LABORATORY 2 Electrical Power and Power Factor Correction OBJECTIVES 1. 2. 3. 4. Study complex power in single-phase AC system and understand power triangles. Measure the phase angle and the power factor of an inductive load. Study the requirements for power factor correction and understand the concept. Perform power factor correction and verify the results using MicroCap circuit simulation and laboratory measurements. INFORMATION 1. Power factor definitions The instantaneous power delivered to a load can be expressed as p(t) = v(t) . i(t) (Equation 2.1) The instantaneous power may be positive or negative depending upon the sign of v(t) and i(t), which is related to the sign of the signal at a given time. A positive value means that power flows from the supply to the load, and a negative value indicates that power flows from the load to the supply. In the case of sine wave voltage and current, the instantaneous power may be expressed as the sum of two sinusoids, or as the sum of two sinusoids with twice the frequency as shown in the following equations. v(t) = Vm cos (t) i(t) = Im cos (t + ) p(t) = Vm Im cos () + Vm Im cos (2t+ ) p(t) = Vm Im cos . (1+ cos2t) + Vm Im sin cos (2t+ ) (Equation 2.2) In the previous power equation, the first term on the right-hand side is known as real power or active power and is measured in watts (W) P= Vm Im cos () (Equation 2.3) The second term on the right-hand side is called instantaneous reactive power, and its average value is zero. The maximum value of the second term is known as the reactive power, and it is measured in volt-ampere reactive (VAR) Q = Vm Im sin ( 2-1 (Equation 2.4) The apparent power (S) is measured in volt-ampere (VA) and can be calculated from P and Q as S = Vm Im = P2 Q2 (Equation 2.5) Complex power in AC circuits can be given as S = P jQ = Vm Im cos () + j Vm Im sin () (Equation 2.6) Here S indicates a complex number. The real part of the complex power is equal to the active power (P) and the imaginary part is the reactive power (Q). The cosine of the phase angle () between the voltage and the current is called the power factor pf. P P pf cos (Equation 2.7) S Vrms I rms Hence, from the previous expressions, the equations associated with the active, reactive and apparent power can be developed geometrically on a right triangle called a power triangle. A power triangle using phasors is illustrated in Figure 2.1. In the phasor graph, the horizontal axis represents the active power P and the vertical axis represents the reactive power Q. The phasor graph also displays the complex power S. In this case the reactive power QL is positive, since it’s caused by the inductive type of load and the power factor is lagging. S QL P Figure 2.1. Power triangle 2. Power Factor Correction Power Factor Correction attempts to improve the power factor by the addition of capacitor(s) in parallel with the load. These capacitors supply some or all of the reactive power to the inductive load, which reduces the reactive power and therefore the current that the power supply delivers. The capacitors are source of the reactive power QC , which is leading or negative– Figure 2.2. A resulting reactive power QL-QC < QL which provides a smaller lagging angle and larger Power factor cos(), compared to the circuit before power factor correction in Figure 2.1. The complete compensation of the lagging effect of the inductive load XL could be achieved by adding more capacitance XC to the circuit, until QL- QC =0 and the power factor cos() =1, as it is shown in Figure 2.3. 2-2 S S QL P QC QL P Q C Figure 2.2. Power factor correction Figure 2.3. Complete Power factor compensation Following Equations are useful in determining Power Factor corrections: Impedance of the inductor: X L L 2fL Impedance of the capacitor: XC 1 1 C 2fC (Equation 2.9) XL R (Equation 2.10) tan 1 Inductive Reactive Power Z RT X L V I S Z QL I 2 X L Capacitive Reactive Power QC Total impedance of the circuit: Total current from the source: (Equation 2.8) 2 2 (Equation 2.11) (Equation 2.12) (Equation 2.13) 2 VS XC (Equation 2.14) Equipment 1. PROTO-BOARD PB-503 (breadboard). 2. Function generator Wavetek FG3B.0 3. Digital Oscilloscope Tektronix TDS-210. 4. Resistors: 150, 22. 5. Capacitors: 10nF, 22nF, 47nF. 6. Inductor 3.3mH/ 6 PRE-LABORATORY PREPARATION 1. Power Factor calculations of the inductive load The circuit of Figure 2.4 represents a model of a power system. The load impedance ZL is build of the inductor L1 3.3mH and resistor R1 150 . Resistor R2 represents simplified transmission 2-3 line with a neglectable inductance. Hence, the voltage across the resistor R2 is proportional to the current trough the ZL, with the phase preserved. For the circuit shown in Figure 2.4 consider VS =10Vp-p and f=10kHz. Figure 2.4 Figure 2.5 1.1. Use phasor analysis methods to find VL and IL. Find the total complex power Stot provided by the source VS and the power absorbed by the "load" SL. Remember to use rms values for these calculations. All phase angles should be referenced to VS. Show your calculations in section 1.1 of the LMS. 1.2. Using Equations 2.8 to 2.14, calculate the following parameters of the circuit in section 1.2 of the LMS and enter the results in Table 2.1 of the LMS: load impedance ZL load power factor angle load power factor cos complex power absorbed by the load expected time shift between load voltage and current in msec. Note: Take in consideration the internal resistance of the inductor of 6. 