Molded Case Circuit Breaker Specifications

Technical Data
Molded Case Circuit Breaker Specifications
Bulletin Number 140G, 140MG
Topic
Page
Product Line Overview
2
Specifications
4
Approximate Dimensions—125 A, G-Frame
8
Approximate Dimensions—125 A, H-Frame
16
Approximate Dimensions—225 A, I-Frame
24
Approximate Dimensions—250 A, J-Frame
32
Approximate Dimensions—400 A, K-Frame
40
Approximate Dimensions—800 A, M-Frame
46
Approximate Dimensions—1200 A, N-Frame
49
Approximate Dimensions—1200 A, NS-Frame
56
Approximate Dimensions—2000…3000 A, R-Frame
60
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Product Overview
2
Bulletin 140G Molded Case Circuit Breaker Specifications
G-Frame
H-Frame
I-Frame
J-Frame
K-Frame
M-Frame
N-, NS-Frame
R-Frame
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Frame Reference
Rated Current In
Product Overview
G-Frame
H-Frame
I-Frame
J-Frame
K-Frame
M-Frame
N-Frame
NS-Frame
R-Frame
125 A
125 A
225 A
250 A
400 A
800 A
1200 A
1200 A
3000 A
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
No. of Poles
Interrupting Rating [kA]
240V
50 65 100 65 100 150 200 200
50 65
65 100 150
65 100 150
125
480V
25 35 65
25 35 65 100 150
25 35
25 35 65 100
35 65 100 150
50 65 100
50 65 100
50 65 100
125
600Y/347V
10 14 25
—
10 10
—
—
—
—
—
—
—
14 18 25 35
10 10
14 18 25 35
25 35 65 100
25 35 42
25 50 65
25 50 65
100
220…240V
65 85 100
65 85 100 150 200
65 85
65 85 100 150
85 100 200 200
85 100 200
85 100 200
85 100 200
130
415V
36 50 70
36 50 70 120 150
36 50
36 50 70 120
50 70 120 200
36 70 100
50 70 120
50 70 120
80
440V
36 50 65
36 50 65 100 150
25 40
36 50 65 100
40 65 100 180
35 50 65
50 65 100
50 65 100
80
690V
6 8 10
10 12 15 18 20
58
10 12 15 20
25 40 70 80
22 25 30
30 42 50
30 42 50
40
250V DC
36 50 70
36 50 70 85 100
36 50
36 50 70 85
—
36 50 65
—
—
—
500V DC
36 50 70
36 50 70 85 100
36 50
36 50 70 85
36 50 70 100
—
—
—
—
750V DC
—
—
—
—
25 36 70 70
16 36 50
—
—
—
600V
65 100 150 200 100 150 200 200 100 200 200
Breaking Capacity [Icu (kA)]
Protection Type
Thermal Magnetic
—
—
—
Electronic
—
—
Molded Case Switch
Auxiliary Contact
Alarm Contact
AX/AL Combo
Trip Unit Contact
—
—
—
—
Internal Accessories
Shunt Trip
Shunt Close
—
—
—
—
—
—
UV Relay
Field Installable
End Cap
STD
STD
STD
STD
STD
STD
STD
STD
—
25 mm Phase
Barriers
STD
STD
STD
STD
STD
—
—
—
—
Insulators
STD
STD
STD
STD
STD
STD
—
—
—
Terminal Lugs
Extended Terminal
—
External Accessories
Spreader Terminal
Rear Terminal
—
—
—
—
—
—
Phase barriers
Terminal Cover
—
Direct Rotary
—
—
Variable Depth (Door)
—
—
Internal NFPA 79
—
—
Flange Operator
—
—
Flange Cable
—
—
Motor Operator
—
Field Installable
Rockwell Automation Publication 140G-TD047A-EN-P
3
Specifications
Bulletin 140G Molded Case Circuit Breaker Specifications
G-Frame
Max. Rated Current
[A]
Rated insulation
voltage, Ui, IEC
[V]
H-Frame‡
125
125
160
160
800
1000
NEMA, UL, CSA
Interrupting Rating Code
G2
G3
G6
G2 G3 G6
H2
H3
H6
H0
H15
H2 H3 H6 H0 H15
240V AC, 50/60Hz
[kA]
50
65
100
50 65 100
65
100
150
200
200
65 100 150 200 200
480V AC, 50/60Hz
[kA]
25
35
65
25 35 65
25
35
65
100
150
25 35 65 100 150
600Y/347V AC,
50/60Hz
[kA]
10
14
25
10 14 25
—
—
—
—
—
—
600V AC, 50/60
Hz
[kA]
—
—
—
—
14
18
25
35
42
14 18 35 35 42
IEC 60947-2
Rated ultimate short-circuit breaking capacity, Icu
220/230/240V AC,
50/60Hz
[kA]
65
85
100
65 85 100
65
85
100
150
200
65 85 100 150 200
380V AC, 50/60Hz
[kA]
36
50
70
36 60 70
36
50
70
120
150
26 50 70 120 150
415V AC, 50/60Hz
[kA]
36
50
70
36 50 70
36
50
70
120
150
36 50 70 120 150
440V AC, 50/60Hz
[kA]
36
50
65
36 50 65
36
50
65
100
150
36 50 65 100 150
500V AC, 50/60Hz
[kA]
30
36
50
36 50 65
30
36
50
60
70
30 36 50 60 70
525V AC, 50/60Hz
[kA]
22
35
35
22 35 35
20
25
30
36
50
20 25 30 36 50
690V AC, 50/60Hz
[kA]
6
8
10
6 8 10
10
12
15
18
20
10 12 15 18 20
250V DC, 2 Poles
in Series
[kA]
36
50
70
36 50 70
36
50
70
85
100
36 50 70 85 100
500V DC, 2 Poles
in Series
[kA]
—
—
—
—
—
—
—
—
—
—
500V DC, 3 Poles
in Series
[kA]
36
50
70
36 50 70
36
50
70
85
100
36 50 70 85 100
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
—
—
—
—
Rated service short-circuit breaking capacity, Ics
220/230/240V AC,
50/60Hz
[kA]
75%
(50)
75%
75%
75% 75% 75%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
380V AC, 50/60Hz
[kA]
100%
100%
75%
100% 100% 75%
100%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
415V AC, 50/60Hz
[kA]
100%
75%
50%
100% 75% 50%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
440V AC, 50/60Hz
[kA]
50%
50%
50%
50% 50% 50%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
500V AC, 50/60Hz
[kA]
50%
50%
50%
50% 50% 50%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
525V AC, 50/60Hz
[kA]
50%
50%
50%
50% 50% 50%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
690V AC, 50/60Hz
[kA]
75%
50%
50%
75 50 50%
100%
100%
100%
75%
75%
100% 100% 100% 75%
75%
250V DC, 2 Poles
in Series
[kA]
100%
100%
75%
100% 100% 75%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
500V DC, 2 Poles
in Series
[kA]
—
—
—
—
—
—
—
—
—
—
500V DC, 3 Poles
in Series
[kA]
100%
100%
75%
100% 100% 75%
100%
100%
100%
100%
100%
100% 100% 100% 100%
100%
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
—
—
—
—
Mechanical Life
Electrical Life @
415V AC
[No.
