Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140G, 140MG Topic Page Product Line Overview 2 Specifications 4 Approximate Dimensions—125 A, G-Frame 8 Approximate Dimensions—125 A, H-Frame 16 Approximate Dimensions—225 A, I-Frame 24 Approximate Dimensions—250 A, J-Frame 32 Approximate Dimensions—400 A, K-Frame 40 Approximate Dimensions—800 A, M-Frame 46 Approximate Dimensions—1200 A, N-Frame 49 Approximate Dimensions—1200 A, NS-Frame 56 Approximate Dimensions—2000…3000 A, R-Frame 60 Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Product Overview 2 Bulletin 140G Molded Case Circuit Breaker Specifications G-Frame H-Frame I-Frame J-Frame K-Frame M-Frame N-, NS-Frame R-Frame Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Frame Reference Rated Current In Product Overview G-Frame H-Frame I-Frame J-Frame K-Frame M-Frame N-Frame NS-Frame R-Frame 125 A 125 A 225 A 250 A 400 A 800 A 1200 A 1200 A 3000 A 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 No. of Poles Interrupting Rating [kA] 240V 50 65 100 65 100 150 200 200 50 65 65 100 150 65 100 150 125 480V 25 35 65 25 35 65 100 150 25 35 25 35 65 100 35 65 100 150 50 65 100 50 65 100 50 65 100 125 600Y/347V 10 14 25 — 10 10 — — — — — — — 14 18 25 35 10 10 14 18 25 35 25 35 65 100 25 35 42 25 50 65 25 50 65 100 220…240V 65 85 100 65 85 100 150 200 65 85 65 85 100 150 85 100 200 200 85 100 200 85 100 200 85 100 200 130 415V 36 50 70 36 50 70 120 150 36 50 36 50 70 120 50 70 120 200 36 70 100 50 70 120 50 70 120 80 440V 36 50 65 36 50 65 100 150 25 40 36 50 65 100 40 65 100 180 35 50 65 50 65 100 50 65 100 80 690V 6 8 10 10 12 15 18 20 58 10 12 15 20 25 40 70 80 22 25 30 30 42 50 30 42 50 40 250V DC 36 50 70 36 50 70 85 100 36 50 36 50 70 85 — 36 50 65 — — — 500V DC 36 50 70 36 50 70 85 100 36 50 36 50 70 85 36 50 70 100 — — — — 750V DC — — — — 25 36 70 70 16 36 50 — — — 600V 65 100 150 200 100 150 200 200 100 200 200 Breaking Capacity [Icu (kA)] Protection Type Thermal Magnetic — — — Electronic — — Molded Case Switch Auxiliary Contact Alarm Contact AX/AL Combo Trip Unit Contact — — — — Internal Accessories Shunt Trip Shunt Close — — — — — — UV Relay Field Installable End Cap STD STD STD STD STD STD STD STD — 25 mm Phase Barriers STD STD STD STD STD — — — — Insulators STD STD STD STD STD STD — — — Terminal Lugs Extended Terminal — External Accessories Spreader Terminal Rear Terminal — — — — — — Phase barriers Terminal Cover — Direct Rotary — — Variable Depth (Door) — — Internal NFPA 79 — — Flange Operator — — Flange Cable — — Motor Operator — Field Installable Rockwell Automation Publication 140G-TD047A-EN-P 3 Specifications Bulletin 140G Molded Case Circuit Breaker Specifications G-Frame Max. Rated Current [A] Rated insulation voltage, Ui, IEC [V] H-Frame‡ 125 125 160 160 800 1000 NEMA, UL, CSA Interrupting Rating Code G2 G3 G6 G2 G3 G6 H2 H3 H6 H0 H15 H2 H3 H6 H0 H15 240V AC, 50/60Hz [kA] 50 65 100 50 65 100 65 100 150 200 200 65 100 150 200 200 480V AC, 50/60Hz [kA] 25 35 65 25 35 65 25 35 65 100 150 25 35 65 100 150 600Y/347V AC, 50/60Hz [kA] 10 14 25 10 14 25 — — — — — — 600V AC, 50/60 Hz [kA] — — — — 14 18 25 35 42 14 18 35 35 42 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 65 85 100 65 85 100 65 85 100 150 200 65 85 100 150 200 380V AC, 50/60Hz [kA] 36 50 70 36 60 70 36 50 70 120 150 26 50 70 120 150 415V AC, 50/60Hz [kA] 36 50 70 36 50 70 36 50 70 120 150 36 50 70 120 150 440V AC, 50/60Hz [kA] 36 50 65 36 50 65 36 50 65 100 150 36 50 65 100 150 500V AC, 50/60Hz [kA] 30 36 50 36 50 65 30 36 50 60 70 30 36 50 60 70 525V AC, 50/60Hz [kA] 22 35 35 22 35 35 20 25 30 36 50 20 25 30 36 50 690V AC, 50/60Hz [kA] 6 8 10 6 8 10 10 12 15 18 20 10 12 15 18 20 250V DC, 2 Poles in Series [kA] 36 50 70 36 50 70 36 50 70 85 100 36 50 70 85 100 500V DC, 2 Poles in Series [kA] — — — — — — — — — — 500V DC, 3 Poles in Series [kA] 36 50 70 36 50 70 36 50 70 85 100 36 50 70 85 100 750V DC, 3 Poles in Series [kA] — — — — — — — — — — Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 75% (50) 75% 75% 75% 75% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 380V AC, 50/60Hz [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 415V AC, 50/60Hz [kA] 100% 75% 50% 100% 75% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 525V AC, 50/60Hz [kA] 50% 50% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 690V AC, 50/60Hz [kA] 75% 50% 50% 75 50 50% 100% 100% 100% 75% 75% 100% 100% 100% 75% 75% 250V DC, 2 Poles in Series [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 500V DC, 2 Poles in Series [kA] — — — — — — — — — — 500V DC, 3 Poles in Series [kA] 100% 100% 75% 100% 100% 75% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 750V DC, 3 Poles in Series [kA] — — — — — — — — — — Mechanical Life Electrical Life @ 415V AC [No. Ops] 25 000 25 000 [Ops/hr] 240 240 [No. Ops] 8000 8000 [Ops/hr] 120 120 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 76.2x70x130 3 poles: 90x82.5x130 [mm] 4 poles: 101.6x70x130 4 poles: 120x82.5x130 IEC version with a 160 A Icu rating ‡ Cannot be reverse fed above 480V 4 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Specifications I-Frame J-Frame‡ Max. Rated Current [A] 225 250 Rated insulation voltage, Ui, IEC [V] 800 1000 NEMA, UL, CSA Interrupting Rating Code I2 I3 J2 J3 J6 J0 240V AC, 50/60Hz [kA] 50 65 65 100 150 200 480V AC, 50/60Hz [kA] 25 35 25 35 65 100 600Y/347V AC, 50/60Hz [kA] 10 10 — — — — 600V AC, 50/60 Hz [kA] — — 14 18 25 35 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 50 85 65 85 100 150 380V AC, 50/60Hz [kA] 36 50 36 50 70 120 415V AC, 50/60Hz [kA] 36 50 36 50 70 120 440V AC, 50/60Hz [kA] 25 40 36 50 65 100 500V AC, 50/60Hz [kA] 20 30 30 36 50 60 525V AC, 50/60Hz [kA] 13 20 20 25 45 50 690V AC, 50/60Hz [kA] 5 6 10 12 15 20 250V DC, 2 Poles in Series [kA] 36 50 36 50 70 85 500V DC, 2 Poles in Series [kA] — — 36 50 70 85 500V DC, 3 Poles in Series [kA] 36 50 36 50 70 85 750V DC, 3 Poles in Series [kA] — — — — — — Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 380V AC, 50/60Hz [kA] 75% 50% (27) 100% 100% 100% 100% 415V AC, 50/60Hz [kA] 75% 50% (27) 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 525V AC, 50/60Hz [kA] 75% 50% 100% 100% 100% 100% 690V AC, 50/60Hz [kA] 50% 50% 100% 100% 100% 100% 250V DC, 2 Poles in Series [kA] 100% 75% 100% 100% 100% 100% 500V DC, 2 Poles in Series [kA] — — 100% 100% 100% 100% 500V DC, 3 Poles in Series [kA] 100% 75% 100% 100% 100% 100% 750V DC, 3 Poles in Series [kA] — — — — — — Mechanical Life Electrical Life @ 415V AC [No. Ops] 25 000 25 000 [Ops/hr] 240 240 [No. Ops] 8000 8000 [Ops/hr] 120 120 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 105x70x150 3 poles: 105x82.5x160 [mm] 4 poles: 140x70x150 4 poles: 140x82.5x160 ‡ Cannot be reverse fed above 600V Rockwell Automation Publication 140G-TD047A-EN-P 5 Specifications Bulletin 140G Molded Case Circuit Breaker Specifications K-Frame M-Frame Max. Rated Current [A] 400 800 Rated insulation voltage, Ui, IEC [V] 1000 1000 NEMA, UL, CSA Interrupting Rating Code K3 K6 K0 K15 K5 K6 K0 240V AC, 50/60Hz [kA] 100 150 200 200 100 200 200 480V AC, 50/60Hz [kA] 35 65 100 150 50 65 100 600Y/347V AC, 50/60Hz [kA] — — — — — — — 600V AC, 50/60 Hz [kA] 25 35 65 100 25 35 42 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 85 100 200 200 85 100 200 380V AC, 50/60Hz [kA] 50 70 120 200 50 70 100 415V AC, 50/60Hz [kA] 50 70 120 200 50 70 100 440V AC, 50/60Hz [kA] 40 65 100 180 45 50 80 500V AC, 50/60Hz [kA] 30 50 85 150 35 50 65 525V AC, 50/60Hz [kA] — — — — — — — 690V AC, 50/60Hz [kA] 25 40 70 80 22 25 30 250V DC, 2 Poles in Series [kA] — — — — — — — 500V DC, 2 Poles in Series [kA] 36 50 70 100 — — — 500V DC, 3 Poles in Series [kA] — — — — — — — 750V DC, 3 Poles in Series [kA] 25 36 70 70 20 36 50 Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 380V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 415V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 440V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 500V AC, 50/60Hz [kA] 100% 100% 100% 100% 100% 100% 75% 525V AC, 50/60Hz [kA] — — — — — — — 690V AC, 50/60Hz [kA] 100% 100% 100% 100% 75% 75% 75% 250V DC, 2 Poles in Series [kA] — — — — — — — 500V DC, 2 Poles in Series [kA] 100% 100% 100% 100% — — — 500V DC, 3 Poles in Series [kA] — — — — — — — 750V DC, 3 Poles in Series [kA] 100% 100% 100% 100% 75% 75% 75% Mechanical Life [No. Ops] [Ops/hr] Electrical Life @ 415V AC [No. Ops] [Ops/hr] 20000 20000 120 120 7000 (400 A) - 5000 (630 A) 7000 (630 A) - 5000 (800 A) - 4000 (1000 A) 60 60 Ambient Temp. w/out derating ºF [ºC] 104 ºF [40 ºC] 104 ºF [40 ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 140x108.5x205 3 poles: 210x103.5x268 [mm] 4 poles: 185x103.5x205 4 poles: 280x103.5x268 6 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Specifications N-, NS-Frame R-Frame Max. Rated Current [A] 1200 2000/2500/3000 Rated insulation voltage, Ui, IEC [V] 1000 1000 NEMA, UL, CSA Interrupting Rating Code N5 N6 N0 R12 240V AC, 50/60Hz [kA] 65 100 150 125 480V AC, 50/60Hz [kA] 50 65 100 125 600Y/347V AC, 50/60Hz [kA] — — — — 600V AC, 50/60 Hz [kA] 25 50 65 100 IEC 60947-2 Rated ultimate short-circuit breaking capacity, Icu 220/230/240V AC, 50/60Hz [kA] 85 100 200 130 380V AC, 50/60Hz [kA] 50 70 120 80 415V AC, 50/60Hz [kA] 50 70 120 80 440V AC, 50/60Hz [kA] 50 65 100 80 500V AC, 50/60Hz [kA] 40 50 85 40 525V AC, 50/60Hz [kA] — — — — 690V AC, 50/60Hz [kA] 30 42 50 40 250V DC, 2 Poles in Series [kA] — — — — 500V DC, 2 Poles in Series [kA] — — — — 500V DC, 3 Poles in Series [kA] — — — — 750V DC, 3 Poles in Series [kA] — — — — 100% Rated service short-circuit breaking capacity, Ics 220/230/240V AC, 50/60Hz [kA] 100% 100% 100% 380V AC, 50/60Hz [kA] 100% 100% 100% 415V AC, 50/60Hz [kA] 100% 100% 100% 100% 440V AC, 50/60Hz [kA] 100% 100% 100% 100% 500V AC, 50/60Hz [kA] 100% 100% 75% 100% 525V AC, 50/60Hz [kA] — — — — 690V AC, 50/60Hz [kA] 100% 75% 75% 100% 250V DC, 2 Poles in Series [kA] — — — — 500V DC, 2 Poles in Series [kA] — — — — 500V DC, 3 Poles in Series [kA] — — — — 750V DC, 3 Poles in Series [kA] — — — — Mechanical Life [No. Ops] [Ops/hr] Electrical Life @ 415V AC [No. Ops] [Ops/hr] 10000 15000 60 60 2000 4500 (2000 A) - 4000 (2500 A) - 3000 (3200 A) 60 60 104 ºF [40 ºC] 104 ºF [40 ºC] Ambient Temp. w/out derating ºF [ºC] Storage Temperature ºF [ºC] -40...