Memorial Hermann Best Practices July, 2013 PLUMBING

advertisement
Memorial Hermann Best Practices
July, 2013
SECTION 22 40 00 PLUMBING FIXTURES
PART 1 - GENERAL
1.01
WORK INCLUDED
A.
Comply with provisions of Section 22 05 00.
B.
Provide plumbing fixtures, trim and related items such as supplies, traps, drains, cleanouts, water
closet flanges, bolts, seats and covers, fixture supports and other accessory items.
C.
Coordinate fixture requirements by reviewing architectural, structural, and equipment drawings.
Install fixtures in accordance with Contract Drawings and manufacturer's rough-in drawings.
1.02
RELATED WORK
A.
Section 22 05 23: Valves for Plumbing Piping
B.
Section 22 11 16: Domestic Water Piping
C.
Section 22 13 19: Sanitary Waste Piping Specialties
1.03
CODES AND STANDARDS
A.
Perform work in accordance with applicable codes and standards enforced by local authorities.
B.
All barrier free fixtures shall be installed in accordance with the Americans with Disabilities Act
(ADA) Rules and Regulations and Texas Department of Licensing Regulations (TDLR), Texas
Accessibility Standards (TAS) regulations.
1.04
A.
SUBMITTALS
Submit manufacturer's product data for review.
PART 2 - PRODUCTS
2.01
ACCEPTABLE MANUFACTURERS
A.
Fixtures: Kohler, American Standard.
B.
Brass Trim: McGuire Engineered Brass Company, Brasscraft, Cambridge Brass.
C.
Roof drains, hydrant, floor drains, carriers and p-traps: Jay R. Smith, Zurn, Wade, Josam, Mi-Fab.
D.
Flush valves: Sloan Royal with low force handles for ADA compliance.
E.
Toilet seats: Olshite, Beneke, Bemis, Church, Zurn.
F.
Faucets: T&S Brass, Chicago Faucet Company, Zurn.
G.
Stainless steel sinks: Elkay, Just.
H.
Shower valves (thermostatic and/or pressure balancing type): Symmons, Leonard, Powers,
Lawler.
I.
Shower stalls: Aqua Bath, Aquarius.
PLUMBING FIXTURES
22 40 00 - Page 1
Memorial Hermann Best Practices
July, 2013
J.
Combination fixture water closet/lavatory: Acorn, Bradley, Willougby.
K.
Flow control devices: Dole Flow Controls Company.
L.
Provide fixtures and trim as a complete unit as required in the individual "P" numbers listed
below.
M.
Pre-fabricated insulation on water lines and p-trap under barrier free lavatories and sinks: Brocar
Products, Inc. Trap Wrap TrueBro, Inc. Handi Lav-Guard McGuire Pro-wrap.
N.
Showers and tubs: Provide non-slip walking surface.
O.
Shower heads, faucets and flush valves shall meet code and state requirements for water
conservation on low consumption fixtures.
P.
Waterproofing floor drains above slab on grade.
1.
Floor drains and/or non prefabricated showers shall have Chloraloy 240 brand nonplaticized chlorinated polyethylene concealed water proofing membrane .040 inch thick.
Install in accordance with manufacturers recommendations and coordinate with structural
construction drawings. Waterproofing membrane shall extend minimum 36" in diameter
from floor drain.
Q.
Thermostatic mixing valves: Symmons, Holby, Lawler, Powers, Leonard.
R.
Emergency equipment: Encon, Haws, and Guardian.
S.
Garbage Disposals: In-sinkerator and Whirlaway.
T.
Electric water coolers: Elkay, Haws, Halsey, Taylor, and Sunroc.
2.02
MATERIALS
A.
Wall hung lavatories: Furnish complete with floor mounted carriers.
B.
Under countertop sinks: Furnished complete with mounting rings where required.
C.
Fixture color: White unless specified otherwise.
D.
Faucets and flush valves: Provide either integral or attached supply stops with nipples.
E.
Flashing clamping device: Provide for drains installed in slabs above grade.
F.