Ops]
25 000
25 000
[Ops/hr]
240
240
[No.
Ops]
8000
8000
[Ops/hr]
120
120
Ambient Temp.
w/out derating
ºF [ºC]
104 ºF [40 ºC]
104 ºF [40 ºC]
Storage Temperature
ºF [ºC]
-40...+176 ºF [-40…+80 ºC]
-40...+176 ºF [-40…+80 ºC]
Dimensions
[Width/Depth/Height]
[mm]
3 poles: 76.2x70x130
3 poles: 90x82.5x130
[mm]
4 poles: 101.6x70x130
4 poles: 120x82.5x130
IEC version with a 160 A Icu rating
‡ Cannot be reverse fed above 480V
4
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Specifications
I-Frame
J-Frame‡
Max. Rated Current
[A]
225
250
Rated insulation
voltage, Ui, IEC
[V]
800
1000
NEMA, UL, CSA
Interrupting Rating Code
I2
I3
J2
J3
J6
J0
240V AC, 50/60Hz
[kA]
50
65
65
100
150
200
480V AC, 50/60Hz
[kA]
25
35
25
35
65
100
600Y/347V AC,
50/60Hz
[kA]
10
10
—
—
—
—
600V AC, 50/60
Hz
[kA]
—
—
14
18
25
35
IEC 60947-2
Rated ultimate short-circuit breaking capacity, Icu
220/230/240V AC,
50/60Hz
[kA]
50
85
65
85
100
150
380V AC, 50/60Hz
[kA]
36
50
36
50
70
120
415V AC, 50/60Hz
[kA]
36
50
36
50
70
120
440V AC, 50/60Hz
[kA]
25
40
36
50
65
100
500V AC, 50/60Hz
[kA]
20
30
30
36
50
60
525V AC, 50/60Hz
[kA]
13
20
20
25
45
50
690V AC, 50/60Hz
[kA]
5
6
10
12
15
20
250V DC, 2 Poles
in Series
[kA]
36
50
36
50
70
85
500V DC, 2 Poles
in Series
[kA]
—
—
36
50
70
85
500V DC, 3 Poles
in Series
[kA]
36
50
36
50
70
85
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
Rated service short-circuit breaking capacity, Ics
220/230/240V AC,
50/60Hz
[kA]
75%
50%
100%
100%
100%
100%
380V AC, 50/60Hz
[kA]
75%
50% (27)
100%
100%
100%
100%
415V AC, 50/60Hz
[kA]
75%
50% (27)
100%
100%
100%
100%
440V AC, 50/60Hz
[kA]
75%
50%
100%
100%
100%
100%
500V AC, 50/60Hz
[kA]
75%
50%
100%
100%
100%
100%
525V AC, 50/60Hz
[kA]
75%
50%
100%
100%
100%
100%
690V AC, 50/60Hz
[kA]
50%
50%
100%
100%
100%
100%
250V DC, 2 Poles
in Series
[kA]
100%
75%
100%
100%
100%
100%
500V DC, 2 Poles
in Series
[kA]
—
—
100%
100%
100%
100%
500V DC, 3 Poles
in Series
[kA]
100%
75%
100%
100%
100%
100%
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
Mechanical Life
Electrical Life @
415V AC
[No.
Ops]
25 000
25 000
[Ops/hr]
240
240
[No.
Ops]
8000
8000
[Ops/hr]
120
120
Ambient Temp.
w/out derating
ºF [ºC]
104 ºF [40 ºC]
104 ºF [40 ºC]
Storage Temperature
ºF [ºC]
-40...+176 ºF [-40…+80 ºC]
-40...+176 ºF [-40…+80 ºC]
Dimensions
[Width/Depth/Height]
[mm]
3 poles: 105x70x150
3 poles: 105x82.5x160
[mm]
4 poles: 140x70x150
4 poles: 140x82.5x160
‡ Cannot be reverse fed above 600V
Rockwell Automation Publication 140G-TD047A-EN-P
5
Specifications
Bulletin 140G Molded Case Circuit Breaker Specifications
K-Frame
M-Frame
Max. Rated Current
[A]
400
800
Rated insulation
voltage, Ui, IEC
[V]
1000
1000
NEMA, UL, CSA
Interrupting Rating Code
K3
K6
K0
K15
K5
K6
K0
240V AC, 50/60Hz
[kA]
100
150
200
200
100
200
200
480V AC, 50/60Hz
[kA]
35
65
100
150
50
65
100
600Y/347V AC,
50/60Hz
[kA]
—
—
—
—
—
—
—
600V AC, 50/60
Hz
[kA]
25
35
65
100
25
35
42
IEC 60947-2
Rated ultimate short-circuit breaking capacity, Icu
220/230/240V AC,
50/60Hz
[kA]
85
100
200
200
85
100
200
380V AC, 50/60Hz
[kA]
50
70
120
200
50
70
100
415V AC, 50/60Hz
[kA]
50
70
120
200
50
70
100
440V AC, 50/60Hz
[kA]
40
65
100
180
45
50
80
500V AC, 50/60Hz
[kA]
30
50
85
150
35
50
65
525V AC, 50/60Hz
[kA]
—
—
—
—
—
—
—
690V AC, 50/60Hz
[kA]
25
40
70
80
22
25
30
250V DC, 2 Poles
in Series
[kA]
—
—
—
—
—
—
—
500V DC, 2 Poles
in Series
[kA]
36
50
70
100
—
—
—
500V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
—
750V DC, 3 Poles
in Series
[kA]
25
36
70
70
20
36
50
Rated service short-circuit breaking capacity, Ics
220/230/240V AC,
50/60Hz
[kA]
100%
100%
100%
100%
100%
100%
75%
380V AC, 50/60Hz
[kA]
100%
100%
100%
100%
100%
100%
75%
415V AC, 50/60Hz
[kA]
100%
100%
100%
100%
100%
100%
75%
440V AC, 50/60Hz
[kA]
100%
100%
100%
100%
100%
100%
75%
500V AC, 50/60Hz
[kA]
100%
100%
100%
100%
100%
100%
75%
525V AC, 50/60Hz
[kA]
—
—
—
—
—
—
—
690V AC, 50/60Hz
[kA]
100%
100%
100%
100%
75%
75%
75%
250V DC, 2 Poles
in Series
[kA]
—
—
—
—
—
—
—
500V DC, 2 Poles
in Series
[kA]
100%
100%
100%
100%
—
—
—
500V DC, 3 Poles
in Series
[kA]
—
—
—
—
—
—
—
750V DC, 3 Poles
in Series
[kA]
100%
100%
100%
100%
75%
75%
75%
Mechanical Life
[No.