+176 ºF [-40…+80 ºC] -40...+176 ºF [-40…+80 ºC] Dimensions [Width/Depth/Height] [mm] 3 poles: 210x154(N)/178(NS)x268 3 poles: 427x282x382 [mm] 4 poles: 280x154(N)/178(NS)x268 4 poles: 553x282x382 Rockwell Automation Publication 140G-TD047A-EN-P 7 Approximate Dimensions — 125 A, G-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Description No. of Poles A With flange 3…4 74 Without flange 3…4 71 3…4 79 ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided ♣ Optional front cover for DIN Rail 8 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, G-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-G-ECM, -ECM4 Terminals Mounting bracket ♠ Required 25 mm insulating phase barriers provided Rockwell Automation Publication 140G-TD047A-EN-P 9 Approximate Dimensions — 125 A, G-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-G-EXT3, -EXT4 Extended Terminals ‡ Extended terminals § Optional Terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ∇ Internal insulating plate required with phase barriers (customer provided) when mounted through the enclosure door Cat. Nos. 140G-G-EXS3, -EXS4 Spreader Terminals ♣ Extended spread terminals for busbar connection ♦ Required 200 mm insulating phase barriers provided 10 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, G-Frame Cat. Nos. 140G-G-TLC13, 140G-G-TLC14 Terminals (Copper Only Lug) ‡ Front terminals Cat. No. 140G-G-MTL63, -MTL64 Terminal (Multi-Cable Terminal Lug) ♣ Required terminal covers with IP40 protection provided Δ Terminal lugs for multi-cable connection Cat. No. 140G-G-RMB or 140G-G-RMY Direct Rotary Operating Handle Drilling: See Detail “A” Min. door rotation radius ‡ Rotary handle operating mechanism on molded case circuit breaker ♣ Door drilling template with direct rotary handle ♦ Required 25 mm insulating phase barriers provided Rockwell Automation Publication 140G-TD047A-EN-P 11 Approximate Dimensions — 125 A, G-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-G-RVM…Variable Depth Rotary Mechanism with Door Mounted Handle 2.68 [68.0] 6.37 [161.8] 12 in. shaft: 11.38 [289] 21 in. shaft: 20.38 [517.8] 0.08 [2.0] 0.41 [10.5] 1.54 [39.0] 1.54 [39.0] 5.12 [130.0] 0.57 [14.5] 5.12 [130.0] 0.57 [14.5] 3.98 [101.2] 3.00 [76.2] 3-Pole Front of Cover 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) 12 0.07 [1.8] 1.41 [35.8] (2) - ø 5.5 (2) - ø 0.22) Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, G-Frame Cat. No. 140G-G-EOP… Motor Operator ♣ Motor operator Δ Door drilling template (without flange) ♦ Door drilling template (with flange) ♠ Cable connection ∇ Required 25 mm insulating phase barriers provided Rockwell Automation Publication 140G-TD047A-EN-P 13 Approximate Dimensions — 125 A, G-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-G-ELP1603 Residual Current Release Module for 3-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 3 74 Without flange 3 71 Terminals for busbar connection ‡ IP40 terminal covers § Drilling template — door with direct rotary mechanism and flange ♣ Drilling template — door with direct rotary mechanism, without flange Δ Drilling template — molded case circuit breaker mounting on mounting plate 14 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, G-Frame Cat. No. 140G-G-ELP1604 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 74 Without flange 4 71 Terminals for busbar connection ‡ IP40 terminal covers § Drilling template — door with direct rotary mechanism and flange ♣ Drilling template — door with direct rotary mechanism, without flange Δ Drilling template — molded case circuit breaker mounting on mounting plate Rockwell Automation Publication 140G-TD047A-EN-P 15 Approximate Dimensions — 125 A, H-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Description No. of Poles A With flange 3…4 86 3…4 83.5 3…4 91.5 Without flange ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phase barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket § Required 25 mm insulating phase barriers provided 16 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, H-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-H-ECM, -ECM4 Terminals Required 25 mm insulating phase barriers provided ‡ Front terminals for busbar connection Rockwell Automation Publication 140G-TD047A-EN-P 17 Approximate Dimensions — 125 A, H-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-H-EXT3, -EXT4 Extended Terminals 3 Poles § Extended terminals ♣ Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ♦ Required internal insulating plate provided for breakers with Ue>440V ♠ Drilling template for 3-pole molded case circuit breaker, Ue>440V (required) ∇ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required) 18 Rockwell Automation Publication 140G-TD047A-EN-P 4 Poles Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, H-Frame Cat. Nos. 140G-H-EXS3, -EXS4 Spreader Terminals 4 Poles 3 Poles Drilling template for 3-pole molded case circuit breaker, Ue>440V (required) ‡ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required) § Extended spread terminals ♣ Required 200 mm insulating phase barriers provided Δ Required insulated plate provided for breakers, with Ue>440V Rockwell Automation Publication 140G-TD047A-EN-P 19 Approximate Dimensions — 125 A, H-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-H-TLC13, -TLC14 Terminals § Required 25 mm insulating phase barriers provided ♦ Copper terminals. Cat. Nos. 140G-H-MTL63, -MTL64 Terminals ♦ Multi-cable terminals Cat. No. 140G-H-RMB, -RMY Direct Rotary Operating Handle ‡ Rotary handle operating mechanism on molded case circuit breaker ♦ Required 25 mm insulating phase barriers provided 20 Rockwell Automation Publication 140G-TD047A-EN-P Approximate Dimensions — 125 A, H-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-H-RVM… Rotary Handle Operating Mechanism — Door Mounted 3.17 [80.5] 12 in. shaft: 10.89 [276.5] 21 in. shaft: 19.89 [505.1] 6.86 [174.3] 1.44 [36.5] 0.08 [2.0] 1.57 [40.0] 1.28 [32.5] 1.28 [32.5] 5.12 [130.0] 5.12 [130.0] 0.89 [22.5] 0.89 [22.5] 4.88 [124.0] 3.54 [90.0] 3-Pole Front of Cover 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Rockwell Automation Publication 140G-TD047A-EN-P 21 Approximate Dimensions — 125 A, H-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-H-EOP… Motor Operator 3 Poles 4 Poles Motor operator Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate ♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate ♠ Required 25 mm insulating phase barriers provided 22 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 125 A, H-Frame Cat. No. 140G-H-ELP1604 Residual Current Release Module 4 Poles Description No. of Poles A With flange 4 86 Without flange 4 83.5 Residual current module ‡ Front terminals ♠ Drilling template — door with direct rotary mechanism and flange ∇ Drilling template — door with direct rotary mechanism, without flange & Drilling template — molded case circuit breaker mounting on mounting plate Rockwell Automation Publication 140G-TD047A-EN-P 23 Approximate Dimensions — 225 A, I-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Description No. of Poles A With flange 3…4 74 3…4 71 3…4 79 Without flange ‡ Overall dimensions of optional wiring ducts § Required 25 mm insulating phases barriers provided DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket ‡ Optional wiring ducts § Optional front cover for DIN Rail ♣ Required 25 mm insulating phase barriers provided 24 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 225 A, I-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-I-ECM, -ECM4 Terminals Front terminals for busbar connection ‡ Required 25 mm insulating phase barriers provided Cat. Nos. 140G-J-EXS3, -EXS4 Terminals ♣ Extended spread terminals ♦ Required 200 mm insulating phase barriers provided Rockwell Automation Publication 140G-TD047A-EN-P 25 Approximate Dimensions — 225 A, I-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-I-EXT3, -EXT4 Extended Terminals ‡ Extended terminals § Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided Cat. Nos. 140G-I-TLA1A3, -TLA1A4 Terminals 30…150 mm2 terminals ‡ Required 25 mm insulating phase barriers provided Cat. Nos. 140G-I-TLA3, -TLA4 Terminals 1x90…185 mm2 terminal § Required 25 mm insulating phase barriers provided 26 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 225 A, I-Frame Cat. Nos. 140G-I-TLC13, -TLC14 Terminals ♦ Front terminals & Required 25 mm insulating phase barriers provided Cat. Nos. 140G-I-MTL63, -MTL64 Terminals § Optional terminal covers with IP40 protection provided Δ Multi-cable terminal lugs Rockwell Automation Publication 140G-TD047A-EN-P 27 Approximate Dimensions — 225 A, I-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-G-RMB, -RMY Direct Rotary Operating Handle (For I- and G-Frame Molded Case Circuit Breaker) Drilling: See Detail “A” Min. door rotation radius ‡ Rotary handle operating mechanism on molded case circuit breaker ♣ Door drilling template with direct rotary handle ♦ Required 25 mm insulating phase barriers provided Cat. No. 140G-G-EOP… Motor Operator (I-Frame) ♣ Motor operator ♠ Required 25 mm insulating phase barriers provided 28 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-G-RVM… Variable Depth Rotary Handle Operating Mechanism (For I-Frame Molded Case Circuit Breaker) 12 in. shaft: 11.38 [289] 21 in. shaft: 20.38 [517.8] 6.37 [161,8] 0.08 [2,0] 0.61 [15,5] 0.61 [15,5] 2.20 [55,9] 2.20 [55,9] 5.91 [150,0] 0.61 [15,6] Front of Cover 0.08 [2,0] 5.91 [150,0] 0.20 [5,1] 4.13 [105,0] 5.51 [140,0] 3-Pole 4-Pole 50 (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Rockwell Automation Publication 140G-TD047A-EN-P 29 Approximate Dimensions — 225 A, I-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-I-ELP2503 Residual Current Release Module Description No. of Poles A With flange 3 74 Without flange 3 71 Terminals for cable connection ‡ Terminal covers with IP40 protection Δ Drilling template — molded case circuit breaker mounting on mounting plate 30 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 225 A, I-Frame Cat. No. 140G-I-ELP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 74 Without flange 4 71 Terminals for busbar connection ‡ Terminal covers with IP40 protection Δ Drilling template — molded case circuit breaker mounting on mounting plate Rockwell Automation Publication 140G-TD047A-EN-P 31 Approximate Dimensions — 250 A, J-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker ‡ Overall dimensions of optional wiring ducts. § Required 25 mm insulating phase barriers provided. Description No. of Poles A With flange 3…4 86 3…4 83.5 3…4 91.5 Without flange DIN Rail Mounted Molded Case Circuit Breaker Mounting bracket § Required 25 mm insulating phase barriers provided 32 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 250 A, J-Frame Drilling Template for Molded Case Circuit Breaker Mounting 3 Poles 4 Poles Cat. Nos. 140G-J-ECM, -ECM4 Terminals Required 25 mm insulating phase barriers provided ‡ Terminals for busbar connection Rockwell Automation Publication 140G-TD047A-EN-P 33 Approximate Dimensions — 250 A, J-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-J-EXT3, -EXT4 Extended Terminals 3 Poles 4 Poles § Extended terminals ♣ Optional terminal covers with IP40 protection provided Δ Required 100 mm insulating phase barriers provided ♦ Required insulating plate provided for molded case circuit breaker with Ue>440V ♠ Drilling template for 3-pole molded case circuit breaker ∇ Drilling template for 4-pole molded case circuit breaker 34 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 250 A, J-Frame Cat. Nos. 140G-J-EXS3, -EXS4 Spreader Terminals 3 Poles 4 Poles Drilling template for 3-pole molded case circuit breaker ‡ Drilling template for 4-pole molded case circuit breaker § Extended spread terminals ♣ Required 200 mm insulating phase barriers provided Δ Required insulated plate provided for molded case circuit breaker with Ue>440V Cat. Nos. 140G-J-TLA13, -TLA14 Terminal Lugs Aluminum Conductor: 6…350 MCM (2.5…185 mm) Copper Conductor: 10…350 MCM (6…185 mm) 1x1…185 mm2 front terminal § Required 25 mm insulating phase barriers provided Cat. Nos. 140G-J-TLC13, -TLC14 Terminal Lugs 10…350 MCM (6…185 mm) External terminals ♣ Required 25 mm insulating phase barriers provided Rockwell Automation Publication 140G-TD047A-EN-P 35 Approximate Dimensions — 250 A, J-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-J-MTL63, -MTL64 Terminals ‡ Multi-cable terminal lugs § Optional terminal covers with IP40 protection provided ‡ Rotary handle operating mechanism on molded case circuit breaker ♦ Required 25 mm insulating phase barriers provided Min. Door Rotation Radius Flange Mount Drill Template 36 Rockwell Automation Publication 140G-TD047A-EN-P Approximate Dimensions — 250 A, J-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-H-RVM… Variable Depth Rotary Handle Operating Mechanism (For J-Frame Molded Case Circuit Breaker) 3.2 [83] 6.86 [174.3] 12 in. shaft: 10.89 [276.5] 21 in. shaft: 19.89 [505.1] 0.08 [2.0] 0.61 [15.5] 1.99 [50.5] 1.85 [47.0] 1.85 [47.0] 6.30 [160.0] 0.89 [22.5] 6.30 [160.0] 0.89 [22.5] 4.13 [105.0] Front of Cover 5.51 [140.0] 3-Pole 50 4-Pole (1.97) ø 35 (ø 1.37) 25 (0.98) 25 (0.98) 25 (0.98) ø 35 (ø 1.37) 31.5 (1.23) 63 (2.47) 50 (1.97) mm (in.) (2) - ø 5.5 (2) - ø 0.22) (2) - ø 5.5 (2) - ø 0.22) Rockwell Automation Publication 140G-TD047A-EN-P 37 Approximate Dimensions — 250 A, J-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-H-EOP… Motor Operator – For H- & J-Frame Molded Case Circuit Breaker 3 Poles 4 Poles Motor operator § Drilling template for door with motor operator with flange ♣ Drilling template for door with motor operator without flange Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate ♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate ♠ Required 25 mm insulating phase barriers provided 38 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 250 A, J-Frame Cat. No. 140G-J-EP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Description No. of Poles A With flange 4 86 Without flange 4 83.5 Residual current module ‡ Front terminals ♠ Drilling template — door with direct rotary mechanism and flange ∇ Drilling template — door with direct rotary mechanism, without flange & Drilling template — molded case circuit breaker mounting on mounting