Electronic Trip Molded Case Circuit Breakers LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit Breakers Only Class 602 Catalog CONTENTS Schneider Electric Brands General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 MICROLOGIC® Trip Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Circuit Breaker Specifics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Index of Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Table of Contents TABLE OF CONTENTS SECTION 1—GENERAL INFORMATION .................................................................................................................7 Introduction ...........................................................................................................................................................7 Also See . . . .....................................................................................................................................................7 Standards .........................................................................................................................................................8 Why Use Electronic Trip Molded Case Circuit Breakers? ................................................................................8 What Do These Benefits Mean to a Customer? ..............................................................................................8 Specifications ........................................................................................................................................................9 Circuit Breaker Ratings .........................................................................................................................................9 Voltage Ratings ................................................................................................................................................9 Ampere Ratings ...............................................................................................................................................9 Continuous Current Rating ..............................................................................................................................9 Frequency Rating .............................................................................................................................................9 Interrupting Rating .........................................................................................................................................10 Withstand Rating ............................................................................................................................................10 100% Rating ..................................................................................................................................................10 Ambient Temperature Rating .........................................................................................................................10 Other Features ....................................................................................................................................................11 Trip System ....................................................................................................................................................11 Internal Operating Mechanism .......................................................................................................................11 Push-to-trip Button .........................................................................................................................................11 Instantaneous OFF Feature ...........................................................................................................................11 Circuit Breaker Mounting ...............................................................................................................................12 Circuit Breaker Connections ..........................................................................................................................12 Testing Requirements .........................................................................................................................................13 Overview ........................................................................................................................................................13 Limited Available Fault Current Tests ............................................................................................................13 High Available Fault Current Tests ................................................................................................................14 Maintenance and Testing ....................................................................................................................................14 Inspection and Preventative Maintenance .....................................................................................................14 Performance and Verification Testing ............................................................................................................14 SECTION 2—MICROLOGIC TRIP SYSTEMS BASED ON LE, LX, LXI, ME, MX, NE, NX, PE AND PX CIRCUIT BREAKERS ..............................................................................................................................................15 RMS Sensing ......................................................................................................................................................15 Rating Plugs ........................................................................................................................................................16 Multiplier .........................................................................................................................................................16 Ammeter/Trip Indicator .......................................................................................................................................16 Overview ........................................................................................................................................................16 Memory Feature .............................................................................................................................................17 Ground-Fault Detection ..................................................................................................................................17 Trip Characteristics ........................................................................................................................................17 Standard-Function Trip Unit ................................................................................................................................18 Overview ........................................................................................................................................................18 Long-time Trip Functions ...............................................................................................................................18 Short-time Trip Functions ...............................................................................................................................19 Instantaneous Trip Function ..........................................................................................................................19 Ground-fault Trip Functions ...........................................................................................................................19 Full-Function Trip Unit .........................................................................................................................................20 Overview ........................................................................................................................................................20 3 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Table of Contents Long-Time Trip Functions ............................................................................................................................. 20 Short-Time Trip Functions ............................................................................................................................ 21 Instantaneous Trip ........................................................................................................................................ 21 Ground-Fault Trip .......................................................................................................................................... 21 Ground-fault Alarm ..............................................................................................................................................22 Additional Settings ............................................................................................................................................. 22 SECTION 3—CIRCUIT BREAKER SPECIFICS ..................................................................................................... 23 Catalog Numbering System ............................................................................................................................... 23 LE, LX and LXI 600 A Frame Circuit Breakers .................................................................................................. 24 Interrupting Ratings ....................................................................................................................................... 24 Lug Information ............................................................................................................................................. 24 Continuous Current Ratings .......................................................................................................................... 25 Accessories ................................................................................................................................................... 25 Control Wiring ............................................................................................................................................... 25 ME and MX 800 A Frame Circuit Breakers ........................................................................................................ 26 Interrupting Ratings ....................................................................................................................................... 26 Continuous Current Ratings .......................................................................................................................... 27 Lug Information ............................................................................................................................................. 27 Accessories ................................................................................................................................................... 27 Control Wiring ............................................................................................................................................... 27 NE and NX 1200 A Frame Circuit Breaker ........................................................................................................ 28 Interrupting Ratings ....................................................................................................................................... 28 Continuous Current Ratings .......................................................................................................................... 28 Lug Information ............................................................................................................................................. 29 Accessories ................................................................................................................................................... 29 Control Wiring ............................................................................................................................................... 29 PE and PX 2500 A Frame Circuit Breakers ....................................................................................................... 30 Interrupting Ratings ....................................................................................................................................... 30 Continuous Current Ratings .......................................................................................................................... 31 Terminations ................................................................................................................................................. 31 Terminal Pad Usage ..................................................................................................................................... 31 Accessories ................................................................................................................................................... 32 Control Wiring ............................................................................................................................................... 32 SECTION 4—ACCESSORIES ................................................................................................................................ 33 Factory-Installed Accessories ............................................................................................................................ 33 Field-Installed Accessories ................................................................................................................................ 33 Shunt Trip ..................................................................................................................................................... 34 Undervoltage Trip ......................................................................................................................................... 35 Undervoltage Trip Time-Delay Unit ............................................................................................................... 36 Auxiliary Switch ............................................................................................................................................. 36 Alarm Switch ................................................................................................................................................. 36 Circuit Breaker Terminations ............................................................................................................................. 37 Mechanical Lugs ........................................................................................................................................... 37 Compression Lugs ........................................................................................................................................ 38 Power Distribution Connectors ..................................................................................................................... 38 CBA I-LINE® Jaw Configuration ................................................................................................................... 38 Control Wire Termination .............................................................................................................................. 38 Other Accessories .............................................................................................................................................. 38 Electric Joint Compound ............................................................................................................................... 38 Rating Plugs .................................................................................................................................................. 38 Trip Indicator ................................................................................................................................................. 39 Ammeter/Trip Indicator ................................................................................................................................. 39 4 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Table of Contents Communications Adapter ...............................................................................................................................40 Electrical Operators .......................................................................................................................................40 Handle Accessories ............................................................................................................................................41 Handle Extensions .........................................................................................................................................41 Handle Interlocking ........................................................................................................................................41 Handle Padlocks ............................................................................................................................................41 Neutral Current Transformers ........................................................................................................................41 Restraint Interface Modules ...........................................................................................................................42 Trip Unit Seals ...............................................................................................................................................42 Universal Test Set ..........................................................................................................................................42 APPENDIX A—DIMENSIONS .................................................................................................................................43 LE, LX and LXI Circuit Breakers .........................................................................................................................43 ME and MX Circuit Breakers ...............................................................................................................................44 NE and NX Circuit Breakers ...............................................................................................................................45 PE and PX Circuit Breakers ................................................................................................................................47 APPENDIX B—TRIP CURVES ................................................................................................................................53 LE, LX and LXI Circuit Breakers .........................................................................................................................54 ME and MX Circuit Breakers ...............................................................................................................................61 NE and NX Circuit Breakers ...............................................................................................................................67 PE and PX Circuit Breakers ................................................................................................................................72 GLOSSARY .............................................................................................................................................................85 INDEX OF CATALOG NUMBERS ...........................................................................................................................89 INDEX ......................................................................................................................................................................93 5 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Table of Contents 6 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information SECTION 1—GENERAL INFORMATION INTRODUCTION Note: This manual includes information about LE, LX, LXI, ME, MX, NE, NX, PE and PX circuit breakers only. For information on new P and R-frame circuit breakers with new style MICROLOGIC® trip units, see the class 0612 catalog. These electronic trip molded case circuit breakers are designed to protect electrical systems from damage caused by overloads, short circuits and ground faults. All circuit breakers are designed to open and close a circuit by nonautomatic means, and to open the circuit automatically on a predetermined overcurrent. Electronic trip circuit breakers can also: — Enhance coordination by their adjustability — Provide integral ground-fault protection — Provide capacity for future growth — Provide zone-selective interlocking for increased selectivity in the electrical system Electronic trip molded case circuit breakers manufactured by Square D use the MICROLOGIC® electronic trip system to sense overcurrents and trip the circuit breaker. Square D makes two types of electronic trip units: full-function trip systems and standard-function trip systems. ■ Section 1—General Information, provides an overview of electronic trip molded case circuit breakers. ■ Section 2—MICROLOGIC Trip Systems Based On LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit Breakers, provides information about the electronic trip systems used in LE, LX, LXI, ME, MX, NE, NX, PE and PX circuit breakers only. ■ Section 3—Circuit Breaker Specifics, provides application information about electronic trip circuit breakers by catalog prefix. ■ Section 4—Accessories, lists the accessories available for use with electronic trip circuit breakers. ■ Appendix A—Dimensions. ■ Appendix B—Trip Curves. Table 1. Also See . . . MICROLOGIC Trip Unit Features Standard-Function Circuit Breakers Full-Function Circuit Breakers • • • • • • • • • • • • • • • • • • • • • • • • • • • 80% rated True root-mean-square (rms) sensing 100-2500 A continuous current ratings LSI, LSIG trip configurations Interchangeable rating plugs Overload indicating light Integral ground-fault protection and testing option Local electronic trip indicator option Local current meter option Universal test set available Neutral current transformer for 4-wire systems available 100% rated True root-mean-square (rms) sensing 100-2500 A continuous current ratings LI, LIG, LS(I), LS(I)G trip configurations Interchangeable rating plugs Overload indicating light Short-time withstand rating Defeatable instantaneous feature option (on LS trip only) Integral ground-fault protection and testing option Integral ground-fault alarm (no trip) option Zone-selective interlocking Local electronic trip indicator Local current meter Universal test set available Neutral current transformer for 4-wire systems available POWERLOGIC® communications For information on other types of molded case circuit breakers manufactured by Square D, See Thermal-Magnetic and Magnetic Only Molded Case Circuit Breakers Catalog 0601CT9101. 7 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information Standards Square D electronic trip molded case circuit breakers are manufactured and tested in accordance with the following standards: • • • • • UL 489 NEMA AB-1-1993 CSA Standard 22.5 IEC 60947-2 Federal Specification W-C-375B/GEN as Class 11a, 11b, 12a, 12b, and 13a, 13b Circuit breakers are applied according to guidelines detailed in the National Electrical Code (NEC) and other local electrical wiring codes. Why Use Electronic Trip Molded Case Circuit Breakers? MICROLOGIC® electronic trip circuit breakers provide the same basic functions as standard thermalmagnetic circuit breakers. Both type of circuit breakers: • • • • provide overload and short-circuit protection. are true rms sensing devices. provide means to manually disconnect power to the circuit. meet UL, CSA, NEMA and IEC standards. However, MICROLOGIC electronic trip circuit breakers offer a variety of benefits in addition to these basic functions. MICROLOGIC circuit breakers can: • • • • provide adjustability for enhanced coordination. provide integral ground fault protection or alarm. measure and report inherent ground-fault leakage. provide capacity for future growth using: — rating plugs. — long-time pickup switch. — 100% rated full-function trip system. • • What Do These Benefits Mean to a Customer? be provided with zone-selective interlocking to reduce fault stress on the electrical system. be provided with power monitoring communications. MICROLOGIC® circuit breakers give the customer more versatility to achieve coordination with features such as adjustable pickup and delay points, interchangeable rating plugs and withstand ratings. Features such as universally interchangeable rating plugs, adjustable long-time pickups and 100% ratings provide capacity for future growth. Integral ground-fault sensing capabilities mean that there are fewer parts and pieces to buy, mount and wire. Square D offers products with integral ground-fault protection which trip when a ground-fault is detected as well as products with integral ground-fault alarm which do not trip but send an alarm when a ground fault is detected. MICROLOGIC full-function circuit breakers also offer the customer true power management system solutions through communications. The full-function trip units can communicate with other circuit breakers in the system and also with a power monitoring system. Communication between circuit breakers allows zone-selective interlocking (ZSI) between circuit breakers at different levels in the system. ZSI reduces fault stress by allowing the upstream circuit breaker closest to the fault to ignore its preset delay time and trip without any intentional delay on a short circuit or ground fault. For more information on ZSI, see Application Guide 0600SC9102, Reducing Fault Stress with Zone-selective Interlocking. Communication with a power monitoring system through a POWERLOGIC® communications link allows a ground fault to be reported without interrupting power to the system. It also allows the power monitoring system to remotely report power usage, current flow and trip history. For more information on POWERLOGIC system capabilities, See publication 3050IM9101, POWERLOGIC Product Interface for MICROLOGIC Circuit Breakers. 