Ops]
[Ops/hr]
Electrical Life @
415V AC
[No.
Ops]
[Ops/hr]
20000
20000
120
120
7000 (400 A) - 5000 (630 A)
7000 (630 A) - 5000 (800 A) - 4000 (1000 A)
60
60
Ambient Temp.
w/out derating
ºF [ºC]
104 ºF [40 ºC]
104 ºF [40 ºC]
Storage Temperature
ºF [ºC]
-40...+176 ºF [-40…+80 ºC]
-40...+176 ºF [-40…+80 ºC]
Dimensions
[Width/Depth/Height]
[mm]
3 poles: 140x108.5x205
3 poles: 210x103.5x268
[mm]
4 poles: 185x103.5x205
4 poles: 280x103.5x268
6
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Specifications
N-, NS-Frame
R-Frame
Max. Rated Current
[A]
1200
2000/2500/3000
Rated insulation
voltage, Ui, IEC
[V]
1000
1000
NEMA, UL, CSA
Interrupting Rating Code
N5
N6
N0
R12
240V AC, 50/60Hz
[kA]
65
100
150
125
480V AC, 50/60Hz
[kA]
50
65
100
125
600Y/347V AC,
50/60Hz
[kA]
—
—
—
—
600V AC, 50/60
Hz
[kA]
25
50
65
100
IEC 60947-2
Rated ultimate short-circuit breaking capacity, Icu
220/230/240V AC,
50/60Hz
[kA]
85
100
200
130
380V AC, 50/60Hz
[kA]
50
70
120
80
415V AC, 50/60Hz
[kA]
50
70
120
80
440V AC, 50/60Hz
[kA]
50
65
100
80
500V AC, 50/60Hz
[kA]
40
50
85
40
525V AC, 50/60Hz
[kA]
—
—
—
—
690V AC, 50/60Hz
[kA]
30
42
50
40
250V DC, 2 Poles
in Series
[kA]
—
—
—
—
500V DC, 2 Poles
in Series
[kA]
—
—
—
—
500V DC, 3 Poles
in Series
[kA]
—
—
—
—
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
100%
Rated service short-circuit breaking capacity, Ics
220/230/240V AC,
50/60Hz
[kA]
100%
100%
100%
380V AC, 50/60Hz
[kA]
100%
100%
100%
415V AC, 50/60Hz
[kA]
100%
100%
100%
100%
440V AC, 50/60Hz
[kA]
100%
100%
100%
100%
500V AC, 50/60Hz
[kA]
100%
100%
75%
100%
525V AC, 50/60Hz
[kA]
—
—
—
—
690V AC, 50/60Hz
[kA]
100%
75%
75%
100%
250V DC, 2 Poles
in Series
[kA]
—
—
—
—
500V DC, 2 Poles
in Series
[kA]
—
—
—
—
500V DC, 3 Poles
in Series
[kA]
—
—
—
—
750V DC, 3 Poles
in Series
[kA]
—
—
—
—
Mechanical Life
[No.
Ops]
[Ops/hr]
Electrical Life @
415V AC
[No.
Ops]
[Ops/hr]
10000
15000
60
60
2000
4500 (2000 A) - 4000 (2500 A) - 3000 (3200 A)
60
60
104 ºF [40 ºC]
104 ºF [40 ºC]
Ambient Temp.
w/out derating
ºF [ºC]
Storage Temperature
ºF [ºC]
-40...+176 ºF [-40…+80 ºC]
-40...+176 ºF [-40…+80 ºC]
Dimensions
[Width/Depth/Height]
[mm]
3 poles: 210x154(N)/178(NS)x268
3 poles: 427x282x382
[mm]
4 poles: 280x154(N)/178(NS)x268
4 poles: 553x282x382
Rockwell Automation Publication 140G-TD047A-EN-P
7
Approximate Dimensions — 125 A, G-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
Description
No. of Poles
A
With flange
3…4
74
Without flange
3…4
71
3…4
79
‡ Overall dimensions of optional wiring ducts
§ Required 25 mm insulating phase barriers provided
DIN Rail Mounted Molded Case Circuit Breaker
Mounting bracket
‡ Overall dimensions of optional wiring ducts
§ Required 25 mm insulating phase barriers provided
♣ Optional front cover for DIN Rail
8
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, G-Frame
Drilling Template for Molded Case Circuit Breaker Mounting
3 Poles
4 Poles
Cat. Nos. 140G-G-ECM, -ECM4 Terminals
Mounting bracket
♠ Required 25 mm insulating phase barriers provided
Rockwell Automation Publication 140G-TD047A-EN-P
9
Approximate Dimensions — 125 A, G-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-G-EXT3, -EXT4 Extended Terminals
‡ Extended terminals
§ Optional Terminal covers with IP40 protection provided
Δ Required 100 mm insulating phase barriers provided
∇ Internal insulating plate required with phase barriers (customer provided) when mounted through the enclosure door
Cat. Nos. 140G-G-EXS3, -EXS4 Spreader Terminals
♣ Extended spread terminals for busbar connection
♦ Required 200 mm insulating phase barriers provided
10
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, G-Frame
Cat. Nos. 140G-G-TLC13, 140G-G-TLC14 Terminals (Copper Only Lug)
‡ Front terminals
Cat. No. 140G-G-MTL63, -MTL64 Terminal (Multi-Cable Terminal Lug)
♣ Required terminal covers with IP40 protection provided
Δ Terminal lugs for multi-cable connection
Cat. No. 140G-G-RMB or 140G-G-RMY Direct Rotary Operating Handle
Drilling: See Detail “A”
Min. door rotation radius
‡ Rotary handle operating mechanism on molded case circuit breaker
♣ Door drilling template with direct rotary handle
♦ Required 25 mm insulating phase barriers provided
Rockwell Automation Publication 140G-TD047A-EN-P
11
Approximate Dimensions — 125 A, G-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-G-RVM…Variable Depth Rotary Mechanism with Door Mounted Handle
2.68
[68.0]
6.37
[161.8]
12 in. shaft: 11.38 [289]
21 in. shaft: 20.38 [517.8]
0.08
[2.0]
0.41
[10.5]
1.54
[39.0]
1.54
[39.0]
5.12
[130.0]
0.57
[14.5]
5.12
[130.0]
0.57
[14.5]
3.98
[101.2]
3.00
[76.2]
3-Pole
Front of Cover
4-Pole
50
(1.97)
ø 35
(ø 1.37)
25
(0.98)
25
(0.98)
25
(0.98)
ø 35
(ø 1.37)
31.5
(1.23)
63
(2.47)
50
(1.97)
mm
(in.)