plate Rockwell Automation Publication 140G-TD047A-EN-P 39 Approximate Dimensions — 400 A, K-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker Overall dimensions with cabled accessories mounted ‡ Overall dimensions with cabled auxiliary contacts mounted Drilling Templates for Molded Case Circuit Breaker Mounting Flange for compartment door Drilling template for compartment door with flange (3…4 poles) Drilling template for mounting plate 3 Poles 40 4 Poles Rockwell Automation Publication 140G-TD047A-EN-P without flange (3…4 poles) Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-K-ECM, -ECM4 Terminals Approximate Dimensions — 400 A, K-Frame Cat. Nos. 140G-K-TLC13, -TLC14 Terminals 250…500 MCM (120…240 mm2) Cat. Nos. 140G-K-TLA23, -TLA24, -TLC23, -TLC24 Terminals (2) 2/0…250 MCM ((2) 95…120 mm2) Terminal covers with IP40 protection Cat. Nos. 140G-K-TLA13, -TLA14 Terminals 250…500 MCM (120…240 mm2) Rockwell Automation Publication 140G-TD047A-EN-P 41 Approximate Dimensions — 400 A, K-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-K-EXT3, -EXT4 Extended Terminals Terminal covers with IP40 protection ‡ Required 100 mm insulating phase barriers provided Cat. Nos. 140G-K-EXS3, -EXS4 Spreader Terminals Required 200 mm insulating phase barriers provided 42 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 400 A, K-Frame Cat. No. 140G-K-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted Rotary handle operating mechanism on molded case circuit breaker ‡ Padlock device for open position (max. 3 padlocks; user provided) § Dimensions with cabled early make contact ♣ Compartment door lock Cat. No. 140G-K-ELP Residual Current Release Module for 4-Pole Molded Case Circuit Breakers Overall dimensions with cabled auxiliary contacts mounted Rockwell Automation Publication 140G-TD047A-EN-P 43 Approximate Dimensions — 400 A, K-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-K-RVM… Variable Depth Rotary Handle Operating Mechanism 4.00 [101.5] 4.80 [122.0] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.01 [0.3] 0.14 [3.5] 0.78 [19.7] 0.92 [23.3] 2.69 [68.3] 2.66 [67.6] 8.07 [205.0] 0.78 [19.7] 8.07 [205.0] 0.80 [20.4] 5.49 [139.5] 7.32 [186.0] 3-Pole 4-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) 44 Front of Cover Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 800 A, M-Frame Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 210 (3P) 8.27 115 4.53 103.5 4.07 140 = 5.51 = 61.25 2.41 2.7 0.11 70 2.76 5.5 0.22 2.7 0.11 105 4.13 268 10.55 134 5.28 70 2.76 105 4.13 70 2.76 3 0.12 280 (4P) 11.02 107 4.21 159 6.26 2 0.08 Overall dimensions with cabled accessories mounted ‡ Overall dimensions with cabled auxiliary contacts mounted Drilling Templates for Molded Case Circuit Breaker Mounting 66.75 2.63 149 = 5.87 = 116 4.57 138 5.43 77.75 3.06 152 = 5.98 = 62.25 2.45 Drilling template for compartment door 142 = 5.59 = 107 4.21 Flange for compartment door with flange without flange Drilling template for mounting plate 70 2.76 5.5 - M5 Ø 0.22 35 1.38 118.5 4.67 140 5.51 237 9.33 237 9.33 118.5 4.67 5.5 - M5 Ø 0.22 3 Poles 4 Poles Rockwell Automation Publication 140G-TD047A-EN-P 45 Approximate Dimensions — 800 A, M-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-M-ECM Terminals Cat. No. 140G-M-TLA23, -TLA24, -TLC23, -TLC24 Terminals 70 2.76 MA X 40 50 1.97 20 0.79 59 2.32 25.5 1 19 Ø 0.75 45 1.77 33.5 1.32 90 3.54 45 1.77 8 0.31 116 4.57 116 4.57 116 4.57 88 3.46 45 1.77 88 3.46 45 1.77 13 Ø 0.51 116 4.57 116 4.57 88 3.46 23 0.9 45 1.77 90 3.54 13 Ø 0.51 50 1.97 8 0.31 230.5 9.07 134 5.28 134 5.28 167.5 6.59 134 5.28 45 1.77 90 3.54 88 3.46 23 0.9 116.5 4.59 53.5 2.11 14 0.55 120.5 4.74 Cat. Nos. 140G-M-EXSLI3, -EXSLO3, -EXS4 Spreader Terminals 70 2.76 116.5 4.59 70 2.76 70 2.76 134 5.28 Cat. Nos. 140G-M-EXT3, -EXT4 Extended Terminals 70 2.76 70 2.76 39 1.53 MIN5 MAX10 120.5 4.74 MAX 12 23 0.9 ±0 .1 18 MIN 22.5 0.89 6.5 Ø 0.26 Cat. No. 140G-M-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted 33 1.3 5.5 0.22 140 5.51 Ø4 Ø 0.16 190 7.48 146.5 5.77 103.5 4.07 5.5 0.22 42.5 1.67 84.5 3.33 140 5.51 5.5 0.22 2.7 0.11 ≥3 ≥ 0.12 140.5 5.53 ≤2 ≤ 0.08 2.7 0.11 Rotary handle operating mechanism on molded case circuit breaker ‡ Padlock device for open position (max. 3 padlocks; user provided) § Dimension with cabled early make contact ♣ Compartment door lock 41.5 1.63 Drilling template for compartment door 43 1.69 14 0.55 43 1.69 14 0.55 148.5 5.85 R min. 200 R min. 7.87 with flange 46 Rockwell Automation Publication 140G-TD047A-EN-P 96.5 3.8 142 5.59 85.5 3.37 5 5.94 90 3.54 100.25 3.95 173 6.81 152 5.98 96.5 38 Flange for compartment door 142 5.59 R min. 200 R min. 7.87 without flange Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 800 A, M-Frame Cat. No. 140G-M-RVM… Variable Depth Rotary Handle Operating Mechanism 3.80 [96.5] 8.74 [221.9] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.24 [6.1] 1.38 [35.0] 