8 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information SPECIFICATIONS Electronic trip molded case circuit breakers have a molded case made of a glass-reinforced insulating material that provides high dielectric strength. These circuit breakers: • • • • • Share common tripping of all poles Can be mounted and operated in any position Meet the requirements of NEC Section 240-6 by providing a means to seal the rating plug and trip unit adjustments Are equipped with an externally accessible test port for use with a Universal Test Set Are fully tested, UL Listed and CSA certified for reverse connection without restrictive LINE or LOAD markings. The L-, M-, N-, and P-frame circuit breakers are also IEC certified CIRCUIT BREAKER RATINGS Voltage Ratings Voltage ratings indicate the maximum voltage for the electrical system on which the circuit breaker can be applied. All Square D electronic trip molded case circuit breakers are designed to be applied on systems rated 600 Vac or less. They are not designed for use on dc systems. Ampere Ratings The ampere rating of an electronic trip circuit breaker is the maximum current that a circuit breaker can carry. It is determined by the mathematical equation: Ampere Rating (P) = Sensor Size (S) × Rating Plug (%) • • The circuit breaker sensor size is the maximum ampere rating possible for a specific circuit breaker. This value is based on the size of the current sensor inside the circuit breaker. (Current sensors are an integral part of the circuit breaker and cannot be removed or replaced.) The rating plug varies the circuit breaker ampere rating as a function of its sensor size. (The rating plug catalog number is ARPXXX, with XXX being the multiplier value.) This multiplier value is printed on the faceplate of the rating plug along with the mathematical equation used to obtain the ampere rating. Note: The maximum ampere rating a circuit breaker family can carry is called the frame size. Sensor size is less than or equal to frame size. Continuous Current Rating The continuous current rating of an electronic trip circuit breaker is determined by the equation: Continuous Current Rating = Ampere Rating (P) × Long-time Setting • • Frequency Rating The circuit breaker ampere rating (P) is found by multiplying the circuit breaker sensor size by the rating plug multiplier. The long-time pickup switch varies the circuit breaker continuous current rating as a multiple of the ampere rating. Switch positions are adjustable from 0.5 to 1.0. Square D circuit breakers can be applied on 50 and 60 Hz systems without rerating. Electronic trip circuit breakers are recommended for applications only on systems at 50/60 Hz. These circuit breakers have not been evaluated at any other frequency. 9 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information Interrupting Rating The interrupting rating is the highest current at rated voltage the circuit breaker is designed to safely interrupt under standard test conditions. Circuit breakers must be selected with interrupting ratings equal to or greater than the available short-circuit current at the point where the circuit breaker is applied to the system (unless it is a branch device in a series rated combination). Interrupting ratings are shown on the faceplate of the circuit breaker. Table 2. Interrupting Ratings Circuit Breaker Withstand Rating IEC 947-2 Rating 415/240 Vac UL/CSA 240 Vac 480 Vac 600 Vac Icu Ics LE, LEL, LX, LXL 100 kA 65 kA 35 kA 65 kA 65 kA LXI, LXIL 200 kA 200 kA 100 kA 65 kA 65 kA ME, MEL, MX, MXL 65 kA 65 kA 25 kA 65 kA 33 kA NE, NEL, NX, NXL 65 kA 65 kA 25 kA 50 kA 50 kA PEF, PXF 125 kA 100 kA 65 kA 70 kA 53 kA The short-time withstand rating of a circuit breaker is the level of rms symmetrical current that a circuit breaker can carry with the contacts in a closed position for a stated period of time (usually 30 cycles). The withstand rating is used to improve coordination by maximizing the current level at which the circuit breaker trips with no intentional delay. For more information on coordination using withstand ratings, See Data Bulletin 0600DB0105, Circuit Breaker Characteristic Trip Curves and Coordination. Note: It is recommended that a system coordination study be done for optimum circuit breaker coordination. 100% Rating Full-function electronic trip circuit breakers (except the 2500 A PE and 600 A LE circuit breakers) are UL Listed to be applied at up to 100% of their continuous current rating. Because of the additional heat generated when applying circuit breakers at 100% of continuous current rating, the use of specially designed enclosures and 90°C rated wire is required. Table 3. Circuit Breaker Enclosure Sizes Circuit Breaker Enclosure Size (H × W × D) LE 52 × 20 × 7-1/2 in (1321 × 508 × 190 mm) ME 52 × 22-1/2 × 14-1/2 in (1321 × 572 × 368 mm) NE 52 × 22-1/2 × 14-1/2 in (1321 × 572 × 368 mm) PE 45 × 36 × 24 in (1143 × 914 × 610 mm) Markings on the circuit breaker indicate minimum enclosure size and ventilation specifications required. The 90°C wire must be sized according to the ampacities of the 75°C wire column in the NEC. Circuit breakers with 100% ratings can also be used in applications requiring only 80% continuous loading. Ambient Temperature Rating To meet the requirements of UL Standard 489, molded case circuit breakers are designed, built and calibrated for use on 50/60 Hz ac systems in a 40°C ambient environment. Electronic trip circuit breakers, however, are designed to react only to the magnitude of the current flowing through the circuit breaker. MICROLOGIC® electronic trip circuit breakers are inherently ambient insensitive in the range of -10°C to +60°C. 10 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information OTHER FEATURES Trip System The trip system causes the circuit breaker to open automatically under overload, short-circuit or groundfault conditions. The MICROLOGIC trip system consists of the current sensors, a microprocessor-based trip unit, and a tripping coil. The tripping coil is a flux transfer solenoid which requires no external power source. All MICROLOGIC protective functions are completely fault powered. The trip system operation and adjustments are described on page 15. Figure 1. MICROLOGIC Trip System 06023006 Trip Coil Microprocessor Trip Unit Switches Trip Indicator Current Sensor (One per pole) Internal Operating Mechanism Square D circuit breakers have a single operating handle that acts directly through the operating mechanism against the contact arms. Multi-pole circuit breakers have a common trip bar for positive action of all poles on manual and automatic operation. These circuit breakers have a trip-free mechanism that allows them to trip even though the operating handle may be restricted (by a handle operating mechanism or a motor operator) in the ON position. If not restricted, the operating handle moves to a position between ON and OFF when the circuit breaker is tripped. The face of the circuit breaker is marked with standard ON/OFF and international I/O markings to indicate handle position. Push-to-trip Button The push-to-trip button located on the face of each circuit breaker is a standard feature of all Square D molded case circuit breakers. This allows the user to manually trip the circuit breaker without risking exposure to live parts. During normal on-off operation, the handle opens and closes the circuit breaker contacts but does not exercise the tripping mechanism. Using the push-to-trip button exercises the tripping mechanism. Use the push-to-trip button to check: ❏ Alarm circuits ❏ Emergency circuits ❏ Motor sequencing operations It is recommended that the circuit breaker tripping mechanism be exercised at least annually. Instantaneous OFF Feature Full-function circuit breakers with adjustable long-time, short-time and instantaneous (LS[I]) trip units provide the ability to turn the instantaneous tripping function OFF. Turning OFF the instantaneous trip function increases the current level at which the circuit breaker will trip with no intentional delay to the level of the short-time withstand rating. This current level is typically much higher than any of the pickup levels provided by the adjustable instantaneous feature. In other words, using the “Instantaneous OFF” feature improves coordination by allowing the user to take advantage of the circuit breaker withstand rating. 11 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information Circuit Breaker Mounting L-, M-, and N-family unit-mount electronic trip circuit breakers (frame sizes through 1200 A) are supplied with four mounting screws. These mounting screws are inserted through mounting holes molded into the circuit breaker base and threaded into the enclosure. To properly support the circuit breaker, all four mounting screws must be used. P-family electronic trip circuit breakers (frame sizes above 1200 A) are supported with mounting brackets attached to each circuit breaker or with a terminal pad kit. Table 4. Terminal Pad Usage Circuit Breaker Connections Terminal Pads Required 600-1600 A PE 600-2000 A PX Bus No Cable Use terminal pad kit PALTB or equivalent bus structure. Cable or Bus Use terminal pad kit supplied with circuit breaker or equivalent bus structure. 1800-2500 A PE 2500 A PX See page 23 for frame-specific mounting information. Circuit Breaker Connections L-, M-, and N-family circuit breakers (frame sizes through 1200 A) are available in unit-mount construction for cable or bus connections; or with plug-on connectors for I-LINE applications. P-family circuit breakers (frame sizes 1200 A and above) are available in unit-mount construction only, using either cable or bus connections. Unit-mount circuit breakers can be ordered with mechanical line and load side lugs. The standard lugs can be removed for the installation of compression-type lugs or for bus connections. All lugs are UL Listed for their proper application and marked for use with aluminum and copper (Al/Cu) or copper only (Cu) conductors. Lugs suitable for copper and aluminum conductors are generally made of tin-plated aluminum. Lugs suitable for use with copper conductors only are made of copper. Plug-on circuit breakers are available through the 1200 A frame size for easy installation and removal in Square D exclusive I-LINE panelboards and switchboards. I-LINE circuit breakers use “blow-on” type connectors. In case of a short circuit, increased magnetic flux causes the plug-on connectors of the circuit breaker to tighten their grasp on the panelboard or switchboard bus bars. The I-LINE connectors are integral parts of I-LINE circuit breakers, and cannot be removed or replaced. See page 23 for frame-specific connection information. 12 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information TESTING REQUIREMENTS Overview The UL label on a Square D molded case circuit breaker indicates that the circuit breaker meets the requirements of UL Standard 489 and that the manufacturer’s production procedure is monitored by UL inspectors to ensure continuing conformance to UL performance requirements. These requirements include the following tests: Limited Available Fault Current Tests • • • • • 200% Overload Calibration—each pole of the circuit breaker must trip within a specified time limit when carrying 200% of its continuous current rating. 135% Overload Calibration—with all poles connected in series, the circuit breaker must trip within a specified time limit while carrying 135% of its continuous current rating. Overload—the circuit breaker must make and break 600% of its continuous current rating at rated voltage. Circuit breaker frame sizes through 1600 A must perform 50 operations at 600%. Circuit breaker frame sizes 1600 A through 3000 A must perform 25 operations at 600%. Temperature Rise—while carrying 100% of rated current and mounted in open air, temperature rise on a wiring terminal must be within specified limits. For 100% rating, the circuit breaker is mounted in an enclosure. Endurance—the circuit breaker must complete the following number of operations: Table 5. • • Endurance Testing Operations Frame Size (A) Number of Operations With Current Without Current 255 4000 4000 400 1000 5000 600 1000 5000 800 500 3000 1200–2500 500 2000 Calibration Retest—both the 200% and 135% overload calibration tests are repeated. Short Circuit—the circuit breaker must interrupt the current while maintaining the integrity of the circuit breaker. For circuit breaker frames 1200 A and below, two short-circuit tests per pole and one test with all poles connected in common are performed. (A 3-pole circuit breaker receives seven short-circuit tests.) For circuit breaker frames above 1200 A, a minimum of two short-circuit tests per pole and two tests with all poles connected in common are performed. (A 3-pole circuit breaker receives eight short-circuit tests.) • • Trip Out—the 200% thermal calibration test is repeated following the short-circuit tests. Dielectric—the circuit breaker must withstand, for one minute, twice its rated voltage plus 1000 V: — Between line and load terminals with the circuit breaker in the tripped and in the OFF positions. — Between terminals of different potential with the circuit breaker closed. — Between live parts and the overall enclosure with the circuit breaker both open and closed. No conditioning of the circuit breaker can take place during or between tests. There can be no failure of functional parts at the conclusion of the sequences. 13 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 1—General Information High Available Fault Current Tests After qualifying a set of circuit breakers to the standard tests, a manufacturer can have additional circuit breaker samples tested on higher than standard available fault currents. The following performance requirements apply: • • • • 200% Overload Calibration – each pole of the circuit breaker must trip within a specified time limit when carrying 200% of its continuous current rating. Short-circuit Test – with the load side terminals connected by 10-inch lengths of specified cable (or a shorting bar), the circuit breaker is exposed to a short-circuit current for a set time interval. After safe interruption, the circuit breaker is reset and closed again on the short circuit. 250% Overload Calibration – each pole of the circuit breaker must trip within a specified time limit when carrying 250% of its continuous current rating. Dielectric Withstand – the circuit breaker is subjected to twice its rated voltage, but not less than 900 V. When the sample circuit breakers pass these tests, circuit breakers of the same construction can be marked or labeled with the higher current interrupting rating. MAINTENANCE AND TESTING Molded case circuit breakers require little maintenance, but an inspection and maintenance procedure should be established from the time of installation. The service life of electronic trip molded case circuit breakers depends on proper application, correct installation, suitable environmental conditions, and preventative maintenance. The guide most frequently used as a basis for field testing requirements is NEMA Standard AB4, Guidelines for Inspections and Preventive Maintenance of Molded Case Circuit Breakers used in Commercial and Industrial Applications. Square D recommends that molded case circuit breakers be inspected and tested during the normal annual maintenance of electrical systems. If operating or environmental conditions are severe, more frequent inspections are recommended. The circuit breaker case is sealed and must not be opened for any reason. Opening the circuit breaker case voids all warranties and the UL Listing. No serviceable parts are located inside the molded case. Inspection and Preventative Maintenance Inspection procedures check items that may indicate a potential problem. For information on inspection and preventative maintenance, See Data Bulletin 0600DB9901 Field Testing and Maintenance Guide for MICROLOGIC® Electronic Trip and Thermal-magnetic Molded Case Circuit Breakers. Performance and Verification Testing Performance tests such as insulation resistance tests, watts loss tests and electronic tripping function trip tests can be performed to verify that the circuit breaker is able to perform its basic functions. Use secondary injection testing or primary injection testing to check the trip system. A Square D Universal Test Set (Cat. No. UTS3) is available for secondary injection testing. For additional information or assistance, contact Square D at 1-888-SquareD (1-888-778-2733). For on-site service, contact the Square D Technical Services Division, 24 hours a day, at 1-800-634-2003. 14 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit SECTION 2—MICROLOGIC TRIP SYSTEMS BASED ON LE, LX, LXI, ME, MX, NE, NX, PE AND PX CIRCUIT BREAKERS Square D electronic trip molded case circuit breakers are equipped with either the MICROLOGIC Standard-function Trip System or the MICROLOGIC Full-function Trip System. Both trip systems provide adjustable tripping functions and characteristics using true root-mean-square (rms) current sensing. MICROLOGIC trip systems use a set of current transformers (called CTs or sensors) to sense current, either a standard-function or full-function trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable rotary switches on the trip unit allow the user to set the proper overcurrent or ground current protection required in the electrical system. If current exceeds a set value for longer than its set time delay, the trip system trips the circuit breaker. Circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit adjustments set at their lowest settings. Actual settings required for a specific application must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system. Standard-Function Trip Unit Full-Function Trip Unit RMS SENSING The sensing system on an electronic trip molded case circuit breaker responds to the flow of current through the circuit breaker. Electronic trip circuit breakers are limited to ac systems because the electronic trip system uses current transformers to sense the current. The MICROLOGIC trip system samples the current waveform 33 times per cycle on a 60 Hz system. It then uses this data to calculate the true rms current through the 13th harmonic. This true rms sensing gives accurate values for the magnitude of a non-sinusoidal waveform. Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated. Electronic trip circuit breakers with MICROLOGIC trip systems can be used on 50/60 Hz systems with alternating current (ac) to direct current (dc), dc to ac, and ac to ac converters. This includes applications that use silicon-controlled rectifiers (SCRs) and adjustable frequency controls. Trip System Current Sensing 06023009 Figure 2. Load Current (Amperes) Time (Seconds) 1 Sample Interval 15 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit RATING PLUGS Rating plugs are used to determine the circuit breaker ampere rating (P) according to the following equation: Ampere Rating (P) = Sensor Size (S) × Rating Plug %. The ampere rating and the longtime pickup switch are then combined to determine the circuit breaker continuous current rating. For example: Multiplier Continuous Current Rating = 225 = ( ( Sensor Size (S) 600 )×( )×( )×( )×( ) ) Rating Plug % Long-time Setting 0.75 0.5 Rating plugs are available with multiplier values ranging from 0.40 to 1.00. If the rating plug is not installed, the circuit breaker will operate safely, but the trip unit will default to a multiplier of 0.40. Rating plugs and ammeter/trip indicators are subject to damage from static charge. Internal damage can result if these devices are handled by their contacts. If either device is removed from the trip unit, it must be held against grounded metal, such as the metal circuit breaker enclosure, for at least two seconds before reinstalling. Each MICROLOGIC circuit breaker is shipped with a rating plug factory installed. The label on the circuit breaker marked “Configuration as Shipped” gives the circuit breaker configuration as it left the factory. Field-installable rating plug kits are also available. See Section 4—Accessories for available field-installable rating plug kits. Ground-fault pickup values are based on the sensor size of the circuit breaker and are not affected by changing the rating plug. AMMETER/TRIP INDICATOR Overview The ammeter/trip indicator is a troubleshooting tool used to identify the type of fault if an overcurrent condition occurs, and to find potential overcurrent situations. The ammeter/trip indicator displays current in phases A, B and C, and the peak ground-fault current flowing in the circuit. Each value can be viewed one at a time using the phase select/indicator reset button. (Phase values are displayed in true rms. Ground-fault current values are displayed in calculated rms based on measured peak current.) A bar graph is provided indicating the level of operating current as a percentage of the programmed ampere rating of the circuit breaker. The ammeter/trip indicator window displays “OVERLOAD,” “SHORT CIRCUIT,” or “GROUND FAULT” when the circuit breaker trips from an overcurrent. The indicator must be manually reset by pushing the phase select/indicator reset button. The ammeter can also be used as a rough guide when setting the ground-fault pickup when a coordination study is not available. Selecting the GF screen under normal operating conditions will display the groundfault leakage current under those conditions. In order to protect against abnormal conditions, the groundfault pickup should be set somewhat higher than the GF value displayed on the screen. The phase select/indicator reset button can be pressed at any time to test the ammeter/trip indicator battery condition. The window will display a battery symbol. If this does not occur, contact Square D for a replacement ammeter/trip indicator. The ammeter/trip indicator is factory installed on the full-function circuit breaker and is available as a field-installable option on the standard-function circuit breaker. It can be installed in or removed from the trip unit without tripping the circuit breaker. 16 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Memory Feature Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit MICROLOGIC trip systems feature a memory circuit for intermittent overload or ground-fault conditions. This allows the circuit breaker to respond to a series of ON and OFF overload or groundfault conditions which could cause conductor overheating, but go undetected in a conventional electronic trip device. If the circuit breaker trips due to an overcurrent condition, wait at least one minute before resetting the circuit breaker. This allows the memory to clear itself sufficiently for the circuit breaker to be turned ON. If checking trip times, wait fifteen minutes after the circuit breaker trips before resetting to allow memory to reset completely to zero (or use a memory reset module, Cat. No. MTMB). Ground-Fault Detection Standard-function and full-function circuit breakers are available with integral ground-fault detection to provide either ground-fault protection (trip) or alarm (no trip) on grounded systems. These circuit breakers utilize a residual sensing scheme for ground-fault detection. Both standard-function and full-function circuit breakers are available with integral equipment groundfault protection. Full-function circuit breakers are also available with integral ground-fault alarm (no trip) to monitor the flow of ground-fault current and signal an alarm condition through the POWERLOGIC® system, or with additional components described in Data Bulletin 0502DB0001: Ground-fault Alarm for LE, ME, NE, PE and SE MICROLOGIC Electronic Trip Circuit Breakers using RIM32 and AROMAT® relay. This feature meets NEC Sections 700-7(d) and 700-26 for emergency systems. Circuit breakers with the ground-fault alarm trip system DO NOT provide ground-fault protection (do not trip on groundfault). Ground-fault protection trip units include both ground-fault pickup and delay adjustments. Ground-fault alarm (no trip) trip units include only ground-fault pickup adjustments. Circuit breakers with either ground-fault protection or alarm (no trip) trip systems are equipped with an internal ground-fault push-to-test feature. The ground-fault push-to-test is built into the circuit breaker and eliminates the need for any additional test equipment. The ground-fault push-to-test requires 120 Vac control power. Trip Characteristics MICROLOGIC trip units provide a full range of adjustable tripping characteristics using a microcomputer that constantly monitors the line currents. The overcurrent or ground-fault current pickup and delay levels are set using adjustable rotary switches on the face of the trip unit. If the load current exceeds the trip settings, the microcomputer signals the circuit breaker to trip. Table 6. Adjustable Tripping Characteristics for Electronic Trip Circuit Breakers Standard-Function Trip Unit Full-Function Trip Unit • • • • • • • • • • • • • • • • Long-time pickup Long-time delay Short-time pickup Short-time delay (I2t IN only) Instantaneous pickup Ground-fault pickup Ground-fault delay (I2t OUT only) Long-time pickup Long-time delay Short-time pickup Short-time delay (I2t IN and I2t OUT) Instantaneous pickup Instantaneous OFF Ground-fault pickup Ground-fault delay (I2t IN and I2t OUT) Ground-fault alarm I2t IN delay is an “inverse time” characteristic in that the delay time decreases as the current increases. I2t OUT delay is a “constant-time” characteristic, the delay time does not change as the current increases. Trip settings are used to obtain a coordinated system in which a downstream circuit breaker will trip before an upstream circuit breaker. Properly adjusting the MICROLOGIC® trip settings will result in a circuit breaker trip curve that falls above and to the right of the branch circuit breaker trip curve. Under overcurrent conditions, the branch circuit breaker will trip first. Square D recommends that a system coordination study be done to find the proper trip unit settings to optimize coordination with other devices. 