Trap primer: Provide connections for floor drain as shown on drawings.
G.
Caulking: General Electric silicon sanitary sealant or equal to match fixture color.
H.
Provide floor mounted carrier for wall hung lavatories.
I.
Provide metal backing at wall fixtures and fixture trim connections so piping and connecting
faucets and valves are rigid to wall.
J.
Provide shower and floor drain water proofing membrane for non-prefabricated shower and floor
drains located above slab on grade.
PLUMBING FIXTURES
22 40 00 - Page 2
Memorial Hermann Best Practices
July, 2013
K.
Wrist blade operation:
1.
Pull wrist blade to operator to turn on.
2.
Push toward splashback to turn off faucet.
L.
All fixtures and fittings relating to drinking water shall meet the requirements of ANSI/NSF 61,
Section 9. Any faucet for drinking water shall be certified by U.L. to the ANSI/NSF 61, Section 9
standards.
M.
Emergency shower and eye/face wash stations shall be installed in compliance with ANSI
Z358.1.
2.03
PLUMBING FIXTURES
P-1 WATER CLOSET - WALL HUNG PATIENT
a.
Fixture: Kohler #K-4330-L Kingston lite, wall hung closet with integral bed pan lugs, 1.6
gallon flush.
b.
Seat: Church #9500C white open front seat with check hinge.
c.
Valve: Sloan Royal #BPW-1150-1.6-ADA-YBYC flush valve offset for grab bar with bed
pan washer, mount split ring 27" above top of fixture.
d.
Carrier: Jay R. Smith #230 or #210 fixture carrier.
e.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
P-2 WATER CLOSET - WALL HUNG - PUBLIC
a.
Fixture: Kohler #K-4330 Kingston lite toilet wall hung closet, 1.6 gallon flush.
b.
Seat: Church #9500C white open front seat with check hinge
c.
Valve: Sloan Royal #111YBYC, 1.28 gallon per flush, flush valve.
d.
Carrier: Jay R. Smith #230 fixture carrier.
5.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
P-5 COMBINATION FIXTURE WATER CLOSET/LAVATORY
a.
Fixture: Acorn #4010R/L-VF-N4 back outlet; Bradley PC-710 R/L-FP; Acorn #4015R/LVF-N4 bottom outlet.
b.
Valve: Flush valve and pedal valve controls provided with unit.
c.
Trim: Supplies, trap, basket strainer, toilet seat furnished with unit, and concealed bed
pan washer.
4.
Mounting: Coordinate installation with Architectural Drawings.
P-7 URINAL - WALL HUNG BARRIER-FREE
a.
Fixture: Kohler #K-5016-ET dexter urinal siphon jet.
b.
Valve: Sloan Royal #186-1, 1.0 GPM per flush.
c.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
P-8 LAVATORY - WALL HUNG - PATIENT
a.
Fixture: Kohler #K-2006 Kingston Lavatory, with 8" centers.
b.
Faucet: Chicago Faucet #786-GN2-FC
c.
Trim: McGuire #155A grid drain with 1-1/4" tailpiece, #8872 1-1/4" P-trap, #H-2165
supply stops.
d.
Mounting: 31" A.F.F. to basin rim.
P-9 LAVATORY - WALL HUNG - PUBLIC
a.
Fixture: Kohler #K-2006 Kingston Lavatory, with 8" centers.
b.
Faucet: Chicago Faucet #786-GN2-FC.
c.
Trim: McGuire #155A grid drain with 1-1/4" tailpiece, #8872 1-1/4" P-trap, #H-2165
supply stops.
d.
Mounting: 31" A.F.F. to basin rim.
PLUMBING FIXTURES
22 40 00 - Page 3
Memorial Hermann Best Practices
July, 2013
P-10 LAVATORY - UNDER COUNTER - PATIENT
a.
Fixture: Kohler #2211-4-19"x15".
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McQuire #155A with 1-1/4" tailpiece, #8872 - 1-1/4" P-trap, #H-2165 supply stops.
P-11 LAVATORY - WALL HUNG - PHOTO SENSOR OPERATED
a.
