ELFOENERGY LARGE2
HIGH EFFICIENCY AIR-COOLED LIQUID CHILLER
FOR OUTDOOR INSTALLATION
WSAT-XEE SERIES
Nominal cooling capacity from 97 to 218 kW
ELFOEnergy LARGE2 is a highly energy efficient liquid chiller which is equipped with Scroll
compressors, large heat-exchange surfaces and electronically controlled fans.
Thanks to its excellent partial-load performance, its ESEER seasonal efficiency is at the top of its
category, enabling great savings on management costs over the entire annual cycle. Furthermore, the
standard EXCELLENCE version is in energy efficiency Class A at full-load.
ELFOEnergy LARGE2 is also available in the PREMIUM compact version, which has been optimized
to reduce on the initial investment. It can be equipped with several built-in accessories, like pump
groups, an energy recovery device and an inertial buffer.
ELFOEnergy LARGE2 is, therefore, the centralised solution for all applications which require high
performance, working continuity and management costs reduction.
BT10C001GB-02
ELFOENERGY LARGE2
®
COST OR RELIABILITY?
THE DILEMMA OF MODERN SYSTEM ENGINEERING APPLICATIONS
Air-conditioning systems in trade centres influence both the starting investment and monthly management costs, for the whole
of their working lives.
This theme is even more relevant in residential applications with centralised systems . Furthermore, maximum working
flexibility requirements should be added to that, in serving different users while avoiding wasting energy and thus, money.
Finally, there are several industrial applications which require chilled water as service fluid, process fluid or vector fluid for
operator comfort and for conserving goods and enabling cycles to function correctly.
Furthermore, in all these cases, the working reliability of the system is decisive.
THE HIGH EFFICIENCY HYDRONIC SYSTEMS ARE EXTREMELY
VERSATILE, RELIABLE AND WIDESPREAD
Despite their apparently low costs, split, multi-split and VRF direct expansion
systems have a lot of limits in these applications. For example, they require a
separate system for primary air treatment. The pipes that contain the refrigerant
cross the served rooms and therefore they are subject to restrictions and use
limitations. They cannot operate in the freecooling mode, the high efficiency and
convenient mode that allows energy savings.
the hydronic systems are certainly more complete and versatile. They make it
possible to adopt various types of terminals in the served environment, from fan
coil units exposed or integrated in the furnishings, up to radiant or induction
systems. They are also irreplaceable in the service and process industrial
applications.
The main component performances , like air-cooled liquid chiller, are checked
and certificated by Eurovent.
CLIVET CHILLERS REDUCE CONSUMPTION
AND ARE COMPACT AND RELIABLE
With over twenty years of technological evolution, Clivet liquid
chillers and heat pumps represent the state of the art in
air-conditioning in residential, trade and industrial environments.
Their success is based on high energy efficiency, compactness
and management and maintenance simplicity, with wide versatility
in the choice of the most suitable model for the specific use.
BT10E005GB-02
2
®
ELFOENERGY LARGE2
ELFOEnergy LARGE2 PROVIDES ALL CLIVET TECHNOLOGICAL
DEVELOPMENTS FOR THEIR MEDIUM CAPACITY HYDRONIC SYSTEMS
High-efficiency Scroll compressors, high-performance heat exchangers, electronically-controlled fans, completely automatic
functions: this is just is some of the technology available in ELFOEnergy LARGE2, in a range of models which are ideal for
trade, residential and industrial medium capacity air-conditioning.
The two available versions enable the best
combination to be chosen between initial
investment and entire life cycle system costs.
The EXCELLENCE version has a very high
energy efficiency while working both at partload and full-load (Eurovent class A
certificate at full load)
The PREMIUM version has a high-level of
compactness and high-efficiency at partial
load.
Furthermore, ELFOEnergy Large2 with its
numerous configurations, can be completed
with most common system options built-in.
COMPETITIVE ADVANTAGES
High efficiency all year round
ELFOEnergy LARGE2 reduces the annual energy consumption thanks to its high partial load
efficiency, or the more frequent operating conditions in the system life cycle. So the value of
the building served increases. The main components are manufactured in large numbers on
industrial scale, with the maximum structural reliability and spare parts availability series.
System simplification
All of the features are provided by Clivet already assembled and tested onboard, differently
then other manufacturers who make numerous additional components available to be installed
on site.
Compact and versatile
Suitable for all types of terminals, from the fan systems to the radiant and chilled beams, also
ELFOEnergy LARGE2 has a extremely low noise configuration, hat energy recovery for the
production of free domestic hot water, Master-Slave management devices.
3
BT10E005GB-02
ELFOENERGY LARGE2
®
ELFOEnergy LARGE2 TECHNOLOGY IS THE ENERGY REFERENCE POINT
FOR LIQUID CHILLERS
MAXIMUM EFFICIENCY IS ASSURED BETWEEN THE 25% AND
THE 75% OF THE SYSTEM LOAD
For maximum loads taking place only for a few hours of functioning
per year. The high efficiency at partial loads of ELFOEnergy
LARGE2 makes it much more competitive and efficient than other
solutions.
* EUROVENT (ESEER) supply times reference and ARI (IPLV) reference for
THE MODULAR SCROLL
IS THE EXCELLENT SOLUTION FOR PARTIAL LOAD
seasonal efficiency calculations.
ELFOEnergy LARGE2 uses Scroll-type high-efficiency compressors,
with optimized spirals.
Main advantages are:
Compressors manufactured in large numbers at industrial level,
with strict quality checks and highest reliability thanks to the
elevated production volumes.
With two different-sized compressors, in order to achive more
adjustment steps. So it is possible to supply for usage only the
energy that is actually require.
Efficiency increases by over 50% when operating at partial
loads, thanks to the larger heat exchange surfaces available.
The electronic expansion valve contributes to the excellent
performance (EEV) it adapts rapidly and precisely to the actual load
required for usage, and the high performance heat exchangers.
Example refers to a WSAT-XEE 352, EXCELLENCE. Version.
External temperature equal to 35°C / 30°C / 25°C, respectively.
VERY HIGH HEAT EXCHANGE EFFICIENCY
Thanks to the external ELFOEnergy LARGE2 coils, equipped with wide frontal surfaces and reduced depth, the following is
obtained:
An improvement in the working temperature of the chiller circuit and, therefore, its efficiency, since the approach
between the air temperature and the temperature of the chiller fluid inside the exchanger is reduced;
A reduction in consumption by the fans, thanks to the reduced depth of the exchanger which decreases air flow renewal
drops. Furthermore, the automatic fan speed control, supplied in series, minimises the air renewal air requirement to
function correctly and therefore further reduces consumption;
A decrease in the sound level, since greater surfaces enable slower air speed in the exchangers.
ECOBREEZE ELECTRONICALLY-CONTROLLED FAN TECHNOLOGY
The external axial fans are equipped with an innovative Winglet blade profile with an integrated deflector, which is able to
increase aerodynamic efficiency. This results in a 10% reduction in consumption. The average acoustic emission is 6 dB
less then traditional fans.
Using ECOBREEZE the external rotary electric motor is operated by a continuous magnetic
switching of the stator, induced by integrated electronic control. The advantages are:
70% increase in efficiency thanks to the brushless technology and the special electricity
supply;
Increase in the working life, thanks to the elimination of the brush wear;
Reduction in the electrical consumption by the system, thanks to a drastic reduction of the
inrush current for the fans obtained using the integrated ‗Soft start‘ function.
Note: ECOBREEZE is supplied as standard in the EXCELLENCE version
COMPLETELY AUTOMATIC FUNCTIONING
The microprocessor controller manages functioning automatically in line with maximum
efficiency criteria, enables up to 6 units to be coordinated in a local network (Master-Slave
function) and includes numerous safety functions and the management of any alarms.
The interface terminal is equipped with a backlit graphic display and a multifunction access
keyboard. The multi-level menu is protected by passwords which are differentiated by different
user types. The daily / weekly clock programmer function is standard.
Thanks to its attractive design, the interface terminal can also be positioned inside the rooms
being serviced or in a special system control room.
BT10E005GB-02
4
®
ELFOENERGY LARGE2
ELFOEnergy LARGE2 TECHNOLOGY ENABLES
THE SYSTEM TO BE INDUSTRIALISED
ELFOEnergy LARGE2 can be supplied complete with system components which are often provided as external to units.
Thus reducing:
Design time: all the accessories are created to guarantee the best overall performance;
Installation costs: the accessories which are already connected manually, electrically wired and individually checked are
ready to start working immediately;
Dimension: integration of system members into the unit reduces technical spaces and increases the space available for
other uses. The slim line structure enables it to be positioned even on terraces or in external service corridors.
THE ON-BOARD PUMPS ARE VERSATILE, READY-FOR-USE AND RELIABLE
The various solutions available are:
Standard pump, with a wide range of available heads.
Standard pump with emergency pump. The on-board microprocessor balances its
working hours and in case of any breakdown signals the fault and automatically activates
the reserve pump.
HYDROPACK, the modular solution with two parallel pumps. Automatically reduces
water flow in critical conditions, avoiding blocks due to overloading and consequential
interventions by specialised technical personnel. It is very useful during start-up, during
re-start after a pause in working (e.g. a weekend) or after a long period of inactivity. In
case of any pump breakdowns, the unit continues to function with 60% of the nominal
flow.
EVEN THE STORAGE TANK AND THE PRIMARY CIRCUIT CAN BE INTEGRATED ON-BOARD
A connection to the secondary use circuit is all that's needed. In this way, the system results even more simple and
reliable. The units are complete with rapid connections on the hydraulic side, which further reduces set-up times by
eliminating pipe threading operations.
Furthermore, other system components are also available as accessories, such as hydraulic attachments reported on the
external walls of the unit (as standard with pumps and/or storage tank) and the required water filter.
ELFOEnergy LARGE2 MAY INCLUDE
MOST OF SYSTEM COMPONENTS
STANDARD RAPID CONNECTIONS
Gasket
Housing
Groove
Bolt/Nut
FREE HOT WATER
Condensation heat recovery:
Partial: recovers around 20% of the available heat (desuperheater);
Total: recovers 100% of available heat.
Free hot water production for :
Supplying hot-water coils for post-heating;
Producing domestic hot water (with the intermediate exchanger);
Other processes or operations.
IT EXPLOITS EXTERNAL AIR FOR COOLING WITHOUT ACTIVATING THE COMPRESSORS
In the FREE-COOLING configuration, as soon as the external conditions enable it, the unit is able to cool the liquid reducing
compressor functioning up to their complete withdrawal. This configuration is particularly useful in applications with a
high number of room loads, since it notably reduces unit energy consumption and compressor wear.
5
BT10E005GB-02
ELFOENERGY LARGE2
®
INDEX OF THE TECHNICAL SECTION
► EXCELLENCE Version - Soundproof compressor configuration (SC)
General technical specification - Electrical data
Pag. 8
Operating limit (COOLING) - Sound level
Pag. 9
COOLING performance
Pag. 10-11
Internal exchanger pressure drop - Admissible water flow rate
Pag. 11
► EXCELLENCE Version - Extremely low noise configuration (EN)
General technical specification - Electrical data
Pag. 12
Operating limit (COOLING) - Sound level
Pag. 13
COOLING performance
Pag. 14-15
Internal exchanger pressure drop - Admissible water flow rate
Pag. 15
► PREMIUM Version - Soundproof compressor configuration (SC)
General technical specification - Electrical data
Pag. 16
Operating limit (COOLING) - Sound level
Pag. 17
COOLING performance
Pag. 18-19
Internal exchanger pressure drop - Admissible water flow rate
Pag. 19
► PREMIUM Version - Extremely low noise configuration (EN)
General technical specification - Electrical data
Pag. 20
Operating limit (COOLING) - Sound level
Pag. 21
COOLING performance
Pag. 21-23
Internal exchanger pressure drop - Admissible water flow rate
Pag. 23
► CONFIGURATIONS
Pag. 24-27
► HYDRONIC GROUP ACCESSORIES
Pag. 28-31
► HYDROPACK
Pag. 32-33
► ACCESSORIES
Pag. 34-38
► FOULING CORRECTION FACTOR - CALIBRATION - EXCHANGER
OPERATING LIMITS
Pag. 39
► OPTION COMPATIBILITY
Pag. 40-41
► DIMENSIONAL
Pag. 42-47
CONFIGURATION CODE
WSAT-XEE
( 1)
(2)
(3)
(4)
EXC
-
-
-
352
( 5)
( 6)
SC
PED
EXC
-
-
-
SC
PED
PRM
D
B
FCD
EN
CLV
R
(1) VERSION
EXCELLENCE (EXC)
standard
PREMIUM (PRM)
(3) LIQUID LOW TEMPERATURE
Liquid low temperature : not required (-)
standard
Liquid low temperature (B)
(5) ACOUSTIC CONFIGURATION
(2) ENERGY RECOVERY
Energy recovery: not required (-)
standard
Partial energy recovery (D)
Total energy recovery (R)
(4) FREE-COOLING
Direct FREE-COOLING: not required (-)
standard
Direct FREE-COOLING (FCD)
(5) HEAT EXCHANGERS APPROVALS
Heat exchangers approvals CE = PED
(European Testing) (PED)
standard
Heat exchangers approvals C = CLIVET
(Internal Testing) (CLV)
standard
BT10E005GB-02
6
Acoustic configuration with compressor
soundproofing (SC) standard
Extremely low noise acoustic configuration (EN)
®
ELFOENERGY LARGE2
TECHNICAL UNIT FEATURES - EXCELLENCE VERSION
COMPRESSOR
Hermetic orbiting scroll compressor complete with motor over-temperature and
over-current devices and protection against excessive gas discharge
temperature. Fitted on rubber antivibration mounts and complete with oil
charge.
A oil heater is automatically switched on at the compressor shut-down to
prevent oil dilution by the refrigerant.
The compressors are connected in tandem on a single refrigerator circuit.
They have bi-phase equalization of the oil and are equipped with cut-off
bibcock.
TECHNICAL UNIT SPECIFICATIONS - PREMIUM VERSION
Technical specifications like EXCELLENCE version, except fan
FAN
Helical fans with sickle-shaped blades with "Winglets" at the end, coupled
directly to a three phase electric external rotor motor with thermal protection
incorporated in version IP 54. Housed in aerodynamically shaped nozzles to
increase efficiency and minimize noise levels. They are fitted with protective
safety guard grilles. The fans have the variable speed control.
CONSTRUCTIVE CONFIGURATIONS
-D
Partial Energy recovery
-R
Total Energy recovery
STRUCTURE
Supporting structure realised in galvanised steel sheet able to supply excellent
mechanical features and long-lasting resistance to corrosion.
-B
Low temperature liquid
PANELLING
External panels in pre-painted aluminium especially indicated in outdoor
installation due to its superior resistance to corrosion avoiding periodic
painting. Side panels are easily removable and allow complete access to unit
components. Internal sound proof lining reduces sound pressure levels.
- SC
- EN
Acoustic configuration with compressor soundproofing
Extremely low noise acoustic configuration
- FCD
Direct FREE-COOLING
INTERNAL EXCHANGER
Direct expansion heat exchanger, braze-welded AISI 316 stainless steel plates
with large exchange surface and complete with external heat and anticondensate insulation.
The exchanger comes complete with:
- differential pressure switch, water side
- antifreeze heater to protect the water side exchanger, preventing the
formation of frost if the water temperature falls below a set value.
ACCESSORIES - HYDRONIC GROUP
- Standard pump (note: different type of pumps are available according to the
head)
- Standard pump with a reserve pump (note: are type of pumps are available
according to the head)
- HYDROPACK (note: type of pumps are available according to the head)
- Storage tank
- Storage tank with primary circuit on board (note: only for unit with standard
pump / standard pump with reserve pump )
- hydraulic couplings on external panel (note: only for unit with standard pump /
standard pump with reserve pump / Hydropack and/ or Storage tank)
- stainless steel mesh mechanical filter (separately provided accessory)
(note: The filter must be installed in the exchanger inlet. Clivet declines all
responsibility and the warranty on the equipment automatically expires if it is
not provided an suitable mechanical filter within the unit).
EXTERNAL EXCHANGER
Finned exchanger, made from copper pipes arranged in staggered rows and
mechanically expanded for better adherence to the collar of the fins. The fins
are made from aluminium with a special corrugated surface, set a suitable
distance apart to ensure maximum heat exchange efficiency. The coils are
complete with integral subcooling circuit which assures the correct refrigerant
feeding of the expansion valve.