17 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit STANDARD-FUNCTION TRIP UNIT Overview The standard-function trip unit trip curve drawing shows the various parts of a typical trip curve affected by the adjustments on a standard-function trip unit. Adjusting the trip unit switches will shift that area of the trip curve. 06023012 Note: The switch settings shown in the following explanation of trip functions are examples only. The pictures are not representative of all frames and sensors. For specific switch settings, see the trip curve for the particular circuit breaker type, frame, and sensor. Long-time Pickup 1000 Standard-function Trip Unit Trip Curve Long-time Delay TIME IN SECONDS 100 10 Short-time Pickup Short-time Delay (I2t IN) 1.0 Instantaneous Pickup 0.1 0.01 1 5 10 100 MULTIPLES OF AMPERE RATING Ampere Rating (P) = Sensor Size (S) x Rating Plug (%) Long-time Trip Functions Long-time Pickup The long-time pickup switch value (multiplied by the ampere rating) sets the maximum current level which the circuit breaker will carry continuously. If the current exceeds this value for longer than the set delay time, the circuit breaker will trip. Long-time Delay The long-time delay switch value sets the length of time that the circuit breaker will carry a sustained overload before tripping. Delay bands are labeled in seconds of overcurrent at six times the ampere rating. For maximum coordination, eight delay bands are available. Long-time delay is an “inverse time” characteristic in that the tripping time decreases as the current increases. The trip unit includes an indicator that will flash when the current reaches 90% of the LONG-TIME PICKUP setting and will be lit continuously when the current is above 100% of the pickup setting. 06023013 Figure 3. .75 Long-time Pickup and Long-time Delay Switches .8 4 .9 .7 5 6 3 .95 .6 .5 PICKUP x P 1.0 7 10 PICKUP x P LONG TIME .32 20 3 24 2 DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD .2 .1 .5 .45 .3 .55 12 .25 12 3 PICKUP x P .65 .2 .75 PICKUP x S LONG-TIME PICKUP LONG-TIME DELAY GROUND FAULT I 2 t OUT .5 I 2 t IN .5 16 .35 10 4 INSTANT. SHORT TIME 11 4.5 8 2 8 5 6 2.5 DELAY SEC. AT 12 x P .32 .2 .1 .5 DELAY SEC. AT 1xS Indicator 18 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit Short-time Trip Functions The short-time pickup switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip after the set SHORT-TIME DELAY. Short-time Delay The short-time delay switch value sets the length of time the circuit breaker will carry a short circuit within the short-time pickup range. The delay (based on 12 times the ampere rating, P) can be set to four positions of I2t ramp operation (I2t IN). 06023025 Short-time Pickup .75 .8 5 4 .9 .7 .5 PICKUP x P PICKUP 12 4.5 x S GROUND FAULT .32 .32 .2 .2 .1 .1 .5 DELAY .5 DELAY DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD Short-time Delay I 2 t OUT .5 20 24 2 .75 PICKUP x P INSTANT. I 2 t IN .5 16 3 Short-time Pickup .65 .2 PICKUP x P SHORT TIME 11 .55 12 .25 3 10 .45 .35 .3 10 4 8 2 LONG TIME 7 5 6 2.5 1.0 8 6 3 .95 .6 SEC. AT 1xS SEC. AT 12 x P Instantaneous Trip Function The instantaneous pickup switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip with no intentional time delay. 06023014 Instantaneous Pickup .75 .8 4 .9 .7 5 .5 PICKUP x P 1.0 8 2 12 PICKUP DELAY Instantaneous Pickup OFF PICKUP GROUND FAULT .32 .32 .2 .2 .1 .1 .5 .5 DELAY DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD Instantaneous Pickup I 2 t OUT .5 20 24 .65 .75 x S INSTANT. I 2 t IN .5 16 2 .55 .2 x P x P 3 .45 .3 12 .25 3 10 .35 10 4 SHORT TIME 11 7 4.5 5 6 2.5 PICKUP LONG TIME 8 6 3 .95 .6 SEC. AT 1xS SEC. AT 12 x P The instantaneous function will override the short-time function if the INSTANTANEOUS PICKUP is adjusted at the same or lower setting than the SHORT-TIME PICKUP. Ground-fault Trip Functions Ground-Fault Pickup The ground-fault pickup switch value (multiplied by the sensor size) sets the current level at which the circuit breaker will trip after the set GROUND-FAULT DELAY. Ground-fault pickup values are based on the circuit breaker sensor size only, not the rating plug multiplier. Changing the rating plug multiplier has no effect on ground-fault pickup values. The ground-fault delay switch value sets the length of time the circuit breaker will carry ground-fault current which exceeds the GROUND-FAULT PICKUP level before tripping. Delay can be adjusted with four positions of fixed time delays (I2t OUT). 06023026 Ground-Fault Delay .75 .8 4 .9 .7 5 .5 PICKUP x P 1.0 7 8 PICKUP DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD .2 .1 .5 DELAY SEC. AT 12 x P 3 12 PICKUP .2 .55 .65 PICKUP .75 x S GROUND FAULT Ground-fault Pickup Ground-fault Delay I 2 t OUT .5 .32 20 24 2 .45 .3 12 .25 INSTANT. I 2 t IN .5 16 .35 10 4 x P SHORT TIME 11 3 10 x P LONG TIME 4.5 5 6 2.5 2 8 6 3 .95 .6 .32 .2 .1 .5 DELAY SEC. AT 1xS 19 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit FULL-FUNCTION TRIP UNIT Overview The full-function trip unit trip curve drawing, below, shows the various parts of a typical trip curve affected by the adjustments on a full-function trip unit. 06023027 Adjusting the trip unit switches will shift that area of the trip curve. Long-time Pickup 1000 Full-function Trip Unit Trip Curve Long-time Delay TIME IN SECONDS 100 10 Short-time Pickup Short-time Delay (I2t IN) 1.0 (I2t OUT) Instantaneous Pickup 0.1 0.01 1 5 100 10 MULTIPLES OF AMPERE RATING Ampere Rating (P) = Sensor Size (S) x Rating Plug (%) Long-Time Trip Functions Long-time Pickup The long-time pickup switch value (multiplied by the ampere rating) sets the maximum current level which the circuit breaker will carry continuously. If the current exceeds this value for longer than the set delay time, the circuit breaker will trip. Long-time Delay The long-time delay switch value sets length of time that the circuit breaker will carry a sustained overload before tripping. Delay bands are labeled in seconds of overcurrent at six times the ampere rating. For maximum coordination, there are eight delay bands. 06023028 Long-time delay is an “inverse time” characteristic in that the delay time decreases as the current increases. .75 .8 4 .9 .7 5 6 3 .95 .6 .5 PICKUP x P 1.0 7 2 24 2 DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD .2 .1 .5 .45 .3 .55 12 .25 12 3 PICKUP x P .65 .2 Long-time Pickup Long-time Delay .75 PICKUP x S GROUND FAULT I 2 t OUT .5 .32 20 .35 10 4 INSTANT. I 2 t IN .5 16 3 10 SHORT TIME 11 4.5 8 PICKUP x P LONG TIME 8 5 6 2.5 DELAY SEC. AT 12 x P .32 .2 .1 .5 DELAY SEC. AT 1xS Indicator The trip unit includes an Indicator that will flash when the current reaches 90% of the LONG-TIME PICKUP setting and will be lit continuously when the current is above 100% of the pickup setting. 20 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit Short-Time Trip Functions The short-time pickup switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip after the set SHORT-TIME DELAY. Short-time Delay The short-time delay switch value sets length of time the circuit breaker will carry a short circuit within the short-time pickup range. The delay (based on 12 times the ampere rating, P) can be adjusted to four positions of I2t ramp operation (I2t IN) or four positions of fixed time delays (I2t OUT). 06023029 Short-time Pickup .75 .8 4 .9 .7 5 .5 INSTANT. 24 2 DELAY GROUND FAULT I 2 t OUT .5 .32 .32 20 3 .75 PICKUP x S I 2 t IN .5 16 .65 .2 PICKUP x P SHORT TIME 11 4.5 .55 12 .25 12 3 10 PICKUP x P LONG TIME 7 2 .3 10 4 8 .1 .1 .5 Short-time Pickup Short-time Delay I2t IN .2 .2 .5 DELAY DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD .45 .35 5 6 2.5 1.0 PICKUP x P 8 6 3 .95 .6 Short-time Delay I2t OUT SEC. AT 1xS SEC. AT 12 x P Instantaneous Trip Instantaneous Pickup The instantaneous pickup switch value (multiplied by the ampere rating) sets the short-circuit current level at which the circuit breaker will trip with no intentional time delay. The instantaneous function will override the short-time function if the instantaneous pickup is adjusted at the same or lower setting than the short-time pickup. In full-function trip units with both adjustable short-time and instantaneous trip functions, the adjustable instantaneous trip can be disabled by setting instantaneous pickup to OFF. Even when the instantaneous pickup is turned OFF, an instantaneous override occurs above the circuit breaker shorttime withstand rating. 06023030 Instantaneous Pickup OFF .75 .8 4 .9 .7 5 .5 PICKUP x P PICKUP 12 3 10 I2 11 4.5 16 24 2 DELAY PICKUP x P Instantaneous Pickup OFF x S I 2 t OUT .5 .32 .32 .2 .2 .1 .1 .5 .5 DELAY DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD Instantaneous Pickup .75 GROUND FAULT t IN .5 20 3 .65 .2 PICKUP INSTANT. SHORT TIME .55 12 .25 x P LONG TIME 7 2 .3 10 4 8 .45 .35 5 6 2.5 1.0 8 6 3 .95 .6 SEC. AT 1xS SEC. AT 12 x P Ground-Fault Trip Ground-fault Pickup The ground-fault pickup switch value (multiplied by the sensor size) sets the current level at which the circuit breaker will trip after the set ground-fault delay. Ground-fault pickup values are based on circuit breaker sensor size only, not on the rating plug multiplier. Changing the rating plug multiplier has no effect on ground-fault pickup values. The ground-fault delay switch value sets length of time the circuit breaker will carry ground-fault current which exceeds the ground-fault delay level before tripping. Delay can be adjusted to four positions of I2t ramp operation (I2t IN) or four positions of fixed time delays (I2t OUT). 06023031 Ground-fault Delay .75 .8 4 .9 .7 5 .5 PICKUP x P 1.0 7 8 2 DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD .45 .3 .55 12 .25 3 12 PICKUP .2 x P .65 PICKUP .75 x S Ground-fault Pickup GROUND FAULT I 2 t OUT .5 .32 20 24 2 .35 10 4 INSTANT. I 2 t IN .5 16 3 10 x P SHORT TIME 11 4.5 5 6 2.5 PICKUP LONG TIME 8 6 3 .95 .6 .2 .1 .5 DELAY SEC. AT 12 x P Ground-fault Delay Ground-fault Delay I2t IN I2t OUT .32 .2 .1 .5 DELAY SEC. AT 1xS 21 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 2—MICROLOGIC® Trip Systems Based on LE, LX, LXI, ME, MX, NE, NX, PE and PX Circuit The ground-fault alarm switch value (multiplied by the sensor size) sets the current level at which the circuit breaker will signal the POWERLOGIC® system or remote monitoring provided with additional components described in Data Bulletin 0502DB0001, Ground-fault Alarm for LE, ME, NE, PE and SE MICROLOGIC Electronic Trip Circuit Breakers using RIM32 and AROMAT® Relay. 06023032 Ground-fault Alarm .75 .8 4 .9 .7 5 .5 PICKUP x P 1.0 7 8 PICKUP I2 16 24 2 DELAY SEC. AT 6xP FLASH=90% ON = OVERLOAD 3 12 .2 PICKUP .65 PICKUP .75 .45 .3 .55 .65 .25 .75 .2 Ground-fault Alarm PICKUP ×S x S INSTANT. GROUND FAULT I 2 t OUT .5 GROUND FAULT ALARM .32 .32 .2 .2 .1 .1 .5 .35 .55 12 .25 t IN .5 20 .45 .35 .3 10 4 x P SHORT TIME 11 3 10 x P LONG TIME 4.5 5 6 2.5 2 8 6 3 .95 .6 .5 DELAY DELAY SEC. AT 1xS SEC. AT 12 x P ADDITIONAL SETTINGS Settings to Approximate Thermal-Magnetic Circuit Breakers The table below shows electronic trip unit settings which result in a trip curve similar to the trip curve of a thermal-magnetic circuit breaker of the same ampere rating. The short-time and instantaneous pickup levels are presented in ranges that approximate the “Lo” to “Hi” magnetic adjustment ranges supplied on thermal-magnetic circuit breakers. Settings to Approximate Zero-Sequence Ground-fault Protection Systems Zero-sequence sensing ground-fault protection systems are used with thermal-magnetic circuit breakers or fusible switches for equipment ground-fault protection. The ground-fault pickup and delay settings on the electronic trip circuit breaker can be used to achieve trip curves similar to the Square D GC ground-fault relay. Table 7. Trip Unit Settings to Approximate Thermal-Magnetic Circuit Breakers1 LA, LH LC, LI LE, LX, LXI ShortTime Pickup 400 A 14 8 600 A 14 8 5 to 8 20 24 10 10 5 to 10 5 to 10 7 4.5 10 10 1200 A 1600 A 2000 A 4.5 4.5 7 8 8 6 3 to 8 3 to 6 4 to 6 1600 A 2000 A 2500 A 7 7 4.5 8 6 5 4 to 8 3 to 6 3.5 to 5 MA, MH ME, MX 400 A 800 A NH, NA, NC NE, NX 600 A 1200 A PA, PH PE, PX PC LongTime Trip LongTime Delay Thermal-Magnetic Electronic Circuit Frame Circuit Breaker Prefix Breaker Prefix Size 1.0 ShortTime Delay Instantaneous Pickup 5 to 8 .5 I2t IN 6 to 12 4 to 8 1. Thermal-magnetic circuit breakers do not have short-time tripping characteristics. To approximate the characteristics of a thermalmagnetic circuit breaker, the short-time pickup level should be equal to the instantaneous pickup level. 22 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics SECTION 3—CIRCUIT BREAKER SPECIFICS This section provides application information on electronic trip circuit breakers available from Square D. The information is organized by catalog prefix. Table 8. Available Circuit Breakers Catalog Prefix Frame Sizes (A) LE, LX (page 24) 600 ME, MX (page 26) 800 NE, NX (page 28) 1200 PE, PX (page 30) 2500 CATALOG NUMBERING SYSTEM When ordering Square D electronic trip circuit breakers, include circuit breaker family, poles, voltage rating, ampere rating and trip unit suffix. Table 9. Catalog Numbering System for Circuit Breakers with MICROLOGIC® Trip Systems Number Segment Character(s) Description ME L 3 6 800 LSG LE, ME, NE, PE Circuit breakers with full-function trip systems Circuit Breaker Family Connection Type LX, MX, NX, PX Circuit breakers with standard-function trip systems LXI Current-limiting circuit breakers with standard-function trip systems No Letter I-LINE L Lugs on both ends F Terminal pads only (PE, PX) P Lugs OFF end 3 3-pole Voltage 6 600 Vac Ampere Rating 800 800 Ampere Rating LI Adjustable long-time ampere rating and delay Adjustable Instantaneous pickup LS Adjustable long-time ampere rating and delay Adjustable Instantaneous pickup LIG Adjustable long-time ampere rating and delay Adjustable Instantaneous pickup Adjustable ground-fault pickup and delay LSG Adjustable long-time ampere rating and delay Adjustable short-time ampere rating and delay Adjustable Instantaneous pickup Adjustable ground-fault pickup and delay LIA Adjustable long-time ampere rating and delay Adjustable Instantaneous pickup Adjustable ground-fault alarm pickup (no delay, no trip) LSA Adjustable long-time ampere rating and delay Adjustable short-time ampere rating and delay Adjustable Instantaneous pickup Adjustable ground-fault alarm pickup (no delay, no trip) No Letter1 LS configuration G1 LSG configuration Poles Trip Unit Option 1. Standard-function trip unit 23 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics LE, LX AND LXI 600 A FRAME CIRCUIT BREAKERS This section provides specific information on LE, LX and LXI electronic trip circuit breakers. Table 10. LE, LX, and LXI Circuit Breaker Catalog Numbers1 Features Sensor Size Ampere Rating • Long-Time • Instantaneous • Long-Time • Short-Time • Instantaneous • Long-Time • Instantaneous w/Ground-Fault Protection • Long-Time • Short-Time • Instantaneous w/Ground-fault Protection • Long-Time • Instantaneous w/Ground-fault Alarm • Long-Time • Short-Time • Instantaneous w/Ground-fault Alarm Rating Plug Installed LE Circuit Breaker with MICROLOGIC® Full-Function Trip System2 250 100 125 150 175 200 225 250 LE(L)36100LI LE(L)36125LI LE(L)36150LI LE(L)36175LI LE(L)36200LI LE(L)36225LI LE(L)36250LI LE(L)36100LS LE(L)36125LS LE(L)36150LS LE(L)36175LS LE(L)36200LS LE(L)36225LS LE(L)36250LS LE(L)36100LIG LE(L)36125LIG LE(L)36150LIG LE(L)36175LIG LE(L)36200LIG LE(L)36225LIG LE(L)36250LIG LE(L)36100LSG LE(L)36125LSG LE(L)36150LSG LE(L)36175LSG LE(L)36200LSG LE(L)36225LSG LE(L)36250LSG LE(L)36100LIA LE(L)36125LIA LE(L)36150LIA LE(L)36175LIA LE(L)36200LIA LE(L)36225LIA LE(L)36250LIA LE(L)36100LSA LE(L)36125LSA LE(L)36150LSA LE(L)36175LSA LE(L)36200LSA LE(L)36225LSA LE(L)36250LSA ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 400 300 350 400 LE(L)36300LI LE(L)36350LI LE(L)36400LI LE(L)36300LS LE(L)36350LS LE(L)36400LS LE(L)36300LIG LE(L)36350LIG LE(L)36400LIG LE(L)36300LSG LE(L)36350LSG LE(L)36400LSG LE(L)36300LIA LE(L)36350LIA LE(L)36400LIA LE(L)36300LSA LE(L)36350LSA LE(L)36400LSA ARP075 ARP088 ARP100 600 3 450 500 600 LE(L)36450LI LE(L)36500LI LE(L)36600LI LE(L)36450LS LE(L)36500LS LE(L)36600LS LE(L)36450LIG LE(L)36500LIG LE(L)36600LIG LE(L)36450LSG LE(L)36500LSG LE(L)36600LSG LE(L)36450LIA LE(L)36500LIA LE(L)36600LIA LE(L)36450LSA LE(L)36500LSA LE(L)36600LSA ARP075 ARP083 ARP100 LX Circuit Breaker and LXI Current-Limiting Circuit Breaker with MICROLOGIC® Standard-Function Trip System1 250 100 125 150 175 200 225 250 — — — — — — — LX(I)(L)36100 LX(I)(L)36125 LX(I)(L)36150 LX(I)(L)36175 LX(I)(L)36200 LX(I)(L)36225 LX(I)(L)36250 — — — — — — — LX(I)(L)36100G LX(I)(L)36125G LX(I)(L)36150G LX(I)(L)36175G LX(I)(L)36200G LX(I)(L)36225G LX(I)(L)36250G — — — — — — — — — — — — — — ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 400 300 350 400 — — — LX(I)(L)36300 LX(I)(L)36350 LX(I)(L)36400 — — — LX(I)(L)36300G LX(I)(L)36350G LX(I)(L)36400G — — — — — — ARP075 ARP088 ARP100 600 450 500 600 — — — LX(I)(L)36450 LX(I)(L)36500 LX(I)(L)36600 — — — LX(I)(L)36450G LX(I)(L)36500G LX(I)(L)36600G — — — — — — ARP075 ARP083 ARP100 1. The (L) indicates that the letter L is optional. —If no L is used, the circuit breaker is I-LINE® configuration and is shipped with standard mechanical lugs on the OFF end. —If no L is used, the circuit breaker is shipped with standard mechanical lugs at both ends. 2. For non-standard lugs, See “Circuit Breaker Terminations” on page 37. 3. 600 A sensor is 80% rated. Interrupting Ratings Table 11. LE, LX, and LXI Circuit Breaker Interrupting Ratings Circuit Breaker UL/CSA Rated 240 Vac 480 Vac IEC 947-2 415/240 Vac 600 Vac Icu Ics LE, LX 100 kA 65 kA 35 kA 65 kA 65 kA1 LXI 200 kA 200 kA 100 kA 65 kA 65 kA1 1. ICS = 50 kA on 600 Ampere sensor. Lug Information Unit-mount circuit breakers have mechanical lugs standard on both ends. I-LINE® circuit breakers have lugs standard on the OFF end. These lugs accept aluminum or copper wire. Square D has other terminations available as accessories for non-standard applications. For additional lug information, See “Circuit Breaker Terminations” on page 37. 24 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics Continuous Current Ratings LE circuit breakers marked “100% Rated” can be continuously loaded to 100% of their rating. Because of the additional heat generated when applying circuit breakers at 100% of continuous current rating, the use of specially designed enclosures and 90°C rated wire is required. Table 12. LE, LX, and LXI Circuit Breaker Continuous Current Ratings Circuit Breaker Trip System Sensor Size LX, LXI 250 A Standard-Function MICROLOGIC® trip system 400 A 600 A LE Full-Function MICROLOGIC® trip system Max. Continuous Current Rating 80% 250 A 400 A 100% 600 A 80% Markings on the circuit breaker indicate minimum enclosure size and ventilation specifications required. The 90°C wire must be sized according to the ampacities of the 75°C wire column in the NEC. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. Accessories Accessories are available either factory installed or field installable. They can be installed in accessory slots on either side of the circuit breaker handle. For additional accessory information, See “Section 4—Accessories” on page 33. Table 13. LE, LX, and LXI Circuit Breaker Accessories Field Installable Description Factory Installed LE LX, LXI LE Shunt Trip × × × LX, LXI × Undervoltage Trip × × × × Auxiliary Switches × × × × Alarm Switch — — × × × × — — Electrical Trip Indicator Handle Padlock Attachment S1 × S1 — Local Current Meter S1 × S1 — Neutral Current Transformer2 × × — — Electrical Operator — — — — Trip Unit Seal × × — — CIM3F communications Adapter × — — — 1. Standard item shipped with circuit breaker. 2. External Accessory: only needed when a neutral is associated with the load on a ground fault circuit breaker. Control Wiring Control Wiring and Terminal Block Wiring Terminals1 Full-Function Trip System Number Terminal Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac ST Restraint IN ST Restraint OUT GF Restraint IN or Reserved (GF Alarm) GF Restraint OUT or Reserved (GF Alarm) Restraint COM CIM3F-RED CIM3F-BLACK Reserved CIM3F-BLUE CIM3F-ORANGE Reserved Standard-Function Trip System Number Terminal Name 1 2 3 4 5–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac Reserved 06023033 Table 14. Control wiring is connected to terminals located under the circuit breaker access cover. Full-function Trip System OFF ON OFF OFF Standardfunction Trip System 1. Torque wire binding screws to 5–10 lb-in (0.6–1.1 N•m). Use (1) #14 AWG or (1 or 2) #18 AWG wires. 25 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics ME AND MX 800 A FRAME CIRCUIT BREAKERS This section provides specific information on ME and MX electronic trip circuit breakers. For additional trip unit information, see page 15. Table 15. ME and MX Circuit Breaker Catalog Numbers Features Sensor Size Ampere Rating • Long-Time • Instantaneous • Long-Time • Short-Time • Instantaneous • Long-Time • Instantaneous w/Ground-Fault Protection • Long-Time • Short-Time • Instantaneous w/ Ground-fault Protection • Long-Time • Instantaneous w/Ground-fault Alarm • Long-Time • Short-Time • Instantaneous w/Ground-fault Alarm Rating Plug Installed ME Circuit Breaker with MICROLOGIC® Full-Function Trip System1 250 100 125 150 175 200 225 250 ME(L)36100LI ME(L)36125LI ME(L)36150LI ME(L)36175LI ME(L)36200LI ME(L)36225LI ME(L)36250LI ME(L)36100LS ME(L)36125LS ME(L)36150LS ME(L)36175LS ME(L)36200LS ME(L)36225LS ME(L)36250LS ME(L)36100LIG ME(L)36125LIG ME(L)36150LIG ME(L)36175LIG ME(L)36200LIG ME(L)36225LIG ME(L)36250LIG ME(L)36100LSG ME(L)36125LSG ME(L)36150LSG ME(L)36175LSG ME(L)36200LSG ME(L)36225LSG ME(L)36250LSG ME(L)36100LIA ME(L)36125LIA ME(L)36150LIA ME(L)36175LIA ME(L)36200LIA ME(L)36225LIA ME(L)36250LIA ME(L)36100LSA ME(L)36125LSA ME(L)36150LSA ME(L)36175LSA ME(L)36200LSA ME(L)36225LSA ME(L)36250LSA ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 400 300 350 400 ME(L)36300LI ME(L)36350LI ME(L)36400LI ME(L)36300LS ME(L)36350LS ME(L)36400LS ME(L)36300LIG ME(L)36350LIG ME(L)36400LIG ME(L)36300LSG ME(L)36350LSG ME(L)36400LSG ME(L)36300LIA ME(L)36350LIA ME(L)36400LIA ME(L)36300LSA ME(L)36350LSA ME(L)36400LSA ARP075 ARP088 ARP100 800 450 500 600 700 800 ME(L)36450LI ME(L)36500LI ME(L)36600LI ME(L)36700LI ME(L)36800LI ME(L)36450LS ME(L)36500LS ME(L)36600LS ME(L)36700LS ME(L)36800LS ME(L)36450LIG ME(L)36500LIG ME(L)36600LIG ME(L)36700LIG ME(L)36800LIG ME(L)36450LSG ME(L)36500LSG ME(L)36600LSG ME(L)36700LSG ME(L)36800LSG ME(L)36450LIA ME(L)36500LIA ME(L)36600LIA ME(L)36700LIA ME(L)36800LIA ME(L)36450LSA ME(L)36500LSA ME(L)36600LSA ME(L)36700LSA ME(L)36800LSA ARP056 ARP063 ARP075 ARP088 ARP100 MX Circuit Breaker with MICROLOGIC® Standard-Function Trip System1 250 100 125 150 175 200 225 250 — — — — — — — MX(L)36100 MX(L)36125 MX(L)36150 MX(L)36175 MX(L)36200 MX(L)36225 MX(L)36250 — — — — — — — MX(L)36100G MX(L)36125G MX(L)36150G MX(L)36175G MX(L)36200G MX(L)36225G MX(L)36250G — — — — — — — — — — — — — — ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 400 300 350 400 — — — MX(L)36300 MX(L)36350 MX(L)36400 — — — MX(L)36300G MX(L)36350G MX(L)36400G — — — — — — ARP075 ARP088 ARP100 800 450 500 600 700 800 — — — — — MX(L)36450 MX(L)36500 MX(L)36600 MX(L)36700 MX(L)36800 — — — — — MX(L)36450G MX(L)36500G MX(L)36600G MX(L)36700G MX(L)36800G — — — — — — — — — — ARP056 ARP063 ARP075 ARP088 ARP100 1. The (L) indicates that the letter L is optional —If no L is used, the circuit breaker is I-LINE® configuration and is shipped with standard mechanical lugs on the OFF end. —If L is used, the circuit breaker is shipped with standard mechanical lugs at both ends. —For non-standard lugs, page 33. Interrupting Ratings Table 16. ME and MX Circuit Breaker Interrupting Ratings Circuit Breaker UL Listed/CSA Certified IEC 60947-2 Rated (415/240 Vac) 240 Vac 480 Vac 600 Vac Icu Ics ME 65 kA 65 kA 25 kA 65 kA 33 kA MX 65 kA 65 kA 25 kA 65 kA 33 kA 26 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics Continuous Current Ratings All ME circuit breakers are marked “100% Rated” and can be continuously loaded to 100% of their rating. Because of the additional heat generated when applying circuit breakers at 100% of continuous current rating, the use of specially designed enclosures and 90°C rated wire is required. Table 17. ME and MX Circuit Breaker Continuous Current Ratings Circuit Breaker MICROLOGIC Trip System Sensor Size Max. Continuous Current Rating MX Standard-Function 250 A 400 A 800 A 80% ME Full-Function 250 A 400 A 800 A 100% Markings on the circuit breaker indicate minimum enclosure size and ventilation specifications required. The 90°C wire must be sized according to the ampacities of the 75°C wire column in the NEC. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. Lug Information Unit-mount circuit breakers have mechanical lugs standard on both ends. I-LINE® circuit breakers have lugs standard on the OFF end. These lugs accept aluminum or copper wire. Other terminations are available as accessories for non-standard applications. See Circuit Breaker Terminations on page 37. Accessories Electrical accessories are available factory installed only. Other accessories are available either factory installed or field installable. Accessories are installed in accessory slots on either side of the circuit breaker. See Section 4—Accessories on page 33. Table 18. ME and MX Circuit Breaker Accessories Field Installable Description Shunt Trip Undervoltage Trip Auxiliary Switches Alarm Switch Factory Installed ME MX ME MX — — — — — — — — × × × × × × × × Handle Padlock Attachment × × — — Electrical Trip Indicator Local Current Meter S1 S1 × × S1 S1 — — Neutral Current Transformer 2 Electrical Operator Trip Unit Seal CIM3F Communications Adapter × — × × × — × — — — — — — — — — 1. Standard item shipped with circuit breaker. 