Fixture: Kohler #K2007 Kingston lavatory, modified to have center faucet hole only 582123-CP
b.
Faucet: Chicago #652-8-123-CP-FC sensor activated gooseneck faucet, with built-in
mixing valve adjusted from top of deck plate, battery powered.
c.
Trim: McGuire #155A grid drain with 1-1/4" tailpiece, #8872 - 1-1/4" P-trap, #H-2165
supply stops.
d.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
P-12 LAVATORY - WALL HUNG - KITCHEN
a.
Fixture: Kohler #K-2031 Greenwich Lavatory, with one center faucet hole.
b.
Faucet: Chicago Faucet #626-CP, with #834-EPCP double pedal valve.
c.
Trim: McGuire #155A grid drain with 1-1/4" tailpiece #H-165LK-HCA-SPL supply to
gooseneck, #8872 - 1-1/4" P-trap.
d.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
P-13 LAVATORY - WALL HUNG - BARRIER-FREE PUBLIC
a.
Fixture: Kohler #K-2006 Kingston lavatory, with 8" centers.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #155 WC grid drain with 1-1/4" tailpiece, off set for wheelchair use. #8872
- 1-1/4" P-trap. #H-2165 supply stops.
d.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
e.
Pre-fabricated insulation on water lines and p-trap under barrier free lavatories and sinks:
Brocar Products, Inc. Inc. Trap Wrap TrueBro, Inc. Handi Lav-Guard McGuire Pro-wrap.
P-14 LAVATORY - UNDER COUNTER - PUBLIC
a.
Fixture: Kohler #2211-4-19"x15".
b.
Faucet: Chicago #786-GN2-FCCP
c.
Trim: McGuire #155A drain grid with 1-1/4" tailpiece, #8872 - 1-1/4" P-trap, #H-2165
supply stops.
P-16 LAVATORY - WALL HUNG - BARRIER-FREE - PATIENT
a.
Fixture: Kohler #K-2006 Kingston lavatory with 8" centers.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #155WC grid drain with 1-1/4" tailpiece, offset for wheelchair use. #8872
1-1/4" P-traps, #H-2165 supply stops.
d.
Mounting: Refer to Architectural Drawings for elevation mounting requirements.
e.
Pre-fabricated insulation on water lines and p-trap under barrier free lavatories and sinks:
Brocar Products, Inc. Inc. Trap Wrap TrueBro, Inc. Handi Lav-Guard McGuire Pro-wrap.
P-18 SINK - S.S. - INTERCEPTOR (STAFF)
a.
Fixture: Just #SLX-2019-A-GR-(14"x16"x10-1/2") 18 gauge stainless steel, self-rimming,
single compartment.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #151, with 1-1/2" tailpiece, #H2165 supply stops, Jay R. Smith #8730 - 11/2" interceptor installed with unions.
d.
Mounting: Install interceptor at side for easy access and cleaning. If piping to and from
interceptor shall be 17 gauge chrome plated.
PLUMBING FIXTURES
22 40 00 - Page 4
Memorial Hermann Best Practices
July, 2013
P-19 SINK - S.S. (STAFF)
a.
Fixture: Just #SLX-2225-A-GR (16"x22"x10-1/2"), 18 gauge stainless steel self-rimming,
single compartment.
b.
Fixture: Just SLX-2019-A-GR (14"x16"x10-1/2")
c.
Faucet: Chicago Faucet #786-GN2-FCCP
d.
Trim: McGuire #151 drain with 1-1/2" tailpiece, #8912 - 1-1/2" P-trap, #H-2165 supply
stops.
P-20 SINK - S.S. (STAFF)
a.
Fixture: Just #SLX-2019-A-GR (14"x16"x10-1/2") 18 gauge stainless steel, self-rimming,
single compartment.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece. #8912 - 1-1/2" P-trap, #H-2165 supply
stops.
P-20A SINK - SS (STAFF) BARRIER FREE
a.
Fixture: Just SL-ADA-2019-A-GR - 14"x16x5" deep, self rimming sink, 18 gauge
stainless steel.
b.