ACCESSORIES
- Finned coil protection grilles
- Anti-hail protection grilles
- Copper/aluminium condenser coil with acrylic coating
- Copper/aluminium condenser coil with Fin Guard (Silver) treatment
- Copper/copper condenser coil
- Spring antivibration mounts (separately provided accessory)
- Electrical panel ventilation
- Electrical heating (for electrical panel heating)
- Phase monitor
- Power factor correction capacitors (cosfi > 0.9)
- Breakaway current reducing device (soft start)
- High and low pressure gauges
- Shut-off valve on compressor suction and discharge
- Device for fan consumption reduction of the external section with variable
speed (phase-cutting) (only for the EXCELLENCE version)
- Free contacts for compressor state
- Free contacts for compressor state and for operation in local/remote mode
- Set point compensation with 0-10 V signal
- Set point compensation with 4-20 mA signal
- Set point compensation with outside temperature probe
- Set point compensation according to the outside enthalpy
- Kit for remote microprocessor remote control interface
(separately provided accessory)
- BACnet Converter
- LonWorks serial converter kit
FAN
ECOBREEZE device (STD)
Helical fans with sickle-shaped blades with "Winglets" at the end, coupled
directly to electronic control (IP 54), driven by the magnetic commutation of the
stator. The brushless technology and the special supply increase both the life
expectancy and the efficiency. As a result the electric consumption is reduced
up to 50%. Fans are housed in aerodynamically shaped structures to increase
efficiency and reduce noise level. The assembly is protected by accident
prevention guards. The fans have the variable speed control.
REFRIGERANT CIRCUIT
The circuit is complete with:
- replaceable anti-acid solid cartridge dehydrator filter
- sight glass with moisture indicator
- electronic expansion valve
- high pressure switch
- low pressure switch
- high pressure safety valve
- low pressure safety valve
- liquid line shut-off valve
- compressor discharge shut-off valve
ELECTRICAL PANEL
The Power Section includes:
- main door lock isolator switch
- isolating transformer for auxiliary circuit power supply
- compressor circuit breaker
- fan overload circuit breakers
- compressor control contactor
TEST
All the units are factory-tested in specific steps, before shipping them. After the
approval, the moisture contents present in all circuits are analyzed, in order to
ensure the respect of the limits set by the manufacturers of the different
components.
The control section includes:
- interface terminal with graphic display
- display of the set values, the error codes and the parameter index
- ON/OFF and alarm reset buttons
- proportional + integral water temperature control
- antifreeze protection on the water side
- compressor overload protection and timer
- pre-alarm function for water anti-ice and high refrigerant gas pressure
- self-diagnosis system with immediate display of the error code
- automatic compressor start rotation control
- compressor operating hour display
- remote ON/OFF control
- relay for remote cumulative fault signal
- input for demand limit (absorbed power limit according to an external signal
0÷10V or 4÷20mA)
- Master-Slave function
- serial port RS485 with Modbus protocol
7
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
97,4
27,2
31,2
119
31,2
3,12
4,42
110
31,4
35,3
139
35,3
3,12
4,48
121
35,1
39
151
39
3,1
4,4
131
36
41,7
161
41,7
3,14
4,39
143
40,1
45,8
176
45,8
3,12
4,44
155
43,8
49,5
190
49,7
3,13
4,44
174
50,5
56,1
215
56,1
3,1
4,36
197
55,7
63,2
242
63,2
3,12
4,5
218
62,8
70,3
269
70,2
3,1
4,29
Nr
HP
Nr
l
Nr
Scroll
2
35
3
8
1
Scroll
2
40
3
10
1
Scroll
2
43
3
12
1
Scroll
2
45
3
10
1
Scroll
2
50
3
11
1
Scroll
2
55
3
13
1
Scroll
2
60
2
13
1
Scroll
2
70
3
13
1
Scroll
2
80
2
13
1
l/s
kPa
l
PHE
4,7
30
7
PHE
5,3
30
8
PHE
5,8
30
9
PHE
6,3
35
9
PHE
6,8
34
10
PHE
7,4
40
10
PHE
8,3
40
12
PHE
9,4
41
14
PHE
10,4
41
17
Nr
l/s
AX
2
12875
AX
2
12792
AX
2
12694
AX
3
19194
AX
3
19194
AX
3
19028
AX
3
18889
AX
4
25278
AX
4
25139
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
COOLING
Cooling capacity
Compressor power input
Total power input
Heating capacity total recovery
Heating capacity partial recovery
EER
ESEER
COMPRESSOR
1
2
3
3
Type of compressors
N°. of Compressors
Nominal capacity
Standard capacity steps
Oil charge
Refrigerant circuits
INTERNAL EXCHANGER
Type of internal exchanger
Water flow rate (Internal Exchanger)
Internal exchanger pressure drop
Water content
EXTERNAL SECTION FANS
4
1
1
Type of fans
Number of fans
Standard air flow
CONNECTIONS
5
kW
kW
kW
kW
kW
Water fittings
POWER SUPPLY
Standard power supply
DIMENSIONS
Length
Depth
Height
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
mm
mm
mm
3075
1097
1805
3075
1097
1805
3075
1097
1805
4025
1097
1805
4025
1097
1805
4025
1097
1805
4025
1097
1805
5025
1097
1805
5025
1097
1805
kg
kg
889
896
925
933
1015
1024
1198
1207
1224
1234
1246
1256
1290
1302
1483
1497
1527
1544
(1) data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air intake 35°C
(2) According to EUROVENT the Total Power Input does not consider the pump share,
required to overcome the pressure drop for the solution circulation inside the exchangers.
(3) Option. recovery exchanger water = 40 / 45°C
(4) PHE = plates
(5) AX = axial-flow fan
ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
F.L.A. - Total
A
79,3
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
90,6
100
102,9
110,7
122
131,4
150
164,5
F.L.I. - Total
M.I.C. MAXIMUM INRUSH CURRENT
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
M.I.C. - Value
kW
47,3
52,4
58,8
61
67,4
72,5
79
91,8
102,4
A
264,6
311,6
317,2
378,4
387,8
399,1
405,7
470,2
484,7
Voltage unbalance: max 2 %
Power supply: 400/3/50 Hz +/-6%
Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.
BT10E005GB-02
8
®
ELFOENERGY LARGE2
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
OPERATING LIMITS (COOLING)
SIZE
EXTERNAL EXCHANGER
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
INTERNAL EXCHANGER
Max water inlet temperature
Min. water outlet temperature
Min. water outlet temperature
352
402
432
452
502
552
602
702
802
1
2
3
4
5
6
°C
°C
°C
°C
°C
°C
47
50
-10
-7
-2
11
46
50
-10
-7
-2
11
46
50
-10
-7
-2
11
47
50
-10
-7
-2
11
47
50
-10
-7
-2
11
46
50
-10
-7
-2
11
46
50
-10
-7
-2
11
47
50
-10
-7
-2
11
46
50
-10
-7
-2
11
7
8
°C
°C
°C
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
Data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air 35°C
- still air
The functioning mode can also be extended up to external air temperatures of less than 39°C, but only with a FREE-COOLING configuration which is complete with an adequately
sized "Electric panel anti-frost protection" option.
Warning: the still air condition is meant as absence of air flow to the unit. Any wind
condition can let air pass through the condenser coil thus worsening the operating limits of
the unit. In case of predominant winds, windbreak barriers are necessary.
In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit,
which has no electricity supply, correct maintenance (not functioning) is possible up to an
external air temperature of -20°C.
Note. For correct maintenance (not functioning) with external air temperatures at less than
-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the
"Electric panel anti-freeze protection" option and be continuously supplied with electricity.
The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this
condition, the minimum external air-temperature which is permitted depends on the chosen
model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.
(1) Max inlet temperature - unit at full load
(2) Max inlet air temperature - Unit at partial load
(3) Min inlet air temperature - Unit at full load and still fresh air
(4) Min inlet air temperature - Unit at partial load and still fresh air
(5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s.
(6) Min inlet air temperature - unit at partial load and air speed of 1 m/s.
(7) Standard unit without low temperature liquid device and external exchanger air intake
35°C
(8) Unit with low temperature liquid device and external exchanger air intake 35°C
Fluid with ethylene glycol of 40%.
20
Graph informed to size 352.
The detail of each size is shown in tabular date.
To (°C)
15
Ta = external exchanger air intake temperature
(dry bulb)
1
10
1
1
To (°C) = internal exchanger water outlet
temperature
3
4
1. Standard unit:
(not with ‗Low temperature liquid‘)
2. ‗Low temperature liquid‘ unit (with ethylene
glycol of 40%)
3. Partial-load unit
(automatic capacity control)
4. Full-load unit
(automatic air flow modulation)
5
0
2
2
2
4
3
-5
-10
-12
-8
-4
0
4
8
12
16
20
24
28
32
36
40
44
48
52
Ta (°C)
SOUND LEVELS
Sound Power Level (dB)
SIZE
Sound pressure level
Sound
pressure
level
Sound
power
level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
352
90
88
87
84
78
74
66
59
67
85
402
90
87
86
84
79
75
67
59
67
85
432
90
88
87
85
80
77
68
59
68
86
452
91
89
87
85
81
75
68
60
68
86
502
91
89
88
86
81
76
68
60
68
87
552
92
89
89
86
82
77
69
61
69
88
602
91
89
88
86
83
77
69
60
69
88
702
93
91
90
88
84
78
70
62
70
89
802
93
91
90
88
84
78
70
62
70
89
The sound levels refer to the unit at full load, in the rated test
conditions.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Measures, according to ISO 3744 regulations, are carried out on a
reflecting surface, with respect to the EUROVENT 8/1 certification.
Data referred to the following conditions:
- internal exchanger water = 12/7°C
- outdoor air temperature 35°C
9
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
To (ºC)
25
30
kWf
kWe
5
102,0
6
105,2
7
8
35
40
44
46
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
22,2
96,9
24,4
91,6
26,8
86,0
29,3
81,3
31,5
78,9
32,7
22,4
100,0
24,6
94,5
27,0
88,7
29,5
83,9
31,7
81,5
32,9
108,5
22,6
103,1
24,8
97,4
27,2
91,5
29,8
86,6
31,9
84,1
33,1
111,7
22,8
106,2
25,0
100,4
27,4
94,3
30,0
89,3
32,2
86,8
33,3
9
115,0
23,0
109,3
25,3
103,3
27,7
97,2
30,2
92,1
32,4
89,5
33,5
10
118,3
23,2
112,4
25,5
106,3
27,9
100,1
30,5
94,9
32,6
92,3
33,7
5
114,7
25,7
109,1
28,2
103,1
30,9
96,8
33,8
91,5
36,3
88,7
37,5
6
118,5
25,9
112,7
28,4
106,5
31,1
100,0
34,0
94,5
36,5
91,6
37,7
7
122,2
26,2
116,2
28,7
109,8
31,4
103,1
34,3
97,4
36,7
94,5
37,9
8
125,9
26,4
119,6
29,0
113,0
31,6
106,1
34,5
100,3
36,9
97,3
38,1
9
129,4
26,7
123,0
29,2
116,2
31,9
109,1
34,7
103,1
37,1
100,1
38,3
10
132,9
26,9
126,3
29,4
119,3
32,1
112,0
34,9
105,9
37,3
102,8
38,5
5
127,0
28,7
120,6
31,5
113,9
34,6
106,9
37,9
101,2
40,8
98,2
42,3
6
131,1
29,0
124,5
31,8
117,6
34,8
110,4
38,2
104,5
41,1
101,5
42,6
7
135,2
29,3
128,4
32,1
121,3
35,1
113,9
38,5
107,8
41,3
104,7
42,8
8
139,3
29,6
132,2
32,4
124,9
35,4
117,4
38,7
111,2
41,6
108,0
43,1
352
402
432
9
143,3
29,9
136,1
32,7
128,6
35,7
120,9
39,0
114,6
41,8
111,4
43,3
10
147,4
30,2
139,9
33,0
132,3
36,0
124,4
39,3
118,0
42,1
114,8
43,5
5
136,5
29,2
130,0
32,2
123,2
35,5
115,9
39,0
109,8
42,1
106,7
43,7
6
141,0
29,5
134,3
32,5
127,2
35,7
119,7
39,3
113,5
42,3
110,2
43,9
7
145,5
29,8
138,5
32,7
131,2
36,0
123,5
39,5
117,1
42,5
113,8
44,1
8
149,9
30,0
142,8
33,0
135,3
36,2
127,3
39,8
120,7
42,8
117,3
44,3
452
502
9
154,4
30,3
147,0
33,3
139,3
36,5
131,1
40,0
124,3
43,0
120,8
44,5
10
158,8
30,5
151,2
33,5
143,3
36,8
134,9
40,3
127,9
43,2
124,3
44,7
5
148,9
32,6
141,7
35,8
134,2
39,4
126,4
43,5
119,9
47,0
116,6
48,8
6
153,8
32,9
146,3
36,1
138,6
39,7
130,5
43,8
123,8
47,3
120,4
49,1
7
158,6
33,2
150,9
36,4
142,9
40,1
134,6
44,1
127,7
47,5
124,2
49,4
8
163,5
33,5
155,5
36,8
147,3
40,4
138,8
44,4
131,7
47,8
128,1
49,7
9
168,3
33,8
160,1
37,1
151,7
40,7
142,9
44,7
135,7
48,1
132,0
49,9
10
173,1
34,2
164,7
37,4
156,0
41,0
147,1
45,0
139,7
48,4
-
-
5
160,7
35,7
153,1
39,2
145,2
43,2
136,9
47,5
129,9
51,3
126,3
53,3
6
165,9
36,0
158,1
39,5
149,9
43,5
141,3
47,8
134,1
51,6
130,4
53,6
7
171,2
36,3
163,1
39,9
154,6
43,8
145,7
48,1
138,2
51,9
134,4
53,8
8
176,5
36,7
168,1
40,2
159,3
44,2
150,1
48,4
142,4
52,1
138,5
54,1
9
181,7
37,0
173,1
40,6
164,0
44,5
154,5
48,7
146,6
52,4
-
-
10
187,0
37,4
178,1
40,9
168,7
44,8
158,9
49,0
150,8
52,7
-
-
5
182,0
41,0
173,3
45,2
164,1
49,8
154,5
54,9
146,5
59,3
142,4
61,6
6
187,5
41,4
178,5
45,5
169,0
50,1
159,2
55,2
150,9
59,6
146,7
61,9
7
193,1
41,8
183,8
45,9
174,1
50,5
163,9
55,5
155,5
59,9
151,2
62,2
8
198,9
42,2
189,3
46,3
179,3
50,9
168,9
55,9
160,2
60,2
155,8
62,5
9
204,8
42,6
195,0
46,7
184,7
51,3
173,9
56,3
165,0
60,5
160,5
62,8
10
210,9
43,0
200,8
47,2
190,1
51,7
179,1
56,6
170,0
60,9
165,3
63,1
552
602
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
BT10E005GB-02
10
®
ELFOENERGY LARGE2
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
To (ºC)
702
802
25
30
35
40
44
46
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
203,8
45,8
194,6
50,0
184,9
54,9
174,8
60,5
166,4
65,5
162,1
68,2
6
210,2
46,1
200,6
50,4
190,7
55,3
180,2
60,9
171,6
65,9
167,2
68,6
7
216,6
46,5
206,8
50,7
196,5
55,7
185,8
61,3
176,9
66,3
172,3
68,9
8
223,3
46,8
213,1
51,1
202,5
56,1
191,4
61,7
182,2
66,7
177,6
69,3
9
230,0
47,2
219,5
51,5
208,6
56,5
197,2
62,1
187,8
67,0
182,9
69,7
10
236,9
47,6
226,1
51,9
214,8
56,9
203,1
62,5
193,4
67,4
188,4
70,0
5
225,9
52,1
215,9
56,6
205,5
61,9
194,7
68,2
185,7
73,8
181,1
76,9
6
232,8
52,5
222,5
57,0
211,8
62,4
200,6
68,6
191,4
74,3
186,7
77,3
7
239,9
52,8
229,3
57,4
218,2
62,8
206,7
69,1
197,2
74,8
192,4
77,8
8
247,2
53,2
236,2
57,8
224,8
63,2
212,9
69,6
203,1
75,2
198,1
78,3
9
254,6
53,6
243,3
58,2
231,5
63,7
219,3
70,0
209,2
75,7
204,0
78,8
10
262,2
54,0
250,5
58,6
238,4
64,1
225,8
70,5
215,3
76,2
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
INTERNAL EXCHANGER PRESSURE DROP
100
THE AIR SIDE PRESSURE DROPS ARE RELATIVE
TO THE MEDIUM AIR TEMPERATURE OF 7°C
35
2
43 402
2
50 452
25
52
60
2
70
2
80
2
90
80
70
Q = AIR FLOW [l/s]
DP = PRESSURE DROP [kPa]
60
P [kPa]
50
THE WATER FLOW RATE CAN BE CALCULATED
WITH THE FOLLOWING FORMULA:
40
30
Q [l/s] = kWf / (4,186 x DT)
kWf = COOLING CAPACITY [kW]
DT = TEMPERATURE DIFFERENCE BETWEEN
WATER INLET / OUTLET
20
15
2
3
4
5
6
7
Q [l/s]
8
9
20
To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the
water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP
ACCESSORIES).
