector switch and an indicating lamp with MCB for ‘ON’ status of motor.

Unit Qty.

1 No. 630 amps TPN MCCB as outgoing for 2 No. 200 KW starter of Hot water Generator . The

MCCB compartment shall contain CT operated digital ammeter of 0-630 amps range with selector switch and an indicating lamp with MCB for ‘ON’ status of motor.

3 No. MPCB, suitable rating Star Delta starter for 15 HP motor, over load relay with built in single phasing protection and outgoing feeder to Primary chilled water pump motor. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of fan motor.

3 No. MPCB, suitable rating Star Delta starter for 30 HP motor, over load relay with built in single phasing protection and outgoing feeder to Condenser water pump motor. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of fan motor.

3 No. MPCB, suitable rating VFD starter for 30 HP motor, over load relay with built in single phasing protection and outgoing feeder to Secondary water pump motor with VFD. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of fan motor.

3 No. MPCB, suitable rating VFD starter for 5 HP motor, over load relay with built in single phasing protection and outgoing feeder to Hot water pump motor with VFD. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of fan motor.

3 No. MPCB, suitable rating VFD starter for 2 No. 10 HP motor, over load relay with built in single phasing protection and outgoing feeder to Cooling. Tower Fan Moter water pump motor. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of fan motor.

c. Necessary cable alleys, space for spare switches, internal wiring, and copper earthing of equipment shall also be included. All switches and other components shall be motor duty rating.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Motor Control Centre as described above.

Note :

Motor Control Centre No. 1 shall be suitable for 50 KA fault current.

Set 1

Item

No.

59 a b

60

Description of Items Unit

CONTROL PANEL TYPE - 1 FOR AIR HANDLING UNITS ( WITH

DOL STARTER )

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, power & control cabling,wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor.

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. DOL / SD starter as per HP ratings c. Terminal block for power distribution.

d. Contactor, over load relay with built in single phasing protection.

e. Phase indicating lights and indicating light for ON status.

f. Digital voltmeter and digital ammeter with selector switches.

g. Time delay relay for delayed automatic restart of air handling unit motor.

h. Wiring for microswitch for stopping the fan when fire damper closes.

j. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

k. All starters shall be provided with suitable potential free contract for connections to the Building

Automation System.

l. 3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for

DDC Panel , fire damper actuator & as a spare.

220 / 24 V Transformer

The number of AHU control panels shall be as follows.

2.5-4.0 Amp MPCB upto 1.5 HP with DOL Starter

No.

2.5-4.0 Amp MPCB 2 HP with DOL Starter

No.

CONTROL PANEL TYPE -2, PANEL No- 1 IN AIR HANDLING UNIT WITH VFD & HEATING

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Qty.

4

11

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

61

Description of Items Unit

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 2 HP VFD for AHU.- 1set

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 2 IN AIR HANDLING UNIT WITH VFD , HEATING

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

2

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Unit Qty.

62

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 7.5 HP VFD for AHU.- 1set c.Suitable rating MCB with 1.5 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB ‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 3 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL& SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

2

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

63

Description of Items Unit

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 7.5 HP VFD for AHU.- 1set c.Suitable rating MCB with 3 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB ‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 4 IN AIR HANDLING UNIT WITH VFD , HEATING

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

1

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items Unit a.Suitable rating MPCB with outgoing feeder to 7.5 HP VFD for AHU.- 1set

Control Panel as described above

64 CONTROL PANEL TYPE -2, PANEL No- 5 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL & SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

65

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 2 HP VFD for AHU.- 1set

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 6 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL & SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

1

2

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Unit

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 7.5 HP VFD for AHU.-

1set c.Suitable rating MCB with 3 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB ‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Qty.

66

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 7 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL & SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Unit Qty.

67

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 10 HP VFD for AHU.- 1set c.Suitable rating MCB with 2 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB ‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No- 8 IN AIR HANDLING UNIT WITH VFD, HEATING

COIL& SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Unit Qty.

68

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 10 HP VFD for AHU.- 1set c.Suitable rating MCB with 3 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

Set

CONTROL PANEL TYPE -2, PANEL No- 9 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL & SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

1

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

69

Description of Items Unit c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 5 HP VFD for AHU.- 1set

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No-10 IN AIR HANDLING UNIT WITH VFD & HEATING

COIL

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Qty.