Faucet: Chicago Faucet #2200-4CP, Marathon
c.
Trim: McGuire #151A drain with 1-1/2" tailpiece #1151 Awe, with off set #8089 p-trap,
#H-2165 supply stops.
P-21 BAR SINK - S.S. (ADMIN.)
a.
Fixture: Just #SL-1815 AGR (12"x12"x7-1/2") - 18 gauge self-rimming, stainless steel,
single compartment modified with single faucet hole.
b.
Faucet: Chicago Faucet #50-E3-FC
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece, #8912 - 1-1/2" p-trap, #H-2165 supply
stops.
P-22 SINK - S.S. (STAFF)
a.
Fixture: Just #SL-1815-AGR (12"x12"x7-1/2") 18 gauge stainless steel, self-rimming
single compartment.
b.
Faucet: Chicago #786-GN2-FCCP
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece, #8912 - 1-1/2" P-trap, #H-2165 supply
stops.
P-23 LAB SINK - POLYETHYLENE
a.
Fixture: Orion #ARLS-15 - 18"x14"x12", one piece black molded polyethylene material,
with corner waste outlet.
b.
Faucet: Chicago Faucet #930-317-CP with vacuum breaker.
c.
Trim: Orion Fitting Inc. #WA-1 waste assembly, tailpiece to be polypropylene material.
Orion Fitting Inc. 1-1/2" swivel drum trap. McGuire #H-2165 supply stops.
d.
Mounting: Provide under sink straps secured to casework to support sink.
P-24 LAB SINK - S.S.
a.
Fixture: Just #SLX-2219-A-GR (16"x16"x10-1/2") bowl, 18 gauge, stainless steel, selfrimming, single compartment.
b.
Faucet: Chicago Faucet #930-317-CP with vacuum breaker.
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece, Orion Fitting Inc. - 1-1/2" swivel drum trap,
McGuire #H-2165 supply stops.
P-25 CLINICAL SINK - WALL HUNG (STAFF)
a.
Fixture: #K-12867 - Camerton (21" x 25"), #K-13864 loose strainer, K-8935 S.S. rim
guard.
b.
Valve: Sloan Royal #117BH flush valve,
PLUMBING FIXTURES
22 40 00 - Page 5
Memorial Hermann Best Practices
July, 2013
c.
d.
e.
Carrier: Jay R. Smith #915 fixture support carrier.
Faucet: Chicago Faucet #814-VBCP with fork brace and stops, 6" wristblade control
handles, #910G-777-19KCP bedpan washer, self closing, double pedal valve, mounting
hook, extended hose, and elevated vacuum breaker.
Mounting: Mount fixture 24" from center line of outlet to finished floor. Mount vacuum
breaker to be 7'-6" A.F.F.
P-26 SCRUB SINK (ROUGH-IN ONLY)
a.
Trim: McGuire #8912, 1-1/2" P-trap, #H-2165 supply stops. Jay R. Smith #870KF support
carrier.
b.
Mounting: Refer to Architectural Drawings.
P-27 SINK - TWO COMP. - S.S. (STAFF)
a.
Fixture: Just #DLX-2237-A-GR (16"x16"x10") 18 gauge stainless steel, self-rimming, two
compartment.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #151 drains, with 1-1/2" tailpieces, #8912 1-1/2" p-trap. #111 - 1-1/2"
continuous waste, #H-2165 supply stops.
P-27A SINK - TWO COMP. - S.S. (STAFF) BARRIER-FREE
a.
Fixture: Just #DL-2237-A-GR (16"x16"x5") 18 gauge stainless steel, self-rimming, two
compartment.
b.
Faucet: Chicago Faucet #786-GN2-FCCP
c.
Trim: McGuire #151 drains, with 1-1/2" tailpieces, #8912 1-1/2" p-trap. #111 - 1-1/2"
continuous waste, #H-2165 supply stops.
P-28 SINK - THREE COMP. - S.S. (STAFF)
a.