(2) - ø 5.5
(2) - ø 0.22)
12
0.07
[1.8]
1.41
[35.8]
(2) - ø 5.5
(2) - ø 0.22)
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, G-Frame
Cat. No. 140G-G-EOP… Motor Operator
♣ Motor operator
Δ Door drilling template (without flange)
♦ Door drilling template (with flange)
♠ Cable connection
∇ Required 25 mm insulating phase barriers provided
Rockwell Automation Publication 140G-TD047A-EN-P
13
Approximate Dimensions — 125 A, G-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-G-ELP1603 Residual Current Release Module for 3-Pole Molded Case Circuit Breakers
Description
No. of Poles
A
With flange
3
74
Without flange
3
71
Terminals for busbar connection
‡ IP40 terminal covers
§ Drilling template — door with direct rotary mechanism and flange
♣ Drilling template — door with direct rotary mechanism, without flange
Δ Drilling template — molded case circuit breaker mounting on mounting plate
14
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, G-Frame
Cat. No. 140G-G-ELP1604 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers
Description
No. of Poles
A
With flange
4
74
Without flange
4
71
Terminals for busbar connection
‡ IP40 terminal covers
§ Drilling template — door with direct rotary mechanism and flange
♣ Drilling template — door with direct rotary mechanism, without flange
Δ Drilling template — molded case circuit breaker mounting on mounting plate
Rockwell Automation Publication 140G-TD047A-EN-P
15
Approximate Dimensions — 125 A, H-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
Description
No. of Poles
A
With flange
3…4
86
3…4
83.5
3…4
91.5
Without flange
‡ Overall dimensions of optional wiring ducts
§ Required 25 mm insulating phase barriers provided
DIN Rail Mounted Molded Case Circuit Breaker
Mounting bracket
§ Required 25 mm insulating phase barriers provided
16
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, H-Frame
Drilling Template for Molded Case Circuit Breaker Mounting
3 Poles
4 Poles
Cat. Nos. 140G-H-ECM, -ECM4 Terminals
Required 25 mm insulating phase barriers provided
‡ Front terminals for busbar connection
Rockwell Automation Publication 140G-TD047A-EN-P
17
Approximate Dimensions — 125 A, H-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-H-EXT3, -EXT4 Extended Terminals
3 Poles
§ Extended terminals
♣ Optional terminal covers with IP40 protection provided
Δ Required 100 mm insulating phase barriers provided
♦ Required internal insulating plate provided for breakers with Ue>440V
♠ Drilling template for 3-pole molded case circuit breaker, Ue>440V (required)
∇ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required)
18
Rockwell Automation Publication 140G-TD047A-EN-P
4 Poles
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, H-Frame
Cat. Nos. 140G-H-EXS3, -EXS4 Spreader Terminals
4 Poles
3 Poles
Drilling template for 3-pole molded case circuit breaker, Ue>440V (required)
‡ Drilling template for 4-pole molded case circuit breaker, Ue>440V (required)
§ Extended spread terminals
♣ Required 200 mm insulating phase barriers provided
Δ Required insulated plate provided for breakers, with Ue>440V
Rockwell Automation Publication 140G-TD047A-EN-P
19
Approximate Dimensions — 125 A, H-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-H-TLC13, -TLC14 Terminals
§ Required 25 mm insulating phase barriers provided
♦ Copper terminals.
Cat. Nos. 140G-H-MTL63, -MTL64 Terminals
♦ Multi-cable terminals
Cat. No. 140G-H-RMB, -RMY Direct Rotary Operating Handle
‡ Rotary handle operating mechanism on molded case circuit breaker
♦ Required 25 mm insulating phase barriers provided
20
Rockwell Automation Publication 140G-TD047A-EN-P
Approximate Dimensions — 125 A, H-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-H-RVM… Rotary Handle Operating Mechanism — Door Mounted
3.17
[80.5]
12 in. shaft: 10.89 [276.5]
21 in. shaft: 19.89 [505.1]
6.86
[174.3]
1.44
[36.5]
0.08
[2.0]
1.57
[40.0]
1.28
[32.5]
1.28
[32.5]
5.12
[130.0]
5.12
[130.0]
0.89
[22.5]
0.89
[22.5]
4.88
[124.0]
3.54
[90.0]
3-Pole
Front of Cover
4-Pole
50
(1.97)
ø 35
(ø 1.37)
25
(0.98)
25
(0.98)
25
(0.98)
ø 35
(ø 1.37)
31.5
(1.23)
63
(2.47)
50
(1.97)
mm
(in.)
(2) - ø 5.5
(2) - ø 0.22)
(2) - ø 5.5
(2) - ø 0.22)
Rockwell Automation Publication 140G-TD047A-EN-P
21
Approximate Dimensions — 125 A, H-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-H-EOP… Motor Operator
3 Poles
4 Poles
Motor operator
Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate
♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate
♠ Required 25 mm insulating phase barriers provided
22
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 125 A, H-Frame
Cat. No. 140G-H-ELP1604 Residual Current Release Module
4 Poles
Description
No. of Poles
A
With flange
4
86
Without flange
4
83.5
Residual current module
‡ Front terminals
♠ Drilling template — door with direct rotary mechanism and flange
∇ Drilling template — door with direct rotary mechanism, without flange
& Drilling template — molded case circuit breaker mounting on mounting plate
Rockwell Automation Publication 140G-TD047A-EN-P
23
Approximate Dimensions — 225 A, I-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
Description
No. of Poles
A
With flange
3…4
74
3…4
71
3…4
79
Without flange
‡ Overall dimensions of optional wiring ducts
§ Required 25 mm insulating phases barriers provided
DIN Rail Mounted Molded Case Circuit Breaker
Mounting bracket
‡ Optional wiring ducts
§ Optional front cover for DIN Rail
♣ Required 25 mm insulating phase barriers provided
24
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 225 A, I-Frame
Drilling Template for Molded Case Circuit Breaker Mounting
3 Poles
4 Poles
Cat. Nos. 140G-I-ECM, -ECM4 Terminals
Front terminals for busbar connection
‡ Required 25 mm insulating phase barriers provided
Cat. Nos. 140G-J-EXS3, -EXS4 Terminals
♣ Extended spread terminals
♦ Required 200 mm insulating phase barriers provided
Rockwell Automation Publication 140G-TD047A-EN-P
25
Approximate Dimensions — 225 A, I-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-I-EXT3, -EXT4 Extended Terminals
‡ Extended terminals
§ Optional terminal covers with IP40 protection provided
Δ Required 100 mm insulating phase barriers provided
Cat. Nos. 140G-I-TLA1A3, -TLA1A4 Terminals
30…150 mm2 terminals
‡ Required 25 mm insulating phase barriers
provided
Cat. Nos. 140G-I-TLA3, -TLA4 Terminals
1x90…185 mm2 terminal
§ Required 25 mm insulating phase barriers provided
26
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 225 A, I-Frame
Cat. Nos. 140G-I-TLC13, -TLC14 Terminals
♦ Front terminals
& Required 25 mm insulating phase barriers provided
Cat. Nos. 140G-I-MTL63, -MTL64 Terminals
§ Optional terminal covers with IP40 protection provided
Δ Multi-cable terminal lugs
Rockwell Automation Publication 140G-TD047A-EN-P
27
Approximate Dimensions — 225 A, I-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-G-RMB, -RMY Direct Rotary Operating Handle (For I- and G-Frame Molded Case Circuit Breaker)
Drilling: See Detail “A”
Min. door rotation radius
‡ Rotary handle operating mechanism on molded case circuit breaker
♣ Door drilling template with direct rotary handle
♦ Required 25 mm insulating phase barriers provided
Cat. No. 140G-G-EOP… Motor Operator (I-Frame)
♣ Motor operator
♠ Required 25 mm insulating phase
barriers provided
28
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 225 A, I-Frame
Cat. No. 140G-G-RVM… Variable Depth Rotary Handle Operating Mechanism (For I-Frame Molded Case Circuit Breaker)
12 in. shaft: 11.38 [289]
21 in. shaft: 20.38 [517.8]
6.37
[161,8]
0.08
[2,0]
0.61
[15,5]
0.61
[15,5]
2.20
[55,9]
2.20
[55,9]
5.91
[150,0]
0.61
[15,6]
Front of Cover
0.08
[2,0]
5.91
[150,0]
0.20
[5,1]
4.13
[105,0]
5.51
[140,0]
3-Pole
4-Pole
50
(1.97)
ø 35
(ø 1.37)
25
(0.98)
25
(0.98)
25
(0.98)
ø 35
(ø 1.37)
31.5
(1.23)
63
(2.47)
50
(1.97)
mm
(in.)