2. External Accessory: needed only when a neutral is associated with the load on a ground-fault circuit breaker. Control Wiring Control Wiring and Terminal Block Wiring Terminals Full-Function Trip System Standard-Function Trip System Number Terminal Name Number Terminal Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac ST Restraint IN ST Restraint OUT GF Restraint IN or Reserved (GF Alarm) GF Restraint OUT or Reserved (GF Alarm) Restraint COM CIM3F-RED CIM3F-BLACK Reserved CIM3F-BLUE CIM3F-ORANGE Reserved 1 2 3 4 5–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac Reserved 06023034 Table 19. Control wiring is connected to terminals located under the circuit breaker access cover. Full-function Trip System xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx Standard-function Trip System 1. Torque wire binding screws to 5–10 lb-in (0.6–1.1 Nm). #14 AWG (1) or #18 AWG (1 or 2) wire. 27 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics NE AND NX 1200 A FRAME CIRCUIT BREAKER This section provides specific information on NE and NX electronic trip circuit breakers. For general information, see page 7. For additional trip unit information, see page 15. Table 20. NE and NX Circuit Breaker Catalog Numbers Features Sensor Size Ampere Rating • Long-Time • Instantaneous • Long-Time • Short-Time Instantaneous • Long-Time • Instantaneous w/Ground-Fault Protection • Long-Time • Short-Time • Instantaneous w/Ground-fault Protection • Long-Time • Instantaneous w/Ground-fault Alarm • Long-Time • Short-Time • Instantaneous w/Ground-fault Alarm Rating Plug Installed NE Circuit Breaker with MICROLOGIC Full-Function Trip System1 1200 600 700 800 NE(L)36600LI NE(L)36700LI NE(L)36800LI NE(L)36600LS NE(L)36700LS NE(L)36800LS NE(L)36600LIG NE(L)36700LIG NE(L)36800LIG NE(L)36600LSG NE(L)36700LSG NE(L)36800LSG NE(L)36600LIA NE(L)36700LIA NE(L)36800LIA NE(L)36600LSA NE(L)36700LSA NE(L)36800LSA ARP050 ARP0583 ARP067 900 1000 1200 NE(L)36900LI NE(L)361000LI NE(L)361200LI NE(L)36900LS NE(L)361000LS NE(L)361200LS NE(L)36900LIG NE(L)361000LIG NE(L)361200LIG NE(L)36900LSG NE(L)361000LSG NE(L)361200LSG NE(L)36900LIA NE(L)361000LIA NE(L)361200LIA NE(L)36900LSA NE(L)361000LSA NE(L)361200LSA ARP075 ARP083 ARP100 NX Circuit Breaker with MICROLOGIC Standard-Function Trip System1 1200 600 700 800 — — — NX(L)36600 NX(L)36700 NX(L)36800 — — — NX(L)36600G NX(L)36700G NX(L)36800G — — — — — — ARP050 ARP0583 ARP067 900 1000 1200 — — — NX(L)36900 NX(L)361000 NX(L)361200 — — — NX(L)36900G NX(L)361000G NX(L)361200G — — — — — — ARP075 ARP083 ARP100 1. The (L) indicates that the letter L is optional —If no L is used, the circuit breaker is I-LINE® configuration and is shipped with standard mechanical lugs on the OFF end. —If L is used, the circuit breaker is shipped with standard mechanical lugs at both ends. —For non-standard lugs, See Circuit Breaker Terminations on page 37. Interrupting Ratings Continuous Current Ratings Table 21. NE and NX Interrupting Ratings Circuit Breaker UL/CSA Rated 240 Vac 480 Vac 600 Vac Icu Ics NE 125 kA 100 kA 65 kA – – NX 125 kA 100 kA 65 kA – – IEC 947-2 415/240 Vac All NE circuit breakers are marked “100% Rated” and can be continuously loaded to 100% of their rating. Because of the additional heat generated when applying circuit breakers at 100% of continuous current rating, the use of specially designed enclosures and 90°C rated wire is required. Table 22. Continuous Current Ratings Sensor Size Max. Continuous Current Rating Circuit Breaker MICROLOGIC Trip System NX, NXL Standard-Function 1200 A 80% NE, NEL Full-Function 1200 A 100% Markings on the circuit breaker indicate minimum enclosure size and ventilation specifications required. The 90°C wire must be sized according to the ampacities of the 75°C wire column in the NEC. Circuit breakers with 100% rating can also be used in applications requiring only 80% continuous loading. 28 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics Lug Information Unit-mount circuit breakers have mechanical lugs standard on both ends. I-LINE® circuit breakers have lugs standard on the OFF end. These lugs accept aluminum or copper wire. Square D has other terminations available as accessories for non-standard applications. See “Circuit Breaker Terminations” on page 37. Accessories Accessories are available either factory installed or field installable. They can be installed in accessory slots on either side of the circuit breaker. For additional accessory information, see page 33. Table 23. NE and NX Circuit Breaker Accessories Description Shunt Trip Undervoltage Trip Auxiliary Switches Alarm Switch Field Installable Factory Installed NE NX NE NX × × × × × × × × × × × × × × × × Handle Padlock Attachment × × — — Electrical Trip Indicator Local Current Meter S1 S1 × × S1 S1 — — Neutral Current Transformer 2 Electrical Operator Trip Unit Seal CIM3F Communications Adapter × — × × × — × — — — — — — — — — 1. Standard item shipped with circuit breaker. 2. External Accessory: needed only when a neutral is associated with the load on a ground-fault circuit breaker. Note: To ensure accurate current sensing in neutral conductor, a neutral bus wider than three inches must be notched. see Bus-Bar Notching for Neutral Current Transformer on page 45. Control Wiring Control wiring is connected to terminals located under the circuit breaker access cover. Control Wiring for NE and NX Circuit Breakers 06023035 Figure 4. Full Function Trip System Standard Function Trip System Table 24. Terminal Block Wiring Terminals Full-Function Trip System Standard-Function Trip System Number Terminal Name Number Terminal Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac ST Restraint IN ST Restraint OUT GF Restraint IN or Reserved (GF Alarm) GF Restraint OUT or Reserved (GF Alarm) Restraint COM CIM3F-RED CIM3F-BLACK Reserved CIM3F-BLUE CIM3F-ORANGE Reserved 1 2 3 4 5–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac Reserved 1. Torque wire binding screws to 5–10 lb-in (0.6–1.1 Nm). (1) #14 AWG or (1 or 2) #18 AWG wires. 29 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics PE AND PX 2500 A FRAME CIRCUIT BREAKERS This section provides specific information on PE and PX electronic trip circuit breakers. For general information, see page 7. For trip unit information, on page 15. Table 25. PE and PX Circuit Breaker Catalog Numbers Features Sensor Size Ampere Rating • Long-Time • Instantaneous • Long-Time • Short-Time Instantaneous • Long-Time • Instantaneous w/Ground-Fault Protection • Long-Time • Short-Time • Instantaneous w/Ground-fault Protection • Long-Time • Instantaneous w/Ground-fault Alarm • Long-Time • Short-Time • Instantaneous w/Ground-fault Alarm Rating Plug Installed PE Circuit Breaker with MICROLOGIC® Full-Function Trip System1 1200 A 600 700 800 900 1000 1200 PEF36600LI PEF36700LI PEF36800LI PEF36900LI PEF361000LI PEF361200LI PEF36600LS PEF36700LS PEF36800LS PEF36900LS PEF361000LS PEF361200LS PEF36600LIG PEF36700LIG PEF36800LIG PEF36900LIG PEF361000LIG PEF361200LIG PEF36600LSG PEF36700LSG PEF36800LSG PEF36900LSG PEF361000LSG PEF361200LSG PEF36600LIA PEF36700LIA PEF36800LIA PEF36900LIA PEF361000LIA PEF361200LIA PEF36600LSA PEF36700LSA PEF36800LSA PEF36900LSA PEF361000LSA PEF361200LSA ARP050 ARP058 ARP067 ARP075 ARP083 ARP100 1600 A 1400 1600 PEF361400LI PEF361600LI PEF361400LS PEF361600LS PEF361400LIG PEF361600LIG PEF361400LSG PEF361600LSG PEF361400LIA PEF361600LIA PEF361400LSA PEF361600LSA ARP088 ARP100 2000 A 1800 2000 PEF361800LI PEF362000LI PEF361800LS PEF362000LS PEF361800LIG PEF362000LIG PEF361800LSG PEF362000LSG PEF361800LIA PEF362000LIA PEF361800LSA PEF362000LSA ARP090 ARP100 2500 A 2500 PEF362500LI PEF362500LS PEF362500LIG PEF362500LSG PEF362500LIA PEF362500LSA ARP100 PX Circuit Breaker with MICROLOGIC® Standard-Function Trip System 1200 A 600 700 800 900 1000 1200 – – – – – – PFX36600 PFX36700 PFX36800 PFX36900 PFX361000 PFX361200 – – – – – – PFX36600G PFX36700G PFX36800G PFX36900G PFX361000G PFX361200G – – – – – – – – – – – – ARP050 ARP058 ARP067 ARP075 ARP083 ARP100 1600 A 1400 1600 – – PFX361400 PFX361600 – – PFX361400G PFX361600G – – – – ARP088 ARP100 2000 A 1800 2000 – – PFX361800 PFX362000 – – PFX361800G PFX362000G – – – – ARP090 ARP100 2500 A 2500 – PFX362500 – PFX362500G – – ARP100 1. For non-standard lugs, See “Circuit Breaker Terminations” on page 37. Interrupting Ratings Table 26. PE and PX Circuit Breaker Interrupting Ratings Circuit Breaker UL/CSA Rated/Certified IEC 60947-2 Rated (415/240 Vac) 240 Vac 480 Vac 600 Vac Icu Ics PE 125 kA 100 kA 65 kA 70 kA 53 kA PX 125 kA 100 kA 65 kA 70 kA 53 kA 30 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics Continuous Current Ratings PE circuit breakers marked “100% Rated” can be continuously loaded to 100% of their rating. Because of the additional heat generated when applying circuit breakers at 100% of continuous current rating, the use of specially designed enclosures and 90°C rated wire is required. Table 27. Continuous Current Ratings Circuit Breaker PX PE MICROLOGIC Trip System Sensor Size Max. Continuous Current Rating Standard-Function 1200 A 1600 A 2000 A 2500 A 80% 1200 A 1600 A 2000 A 100% 2500 A 80% Full-Function Note: Markings on the circuit breaker indicate minimum enclosure size and ventilation specifications required. The 90°C wire must be sized according to the ampacities of the 75°C wire column in the NEC. Note: Circuit breakers with 100% rating can be used in applications requiring only 80% continuous loading. Terminations Table 28. Lug Kits for PE and PX Circuit Breakers Catalog Number Conductors Type No. Size 1 1/0 AWG–750 kcmil (50–400 mm2) AL2500PA Mechanical 2 1/0 AWG–300 kcmil (50–150 mm2) VC2500PA7 Compression 1 50–750 kcmil (240–400 mm2) VC2000PA5 Compression 1 2/0 AWG–500 kcmil (70–240 mm2) Note: If mounting circuit breaker in other than Square D equipment, terminal pads may be required to provide electrical spacing for bus or lugs and mounting hardware. Square D equipment provides the necessary spacing. Terminal Pad Usage Table 29. Terminal Pad Usage Requirements Circuit Breaker Connections Terminal Pads Required PE 600–1600 A PX 600–2000 A Bus No Cable Use terminal pad kit PALTB or equivalent bus structure. Cable or Bus Use terminal pad kit supplied with circuit breaker or equivalent bus structure. PE 1800–2500 A PX 2500 A Note: For bus structure dimensions, refer to dimensional drawings on page 43. 31 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 3—Circuit Breaker Specifics Accessories Accessories are available either factory installed or field installable. They can be installed in accessory slots on either side of the circuit breaker. (Suffix numbers are specific to left or right side of circuit breaker.) Field-installable electrical accessories are mounted externally. Factory installed electrical accessories can be mounted externally or internally. Consult the factory for specific customer mounting requirements. For additional accessory information, See Section 4—Accessories. Table 30. PE and PX Circuit Breaker Accessories Field Installable Factory Installed PE PX PE PX Shunt Trip Undervoltage Trip Auxiliary Switches Alarm Switch × × × — × × × — × × × × × × × × Handle Padlock Attachment — — S1 S1 Electrical Trip Indicator Local Current Meter S1 S1 × × S1 S1 — — Neutral Current Transformer 2 Electrical Operator Trip Unit Seal CIM3F Communications Adapter × × × × × × × — — × — — — × — — Description 1. Standard item shipped with circuit breaker. 2. External Accessory: needed only when a neutral is associated with the load on a ground-fault circuit breaker. Control wiring is connected to terminals located under the circuit breaker access cover. Table 31. xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx 06023036 Control Wiring Full-function Trip System Standard Function Trip System Terminal Block Wiring Terminals1 Full-Function Trip System Standard-Function Trip System Number Terminal Name Number Terminal Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac ST Restraint IN ST Restraint OUT GF Restraint IN or Reserved (GF Alarm) GF Restraint OUT or Reserved (GF Alarm) Restraint COM CIM3F-RED CIM3F-BLACK Reserved CIM3F-BLUE CIM3F-ORANGE Reserved 1 2 3 4 5–16 Neutral CT (to X1) Neutral CT (to X2) Ground-Fault Test 120 Vac Ground-Fault Test 120 Vac Reserved 1. Torque wire binding screws to 5–10 lb-in (0.6–1.1 N•m) #14 AWG (1) or #18 AWG (1 or 2) wire. 32 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories SECTION 4—ACCESSORIES Square D electronic trip molded case circuit breakers can be used with a variety of internal and external accessories to increase application versatility and meet the demands of modern electrical distribution systems. Circuit breaker internal accessories are available either factory installed or field installable. External accessories are field installed. FACTORY-INSTALLED ACCESSORIES Factory-installed accessories are internally mounted by the factory. Accessories available as factoryinstalled only cannot be removed or repaired in the field. Order factory-installed accessories by adding the correct suffix number to the standard circuit breaker catalog number. For example: • • Circuit breaker: MXL36800 Circuit breaker with 1021 shunt trip: MXL368001021 FIELD-INSTALLED ACCESSORIES Field-installable accessories can be installed or replaced in the field without affecting the circuit breaker UL Listing or interrupting ratings. These accessories cannot be installed in a mounting location or pole that has a factory-installed accessory installed in it. Field-installable accessories are shipped separately from the circuit breakers. Install and wire fieldinstallable accessories according to the instructions supplied with them. Field-installable accessories can be installed at the factory for an installation surcharge. Order field-installable accessories by adding (1) and the correct suffix number to the circuit breaker family. For example: • • Circuit breaker: LEL36600LSG Circuit breaker with 1021 shunt trip: LC11021 Table 32. Electrical Accessories for Electronic Trip Molded Case Circuit Breakers Description LE, LX, LXI Series 1 ME, MX All Series NE, NX Series 1, 2 and 3 PE, PX Series 4, 5 and 6 Field Installable Factory Installed Only Field Installable Field Installable Ground-Fault Shunt Trip1 Not Available Not Available Not Available Not Available Undervoltage Trip Field Installable Factory Installed Only Field Installable Field Installable Auxiliary Switches Field Installable Factory Installed Only Field Installable Field Installable Factory Installed Only Factory Installed Only Field Installable Factory Installed Only Shunt Trip Alarm Switch 1. Ground fault shunt trip for use with obsolete GP Ground-Sensor® System. Not used with MICROLOGIC® integral ground-fault trip system. 33 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Shunt Trip The shunt trip provides a means of tripping the circuit breaker electrically from a remote location using an external voltage source. A coil clearing contact opens the shunt trip coil circuit when the circuit breaker opens. A 120 Vac shunt trip operates at 55% or more of rated voltage 1. All other shunt trips operate at 75% or more of rated voltage. Table 33. Shunt Trip Clearing Times Circuit Breaker Average Clearing Time LX, LXI, LE 26 ms MX, ME 33 ms NX, NE 35 ms PX, PE 40 ms Figure 5. Shunt Trip Wiring Diagram Coil Clearing Switch (Opens when circuit breaker is shunt tripped) 06023037 Circuit Breaker Shunt Trip Accessory Field Leads S Trip Coil Table 34: Shunt Trip Electrical Specifications. Control Voltage Suffix UL Listed Max. Current—mA (rms) Coil Burden—Max. VA Min. Supply Transformer (VA) L M, N P L M, N P 24 Vac 50/60 Hz 48 Vac 50/60 Hz 120 Vac 50/60 Hz 208 Vac 50/60 Hz 240 Vac 50/60 Hz 277 Vac 50/60 Hz 480 Vac 50/60 Hz 600 Vac 50/60 Hz 1042 1048 10211 10212 10212 10372 10372 1026 Yes Yes Yes Yes Yes Yes Yes No 1250 — 280 596 715 791 1658 — 850 540 240 515 740 50 93 93 3650 540 4000 500 740 50 93 93 30 — 30 124 172 219 796 — 20.4 26 29 107 154 13.9 44.6 44.6 88 26 54 104 154 13.9 44.6 44.6 25 50 50 50 50 25 50 — 6 Vdc 12 Vdc 24 Vdc 48 Vdc 72 Vdc 125 Vdc 250 Vdc 1040 1039 1027 1028 1038 1029 1030 Yes Yes Yes Yes Yes Yes Yes — — 1230 2380 — 6360 — 1714 800 1500 750 200 350 60 6000 6000 460 920 208 80 160 — — 30 114 — 795 — 10.3 9.6 35 36 14.4 43.7 15 36 72 11 44 15 10 40 — — — — — — — 1. LE, LX, LXI 1021 shunt trip operates at 75% or more of 120 Vac. 2. Use Suffix 1086 for PE, PX circuit breakers. 34 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Undervoltage Trip The undervoltage trip accessory trips the circuit breaker when the voltage drops below a preset level. The preset level is 35% to 70% of the control voltage. The undervoltage trip prevents the circuit breaker from being reset until 85% of the control voltage is restored. The monitored circuit voltage can be wired in series with an externally-mounted normally-closed contact which opens the circuit breaker from a remote location. 06023038 Figure 6. Undervoltage Trip Wiring Diagram and Average Clearing Times Undervoltage Trip Circuit Breaker Average Clearing Time Circuit Breaker Accessory Field Leads UV LX, LXI, LE 26 ms MX, ME 33 ms NX, NE 35 ms PX, PE 40 ms NC Switch Undervoltage Trip Operation 06023039 Figure 7. Must Not Trip May Trip Must Trip Must Pickup and Seal May Pickup and Seal 0% 70% 35% 85% 100% Percent of Rated Voltage Table 35. Undervoltage Trip Electrical Specifications Control Voltage Suffix UL Listed Max. Current mA (rms) Max. Inrush Coil Burden (VA) Sealed Min. Supply Transformer (VA) 24 V 50/60 Hz 48 V 50/60 Hz 120 V 50/60 Hz 208 V 50/60 Hz 1143 1157 1121 1122 Yes No Yes Yes 170 — 63 [20]1 30 4.1 7.6 7.6 [3.4]1 6.2 3.4 5.4 5.4 [2.4]1 4.1 25 25 25 25 240 V 50/60 Hz 277 V 50/60 Hz 380 V 50/60 Hz 415 V 50/60 Hz 1124 1142 1148 1149 Yes No No No 32 63 63 63 7.6 7.6 7.6 7.6 5.4 5.4 5.4 3.4 25 25 25 25 440 V 50/60 Hz 480 V 50/60 Hz 600 V 50/60 Hz 6 Vdc 1134 1125 1126 1136 No No No Yes 63 63 63 400 7.6 7.6 7.6 2.4 5.4 5.4 5.4 2.4 25 25 25 — 12 Vdc 24 Vdc 48 Vdc 72 Vdc 1133 1127 1128 1135 Yes Yes For P only For P only 185 69 64 [50]1 45 2.2 1.6 3.1 [2.4]1 3.2 2.2 1.6 3.1 [2.4]1 3.2 — — — — 125 Vdc 250 Vdc 1129 1130 For P only For P only 40 21 5 5.2 5 5.2 — — 1[ ] are values for L-frame circuit breaker accessories 35 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories A Class 8430 phase failure relay used with a circuit breaker with an undervoltage trip provides undervoltage protection on all three phases. Figure 8. Undervoltage Trip/Phase Relay Wiring Diagram L2 L3 N 06023040 L1 L1 Option Control Power Transformer L2 L3 N.O. C Phase Failure Relay N.C. 120 Vac Undervoltage Trip* * For supply voltages other than 120 Vac, a control power tranformer must be used to power up the 120 Vac undervoltage trip Undervoltage Trip Time-Delay Unit An optional adjustable time delay unit, Cat. No. 690UVTD or 690UVDTI, provides a time delay to avoid nuisance circuit breaker opening due to momentary dips in the monitored voltage source. The time delay is adjustable from 0.1 seconds to 0.6 seconds. The time delay unit works only with the 120 Vac undervoltage trip accessory. Note: On PE and PX circuit breaker time delay, time-delay unit only works with internal 1121. Auxiliary Switch An auxiliary switch is a single-pole double-throw switch operated by the movable contact arm assembly. It is used to remotely indicate the position of the circuit breaker contacts, whether open or closed. Auxiliary switches can be used to operate indicator lights, relays, or other accessories. Figure 9. Auxiliary Switch Contact Indication 06023041 Selection Alarm Switch Type of Contacts Suffix Number 1A1B 2A2B 3A3B 1212 1352 1364 Ratings 120 or 240 Vac 120 Vac lamp load 125 Vdc 250 Vdc 10 A (1/3 hp) 4A 1/2 A 1/4 A An alarm switch indicates that a circuit breaker has tripped. An alarm switch is actuated by the tripping mechanism, and is reset automatically when the circuit breaker is reset. It is not actuated when the circuit breaker is manually opened or closed. Maximum ratings are 7 A at 120 Vac or 240 Vac. Table 36. Alarm Switch Contact Indication Contact Type Suffix Circuit Breaker Status Tripped Normally Open (N.O.) Contact 2100 Normally Closed (N.C.) Contact 2103 Open or Closed 36 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories CIRCUIT BREAKER TERMINATIONS The L-, M- and N-frame circuit breakers have mechanical lugs standard on both ends of unit-mounted circuit breakers and on the OFF end of I-LINE® mounted circuit breakers. These lugs accept aluminum or copper wire. Square D has optional terminations available for use in nonstandard applications. The P-frame circuit breakers have terminal pads only (no lugs) standard for bus connections on both ends. Terminal pad kits are required for the use of lugs. For additional information on terminal pad requirements, See “Terminations” on page 31, and “Appendix A—Dimensions” on page 43. Mechanical Lugs Table 37. Optional copper mechanical lugs are available for use with copper wire only. Circuit Breaker Lug Information Catalog Number Used On Number of Lugs Per Kit Conductors Screw Torque Range(1) No. per Lug Wire Binding AWG/kcmil Metric lb-in N•m Lug Mounting lb-in N•m Aluminum Mechanical Lugs AL600LI35 AL600LI5 AL600LI7 AL800MA7 AL900MA AL1200NE6 LE, LX, LXI LE, LX, LXI LE, LX, LXI ME, MX ME, MX NE, NX 1 1 1 1 1 1 2 2 1 2 3 4 #1 AWG–350 kcmil 4/0 AWG–500 kcmil 500–750 kcmil 500–750 kcmil 3/0 AWG–500 kcmil 3/0 AWG–600 kcmil 50–185 mm2 95–240 mm2 240–400 mm2 240–400 mm2 95–240 mm2 95–300 mm2 300 300 350 300 300 330 34 34 39 34 34 37 80 80 80 180 180 225 9 9 9 21 21 25 1 2 1/0 AWG–750 kcmil 1/0 AWG–300 kcmil 50–400 mm2 50–150 mm2 (2) (3) (3) PE, PX 2 (2) AL2500PA (2) (2) (3) (3) 1 1 1 1 1 2 2 1 3 4 #2 AWG–350 kcmil Cu 4/0 AWG–500 kcmil Cu 500–750 kcmil Cu 3/0 AWG–500 kcmil Cu 3/0 AWG–600 kcmil Cu 35–185 mm2 Cu 95–240 mm2 Cu 240–400 mm2 Cu 95–240 mm2 Cu 95–300 mm2 Cu 300 300 350 300 330 34 34 39 34 37 80 80 80 300 330 9 9 9 21 37 Copper Mechanical Lugs CU600LI35 CU600LI5 CU600LI7 CU1000MA CU1200NE6 LE, LX, LXI LE, LX, LXI LE, LX, LXI ME, MX NE, NX Aluminum Compression Lugs VC600LI3(4) VC600LI5(4) VC600LI7(4) VC600MA5 LE, LX, LXI LE, LX, LXI LE, LX, LXI ME, MX 2 2 1 2 1 1 1 1 #4 AWG–300 kcmil 2/0 AWG–500 kcmil 500–750 kcmil 2/0 AWG–500 kcmil 25–150 mm2 70–240 mm2 240–400 mm2 70–240 mm2 — — — — — — — — 180 370 370 300 21 42 42 34 VC800MA7 ME, MX 2 1 1 500–750 kcmil Al 500 kcmil Cu 240–400 mm2 Al 240 mm2 Cu — — — — 300 300 34 34 VC1200NE5 NE, NX 4 1 2/0 AWG–500 kcmil 70–240 mm2 — — 600 68 1 1 500–750 kcmil Al 500 kcmil Cu 240–400 mm2 Al 240 mm2 Cu — — — — 600 600 68 68 2/0 AWG–500 kcmil 70–240 mm2 — — (3) (3) VC1200NE7 NE, NX 4 VC2000PA5 PE, PX 1 1 2 1 1 500–750 kcmil Al 500 kcmil Cu Al 240–400 240 mm2 Cu — — — — (3) (3) (3) (3) 1 2 4 4 1 1 1 1 250–500 kcmil Cu 250–500 kcmil Cu 2/0 AWG–500 kcmil Cu 500–750 kcmil Cu 120–240 mm2 Cu 120–240 mm2 Cu 70–240 mm2 Cu 240–400 mm2 Cu — — — — — — — — 370 300 600 600 42 34 68 68 1 1 6 12 #12–2/0 AWG Cu #14–4 AWG Cu 2.5–70 mm2 Cu 2.5–25 mm2 Cu (1) (1) (1) (1) 300 300 34 34 VC2500PA7 PE, PX mm2 Copper Compression Lugs CVC600LI5(4) CVC600MA5 CVC1200NE5 CVC1200NE7 LE, LX, LXI ME, MX NE, NX NE, NX Power Distribution Connectors PDC6MA20 PDC12MA4 ME, MX ME, MX 1. Unless otherwise specified, wire sizes apply to both aluminum and copper conductors. 2. See instructions with lug for information. 3. PE and PX circuit breakers require use of terminal pads for lug mounting. 4. Lug cannot be used on I-LINE® circuit breakers. 37 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Compression Lugs Square D offers exclusive VERSA-CRIMP® compression lugs in either copper or aluminum. 06900031 Figure 10. VERSA-CRIMP® Compression Lugs Power distribution connectors are available for ME and MX circuit breakers as field-installable kits. They can be used for multiple load wire connections on one circuit breaker. Each is UL Listed for copper wire only. Power distribution connectors are for use on the OFF end of the circuit breaker only, and the OFF end must be connected to the load. 06023041 Power Distribution Connectors CBA I-LINE® Jaw Configuration Standard 3-pole I-LINE® circuit breakers are supplied with an ABC phase jaw configuration. In applications where the jaw configuration must be reversed, specify a CBA jaw configuration by adding CBA at the end of the circuit breaker catalog number. Control Wire Termination Mechanical lug kits (except for PE/PX circuit breaker lug kits) are available with provisions for control wire terminations. The lug body accepts a #6-32 screw included in the kit. The control wire is crimped to a standard wire crimp terminal (not included) and secured to the lug using the screw provided. These lugs are UL Recognized as a circuit breaker component. 06023042 Figure 11. Mechanical Lugs with Control Wire Terminations OTHER ACCESSORIES Electric Joint Compound I-LINE® circuit breakers, I-LINE busway plug-on units, and I-LINE panelboards and switchboards are supplied with factory-applied joint compound on the plug-on connectors. The compound is especially formulated for I-LINE connections and contributes to the overall performance of the connections. If the joint compound is removed, it must be reapplied. A 2-ounce container of joint compound (Cat. No. PJC7201) is available from Square D. Rating Plugs Rating plugs are used on electronic trip circuit breakers to establish the circuit breaker ampere rating. The rating plug varies the circuit breaker ampere rating as a function of the circuit breaker sensor size. Rating plugs are factory installed and are also available in field-installable kits. Table 38. Rating Plugs Catalog Number Multiplier Catalog Number Multiplier ARP040 ARP050 ARP056 ARP058 ARP060 ARP063 ARP067 0.400 0.500 0.563 0.583 0.600 0.630 0.670 ARP070 ARP075 ARP080 ARP083 ARP088 ARP090 ARP100 0.707 0.757 0.807 0.833 0.880 0.900 1.000 38 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Trip Indicator The trip indicator, Cat. No. ALTI (ALTIP for PE/PX circuit breakers), displays “OVERLOAD,” “SHORT CIRCUIT,” or “GROUND FAULT” when the circuit breaker has experienced a trip condition. After the circuit breaker has cleared the fault and is reset, the trip indicator must be manually reset by pushing the indicator reset button. 06023043 Figure 12. ALTI and ALTIP Trip Indicators Ammeter/Trip Indicator The ammeter/trip indicator, Cat. No. ALAM (ALAMP for PE/PX circuit breakers), is provided with every fullfunction trip unit and is available as an option for the standard-function trip unit. It monitors current in phases A, B and C, and ground-fault current flowing in the circuit. Each value can be viewed one at a time using the phase select/indicator reset button. (Phase values are displayed in true rms. Ground-fault current values are displayed in calculated rms based on measured peak current.) A bar graph is provided indicating the level of operating current as a function of the programmed ampere rating of the circuit breaker. 