Fixture: Just #TLXD-2255-A-GR (16"x16"x12") 18 gauge stainless steel, self-rimming,
three compartment.
b.
Faucet: Chicago Faucet #1888-L12-317-CP (2 reqd)
c.
Trim: McGuire 151 Drains with 1-1/2" tailpieces (3 reqd) #113 - 1-1/2" continuous waste
fitting, #8912 - 1-1/2" p-trap (2 reqd), #H-2165 supply stops (2 pair reqd)
P-29 SINK (ROUGH-IN-ONLY) ONE-COMP. - S.S. (KITCHEN)
a.
Fixture: Stainless steel sink, strainer, tailpiece and faucet by others, Contractor installed.
b.
Trim: McGuire #8904 - 2" p-trap, #H-2165 supply stops.
P-30 SINK (ROUGH-IN ONLY) THREE-COMP., S.S. (KITCHEN)
a.
Fixture: Stainless steel sink, strainers, tailpieces, and faucets by others, Contractor
installed.
b.
Trim: McGuire #8904 - 2" p-trap (3 reqd), #H-2165 supply stops (2 reqd)
P-31 SINK - PHOTO SENSOR OPERATED - S.S. (NURSERY)
a.
Fixture: Just #SL-2019-A-GR (14"x16"x7-1/2") 18 gauge stainless steel, self-rimming,
single compartment.
b.
Faucet: Chicago #652-123-CP E29 sensor activated gooseneck faucet, with built-in
mixing valve adjusted from top of deck plate, contractor provided 120 volt AC to 6 volt DC
plug-in-type transformer, laminar flow without aerator. See Division 26 for G.F.I. outlet
below sink. Connect to life safety branch (emergency power).
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece, #8912 - 1-1/2" p-trap, H-2165 supply
stops.
P-32 PATHOLOGY GROSS CUT SINK (ROUGH-IN ONLY)
a.
Fixture: Stainless steel sink, strainer, tailpiece and faucet furnished by Owner, Contractor
installed.
b.
Trim: McGuire #8912 - 1-1/2" p-trap, #H-2165 supply stops (2 reqd).
PLUMBING FIXTURES
22 40 00 - Page 6
Memorial Hermann Best Practices
July, 2013
P-33 PHARMACY SINK (ROUGH-IN ONLY)
a.
Fixture: Stainless steel sink, strainer, tailpiece and faucet furnished by Owner, Contractor
installed.
b.
Trim: McGuire #8912 - 1-1/2" p-trap, #H-2165 supply stops (2 - required)
P-34 SERVICE SINK - FLOOR BASIN (24"x24")
a.
Fixture: Stern-Williams #SB-900-BP, 24"x24"x12" with stainless steel cap and 3" chrome
drain.
b.
Faucet: # Chicago Faucet #911-ISCP, mounted 36" A.F.F. to faucet, vacuum breaker and
integral stops, mount vacuum breaker 7'-6" A.F.F.
P-35 SERVICE SINK - FLOOR BASIN (24"x36")
a.
Fixture: Stern-Williams #SB-300-BP - 24"x36"x12" with stainless steel cap and 3" chrome
drain.
b.
Faucet: Chicago Faucet #911-ISCP, mounted 36" A.F.F. to faucet, vacuum breaker and
integral stops, mount vacuum breaker 7'-6" A.F.F.
P-36 CUP SINK (LAB)
a.
Fixture: Orion Fitting Inc. #CSI, Black Polypropylene cup sink.
b.
Trim: Orion acid resistant waste trap and drain.
P-37 LAUNDRY SINK - TWO COMP. - MOLDED STONE
a.
Fixture: Fiat #FLTD - 43"x18"x18" with aluminum legs and compartment drains.
b.
Faucet: Chicago #895-317-FCCP with 4" wristblades, and swing spout.
c.
Trim: McGuire #8912, 1-1/2" p-trap, McGuire #520 two compartment waste outlet, #H2165 supply stops.
P-38 SHOWER - 36"x36" (PATIENT)
a.
Fixture: Aqua Bath #C4136BF-FUS-3/4" 36"x36"x80" modified to have 3/4" threshold.
b.