1.3. Draw the Power triangle of this circuit in section 1.5-a of the LMS. 1.4. Calculate the value of the parallel capacitance C1 as it is shown in Figure 2.5, in order to correct the load pf to unity. Show your calculations in section 2 of the LMS. 1.5. Enter the calculated data in Table 2.2 for future comparison with the MicroCap simulations and the experimental results. 2. MicroCap simulations: 2.1. Simulate the circuit in Figure 2.4 in MicroCap using sinusoidal voltage source Vs= 10Vp-p and f=10kHz. Run Transient Analysis and apply the technique from Lab #1 to measure the time difference and calculate the power factor angle Calculate the load power factor cos 2.2. Enter the calculated data in Table2.1 for comparison with the Pre-Lab calculations and the experimental results. 2.3. Modify the circuit by adding the power factor correction capacitor C1, calculated theoretically, and run the Transient Analysis again. 2.4. Determine load power factor angle calculate the load power factor cos for this compensated circuit and record the results in Table 2.2 2-4 PROCEDURE 1. Power Factor Analysis 1.1. Build the circuit in Figure 2.6 on the Breadboard. 1.2. Connect the CH1 of the oscilloscope to measure the input voltage VS and the CH2 to measure the output signal at resistor R2, as it is shown in Figure 2.6. 1.3. Set the input signal Vs to 10 Vp-p, and use oscilloscope vertical cursors to measure the amplitudes and the time difference between the input voltage Vs and output voltage Vo. Calculate the sift angle [deg]. Record the measured values in Table 2.1 of your LMS. Calculate the power factor cos for this circuit. 1.4. Compare the simulated and measured data and make a comment in section 1.3 of the LMS. Figure 2.6. Inductive load power factor measurement Note: Do not turn the power on before your circuit has been checked by your TA! When the layout has been completed, have your TA to check your circuit connections and get his/her signature in your log book. 1.5. Use the VL and IL data collected in part 1 to compute the complex power Stot and SL in section 1.4 of the LMS. Compare these results with the complex power calculated in Pre-lab. From your measurements, determine the average power P and the reactive power Q delivered to the load. Use the values of P and Q computed from the measurements to compute the power factor from pf = P/|S|. Indicate whether the load power factor is leading or lagging. 1.6. Draw the Power triangle of this circuit based on your measurements results and calculations in section 1.5-b of the LMS. 1.7. Complete the Part 1 of the experiment by answering the question in section 1.6 of the LMS. 2. Power Factor Correction 2.1. Modify the circuit built in part 1 of this experiment by connecting C1=10nF in parallel with the load, as it is shown in Figure 2.7. Figure 2.7. Power factor correction experiment 2-5 2.2. Connect the CH1 of the oscilloscope to measure the input voltage VS and the CH2 to measure the output signal Vo at resistor R2, as it is shown in Figure 2.7. 2.3. Set the input signal Vs to 10 Vp-p, measure the time difference between the input and output voltages Vo and calculate the sift angle [deg]. Calculate the power factor cos for this circuit. Record the measured values in Table 2.2 of your LMS. 2.4. Replace the capacitor C1 =10nF with a capacitor C2=22nF and repeat the same measurements. Calculate the power factor cos for this circuit. Record the measured values in Table 2.2 of your LMS 2.5. Replace the capacitor C2 =22nF with a capacitor C3=47nF and repeat the same measurements. Calculate the power factor cos for this circuit. Record the measured values in Table 2.2 of your LMS. 2.8. Use the VL and IL data collected in part 2 to compute the complex power Stot and SL. Compare these results with the complex power calculated in Pre-lab. From your measurements, determine the average power P and the reactive power Q delivered to the load. Use the values of P and Q computed from the measurements to compute the power factor from pf = P/|S|. Indicate whether the load power factor is leading or lagging. 2-6 LAB MEASUREMENTS SHEET – LAB #2 Name _________________________ Student No_____________________ Workbench No_____ 1. Power Factor calculations of the inductive load 1.1. Phasor analysis- measured complex power Stot and SL 1.2. Circuit parameters calculations based on Lab measurements 2-7 Table 2.1. Calculated values* MicroCap* Measured values Vs Vo us] T T 360 0 cos 1.3. How close the calculated, experimental and simulated results are and what could cause the discrepancy. _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ 1.4 Calculate the measured complex power Stot and SL 2-8 1.5-a.*Calculated Power Triangle diagram 1.5-b. Measured Power Triangle diagram 1.6. Compare measured to the estimated power triangle and comment on differences. _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ _____________________________________________________________________________ 2. Power factor correction calculations. Table 2.2. 2-9 Calculated values* MicroCap* C1 Measured values 10nF 22nF 47nF Vs Vo T T 360 0 cos 3. Discussion: Interpret and analyze your observations and calculations. Discuss the trends you see in the data. ________________________________________________________________________ ________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ____________________________________________________________________ 2-10 SIGNATURE AND MARKING TABLE – LAB #2 TA Name:___________________ Check Task boxes Max. Granted TA Marks Marks Signature Pre-lab completed 50 Power factor measurements 20 Power factor corrections 20 Overall Report Preparation 10 TOTAL MARKS 100 2-11