06023044 Figure 13. ALAM and ALAMP Ammeter/Trip Indicators The ammeter/trip indicator displays “OVERLOAD,” “SHORT CIRCUIT,” or “GROUND FAULT” when the circuit breaker has experienced a trip condition. After the circuit breaker has cleared the fault and is reset, the ammeter/trip indicator must be manually reset by pushing the phase sect/indicator reset button. 06023045 Figure 14. Trip Condition Displays on ALAM and ALAMP Ammeter/Trip Indicators 39 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Figure 15. Communications Adapter The field-installable communications adapter, Cat. No. CIM3F, allows a full function circuit breaker trip unit to communicate with a Square D POWERLOGIC® Communications Network. This allows full function circuit breakers to be networked in a POWERLOGIC® system. The communications adapter cannot be used with standard-function circuit breakers. 06023046 Communications Adapter Note: The communications adapter cannot be used with standard-function circuit breakers. Electrical Operators Electrical operators provide ON, OFF and RESET control from remote locations for electronic-trip molded case circuit breakers. When remote indication of the circuit breaker status is required, use of a circuit breaker with a 1A1B auxiliary switch for on-off indications or with an alarm switch for trip indication is necessary. The PAM02 is an electronically-controlled operating mechanism that installs to the top surface of a PX/PE electronic trip circuit breaker. It requires momentary, continuous, or solid state contacts and the correct control voltages. 06023047 Figure 16. PAM02 Wiring Diagram Table 39. PAM02 Electrical Operator Characteristics1 Current Closing Time (sec.) Inrush (peak) Continuous (rms) Endurance (minimum operations) 0.20 40 A 10 A 5000 1. Values are based on 120 Vac 60 Hz control voltage. A 50 Hz supply voltage increases the operating times by approximately 20%. For electrical operator dimensions, see page 51. Note: There are no electrical operators available for the LE/LX/LXI, ME/MX or NE/NX circuit breakers. 40 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories HANDLE ACCESSORIES Handle Extensions A handle extension is available for the LX/LE, MX/ME and NX/NE frame circuit breakers. It fits over the existing handle to ease movement. Handle extensions are not available for PX/PE circuit breakers. Handle Interlocking A handle accessory is available for PX/PE circuit breakers which allows mechanical interlocking with a key interlock (not included in kit). The assembly kit (Cat. No. PAKK) includes hardware to mount the accessory on the circuit breaker handle. Handle Padlocks A handle padlock is available for LX/LE, MX/ME and NX/NE electronic trip molded case circuit breakers to lock the circuit breaker handle in the ON or OFF position with the use of a padlock. A field-installable handle padlock attachment is available for the LX/LXI/LE, MX/ME and NX/NE frame circuit breakers. PX/PE circuit breakers have a built-in (factory installed) padlocking feature for locking OFF only. An additional hinge over hasp feature is available on PX/PE to meet EUSERC requirements—add PL suffix. 06023048 Figure 17. PX and PE Circuit Breaker Handle Padlock Attachment Neutral Current Transformers Current transformers are available for applications requiring ground-fault protection on three-phase, four-wire loads. Neutral current transformers are not required on non-ground fault circuit breakers, or on three-phase, three-wire loads. Table 40. Neutral Current Transformers Circuit Breaker Circuit Breaker Sensor Size Neutral Current Transformer Catalog Number LX, LXI, LE 250 A 400 A 600 A LE2CT2 LE4CT2 LE6CT2 MX, ME 250 A 400 A 800 A ME25CT2 ME4CT2 ME8CT2 NX, NE 1200 A NE12CT2 PX, PE 1200 A 1600 A 2000 A 2500 A PE12CT2 PE16CT2 PE20CT2 PE25CT2 41 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Section 4—Accessories Restraint Interface Modules A restraint interface module is required for zone-selective interlocking when: • • The distance between any two circuit breakers in the restraint system exceeds 1000 ft. (305 m) and/or Trip units of the circuit breakers and/or ground-fault modules to be interlocked are not the same series Note: The restraint interface module cannot be used with standard-function circuit breakers. Figure 18. Restraint Interface Modules Cat. No. RIM32 Cat. No. S48890—120 Vac/24 Vdc S48895—240 Vac/24 Vdc The restraint interface module (catalog numbers S48890 and S48895) is used to allow zone-selective interlocking communications between circuit breakers with Series B to 5.0x and 6.0x MICROLOGIC, MERLIN GERIN, or FEDERAL PIONEER trip units and GC Series ground-fault relays. Trip Unit Seals The NEC allows electronic trip circuit breakers to be used with cable up to the adjusted continuous current rating as long as the circuit breaker has a removable and sealable cover over the trip unit adjustments. Square D trip unit seals are available for all electronic trip molded case circuit breakers: Cat. No. TUSEAL designates a quantity of 100 plastic seals that cannot be removed without being destroyed. Seals installed in posts on the circuit breaker limit access to both the rating plug and the trip unit adjustments. The rating plug and the clear plastic cover over the switches each have one sealing location. Universal Test Set The Universal Test Set, Cat. No. UTS3, is available to test Square D circuit breakers with MICROLOGIC® trip units. It runs trip unit test automatically or manually with prompts to the user for initial information. Testing can be done with the circuit breaker installed in the switchboard, following the directions shipped with the test set. A test module stores data necessary for automatic test for each frame. MICROLOGIC® Series 3B trip units require test module CBTMB, which is included with the Universal Test Set. If an older Universal Test Set is used that does not contain a CBTMB test module, a CBTMB test module must be obtained. Figure 19. Universal Test Set 42 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions APPENDIX A—DIMENSIONS LE, LX AND LXI CIRCUIT BREAKERS 0.55 [14] 2.48 [63] 0.29 [7] 2.50 [64] 6.75 [171] 1.35 [34] 4.86 [123] 0.47 [12] 10.75 [273] 6.63 [168] 10.54 [268] 11.84 [301] Mounting Holes (4) 10-32 × 3-1/2 in. Cap Screws 8.44 [214] 1.38 [35] 0.22 [6] 0.30 [8] 4.26 [108] 0.38 [10] 5.48 [139] 0.87 [22] 6.74 [171] 06023050 7.48 [190] 7.14 [182] 1.77 [45] Neutral Current Transformer for LE, LX and LXI Circuit Breakers 0.17 [4] 0.88 [22] 2.10 [53] 4× 0.40 dia. [10] 0.87 [22] 1.00 [25] 0.25 [6] 0.25 [6] 5.86 [149] 0.81 [21] 2.81 [71] 4.00 [102] 2.04 3× [52] 3× 1.90 [48] 1.62 3× [41] 1.24 [32] 2.50 [64] 2.50 [64] 7.13 [18] 0.85 [22] 1.53 [39] 0.25 [6] 0.56 [14] 2.75 [70] Dimensions: in. [mm] 43 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions ME AND MX CIRCUIT BREAKERS 0.344 dia. [9] 0.620 Counterbore dia. [16] 4 Mounting Holes 1.00 [25] 3.00 [76] 12 Bus Mounting Holes 7/16-14 tapped hole 20–25 lb-ft (27–34 N•m) max. torque 3.00 [76] 06023051 0.22 [6] 3.00 [76] 0.50 [13] 5.90 [150] 1.64 [42] 0.79 [20] 1.64 [42] 5.00 [127] 16 30' ON 11.43 [290] 14.75 [375] 11.43 [290] 8 TRIPPED 5 30' OFF 3.50 [89] 5.09 [129] 10 RESET 1.59 [40] 6.75 [171] 1.66 [42] 1.66 [42] 0.22 [6] 2.73 [69] 2.98 [76] 4.48 [114] 4.37 [111] 5.13 [130] 1.50 [38] 6.50 Max. [165] 8.46 [215] 4.23 [107] 1.64 [42] Neutral Current Transformer for ME and MX Circuit Breakers 2.10 [53] 0.50 [13] 1.05 [27] 0.64 [16] 0.93 [24] 5.74 [146] 7.13 [181] 2.83 [72] 4.93 [125] 1.03 [26] 0.06 [2] 0.78 [20] 3.53 [91] 2.25 [57] 5.86 [149] 2.34 [60] 2.44 [62] 8.96 [228] 0.56 dia. [14] 2 Holes 0.25 [6] 1.00 [25] 0.40 dia. [10] 4 Holes Dimensions: in. [mm] 44 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions 06023052 NE AND NX CIRCUIT BREAKERS 8.10 Max. [206] 6.43 [163] 14.98 [380] 7.49 [190] 5.00 [127] 5.00 [127] 2.50 [63] 4.31 [109] 0.48 [12] 2.50 [63] 2.25 [57] 1.33 [34] 2.25 [57] 1.68 [43] 1.08 [28] 0.92 [23] 21 ˚ ON 8.75 [222] 12.12 [308] 8.17 [208] 10.75 [273] 0.48 [12] 3 TRIPPED 19 30' OFF 1.68 [43] 5.55 [141] 24 30' RESET 4.81 [122] 0.18 [5] 0.92 [23] See Detail A 4.99 [127] 14.62 [371] 1.75 [44] 3/8-16 Hex Head Bolt 140–170 lb-in Torque 3.28 [83] 8.07 [205] 1.64 [42] 2.12 [54] 6.40 [163] 8.07 [205] 0.98 [25] 0.98 [25] 1.08 [27] 4.40 [112] 0.29 [7] 4.40 [112] 5.29 [134] 4.40 [112] 0.25 [6] 10.29 [261] Neutral Current Transformer for NE and NX Circuit Breakers 3.75 [95] 1.75 [44] 1.75 [44] Bus Bar Notching for Neutral Current Transformer 0.50 [13] 1.34 [34] 0.30 0.67 [8] [17] 6.00 [152] 4.07 [10] 1.50 [38] 0.96 [24] 4x 0.32 [8] 1.71 [43] Detail A Bus Mounting Holes 6 places 1.06 [27] 2.90 [74] 3.50 [89] 0.27 dia. [7] 1.25 [32] 0.95 [24] 1.20 [30] 4.00 Bus [102] Neutral CT Assembly 0.11 [3] Notch Bus, Two Places Dimensions: in. [mm] 45 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions Neutral Current Transformer Clearance Requirements for NE and NX Circuit Breakers 06023053 Steel enclosure or other ferrous surface. Neutral Current Transformer 0.75 Min. [19] NE Circuit Breaker 0.75 Min. [19] 1.00 [25] 1.00 [25] Min. Min. 46 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions PE AND PX CIRCUIT BREAKERS 6x 24 x PE and PX Circuit Breaker 0.56 [14] dia. 1.00 [25] 0.75 [19] 2.75 [70] 0.44 [11] dia. 3.00 [76] 1.50 [38] 0.38 [10] 2.00 [51] 1.25 [32] 0.85 [22] 3.25 [83] 0.28 0.50 8 x [7 x [13] Slot ] ON 0.37 [9 ] RE SE 1.60 Max. [40.6 ] 20.10 [511] 40˚ TR IP OFF T 90˚ 14.00 [356] 30˚ 12.00 [305] 9.00 [229] 2.00 [51] 1.75 [44] 0.38 [10] 3.10 [79] 1.50 [38] 1. 0 [25] 0.75 [19] 06023054 0.75 [19] 12.00 [305] 1.50 [38] 4.00 [102] 6.00 [152] 11.00 [279] 5.75 [146] 6.88 [175] 10.47 [266] Dimensions: in. [mm] Neutral Current Transformer for PE and PX Circuit Breakers 4.23 [107] 3.87 [98] 0.56 2 x [14] dia. 06023055 3.06 [78] 8 x 0.44 [11] dia. 2.38 [61] 8.50 [216] 0.40 [10] 2.25 [57] 1.50 [38] 0.75 [19] 0.62 [16] 2.13 [54] 1.37 [35] 2.75 [70] Dimensions: in. [mm] 47 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions 600–1600 A PE and 600–2000 A PX Circuit Breaker with Terminal Pads 06023056 33.50 [851] 32.25 [819] 17.62 [448] 16.55 [420] 1.00 [25] Max 4.59 [117] 3.59 [91] 0.50 [13] 1.20 [30] 14.10 [358] 32.58 [828] Mounting Plane 26.10 [663] Push-to-trip Button 6.10 [155] 6 x 0.437 dia. [11] 9.24 [235] Do Not Run Cables In Shaded Area Rear Support 8.11 [210] 0.12 [3] 1.75 [44] 0.88 [22] 7.00 [178] 16.12 [410] 1.12 [28] 13.38 [340] Front Support 0.13 [3] Dimensions: in. [mm] 48 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions 1800–2500 A PE and 2500 A PX Circuit Breaker with Terminal Pads 1.12 [28] Connector Ho l e 0.59 dia. [15] 1.12 [28] 0.40 [10 ] 06023057 3.46 [88] ON 14.10 [358 ] 26.10 [663] OFF 3.46 [88] 13.33 [339] 7.75 [197] 9.43 [240] 14.60 [371] 23.30 [592] 17.82 [453] 4.12 [105 4.75 [121] 4.12 [105] 4.75 [121] 4.12 [105] 0.72 [18] Dimensions: in. [mm] 49 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions PALTB Terminal Pad Bus for 600–1600 A PE and 600–2000 A PX Circuit Breakers 2.75 [70] 4.12 [105] 8.50 [216] 5.50 Lug Mtg. Holes 0.562 dia. [14] [140] 06023058 3 per bus 3.00 [76] 1.38 [35] 4.38 [111] Rawstock: 6.00 [152] 0.25 [6] Thick Aluminum ASTM B-317 Type 5 Alloy No. 6101 1.50 [38] 2.25 [57] 1.50 [38] 0.75 [19] Dimensions: in. [mm] Terminal Pad Bus for 1800-2500 A PE and 2500 A PX Circuit Breakers 2.75 [60] [70] 1.48 [38] 3.23 [82] 06023059 2.37 4.12 [105] 2.82 [72] 1.50 1.75 [38] [44] 5.42 [138] 8.60 [218] 6.72 [171] 8.35 [212] 0.81 [21] 1.38 [35] Lug Mounting Holes: 0.53 Sq. [13] Eight Per Terminal 1.38 [35] Rawstock: 1.50 [38] 0.25 [6] Thick Copper Tin Plated 6.00 [152] 5.68 [144] 6.56 [167] Dimensions: in. [mm] 50 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions Electrical Operator for PX and PE Circuit Breakers 06023060 2.75 [70] 3.00 [76] 20.10 [511] 10.40 [264] 14.00 [356] 3.10 [79] 1.0 [25] 5.75 [146] 6.88 [175] 4.00 [102] 12.00 [305] 6.00 [152] 10.47 [266] Dimensions: in. [mm] 51 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix A—Dimensions 52 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves APPENDIX B—TRIP CURVES Trip curve drawings show the tripping characteristics for electronic trip molded case circuit breakers for the various trip unit settings. Properly adjusted trip unit settings will result in the upstream circuit breaker trip curve falling above and to the right of the downstream (branch) circuit breaker trip curve. This will result in the downstream circuit breaker tripping first, under overload, inrush and low-level short-circuit conditions. 53 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves LE, LX AND LXI CIRCUIT BREAKERS Figure 20. LXI Series 2B 250 A and 400 A Sensor Current Limiting Let-through Curves 54 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 21. LXI Series 2B 600 A Sensor Current Limiting Let-through Curves 55 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 22. LE 250 A, 400 A and 600 A Sensor LS Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 7000 .6 6000 6000 5000 5000 .5 4000 .75 3000 2000 For withstand breaker, turn instantaneous off. 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .9 LE ELECTRONIC TRIP MOLDED CASE CIR CUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 661-1 MICROLOGIC® Full Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous of f. CIRCUIT BREAKER INFORMA TION 3000 Sensor (S) Ampere Rating (P) Suitable Rating Plug Catalog No. Multiplier (%) 250 100 125 150 175 200 225 250 ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 40 50 60 70 80 90 100 400 300 350 400 ARP075 ARP088 ARP100 75 88 100 600 450 500 600 ARP056 ARP063 ARP100 56 63 100 2000 .8 .95 1500 1500 1000 900 800 1000 900 800 12 700 700 600 600 500 500 8 400 400 300 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 6 8 10 12 14 10 4.5 200 14 3 150 100 90 80 6 300 200 150 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip cur ve also. 2 70 60 2 80000 90000 100000 70000 60000 50000 40000 8000 9000 10000 7000 6000 5000 4000 3000 2000 30000 AMPS 2.5 30 20000 40 15000 50 600A 20 .020 4 15 .015 3 .010 .009 .008 250A 400A 6 .007 TIME IN SECONDS 7 .006 6 5 5 4 3 .005 8 SHORT TIME DELAY BANDS I 2 t IN .004 SHORT TIME PICKUP xP 7 .003 MAGNETIC OVERRIDE TIME IN SECONDS 10 9 8 .002 2 .5 .0015 1.5 .32 1 .9 .8 .2 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 .7 .6 .1 .5 .4 .5 SHORT TIME DELAY BANDS I 2 t OUT (FIXED DELAY) .3 .2 .8 .7 .6 .5 .4 .3 .32 .2 .2 .15 .15 .1 .09 .08 .1 .07 .07 .06 .05 MAXIMUM UNRESTRAINED SHORT TIME DELAY .04 .03 2.5 3 4 .06 INSTANTANEOUS PICKUP xP 5 6 7 8 .05 .04 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 56 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS .1 .09 .08 INSTANTANEOUS OVERRIDE (ELECTRONIC) Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 23. LE 250 A, 400 A and 600 A Sensor LI Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 7000 .6 6000 6000 CIRCUIT BREAKER INFORMATION 5000 5000 4000 LE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 661-2 MICROLOGIC® Full Function trip unit with adjustable long time pickup and delay; instantaneous pickup. .5 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .9 .75 3000 2000 .8 .95 1000 900 800 12 600 500 500 8 250 100 125 150 175 200 225 250 ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 40 50 60 70 80 90 100 400 300 350 400 ARP075 ARP088 ARP100 75 88 100 600 450 500 600 ARP056 ARP063 ARP100 56 63 100 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 6 8 10 12 14 300 10 4.5 200 14 150 Multiplier (%) 700 600 400 Suitable Rating Plug2 Catalog No. 1500 1000 900 800 700 Ampere Rating (P) 3000 2000 1500 Sensor (S) 3 6 100 90 80 70 300 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. 200 (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 150 2 60 50 80000 90000 100000 70000 60000 50000 40000 30000 20000 8000 9000 10000 7000 6000 5000 4000 3000 2000 30 15000 AMPS 40 600A 20 .020 .015 15 TIME IN SECONDS .010 .009 .008 250A 400A 7 .007 6 .006 5 .005 .004 4 3 .003 MAGNETIC OVERRIDE TIME IN SECONDS 10 9 8 .002 2 .0015 1.5 1 .9 .8 .8 .7 .7 6 .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 7 2.5 .15 2 3 4 5 INSTANTANEOUS PICKUP xP 8 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 TIME IN SECONDS .1 .09 .08 .15 INSTANTANEOUS OVERRIDE (ELECTRONIC) .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 57 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 24. LE 250 A, 400 A and 600 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 3000 3000 2000 2000 1500 1500 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 300 300 LE ELECTRONIC TRIP MOLDE D CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 661-5 MICROLOGIC ® Full Function trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER IN FORMATION Circuit Breaker Prefix Sensor (S) LE (G) 250 400 600 200 GROUND FAULT PICKUP xS 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 150 15 150 20 200 100 90 80 100 90 80 .65 70 60 70 60 .3 50 50 .45 40 40 30 30 .2 20 20 .25 .35 15 10 9 8 10 9 8 .55 GROUND FAULT BANDS I 2 t IN 7 6 5 7 6 5 4 3 .2 2 4 DELAY SECONDS AT 1xS .10 .20 .32 .50 .32 3 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .5 .6 .6 .5 .5 .5 GROUND FAULT DELAY BANDS I 2 t OUT (FIXED DELAY) .4 .3 .2 .1 .4 .3 .32 .2 .2 .15 .15 .1 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 150 200 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 58 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 15 .75 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 25. LX AND LXI 250 A, 400 A and 600 A Sensor Circuit Breaker Trip Curve 10000 9000 8000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 1 .7 LX AND LXI ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 661-3 7000 7000 .6 6000 6000 5000 5000 .5 4000 .9 .75 3000 2000 MICROLOGIC® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup. 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING CIRCUIT BREAKER INFORMATION 3000 Sensor (S) Ampere Rating (P) Suitable Rating Plug Catalog No. Multiplier (%) 250 100 125 150 175 200 225 250 ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 40 50 60 70 80 90 100 400 300 350 400 ARP075 ARP088 ARP100 75 88 100 600 450 500 600 ARP100 ARP063 ARP100 56 63 100 2000 .8 .95 1500 1500 1000 900 800 1000 900 800 12 700 700 600 600 500 500 400 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 6 8 10 12 14 300 8 200 14 150 4.5 100 90 80 2 70 10 300 200 150 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 6 3 60 50 80000 90000 100000 70000 60000 50000 40000 30000 600A 20 2 3 15 .020 4 .015 6 5 6 .010 .009 .008 250A 400A SHORT TIME PICKUP xP 7 .007 .006 .005 5 SHORT TIME DELAY BANDS I 2 t IN 4 3 .004 7 .003 MAGNETIC OVERRIDE TIME IN SECONDS 10 9 8 TIME IN SECONDS 20000 8000 9000 10000 7000 6000 5000 4000 3000 2000 30 15000 AMPS 2.5 40 8 2 .002 .5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1.5 .32 1 .9 .8 .2 .0015 .8 .7 .7 .6 .6 .1 .5 .5 .4 .4 .3 .3 .2 .2 INSTANTANEOUS OVERRIDE (ELECTRONIC) .15 2.5 3 4 5 6 7 8 .1 .09 .08 INSTANTANEOUS PICKUP xP .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 TIME IN SECONDS .1 .09 .08 .15 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 59 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 26. LX AND LXI 250 A, 400 A and 600 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 3000 3000 Circuit Breaker Prefix Sensor (S) 2000 2000 LX (G) LXI (G) 250 400 600 1500 1500 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 LX AND LXI ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 661-4 MICROLOGIC® Standard Function trip unit with adjustable ground fault pickup and delay (G). CIRCUIT BREAKER INFORMATION 300 300 GROUND FAULT PICKUP xS 200 100 90 80 60 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 100 90 80 .65 .45 70 30 150 15 150 20 200 70 60 .3 50 50 .2 40 40 30 30 20 20 15 15 .25 .75 .35 10 9 8 10 9 8 7 .55 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .5 GROUND FAULT DELAY BANDS I 2 t OUT (FIXED DELAY) .4 .3 .2 .4 .3 .32 .2 .2 .15 .15 .1 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 60 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 7 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves ME AND MX CIRCUIT BREAKERS Figure 27. ME 250 A, 400 A and 800 A Sensor LS Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 10000 9000 8000 .7 7000 1 7000 ME ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 666-7 5000 5000 MICROLOGIC® trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous off. 4000 4000 For withstand breaker instantaneous is off. 6000 .6 .9 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .75 Sensor (S) .95 600 500 500 7 300 350 400 RP075 RP088 RP100 75 88 100 800 450 500 600 700 800 RP056 RP063 RP075 RP088 RP100 56 63 75 88 100 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 4.5 70 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 80000 90000 100000 70000 60000 50000 40000 30000 150 20000 11 100 90 80 200 6000 20 3 5000 200 300 2000 300 150 400 700 16 600 400 40 50 60 70 80 90 100 1000 900 800 24 700 250 RP040 RP050 RP060 RP070 RP080 RP090 RP100 1500 15000 1000 900 800 Multiplier (%) 100 125 150 175 200 225 250 8000 9000 10000 1500 Suitable Rating Plug Cat. No. Ampere Rating (P) 2000 .8 7000 2000 CIRCUIT BREAKER INFORMATION 3000 4000 .5 3000 3000 6000 100 90 80 70 60 60 2.5 50 50 2 40 40 2 30 30 4 20 20 3 15 15 6 10 9 8 TIME IN SECONDS 6 5 4 7 8 3 6 SHORT TIME PICKUP XP 5 4 3 10 2 2 .5 1.5 .32 1 .9 .8 .2 .7 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 SHORT TIME DELAY OVERIDE 250, 400 SENSOR .1 .6 .5 .3 .2 1 .9 .8 800 SENSOR .7 .6 .5 SHORT TIME DELAY BANDS 2 1 t OUT (FIXED DELAY) .4 TIME IN SECONDS SHORT TIME DELAY BANDS 1 2 t IN 7 10 9 8 5 .5 .4 .3 .32 .2 .15 .1 .09 .08 .2 MAXIMUM UNRESTRAINED SHORT TIME DELAY .15 .1 .09 .08 .1 .07 .07 .06 .06 3 .05 5 4 .04 12 8 INSTANTANEOUS PICKUP XP 10 6 .05 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 61 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 28. ME 250 A, 400 A and 800 A Sensor LI Circuit Breaker Trip Curve 7000 .6 6000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 10000 9000 8000 1 .7 6000 5000 5000 .9 4000 4000 2000 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .8 3000 Sensor (S) Ampere Rating (P) Suitable Rating Plug Cat. No. Multiplier (%) 2000 1500 .95 1500 1000 900 800 24 1000 900 800 250 100 125 150 175 200 225 250 RP040 RP050 RP060 RP070 RP080 RP090 RP100 40 50 60 70 80 90 100 400 300 350 400 RP075 RP088 RP100 75 88 100 800 450 500 600 700 800 RP056 RP063 RP075 RP088 RP100 56 63 75 88 100 700 700 600 600 16 500 400 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 4.5 70 60 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 600 11 100 90 80 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 500 3 200 150 400 20 150 300 200 300 150 7 300 700 500 100 90 80 24 70 60 2 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 2 .15 4 3 .1 .09 .08 6 10 8 5 .15 INSTANTANEOUS PICKUP XP 12 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .015 .01 .009 .008 1 1 2 CYCLE .01 .009 .008 2 CYCLE 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 62 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS For withstand breaker instantaneous is off. CIRCUIT BREAKER INFORMATION .75 .5 MICROLOGIC® trip unit with adjustable long time pickup and delay; instantaneous pickup. 