If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm,
because they can cause a bad unit operation and also its serious damaging.
ADMISSIBLE WATER FLOW RATE
Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.
352
402
432
452
502
552
602
702
802
Qmin
[l/s]
3,2
3,6
3,9
3,9
4,4
4,4
4,9
5,5
6,1
Qmax
[l/s]
9,0
10,2
11,1
11,1
12,2
12,2
13,5
15,1
16,6
11
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
91,7
28,4
31,2
119
30
2,94
4,27
104
32,8
35,6
139
34
2,92
4,4
116
37
39,8
151
38
2,91
4,32
125
37,5
41,5
161
41
3,01
4,31
135
41,9
45,9
176
44
2,94
4,31
146
46
50
190
48
2,92
4,29
167
53,3
57,3
215
55
2,91
4,26
185
58,4
63,6
242
61
2,91
4,35
209
66,1
71,3
269
69
2,93
4,17
Nr
HP
Nr
l
Nr
Scroll
2
35
3
8
1
Scroll
2
40
3
10
1
Scroll
2
43
3
12
1
Scroll
2
45
3
10
1
Scroll
2
50
3
11
1
Scroll
2
55
3
13
1
Scroll
2
60
2
13
1
Scroll
2
70
3
13
1
Scroll
2
80
2
13
1
l/s
kPa
l
PHE
4,4
27
7
PHE
5
27
8
PHE
5,5
28
9
PHE
6
32
9
PHE
6,5
31
10
PHE
7
35
10
PHE
8
37
12
PHE
8,8
37
14
PHE
10
38
17
Nr
l/s
AX
2
9819
AX
2
9722
AX
2
9639
AX
3
14583
AX
3
14583
AX
3
14431
AX
3
14292
AX
4
19167
AX
4
18986
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
COOLING
Cooling capacity
Compressor power input
Total power input
Heating capacity total recovery
Heating capacity partial recovery
EER
ESEER
COMPRESSOR
1
2
3
3
Type of compressors
N°. of Compressors
Nominal capacity
Standard capacity steps
Oil charge
Refrigerant circuits
INTERNAL EXCHANGER
Type of internal exchanger
Water flow rate (Internal Exchanger)
Internal exchanger pressure drop
Water content
EXTERNAL SECTION FANS
4
1
1
Type of fans
Number of fans
Standard air flow
CONNECTION
5
kW
kW
kW
kW
kW
Water fittings
POWER SUPPLY
Standard power supply
DIMENSIONS
Length
Depth
Height
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
mm
mm
mm
3075
1097
1805
3075
1097
1805
3075
1097
1805
4025
1097
1805
4025
1097
1805
4025
1097
1805
4025
1097
1805
5025
1097
1805
5025
1097
1805
kg
kg
889
896
925
933
1015
1024
1198
1207
1224
1234
1246
1256
1290
1302
1483
1497
1527
1544
(1) data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air intake 35°C
(2) According to EUROVENT the Total Power Input does not consider the pump share,
required to overcome the pressure drop for the solution circulation inside the exchangers.
(3) Option. recovery exchanger water = 40 / 45°C
(4) PHE = plates
(5) AX = axial-flow fan
ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
90,6
100
102,9
110,7
122
131,4
150
164,5
52,4
58,8
61
67,4
72,5
79
91,8
102,4
311,6
317,2
378,4
387,8
399,1
405,7
470,2
484,7
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Total
A
79,3
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Total
kW
47,3
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value
A
264,6
Voltage unbalance: max 2 %
Power supply: 400/3/50 Hz +/-6%
Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.
BT10E005GB-02
12
®
ELFOENERGY LARGE2
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
OPERATING LIMITS (COOLING)
SIZE
352
402
432
452
502
552
602
702
802
EXTERNAL EXCHANGE
Max air intake temperature
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
INTERNAL EXCHANGE
Max water inlet temperature
Min. water outlet temperature
Min. water outlet temperature
1
2
3
4
5
6
7
°C
°C
°C
°C
°C
°C
°C
46
47
50
-10
-7
-2
11
45
46
50
-10
-7
-2
11
44
46
50
-10
-7
-2
11
46
47
50
-10
-7
-2
11
46
47
50
-10
-7
-2
11
45
46
50
-10
-7
-2
11
44
46
50
-10
-7
-2
11
46
47
50
-10
-7
-2
11
45
46
50
-10
-7
-2
11
8
9
°C
°C
°C
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
The functioning mode can also be extended up to external air temperatures of less than 39°C, but only with a FREE-COOLING configuration which is complete with an adequately
sized "Electric panel anti-frost protection" option.
Data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air 35°C
- still air
In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit,
which has no electricity supply, correct maintenance (not functioning) is possible up to an
external air temperature of -20°C.
Warning: the still air condition is meant as absence of air flow to the unit. Any wind
condition can let air pass through the condenser coil thus worsening the operating limits of
the unit. In case of predominant winds, windbreak barriers are necessary.
(1) Max inlet temperature - unit at full load
(2) Max inlet air temperature - Unit at partial load
(3) Min inlet air temperature - Unit at full load and still fresh air
(4) Min inlet air temperature - Unit at partial load and still fresh air
(5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s.
(6) Min inlet air temperature - unit at partial load and air speed of 1 m/s.
(7) Standard unit without low temperature liquid device and external exchanger air intake
35°C
(8) Unit with low temperature liquid device and external exchanger air intake 35°C
Fluid with ethylene glycol of 40%
Note. For correct maintenance (not functioning) with external air temperatures at less than
-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the
"Electric panel anti-freeze protection" option and be continuously supplied with electricity.
The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this
condition, the minimum external air-temperature which is permitted depends on the chosen
model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.
Graph informed to size 352.
The detail of each size is shown in tabular date.
15
Ta = external exchanger air intake temperature
(dry bulb)
To (°C)
20
1
10
1
1
4
To (°C) = internal exchanger water outlet
temperature
3
1. Standard unit:
(not with ‗Low temperature liquid‘)
2. ‗Low temperature liquid‘ unit (with ethylene
glycol of 40%)
3. Partial-load unit
(automatic capacity control)
4. Full-load unit
(automatic air flow modulation)
5
0
2
2
2
4
3
-5
-10
-12
-8
-4
0
4
8
12
16
20
24
28
32
36
40
44
48
52
Ta (°C)
SOUND LEVEL
Sound Power Level (dB)
SIZE
Sound pressure level
Sound
pressure
level
Sound
power
level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
352
82
84
84
80
71
68
60
55
63
81
402
82
83
84
80
74
70
62
57
63
81
432
82
83
86
82
75
71
62
57
65
83
452
85
85
86
83
76
70
63
58
65
83
502
84
85
87
83
76
71
63
57
66
84
552
84
85
87
83
78
72
64
59
66
84
602
84
85
87
84
78
72
64
58
66
85
702
86
86
88
85
79
73
65
59
67
86
802
86
86
89
85
80
73
66
60
67
86
13
The sound levels refer to the unit at full load, in the rated test conditions.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Measures, according to ISO 3744 regulations, are carried out on a
reflecting surface, with respect to the EUROVENT 8/1 certification.
Data referred to the following conditions:
- internal exchanger water = 12/7°C
- outdoor air temperature 35°C
The sound levels indicated sideways are valid only for the operating
range of the ‗Extremely low noise EN‘ configuration; with fresh air
temperatures higher and in any case into the operating range of the
‗Compressor soundproofing SC‘ configuration, consider the sound levels
of the ‗Compressor soundproofing‘ configuration .
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
352
To (ºC)
25
30
35
40
42
44
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
96,6
23,3
91,6
25,5
86,3
27,9
80,9
30,5
78,6
31,6
76,3
32,7
6
99,6
23,5
94,4
25,8
89,0
28,2
83,4
30,8
81,1
31,8
78,8
32,9
7
102,6
23,7
97,2
26,0
91,7
28,4
86,0
31,0
83,7
32,1
81,3
33,2
8
105,6
24,0
100,1
26,2
94,5
28,7
88,6
31,3
86,3
32,3
83,8
33,4
9
108,6
24,2
103,0
26,5
97,2
28,9
91,3
31,5
88,8
32,6
86,4
33,7
10
111,7
24,4
105,9
26,7
100,0
29,2
93,9
31,8
91,4
32,9
88,9
34,0
5
109,5
26,9
103,9
29,5
98,0
32,3
91,8
35,2
89,2
36,4
86,6
37,6
6
113,1
27,2
107,3
29,8
101,1
32,5
94,8
35,4
92,1
36,6
89,5
37,8
7
116,6
27,5
110,5
30,1
104,2
32,8
97,6
35,7
94,9
36,8
92,1
38,0
8
119,8
27,8
113,7
30,3
107,2
33,1
100,3
36,0
97,4
37,2
94,5
38,4
9
122,9
28,2
116,9
30,6
110,2
33,3
102,9
36,3
99,8
37,5
96,6
38,9
10
125,9
28,6
119,9
30,9
113,1
33,6
105,3
36,6
102,0
38,0
98,5
39,4
5
122,1
30,3
115,6
33,2
109,0
36,3
102,0
39,8
99,2
41,2
96,3
42,7
6
125,8
30,7
119,4
33,5
112,4
36,7
104,9
40,3
101,8
41,8
98,5
43,4
7
129,5
31,1
123,0
33,8
115,9
37,0
108,3
40,5
105,0
42,1
101,7
43,7
8
133,2
31,5
126,5
34,2
119,4
37,3
112,0
40,6
108,9
42,1
105,8
43,5
9
137,0
31,8
129,8
34,7
122,9
37,6
116,1
40,5
113,5
41,7
110,9
42,9
10
140,7
32,1
133,0
35,2
126,3
37,9
120,7
40,2
118,7
41,0
116,9
41,8
5
130,7
30,6
124,3
33,6
117,5
37,0
110,5
40,5
107,5
42,0
104,6
43,6
6
135,0
30,9
128,3
33,9
121,3
37,3
114,0
40,8
111,0
42,3
107,9
43,9
7
139,2
31,2
132,3
34,2
125,1
37,6
117,5
41,1
114,4
42,6
111,2
44,2
8
143,4
31,5
136,3
34,5
128,8
37,9
121,1
41,4
117,8
42,9
114,6
44,4
402
432
452
9
147,6
31,8
140,2
34,8
132,6
38,2
124,6
41,7
121,3
43,1
118,0
44,6
10
151,7
32,1
144,2
35,2
136,3
38,5
128,1
41,9
124,8
43,4
121,4
44,9
5
140,9
34,1
133,9
37,5
126,6
41,3
119,0
45,4
115,9
47,1
112,7
49,0
6
145,5
34,5
138,2
37,9
130,6
41,6
122,8
45,7
119,6
47,4
116,4
49,2
7
150,0
34,8
142,5
38,2
134,7
42,0
126,6
46,0
123,3
47,8
120,0
49,6
8
154,5
35,2
146,7
38,6
138,7
42,3
130,4
46,4
127,0
48,1
123,6
49,9
9
159,0
35,5
151,0
38,9
142,8
42,7
134,2
46,8
130,7
48,5
127,2
50,3
10
163,5
35,9
155,3
39,3
146,8
43,0
138,0
47,1
134,4
48,9
130,7
50,7
5
152,0
37,4
144,6
41,2
136,8
45,2
128,7
49,7
125,3
51,6
121,9
53,5
6
156,9
37,8
149,2
41,5
141,1
45,6
132,7
50,1
129,2
51,9
125,7
53,9
7
161,8
38,2
153,8
41,9
145,4
46,0
136,7
50,4
133,1
52,3
129,5
54,2
8
166,7
38,6
158,4
42,3
149,8
46,3
140,8
50,7
137,1
52,6
133,3
54,5
9
171,5
39,0
163,0
42,7
154,1
46,7
144,9
51,0
141,1
52,8
137,2
54,7
10
176,3
39,4
167,5
43,1
158,4
47,1
149,0
51,3
145,1
53,1
141,1
54,9
5
175,2
43,3
166,4
47,7
157,2
52,4
147,6
57,7
143,7
59,9
139,7
62,2
6
180,3
43,7
171,3
48,1
161,8
52,9
152,0
58,0
147,9
60,2
143,8
62,5
7
185,6
44,2
176,3
48,5
166,6
53,3
156,5
58,4
152,3
60,6
148,1
62,8
8
191,1
44,6
181,5
49,0
171,5
53,7
161,1
58,8
156,9
60,9
152,6
63,2
9
196,7
45,1
186,8
49,4
176,5
54,1
165,9
59,2
161,5
61,3
157,1
63,5
10
202,5
45,6
192,3
49,9
181,7
54,6
170,7
59,6
166,3
61,7
161,8
63,8
502
552
602
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
BT10E005GB-02
14
®
ELFOENERGY LARGE2
VERSION: EXCELLENCE
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
To (ºC)
25
30
35
40
42
44
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
193,0
47,8
184,0
52,3
174,5
57,5
164,7
63,3
160,6
65,8
156,5
68,5
6
198,9
48,2
189,5
52,8
179,8
57,9
169,7
63,7
165,6
66,2
161,4
68,8
7
204,9
48,6
195,2
53,2
185,2
58,4
174,8
64,2
170,6
66,7
166,3
69,3
8
211,1
49,1
201,1
53,6
190,7
58,8
180,0
64,7
175,6
67,1
171,1
69,7
702
802
9
217,3
49,5
207,1
54,1
196,4
59,3
185,2
65,1
180,6
67,6
176,0
70,2
10
223,7
50,0
213,2
54,5
202,1
59,8
190,5
65,6
185,7
68,2
180,9
70,8
5
217,7
54,5
207,8
59,3
197,4
65,1
186,7
71,6
182,3
74,5
177,9
77,5
6
224,3
54,9
214,0
59,8
203,4
65,6
192,3
72,2
187,8
75,0
183,2
78,0
7
231,0
55,3
220,4
60,3
209,4
66,1
198,0
72,7
193,4
75,6
188,6
78,6
8
237,9
55,8
227,0
60,8
215,6
66,6
203,9
73,2
199,1
76,1
194,2
79,1
9
244,9
56,3
233,6
61,3
222,0
67,1
209,9
73,8
205,0
76,6
200,0
79,6
10
252,1
56,7
240,5
61,8
228,5
67,7
216,1
74,3
211,1
77,1
206,0
80,1
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
INTERNAL EXCHANGER PRESSURE DROP
100
THE AIR SIDE PRESSURE DROPS ARE RELATIVE
TO THE MEDIUM AIR TEMPERATURE OF 7°C
35
2
43 402
2
50 452
25
52
60
2
70
2
80
2
90
80
70
Q = AIR FLOW [l/s]
DP = PRESSURE DROP [kPa]
60
P [kPa]
50
40
THE WATER FLOW-RATE
CAN BE CALCULATED
WITH THE FOLLOWING FORMULA
30
Q [l/s] = kWf / (4,186 x DT)
kWf = COOLING CAPACITY [kW]
DT = TEMPERATURE DIFFERENCE BETWEEN
WATER INLET / OUTLET
20
15
2
3
4
5
6
7
Q [l/s]
8
9
20
To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the
water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP
ACCESSORIES).
If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm,
because they can cause a bad unit operation and also its serious damaging.
ADMISSIBLE WATER FLOW-RATE
Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.