1

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items Unit a.Suitable rating MPCB with outgoing feeder to 2 HP VFD for AHU.- 1set

Control Panel as described above

70 CONTROL PANEL TYPE -2, PANEL No-11 IN AIR HANDLING UNIT WITH VFD & HEATING

COIL

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

1

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

71

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 5 HP VFD for AHU.- 1set

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No-12 IN AIR HANDLING UNIT WITH VFD & HEATING

COIL

Set 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Unit Qty.

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 2 HP VFD for AHU.- 1set

Control Panel as described above

72 CONTROL PANEL TYPE -2, PANEL No-13 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL& SMOKE EXTRACTION FAN

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set 1

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

Unit c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Qty.

73

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 10 HP VFD for AHU.- 1set c.Suitable rating MCB with 3 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB‘s and push button for ON /

OFF status of motor - 1 set

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

CONTROL PANEL TYPE -2, PANEL No-14 IN AIR HANDLING UNIT WITH VFD, HEATING

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

74

Description of Items Unit

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 10 HP VFD for AHU.- 1set c.Suitable rating MCB with 3 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB‘s and push button for ON /

OFF status of motor - 1 set.

Note : This Panel should be provided with a standby feeder for AHU Fan.

Control Panel as described above

CONTROL PANEL TYPE -3, PANEL No-1 IN AIR HANDLING UNIT WITH VFD , HEATER

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

1

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 30 HP VFD for AHU.- 1set

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

75

Description of Items Unit c.Suitable rating MCB for humidifier ( 5 litre / hr. approx.) d.Suitable rating MCB with 1.5 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB‘s and push button for ON /

OFF status of motor - 1 set

Control Panel as described above

CONTROL PANEL TYPE -3, PANEL No-2 IN AIR HANDLING UNIT WITH VFD , HEATING

COIL & HUMIDIFIER

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Set

Qty.

1

76

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 20 HP VFD for AHU.- 1set c.Suitable rating MCB for humidifier ( 5 litre / hr. approx.)

Control Panel as described above

Set

CONTROL PANEL TYPE -3, PANEL No-3 IN AIR HANDLING UNIT WITH VFD, HEATING

COIL, SMOKE EXTRACTION FAN & HUMIDIFIER

1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

Unit Qty.

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building

Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

100 amp 4 pole MCCB type isolator with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-100 amps digital electronic ammeter with selector switch and 100/5 amps 5VA, CL.1CTs – 1 set

77

Phase indicating light through 2 amps SP MCB -3 sets

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a.Suitable rating MPCB with outgoing feeder to 20 HP VFD for AHU.- 1set c.Suitable rating MCB for humidifier ( 10 litre / hr. approx.) d.Suitable rating MCB with 1.5 HP DOL starter and outgoing feeder to Smoke Extraction fan.

Compartment shall contain direct operated digital electronic ammeters of 0-40 amps rang, Auto /

Manual selector switch and ON / OFF trip indicating lamp with MCB‘s and push button for ON /

OFF status of motor - 1 set

Control Panel as described above

CONTROL PANELS TYPE-4 FOR FANS ( TFA,FAN SECTIONS,VANE & TUBE AXIAL FLOW

FANS)

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MPCB and copper earthing, in each panel shall be provided by the electrical contractor.

Set 1

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

The panel shall include the following components & accessories .

a. MCB / MCCB with built-in overload relay and single phase preventor as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

Unit b. Terminal block for power distribution as required.

c. Contactor, over load relay with built in single phasing protection.

d. Phase indicating lights and indicating light for `ON’ status.

e. 96 mm x 96 mm voltmeter and ammeter.

f. Time delay relay for delayed automatic restart of motor (0-180 sec).

g. The Control panel shall be out door type and shall have potential free contacts for fire alarm integration.

h. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation.

The number of control panels shall be as follows.

MPCB with DOL starters suitable for 1-7.5 HP motors

No.

Rates shall also include the following:

All fixing accessories such as brass saddles, brass screws rawl plugs etc.

Jointing by riveting and brazing after riveting in case of copper and welding/ bolting in case of GI earthing.

Cutting chases holes and making good the same wherever required.

Effecting adequate and proper interconnections.

Use of copper thimbles.

Earthing system shall comply to IS: 3043-1987.

All earthing pits shall be interconnected.