200 3000 ME ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 666-8 7000 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 29. ME 250 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 ME ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 666-9 MICROLOGIC® trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Sensor (S) ME (G) 250 800 900 1000 700 150 600 200 150 500 200 400 300 300 400 300 200 500 400 150 600 500 80 90 100 700 600 70 1000 900 800 700 60 1000 900 800 50 1500 40 1500 30 2000 15 2000 20 3000 3000 100 90 80 100 90 80 70 70 .25 60 60 .55 50 50 40 40 .75 .35 30 30 GROUND FAULT PICKUP XS 20 .2 15 .45 .3 10 9 8 20 15 .65 10 9 8 7 6 6 GROUND FAULT DELAY BANDS 1 2 t IN 5 4 3 5 DELAY SECONDS AT 1XS .10 .20 .32 .50 .5 2 4 3 2 .32 1.5 1.5 .2 TIME IN SECONDS TIME IN SECONDS 7 1 .9 .8 1 .9 .8 .7 .7 .1 .6 .6 .5 .5 .5 .4 .4 GROUND FAULT DELAY BANDS 1 2 t OUT (FIXED DELAY) .3 .2 .15 .3 .32 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .2 .2 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 63 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 30. ME 400 A and 800 A Sensor Ground-fault Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 ME ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 666-10 MICROLOGIC® trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Sensor (S) ME (G) 400 800 800 900 1000 700 150 600 200 150 500 300 200 400 400 300 300 500 400 200 600 500 150 700 600 80 90 100 700 70 1000 900 800 60 1000 900 800 50 1500 40 1500 30 2000 15 2000 20 3000 3000 100 90 80 100 90 80 70 70 60 60 .2 50 .45 40 50 40 .65 .3 30 30 GROUND FAULT PICKUP XS 20 .25 .55 15 .35 10 9 8 20 15 .75 10 9 8 7 6 6 GROUND FAULT DELAY BANDS 1 2 t IN 5 4 3 5 4 .5 3 DELAY SECONDS AT 1XS .10 .20 .32 .50 2 .32 1.5 2 1.5 .2 1 .9 .8 .7 1 .9 .8 .7 .1 .6 .6 .5 .5 .5 .4 GROUND FAULT DELAY BANDS 1 2 t OUT (FIXED DELAY) .3 .2 .15 .4 .3 .32 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .2 .1 .09 .08 .2 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 64 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 7 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 31. MX 250 A, 400 A and 800 A Sensor Circuit Breaker Trip Curve 80 90 100 Ampere Rating (P) Suitable Rating Plug Catalog No. Multiplier (%) 250 100 125 150 175 200 225 250 ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 40 50 60 70 80 90 100 400 300 350 400 ARP075 ARP088 ARP100 75 88 100 800 450 500 600 700 800 ARP056 ARP063 ARP075 ARP088 ARP100 56 63 75 88 100 3000 2000 1500 .95 1000 900 800 700 600 600 500 500 400 7 150 4.5 100 90 80 3 70 300 200 150 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 5000 200 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 11 2000 300 4000 16 400 80000 90000 100000 700 70000 20 3000 1000 900 800 60000 .8 1500 50000 2000 Sensor (S) 40000 .75 3000 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING 30000 .9 20000 5000 .5 4000 MICROLOGIC® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup. CIRCUIT BREAKER INFORMATION 15000 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 6000 8000 9000 10000 5000 7000 .6 6000 MX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 666-11 7000 7000 10000 9000 8000 1 .7 6000 10000 9000 8000 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 100 90 80 70 2 60 60 50 50 2.5 40 40 2 30 30 3 20 20 4 15 10 9 8 10 9 8 5 SHORT TIME DELAY BANDS I2 t IN 7 6 5 4 7 6 SHORT TIME PICKUP xP 6 5 4 8 3 3 10 .5 2 2 .32 1.5 .2 1 .9 .8 .7 .6 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 INSTANTANEOUS OVERRIDE (MAGNETIC) 250A, 400A SENSOR TIME IN SECONDS TIME IN SECONDS 15 1 .9 .8 800A SENSOR .7 .6 .1 .5 .5 .5 .4 .4 .3 .3 .32 .2 .2 .2 .15 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 3 .05 5 4 .04 12 8 INSTANTANEOUS PICKUP xP 10 6 .05 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 65 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 32. MX 250 A, 400 A, and 800 A Sensor Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 MX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 666-12 7000 7000 6000 6000 5000 5000 MICROLOGIC® Standard Function trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION 4000 4000 3000 3000 2000 2000 1500 1500 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 Circuit Breaker Prefix Sensor (S) MX (G) 250 400 800 300 300 .25 .55 200 200 .75 .35 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 15 20 150 150 100 90 80 100 90 80 70 70 60 60 50 50 40 40 30 30 GROUND FAULT PICKUP xS 20 15 10 9 8 10 9 8 7 .2 6 .45 .3 7 .65 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 GROUND FAULT DELAY BANDS I 2 t OUT (FIXED DELAY) .6 .5 .4 .3 .6 .5 .5 .4 .3 .32 DELAY SECONDS .2 .2 .2 .15 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 150 200 80 90 100 70 50 60 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 66 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 20 15 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves NE AND NX CIRCUIT BREAKERS Figure 33. NE 600 A and 1200 A Sensor LS Circuit Breaker Trip Curve 100 80 90 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 NE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 671-10 10000 9000 8000 .7 7000 4000 .9 MICROLOGIC® trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous off. LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .75 4000 For withstand breaker instantaneous is off. 2000 .95 1000 900 800 700 16 600 500 500 7 1200 RP050 RP058 RP067 RP075 RP083 RP100 Multiplier (%) 50 58 67 75 83 100 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 4.5 70 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 11 100 90 80 200 150 8000 9000 10000 20 3 7000 200 300 2000 300 150 Suitable Rating Plug Cat. No. 600 700 800 900 1000 1200 1000 900 800 600 400 Ampere Rating (P) 1500 24 700 Sensor (S) 2000 .8 1500 CIRCUIT BREAKER INFORMATION 3000 6000 .5 3000 5000 6000 .6 5000 5000 6000 1 4000 7000 3000 .7 .8 .9 1 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 100 90 80 70 60 60 2.5 50 50 2 40 40 2 30 30 4 20 20 3 15 15 6 10 9 8 TIME IN SECONDS 6 5 4 7 8 3 6 SHORT TIME PICKUP XP 5 4 3 10 2 2 .5 1.5 .32 1 .9 .8 .2 .7 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1 .9 .8 SHORT TIME DELAY OVERRIDE .7 .1 .6 .5 .3 .2 .6 .5 SHORT TIME DELAY BANDS 2 1 t OUT (FIXED DELAY) .4 TIME IN SECONDS SHORT TIME DELAY BANDS 1 2 t IN 7 10 9 8 5 .5 .4 .3 .32 MAXIMUM UNRESTRAINED SHORT TIME DELAY .2 .15 .1 .09 .08 .2 .15 .1 .09 .08 .1 .07 .07 .06 .06 3 .05 5 4 .04 12 8 INSTANTANEOUS PICKUP XP 10 6 .05 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 67 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 34. NE 600 A and 1200 A Sensor LI Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 10000 9000 8000 10000 9000 8000 1 6000 5000 5000 4000 4000 .9 CIRCUIT BREAKER INFORMATION LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .75 3000 Ampere Rating(P) Sensor(S) .8 1500 .95 1000 900 800 24 700 700 600 600 16 8000 9000 10000 7000 6000 5000 100 90 80 4.5 70 60 70 60 2 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 2 .15 4 3 .1 .09 .08 6 10 5 8 .15 INSTANTANEOUS PICKUP XP 12 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 8000 9000 10000 7000 5000 6000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 68 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 150 4000 11 3000 3 100 90 80 200 500 20 300 400 200 150 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 7 300 50 58 67 75 83 100 500 400 150 500 Multiplier(%) RP050 RP058 RP067 RP075 RP083 RP100 NOTE: Ampererating(P) = Sensor(S) x ratingplugmultiplier(%) 300 1000 900 800 1200 200 1500 SuitableRatingPlug Cat. No. 600 700 800 900 1000 1200 2000 2000 2000 .5 MICROLOGIC® trip unit with adjustable long time pickup and delay; instantaneouspickup. 1500 3000 NE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 671-11 7000 800 900 1000 .6 6000 .7 700 7000 600 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 35. NE 600 A and 1200 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 NE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 671-12 MICROLOGIC® trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Sensor (S) NE (G) 1200 800 900 1000 700 150 600 200 150 500 200 400 300 300 400 300 200 500 400 150 600 500 80 90 100 700 600 70 1000 900 800 700 60 1000 900 800 50 1500 40 1500 30 2000 15 2000 20 3000 3000 100 90 80 100 90 80 70 70 60 50 60 .45 .2 50 .3 40 .65 40 30 30 GROUND FAULT PICKUP XS 20 .25 .55 15 15 .75 .35 10 9 8 20 10 9 8 7 6 6 GROUND FAULT DELAY BANDS 1 2 t IN 5 4 3 5 4 .5 3 DELAY SECONDS AT 1XS .10 .20 .32 .50 2 1.5 .32 1 .9 .8 2 1.5 1 .9 .8 .2 .7 .7 .1 .6 TIME IN SECONDS TIME IN SECONDS 7 .6 .5 .5 .5 .4 .4 GROUND FAULT DELAY BANDS 1 2 t OUT (FIXED DELAY) .3 .2 .15 .3 .32 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .2 .2 .15 .1 .09 .08 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 69 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 36. NX 250 A, 600 A and 1200 A Sensor Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 10000 9000 8000 .6 .9 7000 7000 6000 50 58 67 75 83 100 1200 600 700 800 900 1000 1200 ARP050 ARP058 ARP067 ARP075 ARP083 ARP100 50 58 67 75 83 100 16 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 3 150 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 4000 4.5 200 3000 7 300 2000 24 11 80000 90000 100000 400 70000 500 400 70 ARP050 ARP058 ARP067 ARP075 ARP083 ARP100 60000 600 500 100 90 80 300 350 400 450 500 600 50000 700 600 150 600A DRAWOUT ONLY 40000 20 700 200 40 50 60 70 80 90 100 30000 1000 900 800 300 250A DRAWOUT ONLY 1500 .95 1000 900 800 Multiplier (%) ARP040 ARP050 ARP060 ARP070 ARP080 ARP090 ARP100 20000 2000 1500 Suitable Rating Plug Catalog No. 100 125 150 175 200 225 250 15000 3000 .8 2000 Ampere Rating (P) 8000 9000 10000 .75 3000 Sensor (S) 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING 7000 1 4000 6000 5000 .7 .5 5000 6000 5000 NX ELECTRONIC TRIP MOLDED CASE CI RCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 671-13 MICROLOGIC ® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay, and instantaneous pickup. CIRCUIT BREAKER IN FORMATION 100 90 80 70 2 60 60 50 50 2.5 40 40 2 30 30 3 20 20 4 15 10 9 8 10 9 8 5 SHORT TIME DELAY BANDS I2 t IN 7 6 5 4 7 6 5 6 4 8 3 3 10 .5 2 2 .32 1.5 1.5 .2 1 .9 .8 .7 .6 .1 .5 .5 .4 1 .9 .8 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 .7 INSTANTANEOUS OVERRIDE (MAGNETIC) .6 .5 .4 .3 .3 .32 .2 .2 .2 .15 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 3 .05 5 4 .04 12 8 INSTANTANEOUS PICKUP xP 10 6 .05 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 70 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 15 SHORT TIME PICKUP xP Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 37. NX 250 A, 600 A and 1200 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 400 300 300 200 200 150 150 100 90 80 .25 70 800 900 1000 500 400 700 600 500 600 700 600 500 1000 900 800 700 400 1000 900 800 250 600 1200 300 1500 Sensor (SI) NX (G) 200 2000 1500 15 2000 Circuit Breaker Prefix 150 3000 80 90 100 4000 3000 70 5000 4000 60 6000 5000 50 6000 NX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 671-14 MICROLOGIC® Standard Function trip unit with adjustable ground fault pickup and delay (G). CIRCUIT BREAKER INFORMATION 40 7000 30 10000 9000 8000 7000 20 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 100 90 80 .55 .35 70 60 60 50 50 40 40 .75 .2 30 30 GROUND FAULT PICKUP xS 20 20 15 15 .45 .65 10 9 8 10 9 8 7 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 TIME IN SECONDS TIME IN SECONDS .3 .6 .6 .5 .5 .5 .4 GROUND FAULT DELAY BANDS I 2 t OUT (FIXED DELAY) .3 .2 .15 .4 .3 .32 DELAY SECONDS .2 .2 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 71 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves PE AND PX CIRCUIT BREAKERS Figure 38. PE 1200 A and 1600 A Sensor LS Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 .6 6000 5000 5000 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/-7.5%) TIMES THE SETTING .9 4000 .75 MICROLOGIC® trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous off. For withstand breaker instantaneous is off. 3000 CIRCUIT BREAKER INFORMATION 2000 2000 .8 1500 .95 Sensor (S) Ampere Rating (P) Suitable Rating Plug Cat. No. Multiplier (%) 1200 600 700 800 900 1000 1200 RP050 RP058 RP067 RP075 RP083 RP100 50 58 67 75 83 100 1600 1400 1600 RP088 RP100 88 100 1500 24 1000 900 800 16 700 600 600 500 500 7 400 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 4.5 80000 90000 100000 70000 60000 50000 40000 30000 150 20000 11 100 90 80 200 15000 20 3 150 NOTE: (P) = Sensor (S) x rating plug multiplier (%) 8000 9000 10000 200 300 2000 300 7000 700 6000 1000 900 800 5000 .5 3000 4000 4000 6000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 677-17 7000 3000 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 100 90 80 70 70 2.5 60 2 50 60 50 40 40 2 30 4 20 30 20 3 15 15 6 10 9 8 6 5 7 7 6 5 8 4 4 3 3 2 2 .5 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 .32 .2 1 .9 .8 1.5 1 .9 .8 SHORT TIME DELAY OVERRIDE .1 .7 .7 .6 .6 SHORT TIME DELAY BANDS 2 1 t OUT (FIXED DELAY) .5 .4 .3 .5 .5 .4 .3 .32 MAXIMUM UNRESTRAINED SHORT TIME DELAY .2 .2 .15 .1 .09 .08 .2 .15 .1 .09 .08 .1 .07 .07 .06 3 .05 5 4 2.5 .06 INSTANTANEOUS PICKUP XP 7 6 8 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 72 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 7 10 9 8 SHORT TIME PICKUP XP 5 SHORT TIME DELAY BANDS 1 2 t IN Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 39. PE 1200 A and 1600 A Sensor LI Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 6000 .6 .9 .75 .95 1500 1000 900 800 24 700 700 LONG TIME DELAY BANDS 1400 1600 RP088 RP100 88 100 4.5 70 8000 9000 10000 7000 6000 5000 4000 3000 2000 11 1500 3 200 150 150 20 100 90 80 300 SECONDS AT 6P 2 3 4.5 7 11 16 20 24 200 100 90 80 70 24 2 60 1600 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 400 7 150 50 58 67 75 83 100 500 400 300 1200 RP050 RP058 RP067 RP075 RP083 RP100 600 16 500 Multiplier (%) 600 700 800 900 1000 1200 200 600 Suitable Rating Plug Cat. No. Ampere Rating (P) 800 900 1000 1000 900 800 Sensor (S) 2000 .8 1500 CIRCUIT BREAKER INFORMATION 3000 700 2000 4000 600 .5 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/-7.5%) TIMES THE SETTING 500 4000 60 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .4 .4 .3 .3 .2 2 .15 3 5 4 2.5 .2 7 6 TIME IN SECONDS TIME IN SECONDS MICROLOGIC® trip unit with adjustable long time pickup and delay; instantaneous pickup. 5000 5000 3000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 677-18 7000 400 6000 10000 9000 8000 1 .7 7000 300 10000 9000 8000 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) .15 8 INSTANTANEOUS PICKUP XP .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 7000 6000 5000 4000 3000 8000 9000 10000 MULTIPLES OF AMPERE RATING (P) 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 73 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 40. PE 1200 A and 1600 A Sensor Ground-Fault Breaker Trip Curve 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-19 MICROLOGIC® trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Sensor (S) PE (G) 1200 1600 800 900 1000 150 700 200 150 600 200 500 300 400 400 300 300 500 400 200 600 500 150 700 600 80 90 100 700 70 1000 900 800 60 1000 900 800 50 1500 40 1500 30 2000 15 2000 20 3000 3000 100 90 80 100 90 80 70 70 60 60 .45 .2 50 50 .3 40 .65 40 30 30 GROUND FAULT PICKUP XS 20 .25 .55 15 .35 10 9 8 20 15 .75 10 9 8 7 6 6 GROUND FAULT DELAY BANDS 1 2 t IN 5 4 3 5 4 .5 3 DELAY SECONDS AT 1XS .10 .20 .32 .50 2 .32 1.5 .2 1 .9 .8 .7 2 1.5 1 .9 .8 .7 .1 .6 .6 .5 .5 .5 .4 .4 GROUND FAULT DELAY BANDS 1 2 t OUT (FIXED DELAY) .3 .2 .15 .3 .32 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .2 .1 .09 .08 .2 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 74 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 7 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 41. PE 2000 A Sensor LS Circuit Breaker Trip Curve 10000 9000 8000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) .6 6000 6000 5000 5000 .9 4000 .5 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/-7.5%) TIMES THE SETTING .75 3000 4000 2000 .8 .95 1000 900 800 16 700 For withstand breaker instantaneous is off. CIRCUIT BREAKER INFORMATION Sensor (S) 1500 24 1000 900 800 MICROLOGIC® trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous off. 3000 2000 1500 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 677-20 7000 Ampere Rating (P) Suitable Rating Plug Cat. No. 1800 2000 2000 Multiplier (%) 90 100 RP090 RP100 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 700 600 600 500 500 7 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 4.5 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 150 6000 11 100 90 80 200 5000 20 3 150 4000 200 300 3000 300 2000 400 100 90 80 70 70 60 60 2.5 2 50 50 40 40 2 30 4 20 30 20 3.5 SHORT TIME PICKUP XP 15 3 10 9 8 5 7 6 5 4.5 4 4 SHORT TIME DELAY OVERRIDE SHORT TIME DELAY OVERRIDE 3 3 .5 2 2 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1.5 .32 1 .9 .8 .2 1.5 1 .9 .8 .1 .7 TIME IN SECONDS TIME IN SECONDS 6 15 10 9 8 SHORT TIME DELAY BANDS 1 2 t IN 7 6 5 .7 .6 .6 .5 SHORT TIME DELAY BANDS 1 2 t OUT (FIXED DELAY) .4 .3 .5 .5 .4 .3 .32 MAXIMUM UNRESTRAINED SHORT TIME DELAY .2 .2 .15 3.5 .1 .09 .08 .2 .15 4.5 .1 .09 .08 .1 .07 .07 .06 3 .05 4 2.5 .06 INSTANTANEOUS PICKUP XP 5 6 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 75 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 42. PE 2000 A Sensor LI Circuit Breaker Trip Curve 10000 9000 8000 6000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 6000 .6 5000 5000 4000 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .9 .5 3000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 677-21 7000 .75 MICROLOGIC® trip unit with adjustable long time pickup and delay; instantaneous pickup. 4000 CIRCUIT BREAKER INFORMATION 3000 Sensor (S) 2000 2000 Suitable Rating Plug Cat. No. 1800 2000 2000 .8 1500 Ampere Rating (P) Multiplier (%) 90 100 RP090 RP100 1500 .95 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 1000 900 800 1000 900 800 24 700 700 600 600 16 500 500 400 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 4.5 70 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 100 90 80 70 24 60 2 50 500 11 100 90 80 150 400 3 200 300 20 150 200 200 300 150 7 300 60 50 2.5 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 5 5 4.5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 INSTANTANEOUS PICKUP XP .6 .5 .6 .5 .4 .4 .3 .3 2 .2 3 .2 6 4 2.5 .15 5 .15 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 76 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 3.5 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 43. PE 2500 A Sensor LS Circuit Breaker Trip Curve 10000 9000 8000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .7 .8 .9 1 .5 .6 MULTIPLES OF AMPERE RATING (P) .6 6000 6000 5000 5000 .9 4000 .5 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/-7.5%) TIMES THE SETTING .75 3000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LS (LSI) CHARACTERISTIC TRIP CURVE NO. 677-22 7000 4000 MICROLOGIC® trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup and instantaneous off. For withstand breaker instantaneous is off. CIRCUIT BREAKER INFORMATION 3000 Sensor (S) Ampere Rating (P) Suitable Rating Plug Cat. No. Multiplier (%) RP100 100 2000 2000 .8 1500 2500 .95 1500 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 24 1000 900 800 1000 900 800 16 700 2500 700 600 600 500 500 7 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 4.5 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 11 100 90 80 200 150 5000 20 3 150 4000 200 300 3000 300 2000 400 100 90 80 70 70 60 60 2.5 2 50 50 2 40 40 30 4 30 SHORT TIME PICKUP XP 2.2 20 3.5 20 15 15 3 10 9 8 6 5 4 10 9 8 7 6 SHORT TIME DELAY OVERRIDE 5 SHORT TIME DELAY OVERRIDE 5 4 3 3 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 .5 2 .32 1.5 1 .9 .8 2 1.5 1 .9 .8 .2 .7 .1 .7 TIME IN SECONDS TIME IN SECONDS 4.5 SHORT TIME DELAY BANDS 1 2 t IN 7 .6 .6 .5 .5 SHORT TIME DELAY BANDS 2 1 t OUT (FIXED DELAY) .4 .3 .2 .5 .4 .3 .32 MAXIMUM UNRESTRAINED SHORT TIME DELAY .2 .15 3.5 .1 .09 .08 .2 .15 4.5 .1 .09 .08 .1 .07 .07 2.5 .06 3 .05 4 2.2 .06 INSTANTANEOUS PICKUP XP 5 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 77 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 44. PE 2500 A Sensor LI Circuit Breaker Trip Curve 10000 9000 8000 6000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 .7 7000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 6000 .6 5000 5000 4000 LONG TIME PICKUP XP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .9 .5 3000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS LI CHARACTERISTIC TRIP CURVE NO. 677-23 7000 .75 MICROLOGIC® trip unit with adjustable long time pickup and delay; instantaneous pickup. 4000 CIRCUIT BREAKER INFORMATION 3000 Sensor (S) 2000 2000 .8 .95 1500 2500 Ampere Rating (P) Suitable Rating Plug Cat. No. Multiplier (%) RP100 100 2500 1500 NOTE: Ampere rating (P) = Sensor (S) x rating plug multiplier (%) 1000 900 800 1000 900 800 24 700 700 600 600 16 500 500 400 400 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 4.5 70 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 100 90 80 70 24 60 2 50 500 11 400 3 100 90 80 200 150 300 20 150 200 200 300 150 7 300 60 50 2.5 40 40 30 30 3.5 20 20 15 15 10 9 8 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 INSTANTANEOUS PICKUP XP .6 .5 .6 .5 .4 .4 .3 .3 2.2 5 3 .2 .2 .15 .15 2 4 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 MULTIPLES OF AMPERE RATING (P) 78 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 10 9 8 4.5 7 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 45. PE 2000 A and 2500 A Sensor Ground-Fault Circuit Breaker Trip Curve 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 AMPERES 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 PE ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-24 MICROLOGIC® trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Sensor (S) PE (G) 2000 2500 100 90 80 800000 900000 1000000 700000 150 600000 200 150 500000 300 200 400000 400 300 300000 500 400 200000 600 500 150000 700 600 80000 90000 100000 700 70000 1000 900 800 60000 1000 900 800 50000 1500 40000 1500 30000 2000 15000 2000 20000 3000 3000 100 90 80 720 70 70 1120 60 50 60 50 800 40 40 GROUND FAULT PICKUP AMP 30 20 880 30 20 1200 15 15 640 10 9 8 10 9 8 1040 7 6 6 5 5 4 4 960 3 3 DELAY SECONDS AT 2000A .10 .20 .32 .50 2 1.5 GROUND FAULT DELAY BANDS 1 2 t IN 1 .9 .8 .5 2 1.5 1 .9 .8 32 .7 TIME IN SECONDS TIME IN SECONDS 7 .7 .6 .6 .5 .5 .2 .5 .4 .4 .3 .3 .32 GROUND FAULT DELAY BANDS 1 2 t OUT (FIXED DELAY) .2 .15 .1 MAXIMUM UNRESTRAINED GROUND FAULT DELAY .2 .1 .09 .08 .2 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 700000 600000 500000 400000 300000 800000 900000 1000000 AMPERES 200000 150000 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 .005 70 .006 .005 60 .007 .006 50 .007 79 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 46. PX 1200 A and 1600 A Sensor Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 CIRCUIT BREAKER INFORMATION 5000 .5 2000 .9 1000 900 800 20 700 700 600 600 500 500 400 16 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 16 10 20 24 3 70 ARP088 ARP100 88 100 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 300 200 80000 90000 100000 70000 60000 50000 150 40000 4.5 100 90 80 1400 1600 30000 7 150 1600 20000 24 11 200 50 58 67 75 83 100 2000 300 1200 4000 400 Multiplier (%) ARP050 ARP058 ARP067 ARP075 ARP083 ARP100 1500 .95 1000 900 800 Suitable Rating Plug Catalog No. 600 700 800 900 1000 1200 3000 2000 1500 Ampere Rating (P) 15000 .8 Sensor (S) 8000 9000 10000 .75 3000 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING 5000 4000 7000 8 9 10 7 6 5 4 3 2 1.5 6000 MICROLOGIC® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup. 3000 5000 7000 .6 6000 PX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-25 10000 9000 8000 1 .7 7000 6000 10000 9000 8000 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 100 90 80 70 2 60 60 50 50 40 40 2.5 30 30 3 2 20 20 4 15 10 9 8 10 9 8 5 6 5 4 SHORT TIME PICKUP xP 8 6 7 6 5 4 7 3 3 .5 2 2 .32 1.5 .2 1 .9 .8 .7 .6 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1 .9 .8 INSTANTANEOUS OVERRIDE (MAGNETIC) .1 .7 .6 .5 .5 .5 .4 .4 .3 .3 .32 .2 .2 .2 .15 .15 7 .1 .09 .08 6 .1 .09 .08 .1 .07 .07 3 INSTANTANEOUS PICKUP xP .06 .05 2.5 .06 4 5 8 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE .007 .007 .006 .006 .005 AMPERES 80 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 7000 6000 5000 4000 3000 8000 9000 10000 MULTIPLES OF AMPERE RATING (P) 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .005 TIME IN SECONDS SHORT TIME DELAY BANDS I2 t IN 7 TIME IN SECONDS 15 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 47. PX 1200 A and 1600 A Sensor Ground-Fault Circuit Breaker Trip Curve 8 9 10 600 500 500 400 400 300 300 200 200 150 150 .25 100 90 80 .55 .35 800 900 1000 700 600 700 1000 900 800 700 600 1000 900 800 500 1500 1200 1600 400 2000 1500 Sensor (S) PX (G) 300 2000 Circuit Breaker Prefix 200 3000 150 4000 3000 80 90 100 4000 MICROLOGIC® Standard Functon trip unit with adjustable ground fault pickup and delay. CIRCUIT BREAKER INFORMATION 70 5000 60 6000 5000 50 6000 PX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-26 40 7000 30 10000 9000 8000 7000 15 10000 9000 8000 20 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 MULTIPLES OF SENSOR RATING (S) 100 90 80 70 70 60 60 50 50 40 40 .75 .2 30 30 GROUND FAULT PICKUP xS 20 .3 .45 .65 20 15 10 9 8 10 9 8 7 7 6 6 5 5 4 4 3 3 2 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 TIME IN SECONDS TIME IN SECONDS 15 .5 .5 .5 .4 GROUND FAULT DELAY BANDS I 2 t OUT (FIXED DELAY) .3 .2 .15 .4 .3 .32 DELAY SECONDS .2 .2 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 1 CYCLE 1 2 CYCLE .015 .01 .009 .008 2 CYCLE 800 900 1000 600 700 500 400 300 150 200 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .005 .07 .006 .005 .06 .007 .006 .05 .007 MULTIPLES OF SENSOR RATING (S) 81 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 48. PX 2000 A Sensor Circuit Breaker Trip Curve 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 7000 7000 .6 6000 6000 .7 .5 5000 .95 4000 .8 MICROLOGIC® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup. CIRCUIT BREAKER INFORMATION 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .75 3000 PX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-27 3000 Sensor (S) Ampere Rating (P) Suitable Rating Plug Catalog No. Multiplier (%) 2000 1800 2000 ARP088 ARP100 88 100 2000 2000 1500 .9 1500 1000 900 800 1000 900 800 20 700 700 600 600 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 500 500 400 16 100 90 80 3 70 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 150 100 90 80 70 2 60 200 7000 4.5 6000 7 150 300 5000 11 200 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 18 20 24 24 2000 300 4000 400 3000 5000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 10000 9000 8000 2.5 60 50 50 3 40 40 30 30 3.5 2 20 20 4 15 10 9 8 10 9 8 4.5 SHORT TIME PICKUP xP 6 6 5 4 7 6 5 5 4 3 3 2 2 1.5 .5 1 .9 .8 .32 .7 .6 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1 .9 .8 INSTANTANEOUS OVERRIDE (MAGNETIC) .2 .5 .7 .6 .5 .5 .4 .4 .1 .3 .3 .32 5 .2 .2 2.5 INSTANTANEOUS PICKUP xP .1 .09 .08 .2 4.5 .15 4 .15 6 .1 .09 .08 .1 3.5 .07 .07 .06 .06 3 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE .007 .007 .006 .006 .005 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 7000 6000 5000 4000 3000 8000 9000 10000 MULTIPLES OF AMPERE RATING (P) 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .005 AMPERES 82 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS SHORT TIME DELAY BANDS I 2 t IN 7 TIME IN SECONDS 15 Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 49. PX 2000 A and 2500 A Sensor Ground-Fault Circuit Breaker Trip Curve 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 AMPERES PX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CUR VE NO. 677-28 10000 9000 8000 10000 9000 8000 7000 7000 6000 6000 5000 5000 4000 4000 Circuit Br eaker Pr efix Sensor (S) 3000 3000 PX (G) 2000 2500 2000 2000 1500 1500 1000 900 800 MICROLOGIC and delay . ® Standar d Function trip unit with adjustable gr CIRCUIT BREAKER INFORMA ound fault pickup TION 1000 900 800 1200 700 700 600 600 500 500 400 400 300 300 100 90 80 800000 900000 1000000 700000 600000 500000 400000 300000 200000 150000 80000 90000 100000 70000 60000 50000 40000 150 30000 200 150 15000 200 20000 1120 100 90 80 1040 70 70 60 60 50 50 960 40 40 30 30 GROUND FAULT PICKUP AMPERES 880 20 20 15 15 10 9 8 10 9 8 800 7 7 6 6 5 720 4 TIME IN SECONDS TIME IN SECONDS 5 4 3 3 2 2 640 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 GROUND FAULT DELAY BANDS I 2t OUT (FIXED DELAY) .6 .5 .4 .3 .6 .5 .5 .4 .3 DELAY SECONDS .32 .2 .2 .2 .15 .1 .09 .08 .15 .1 .09 .08 .1 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE .015 .01 .009 .008 1 2 1 CYCLE 1 CYCLE 2 .015 .01 .009 .008 CYCLE 800000 900000 1000000 700000 600000 500000 400000 300000 200000 150000 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 1500 800 900 1000 700 600 500 400 300 200 150 80 90 100 .005 70 .006 .005 60 .007 .006 50 .007 AMPERES 83 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Appendix B—Trip Curves Figure 50. PX 2500 A Sensor Circuit Breaker Trip Curve 10000 9000 8000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 10000 9000 8000 1 7000 7000 .6 6000 6000 .95 .7 .5 5000 CIRCUIT BREAKER INFORMATION 4000 4000 LONG TIME PICKUP xP PICKUP POINT IS 1.075 (+/- 7.5%) TIMES THE SETTING .75 3000 3000 .8 2000 1500 2000 1500 .9 1000 900 800 PX ELECTRONIC TRIP MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 677-29 MICROLOGIC® Standard Function trip unit with adjustable long time pickup and delay; short time pickup and delay; instantaneous pickup. 