352
402
432
452
502
552
602
702
802
Qmin
[l/s]
3,2
3,6
3,9
3,9
4,4
4,4
4,9
5,5
6,1
Qmax
[l/s]
9,0
10,2
11,1
11,1
12,2
12,2
13,5
15,1
16,6
15
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: PREMIUM
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
91,5
28,6
32,6
114
30
2,81
4,07
102
33,6
37,5
129
33,9
2,72
4,11
113
37,8
41,7
144
37,7
2,71
4,06
122
40
43,9
155
40,5
2,78
4,22
131
43,6
47,5
169
43,6
2,76
4,21
143
48,7
52,6
186
47,9
2,72
4,18
162
56,2
60,1
208
54,5
2,7
4,09
183
60,7
66,4
238
60,9
2,76
4,18
204
69,8
75,5
263
68,4
2,7
3,98
Nr
HP
Nr
l
Nr
Scroll
2
35
3
8
1
Scroll
2
40
3
10
1
Scroll
2
43
3
12
1
Scroll
2
45
3
10
1
Scroll
2
50
3
11
1
Scroll
2
55
3
13
1
Scroll
2
60
2
13
1
Scroll
2
70
3
13
1
Scroll
2
80
2
13
1
l/s
kPa
l
PHE
4,4
47
5
PHE
4,9
47
5
PHE
5,4
48
6
PHE
5,8
45
7
PHE
6,3
41
8
PHE
6,8
41
9
PHE
7,7
43
10
PHE
8,7
45
12
PHE
9,7
44
14
Nr
l/s
AX
2
12875
AX
2
12875
AX
2
12819
AX
2
12569
AX
2
12361
AX
2
12361
AX
2
12500
AX
3
19167
AX
3
19167
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
COOLING
Cooling capacity
Compressor power input
Total power input
Heating capacity total recovery
Heating capacity partial recovery
EER
ESEER
COMPRESSOR
1
2
3
3
Type of compressors
N°. of Compressors
Nominal capacity
Standard capacity steps
Oil charge
Refrigerant circuits
INTERNAL EXCHANGER
Type of internal exchanger
Water flow rate (Internal Exchanger)
Internal exchanger pressure drop
Water content
EXTERNAL SECTION FANS
4
1
1
Type of fans
Number of fans
Standard air flow
CONNECTION
5
kW
kW
kW
kW
kW
Water fittings
POWER SUPPLY
Standard power supply
DIMENSION
Length
Depth
Height
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
mm
mm
mm
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
3075
1097
1805
4025
1097
1805
4025
1097
1805
kg
kg
773
778
796
802
885
892
917
924
955
963
975
984
1077
1087
1283
1295
1310
1324
((1) data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air intake 35°C
(2) According to EUROVENT the Total Power Input does not consider the pump share,
required to overcome the pressure drop for the solution circulation inside the exchangers.
(3) Option. recovery exchanger water = 40 / 45°C
(4) PHE = plates
(5) AX = axial-flow fan
ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
F.L.A. - Total
A
79,3
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
90,6
100
98,8
106,6
117,9
127,3
145,9
160,4
F.L.I. - Total
M.I.C. MAXIMUM INRUSH CURRENT
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
M.I.C. - Value
kW
47,3
52,4
58,8
58,8
65,2
70,3
76,8
89,6
100,2
A
264,6
311,6
317,2
374,3
383,7
395
401,6
466,1
480,6
Voltage unbalance: max 2 %
Power supply: 400/3/50 Hz +/-6%
Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.
BT10E005GB-02
16
®
ELFOENERGY LARGE2
VERSION: PREMIUM
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
OPERATING LIMITS (COOLING)
SIZE
352
402
432
452
502
552
602
702
802
EXTERNAL EXCHANGER
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
INTERNAL EXCHANGER
Max water inlet temperature
Min. water outlet temperature
Min. water outlet temperature
1
2
3
4
5
6
°C
°C
°C
°C
°C
°C
45
50
-10
-7
-2
11
44
50
-10
-7
-2
11
43
50
-10
-7
-2
11
44
50
-10
-7
-2
11
44
50
-10
-7
-2
11
43
50
-10
-7
-2
11
42
50
-10
-7
-2
11
44
50
-10
-7
-2
11
43
50
-10
-7
-2
11
7
8
°C
°C
°C
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
The functioning mode can also be extended up to external air temperatures of less than
-39°C, but only with a FREE-COOLING configuration which is complete with an adequately
sized "Electric panel anti-frost protection" option.
Data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air 35°C
- still air
In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit,
which has no electricity supply, correct maintenance (not functioning) is possible up to an
external air temperature of -20°C.
Warning: the still air condition is meant as absence of air flow to the unit. Any wind
condition can let air pass through the condenser coil thus worsening the operating limits of
the unit. In case of predominant winds, windbreak barriers are necessary.
(1) Max inlet temperature - unit at full load
(2) Max inlet air temperature - Unit at partial load
(3) Min inlet air temperature - Unit at full load and still fresh air
(4) Min inlet air temperature - Unit at partial load and still fresh air
(5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s.
(6) Min inlet air temperature - unit at partial load and air speed of 1 m/s.
(7) Standard unit without low temperature liquid device and external exchanger air intake
35°C
(8) Unit with low temperature liquid device and external exchanger air intake 35°C
Fluid with ethylene glycol of 40%
Note. For correct maintenance (not functioning) with external air temperatures at less than
-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the
"Electric panel anti-freeze protection" option and be continuously supplied with electricity.
The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this
condition, the minimum external air-temperature which is permitted depends on the chosen
model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.
20
Graph informed to size 352.
The detail of each size is shown in tabular date.
To (°C)
15
Ta = external exchanger air intake temperature
(dry bulb)
1
10
1
1
4
To (°C) = internal exchanger water outlet
temperature
3
1. Standard unit:
(not with ‗Low temperature liquid‘)
2. ‗Low temperature liquid‘ unit (with ethylene
glycol of 40%)
3. Partial-load unit
(automatic capacity control)
4. Full-load unit
(automatic air flow modulation)
5
0
2
2
2
4
3
-5
-10
-12
-8
-4
0
4
8
12
16
20
24
28
32
36
40
44
48
52
Ta (°C)
SOUND LEVEL
Sound Power Level (dB)
SIZE
Sound pressure level
Sound
pressure
level
Sound
power
level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
352
90
88
86
84
78
74
66
58
67
85
402
89
87
86
83
79
75
67
59
67
85
432
89
87
86
84
79
75
67
58
67
85
452
89
87
86
84
80
74
67
58
67
85
502
89
86
86
84
80
75
67
57
68
85
552
89
87
86
85
81
76
68
59
68
86
602
89
87
86
85
81
76
68
58
68
86
702
91
89
88
87
83
77
69
60
69
88
802
91
89
88
86
83
77
69
60
69
88
17
The sound levels refer to the unit at full load, in the rated test conditions.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Measures, according to ISO 3744 regulations, are carried out on a
reflecting surface, with respect to the EUROVENT 8/1 certification.
Data referred to the following conditions:
- internal exchanger water = 12/7°C
- outdoor air temperature 35°C
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: PREMIUM
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
352
To (ºC)
25
30
35
38
40
42
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
96,2
23,4
91,2
25,7
86,0
28,2
82,7
29,7
80,5
30,8
78,2
31,9
6
99,3
23,6
94,1
25,9
88,7
28,4
85,3
30,0
83,0
31,1
80,7
32,2
7
102,3
23,9
97,0
26,2
91,5
28,7
88,0
30,2
85,6
31,3
83,2
32,4
8
105,4
24,1
99,9
26,4
94,2
28,9
90,7
30,5
88,3
31,6
85,8
32,7
9
108,4
24,3
102,8
26,7
97,0
29,2
93,4
30,7
91,0
31,8
88,5
32,9
10
111,4
24,6
105,7
26,9
99,8
29,4
96,1
31,0
93,7
32,0
91,2
33,1
5
107,8
27,6
102,2
30,2
96,1
33,1
92,4
34,9
89,8
36,1
87,1
37,4
6
110,8
27,8
105,0
30,5
98,8
33,3
94,9
35,1
92,3
36,3
89,6
37,6
7
113,9
28,1
107,9
30,8
101,6
33,6
97,6
35,3
94,9
36,6
92,2
37,8
8
117,1
28,4
111,0
31,1
104,5
33,9
100,4
35,6
97,7
36,8
94,9
38,0
9
120,6
28,7
114,2
31,3
107,5
34,1
103,4
35,9
100,6
37,0
97,7
38,2
10
124,1
29,0
117,5
31,6
110,7
34,4
106,4
36,1
103,6
37,3
100,6
38,5
5
119,6
30,8
113,2
33,8
106,5
37,1
102,3
39,2
99,5
40,7
96,7
42,2
6
123,2
31,1
116,5
34,2
109,6
37,4
105,5
39,5
102,6
40,9
99,8
42,4
7
126,8
31,5
119,9
34,5
112,9
37,8
108,6
39,8
105,6
41,3
102,7
42,7
8
130,3
31,9
123,5
34,8
116,3
38,1
111,7
40,2
108,6
41,7
105,4
43,2
9
133,8
32,3
127,2
35,1
119,7
38,4
114,9
40,6
111,5
42,1
108,0
43,7
10
137,3
32,8
130,9
35,5
123,3
38,7
118,0
41,0
114,3
42,6
110,4
44,4
5
128,3
32,7
121,7
35,9
114,7
39,3
110,3
41,5
107,4
43,1
104,3
44,6
6
132,2
33,0
125,4
36,2
118,2
39,7
113,8
41,8
110,7
43,3
107,7
44,9
7
136,2
33,3
129,2
36,6
121,8
40,0
117,2
42,2
114,1
43,6
111,0
45,2
8
140,3
33,7
133,0
36,9
125,4
40,3
120,7
42,5
117,5
43,9
114,3
45,4
402
432
452
9
144,3
34,0
136,8
37,3
129,0
40,7
124,2
42,8
120,9
44,2
117,6
45,7
10
148,4
34,4
140,6
37,6
132,6
41,0
127,6
43,1
124,3
44,5
120,9
46,0
5
138,1
35,5
131,5
39,0
124,1
42,9
119,2
45,4
115,8
47,2
112,2
49,0
6
142,0
35,8
134,8
39,3
127,6
43,2
123,3
45,7
120,4
47,4
117,5
49,1
7
146,2
36,1
138,5
39,7
131,4
43,6
127,3
46,0
124,7
47,7
122,1
49,4
8
150,7
36,5
142,7
40,1
135,4
44,0
131,2
46,4
128,6
48,0
126,1
49,7
9
155,5
36,9
147,3
40,5
139,6
44,4
135,1
46,8
132,2
48,5
129,3
50,3
10
160,5
37,3
152,4
40,9
144,0
44,8
138,9
47,3
135,4
49,1
131,8
50,9
5
151,0
39,7
143,0
43,7
134,7
47,9
129,6
50,7
126,1
52,5
122,6
54,5
6
155,5
40,3
147,7
44,0
139,1
48,3
133,5
51,1
129,6
53,1
125,6
55,2
7
160,1
40,8
152,2
44,5
143,3
48,7
137,4
51,6
133,3
53,6
129,1
55,7
8
164,6
41,3
156,4
45,0
147,3
49,2
141,4
52,0
137,4
53,9
133,2
55,9
9
169,2
41,8
160,3
45,7
151,1
49,8
145,5
52,4
141,7
54,1
137,9
56,0
10
173,9
42,2
164,0
46,4
154,8
50,4
149,6
52,7
146,3
54,2
143,1
55,7
5
171,1
45,5
162,2
50,1
153,1
55,1
147,5
58,2
143,7
60,4
139,8
62,7
6
176,2
46,1
167,1
50,8
158,1
55,5
152,8
58,3
149,3
60,2
145,9
62,1
7
181,4
46,7
171,9
51,4
162,9
56,0
157,7
58,7
154,3
60,4
151,0
62,2
8
186,7
47,3
176,8
52,0
167,4
56,6
162,0
59,3
158,5
61,1
155,2
62,9
9
192,2
47,9
181,6
52,5
171,6
57,3
165,8
60,2
162,1
62,2
158,4
64,3
10
197,7
48,5
186,5
53,0
175,6
58,1
169,2
61,4
164,9
63,8
160,7
66,2
502
552
602
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
BT10E005GB-02
18
®
ELFOENERGY LARGE2
VERSION: PREMIUM
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
To (ºC)
25
30
35
38
40
42
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
193,8
49,6
184,2
54,4
174,3
59,7
168,2
63,3
164,0
65,7
159,8
68,3
6
199,3
50,1
189,5
54,8
179,3
60,2
172,9
63,7
168,5
66,2
164,1
68,8
7
205,0
50,5
195,0
55,3
184,4
60,7
177,8
64,2
173,4
66,7
168,8
69,3
8
211,0
51,0
200,6
55,8
189,7
61,2
183,0
64,7
178,5
67,2
173,8
69,7
9
217,0
51,5
206,3
56,3
195,2
61,7
188,4
65,2
183,8
67,6
179,2
70,2
10
223,3
52,0
212,2
56,8
201,0
62,2
194,1
65,7
189,5
68,1
184,9
70,6
5
213,8
57,2
203,5
62,5
192,9
68,6
186,3
72,6
181,9
75,4
177,4
78,4
6
220,4
57,6
209,7
63,0
198,6
69,2
191,7
73,3
187,1
76,2
182,4
79,2
7
226,8
58,2
215,7
63,6
204,4
69,8
197,5
73,8
192,8
76,7
188,1
79,6
8
233,0
58,8
221,8
64,3
210,4
70,4
203,5
74,3
198,9
77,0
194,3
79,8
9
239,1
59,6
227,7
65,1
216,5
71,0
209,9
74,6
205,4
77,1
201,0
79,7
10
244,9
60,4
233,6
66,0
222,8
71,5
216,5
74,8
212,4
77,1
208,4
79,3
702
802
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
INTERNAL EXCHANGER PRESSURE DROP
100
THE AIR SIDE PRESSURE DROPS ARE RELATIVE
TO THE MEDIUM AIR TEMPERATURE OF 7°C
35
2
40
2
43
2
45
2
50
2
55
2
60
2
70
2
80
2
90
80
70
Q = AIR FLOW [l/s]
DP = PRESSURE DROP [kPa]
60
P [kPa]
50
THE WATER FLOW RATE CAN BE CALCULATED
WITH THE FOLLOWING FORMULA:
40
30
Q [l/s] = kWf / (4,186 x DT)
kWf = COOLING CAPACITY [kW]
DT = TEMPERATURE DIFFERENCE BETWEEN
WATER INLET / OUTLET
20
15
2
3
4
5
6
7
Q [l/s]
8
9
20
To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the
water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP
ACCESSORIES).
If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm,
because they can cause a bad unit operation and also its serious damaging.
ADMISSIBLE WATER FLOW RATE
Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.
352
402
432
452
502
552
602
702
802
Qmin
[l/s]
2,3
2,6
2,9
3,2
3,6
3,9
4,4
4,9
5,5
Qmax
[l/s]
6,6
7,4
8,1
9,0
10,2
11,1
12,2
13,5
15,1
19
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: PREMIUM
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
84,3
30
32,8
114
29
2,57
3,75
95,6
35,4
38,2
129
33
2,5
3,91
108
40,1
42,9
144
37
2,52
3,9
116
42,6
45,4
155
40
2,56
4,1
125
46,2
49
169
43
2,55
4,08
139
52,3
55,1
186
48
2,52
4,05
158
60,3
63,1
208
55
2,5
3,95
172
64,7
68,7
238
59
2,5
3,98
199
75,3
79,3
263
69
2,51
3,84
Nr
HP
Nr
l
Nr
Scroll
2
35
3
8
1
Scroll
2
40
3
10
1
Scroll
2
43
3
12
1
Scroll
2
45
3
10
1
Scroll
2
50
3
11
1
Scroll
2
55
3
13
1
Scroll
2
60
2
13
1
Scroll
2
70
3
13
1
Scroll
2
80
2
13
1
l/s
kPa
l
PHE
4
41
5
PHE
4,6
42
5
PHE
5,2
44
6
PHE
5,5
41
7
PHE
6
37
8
PHE
6,6
38
9
PHE
7,5
41
10
PHE
8,2
39
12
PHE
9,5
42
14
Nr
l/s
AX
2
9833
AX
2
9833
AX
2
9764
AX
2
9514
AX
2
9319
AX
2
9319
AX
2
9653
AX
3
14583
AX
3
14583
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
2" 1/2
COOLING
Cooling capacity
Compressor power input
Total power input
Heating capacity total recovery
Heating capacity partial recovery
EER
ESEER
COMPRESSOR
Type of compressors
N°. of Compressors
Nominal capacity
Standard capacity steps
Oil charge
Refrigerant circuits
INTERNAL EXCHANGER
1
Type of internal exchanger
Water flow rate (Internal Exchanger)
Internal exchanger pressure drop
Water content
EXTERNAL SECTION FANS
4
1
Type of fans
Number of fans
Standard air flow
CONNECTION
Water fittings
POWER SUPPLY
5
2
3
3
kW
kW
kW
kW
kW
Standard power supply
DIMENSION
Length
Depth
Height
STANDARD UNIT WEIGHTS
Shipping weight
Operating weight
400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
mm
mm
mm
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
2710
1097
1805
3075
1097
1805
4025
1097
1805
4025
1097
1805
kg
kg
773
778
796
802
885
892
917
924
955
963
975
984
1077
1087
1283
1295
1310
1324
(1) data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air intake 35°C
(2) According to EUROVENT the Total Power Input does not consider the pump share,
required to overcome the pressure drop for the solution circulation inside the exchangers.