All earthing should be Body earthing to Body Earthing & Neutral earthing to Neutral Earthing.

All equipment motors, DB’s, panels to be connected on either ends (double earthing) with suitable strip/ wires.

CABLES, MAINS AND SUB MAINS

Qty.

21

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

78 c d e a b f g

79 a b

Description of Items Unit

Supplying of following 1100 volt grade XLPE insulated sheathed cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

4 Core 6 Sq.mm. (Copper armoured Cable)

4 Core 10 Sq.mm. (Copper armoured Cable)

4 Core 16 Sq.mm. (Aluminium armoured Cable)

4 Core 25 Sq.mm. (Aluminium armoured Cable)

3.5 Core 50 Sq.mm. (Aluminium armoured Cable)

3.5 Core 70 Sq.mm. (Aluminium armoured Cable)

3.5 Core 240 Sq.mm. (Aluminium armoured Cable)

RM

RM

RM

RM

RM

RM

RM

END TERMINATION OF CABLES

Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.

4 Core 6 Sq.mm. (Copper armoured Cable)

4 Core 10 Sq.mm. (Copper armoured Cable)

No.

TOTAL OF SUB HEAD (E)

No.

Qty.

130

130

700

121

154

11

25

35

300

Rate in figures

(Rs.)

Rate in words

(Rs.)

Amount (Rs.)

Item

No.

Description of Items

A.

80

ANIMAL HOUSE

EQUIPMENT

Supply, installing, testing and commissioning of horizontal FAN COIL UNITS (2 PIPE

SYSTEMS), blow thru type, each complete with 3 rows deep Chilled Water Coil, one or more centrifugal fans, cleanable fabric filters, main condensate extended SS drain pans, RA insulated plenum, as described in specifications, casing, coil piping connections, through copper pipes, condensate drain connections, wiring, control wiring in conduit upto thermostat boxes. Fan coil unit shall be factory fitted with valve package comprising of pressure independent Balancing cum Control Valve with integrated 2 way motorized actuator in a single body for modulating operation suitable for static pressure of 1600 kPa and actuator shall be capable of withstanding 400 kPa shut off pressure, 24 V AC incoming power supply, ball valve with Y-strainer at inlet &

Ball valve at outlet and necessary copper coil piping connections. The actuator of modulating valve shall be provided with interface cards to receive 0-10V or 4-20 mA signal from Digital Thermostat.

Unit a

81

The actuator of the valve shall have necessary torque to overcome pressure differential of 4 bars rating. All fan coil units shall be suitable for 220±6% volts, 50 cycles, single phase power supply. Fan coil units shall be of following refrigeration capacities as listed.

1.0 TR nominal capacity - 400 CFM

Double skin TREATED FRESH AIR HANDLING UNITS (in Single /double Decker construction) complete with thermal break profile, Fresh air section with Fresh air manual AL damper with double HDPE insect mesh, Filter sections with G-4 filters & F6

/F9 filters (The Velocity across F6 filters not to exceed 500 FPM), Coil section with CHW coil & heating coil, PVC Moisture Eliminator,DIDW backward Curved Centrifugal Blower ,

Supply air plenum with Supply air manual AL damper, Return Air plenum with return air manual AL damper, Differential pressure nozzles, Exhaust air manual AL damper with double HDPE insect mesh, Magnehelic gauges with pvc tubing across all filters & blower, Service windows as per approved design & Motor for Supply air blower.The

filter stages shall be as specified in the ahu data sheet.EU 13 filters if specified shall be terminal mounted and rates for the same to be quoted as specified under respective items under filter housing/hooded filters.

No.

Qty.

4

Rate in figures

(Rs.)

Limitswitches in Supply fan section for AHU doors and Inspection lamp, Cushy foot mountings, Fire proof double canvass connections (Fungal resistant and Lint free) and

Standard accessories duly a. 8 Row deep cooling & 2 Row deep heating coil of copper tube and aluminum construction sized at maximum face velocity of 500 fpm.

b. Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency.

c. Vibration isolators.

d. Fan outlet velocity not exceeding 10 mps.

Rate in words (Rs.) Amount (Rs.)

g h e f

Item

No.

Description of Items e. Minimum 50 mm (WC) external static pressure after sound attenuators. Total static pressure of AHU shall be checked by Vendor.

g. VFD designed for HVAC applications for supply air fan with built-in PID controller, control panel (keypad & display) , IP-55 enclosure for use on standard centrifugal fans.