Accessories: Institutional shower with factory installed grab bars and curtain rod.
c.
Trim: Symmons VISU-Temp #1250VT-H401-V-B30-QD-X-3/4" pressure-balancing mixing
valve with Clear-Vue thermometer and adjustable stop screw to limit handle turn, 30"
slide bar for hand shower mounting, quick disconnect feature - Casper #101C brass drain
with stainless steel top.
P-39 SHOWER - 36"x36" (PATIENT BARRIER-FREE)
a.
Fixture: Aqua Bath #C4136 BF-FUS-3/4" -36"x36"x80" modified to have 3/4" threshold
b.
Accessories: Factory installed fold-up seat, grab bars and curtain rod.
c.
Trim: Symmons VISU-Temp #1250VT-H401-V-B30-QD-X-3/4" pressure-balancing mixing
valve with Clear-Vue thermometer and adjustable stop screw to limit handle turn, 30"
slide bar for hand shower mounting, quick disconnect feature - Casper #101C brass drain
with stainless steel top.
P-40 SHOWER - 60"x36" (PATIENT BARRIER-FREE)
a.
Fixture: Aqua Bath #C65-36BF-FUS-3/4" modified to have 3/4" threshold.
b.
Accessories: Factory installed fold-up seat, grab bars, and curtain rod.
c.
Trim: Symmons VISU-Temp #1250VT-H401-V-B30-QD-X-3/4" pressure-balancing mixing
valve with Clear-Vue thermometer and adjustable stop screw to limit handle turn, 30"
slide bar for hand shower mounting, quick disconnect feature - Casper #101C brass drain
with stainless steel top.
P-41 SHOWER - CORNER - (PATIENT)
a.
Fixture: Aqua Bath #C4136 BF-FUS-3/4" 36"x36"x80 modified to have a 3/4" threshold.
b.
Accessories: Institutional shower with factory installed grab bars and curtain rod.
PLUMBING FIXTURES
22 40 00 - Page 7
Memorial Hermann Best Practices
July, 2013
c.
Trim: Symmons VISU-Temp #1250VT-H401-V-B30-QD-X-3/4" pressure-balancing mixing
valve with Clear-Vue thermometer and adjustable stop screw to limit handle turn, 30"
slide bar for hand shower mounting, quick disconnect feature - Casper #101C brass drain
with stainless steel top.
P-42 SHOWER - TILE (PATIENT)
a.
Shower stall by Architect.
b.
Trim: Symmons VISU-Temp #1250VT-H401-V-B30-QD-X-3/4" pressure-balancing mixing
valve with Clear-Vue thermometer and adjustable stop screw to limit handle turn, 30"
slide bar for hand shower mounting, quick disconnect feature; Jay R. Smith #2005 ACP
2" bronze body, chrome top floor drain. Floor drain installation shall incorporate water
proofing membrance per specification requirements for drains above slab-on grade.
P-43 EMERGENCY SHOWER
a.
Fixture: Gaurdian G1629 with stay open control valve and concealed, 10" dia. emergency
shower head for flush ceiling mounting.
b.
Provide pull rod to activate, push to close with triangle handle and ceiling escutcheon
plate. Handle shall be mounted 48" A.F.F.
c.
Provide Leonard, Model No. TM-500 cabinet (recessed type) to supply 85 degrees F.
Tempered water to emergency shower head. Supply lines to mixing valve to be 3/4" and
a 1" supply from mixing valves to overhead shower.
P-44 BATHTUB/SHOWER (PATIENT) 5'-0"
a.
Fixture: Aqua Bath #156032TS 60"x32"x80" I.D." Acrylic institutional tub/shower
b.
Accessories: Factory installed grab bars and curtain rod.
c.
Trim: Symmons #S-96-2-X-131-L shower valve unit, 2.5 GPM flow control. McGuire
#1221-TL - 1-1/2" tub drain/overflow unit.
P-45 BATH TUB - 5'-0" - CAST IRON
a.