(2) - ø 5.5
(2) - ø 0.22)
(2) - ø 5.5
(2) - ø 0.22)
Rockwell Automation Publication 140G-TD047A-EN-P
29
Approximate Dimensions — 225 A, I-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-I-ELP2503 Residual Current Release Module
Description
No. of Poles
A
With flange
3
74
Without flange
3
71
Terminals for cable connection
‡ Terminal covers with IP40 protection
Δ Drilling template — molded case circuit breaker mounting on mounting plate
30
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 225 A, I-Frame
Cat. No. 140G-I-ELP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers
Description
No. of Poles
A
With flange
4
74
Without flange
4
71
Terminals for busbar connection
‡ Terminal covers with IP40 protection
Δ Drilling template — molded case circuit breaker mounting on mounting plate
Rockwell Automation Publication 140G-TD047A-EN-P
31
Approximate Dimensions — 250 A, J-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
‡ Overall dimensions of optional wiring ducts.
§ Required 25 mm insulating phase barriers provided.
Description
No. of Poles
A
With flange
3…4
86
3…4
83.5
3…4
91.5
Without flange
DIN Rail Mounted Molded Case Circuit Breaker
Mounting bracket
§ Required 25 mm insulating phase barriers provided
32
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 250 A, J-Frame
Drilling Template for Molded Case Circuit Breaker Mounting
3 Poles
4 Poles
Cat. Nos. 140G-J-ECM, -ECM4 Terminals
Required 25 mm insulating phase barriers provided
‡ Terminals for busbar connection
Rockwell Automation Publication 140G-TD047A-EN-P
33
Approximate Dimensions — 250 A, J-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-J-EXT3, -EXT4 Extended Terminals
3 Poles
4 Poles
§ Extended terminals
♣ Optional terminal covers with IP40 protection provided
Δ Required 100 mm insulating phase barriers provided
♦ Required insulating plate provided for molded case circuit breaker with Ue>440V
♠ Drilling template for 3-pole molded case circuit breaker
∇ Drilling template for 4-pole molded case circuit breaker
34
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 250 A, J-Frame
Cat. Nos. 140G-J-EXS3, -EXS4 Spreader Terminals
3 Poles
4 Poles
Drilling template for 3-pole molded case circuit breaker
‡ Drilling template for 4-pole molded case circuit breaker
§ Extended spread terminals
♣ Required 200 mm insulating phase barriers provided
Δ Required insulated plate provided for molded case circuit
breaker with Ue>440V
Cat. Nos. 140G-J-TLA13, -TLA14 Terminal Lugs
Aluminum Conductor: 6…350 MCM (2.5…185 mm)
Copper Conductor: 10…350 MCM (6…185 mm)
1x1…185 mm2 front terminal
§ Required 25 mm insulating phase barriers provided
Cat. Nos. 140G-J-TLC13, -TLC14 Terminal Lugs
10…350 MCM (6…185 mm)
External terminals
♣ Required 25 mm insulating phase barriers provided
Rockwell Automation Publication 140G-TD047A-EN-P
35
Approximate Dimensions — 250 A, J-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-J-MTL63, -MTL64 Terminals
‡ Multi-cable terminal lugs
§ Optional terminal covers with IP40 protection provided
‡ Rotary handle operating mechanism on molded case circuit breaker
♦ Required 25 mm insulating phase barriers provided
Min. Door
Rotation Radius
Flange Mount Drill Template
36
Rockwell Automation Publication 140G-TD047A-EN-P
Approximate Dimensions — 250 A, J-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-H-RVM… Variable Depth Rotary Handle Operating Mechanism (For J-Frame Molded Case Circuit Breaker)
3.2
[83]
6.86
[174.3]
12 in. shaft: 10.89 [276.5]
21 in. shaft: 19.89 [505.1]
0.08
[2.0]
0.61
[15.5]
1.99
[50.5]
1.85
[47.0]
1.85
[47.0]
6.30
[160.0]
0.89
[22.5]
6.30
[160.0]
0.89
[22.5]
4.13
[105.0]
Front of Cover
5.51
[140.0]
3-Pole 50
4-Pole
(1.97)
ø 35
(ø 1.37)
25
(0.98)
25
(0.98)
25
(0.98)
ø 35
(ø 1.37)
31.5
(1.23)
63
(2.47)
50
(1.97)
mm
(in.)