The VFDs should not cause any deration of the connected motors and must ensure that class B temperature levels of the connected motors are never exceeded. The display should be in alpha-numeric characters and programming facility should be in userfriendly HVAC terminology. VFD’s shall have builtin harmonic filters.VFD shall be BMS compatible with open protocol communication port, so that complete data can be transported to remote IBMS console.

Unit a b c d

No.

Tag Floor Space

AHU- 1 Ground Air Lock-1,2,Change

Room,Clean Corridor & Clean

Area

AHU- 2 Ground Mortuary

Type CFM TR

FMU 900 7

Max

Motor

1.5/1

Heati ng

6

AHU- 3 Ground Dirty Cage wash, Mortuary

Corridor,Dirty Corridor-1 &2

AHU- 4 Ground Clean store, Quality Control

Room & Quarantine Room

FMU 300 2.5

1.0/1.0

FMU 1300 8

1.5/1.5

FMU 300 2

1.0/1.0

2

8

1

AHU- 5 Ground

Room-1

AHU- 6 Ground

Room-2

FMU 1100 9.4

FMU 1100 9.2

1.5/1

1.5/1

7.7

8.3

AHU- 7 Ground

Room-3

AHU-8 Ground

Room-4

FMU 600

FMU 1100

4.7

9

1.0/1.0

1.5/1

3.3

9.2

Note 1 : All to be provided with VFD's.

2 : AHU No- 1, 2,3 & 4 to be provided Exhaust unit with bagin/bag out hepafilter

3 : AHU No- 5, 6,7 & 8 to be provided H-13 hepa at terminal &, 20 micron filter in h

4 : All AHU to be provided with standby fan arrangement as Animal house are 24 ti l

No.

No.

No.

No.

No.

No.

No.

No.

Qty.

1

1

1

1

1

1

1

1

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

Item

No.

82

83

Description of Items Unit

Supply, installation, testing and commissioning of Fan Filter Unit (FFU) of Stainless

Steel housing with high performance ,directdriven backward curved fan/ motor combination with HEPA (99.99 % efficiency ) filter to achive class of air.All selected FFU shall be having 700 CFM flow rate.

Supply, installation, testing and commissioning of Electronic Self Balancing Valve pressure independent with independent type dynamic balancing valve for AHUs with integrated 2 way modulating control valves in a single body. The actuator shall be capable of accepting 2-10 VDC / 4-20 mA electric signal and shall provide similar transduced feedback output signal to control system for flow measurement. The minimum close off pressure actuator must be 1.5 times shut off head of pump 5 bars whichever is maximum. The valves shall be suitable for following pipe sizes:

No.

Qty.

17 a b

85 a b c

84

32 mm dia

25 mm dia

20 mm dia

Supply, installation, testing and commissioning of cooling Thermostats for various air handling units and fan coil units.

Proportional cooling thermostat at AHU.

Proportional cooling thermostat at FCU.

Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply. All units shall be complete with duct flexible connector and volume control damper.

No.

No.

No.

No.

No.

5

1

10

8

4 a

86 a

Tag

No.

IF-1

Floor Space

Toilet

CFM

150 d

Volume Terminal units, suitable for installtion in horizontal ducts. The casing shall be double skin acoustically lined and constructed with galvanised sheet steel.Should

include all accessories such as single / multileaf damper (with equal % characteristics) etc. actuators, control cabling , thermostat , feed back control cabling upto VFD panel /

DDC Panel in AHU room and any other ancilary requirement for the functioning of the units. Cost of duct mounted Diff. pressure transmitter with cabling upto VFD panel shall also be included.

No.

VAV boxes shall be suitable for following air flow capacitties.

50 -499CFM

Note : Quoted price shall include the following:

No.

1

8

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

g

90 e f a

91 c d a b a b

92 a

Item

No.

87 a

88

Description of Items Unit a. Motorized aluminium construction damper with actuator.

b. Differential pressure sensor c. 220 volts power supply cord with 6 amp. Plug top up to the power socket

Supply, installation, testing and commissioning of INTEGRATOR for VAV boxes, capable of giving industry standard (Modbus / Lon Works / Bacnet) output to BMS system.

Mapping shall be required for monitoring individual room temperature for areas conditioned through VAV boxes. Quoted price shall be inclusive of wiring in GI conduit between integrator and individual VAV Boxes.