Fixture: Kohler #785 or #786 enamel cast-iron tub with non-slip bottom. #K-9620 hand
grip rails, 60"x32"x16"
b.
Trim: Symmons #1-50VT-FS-X shower valve unit, 2.5 GPM flow control; McGuire #1221TL - 1-1/2" tub drain/overflow unit.
P-46 BATHTUB - INSTITUTIONAL WITH PEDESTAL MOUNT
a.
Fixture: Eljer #012-1620, enameled cast iron tub with cast iron base, no slip bottom.
b.
Trim: Symmons #1-50VT-FS-X shower valve unit, 2.5 GPM flow control; McGuire #1221TL - 1-1/2" tub drain/overflow unit.
P-47 WHIRLPOOL TUB ROUGH-IN ONLY
a.
Whirlpool furnished by Owner, install complete rough-in, and connections.
b.
Trim: Symmons #5-200 PW thermostatic mixing valve furnished with T-425 thermometer
and Chicago #892-GCP vacuum breaker.
c.
Mounting: Mount vacuum breaker 7'-6" A.F.F.
d.
Provide access panel to motor and drain assembly.
P-48 ROOF DRAIN - OVERFLOW
a.
Fixture: Jay R. Smith #108-Y with water dam collar, L-shaped under deck clamp, cast
iron dome, #1710 expansion joint if no pipe offset in R.W.L., sized as shown on drawings.
P-49 ROOF DRAIN
a.
Fixture: Jay R. Smith #1010-CRAD with deck clamp, sump receiver, cast iron dome, if no
insulation above roof slab, - use #1015 CRA with same accessories if insulation is above
roof slab.
PLUMBING FIXTURES
22 40 00 - Page 8
Memorial Hermann Best Practices
July, 2013
P-50 FLOOR DRAIN (REGULAR)
a.
Fixture: Jay R. Smith #2005-ABPB, add suffix "-P" if required, see drawings, sediment
bucket, and polished nickel bronze top, provide flashing clamp if drain is installed above
slab on grade. Floor drain shall incorporate water proofing membrane per specification
requirements for drains above slab-on grade. Provide trap primer connections.
P-51 FLOOR DRAIN (EQUIPMENT ROOMS)
a.
Fixture: Jay R. Smith #2233-YPB, add suffix "-P" if required, see drawings, sediment
bucket, and polished nickel bronze top, provide flashing clamp if drain is installed above
slab on grade. Floor drain shall incorporate water proofing membrane per specification
requirements for drains above slab-on grade. Provide trap primer connections.
P-52 FLOOR DRAIN (KITCHEN)
a.
Fixture: Jay R. Smith #3001-Y, add suffix "-P" if required, see drawings, sediment bucket,
porclean enamel interior, nickel bronze rim and grate, provide flashing clamp if drain is
installed above slab on grade. Floor drain shall incorporate water proofing membrane per
specification requirements for drains above slab-on grade. Provide trap primer
connections.
P-53 FLOOR DRAIN (KITCHEN 1/2 GRATE)
a.
Fixture: Jay R. Smith #3101-Y12, add suffix "-P" if required, see drawings, sediment
bucket, porclean enamel interior, nickel bronze rim and grate, provide flashing clamp if
drain is installed above slab on grade. Floor drain shall incorporate water proofing
membrane per specification requirements for drains above slab-on grade. Provide trap
primer connections.
P-54 FLOOR DRAIN (FUNNEL TYPE)
a.
Fixture: Jay R. Smith #3510-F10, with polished brass strainer and 4" diameter integral
funnel, provide flashing clamp if drain is installed above slab on grade. Floor drain shall
incorporate water proofing membrane per specification requirements for drains above
slab-on grade. Provide trap primers.
P-55 FLUSHING RIM FLOOR DRAIN (CYSTO)
a.
Fixture: Jay R. Smith #2505 acid resistant interior, flushing rim floor drain, with polished
bronze hinged top.
b.
Trim: Sloan Royal #150-WB push button flush valve with access wall box, mounted 62"
A.F.F. on wall, provide flashing clamp for floor drain if installed above slab-on grade.