(2) - ø 5.5
(2) - ø 0.22)
(2) - ø 5.5
(2) - ø 0.22)
Rockwell Automation Publication 140G-TD047A-EN-P
37
Approximate Dimensions — 250 A, J-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-H-EOP… Motor Operator – For H- & J-Frame Molded Case Circuit Breaker
3 Poles
4 Poles
Motor operator
§ Drilling template for door with motor operator with flange
♣ Drilling template for door with motor operator without flange
Δ Drilling template for 3-pole molded case circuit breaker, mounted on mounting plate
♦ Drilling template for 4-pole molded case circuit breaker, mounted on mounting plate
♠ Required 25 mm insulating phase barriers provided
38
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 250 A, J-Frame
Cat. No. 140G-J-EP2504 Residual Current Release Module for 4-Pole Molded Case Circuit Breakers
Description
No. of Poles
A
With flange
4
86
Without flange
4
83.5
Residual current module
‡ Front terminals
♠ Drilling template — door with direct rotary mechanism and flange
∇ Drilling template — door with direct rotary mechanism, without flange
& Drilling template — molded case circuit breaker mounting on mounting plate
Rockwell Automation Publication 140G-TD047A-EN-P
39
Approximate Dimensions — 400 A, K-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
Overall dimensions with cabled accessories mounted
‡ Overall dimensions with cabled auxiliary contacts mounted
Drilling Templates for Molded Case Circuit Breaker Mounting
Flange for compartment door
Drilling template for compartment door
with flange
(3…4 poles)
Drilling template for mounting plate
3 Poles
40
4 Poles
Rockwell Automation Publication 140G-TD047A-EN-P
without flange
(3…4 poles)
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-K-ECM, -ECM4 Terminals
Approximate Dimensions — 400 A, K-Frame
Cat. Nos. 140G-K-TLC13, -TLC14 Terminals
250…500 MCM (120…240 mm2)
Cat. Nos. 140G-K-TLA23, -TLA24, -TLC23, -TLC24 Terminals
(2) 2/0…250 MCM ((2) 95…120 mm2)
Terminal covers with IP40 protection
Cat. Nos. 140G-K-TLA13, -TLA14 Terminals
250…500 MCM (120…240 mm2)
Rockwell Automation Publication 140G-TD047A-EN-P
41
Approximate Dimensions — 400 A, K-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-K-EXT3, -EXT4 Extended Terminals
Terminal covers with IP40 protection
‡ Required 100 mm insulating phase barriers provided
Cat. Nos. 140G-K-EXS3, -EXS4 Spreader Terminals
Required 200 mm insulating phase barriers provided
42
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 400 A, K-Frame
Cat. No. 140G-K-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted
Rotary handle operating mechanism on molded case circuit breaker
‡ Padlock device for open position (max. 3 padlocks; user provided)
§ Dimensions with cabled early make contact
♣ Compartment door lock
Cat. No. 140G-K-ELP Residual Current Release Module for 4-Pole Molded Case Circuit Breakers
Overall dimensions with cabled auxiliary contacts mounted
Rockwell Automation Publication 140G-TD047A-EN-P
43
Approximate Dimensions — 400 A, K-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-K-RVM… Variable Depth Rotary Handle Operating Mechanism
4.00
[101.5]
4.80
[122.0]
12 in. shaft: 17.75 [450.8]
21 in. shaft: 26.75 [679.4]
0.01
[0.3]
0.14
[3.5]
0.78
[19.7]
0.92
[23.3]
2.69
[68.3]
2.66
[67.6]
8.07
[205.0]
0.78
[19.7]
8.07
[205.0]
0.80
[20.4]
5.49
[139.5]
7.32
[186.0]
3-Pole
4-Pole
75
(2.95)
37.5
(1.47)
mm
(in.)
37.5
(1.47)
65 ø
(2.56 ø)
75
(2.95)
4 - 5.5 ø
(4) - 0.22 ø)
44
Front of Cover
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 800 A, M-Frame
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
210 (3P)
8.27
115
4.53
103.5
4.07
140
= 5.51 =
61.25
2.41
2.7
0.11
70
2.76
5.5
0.22
2.7
0.11
105
4.13
268
10.55
134
5.28
70
2.76
105
4.13
70
2.76
3
0.12
280 (4P)
11.02
107
4.21
159
6.26
2
0.08
Overall dimensions with cabled accessories mounted
‡ Overall dimensions with cabled auxiliary contacts mounted
Drilling Templates for Molded Case Circuit Breaker Mounting
66.75
2.63
149
= 5.87 =
116
4.57
138
5.43
77.75
3.06
152
= 5.98 =
62.25
2.45
Drilling template for compartment door
142
= 5.59 =
107
4.21
Flange for compartment door
with flange
without flange
Drilling template for mounting plate
70
2.76
5.5 - M5
Ø 0.22
35
1.38
118.5
4.67
140
5.51
237
9.33
237
9.33
118.5
4.67
5.5 - M5
Ø 0.22
3 Poles
4 Poles
Rockwell Automation Publication 140G-TD047A-EN-P
45
Approximate Dimensions — 800 A, M-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-M-ECM Terminals
Cat. No. 140G-M-TLA23, -TLA24, -TLC23, -TLC24 Terminals
70
2.76
MA X 40
50
1.97
20
0.79
59
2.32
25.5
1
19
Ø 0.75
45
1.77
33.5
1.32
90
3.54
45
1.77
8
0.31
116
4.57
116
4.57
116
4.57
88
3.46
45
1.77
88
3.46
45
1.77
13
Ø 0.51
116
4.57
116
4.57
88
3.46
23
0.9
45
1.77
90
3.54
13
Ø 0.51
50
1.97
8
0.31
230.5
9.07
134
5.28
134
5.28
167.5
6.59
134
5.28
45
1.77
90
3.54
88
3.46
23
0.9
116.5
4.59
53.5
2.11
14
0.55
120.5
4.74
Cat. Nos. 140G-M-EXSLI3, -EXSLO3, -EXS4 Spreader Terminals
70
2.76
116.5
4.59
70
2.76
70
2.76
134
5.28
Cat. Nos. 140G-M-EXT3, -EXT4 Extended Terminals
70
2.76
70
2.76
39
1.53
MIN5 MAX10
120.5
4.74
MAX 12
23
0.9
±0 .1
18 MIN
22.5
0.89
6.5
Ø 0.26
Cat. No. 140G-M-RMB, -RMY Rotary Handle Operating Mechanism — Door Mounted
33
1.3
5.5
0.22
140
5.51
Ø4
Ø 0.16
190
7.48
146.5
5.77
103.5
4.07
5.5
0.22
42.5
1.67
84.5
3.33
140
5.51
5.5
0.22
2.7
0.11
≥3
≥ 0.12
140.5
5.53
≤2
≤ 0.08
2.7
0.11
Rotary handle operating mechanism on molded case circuit breaker
‡ Padlock device for open position (max. 3 padlocks; user provided)
§ Dimension with cabled early make contact
♣ Compartment door lock
41.5
1.63
Drilling template for compartment door
43
1.69
14
0.55
43
1.69
14
0.55
148.5
5.85
R min. 200
R min. 7.87
with flange
46
Rockwell Automation Publication 140G-TD047A-EN-P
96.5
3.8
142
5.59
85.5
3.37
5
5.94
90
3.54
100.25
3.95
173
6.81
152
5.98
96.5
38
Flange for compartment door
142
5.59
R min. 200
R min. 7.87
without flange
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 800 A, M-Frame
Cat. No. 140G-M-RVM… Variable Depth Rotary Handle Operating Mechanism
3.80
[96.5]
8.74
[221.9]
12 in. shaft: 17.75 [450.8]
21 in. shaft: 26.75 [679.4]
0.24
[6.1]
1.38
[35.0]
2.99
[75.9]
10.55
[268.0]
1.68
[42.6]
8.23
[209.0]
3-Pole
75
(2.95)
37.5
(1.47)
mm
(in.)