2.99 [75.9] 10.55 [268.0] 1.68 [42.6] 8.23 [209.0] 3-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) Front of Cover Rockwell Automation Publication 140G-TD047A-EN-P 47 Approximate Dimensions — 800 A, M-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-M-EOP, -ECOP Motor Operator 1.1 Nm 140 = 5.51 = 5.5 5.5 0.22 0.22 140 5.51 70 2.76 191.5 7.54 5.5 0.22 Overall dimension with cabled accessories mounted ‡ Overall dimension with cabled auxiliary contacts mounted 3 0.12 222 8.74 233 9.17 Drilling template for compartment door Flange for compartment door 152 = 5.98 = Drilling template for mounting plate 118.5 4.66 Ø 5.5 - M5 Ø 0.22 - M5 237 9.33 237 9.33 118.5 4.66 48 70 2.76 142 = 5.59 = 142 5.59 71.25 2.8 151 5.94 75.75 2.98 173 6.81 86.5 3.4 148.5 = 5.85 = R min. 200 R min. 7.87 with flange Ø 5.5 - M5 Ø 0.22 - M5 2 0.08 140 5.51 35 1.38 Rockwell Automation Publication 140G-TD047A-EN-P R min. 200 R min. 7.87 without flange Approximate Dimensions — 1200 A, N-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 103.6 4.08 70 2.76 18.75 0.74 14.5 0.58 105 4.13 204 8.03 268 10.55 102 4.02 70 2.76 10 0.39 10 0.39 24 0.94 6 0.24 134 5.28 147.5 5.81 70 2.76 50 1.97 25 0.98 125 4.92 97 3.82 10 0.39 2 0.08 154.25 6.07 152 5.98 225 8.86 125 4.92 160 6.3 280 11.02 3 0.12 210 8.27 Description A With flange 125…141 Without flange 147 190 7.48 206 8.11 Front terminals for flat connection ‡ Busbars § Door flange Δ Tightening torque: 18 N•m ♠ Padlock (optional) ∇ Tightening torque: 2.5 N•m & Terminal for auxiliary contacts Rockwell Automation Publication 140G-TD047A-EN-P 49 Approximate Dimensions — 1200 A, N-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Drilling Templates for Molded Case Circuit Breaker Mounting Flange for compartment door Drilling template for compartment door 268 10.55 192 7.56 with reduced flange 206 8.11 103 4.05 144.5 5.69 208 8.19 144.5 5.69 151 5.94 263 10.35 35.25 1.39 138 5.43 Front 190 x 105 241 9.49 226 8.9 203 7.99 19.75 0.78 107 4.21 24.25 0.95 116 4.57 304 11.97 152 5.98 201 7.91 2 0.08 155 6.1 § Door flange # Reduced flange for compartment door Ø 4 n°7 HOLES Ø 0.16 with flange 122.5 4.82 Drilling template for mounting plate 245 9.65 35 1.38 Ø 5.5 - M5 Ø 0.22 50 No. of Poles C 3 70 4 140 Rockwell Automation Publication 140G-TD047A-EN-P Front 206 x 204 Approximate Dimensions — 1200 A, N-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-N-RVM… Variable Depth Rotary Handle Operating Mechanism 3.82 [97.0] 10.75 [273.0] 12 in. shaft: 17.75 [450.8] 21 in. shaft: 26.75 [679.4] 0.93 [23.6] 1.73 [44.0] 1.38 [35.0] 4.82 [122.5] 2.41 [61.1] 4.83 [122.6] 10.55 [268.0] 10.55 [268.0] 0.83 [21.0] 0.83 [221.1] 8.27 [210.0] 11.02 [280.0] 3-Pole 4-Pole 75 (2.95) 37.5 (1.47) mm (in.) 37.5 (1.47) 65 ø (2.56 ø) 75 (2.95) 4 - 5.5 ø (4) - 0.22 ø) Front of Cover Rockwell Automation Publication 140G-TD047A-EN-P 51 Approximate Dimensions — 1200 A, N-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-N-TLH3, -TLV3, TLH4, TLV4 Terminals 109 4.29 218 8.58 237 9.34 273 10.75 118.5 4.66 44 1.73 59 2.32 70 2.76 70 2.76 44 1.73 25 0.98 1 Ø1 3 .4 Ø0 46.5 1.84 59 2.32 46.5 1.84 70 2.76 Ø Ø 11 0.4 3 25 0.98 15 0.59 18.5 0.73 15 0.59 70 2.76 No. of Poles B C 3 70 192.5 4 140 262.5 70 2.76 70 2.76 Rear horizontal terminals ‡ Rear vertical terminals ♠ Tightening torque: 20 N•m Drilling template for mounting plate 35 1.38 52.5 2.07 122.5 4.82 245 9.65 8 0.31 39.75 1.56 61.25 2.41 17.5 0.69 Ø 5.5 - M5 Ø 0.22 52 Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-EXT3, -EXT4 Extended Front Terminals 320 12.6 25 0.98 70 2.76 Y 125 70 4.92 2.76 44 1.73 100 3.94 29.5 29.5 15 0.59 1 Ø 11 Ø 0.43 79 3.11 118.5 4.66 250 9.84 12.5 0.49 160.5 6.32 199.5 7.85 229 9.02 25 0.98 70 2.76 250 9.84 X X X Extended terminals ∇ Required 100 mm insulating phase barriers provided ♠ Tightening torque: 18 N•m & Required insulating plate provided for molded case circuit breaker X Cat. Nos. 140G-N-EXSL13 Top (3-Pole), 140G-N-EXS4 (4-Pole) Rear Spread Terminals 116 / 4.57 116 90 / 3.54 90 / 3.54 / 4.57 Ø Ø 0 13 .51 100 116 / 4.57 40.5 90 / 3.54 45 1.77 79 3.11 15 55 2.17 100 3.94 118.5 258 10.16 334 33 1.3 45 1.77 268 10.55 134 5.28 79 3.11 100 3.94 23 0.91 144 5.67 189 7.44 45 1.77 45 1.77 147.5 5.81 ~200 ~10.16 23 X X ‡ Extended spread terminals # Required 200 mm insulating phase barriers provided ♠ Tightening torque: 18 N•m § Terminal for auxiliary contacts & Required insulating plate provided for molded case circuit breaker Rockwell Automation Publication 140G-TD047A-EN-P 53 Approximate Dimensions — 1200 A, N-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. No. 140G-N-RMB, -RMY Rotary Handle Operating Mechanism 280 11.02 210 8.27 70 70 70 70 6 0.24 97 3.82 134 5.28 147.5 5.81 33 1.30 18.75 0.74 268 10.55 204 8.03 43.5 1.71 2 0.08 2 0.08 Description A With flange 125…141 Without flange 147 154 6.06 190 7.48 206 8.11 Rotary handle operating mechanism on molded