Integrator as described above for 8 number VAV Boxes.

Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows :

No.

a

B.

89

150 mm dia 1450 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

No.

TOTAL OF SUB HEAD (A)

PIPING-CHILLED AND CONDENSER WATER

Providing and fixing in position the following MS class ‘C’ pipes cut to required lengths and installed with all welded joints, providing and fixing in position the necessary fittings like elbows, tees and reducers, mating flanges & sockets for BAS:

80 mm dia MS pipes

65 mm dia MS pipes

50 mm dia MS pipes

40 mm dia MS pipes

32 mm dia MS pipes

25 mm dia MS pipes

20 mm dia MS pipes

Providing and fixing in position the following manual butterfly valves (PN 16) :

80 mm dia Valves.

Providing and fixing in position the following manual balancing valves (PN 16) :

80 mm dia Valves.

32 mm dia Valves.

Providing and fixing in position following ball valves (PN 16) :

32 mm dia valves

RM

RM

RM

RM

RM

RM

RM

No.

No.

No.

No.

Qty.

1

3

2

1

1

12

185

4

9

29

242

22

130

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

Item

No.

Description of Items Unit b c

6

94

95

96 b c

93 a

97

98

99

100

25 mm dia valves

20 mm dia valves

Providing and fixing in position the following ‘Y’ Strainers (PN 16) :

32 mm dia valves

25 mm dia valves

20 mm dia valves

Providing and fixing in position the following Drain Valves :

25 mm dia Valves.

Supplying, installation, testing and commissioning of Auto air vents(PN-16).

Supplying, installation, testing and commissioning of Flow Switches .

Providing and fixing in position SS 304 the industrial dial type pressure gauges with gun metal valves.

Providing and fixing in position SS 304 the mercury-in- glass industrial dial type thermometers.

Supply, installation, testing and commissioning of Magnehelic Gauges 100mm dial, range 0 to 60 Pa with SS box, probes & tubes, at different rooms

Providing and fixing in position the following GI class ‘B’ pipes cut to required lengths and installed with all screwed joints, and providing and fixing in position the necessary elbows, tees and reducers as per specifications for AHU / FCU drain.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

a

C.

101

25 mm dia GI pipes

TOTAL OF SUB HEAD (B)

AIR DISTRIBUTION

Supply, installation and testing of Factory fabricated GI sheet metal ducts as per

SMACNA in accordance with the approved shop drawings and as per specifications.

RM

Qty.

2

20

5

1

10

50

4

1

8

32

32

8 a

102

26 gauge galvanised sheet steel

Supply, installation, testing and commissioning of Aluminum Powder Coated Risers with filter fixing arrangement & opening complete with perforated grill & bolts in front.

Sqm a

103

104

105

450mm X 150 mm (3.5m Vertical Length)

No

Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resin sleeve as per the approved shop drawings.

Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air Grilles with volume control dampers in accordance with the approved shop drawings and specifications.

Supply, installation, testing and commissioning of motorised combined smoke & fire damper complete with control panel, inter connecting wiring at locations shown in approved shop drawings and as per specifications.

Sqm

Sqm

Sqm

46

8

1

1.5

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

Item

No.

Description of Items Unit a b

106

107

108

109

110

111 a

D.

112 a

113

Smoke & Fire Damper

Sqm

Control Panel & Wiring(with actuators)

No.

Supply, installation, testing and balancing of Powder coated extruded aluminium construction square / round shape supply air diffusers with removable core & anti smudge ring & volume control dampers as per approved drawings and specifications.

Sqm

Supply, installation, testing and balancing of Powder coated extruded aluminium construction. Square / round shape return air diffusers with removable core, antismudge ring & without volume control damper as per specifications.

Supplying & fixing of opposed blade volume control dampers in supply air duct collars as per approved drawings and specifications.

Sqm

Sqm

Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. louvers with bird screen for exhaust air as per specifications and approved drawings.

Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. louvers with bird screen for fresh air as per specifications and approved drawings.

Hooded Type Terminal Hepa Filter Box with Filter & filter shall be gel seal type & replaceable from Room side, Frame material: Aluminum anodised, Dop efficiency:99.997% down to 0.3 micron with SS Terminal Plate.

Hepa Filter boxes shall be of following sizes.