37.5
(1.47)
65 ø
(2.56 ø)
75
(2.95)
4 - 5.5 ø
(4) - 0.22 ø)
Front of Cover
Rockwell Automation Publication 140G-TD047A-EN-P
47
Approximate Dimensions — 800 A, M-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-M-EOP, -ECOP Motor Operator
1.1 Nm
140
= 5.51 =
5.5
5.5
0.22
0.22
140
5.51
70
2.76
191.5
7.54
5.5
0.22
Overall dimension with cabled accessories mounted
‡ Overall dimension with cabled auxiliary contacts mounted
3
0.12
222
8.74
233
9.17
Drilling template for compartment door
Flange for compartment door
152
= 5.98 =
Drilling template for mounting plate
118.5
4.66
Ø 5.5 - M5
Ø 0.22 - M5
237
9.33
237
9.33
118.5
4.66
48
70
2.76
142
= 5.59 =
142
5.59
71.25
2.8
151
5.94
75.75
2.98
173
6.81
86.5
3.4
148.5
= 5.85 =
R min. 200
R min. 7.87
with flange
Ø 5.5 - M5
Ø 0.22 - M5
2
0.08
140
5.51
35
1.38
Rockwell Automation Publication 140G-TD047A-EN-P
R min. 200
R min. 7.87
without flange
Approximate Dimensions — 1200 A, N-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
103.6
4.08
70
2.76
18.75
0.74
14.5
0.58
105
4.13
204
8.03
268
10.55
102
4.02
70
2.76
10
0.39
10
0.39
24
0.94
6
0.24
134
5.28
147.5
5.81
70
2.76
50
1.97
25
0.98
125
4.92
97
3.82
10
0.39
2
0.08
154.25
6.07
152
5.98
225
8.86
125
4.92
160
6.3
280
11.02
3
0.12
210
8.27
Description
A
With flange
125…141
Without flange
147
190
7.48
206
8.11
Front terminals for flat connection
‡ Busbars
§ Door flange
Δ Tightening torque: 18 N•m
♠ Padlock (optional)
∇ Tightening torque: 2.5 N•m
& Terminal for auxiliary contacts
Rockwell Automation Publication 140G-TD047A-EN-P
49
Approximate Dimensions — 1200 A, N-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Drilling Templates for Molded Case Circuit Breaker Mounting
Flange for compartment door
Drilling template for compartment door
268
10.55
192
7.56
with reduced flange
206
8.11
103
4.05
144.5
5.69
208
8.19
144.5
5.69
151
5.94
263
10.35
35.25
1.39
138
5.43
Front 190 x 105
241
9.49
226
8.9
203
7.99
19.75
0.78
107
4.21
24.25
0.95
116
4.57
304
11.97
152
5.98
201
7.91
2
0.08
155
6.1
§ Door flange
# Reduced flange for compartment door
Ø 4 n°7 HOLES
Ø 0.16
with flange
122.5
4.82
Drilling template for mounting plate
245
9.65
35
1.38
Ø 5.5 - M5
Ø 0.22
50
No. of Poles
C
3
70
4
140
Rockwell Automation Publication 140G-TD047A-EN-P
Front 206 x 204
Approximate Dimensions — 1200 A, N-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-N-RVM… Variable Depth Rotary Handle Operating Mechanism
3.82
[97.0]
10.75
[273.0]
12 in. shaft: 17.75 [450.8]
21 in. shaft: 26.75 [679.4]
0.93
[23.6]
1.73
[44.0]
1.38
[35.0]
4.82
[122.5]
2.41
[61.1]
4.83
[122.6]
10.55
[268.0]
10.55
[268.0]
0.83
[21.0]
0.83
[221.1]
8.27
[210.0]
11.02
[280.0]
3-Pole
4-Pole
75
(2.95)
37.5
(1.47)
mm
(in.)
37.5
(1.47)
65 ø
(2.56 ø)
75
(2.95)
4 - 5.5 ø
(4) - 0.22 ø)
Front of Cover
Rockwell Automation Publication 140G-TD047A-EN-P
51
Approximate Dimensions — 1200 A, N-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-N-TLH3, -TLV3, TLH4, TLV4 Terminals
109
4.29
218
8.58
237
9.34
273
10.75
118.5
4.66
44
1.73
59
2.32
70
2.76
70
2.76
44
1.73
25
0.98
1
Ø1 3
.4
Ø0
46.5
1.84
59
2.32
46.5
1.84
70
2.76
Ø
Ø 11
0.4
3
25
0.98
15
0.59
18.5
0.73
15
0.59
70
2.76
No. of Poles
B
C
3
70
192.5
4
140
262.5
70
2.76
70
2.76
Rear horizontal terminals
‡ Rear vertical terminals
♠ Tightening torque: 20 N•m
Drilling template for mounting plate
35
1.38
52.5
2.07
122.5
4.82
245
9.65
8
0.31
39.75
1.56
61.25
2.41
17.5
0.69
Ø 5.5 - M5
Ø 0.22
52
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 1200 A, N-Frame
Cat. No. 140G-N-EXT3, -EXT4 Extended Front Terminals
320
12.6
25
0.98
70
2.76
Y
125
70 4.92
2.76
44
1.73
100
3.94
29.5
29.5
15
0.59
1
Ø 11
Ø 0.43
79
3.11
118.5
4.66
250
9.84
12.5
0.49
160.5
6.32
199.5
7.85
229
9.02
25
0.98
70
2.76
250
9.84
X
X
X
Extended terminals
∇ Required 100 mm insulating phase barriers provided
♠ Tightening torque: 18 N•m
& Required insulating plate provided for molded case circuit breaker
X
Cat. Nos. 140G-N-EXSL13 Top (3-Pole), 140G-N-EXS4 (4-Pole) Rear Spread Terminals
116 / 4.57
116
90 / 3.54
90 / 3.54
/ 4.57
Ø
Ø 0 13
.51
100
116 / 4.57
40.5
90 / 3.54
45
1.77
79
3.11
15
55
2.17
100
3.94
118.5
258
10.16
334
33
1.3
45
1.77
268
10.55
134
5.28
79
3.11
100
3.94
23
0.91
144
5.67
189
7.44
45
1.77
45
1.77
147.5
5.81
~200
~10.16
23
X
X
‡ Extended spread terminals
# Required 200 mm insulating phase barriers provided
♠ Tightening torque: 18 N•m
§ Terminal for auxiliary contacts
& Required insulating plate provided for molded case circuit breaker
Rockwell Automation Publication 140G-TD047A-EN-P
53
Approximate Dimensions — 1200 A, N-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. No. 140G-N-RMB, -RMY Rotary Handle Operating Mechanism
280
11.02
210
8.27
70
70
70
70
6
0.24
97
3.82
134
5.28
147.5
5.81
33
1.30
18.75
0.74
268
10.55
204
8.03
43.5
1.71
2
0.08
2
0.08
Description
A
With flange
125…141
Without flange
147
154
6.06
190
7.48
206
8.11
Rotary handle operating mechanism on molded case circuit breaker
‡ Compartment door interlock