case circuit breaker ‡ Compartment door interlock § Door flange ♦ Tightening torque: 2.5 N•m ♠ Terminal for auxiliary contacts ∇ Reduced flange of rotary handle for door (optional) 54 2 0.08 152 5.98 189.5 7.46 184 7.24 Rockwell Automation Publication 140G-TD047A-EN-P 105 4.13 70 70 125 4.92 102 4.01 103.6 4.08 Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 1200 A, N-Frame Cat. No. 140G-N-TLA43, -TLA44, -TLC43, -TLC44 Terminals 320 12.6 70 2.76 250 9.84 70 2.76 70 2.76 34.75 0.52 1 0.04 28 1.1 66.25 2.61 79 3.11 202 7.95 150 5.9 Y 101 3.98 125 4.92 X X Y Y X X Ø 21.5 Ø 0.85 Terminal lugs for cables ‡ Tightening torque: 43 N•m ♠ Tightening torque: 18 N•m ∇ Required insulating plate provided for molded case circuit breaker Rockwell Automation Publication 140G-TD047A-EN-P 55 Approximate Dimensions — 1200 A, NS-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Molded Case Circuit Breaker 125 4.92 97 3.82 50 1.97 24 0.94 10 0.39 10 0.39 ≥3 ≥ 0.12 210 8.27 193.5 7.62 2 0.079 175 6.89 178 7.01 125 4.92 280 11.02 204 8.03 268 10.55 237 9.34 102 4.02 70 2.76 10 0.39 12 14.5 0.58 70 2.76 6 0.24 118.5 4.66 103.6 4.08 134 5.28 147.5 5.81 70 2.76 25 0.98 190 7.48 206 8.11 Description A With flange 125…184 (4.92…7.24) Without flange 170 (6.7) Description Standard B 208 (8.19) No. of Poles C 3 70 (2.76) 4 140 (5.51) Front terminals for busbar connection ‡ Busbars § Door flange Δ Drilling template for fixing onto mounting plate ♦ Tightening torque: 18 N•m ♠ Key lock (optional) ∇ Padlock (optional) & Tightening torque: 2.5 N•m # Compartment door with flange sheet drilling 11Compartment door without flange sheet drilling 12Terminal for auxiliary contacts Drilling Templates for Molded Case Circuit Breaker Mounting 208 8.19 268 10.55 Ø 5.5 - M5 Ø 0.22 Drilling template for compartment door 56 35 1.38 245 9.65 304 11.97 206 8.11 103 4.05 263 10.35 151 5.94 144.5 5.69 144.5 5.69 152 5.98 11 122.5 4.82 Ø 4 n°7 HOLES Ø 0.16 241 9.49 226 8.9 Flange for compartment door Rockwell Automation Publication 140G-TD047A-EN-P Drilling template for mounting plate Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 1200 A, NS-Frame Cat. Nos. 140G-N-TLA63, -TLA64, -TLC63, -TLC64 Terminals 320 12.6 70 2.76 70 2.76 250 9.84 70 2.76 125 4.92 34.75 1.37 1 0.04 79 3.11 202 7.95 150 5.9 28 1.1 101 3.98 66.25 2.61 Ø 21.5 Ø 0.85 Front terminals for cables ‡ Tightening torque: 43 N•m ♠ Tightening torque: 18 N•m ∇ Required insulating plates provided for molded case circuit breaker Rockwell Automation Publication 140G-TD047A-EN-P 57 Approximate Dimensions — 1200 A, NS-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Cat. Nos. 140G-N-TLV3, -TLV4, -TLH3, -TLH4 Rear Terminals 59 2.32 X 109 4.29 X X 218 8.58 X 237 9.34 273 10.75 118.5 4.66 44 1.73 Y X 25 0.98 15 0.59 18.5 0.73 Y 70 2.76 44 1.73 70 2.76 25 0.98 46.5 1.84 59 2.32 Rear horizontal terminals ‡ Rear vertical terminals ♠ Tightening torque: 20 N•m 1 Ø1 3 .4 Ø0 46.5 1.84 70 2.76 Ø 11 Ø 0.43 Y 70 2.76 70 2.76 Y 70 2.76 15 0.59 245 9.65 122.5 4.82 8 0.31 Y X X 17.5 0.69 Ø 5.5 - M5 Ø 0.22 58 B 52.5 2.07 61.25 2.41 39.75 1.56 Drilling template for mounting plate C No. of Poles B C 3 70 (2.76) 192.5 (7.58) 4 140 (5.51) 262.5 (10.33) R 10 Y Rockwell Automation Publication 140G-TD047A-EN-P X Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions — 1200 A, NS-Frame Cat. No. 140G-N-EXSLI3, -EXSL03, -EXS4 Extended Front Spreader Terminals 320 12.6 250 9.84 116 4.57 90 3.54 45 1.77 116 4.57 116 4.57 90 3.54 45 1.77 90 3.54 23 0.9 90 3.54 45 1.77 45 1.77 100 3.94 40.5 1.59 Ø 13 Ø 0.51 15 0.59 79 3.11 79 3.11 118.5 4.66 229 9.02 258 10.16 79 3.11 278 10.94 334 13.15 33 1.3 Extended spread terminals ‡ Tightening torque: 18 N•m § Required 200 mm insulating phase barriers provided Δ Required insulating plate provided Cat. Nos. 140G-N-EXT3, -EXT4 Extended Front Terminals 320 12.6 25 0.98 70 2.76 100 3.94 29.5 1.16 125 70 4.92 2.76 44 1.73 15 0.59 Ø 11 Ø 0.43 250 9.84 118.5 4.66 79 3.11 12.5 0.49 160.5 6.32 199.5 7.85 229 9.02 25 0.98 70 2.76 250 9.84 ‡ Tightening torque: 18 N•m ♣ Required insulating plate provided Δ Extended terminals ♦ Required 100 mm insulating phase barriers provided ♠ Terminal for auxiliary contacts Rockwell Automation Publication 140G-TD047A-EN-P 59 Approximate Dimensions—2000…3000 A, R-Frame Bulletin 140G Molded Case Circuit Breaker Specifications Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Panel Mounted Breakers 2500 A Breakers Drilling Templates Mounting Plate (4 Poles) 60 Mounting Plate (3 Poles) Rockwell Automation Publication 140G-TD047A-EN-P Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions—2000…3000 A, R-Frame 3000 A Breakers Drilling Templates Mounting Plate (4 Poles) Mounting Plate (3 Poles) Rockwell Automation Publication 140G-TD047A-EN-P Compartment Door 61 Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 140G-TD047A-EN-P - October 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.