1000 900 800 20 700 700 600 600 Sensor (S) Ampere Rating (P) Suitable Rating Plug Catalog No. Multiplier (%) 2500 2500 ARP100 100 NOTE: (1) Ampere rating (P) = Sensor (S) x rating plug multiplier. (2) Rating plugs shown reflect those supplied factory installed in the circuit breaker. Circuit breakers using other appropriate rating plugs shall use this trip curve also. 500 500 400 16 100 90 80 3 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 150 7000 4.5 200 6000 7 150 300 5000 200 LONG TIME DELAY BANDS SECONDS AT 6P 2 3 4.5 7 11 16 20 24 24 11 2000 300 4000 400 3000 5000 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF AMPERE RATING (P) 100 90 80 2.2 70 70 2 60 60 50 50 40 40 2.5 30 30 3 2 20 20 15 15 3.5 10 9 8 SHORT TIME DELAY BANDS I 2 t IN 6 5 4 SHORT TIME PICKUP xP 7 6 4.5 5 4 3 3 2 2 1.5 .5 1 .9 .8 .32 .7 .6 1.5 SHORT TIME DELAY SECONDS AT 12P .10 .20 .32 .50 1 .9 .8 INSTANTANEOUS OVERRIDE (MAGNETIC) .2 .7 .6 .5 .5 .5 .4 .4 .1 4.5 .3 .3 .32 4 .2 .2 2.2 .2 .15 3.5 INSTANTANEOUS PICKUP xP .1 .09 .08 .15 5 3 .1 .09 .08 .1 .07 .07 2.5 .06 .06 .05 .05 .04 .04 .03 .03 .02 .02 1 CYCLE 1 CYCLE .015 .01 .009 .008 1 1 2 CYCLE .015 .01 .009 .008 2 CYCLE MULTIPLES OF AMPERE RATING (P) 80000 90000 100000 70000 60000 50000 40000 30000 20000 15000 8000 9000 10000 7000 6000 5000 4000 3000 2000 80 90 100 70 60 50 40 30 20 15 10 8 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .006 .005 .6 .007 .006 .5 .007 AMPERES 84 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com TIME IN SECONDS TIME IN SECONDS 10 9 8 5 4 7 Electronic Trip Molded Case Circuit Breakers Glossary GLOSSARY accessory. An electrical or mechanical device that performs a secondary or minor function apart from overcurrent protection. AIC. See AIR AIR. Abbreviation for amps interrupting rating. alarm switch or bell alarm. A mechanicallyoperated switch which indicates when a circuit breaker has tripped due to overcurrent conditions. ambient temperature rating. The temperature of the air immediately surrounding the circuit breaker which can affect the thermal (overload) tripping characteristics of thermalmagnetic circuit breakers. Electronic trip circuit breakers, however, are insensitive to normal (-20 to 50°C) ambient conditions. ammeter/trip indicator or local current meter/ trip indicator. A module that mounts directly to the circuit breaker trip unit. The ammeter (current meter) reports rms phase and ground-fault current values as seen by the trip unit. Current values are displayed one phase at a time. The trip indicator displays whether the circuit breaker tripped due to an overload, short-circuit or ground-fault condition. auxiliary switch. A switch mechanically operated by the main device for signaling, interlocking, or other purposes. bell alarm. see alarm switch. branch circuit. The circuit conductor between the final overcurrent device protecting the circuit and the outlet(s). circuit breaker. A device designed to open and close a circuit by non-automatic means and to open the circuit automatically on an overcurrent without damage to itself when properly applied within its rating. circuit breaker frame. The circuit breaker housing which contains the current carrying components, the current sensing components, and the tripping and operating mechanism. coil clearing switch. A mechanically-operated switch in series with the coil of a shunt trip device which breaks the coil current when the circuit breaker opens. continuous current rating (handle rating). The designated rms alternating current in amperes which a device or assembly will carry continuously in free air without tripping or exceeding temperature limits. continuous load. A load where the maximum current on the circuit is expected to continue for three hours or more. CSA. Canadian Standards Association. CT. Abbreviation for current transformer. current path. The current-carrying conductors within a circuit breaker between, and including, line and load terminations. current sensor. see current transformer. current transformer or current sensor (CT). An instrument to measure current, encircling a conductor carrying the current to be measured or controlled. electrical operator or motor operator. An electrical controlling device which is used to open and close a circuit breaker or switch and reset a circuit breaker. electronic trip circuit breaker. A circuit breaker which uses current sensors and electronic circuitry to sense, measure and respond to current levels. frame size. A group of circuit breakers of similar physical configuration. Frame size is expressed in amperes, corresponding to the largest ampere rating available in the group. frequency. The number of cycles per second for an alternating current system. frequency rating. The range of frequencies within which a product can be applied. ground fault. An unintentional current path, through ground, back to the source. ground-fault delay. The length of time the circuit breaker trip unit will delay before initiating a trip signal to the circuit breaker after a ground fault has been detected. ground-fault module. An electronic accessory used in combination with thermal-magnetic circuit breakers to provide branch circuit ground-fault protection and ground-fault indication. ground-fault pickup. The level of ground-fault current at which the trip system begins timing. handle rating. See continuous current rating. IEC. International Electrotechnical Commission instantaneous pickup. The current level at which the circuit breaker will trip with no intentional time delay. instantaneous trip. A qualifying term indicating that no delay is purposely introduced in the tripping action of the circuit breaker during short-circuit conditions. integral ground-fault protection. Equipment ground-fault protection on grounded neutral 85 06/01 © 1995–2001 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Glossary systems provided by components internal to the circuit breaker. interchangeable trip unit. A trip unit which can be interchanged by a user among circuit breaker frames of the same design. interrupting rating. The highest current at rated voltage available at the incoming terminals of the circuit breaker. When the circuit breaker can be used at more than one voltage, the interrupting rating will be shown on the circuit breaker for each voltage level. The interrupting rating of a circuit breaker must be equal to or greater than the available shortcircuit current at the point at which the circuit breaker is applied to the system. inverse time. A qualifying term indicating there is purposely introduced a delay in the tripping action of the circuit breaker, which delay decreases as the magnitude of the current increases. I2t. See let-through. I2t IN. An inverse time delay characteristic. I2t OUT. A constant time delay characteristic. let-through (I2t). An expression related to energy (measured in ampere-squared seconds) which passes through an overcurrent protective device during an interruption. LI (dual trip device). A combination of adjustable trip functions including long-time ampere rating, long-time delay, and instantaneous pickup. LIG (dual with ground trip device). A combination of adjustable trip functions including long-time ampere rating, long-time delay, instantaneous pickup, ground-fault pickup and ground-fault delay. local current meter. See ammeter/trip indicator. long-time ampere rating. An adjustment which, in combination with the installed rating plug, establishes the continuous current rating of an electronic trip circuit breaker. long-time delay. The length of time the circuit breaker will carry a sustained overload (greater than the long-time pickup) before initiating a trip signal. long-time pickup. The current level at which the circuit breaker long-time delay function begins timing. LS (LSI). A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay and a defeatable instantaneous pickup. LSG (LSIG). A combination of adjustable trip functions including long-time ampere rating, long-time delay, short-time pickup, short-time delay, defeatable instantaneous pickup, ground-fault pickup and ground-fault delay. molded case circuit breaker. A circuit breaker which is assembled as an integral unit in a supportive and enclosed housing of insulating material. molded case switch. A device designed to open and close a circuit by non-automatic means that is not intended to provide overcurrent protection. motor operator or electrical operator. An electrical controlling device which is used to open and close a circuit breaker or switch and reset a circuit breaker. neutral current transformer. A current transformer which encircles the neutral conductor; required for use with circuit breakers with integral ground-fault protection, when applied on a grounded system. operating mechanism. An internal mechanical system which opens and closes the circuit breaker contacts. overcurrent. Any current in excess of the rated continuous current of electrical equipment or the ampacity of a conductor. overload delay. The length of time the circuit breaker will carry a sustained low-level overcurrent before initiating a trip signal. peak current sensing. A method of determining the current flowing in a circuit by measuring the peak amplitude of the current wave each half cycle, then calculating the effective rms. (The effective rms value is assumed to equal 0.707 times the measured peak. This results in accurate rms values on pure sinusoidal waveforms only.) peak let-through. The maximum peak current in a circuit during an overcurrent condition. push-to-trip button. A button for manually tripping the circuit breaker. rating plug. A component which plugs into the trip unit, establishing the ampere rating of the circuit breaker. residual sensing. A means of checking for current imbalance by using a current sensor across each current-carrying conductor to check the magnitude of current flowing in each conductor, then summing all current sensors to check for a current imbalance. restraint interface module (RIM). A component which allows zone-selective interlocking communication between Square D fullfunction electronic trip systems, add-on ground-fault modules and zero-sequence ground-fault relays. RIM. Abbreviation for restraint interface module. rms. Abbreviation for root-mean-square. rms current sensing. A method of determining the true rms current of sinusoidal and nonsinusoidal waveforms by sampling the current 86 © 1995–2001 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 11/01 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Glossary waveform a number of times per cycle, then calculating the true rms value. (Square D circuit breakers sample 33 times per cycle.) sensor. Current sensing element within a circuit breaker frame. The sensor has a current rating less than or equal to the frame size and provides the sensing function for a specific group of current ratings within the frame size. short-circuit delay. The length of time the circuit breaker will carry a short circuit (current greater than the short-circuit pickup) before initiating a trip signal. short-circuit pickup. The current level at which the circuit breaker short-circuit delay function begins timing. short-time delay. The length of time the circuit breaker will carry a short circuit (current greater than the short-time pickup) before initiating a trip signal. short-time pickup. The current level at which the circuit breaker short-time delay function begins timing. shunt trip. An accessory which trips the circuit breaker from a remote location using an external voltage source. STD. See short-time delay. terminal block. The connections for control wiring. thermal-magnetic circuit breaker. A general purpose term for circuit breakers that use bimetals and electromagnetic assemblies to provide both overload and short circuit protection. trip indicator. A module that mounts directly to the circuit breaker trip unit that displays whether the circuit breaker tripped due to an overload, a short-circuit or a ground-fault condition. trip indicator reset. A button on the trip indicator module used to reset the trip indicator. trip system. A system which consists of a MICROLOGIC® trip unit, current transformers, and trip coil. trip unit. A programmable microprocessor-based device which measures and times current flowing through the circuit breaker and initiates a trip signal when appropriate. UL®. Underwriters Laboratories® Inc. undervoltage trip (UVR). An accessory which trips the circuit breaker automatically when the monitored circuit voltage falls below a predetermined percentage of its specified value. UVR. Abbreviation for undervoltage trip release. withstand rating. The level of rms symmetrical current that a circuit breaker can carry with the contacts in a closed position for a stated period of time (usually described as the number of cycles). zero-sequence sensing. A means of sensing the current flowing on a circuit by using one current sensor surrounding all currentcarrying conductors, then checking for current imbalance in the currents flowing in all directions. zone-selective interlocking (ZSI). A communication capability between electronic trip systems and ground-fault relays which permits a short circuit or ground fault to be isolated and cleared by the nearest upstream device with no intentional time delay. ZSI. Abbreviation for zone-selective interlocking. 87 06/01 © 1995–2001 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Glossary 88 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index of Catalog Numbers INDEX OF CATALOG NUMBERS Numerics 690UVDTI ......................................................... 36 690UVTD .......................................................... 36 A AL1200NE6 ...................................................... 37 AL2500PA ..................................................31, 37 AL600LI35 ........................................................ 37 AL600LI5 .......................................................... 37 AL600LI7 .......................................................... 37 AL800MA7 ........................................................ 37 AL900MA .......................................................... 37 ARP040 ............................................... 24, 26, 38 ARP050 ..................................24, 26, 28, 30, 38 ARP056 ......................................................26, 38 ARP058 ......................................................30, 38 ARP0583 .......................................................... 28 ARP060 ............................................... 24, 26, 38 ARP063 ......................................................26, 38 ARP067 ............................................... 28, 30, 38 ARP070 ............................................... 24, 26, 38 ARP075 ..................................24, 26, 28, 30, 38 ARP080 ............................................... 24, 26, 38 ARP083 ........................................ 24, 28, 30, 38 ARP088 ........................................ 24, 26, 30, 38 ARP090 ........................................ 24, 26, 30, 38 ARP100 ..................................24, 26, 28, 30, 38 C CBTMB ............................................................ 42 CIM3F .............................................................. 40 CU1000MA ....................................................... 37 CU1200NE6 ...................................................... 37 CU600LI35 ....................................................... 37 CU600LI5 ......................................................... 37 CU600LI7 ......................................................... 37 CVC1200NE5 .................................................... 37 CVC1200NE7 .................................................... 37 CVC600LI5 ....................................................... 37 CVC600MA5 ..................................................... 37 L LC11021 ........................................................... 33 LE(L)36100LI .................................................... 24 LE(L)36100LIA .................................................. 24 LE(L)36100LIG .................................................. 24 LE(L)36100LS ................................................... 24 LE(L)36100LSA ................................................. 24 LE(L)36100LSG ................................................. 24 LE(L)36125LI .................................................... 24 LE(L)36125LIA .................................................. 24 LE(L)36125LIG .................................................. 24 LE(L)36125LS ................................................... 24 LE(L)36125LSA ................................................. 24 LE(L)36125LSG ................................................. 24 LE(L)36150LI .................................................... 24 LE(L)36150LIA .................................................. 24 LE(L)36150LIG .................................................. 24 LE(L)36150LS ................................................... 24 LE(L)36150LSA ................................................. 24 LE(L)36150LSG ................................................. 24 LE(L)36175LI .................................................... 24 LE(L)36175LIA .................................................. 24 LE(L)36175LIG .................................................. 24 LE(L)36175LS ................................................... 24 LE(L)36175LSA ................................................. 24 LE(L)36175LSG ................................................. 24 LE(L)36200LI .................................................... 24 LE(L)36200LIA .................................................. 24 LE(L)36200LIG .................................................. 24 LE(L)36200LS ................................................... 24 LE(L)36200LSA ................................................. 24 LE(L)36200LSG ................................................. 24 LE(L)36225LI .................................................... 24 LE(L)36225LIA .................................................. 24 LE(L)36225LIG .................................................. 24 LE(L)36225LS ................................................... 24 LE(L)36225LSA ................................................. 24 LE(L)36225LSG ................................................. 24 LE(L)36250LI .................................................... 24 LE(L)36250LIA .................................................. 24 LE(L)36250LIG .................................................. 24 LE(L)36250LS ................................................... 24 LE(L)36250LSA ................................................. 24 LE(L)36250LSG ................................................. 24 LE(L)36300LI .................................................... 24 LE(L)36300LIA .................................................. 24 LE(L)36300LIG .................................................. 24 LE(L)36300LS ................................................... 24 LE(L)36300LSA ................................................. 24 LE(L)36300LSG ................................................. 24 LE(L)36350LI .................................................... 24 LE(L)36350LIA .................................................. 24 LE(L)36350LIG .................................................. 24 LE(L)36350LS ................................................... 24 LE(L)36350LSA ................................................. 24 LE(L)36350LSG ................................................. 24 LE(L)36400LI .................................................... 24 LE(L)36400LIA .................................................. 24 LE(L)36400LIG .................................................. 24 LE(L)36400LS ................................................... 24 LE(L)36400LSA ................................................. 24 LE(L)36400LSG ................................................. 24 LE(L)36450LI .................................................... 24 LE(L)36450LIA .................................................. 24 LE(L)36450LIG .................................................. 24 LE(L)36450LS ................................................... 24 LE(L)36450LSA ................................................. 24 LE(L)36450LSG ................................................. 24 89 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index of Catalog Numbers LE(L)36500LI ..................................................... 24 LE(L)36500LIA .................................................. 24 LE(L)36500LIG .................................................. 24 LE(L)36500LS ................................................... 24 LE(L)36500LSA ................................................. 24 LE(L)36500LSG ................................................. 24 LE(L)36600LI ..................................................... 24 LE(L)36600LIA .................................................. 24 LE(L)36600LIG .................................................. 24 LE(L)36600LS ................................................... 24 LE(L)36600LSA ................................................. 24 LE(L)36600LSG ................................................. 24 LE2CT2 ............................................................ 41 LE4CT2 ............................................................ 41 LE6CT2 ............................................................ 41 LEL36600LSG ................................................... 33 LX(I)(L)36100 .................................................... 24 LX(I)(L)36100G .................................................. 24 LX(I)(L)36125 .................................................... 24 LX(I)(L)36125G .................................................. 24 LX(I)(L)36150 .................................................... 24 LX(I)(L)36150G .................................................. 24 LX(I)(L)36175 .................................................... 24 LX(I)(L)36175G .................................................. 24 LX(I)(L)36200 .................................................... 24 LX(I)(L)36200G .................................................. 24 LX(I)(L)36225 .................................................... 24 LX(I)(L)36225G .................................................. 24 LX(I)(L)36250 .................................................... 24 LX(I)(L)36250G .................................................. 24 LX(I)(L)36300 .................................................... 24 LX(I)(L)36300G .................................................. 24 LX(I)(L)36350 .................................................... 24 LX(I)(L)36350G .................................................. 24 LX(I)(L)36400 .................................................... 24 LX(I)(L)36400G .................................................. 24 LX(I)(L)36450 .................................................... 24 LX(I)(L)36450G .................................................. 24 LX(I)(L)36500 .................................................... 24 LX(I)(L)36500G .................................................. 24 LX(I)(L)36600 .................................................... 24 LX(I)(L)36600G .................................................. 24 M ME(L)36100LI .................................................... 26 ME(L)36100LIA ................................................. 26 ME(L)36100LIG ................................................. 26 ME(L)36100LS .................................................. 26 ME(L)36100LSA ................................................ 26 ME(L)36100LSG ................................................ 26 ME(L)36125LI .................................................... 26 ME(L)36125LIA ................................................. 26 ME(L)36125LIG ................................................. 26 ME(L)36125LS .................................................. 26 ME(L)36125LSA ................................................ 26 ME(L)36125LSG ................................................ 26 ME(L)36150LI .................................................... 26 ME(L)36150LIA ................................................. 26 ME(L)36150LIG ................................................. 26 ME(L)36150LS .................................................. 26 ME(L)36150LSA ................................................ 26 ME(L)36150LSG ................................................ 26 ME(L)36175LI .................................................... 26 ME(L)36175LIA .................................................. 26 ME(L)36175LIG ................................................. 26 ME(L)36175LS .................................................. 26 ME(L)36175LSA ................................................ 26 ME(L)36175LSG ................................................ 26 ME(L)36200LI .................................................... 26 ME(L)36200LIA .................................................. 26 ME(L)36200LIG ................................................. 26 ME(L)36200LS .................................................. 26 ME(L)36200LSA ................................................ 26 ME(L)36200LSG ................................................ 26 ME(L)36225LI .................................................... 26 ME(L)36225LIA .................................................. 26 ME(L)36225LIG ................................................. 