§ Door flange
♦ Tightening torque: 2.5 N•m
♠ Terminal for auxiliary contacts
∇ Reduced flange of rotary handle for door (optional)
54
2
0.08
152
5.98
189.5
7.46
184
7.24
Rockwell Automation Publication 140G-TD047A-EN-P
105
4.13
70
70
125
4.92
102
4.01
103.6
4.08
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 1200 A, N-Frame
Cat. No. 140G-N-TLA43, -TLA44, -TLC43, -TLC44 Terminals
320
12.6
70
2.76
250
9.84
70
2.76
70
2.76
34.75
0.52
1
0.04
28
1.1
66.25
2.61
79
3.11
202
7.95
150
5.9
Y
101
3.98
125
4.92
X
X
Y
Y
X
X
Ø 21.5
Ø 0.85
Terminal lugs for cables
‡ Tightening torque: 43 N•m
♠ Tightening torque: 18 N•m
∇ Required insulating plate provided for molded case circuit breaker
Rockwell Automation Publication 140G-TD047A-EN-P
55
Approximate Dimensions — 1200 A, NS-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Molded Case Circuit Breaker
125
4.92
97
3.82
50
1.97
24
0.94
10
0.39
10
0.39
≥3
≥ 0.12
210
8.27
193.5
7.62
2
0.079
175
6.89
178
7.01
125
4.92
280
11.02
204
8.03
268
10.55
237
9.34
102
4.02
70
2.76
10
0.39
12
14.5
0.58
70
2.76
6
0.24
118.5
4.66
103.6
4.08
134
5.28
147.5
5.81
70
2.76
25
0.98
190
7.48
206
8.11
Description
A
With flange
125…184 (4.92…7.24)
Without flange
170 (6.7)
Description
Standard
B
208 (8.19)
No. of Poles
C
3
70 (2.76)
4
140 (5.51)
Front terminals for busbar connection
‡ Busbars
§ Door flange
Δ Drilling template for fixing onto mounting plate
♦ Tightening torque: 18 N•m
♠ Key lock (optional)
∇ Padlock (optional)
& Tightening torque: 2.5 N•m
# Compartment door with flange sheet drilling
11Compartment door without flange sheet drilling
12Terminal for auxiliary contacts
Drilling Templates for Molded Case Circuit Breaker Mounting
208
8.19
268
10.55
Ø 5.5 - M5
Ø 0.22
Drilling template for compartment door
56
35
1.38
245
9.65
304
11.97
206
8.11
103
4.05
263
10.35
151
5.94
144.5
5.69
144.5
5.69
152
5.98
11
122.5
4.82
Ø 4 n°7 HOLES
Ø 0.16
241
9.49
226
8.9
Flange for compartment door
Rockwell Automation Publication 140G-TD047A-EN-P
Drilling template for mounting plate
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 1200 A, NS-Frame
Cat. Nos. 140G-N-TLA63, -TLA64, -TLC63, -TLC64 Terminals
320
12.6
70
2.76
70
2.76
250
9.84
70
2.76
125
4.92
34.75
1.37
1
0.04
79
3.11
202
7.95
150
5.9
28
1.1
101
3.98
66.25
2.61
Ø 21.5
Ø 0.85
Front terminals for cables
‡ Tightening torque: 43 N•m
♠ Tightening torque: 18 N•m
∇ Required insulating plates provided for molded case circuit breaker
Rockwell Automation Publication 140G-TD047A-EN-P
57
Approximate Dimensions — 1200 A, NS-Frame
Bulletin 140G Molded Case Circuit Breaker Specifications
Cat. Nos. 140G-N-TLV3, -TLV4, -TLH3, -TLH4 Rear Terminals
59
2.32
X
109
4.29
X
X
218
8.58
X
237
9.34
273
10.75
118.5
4.66
44
1.73
Y
X
25
0.98
15
0.59
18.5
0.73
Y
70
2.76
44
1.73
70
2.76
25
0.98
46.5
1.84
59
2.32
Rear horizontal terminals
‡ Rear vertical terminals
♠ Tightening torque: 20 N•m
1
Ø1 3
.4
Ø0
46.5
1.84
70
2.76
Ø 11
Ø 0.43
Y
70
2.76
70
2.76
Y
70
2.76
15
0.59
245
9.65
122.5
4.82
8
0.31
Y
X
X
17.5
0.69
Ø 5.5 - M5
Ø 0.22
58
B
52.5
2.07
61.25
2.41
39.75
1.56
Drilling template for mounting plate
C
No. of Poles
B
C
3
70 (2.76)
192.5 (7.58)
4
140 (5.51)
262.5 (10.33)
R 10
Y
Rockwell Automation Publication 140G-TD047A-EN-P
X
Bulletin 140G Molded Case Circuit Breaker Specifications
Approximate Dimensions — 1200 A, NS-Frame
Cat. No. 140G-N-EXSLI3, -EXSL03, -EXS4 Extended Front Spreader Terminals
320
12.6
250
9.84
116
4.57
90
3.54
45
1.77
116
4.57
116
4.57
90
3.54
45
1.77
90
3.54
23
0.9
90
3.54
45
1.77
45
1.77
100
3.94
40.5
1.59
Ø 13
Ø 0.51
15
0.59
79
3.11
79
3.11
118.5
4.66
229
9.02
258
10.16
79
3.11
278
10.94
334
13.15
33
1.3
Extended spread terminals
‡ Tightening torque: 18 N•m
§ Required 200 mm insulating phase barriers provided
Δ Required insulating plate provided
Cat. Nos. 140G-N-EXT3, -EXT4 Extended Front Terminals
320
12.6
25
0.98
70
2.76
100
3.94
29.5
1.16
125
70 4.92
2.76
44
1.73
15
0.59
Ø 11
Ø 0.43
250
9.84
118.5
4.66
79
3.11
12.5
0.49
160.5
6.32
199.5
7.85
229
9.02
25
0.98
70
2.76
250
9.84
‡ Tightening torque: 18 N•m
♣ Required insulating plate provided
Δ Extended terminals
♦ Required 100 mm insulating phase barriers provided
♠ Terminal for auxiliary contacts
Rockwell Automation Publication 140G-TD047A-EN-P
59
Approximate Dimensions—2000…3000 A, R-Frame Bulletin 140G Molded Case Circuit Breaker Specifications
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Panel Mounted Breakers
2500 A Breakers
Drilling Templates
Mounting Plate
(4 Poles)
60
Mounting Plate
(3 Poles)
Rockwell Automation Publication 140G-TD047A-EN-P
Bulletin 140G Molded Case Circuit Breaker Specifications Approximate Dimensions—2000…3000 A, R-Frame
3000 A Breakers
Drilling Templates
Mounting Plate
(4 Poles)
Mounting Plate
(3 Poles)
Rockwell Automation Publication 140G-TD047A-EN-P
Compartment Door
61
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 140G-TD047A-EN-P - October 2014
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.