(3) Option. recovery exchanger water = 40 / 45°C
(4) PHE = plates
(5) AX = axial-flow fan
ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)
SIZE
352
402
432
452
502
552
602
702
802
F.L.A. - Total
A
79,3
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
90,6
100
98,8
106,6
117,9
127,3
145,9
160,4
F.L.I. - Total
M.I.C. MAXIMUM INRUSH CURRENT
F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
M.I.C. - Value
kW
47,3
52,4
58,8
58,8
65,2
70,3
76,8
89,6
100,2
A
264,6
311,6
317,2
374,3
383,7
395
401,6
466,1
480,6
Voltage unbalance: max 2 %
Power supply: 400/3/50 Hz +/-6%
Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.
BT10E005GB-02
20
®
ELFOENERGY LARGE2
VERSION: PREMIUM
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
OPERATING LIMITS (COOLING)
SIZE
352
402
432
452
502
552
602
702
802
EXTERNAL EXCHANGER
Max air intake temperature
Max air intake temperature
Max air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
Min. air intake temperature
INTERNAL EXCHANGER
Max water inlet temperature
Min. water outlet temperature
Min. water outlet temperature
1
2
3
4
5
6
7
°C
°C
°C
°C
°C
°C
°C
43
45
50
-10
-7
-2
11
41
44
50
-10
-7
-2
11
40
43
50
-10
-7
-2
11
41
44
50
-10
-7
-2
11
41
44
50
-10
-7
-2
11
40
43
50
-10
-7
-2
11
40
42
50
-10
-7
-2
11
41
44
50
-10
-7
-2
11
40
43
50
-10
-7
-2
11
8
9
°C
°C
°C
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
24
5
-7
The functioning mode can also be extended up to external air temperatures of less than 39°C, but only with a FREE-COOLING configuration which is complete with an adequately
sized "Electric panel anti-frost protection" option.
Data referred to the following conditions :
- internal exchanger water = 12/7°C
- external exchanger air 35°C
- still air
In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit,
which has no electricity supply, correct maintenance (not functioning) is possible up to an
external air temperature of -20°C.
Warning: the still air condition is meant as absence of air flow to the unit. Any wind
condition can let air pass through the condenser coil thus worsening the operating limits of
the unit. In case of predominant winds, windbreak barriers are necessary.
(1) Max inlet temperature - unit at full load
(2) Max inlet air temperature - Unit at partial load
(3) Min inlet air temperature - Unit at full load and still fresh air
(4) Min inlet air temperature - Unit at partial load and still fresh air
(5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s.
(6) Min inlet air temperature - unit at partial load and air speed of 1 m/s.
(7) Standard unit without low temperature liquid device and external exchanger air intake
35°C
(8) Unit with low temperature liquid device and external exchanger air intake 35°C
Fluid with ethylene glycol of 40%
Note. For correct maintenance (not functioning) with external air temperatures at less than
-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the
"Electric panel anti-freeze protection" option and be continuously supplied with electricity.
The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this
condition, the minimum external air-temperature which is permitted depends on the chosen
model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.
Graph informed to size 352.
The detail of each size is shown in tabular date.
15
Ta = external exchanger air intake temperature
(dry bulb)
To (°C)
20
1
10
1
1
To (°C) = internal exchanger water outlet
temperature
3
4
1. Standard unit:
(not with ‗Low temperature liquid‘)
2. ‗Low temperature liquid‘ unit (with ethylene
glycol of 40%)
3. Partial-load unit
(automatic capacity control)
4. Full-load unit
(automatic air flow modulation)
5
0
2
2
2
4
3
-5
-10
-12
-8
-4
0
4
8
12
16
20
24
28
32
36
40
44
48
52
Ta (°C)
SOUND LEVEL
Sound Power Level (dB)
SIZE
Sound pressure level
Sound
pressure
level
Sound
power
level
63
125
250
500 1000 2000 4000 8000
dB(A)
dB(A)
352
83
84
85
80
72
69
60
55
63
81
402
82
83
84
80
74
70
62
57
63
81
432
82
83
86
81
75
71
62
56
65
82
452
83
83
85
82
76
70
63
57
65
83
502
81
83
86
82
75
70
62
55
65
83
552
82
83
87
83
77
72
64
58
66
84
602
82
83
86
83
78
71
64
57
66
84
702
85
85
88
85
79
73
65
59
67
86
802
84
85
88
85
79
73
65
59
67
86
21
The sound levels refer to the unit at full load, in the rated test
conditions.
The sound pressure level refers to a distance of 1m from the external
surface of the units operating in an open field.
Measures, according to ISO 3744 regulations, are carried out on a
reflecting surface, with respect to the EUROVENT 8/1 certification.
Data referred to the following conditions:
- internal exchanger water = 12/7°C
- outdoor air temperature 35°C
The sound levels indicated sideways are valid only for the operating
range of the ‗Extremely low noise EN‘ configuration; with fresh air
temperatures higher and in any case into the operating range of the
‗Compressor soundproofing SC‘ configuration, consider the sound
levels of the ‗Compressor soundproofing‘ configuration .
BT10E005GB-02
ELFOENERGY LARGE2
®
VERSION: PREMIUM
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
352
To (ºC)
25
30
32
35
38
40
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
89,1
24,6
84,3
26,9
82,3
27,9
79,3
29,4
76,1
31,0
74,0
32,1
6
91,9
24,8
87,0
27,2
84,9
28,2
81,7
29,7
78,5
31,3
76,3
32,4
7
94,7
25,1
89,6
27,5
87,5
28,5
84,3
30,0
81,0
31,5
78,8
32,6
8
97,4
25,4
92,1
27,8
90,0
28,8
86,8
30,2
83,6
31,7
81,5
32,7
9
100,1
25,7
94,5
28,2
92,4
29,1
89,3
30,5
86,4
31,9
84,5
32,8
10
102,7
26,0
96,9
28,6
94,8
29,5
91,9
30,8
89,3
32,0
87,7
32,7
5
102,2
29,3
96,5
32,0
94,2
33,1
90,6
34,8
87,0
36,6
84,5
37,8
6
104,9
29,6
98,9
32,3
96,6
33,4
93,0
35,1
89,5
36,9
87,2
38,1
7
107,7
30,0
101,6
32,6
99,2
33,7
95,5
35,4
91,9
37,2
89,6
38,4
8
110,7
30,3
104,5
33,0
101,9
34,1
98,1
35,7
94,3
37,4
91,7
38,6
9
113,7
30,6
107,5
33,3
104,9
34,4
100,8
36,0
96,6
37,7
93,6
38,8
10
116,7
31,0
110,8
33,7
108,1
34,8
103,6
36,4
98,7
37,9
95,3
38,9
5
115,3
32,9
108,6
36,0
105,9
37,3
102,0
39,4
98,1
41,5
95,6
42,9
6
118,1
33,4
111,9
36,4
109,2
37,7
104,8
39,7
100,1
42,0
96,8
43,5
7
121,3
33,8
115,1
36,8
112,4
38,1
107,9
40,1
102,9
42,3
99,5
43,9
8
124,8
34,2
118,1
37,3
115,4
38,5
111,1
40,5
106,6
42,5
103,5
44,0
9
128,6
34,5
121,0
37,8
118,2
39,1
114,4
40,9
111,0
42,6
109,0
43,7
10
132,9
34,8
123,7
38,4
121,0
39,7
118,0
41,3
116,3
42,6
115,8
43,2
5
123,3
35,0
116,7
38,3
114,0
39,7
109,8
41,8
105,5
44,0
102,6
45,5
6
127,4
35,3
120,1
38,7
117,3
40,1
113,0
42,2
108,8
44,4
106,1
45,8
7
131,1
35,7
123,5
39,1
120,5
40,5
116,2
42,6
112,1
44,7
109,4
46,1
8
134,6
36,2
126,8
39,6
123,8
41,0
119,5
42,9
115,3
44,9
112,6
46,1
402
432
452
9
137,7
36,8
130,1
40,3
127,1
41,5
122,8
43,3
118,5
45,0
115,8
46,0
10
140,5
37,6
133,3
41,0
130,4
42,1
126,1
43,7
121,7
45,0
118,8
45,8
5
131,8
37,9
124,7
41,9
121,9
43,4
117,9
45,5
114,0
47,6
111,5
49,0
6
135,8
38,4
128,4
42,1
125,4
43,7
120,6
46,2
115,7
48,9
112,3
50,7
7
139,8
38,9
132,3
42,5
129,0
44,1
123,9
46,8
118,5
49,6
114,7
51,6
8
143,8
39,4
136,2
43,0
132,9
44,6
127,8
47,2
122,3
49,9
118,5
51,8
9
147,8
39,8
140,2
43,7
137,1
45,2
132,2
47,4
127,2
49,6
123,7
51,1
10
151,9
40,2
144,4
44,4
141,5
45,8
137,2
47,5
133,1
48,9
130,5
49,7
5
147,2
43,1
139,1
47,1
135,7
48,8
130,3
51,5
124,6
54,4
120,7
56,3
6
151,0
43,8
143,1
47,8
139,7
49,5
134,3
51,9
128,6
54,5
124,6
56,1
7
155,1
44,4
147,0
48,5
143,5
50,1
138,2
52,4
132,6
54,8
128,7
56,4
8
159,6
44,9
150,8
49,0
147,3
50,6
141,9
53,0
136,5
55,4
132,9
57,0
9
164,4
45,3
154,7
49,5
151,0
51,1
145,6
53,7
140,5
56,2
137,2
57,9
10
169,6
45,6
158,4
49,8
154,5
51,6
149,2
54,4
144,5
57,3
141,7
59,2
5
165,7
49,8
157,4
54,2
153,9
56,2
148,4
59,3
142,5
62,8
138,5
65,2
6
171,1
50,3
161,5
55,1
158,0
57,0
152,9
59,8
148,3
62,6
145,4
64,5
7
176,3
50,9
165,9
55,9
162,3
57,7
157,7
60,3
153,8
62,6
151,6
64,0
8
181,3
51,5
170,6
56,5
167,1
58,3
162,6
60,6
159,0
62,6
157,2
63,8
9
186,1
52,2
175,6
57,0
172,1
58,7
167,6
60,9
164,0
62,7
162,0
63,8
10
190,7
52,9
181,0
57,4
177,5
58,9
172,8
61,0
168,7
62,9
166,3
64,0
502
552
602
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
BT10E005GB-02
22
®
ELFOENERGY LARGE2
VERSION: PREMIUM
ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)
COOLING PERFORMANCE
EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C
SIZE
To (ºC)
702
802
25
30
32
35
38
40
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
kWf
kWe
5
181,6
52,8
172,2
57,9
168,4
60,1
162,7
63,5
156,9
67,1
153,0
69,6
6
186,9
53,4
176,8
58,6
172,9
60,8
167,2
64,1
161,7
67,6
158,1
70,0
7
192,1
54,0
181,7
59,2
177,6
61,4
171,7
64,7
166,0
68,3
162,3
70,7
8
197,0
54,7
186,9
59,8
182,7
61,9
176,4
65,4
169,9
69,0
165,6
71,5
9
201,8
55,5
192,5
60,3
188,2
62,5
181,1
66,0
173,4
69,9
167,9
72,6
10
206,4
56,4
198,4
60,8
193,9
63,0
186,0
66,7
176,5
70,9
169,3
74,0
5
209,5
61,4
199,6
67,0
195,2
69,5
188,1
73,5
180,4
77,9
175,0
81,0
6
215,7
62,0
204,4
68,0
200,1
70,4
194,0
74,2
188,2
78,0
184,5
80,5
7
222,2
62,6
209,9
68,8
205,5
71,3
199,5
75,0
194,3
78,6
191,2
81,0
8
228,7
63,3
215,9
69,6
211,2
72,1
204,6
75,9
198,5
79,8
194,8
82,5
9
235,4
64,0
222,5
70,1
217,2
72,8
209,2
77,1
201,0
81,7
195,5
84,9
10
242,2
64,8
229,6
70,5
223,5
73,4
213,3
78,4
201,7
84,1
193,2
88,3
kWf = Cooling capacity in kW
kWe = Compressor power input in kW
To = Internal exchanger water outlet temperature in° C
INTERNAL EXCHANGER PRESSURE DROP
100
THE AIR SIDE PRESSURE DROPS ARE RELATIVE
TO THE MEDIUM AIR TEMPERATURE OF 7°C
35
2
40
2
43
2
45
2
50
2
55
2
60
2
70
2
80
2
90
80
70
Q = AIR FLOW [l/s]
DP = PRESSURE DROP [kPa]
60
P [kPa]
50
40
THE WATER FLOW RATE CAN BE CALCULATED
WITH THE FOLLOWING FORMULA:
30
Q [l/s] = kWf / (4,186 x DT)
kWf = COOLING CAPACITY [kW]
DT = TEMPERATURE DIFFERENCE BETWEEN
WATER INLET / OUTLET
20
15
2
3
4
5
6
7
Q [l/s]
8
9
20
To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the
water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP
ACCESSORIES).
If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm,
because they can cause a bad unit operation and also its serious damaging.
ADMISSIBLE WATER FLOW RATE
Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.
352
402
432
452
502
552
602
702
802
Qmin
[l/s]
2,3
2,6
2,9
3,2
3,6
3,9
4,4
4,9
5,5
Qmax
[l/s]
6,6
7,4
8,1
9,0
10,2
11,1
12,2
13,5
15,1
23
BT10E005GB-02
ELFOENERGY LARGE2
®
CONFIGURATIONS
Consult the appropriate table, shown in the final section, to verify the compatibility between the different options.
B - WATER LOW TEMPERATURE
Configuration also known as "Brine". Enables a non-freezable solution to be cooled (for instance, water and ethylene glycol in
appropriate quantities) up to a temperature of between +4°C and –7°C.
Includes:
- Appropriate exchangers, complete with thick closed-cell insulation;
- Electronic-type expansion valve, functional calibration and safety devices adapted to the particulars of use.
In the selection phase, it is necessary to indicate the type of function required, and the unit will be optimised with:
- Unit with single working set-point (only at low temperature)
- Unit with double working set-point.
The unit in this configuration have a different operation field, indicated on the previous pages.
In the low temperature operation, some partialisation degrees could be not available. For more information, contact our Sales Department.
D - PARTIAL ENERGY RECOVERY
Configuration
which
allows
hot
water
production
free-of-charge during the cooling function, thanks to the
recovery of part of the condensation heat which would
otherwise be disposed of into the external heat source.
This configuration is also known as "desuperheating coil". It is
made up of brazed-plate exchanger in AISI 316 stainless steel
which is ideal for recovering around a quarter of the heating
capacity of the unit (equal to the sum of the cooling capacity
and the absorbed power input of the compressors).
4
T
3
5
AE
35°C
RW in
40°C
T
EEV
RW out
45°C
D
2
The partial recovery device is considered to be working when
it is supplied by the flow of water to be heated. This condition
improves the unit performance, since it reduces the
condensation temperature: in nominal conditions, the cooling
capacity increases indicatively by 3,2% and the absorbed
power input from the compressors is reduced by 3,6%.
1
TW out
7°C
When the temperature of the water to be heated is particularly
low, it is opportune to insert a flow regulation valve in the
hydraulic circuit, to maintain the recovery output temperature
at higher than 35°C and thus avoid refrigerant condensation in
the partial energy recovery device.
TW in
12°C
D - Partial recovery device
1.
2.
3.
4.
5.
TW in Chilled water Inlet
TW out Chilled water Outlet
Internal exchanger
Compressors
Recovery exchanger
External exchanger
Electronic expansion valve
RW in Recovery water inlet
RW out Recovery water outlet
AE
Outdoor air
INTERNAL EXCHANGER PRESSURE DROP - PARTIAL ENERGY RECOVERY
45
Δ P [kPa]
352
402
432-452
502
702-802
552-602
40
35
30
25
20
15
10
5
0,5
1
1,5
2
2,5
3
BT10E005GB-02
3,5
4
4,5
5
5,5
Q [l/s]
Q WATER FLOW RATE [l/s]
DP PRESSURE DROP [kPa]
24
6
®
ELFOENERGY LARGE2
R - TOTAL ENERGY RECOVERY
Configuration which allows hot water production free-of-charge during the cooling function, thanks to the total recovery of the
condensation heat which would otherwise be discharge into the external heat source. This solution increases the overall
efficiency of the system in all cases in which a high-level of hot water production is requested.
It is made up of 316 Stainless steel brazed plate heat exchanger, which is ideal for recovering the entire unit heating capacity
(equal to the sum of the cooling capacity and the absorbed power input of the compressors), from the on-of type solenoid
valves, the temperature sensors for the hot water circuit supply and return and the relative integrated logic controller with two
partialisation steps.
La disponibilità di acqua calda è sempre subordinata alla produzione di acqua refrigerata. Si veda il seguente esempio:
1. Cooling capacity request = 100% / Heat capacity request = 0%→ Cooling capacity production only.
2. Cooling capacity request = 100% / Heat capacity request = 100%→ Cooling capacity production and heat capacity
production by recovery.