26 ME(L)36225LS .................................................. 26 ME(L)36225LSA ................................................ 26 ME(L)36225LSG ................................................ 26 ME(L)36250LI .................................................... 26 ME(L)36250LIA .................................................. 26 ME(L)36250LIG ................................................. 26 ME(L)36250LS .................................................. 26 ME(L)36250LSA ................................................ 26 ME(L)36250LSG ................................................ 26 ME(L)36300LI .................................................... 26 ME(L)36300LIA .................................................. 26 ME(L)36300LIG ................................................. 26 ME(L)36300LS .................................................. 26 ME(L)36300LSA ................................................ 26 ME(L)36300LSG ................................................ 26 ME(L)36350LI .................................................... 26 ME(L)36350LIA .................................................. 26 ME(L)36350LIG ................................................. 26 ME(L)36350LS .................................................. 26 ME(L)36350LSA ................................................ 26 ME(L)36350LSG ................................................ 26 ME(L)36400LI .................................................... 26 ME(L)36400LIA .................................................. 26 ME(L)36400LIG ................................................. 26 ME(L)36400LS .................................................. 26 ME(L)36400LSA ................................................ 26 ME(L)36400LSG ................................................ 26 ME(L)36450LI .................................................... 26 ME(L)36450LIA .................................................. 26 ME(L)36450LIG ................................................. 26 ME(L)36450LS .................................................. 26 ME(L)36450LSA ................................................ 26 ME(L)36450LSG ................................................ 26 ME(L)36500LI .................................................... 26 ME(L)36500LIA .................................................. 26 ME(L)36500LIG ................................................. 26 ME(L)36500LS .................................................. 26 ME(L)36500LSA ................................................ 26 ME(L)36500LSG ................................................ 26 ME(L)36600LI .................................................... 26 ME(L)36600LIA .................................................. 26 ME(L)36600LIG ................................................. 26 ME(L)36600LS .................................................. 26 ME(L)36600LSA ................................................ 26 ME(L)36600LSG ................................................ 26 ME(L)36700LI .................................................... 26 ME(L)36700LIA .................................................. 26 ME(L)36700LIG ................................................. 26 ME(L)36700LS .................................................. 26 90 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index of Catalog Numbers ME(L)36700LSA ................................................ 26 ME(L)36700LSG ................................................ 26 ME(L)36800LI ................................................... 26 ME(L)36800LIA ................................................. 26 ME(L)36800LIG ................................................. 26 ME(L)36800LS .................................................. 26 ME(L)36800LSA ................................................ 26 ME(L)36800LSG ................................................ 26 ME25CT2 ......................................................... 41 ME4CT2 ........................................................... 41 ME8CT2 ........................................................... 41 MX(L)36100 ...................................................... 26 MX(L)36100G .................................................... 26 MX(L)36125 ...................................................... 26 MX(L)36125G .................................................... 26 MX(L)36150 ...................................................... 26 MX(L)36150G .................................................... 26 MX(L)36175 ...................................................... 26 MX(L)36175G .................................................... 26 MX(L)36200 ...................................................... 26 MX(L)36200G .................................................... 26 MX(L)36225 ...................................................... 26 MX(L)36225G .................................................... 26 MX(L)36250 ...................................................... 26 MX(L)36250G .................................................... 26 MX(L)36300 ...................................................... 26 MX(L)36300G .................................................... 26 MX(L)36350 ...................................................... 26 MX(L)36350G .................................................... 26 MX(L)36400 ...................................................... 26 MX(L)36400G .................................................... 26 MX(L)36450 ...................................................... 26 MX(L)36450G .................................................... 26 MX(L)36500 ...................................................... 26 MX(L)36500G .................................................... 26 MX(L)36600 ...................................................... 26 MX(L)36600G .................................................... 26 MX(L)36700 ...................................................... 26 MX(L)36700G .................................................... 26 MX(L)36800 ...................................................... 26 MX(L)36800G .................................................... 26 MXL36800 ........................................................ 33 MXL368001021 ................................................. 33 N NE(L)361000LI .................................................. 28 NE(L)361000LIA ................................................ 28 NE(L)361000LIG ............................................... 28 NE(L)361000LS ................................................. 28 NE(L)361000LSA ............................................... 28 NE(L)361000LSG .............................................. 28 NE(L)361200LI .................................................. 28 NE(L)361200LIA ................................................ 28 NE(L)361200LIG ............................................... 28 NE(L)361200LS ................................................. 28 NE(L)361200LSA ............................................... 28 NE(L)361200LSG .............................................. 28 NE(L)36600LI .................................................... 28 NE(L)36600LIA .................................................. 28 NE(L)36600LIG ................................................. 28 NE(L)36600LS .................................................. 28 NE(L)36600LSA ................................................ 28 NE(L)36600LSG ................................................ 28 NE(L)36700LI .................................................... 28 NE(L)36700LIA .................................................. 28 NE(L)36700LIG ................................................. 28 NE(L)36700LS ................................................... 28 NE(L)36700LSA ................................................ 28 NE(L)36700LSG ................................................ 28 NE(L)36800LI .................................................... 28 NE(L)36800LIA .................................................. 28 NE(L)36800LIG ................................................. 28 NE(L)36800LS ................................................... 28 NE(L)36800LSA ................................................ 28 NE(L)36800LSG ................................................ 28 NE(L)36900LI .................................................... 28 NE(L)36900LIA .................................................. 28 NE(L)36900LIG ................................................. 28 NE(L)36900LS ................................................... 28 NE(L)36900LSA ................................................ 28 NE(L)36900LSG ................................................ 28 NE12CT2 .......................................................... 41 NX(L)361000 ..................................................... 28 NX(L)361000G .................................................. 28 NX(L)361200 ..................................................... 28 NX(L)361200G .................................................. 28 NX(L)36600 ...................................................... 28 NX(L)36600G .................................................... 28 NX(L)36700 ...................................................... 28 NX(L)36700G .................................................... 28 NX(L)36800 ...................................................... 28 NX(L)36800G .................................................... 28 NX(L)36900 ...................................................... 28 NX(L)36900G .................................................... 28 P PAKK ............................................................... 41 PAM02 ............................................................. 40 PDC12MA4 ....................................................... 37 PDC6MA20 ....................................................... 37 PE12CT2 .......................................................... 41 PE16CT2 .......................................................... 41 PE20CT2 .......................................................... 41 PE25CT2 .......................................................... 41 PEF361000LI .................................................... 30 PEF361000LIA .................................................. 30 PEF361000LIG .................................................. 30 PEF361000LS ................................................... 30 PEF361000LSA ................................................. 30 PEF361000LSG ................................................ 30 PEF361200LI .................................................... 30 PEF361200LIA .................................................. 30 PEF361200LIG .................................................. 30 PEF361200LS ................................................... 30 PEF361200LSA ................................................. 30 PEF361200LSG ................................................ 30 PEF361400LI .................................................... 30 PEF361400LIA .................................................. 30 PEF361400LIG .................................................. 30 PEF361400LS ................................................... 30 PEF361400LSA ................................................. 30 PEF361400LSG ................................................ 30 PEF361600LI .................................................... 30 PEF361600LIA .................................................. 30 91 06/02 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index of Catalog Numbers PEF361600LIG .................................................. 30 PEF361600LS ................................................... 30 PEF361600LSA ................................................. 30 PEF361600LSG ................................................. 30 PEF361800LI .................................................... 30 PEF361800LIA .................................................. 30 PEF361800LIG .................................................. 30 PEF361800LS ................................................... 30 PEF361800LSA ................................................. 30 PEF361800LSG ................................................. 30 PEF362000LI .................................................... 30 PEF362000LIA .................................................. 30 PEF362000LIG .................................................. 30 PEF362000LS ................................................... 30 PEF362000LSA ................................................. 30 PEF362000LSG ................................................. 30 PEF362500LI .................................................... 30 PEF362500LIA .................................................. 30 PEF362500LIG .................................................. 30 PEF362500LS ................................................... 30 PEF362500LSA ................................................. 30 PEF362500LSG ................................................. 30 PEF36600LI ...................................................... 30 PEF36600LIA .................................................... 30 PEF36600LIG .................................................... 30 PEF36600LS ..................................................... 30 PEF36600LSA ................................................... 30 PEF36600LSG .................................................. 30 PEF36700LI ...................................................... 30 PEF36700LIA .................................................... 30 PEF36700LIG .................................................... 30 PEF36700LS ..................................................... 30 PEF36700LSA ................................................... 30 PEF36700LSG .................................................. 30 PEF36800LI ...................................................... 30 PEF36800LIA .................................................... 30 PEF36800LIG .................................................... 30 PEF36800LS ..................................................... 30 PEF36800LSA ................................................... 30 PEF36800LSG .................................................. 30 PEF36900LI ...................................................... 30 PEF36900LIA .................................................... 30 PEF36900LIG .................................................... 30 PEF36900LS ..................................................... 30 PEF36900LSA ................................................... 30 PEF36900LSG .................................................. 30 PFX361000 ....................................................... 30 PFX361000G ..................................................... 30 PFX361200 ....................................................... 30 PFX361200G ..................................................... 30 PFX361400 ....................................................... 30 PFX361400G ..................................................... 30 PFX361600 ....................................................... 30 PFX361600G ..................................................... 30 PFX361800 ....................................................... 30 PFX361800G ..................................................... 30 PFX362000 ....................................................... 30 PFX362000G ..................................................... 30 PFX362500 ....................................................... 30 PFX362500G ..................................................... 30 PFX36600 ......................................................... 30 PFX36600G ...................................................... 30 PFX36700 ......................................................... 30 PFX36700G ...................................................... 30 PFX36800 ......................................................... 30 PFX36800G ...................................................... 30 PFX36900 ......................................................... 30 PFX36900G ...................................................... 30 PJC7201 ........................................................... 38 R RIM32 ............................................................... 42 S S48890 ............................................................. 42 S48895 ............................................................. 42 T TUSEAL ........................................................... 42 U UTS3 ................................................................ 42 V VC1200NE5 ...................................................... 37 VC1200NE7 ...................................................... 37 VC2000PA5 ............................................... 31, 37 VC2500PA7 ............................................... 31, 37 VC600LI3 .......................................................... 37 VC600LI5 .......................................................... 37 VC600LI7 .......................................................... 37 VC600MA5 ........................................................ 37 VC800MA7 ........................................................ 37 92 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index INDEX Numerics 100% rating 10 A accessories alarm switch 36 ammeter/trip indicator 39 auxiliary switch 36 communications adapter 40 electrical operators 40 for LE/LX/LXI circuit breakers 25 for ME/MX circuit breakers 27 for NE/NX circuit breakers 29 handle extensions for 41 mechanical interlocking of 41 padlocks for 41 lug kits (PE/PX circuit breakers only) 31 neutral current transformers 41 rating plugs 38 restraint interface module 42 RIM. See restraint interface module shunt trip 34 terminations 37 trip indicator 39 trip unit seals 42 undervoltage trip 35, 36 universal test set 42 ALAM and ALAMP ammeter/trip indicators 39 alarm switch 36 ALTI and ALTIP trip indicators 39 ambient temperature rating 10 ammeter/trip indicator 39 ampere rating 9 auxiliary switch 36 B bus bar notching for neutral current transformer 29 C catalog numbers for LE/LX/LXI circuit breakers 24 for ME/MX circuit breakers 26 for NE/NX circuit breakers 28 for PE/PX circuit breakers 30 circuit breakers accessories for 33 catalog numbers. See catalog numbers connections for 12 control wiring. See control wiring dimensions. See dimensions frame sizes of 9 full-function trip system for 15 ground-fault detection 17 internal operating mechanism for 11 interrupting ratings for LE/LX/LXI circuit breakers 24 for ME/MX circuit breakers 26 for NE/NX circuit breakers 28 for PE/PX circuit breakers 30 maintenance and testing for 14 mounting of 12 push-to-trip button for 11 ratings. See ratings selection of 23 specifications for 9 standard-function trip system for 15 standards for 8 terminal pads for (PE/PX circuit breakers only) 31 terminations for 37 testing requirements for 13 trip characteristics. See trip unit trip curves for 53 tripping system for 11 communications adapter 40 compression lugs 38 connections for I-LINE circuit breakers 12 for unit-mount circuit breakers 12 connectors, power distribution 38 continuous current ratings 25 control wiring for LE/LX/LXI circuit breakers 25 for ME/MX circuit breakers 27 for NE/NX circuit breakers 29 for PE/PX circuit breakers 32 CT. See neutral current transformers D dimensions for LE/LX/LXI circuit breakers 43 for LE/LX/LXI neutral current transformers 43 for ME/MX circuit breakers 44 for ME/MX neutral current transformers 44 for NE/NX circuit breakers 45 for NE/NX neutral current transformers bus bar notching 45 for PE/PX circuit breakers 47 for PE/PX circuit breakers with terminal pads 1800-2500 A PE circuit breakers 49 2500 A PX circuit breakers 49 600-1600 A PE circuit breakers 48 600-2000 A PX circuit breakers 48 for PE/PX neutral current transformers 47 for PE/PX terminal pad bus 1800-2500 A PE circuit breakers 50 1800–2500 A PE circuit breakers 50 2500 A PX circuit breakers 50 E electric joint compound 38 electrical operators 40 electronic trip unit 15 See also trip unit 93 06/02 © 1995–2001 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index F frame size 9 Also see sensor size frequency rating 9 full-function trip system 15 See also full-function trip unit full-function trip unit ground-fault trip functions for 21 instantaneous trip 21 long-time trip function 20 short-time trip function 21 trip curve 20 trip curves 20 trip functions 20 functions description for full-function trip unit 20 standard-function trip unit 19 G ground-fault alarm description of 17 for full-function trip unit 22 detection of 17 full-function trip unit 21 protection description of 17 full-function trip unit 21 standard-function trip unit for 19 zero-sequence, to approximate 22 standard-function trip unit 19 test feature, description of 17 trip functions full-function trip unit 21 standard-function trip unit 19 continuous current ratings for 25 control wiring 25 dimensions for circuit breaker 43 neutral current transformer 43 interrupting ratings 24 lug information for 24 withstand ratings 10 long-time trip function full-function trip unit 20 standard-function trip unit 18 lug information compression lugs 38 control wire terminations 38 copper mechanical lugs 37 LE/LX/LXI circuit breakers 24 ME/MX circuit breakers 27 NE/NX circuit breakers 29 PE/PX circuit breakers 31 power distribution connectors 38 lug kits for PE/PX circuit breakers 31 M maintenance and testing 14 ME/MX circuit breakers accessories for 27 catalog numbers for 26 continuous current ratings 27 control wiring for 27 dimensions for 44 interrupting ratings 26 lug information 27 withstand ratings for 10 memory feature, trip unit 17 mounting 12 mounting kit. See terminal pads H N handle extensions for 41 mechanical interlocking of 41 padlocks for 41 J NE/NX circuit breakers accessories 29 catalog numbers 28, 30 continuous current ratings 28 control wiring 29 dimensions circuit breaker 45 neutral current transformer 45 interrupting ratings 28 lug information 29 withstand rating 10 neutral CT. See neutral current transformers neutral current transformers 41 bus bar notching 45 catalog numbers 41 dimensions NE/NX circuit breakers 45 PE/PX circuit breakers 47 joint compound. See electric joint compound P L PAM02 electrical operator 40 PE/PX circuit breakers accessories 32 catalog numbers 30 continuous current ratings for 31 I instantaneous trip function full-function trip unit 21 standard-function trip unit 19 integral ground-fault detection 17 internal operating mechanism 11 interrupting ratings LE/LX/LXI circuit breakers 24 ME/MX circuit breakers 26 NE/NX circuit breakers 28 PE/PX circuit breakers 30 LE/LX/LXI circuit breakers accessories for 25 catalog numbers for 24 94 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index control wiring for 32 dimensions circuit breaker with terminal pads 48, 49 neutral current transformer 47 terminal pad bus 50 interrupting ratings 30 lug information 31 terminations 31 withstand rating 10 POWERLOGIC system 40 R rating plugs 9, 38 ratings, frequency 9 ratings, interrupting 10 for LE/LX/LXI circuit breakers 24 for ME/MX circuit breakers 26 for NE/NX circuit breakers 28 for PE/PX circuit breakers 30 requirements EUSRC for handle padlocks 41 for circuit breaker testing 13 for restraint interface module (RIM) 42 for series 3B trip unit testing 42 maintenance and testing 14 PAM02 electrical operator 40 power for ground-fault push-to-test 17 terminal pad usage 31, 37 terminal pads 12 terminations 31 wire temperature rating 10, 25, 27, 28, 31 restraint interface modules (RIM) 42 RIM See restraint interface modules RMS sensing 15 S seals, trip unit 42 sensor size 9 short-time trip function full-function trip unit 21 standard-function trip unit 19 shunt trip 34 specifications. See circuit breakers standard-function trip system 15 standard-function trip unit 19 ground-fault trip function 19 instantaneous trip function 19 long-time trip function 18 short-time trip function 19 standards. See circuit breaker switch, alarm 36 switch, auxiliary 36 T temperature rating 10 See also ambient temperature rating temperature rise 13 terminal pads dimensions with circuit breaker 1800–2500 A PE circuit breakers 49 2500 A PX circuit breakers 49 600-1600 A PE circuit breakers 600–1600 A PE circuit breakers 48 600–2000 A PX circuit breakers 48 usage 31 terminations for I-LINE circuit breakers 38 CBA jaw configuration 38 electric joint compound 38 LE/LX/LXI circuit breakers 24 ME/MX circuit breakers 27 NE/NX circuit breakers 29 unit-mount construction 12 testing requirements 13 high available fault current 14 200% overload calibration 14 250% overload calibration 14 dielectric withstand 14 short-circuit test 14 limited available fault current 135% overload calibration 13 200% overload calibration 13 calibration re-test 13 dielectric 13 endurance 13 overload 13 short circuit 13 temperature rise 13 trip out 13 trip characteristics 17 trip curves 53 full-function trip unit 20 standard-function trip unit 19 trip indicator ALAM and ALAMP 39 ALTI and ALTIP 39 trip unit 19, 20 ammeter/trip indicator 16 full-function trip unit 20 integral ground-fault detection 17 memory feature 17 RMS sensing 15 seals 42 setting functions for 15 settings to approx. thermal-magnetic 22 to approx. zero-sequence ground-fault 22 standard-function trip unit 18 trip characteristics 17 tripping system 11 U undervoltage trip 35, 36 adjustable delay 36 universal test set 42 W wiring diagram, PAM02 40 withstand ratings 10 Z zero-sequence ground-fault protection 22 95 06/02 © 1995–2001 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Electronic Trip Molded Case Circuit Breakers Index 96 © 1995–2002 Schneider Electric All Rights Reserved This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 06/02 www.barr-thorp.com This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com Square D Company PO Box 3069 3700 Sixth St SW Cedar Rapids, IA 52406-3069 USA 1-888-SquareD (1-888-778-2733) www.SquareD.com Square D and are registered trademarks of Square D Company or related companies. All other trademarks are the intellectual property of their respective companies. Catalog No. 0602CT9201R1/02 June 2002 Replaces 0602CT9201R11/97 This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com