NASHVILLE CITY CENTER BUILDING PROFILE Zoning: CC

advertisement
NASHVILLE CITY CENTER
BUILDING PROFILE
Zoning:
CC
Construction
Completion:
12/1988
Area:
Office Tower:
Garage:
Floors:
26 structured floors
Land:
Phase I:
Phase II:
Building Data:
Ceiling grid:
2 x 2 lay-in tegular edge with white
aluminum grid
Window module:
5’-0”
Floor to ceiling:
9’-0”
Floor to sill:
2’-6” and 6” at corners and curve
Window height:
5’-2” and 7’-3” at corners and curve
Window to ceiling:
1’-4”
Floor to floor:
12’-6”
Ceiling to slab:
3’-0”
Estimated population:
3,000
Design criteria:
1/150 RSF
Exterior:
Precast concrete
Granite
Glass:
Double glazed, blue tint exterior, clear interior
Occupancy Data:
Architectural
Finishes:
477,766 RSF 508,250 GSF
156,520 GSF
35,798 sf
22,177 sf and 5,669 sf
Reflectivity:
24% exterior
35% interior
“U” value:
.44 winter
.52 summer
Shade coeff:
.26
% of window:
45%
Lobby:
Restrooms:
Granite walls and floors
Concealed spine ceiling
21’ tall tvs glass
Typical count:
Men:
2 toilets, including 1 handicap
2 urinals
3 sinks
Women:
4 toilets, including 1 handicap
3 sinks
Finishes:
Walls:
Floors:
Vanity tops:
Partitions:
Structural:
Loading Dock:
Mechanical:
Zolatone and paint
Ceramic tile
Granite
Painted metal
General:
Concrete frame with post-tension beams and slabs,
concrete columns, concrete core
Design loads:
50 psf live load
(105 psf for 20’ ring around core)
20 psf interior construction load
Bays:
3 @ 14’ x 50’
Trash:
Compactor
Design conditions:
Outside summer:
Inside summer:
Outside winter:
Inside winter:
95 FDB, 77FWB
75 FBD, 50% humidity
0 FDB
70 FDB
Heating:
Electric reheat boxes
Cooling:
Chilled water provided by DES
1 AHU/floor
6 interior zones
7 perimeter zones
VAV, inlet vanes
Total Envelop:
48,100 BTUs/RSF/yr
Air quantities:
Design: 1 CFM/RSF
Max air: 1.1 CFM/RSF
Energy management:
Controls:
Tenant Lighting:
Electrical:
On/Off
Temperature
Inlet vanes
Supply air temperature
Duct static
Start times
Fixture Type:
MFS Metalux
3 tubes/fixture
2 x 4 parabolic lens
118 watts
Recessed trouffer
Ratio:
1/80 RF
Design:
60 footcandles
Service:
Underground from NES vault
Capacity:
8,000 amps, 277/480 volt
Generator:
600 KW
Wattage/RSF:
Lights:
Power:
Base Building:
Spare:
Total;
2
2.5
8
2
14.5
Elevators:
Quantity
5
5
1
2
Life Safety:
Floors
1 – 15
15 – 27
1 – 27
1 – P5
Speed
500 fpm
700 fpm
450 fpm
350 fpm
Weight
Capacity
3500 lbs
3500 lbs
4520 lbs
3500 lbs
Average
Interval
25 sec
25 sec
na
25 sec
Manufacturer:
Dover
Type:
Gearless
Platform:
Passenger:
Freight:
7’-2” x 6’x2”
6’-6” x 8’-7” x 10’-0”
Door opening:
Passenger:
Freight:
4’ x 8’
4’ x 7’
Sprinkler:
Return
Interval
30 sec
30 sec
na
30 sec
Building:
Garage:
Heads:
Wet
Dry
Semi-recessed in building
Detection:
Smoke detectors in lobbies
Sprinkler heads
Voice Comm:
2-way
Automatic
Stairwell:
Pressurized
Fireboard:
Simplex 4100U