3. Cooling capacity request = 50% / Heat capacity request = 100%→ Cooling capacity production and heat capacity
production by recovery, equals 50% of the requested heat capacity.
To avoid constant switching in the cooling circuit should be added to a adequate capacity storage tank in the hot water circuit of the
system.
If the hot water circulation is not present on the heat recovery exchanger, the maximum inlet air temperature decreases of about 2 °C
compared to units without 'Total Energy Recovery'.
TOTAL ENERGY RECOVERY OPERATING
TOTAL ENERGY RECOVERY NOT OPERATING
When hot water is required, the condensing coil is turned off.
The condensation takes place entirely in the recovery circuit.
When the set-point recovery is fulfilled, the coil is reactivated. In this
condition the total recovery circuit operates as a partial recovery
(desuperheater).
6
6
AE
35°C
5
T
4
3
7
RW in
40°C
5
4
3
T
EEV
T
R
RW out
45°C
2
RW out
45°C
2
1
1
TW out
7°C
TW in
12°C
TW out
7°C
R - Total recovery device
1
2
3
4
5
AE
35°C
RW in
44°C
EEV
7
R
T
Internal exchanger
Compressors
Recovery exchanger
Total recovery enabling valve
External exchanger enabling valve
TW in
12°C
6 External exchanger
7 Electronic expansion valve
TW in Chilled water inlet
TW out Chilled water outlet
T Temperature probe
RW
Recovery water inlet
RW out Recovery water outlet
AE
Outdoor air
ΔP [kPa]
INTERNAL EXCHANGER PRESSURE DROP - TOTAL RECOVERY ENERGY
100
90
80
70
60
50
40
30
20
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Q [l/s]
18
Q WATER FLOW RATE [l/s]
DP PRESSURE DROP [kPa]
25
BT10E005GB-02
ELFOENERGY LARGE2
®
FCD - DIRECT FREE-COOLING
Configuration which enables great savings on the management costs of the system in applications which require chilled
water even during cold seasons like, for instance, industrial processes, data centres, telecommunications, technological
applications and trade centres.
When the external air temperature is less than the temperature of the return water in the system, the FREE-COOLING system
recovers coolness from outdoor and reduces the compressor working up to their being withdrawn completely.
The higher the temperature of the chilled water in the system (e.g. 10-15°C instead of 7-12°C), the greater the field of application of
the FREE-COOLING system and, therefore, the energy saving.
USING UNFREEZABLE SOLUTIONS
The FREE-COOLING configuration is particularly indicated in buildings where, at least at certain times of the year, the external air
temperature also reaches very low values. For this reason, the liquid must be protected from the risk of freezing, typically by adding
an appropriate anti-freeze substance such as ethylene glycol. The percentage of glycol in the solution depends on the minimum
temperature value foreseen in the installation area, and in any case, remains within the main parameters of the system design.
TECHNICAL DESCRIPTION
In comparison with standard units, Clivet units in the direct FREE-COOLING configuration also include:
three-way switching valve with on/off regulation
Finned water-air COIL exchanger (FREE-COOLING coil)
additional outdoor air temperature sensor and control logic dedicated
flush hydraulic connections.
5
MANAGEMENT LOGIC
There are three main function modes, which can be differentiated in essence
by the position of the three-way switching valve and by the number of active
compressors.
(A) SUMMER SEASON
In the summer, with external air temperatures greater than the return
temperature of the system liquid, the three-way valve is switched in such a way
as to exclude the FREE-COOLING coils.
The cooling of the liquid is referred to the direct expansion circuit, via the
workings of the compressors as in a traditional chiller.
(B) INTERMEDIATE SEASON
During the intermediate season, or rather when the external air temperature is a
little less than the temperature of the return water in the system, when the
system senses that the external air temperature conditions are favourable:
it switches the position of the three-way valve forcing the solution to transit
through the FREE-COOLING coils before reaching the evaporator;
it puts the fans to their maximum speed to exploit as much as possible the
solution cooling using the outdoor air ;
it undertakes the initial cooling of the solution in a "natural and free" way;
it supplies any missing capacity through the chiller cycle, using the
compressors functioning partially (the absorbed power input is proportional to
the level of partialisation).
In case of an increase in the external air temperature, the microprocessor
automatically converts the unit functioning to the summer setting, guaranteeing
the conditions requested by the user at all times.
4
6
T
AE
35°C
EEV
3
1
TW out
7°C
TW in
12°C
2
A
5
4
6
T
AE
11°C
EEV
3
1
(C) WINTER SEASON
During the winter season, with the temperature of the external air lower than the
temperature of the return water in the system, the system senses that conditions
are favourable for the FREE-COOLING function:
the three-way valve is switched as in the previous case, forcing the solution
to transit through the FREE-COOLING coils before reaching the evaporator;
the external air temperature brings the solution to the FREE-COOLING coil
output already at the temperature requested by the user;
the microprocessor management totally deactivates all the compressors
supplying all the requested cooling capacity AT NO COST, in contrast to
traditional chillers.
The difference between the outdoor air temperature and that requested by the
user can also be such as to lower the solution temperature at the
FREE-COOLING coil output to below the set-point requested for this use. This is
a condition which does not compromise unit safety thanks to the presence of
anti-freeze in the solution. The microprocessor modulates the fan speed until
their withdrawal.
If, with all the fans switched off, the temperature continues to go down, the
three-way valve automatically positions itself in the summer setting, thus
enabling the set-point to be maintained.
D - Partial recovery device
1. Internal exchanger
2. Compressors
BT10E005GB-02
3. Recovery exchanger
4. External exchanger
5. Electronic expansion valve
TW in
Chilled water Inlet
26
TW out
10°C
TW in
15°C
2
B
5
4
6
T
AE
0°C
EEV
3
1
TW out
10°C
TW in
15°C
2
TW out
Chilled water Outlet
RW in
RW out
AE
Recovery water inlet
Recovery water outlet
Outdoor air
C
®
ELFOENERGY LARGE2
UNIT PERFORMANCES IN THE DIRECT FREE-COOLING CONFIGURATION
The unit performance in the direct FREE-COOLING configuration also depends on the antifreeze percentage used in the
circuit and are shown below in two main operating modes.
OPERATING MODE: DEACTIVATED DIRECT FREE-COOLING
To consider the standard unit performance at the requested conditions and apply the following correction factors.
Percentage weight of ethylene glycol
10%
20%
30%
40%
Cooling power factor
0,97
0,96
0,95
0,94
Compressor input factor
1,040
1,034
1,030
1,027
EXAMPLE
Determine the performance of the following units : WSAT-XEE FCD 702 SC EXC (EXCELLENCE version, direct FREE-COOLING configuration), with water =
15/10 °C / 30% glycol / Outdoor air 35°C
Reference:
WSAT-XEE S 702 SC EXC
Cooling capacity = 214,8 kW / Electric compressor capacity = 56,9 kW
Calculation:
WSAT-XEE FCD 702 SC EXC (Direct FREE-COOLING)
Cooling capacity = 214,8 x 0,95 = 204,1 kW / Electric compressor capacity = 56,9 x 1,03 = 58,6 kW
OPERATING MODE: ACTIVATED DIRECT FREE-COOLING
Size (SC / EN Version)
352
402
432
452
502
552
602
702
802
Free-cooling nominal capacity (1)
kW
101
113
126
136
148
160
181
204
227
Temperature wih Free-cooling at 100% (1)
°C
0,5
-0,5
-2,0
0,0
-0,5
-1,0
-2,5
0,0
-2,5
(1) Data referred to the following conditions:
- water temperature: 15°C inlet / 10°C outlet
- glycol percentage 30%
DT [°C]
When the outside air temperature increases, the cooling capacity of FREE-COOLING decreases (at the same temperature of
water on returning from). If you know the cooling capacity required by the system, you can calculate the maximum outside air
temperature from which the cooling capacity is available through FREE-COOLING. Below this temperature, the required power
is supplied only by modulation of the air flow fans.
18
602-802
432
16
402-502-552
352-452-702
14
12
10
8
6
4
2
20%
KEY
DT
%FC
30%
40%
50%
60%
70%
80%
90%
100% % FC
Approach between the system outlet water temperature and the outdoor air
FREE-COOLING percentage (compared with the FREE-COOLING nominal capacity)
EXAMPLE
Determine the performances with outdoor air = +1°C for the following unit: WSAT-XEE FCD 702 SC EXC, EXCELLENCE version, Direct FREE-COOLING
configuration), with water at 15/10 °C / 30% glycol.
Reference:
WSAT-XEE FCD 702 SC EXC
FREE-COOLING nominal capacity = 204 kW (from table - Water 15/10 ° C / 30% glycol / outdoor air temperature 0 ° C)
Calculation:
Approach between the system outlet water temperature and the outdoor air = 15°C - 1°C = 14°C
From the graph: FREE-COOLING percentage = 93%
FREE-COOLING capacity at +1°C of outdoor temperature = 204 x 93% = 189,7 kW
27
BT10E005GB-02
ELFOENERGY LARGE2
®
HYDRONIC GROUP ACCESSORIES
1PUS - STANDARD PUMP
Option supplied built-in. Centrifugal electro-pump, with AISI type 304 stainless steel body and rotor. Mechanical seal using
ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55 protection. Complete with
thermoforming insulating shell, rapid attachments with insulating shells, non-return valve, safety valve, manometers, system
load safety pressure switch, stainless steel anti-freeze immersion heaters set on inlet and supply.
The different available models can be set apart by the useful prevalence of the system.
1PU1SB - STANDARD PUMP WITH EMERGENCY PUMP
Option supplied built-in. Two centrifugal electro-pumps one of which is in stand-by, with AISI type 304 stainless steel body and
impeller. Mechanical seal using ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55
protection. Complete with thermoforming insulating shell, rapid attachments with insulating shells, non-return valve, safety
valve, manometers, system load safety pressure switch, stainless steel anti-freeze immersion heaters set on inlet and supply.
The built-in microprocessor controller balances the working hours and in case of any breakdown signals the fault and
automatically activates the reserve pump.
The different available models can be set apart by the useful prevalence of the system
The 1PUS and 1PU1SB options are supplied as standard with a hydraulic connection kit on the system return (to be installed externally
to the unit, by the Customer). The kit is made up of:
no. 1 cast-iron butterfly shut-off valve, complete with activating handle and mechanical calibration lock
no. 1 rapid connection
A300 / A500 - 300 / 500 LITRES STORAGE TANK
Option supplied built-in. Stainless steel storage tank complete with double-sheeted coating with closed-cell insulation, stainless
steel anti-freeze immersion heater, bleed valve, discharge cock, cast-iron butterfly shut-off valve with rapid attachments and
activating handle with mechanical calibration lock at the evaporator output, rapid attachments with insulation shells.
The available models have different static pressure.
The A300 and A500 options are supplied as standard with the hydraulic connection kit on the system return (to be installed externally to
the unit, by the Customer). The kit is made up of:
no. 1 cast-iron butterfly intercept valve, complete with activating handles and mechanical calibration lock
no. 1 rapid connection
STANDARD PUMP / STANDARD PUMP
WITH EMERGENCY PUMP
STANDARD PUMP / WITH EMERGENCY
PUMP AND STORAGE TANK
1
1
TW out
7°C
STORAGE TANK
TW out
7°C
TW in
12°C
12
2
1
8
TW in
12°C
TW out
7°C
2
TW in
12°C
12
9
8
9
A
A
11
11
11
11
10
10
10
10
8
3
9
3
4
5
2
2
IFWX
IFWX
IFWX
7
7
7
6
6
6
Internal exchanger
Shut-off valve
Bleed valve
Storage tank with antifreeze heater
Drain valve
Shut-off valve with rapid connection
Steel mesh filter water side
BT10E005GB-02
9
5
2
1
2
3
4
5
6
7
8
4
8 Manometer
9 Safety valve (6 Bar)
10 Closed couple pumps with high efficiency
impellers
11 Non-return valve
12 Safety pressure switch system load (Prevents
the operation of the pumps in case of lack of
28
water)
TW in Cooling water inlet
TW out Cooling water outlet
- - - Standard Hydraulic connection Kit
The gray area indicates additional optional
components.
®
ELFOENERGY LARGE2
1PUS / 1PU1SB PERFORMANCE OPTIONS
VERSION: EXCELLENCE
260
240
220
ΔP [KPa]
200
180
160
140
120
PU6
100
PU3
PU5
80
PU2
60
PU1
40
PU4
20
0
2
2,5
3
3,5
4
4,5
5
5,5
6
6,5
7
7,5
8
8,5
9
9,5
10 10,5 11
802
702
602
552
502
452
432
402
352
Q [l/s]
VERSION: PREMIUM
260
240
220
ΔP [KPa]
200
180
160
140
120
100
PU6
PU3
80
PU5
PU2
60
PU1
40
PU4
20
0
6,5
7
7,5
8
8,5
9
9,5
10
802
6
702
5,5
602
5
552
4,5
502
4
452
3,5
432
3
402
2,5
352
2
10,5
11
Q [l/s]
Attention: to obtain the values of available head, the heads represented on these charts must be decreased by:
Evaporator pressure drop
IFVX Accessory - Steel mesh filter water side (if supplied)
SINGLE PUMP TECHNICAL FEATURES
PUMP
PU1
PU2
PU3
PU4
NOMINAL CAPACITY [kW]
1,4
1,4
1,8
1,8
NOMINAL CURRENT [A]
2,6
2,6
3,2
3,4
PU5
PU6
2,9
3,3
4,8
5,6
29
BT10E005GB-02
ELFOENERGY LARGE2
®
A300RPS / A500RPS - 300 / 500 LITRES STORAGE TANK WITH PRIMARY CIRCUIT BUILT-IN
Option supplied built-in. Simplifies system design and manufacture.
Available only with ‗1PUS option - Standard pump or‘ ‗1PU1SB - Standard pump with emergency pump‘. This accessory
includes components designed for the A300 / A500 option and:
Primary circuit, already built and tested on the unit
cast-iron butterfly shut-off valve, with rapid connection and activating handle and mechanical calibration lock in evaporator
outlet and on the pump suction
A300RPS / A500RPS options are available only with ―Low head pump‖ option.
1
TW out
7°C
1
2
3
4
5
6
7
8
9
10
11
12
TW in
12°C
12
2
8
9
A
11
11
10
10
3
8
4
Internal exchanger
Shut-off valve
Bleed valve
Storage tank with antifreeze heater
Drain valve
Shut-off valve with rapid connection
Steel mesh filter water side
Manometer
Safety valve (6 Bar)
Closed couple pumps with high efficiency impellers
Non-return valve
Safety pressure switch system load (Prevents the
operation of the pumps in case of lack of water)
TW in Cooling water inlet
TW out Cooling water outlet
The gray area indicates additional optional components.
9
2
5
6
IFWX
7
IFWX - STEEL MESH FILTER WATER SIDE
The device prevents fouling of the exchanger by any impurities in the hydraulic circuit. The mechanical filter mesh stainless
steel should be placed on the water inlet. It is easily removed for periodic maintenance and cleaning. Also includes:
cast-iron butterfly shut-off valve, with rapid connection and activating handle and mechanical calibration lock;
rapid connections with insulating protection.
STEEL MESH FILTER
CHARACTERISTICS
P [kPa]
STEEL MESH FILTER PRESSURE DROP
30
SIZE
25
20
2 1/2’’
Filtering degree
1,6 mm
15
10
5
0
2
4
6
8
Q = WATER FLOW [l/s]
DP = PRESSURE DROP WATER SIDE[kPa]
10
12
14
Q [l/s]
Pressure drop with clean filter
Installation by the User, outside the unit
Check the presence of the necessary hydraulic shut off valve on the system, to the periodic maintenance
Accessories supplied separately
BT10E005GB-02
30
352÷802
Diameter
®
ELFOENERGY LARGE2
ABU - FLUSH HYDRAULIC CONNECTIONS
Option which simplifies the hydraulic connections which otherwise occur within the unit (by the Customer).
Includes from internal piping to the external unit panel, two rapid flush connections, two "welding" pipes for connecting to the
system by the Customer.
The accessory is supplied built-in.
A - STANDARD UNIT
B - UNIT WITH ABU OPTION
Scheme, not in scale
IMPORTANT!
The flush hydraulic connections are supplied as a standard in the unit complete with the following options:
Direct FREE-COOLING configuration
Standard pump / Standard emergency pump
Storage tank
Storage tank with a primary circuit built-in
HYDROPACK
GENERAL NOTE
It is also opportune to provide for the following system components, which are not included in the Clivet supply.
Shut-off valve, where it is not already provided for in the Clivet supply.