Sqm

Sqm

610 x 610 x 133 (700 CFM)

No.

TOTAL OF SUB HEAD (C)

THERMAL INSULATION

Supply, installation testing and commissioning of acoustic insulation. Material shall be

Open cell Nitrile rubber and all accessories as per specification.

15 mm thick acoustic lining

Supply and installation of External Thermal closed cell crosslinked polyethelene/Nitrile rubber insulation fire rated for Class 0 as per BS 476 Part 6 : 1989 with Self adhesive backing on ducts as per the approved specifications. Quoted price shall be inclusive of

UV protective coating over exposed to weather ducts.

Sqm

Qty.

2

16

5

10

2.5

3

7

4

23

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

Item

No.

Description of Items Unit c d a b e

115 a

114

13 mm thick insulation for supply & return air ducts

Supplying, installing and testing of 25 mm thick (pre-moulded pipe section of T.F.

quality expanded polystyrene, 24 Kg / M³) insulation on chilled water and condensate drain piping and fitting like valves, flanges union etc. as per the approved shop drawings and specifications.

40 mm dia pipes

32 mm dia pipes

Sqm

RM

RM

25 mm dia pipes

RM

20 mm dia pipes

RM

25 mm dia condensate drain pipes.

Supplying, installing and testing of 50 mm thick (pre-moulded pipe section of T.F.

quality expanded polystyrene, 24 Kg / M3) insulation on chilled water piping and fitting like valves, flanges union, etc. as per the approved shop drawings and specifications.

RM

Qty.

500

29

242

22

130

50

Rate in figures

(Rs.)

Rate in words (Rs.) a b c

80 mm dia pipes

65 mm dia pipes

50 mm dia pipes

E.

116

TOTAL OF SUB HEAD (D)

ELECTRICAL INSTALLATION

CONTROL PANEL PANEL No-1 to 8 IN AIR HANDLING UNIT WITH VFD

Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MPCB in each panel shall be provided by the electrical contractor.

All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for

Connections to Building Automation System.

The panel shall include the following components and accessories.

a. MCCB with over-load relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.

RM

RM

RM

185

4

9

Amount (Rs.)

Item

No.

Description of Items Unit

117 b. Phase indicating lights and indicating for ON status.

c. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.

Incoming

32 amp 4 pole MCB with following accessories.

96 mm x 96 mm 0-500 volt digital voltmeter with selector switches-1 set

0-32 amps digital electronic ammeter with selector switch and 100/5 amps 5VA,

CL.1CTs – 1 set

Phase indicating light through 2 amps SP MCB -3 Set

Bus Bars

150 amps 4 pole copper bus bars with heat shrinkable insulation sleeve.

Outgoing a. 16 Amp MCB with outgoing feeder to 1.5/1.0 HP VFD for AHU.- 1set b.16 Amp MCB with outgoing feeder to 1.5/1.0 HP DOL for AHU.- 1set

Control Panel as described above

CABLES, MAINS AND SUB MAINS

Supplying of following 1100 volt grade XLPE insulated sheathed cable as per specification in existing trenches, cable trays ducts over bed of sand, clamped includes anchor fastners to wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning.

Set a 4 Core 2.5 Sq.mm. (Copper armoured Cable)

Rates shall also include the following:

Providing and fixing junction boxes with covers including painting.

Effecting adequate and proper connections at terminations.

Providing all fixing accessories such as clamping devices nuts, bolts and screws.

Excavation laying of cable filling of sand, brick protection, back filling of earth, watering, ramming and making good.

Earthing system shall comply to IS: 3043-1987.

All cable shall be laid with one diameter gap.

RM

Qty.

8

150

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)

Item

No.

Description of Items

118

All cables shall be IS approved.

Fire retardant paint one meter on both side of wall penetration and at termination as per specifications.

Buried LT cables to be laid atleast 750 mm below ground.

All cut-outs/ Sleeves shall be sealed with fire retardant sealant as per specification.

END TERMINATION OF CABLES

Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.

Unit a 4 Core 6 Sq.mm. (Copper armoured Cable)

TOTAL OF SUB HEAD (E)

Total cost of NON Schedule items (HVAC WORK)-Laboratory+Animal

SCHEDULE-F

No.

Qty.

16

Rate in figures

(Rs.)

Rate in words (Rs.) Amount (Rs.)