XG Category 6A FTP Cable 1859218-X Description AMP NETCONNECT Category 6A FTP cables exceed TIA/EIA-568-B.2-10 Category 6A and ISO/IEC 11801:2002 Class EA performance requirements by significant margins on all parameters. The AMP NETCONNECT Category 6A System complies with all of the performance requirements for current and proposed applications such as 10 Gigabit Ethernet, Gigabit Ethernet (1000BASE-Tx), 10/100BASE-Tx, token ring, 155 Mbps ATM, 100 Mbps TPPMD, ISDN, analog and digital video and analog and digital voice (VoIP). Specification (text in brackets [ ] requires a choice) Horizontal cabling shall be 23 AWG, 4-pair FTP, Jacket LSZH rated and shall be independently verified for compliance. Cable jacketing shall be [white, gray, blue]. Cable shall meet all the requirements of TIA 568-B.2-10 as well as the performance requirements listed in the following table: [include Performance Characteristics tables from page 2]. Cable shall be independently verified for performance and characterized to 500 MHz. Independent verification for flammability compliance shall be to NEC article 800 and UL 444. Cable shall be supplied on reels box. Horizontal cable shall be AMP NETCONNECT part number [1859218-X (X denotes jacket color)]. Part Numbers Description Category 6A (XG) FTP Cable, 4-Pair UL/NEC Rating Packaging LSZH 1000FT (305m) WR Part Numbers 1859218-X X denotes jacket color: -2 = White, -4 = Gray, -6 = Blue ©Copyright 2008 by Tyco Electronics Corporation. All Rights Reserved. AMP, AMP NETCONNECT, NETCONNECT, and Tyco are trademarks. Specifications subject to change without notice. Page 1 of 2 XG Category 6A FTP Cable 1859218-X Performance Characteristics (meet or exceed EIA/TIA and ISO requirements) Frequency (MHz) 4 8 10 16 20 25 31.25 62.5 100 150 200 250 300 500 ATTENUATION NEXT (dB/100m) (dB, WORST PR) PSNEXT ELFEXT PSELFEXT DELAY (dB) (dB, WORST PR) (dB) (ns/100m) RL (dB) MAXIMUM MINUMUM MINUMUM MINUMUM MINUMUM MAXIMUM MINUMUM 3.7 5.2 5.9 7.4 8.3 9.3 10.4 14.9 19.0 23.6 27.5 31.0 34.2 45.3 65.3 60.8 59.3 56.2 54.8 53.3 51.9 47.4 44.3 41.7 39.8 38.3 37.1 33.8 63.3 58.8 57.3 54.2 52.8 51.3 49.9 45.4 42.3 39.7 37.8 36.3 35.1 31.8 55.8 49.7 47.8 43.7 41.8 39.8 37.9 31.9 27.8 24.3 21.8 19.8 18.3 13.8 52.8 46.7 44.8 40.7 38.8 36.8 34.9 28.9 24.8 21.3 18.8 16.8 15.3 10.8 552 547 545 543 542 541 540 539 538 537 537 536 536 536 23.0 24.5 25.0 25.0 25.0 24.3 23.6 21.5 20.1 18.9 18.0 17.3 16.8 15.2 IMPEDANCE ACR (dB) (ohms) MINUMUM 100 100 100 100 100 100 100 100 100 100 100 100 100 100 15 15 15 15 15 15 15 15 22 22 22 25 25 25 61 55 53 49 46 44 41 32 24 16.8 10.6 5.3 - Technical Details Materials Electrical Characteristics Conductors – Insulation – Jacket – Filler – Impedance – Propagation delay – Skew – Mutual capacitance – Conductor resistance – Nominal Velocity of Propagation – Mechanical Characteristics Bend radius – Operating temperature – Storage temperature – Approvals Safety – Performance – RoHS Compliant 23 AWG, Solid Copper, (Ø.0225 ± .0001) 0.010in (Ø.044 ± .001), Polyethylene 0.020in nominal (Ø.283 nominal), LSZH Polyethylene 100 ±15%, 1 – 62.5MHZ, 100 ±25%, 250 – 500MHZ 536 ns/100 m max. @ 250 MHz 45ns/100m @ 250MHz maximum 5.6 nF max/100 m 6.65 / 100m maximum @ 20°C 72% The minimum bending radius is 8x outside diameter during installation and 4x the outside diameter after installation 1" -20 C to 60 C (-4° F – 140° F) -20 C to 50 C IEC 60332-1-2 IEC 60754-1 IEC 60754-2 IEC 61034-2 ETL Verified to: TIA/EIA-568-B.2-10 “Performance Specifications for 4-Pair 100 Augmented Category 6 Cabling and ISO/IEC 11801 Ed.2.1 Class EA” Specifications subject to change without notice. Revised 02/10 http://www.ampnetconnect.com/thailand ©Copyright 2008 by Tyco Electronics Corporation. All Rights Reserved. AMP, AMP NETCONNECT, NETCONNECT, and Tyco are trademarks. Specifications subject to change without notice. Page 2 of 2