Support devices for the piping and anti-vibration flexible joints.
Expansion vessel (example for closed-circuit system)
Supply control thermometer
Additional vent and discharge valves where necessary
31
BT10E005GB-02
ELFOENERGY LARGE2
®
HYDROPACK
2PM - HYDROPACK WITH TWO PUMPS
Option supplied built-in. Pumping station made up of two parallel electro-pumps, with modular self-adapting activation logic.
Enables an automatic reduction in liquid flow in critical conditions, avoiding blocks due to overloading and consequential
interventions by specialised technical personnel.
Centrifugal electro-pump, with AISI type 304 stainless steel body and impeller.
Mechanical seal using ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55 protection.
Three-phase electric motor with an IP55 protection grade. Complete with thermoforming insulating shell, rapid connections
with insulating shells, non-return valve, safety valve, manometers, system load safety pressure switch, stainless steel
anti-freeze immersion inlet and supply resistances.
The different available models can be set apart by the useful prevalence of the system.
The 2PM option is supplied as standard with the hydraulic connection kit on the system return (to be installed externally to the unit, by
the Customer). The kit is made up of:
no. 1 cast-iron butterfly intercept valve, complete with activating handles and mechanical calibration lock
no. 1 rapid connection
The 2PM option is supplied with a kit made up of 2 blind rapid connections, for the removal of a pump in case of maintenance.
The 2PM option is:
compatible with the A300 / A500 option - 300 / 500 litre storage tank
not compatible with the A300RPS / A500RPS option - 300 / 500 litres storage tank with a primary circuit built-in.
HYDROPACK
HYDROPACK
WITH STORAGE TANK
1
TW out
7°C
1
TW in
12°C
2
TW out
7°C
TW in
12°C
2
12
8
12
9
8
9
11
11
11
11
10
10
10
10
8
3
9
9
8
4
5
2
2
IFWX
11 Internal exchanger
2 Compressors
3 Recovery exchanger
4 Total recovery enabling valve
5 External exchanger enabling valve
6 External exchanger
7 Electronic expansion valve
BT10E005GB-02
IFWX
7
7
6
6
T Temperature probe
TW in Chilled water inlet
TW out Chilled water outlet
RW
Recovery water inlet
RW out Recovery water out
32
- - - Standard Hydraulic connection Kit
The gray area indicates additional optional
components.
®
ELFOENERGY LARGE2
PERFORMANCES OF THE 2PM OPTION (HYDROPACK)
VERSION: EXCELLENCE
260
240
220
200
ΔP [KPa]
180
2 x PU6
160
2 x PU5
140
120
100
80
2 x PU3
60
40
2 x PU2
2 x PU1
20
6,5
7
7,5
8
8,5
9
9,5
10 10,5
11 11,5
802
6
702
5,5
602
5
552
4,5
452
4
432
3,5
402
3
352
2,5
502
0
12 12,5
13
Q [l/s]
VERSION: PREMIUM
260
240
220
200
ΔP [KPa]
180
2 x PU6
160
2 x PU5
140
120
100
80
2 x PU3
60
40
2 x PU2
2 x PU1
20
0
2,5
3
3,5
4
4,5
5
5,5
6
6,5
7
7,5
8
8,5
9
9,5
10
10,5
11
11,5
12
12,5
13
802
702
602
552
502
452
432
402
352
Q [l/s]
Attention: to obtain the values of available head, the heads represented on these charts must be decreased by:
Evaporator pressure drop
IFVX Accessory - Steel mesh filter water side (if supplied)
SINGLE PUMP TECHNICAL CHARACTERISTICS
PUMP
2PU1
2PU2
2PU3
NOMINAL CAPACITY [kW]
2 x 1,4
2 x 1,4
2 x 1,8
NOMINAL CURRENT [A]
2 x 2,6
2 x 2,6
2 x 3,2
2PU5
2 x 2,9
2 x 4,8
2PU6
2 x 3,3
2 x 5,6
33
BT10E005GB-02
ELFOENERGY LARGE2
®
ACCESSORIES
PGFC - FINNED COIL PROTECTION GRILL
This accessory is used to protect the external coil from the accidental contact with
external things or people. Ideal for installation in places where is possible the passage
of people such as parking, terraces, etc.
The accessory is supplied built-in.
PGCCH - ANTI-HAIL PROTECTION GRILLES
This accessory is used to protect the external coil from hail.
The hail can deform the fins of the Exchange worsting heat exchange with air.
The accessory is supplied built-in.
CCCA - COPPER / ALUMINIUM CONDENSER COIL WITH ACRYLIC LINING
Batteries with copper tubes and aluminium fins with acrylic paint. They can be used in
the presence of saline concentrations in the air and other weathering agents
moderately aggressive.
Option is not suitable for application in sulphureous ambient.
CCCA1 - COPPER / ALUMINIUM CONDENSER COIL WITH FIN GUARD (SILVER) TREATMENT
Treatment that offers an optimum heat exchange and guaranteed over time and
protects against corrosion finned heat exchangers. They can be used in the presence
of saline concentrations in the air and other aggressive chemical agents, keeping the
performance of the exchanger constant over time.
CCCC - COPPER / COPPER CONDENSER COIL
Exchange with copper tubes, copper fins and brass shell. They can be used in the
presence of saline concentrations in the air and other weathering agents moderately
aggressive.
Option is not suitable for application in sulphureous ambient.
AMMX - SPRING ANTIVIBRATION MOUNTS
The spring anti-vibration devices are fastened in housings on the longitudinal members.
They reduce the vibrations caused by the machine, reducing the noises transmitted by
the support structures.
Accessory is supplied separately
BT10E005GB-02
34
®
ELFOENERGY LARGE2
FANQE - ELECTRICAL PANEL VENTILATION
This option is necessary for very hot climates, where the external temperature can be between +40°C and
+50°C. It is made up of a forced ventilation system, activated by a thermostat, which provides for the
correct usage temperature to be maintained by the components inside the electrical panel. The option
includes a thermostat which activates forced ventilation when necessary.
The device is installed and tested built-in.
This accessory functions at all times even when the unit is switched off as long as the electricity supply is
maintained and the unit is not isolated.
In order to guarantee that the correct unit operation, the temperature inside the unit must not exceed 50°C.
Therefore, during storage or when the unit is already installed but not powered, it is necessary to avoid exceeding
the above-indicated temperature. When the unit has been installed, the protection and safety devices are only
active with the power supply switched on and the unit not isolated.
RE-20 / RE-25 / RE-30 / RE-35 / RE-39 - PROTEZIONE ANTIGELO QUADRO ELETTRICO
This option is necessary for very cold climates, where the external temperature can be between -10°C
and -39°C. It includes thermostat self-regulating heaters which are able to protect the electric panel from
condensation and frost, guaranteeing its correct operation. The selection of devices is carried out based
on the minimum temperatures reached at the unit installation site.
The device is installed and tested built-in.
This accessory is necessary for the correct unit operation in the FCD (FREE-COOLING) configuration with
external temperatures below –10°C. Furthermore, it is necessary for the units to be maintained correctly in all the
remaining configurations (not functioning).
This addiction element stay always switch on also when the unit is switch off as long as to keep the supply power
on.
This accessory does not lead to substantial variations in the electrical data of the unit declared in the section Electrical Data.
PM - PHASE MONITOR
The phase monitor makes it possible to check the correct connection of the phases and their imbalance in
units powered with a tri-phase system. If the connection of the phases is not correct, or the threshold of
phase imbalance is exceeded, or the voltage is too high or too low for a certain amount of time, the
monitor acts on the control circuit and orders the unit to be shut down. As soon as nominal line conditions
are restored, the unit is automatically reset. As soon as nominal line conditions are restored, the unit reset
is manual.
The device is installed and tested built-in.
PFCP - POWER FACTOR CORRECTION CAPACITORS
The component is necessary to lower the phase difference between current and voltage in the
electromagnetic components of the machine, such as asynchronous motors. By re-phasing it is possible
to reduce the intensity of the line current by reducing a part of the power of the mains (reactive power).
This often leads to an economic benefit which the energy provider grants to the final user. The component
makes it possible to bring the cosfi power factor to values which on average are greater than 0.9.
The device is installed and tested built-in.
SFSTR - BREAKAWAY CURRENT REDUCING DEVICE
I
Option also known as 'Soft starter'. Electronic device that automatically and gradually
starts the compressors reducing the start-up current of about 40% in comparison with
the nominal value. It follows that the electrical power and its protective devices can be
sized with lower parameters , so with a lower cost of initial investment.
Nominal
operating
point
The device is installed and tested built-in.
RPM
- - - CURRENT ABSORBED WITHOUT SFSTR OPTION
— CURRENT ABSORBED WITH SFSTR OPTION
ELFOEnergy LARGE2 ELECTRICAL DATA (SERIES WSAT-XEE) WITH SFSTR OPTION
SIZE
352
402
432
452
502
552
602
702
802
167
167
179
179
189
184
216
212
222
217
230
226
244
240
298
294
313
309
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value (EXCELLENCE VERSION)
M.I.C. - Value (PREMIUM VERSION)
A
A
35
BT10E005GB-02
ELFOENERGY LARGE2
®
MHP - HIGH AND LOW PRESSURE GAUGESMANOMETRI
Although the standard unit permit already to show the digital parameters of pressure of the
refrigeration circuit, this option allow the analogic measures of the refrigerant pressures on suction
and compression, giving a most easy way to check the work parameters from specialists in the field.
The two liquid pressure gauges and corresponding pressure sockets are installed on the machine in
an easily accessible location.
The device is installed and tested built-in.
SDV - SHUT-OFF VALVE ON COMPRESSOR SUCTION AND DISCHARGE
This option integrates the shut-off valve, supplied as standard. The presence of the shut-off valve
also on the inlet enables the compressors to be isolated and substituted without discharging the
refrigerant from the entire chiller circuit. Extraordinary maintenance activities are thus eased.
2
1
The device is installed and tested built-in.
1
2
3
4
Compressors
Shut-off valve
Safety valve
SDV option
4
3
CREFP - DEVICE FOR FAN CONSUMPTION REDUCTION OF THE EXTERNAL SECTION WITH VARIABLE SPEED
(PHASE-CUTTING) (ONLY EXCELLENCE VERSION)
External axial fan option. This device is installed as an alternative to the ECOBREEZE that is
standard on the EXCELLENCE version. It provides the three-phase electric motor with external
rotor and built-in thermal protection, running IP54. It is equipped with variable speed control.
The device is installed and tested built-in.
KRIX - KIT FOR REMOTE MICROPROCESSOR REMOTE CONTROL INTERFACE
This accessory permits to be install keyboard in a remote position .
It includes the compartment and the power transformer.
To be connected during commissioning of the unit at a maximum distance of 1000 m.
2 x 0.25 mm2 MAX 1000 m
Unit connection. Shielded cable .
Power input
230/1/50
The compartment must be installed on a wall using appropriate anchors. It can also be mounted on wall box universal 503 (installation by
the costumer)
The transformer is designed for DIN rail. It must be powered at 230/1/50 and electrically connected to the multifunction keypad
compartment (installation by the costumer)
Separately provided accessory
BT10E005GB-02
36
®
ELFOENERGY LARGE2
CFSC - FREE CONTACTS FOR COMPRESSOR STATE
Option to display the compressor operating status from the remote location . The
contacts are available in a special terminal block.
-+
MAX 24V 1A
CLSCLR - FREE CONTACTS FOR COMPRESSOR STATE AND FOR OPERATION IN LOCAL/REMOTE MODE
Option to display the compressor operating status
from the remote location . The contacts are available
in a special terminal block.
-+
MAX 24V 1A
The three-position selector allows the following
actions:
Sequential unit switching off that allows its next
correct restarting
Enabling to the unit starting from the built-in
multifunction keypad.
Enabling to the unit starting via serial port from
remote supervisor.
0
UNIT STATUS
SELECTOR POSITION
0
OFF
1
LOCAL ON
2
FROM SERIAL
1
2
SPC4 - SPC4 - SET POINT COMPENSATION WITH 0-10 V SIGNAL
Set-Point [°C]
The device allows variation of the set-point pre-set by
an external signal of type 0÷10 V.
14
13
12
11
10
9
8
7
6
5
0
1
2
3
4
5
6
7
8
9
10
Input [V]
SPC1 - SET POINT COMPENSATION WITH 4-20 mA
Set-Point [°C]
The device allows variation of the set-point pre-set by
an external signal of type 4÷20 mA.
14
13
12
11
10
9
8
7
6
5
4
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Input [mA]
SPC2 - SET POINT COMPENSATION WITH OUTSIDE TEMPERATURE PROBE
Set-Point [°C]
The device allows the automatic adjustment of the setpoint pre-set depending on outside air temperature. It
provides the sliding temperature of the liquid, that is
variable depending on external conditions, for the
benefit of saving energy of the system.
13
12
11
10
9
8
The device is installed and tested built-in.
7
6
12
37
14
16
18
20
22
24
26
28
30
32
34
36
Air Temperature (dry bulb) [°C]
BT10E005GB-02
ELFOENERGY LARGE2
®
SPC3 - SET POINT COMPENSATION ACCORDING TO THE OUTSIDE ENTHALPY
The device allows the automatic adjustment of the unit set-point according to the
external enthalpy.
It provides the sliding temperature of the liquid, that is variable depending on external
conditions, for the benefit of saving energy of the system.
The device is installed and tested built-in.
CMSC8 - BACnet SERIAL CONVERTER KIT
It allows serial connection of supervision systems, using BACnet or
SNMPv3.0 as the communication protocol. It allows access to the
complete list of operating variables, controls and alarms.
The device has the following communication ports:
2 serial ports configurable as RS232 or RS485 protocols available for
MODBUS and BACnet MSTP;
1 RJ45 Ethernet port for BACnet IP, SNMPv3, TCP / IP.
The device configuration is done through the integrated Web Server Linux
can be done from a PC connected to the network.
The device is installed and tested built-in.
The configuration and management of the BACnet network are by the Customer
CMSC10 - LonWorks SERIAL CONVERTER KIT
It allows serial connection of supervision systems, using LonWorks as the
communication protocol. It allows access to a list of operating variables, control and
alarms compliant with the Echelon® standard.
The device is installed and tested built-in.
The configuration and management of the LonWorks network are by the Customer
The LonWorks technology uses LonTalk® protocol for the communication between network
nodes. Contact your service provider for more information
BT10E005GB-02
38
ETHERNET
®
ELFOENERGY LARGE2
CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS
% ethylene glycol by weight
Freezing temperature
Safety temperature
Cooling capacity factor
Compressor input factor
Internal exchanger glicol solution flow factor
Pressure drop factor
°C
°C
Nr
Nr
Nr
Nr
5%
-2,0
3,0
0,995
0,997
1,003
1,029
10%
-3,9
1,0
0,990
0,993
1,010
1,060
15%
-6,5
-1,0
0,985
0,990
1,020
1,090
20%
-8,9
-4,0
0,981
0,988
1,033
1,118
25%
-11,8
-6,0
0,977
0,986
1,050
1,149
30%
-15,6
-10,0
0,974
0,984
1,072
1,182
35%
-19,0
-14,0
0,971
0,982
1,095
1,211
40%
-23,4
-19,0
0,968
0,981
1,124
1,243
The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.
FOULING CORRECTION FACTOR
INTERNAL EXCHANGER
m² °C/W
0.44 x 10^(-4)
0.88 x 10^(-4)
1.76 x 10^(-4)
F1
1,00
0,97
0,94
FK1
1,00
0,99
0,98
F1 = Cooling capacity correction factors
FK1 = Compressor power input correction factor
OVERLOAD AND CONTROL DEVICE CALIBRATION
High pressure switch
Low pressure switch
Low pressure switch (Brine)
Antifreeze protection
High pressure safety valve
Low pressure safety valve
Max n° avviamenti del compressore per ora
High compressor discharge temperature safety
thermostat
kPa
kPa
kPa
°C
kPa
kPa
Nr
OPEN
4050
450
200
3,0
-
CLOSED
3300
600
350
5,5
-
VALUE
4500
3000
10
°C
-
-
120
PLATE EXCHANGER OPERATING LIMITS
INTERNAL EXCHANGER
DPr
kPa
4500
4500
CLIVET (C)
PED (CE)
DPw
kPa
1000
1000
DPr = Maximum operating pressure on refrigerant side
DPw = Maximum operating pressure on water side
39
BT10E005GB-02
ELFOENERGY LARGE2
®
OPTION COMPATIBILITY - WSAT-XEE SERIE / EXCELLENCE VERSION
REF.
DESCRIPTION
352
402
432
452
502
552
602
702
802
CONFIGURATION AND MAIN OPTIONS
B
Water lo w temperature
o
o
o
o
o
o
o
o
o
D
P artial energy reco very
o
o
o
o
o
o
o
o
o
R
To tal energy reco very
o
o
o
o
o
o
o
o
o
FCD
Direct FREE-COOLING
o
o
o
o
o
o
o
o
o
B+D
Water lo w temperature + P artial energy reco very
o
o
o
o
o
o
o
o
o
B+R
Water lo w temperature + To tal energy reco very
o
o
o
o
o
o
o
o
o
B + FCD
Water lo w temperature + Direct FREE-COOLING
x
x
x
x
x
x
x
x
x
D + FCD
P artial energy reco very + Direct FREE-COOLING
o
o
o
o
o
o
o
o
o
R + FCD
To tal energy reco very + Direct FREE-COOLING
x
x
x
x
x
x
x
x
x
A300
300 l. sto rage tank
o
o
o
o
o
o
o
x
x
A500
500 l. sto rage tank
x
x
x
x
x
x
x
o
o
1PUS - Standard pum p
(PU1)
P ump type 1
o
o
o
x
x
x
x
x
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
x
x
x
x
(PU4) / (PU5) / (PU6) P ump type 4 / P ump type 5 / P ump type 6
o
o
o
o
o
o
o
o
o
+D
+ P artial energy reco very
o
o
o
o
o
o
o
o
o
+ D + A300
+ P artial energy reco very + 300 l. sto rage tank
o
o
o
o
o
o
o
x
x
+ D + A500
+ P artial energy reco very + 500 l. sto rage tank
x
x
x
x
x
x
x
o
o
+ A300RPS (PU1)
+ 300 l. sto rage tank with primary circuit o nbo ard
o
o
o
x
x
x
x
x
x
+ A300RPS (PU4)
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
o
o
o
o
x
x
+ A500RPS (PU4)
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
o
o
1PU1SB - Standard pum p w ith standby pum p
(PU1)
P ump type 1
o
o
o
x
x
x
x
x
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
x
x
x
x
(PU4) / (PU5) / (PU6) P ump type 4 / P ump type 5 / P ump type 6
o
o
o
o
o
o
o
o
o
+D
+ P artial energy reco very
o
o
o
o
o
o
o
o
o
+ D + A300
+ P artial energy reco very + 300 l. sto rage tank
o
o
o
o
o
o
o
x
x
+ D + A500
+ P artial energy reco very + 500 l. sto rage tank
x
x
x
x
x
x
x
o
o
+ A300RPS (PU1)
+ 300 l. sto rage tank with primary circuit o nbo ard
o
o
o
x
x
x
x
x
x
+ A300RPS (PU4)
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
o
o
o
o
x
x
+ A500RPS (PU4)
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
o
o
2PM - Hydropack w ith 2 pum ps
(PU1)
P ump type 1
o
o
o
o
o
o
o
o
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
o
o
o
o
(PU4)
P ump type 4
x
x
x
x
x
x
x
x
x
(PU5) / (PU6)
P ump type 5 / P ump type 6
x
x
x
x
x
x
o
o
o
+ A300RPS
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
x
x
+ A500RPS
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
x
x
CREFB
Device fo r reducing co nsumptio n ECOB REEZE o f the o utdo o r
sectio n variable speed fans
•
•
•
•
•
•
•
•
•
CREFP
Device fo r reducing co nsumptio n o f the o utdo o r sectio n variable
speed fans (phase-cut)
o
o
o
o
o
o
o
o
o
FCD + CCCA
Direct FREE-COOLING + Co pper / aluminium co ndenser co il with
acrylic lining
o
o
o
o
o
o
o
o
o
FCD + CCCA1
Direct FREE-COOLING + Co pper / aluminium co ndenser co il with Finguard treatment
x
x
x
x
x
x
x
x
x
FCD + CCCC
Direct FREE-COOLING + Co pper /co pper co ndenser co il
x
x
x
x
x
x
x
x
x
ACCESSORIES
Standard
o
Option
X
Not available
BT10E005GB-02
40
®
ELFOENERGY LARGE2
OPTION COMPATIBILITY - WSAT-XEE SERIE / PREMIUM VERSION
REF.
DESCRIPTION
352
402
432
452
502
552
602
702
802
CONFIGURATION AND MAIN OPTIONS
B
Water lo w temperature
o
o
o
o
o
o
o
o
o
D
P artial energy reco very
o
o
o
o
o
o
o
o
o
R
To tal energy reco very
o
o
o
o
o
o
o
o
o
FCD
Direct FREE-COOLING
o
X
o
X
Xo
Xo
Xo
Xo
Xo
Xo
o
X
B+D
Water lo w temperature + P artial energy reco very
o
o
o
o
o
o
o
o
o
B+R
Water lo w temperature + To tal energy reco very
o
o
o
o
o
o
o
o
o
B + FCD
Water lo w temperature + Direct FREE-COOLING
x
x
x
x
x
x
x
x
x
D + FCD
P artial energy reco very + Direct FREE-COOLING
o
o
o
o
o
o
o
o
o
R + FCD
To tal energy reco very + Direct FREE-COOLING
x
x
x
x
x
x
x
x
x
A300
300 l. sto rage tank
o
o
o
o
o
o
o
x
x
A500
500 l. sto rage tank
x
x
x
x
x
x
x
o
o
1PUS - Standard pum p
(PU1)
P ump type 1
o
o
o
x
x
x
x
x
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
x
x
x
x
(PU4) / (PU5) / (PU6) P ump type 4 / P ump type 5 / P ump type 6
o
o
o
o
o
o
o
o
o
+D
+ P artial energy reco very
o
o
o
o
o
o
o
o
o
+ D + A300
+ P artial energy reco very + 300 l. sto rage tank
o
o
o
o
o
o
o
x
x
+ D + A500
+ P artial energy reco very + 500 l. sto rage tank
x
x
x
x
x
x
x
o
o
+ A300RPS (PU1)
+ 300 l. sto rage tank with primary circuit o nbo ard
o
o
o
x
x
x
x
x
x
+ A300RPS (PU4)
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
o
o
o
o
x
x
+ A500RPS (PU4)
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
o
o
1PU1SB - Standard pum p w ith standby pum p
(PU1)
P ump type 1
o
o
o
x
x
x
x
x
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
x
x
x
x
(PU4) / (PU5) / (PU6) P ump type 4 / P ump type 5 / P ump type 6
o
o
o
o
o
o
o
o
o
+D
+ P artial energy reco very
o
o
o
o
o
o
o
o
o
+ D + A300
+ P artial energy reco very + 300 l. sto rage tank
o
o
o
o
o
o
o
x
x
+ D + A500
+ P artial energy reco very + 500 l. sto rage tank
x
x
x
x
x
x
x
o
o
+ A300RPS (PU1)
+ 300 l. sto rage tank with primary circuit o nbo ard
o
o
o
x
x
x
x
x
x
+ A300RPS (PU4)
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
o
o
o
o
x
x
+ A500RPS (PU4)
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
o
o
2PM - Hydropack w ith 2 pum ps
(PU1)
P ump type 1
o
o
o
o
o
o
o
o
x
(PU2) / (PU3)
P ump type 2 / P ump type 3
o
o
o
o
o
o
o
o
o
(PU4)
P ump type 4
x
x
x
x
x
x
x
x
x
(PU5) / (PU6)
P ump type 5 / P ump type 6
x
x
x
x
x
x
o
o
o
+ A300RPS
+ 300 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
x
x
+ A500RPS
+ 500 l. sto rage tank with primary circuit o nbo ard
x
x
x
x
x
x
x
x
x
CREFB
Device fo r reducing co nsumptio n ECOB REEZE o f the o utdo o r
sectio n variable speed fans
x
x
x
x
x
x
x
x
x
CREFP
Device fo r reducing co nsumptio n o f the o utdo o r sectio n variable
speed fans (phase-cut)
•
•
•
•
•
•
•
•
•
ACCESSORIES
Standard
o
Option
X
Not available
41
BT10E005GB-02
ELFOENERGY LARGE2
®
DIMENSIONAL: WSAT-XEE 352-402-432 - EXCELLENCE VERSION
(Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
2
5
1
4
8
4
3
40
160
1805
7
329
321 369.5
9
6
OD
1097
3
548
3075
40
2575
250
W2
W1
(12)
1000
30
1350
(11)
250
W4
M
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
EXC - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
EXC - EN
352
402
432
352
402
432
1933
1142
579
518
76,1
3075
1097
1805
149
325
161
261
896
889
1946
1129
581
516
76,1
3075
1097
1805
153
342
165
272
933
925
2011
1064
590
507
76,1
3075
1097
1805
156
396
168
304
1024
1015
1933
1142
579
518
76,1
3075
1097
1805
149
325
161
261
896
889
1946
1129
581
516
76,1
3075
1097
1805
153
342
165
272
933
925
2011
1064
590
507
76,1
3075
1097
1805
156
396
168
304
1024
1015
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
BT10E005GB-02
42
30
W3
(10)
700
(11)
1350
O
1037
P
G
549
®
ELFOENERGY LARGE2
DIMENSIONAL: WSAT-XEE 452-502-552-602 - EXCELLENCE VERSION
(Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
2
5
1
7
1097
8
4
3
3
40
4
4
4
160
1805
7
321 369.5
9
329.5
6
OD
3
548
4025
40
1762.5
1762.5
250
W1
W3
W2
(12)
1000
30
1350
(11)
250
549
W6
M
30
W5
W4
(10)
700
(11)
1350
O
1037
P
G
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
EXC - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
W5
W6
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
kg
kg
EXC - EN
452
502
552
602
452
502
552
602
2553
1472
564
533
76,1
4025
1097
1805
80
254
287
85
253
247
1207
1198
2576
1449
565
532
76,1
4025
1097
1805
80
257
301
85
255
258
1234
1224
2574
1451
565
532
76,1
4025
1097
1805
82
261
306
87
259
262
1256
1246
2590
1435
566
531
76,1
4025
1097
1805
84
267
323
89
265
275
1302
1290
2553
1472
564
533
76,1
4025
1097
1805
80
254
287
85
253
247
1207
1198
2576
1449
565
532
76,1
4025
1097
1805
80
257
301
85
255
258
1234
1224
2574
1451
565
532
76,1
4025
1097
1805
82
261
306
87
259
262
1256
1246
2590
1435
566
531
76,1
4025
1097
1805
84
267
323
89
265
275
1302
1290
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
43
BT10E005GB-02
ELFOENERGY LARGE2
®
DIMENSIONAL: WSAT-XEE 702-802 - EXCELLENCE VERSION
(Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
2
5
1
4
4
3
40
8
3
548
5025
2262.5
2262.5
250
(11)
250
1000
30
1350
(12)
W3
W2
W1
30
1097
159
4
329
(11)
1350
1805
4
7
O
1037
P
G
W4
(10)
700
W6
W5
M
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
EXC - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
W5
W6
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
kg
kg
EXC - EN
702
802
702
802
3216
1809
564
533
76,1
5025
1097
1805
114
284
374
108
306
312
1497
1483
3227
1798
565
532
76,1
5025
1097
1805
115
292
389
109
315
323
1544
1527
3216
1809
564
533
76,1
5025
1097
1805
114
284
374
108
306
312
1497
1483
3227
1798
565
532
76,1
5025
1097
1805
115
292
389
109
315
323
1544
1527
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
BT10E005GB-02
44
320 369.5
9
6
OD
3
40
7
547
®
ELFOENERGY LARGE2
DIMENSIONAL: WSAT-XEE 352-402-432-452-502-552 - PREMIUM VERSION
1805 (Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
40
2
5
6
329
160
7
1
321 369.5
9
OD
8
4
1097
4
3
3
40
548
2710
2210
250
(12)
1000
W2
W1
30
1350
(11)
250
549
W3
W4
M
30
(10)
700
(11)
1350
O
1037
P
G
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
PRM - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
PRM - EN
352
402
432
452
502
552
352
402
432
452
502
552
1637
1073
584
513
76,1
2710
1097
1805
138
277
152
211
778
773
1658
1052
587
510
76,1
2710
1097
1805
138
291
153
219
802
796
1724
986
596
501
76,1
2710
1097
1805
141
344
155
250
892
885
1699
1011
594
503
76,1
2710
1097
1805
152
350
166
256
924
917
1704
1006
596
501
76,1
2710
1097
1805
158
367
172
267
963
955
1714
996
596
501
76,1
2710
1097
1805
159
377
173
274
984
975
1637
1073
584
513
76,1
2710
1097
1805
138
277
152
211
778
773
1658
1052
587
510
76,1
2710
1097
1805
138
291
153
219
802
796
1724
986
596
501
76,1
2710
1097
1805
141
344
155
250
892
885
1699
1011
594
503
76,1
2710
1097
1805
152
350
166
256
924
917
1704
1006
596
501
76,1
2710
1097
1805
158
367
172
267
963
955
1714
996
596
501
76,1
2710
1097
1805
159
377
173
274
984
975
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
45
BT10E005GB-02
ELFOENERGY LARGE2
®
DIMENSIONAL: WSAT-XEE 602 - PREMIUM VERSION
(Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
2
5
1
4
8
4
3
40
160
1805
7
329
321 369.5
9
6
OD
1097
3
548
3075
40
2575
250
W2
W1
(12)
1000
30
1350
(11)
250
W3
W4
M
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
PRM - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
W5
W6
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
kg
kg
PRM - EN
602
602
2052
1023
595
502
76,1
3075
1097
1805
157
434
169
326
0
0
1087
1077
2052
1023
595
502
76,1
3075
1097
1805
157
434
169
326
0
0
1087
1077
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
BT10E005GB-02
46
30
(10)
700
(11)
1350
O
1037
P
G
549
®
ELFOENERGY LARGE2
DIMENSIONAL: WSAT-XEE 702-802 - PREMIUM VERSION
(Ecobreeze + 30mm)
ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)
2
5
1
7
1097
8
4
3
3
40
4
4
4
160
1805
7
3
548
4025
40
1762.5
1762.5
549
250
W1
W3
W2
(12)
1000
30
1350
(11)
250
321 369.5
9
329.5
6
OD
W6
M
30
W5
W4
(10)
700
(11)
1350
O
1037
P
G
N
(1) INTERNAL EXCHANGER (EVAPORATOR)
(2) EXTERNAL EXCHANGER (CONDENSER)
(3) HOLE TO HANG UNIT
(4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT)
(5) ELECTRICAL PANEL
(6) POWER INPUT
(7) SOUNDPROOFED CABIN
(8) INTERNAL EXCHANGER WATER OUTLET
(9) INTERNAL EXCHANGER WATER INLET
(10) MINIMUM DIMENSION FOR A SAFE PASSAGE.
(11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL.
(12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE.
(G) BARYCENTRE
PRM - SC
SIZE
M
N
O
P
OD
Length
Depth
Height
W1
W2
W3
W4
W5
W6
Operating weight
Shipping weight
mm
mm
mm
mm
mm
mm
mm
mm
kg
kg
kg
kg
kg
kg
kg
kg
PRM - EN
702
802
702
802
2626
1399
567
530
76,1
4025
1097
1805
79
260
332
84
258
282
1295
1283
2643
1382
567
530
76,1
4025
1097
1805
79
264
344
84
262
292
1324
1310
2626
1399
567
530
76,1
4025
1097
1805
79
260
332
84
258
282
1295
1283
2643
1382
567
530
76,1
4025
1097
1805
79
264
344
84
262
292
1324
1310
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
47
BT10E005GB-02
The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice.
All reproduction, even partial, is prohibited. © Copyright - CLIVET S.p.A. - Feltre (BL) - Italy
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy
Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET UK LTD
4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom
Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - info@clivet-uk.co.uk
CLIVET SAS
ZAC des Godets 1, Impasse de la Noisette, Hall A6 - 91370 Verrières le Buisson - France
Tel. + 33 (0)1 69202575 - Fax + 33 (0)1 69206076 -info.fr@clivet.com
CLIVET ESPAÑA S.A.
Parque Empresarial Villapark, Avda. Quitapesares 50 - 28670, Villaviciosa de Odón, Madrid - España
Tel. + 34 91 6658280 - Fax + 34 91 6657806 - info@clivet.es
CLIVET GmbH
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany
Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET NEDERLAND B.V.
Siliciumweg 20a, 3812 SX Amersfoort - Netherlands
Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - info@clivet.nl
CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia
Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZC
Rep Office: PO Box 28178 - Light industrial unit #10 -Dubai Silicon Oasis - Dubai,UAE
Tel. + 97 14 3208499 - Fax + 97 14 3208216 - info@clivetme.com
CLIVET AIRCONDITIONING SYSTEMS (P) LTD
3C3, Gundecha Onclave,
Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA)
Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - sales.india@clivet.com
www.clivet.com
Download