Floor drain shall incorporate water proofing membrane per specification requirements for
drains above slab-on grade.
P-56 FLOOR DRAIN (ACID RESISTANT - FUNNEL)
a.
Fixture: Orion Fittings Inc. #FD-1, polypropylene material floor drain with funnel less plug,
trap shall be acid resistant material. Floor drain shall incorporate water proofing
membrane per specification requirements for drains above slab-on grade.
P-57 FLOOR DRAIN (ACID RESISTANT)
a.
Fixture: Orion Fittings Inc. #FD-1, polypropylene material floor drain trap shall be acid
resistant material. Floor drain shall incorporate water proofing membrane per
specification requirements for drains above slab-on grade.
P-58 TRAP PRIMER
a.
Fixture: Precision Plumbing Products, Inc. #Prime-Rite, sized as required to serve
number of drains shown on drawings. Includes trap primer valve, distribution unit with
integral vacuum breakers. Installation to be rigid to wall. See detail.
PLUMBING FIXTURES
22 40 00 - Page 9
Memorial Hermann Best Practices
July, 2013
P-59 DRINKING FOUNTAIN (S.S. SEMI-RECESSED)
a.
Fixture: Oasis #PLF 14S-STN, 14.0 GPH of 50 degrees F. outlet water, 80 degree F.
inlet water temperature, 90 degree F. ambient air, all exposed surfaces to be stainless
steel, mount per Architectural drawings.
b.
Trim: McGuire #8872 - 1-1/4" p-trap, #HST-2 supply stop.
P-60 DRINKING FOUNTAIN (BARRIER-FREE - WALL HUNG)
a.
Fixture: Oasis PLF8 SKTP-STN, 10.5 GPH of 50 degree F. outlet water, 80 degree F.
inlet water and 90 degree F. ambient air, all exposed surfaces to be stainless steel,
mount per Architectural drawings.
b.
Trim: McGuire #8872 - 1-1/4" p-trap, #HST-2 supply stop.
P-61 WALL HYDRANT (HOT AND COLD) NON-FREEZE
a.
Fixture: Jay R. Smith #5560-PB-VBQT, non freeze, 3/4" vacuum breaker outlet, for hot
and cold water service mount 48" above loading dock service.
P-62 WALL HYDRANT (COLD WATER) NON-FREEZE
a.
Fixture: Jay R. Smith #5609-PBQT, non-freeze, with vacuum breaker mount 18" A.F.G.
P-63 HOSE BIBB (MECH. EQUIP. ROOM)
a.
Fixture: MIFAB #MHY-90, integral stops, and anti-siphon vacuum breaker, brass exterior
finish, cast iron wheel handle, 3/4" inlet.
P-64 COLD WATER FAUCET (MECH. EQUIP. ROOM)
a.
Fixture: Chicago Faucet #952-634COLD-JKCP handle, integral stop, and vacuum
breaker, mount faucet 36" A.F.F.
P-65 SHOCK ARRESTORS
a.
Fixture: MIFAB #WHB series, sized per manufacturers recommendation.
P-66 DM1EMERGENCY EYE/FACE WASH (LAB) - DECK MOUNTED
a.
Fixture: Guardian #G1730 recessed deck mounted ball valve with flag handle.
b.
Trim: McGuire #8872 - 1-1/4" p-trap, provide 3/4" C.W. supply with stop at fixture.
c.
Mixing Valve: Leonard, Model No. TA-300 in case work below eye wash, set for 85
degrees F. Route supply line from mixing valve up to eye wash with stop valve. Supply
lines to mixing valve to be 1/2" I.P.S.
P-66 DM2 EYE WASH - DECK MOUNT
a.
Fixture: Guardian #1806 eye wash, 90 degree swivel.
b.
Trim: McGuire #8872 - 1-1/4" p-trap, provide 3/4" C.W. supply with stop at fixture.
c.
Mixing Valve: Leonard, Model No. TA-300 in case work below eye wash, set for 85
degrees F. Route supply line from mixing valve up to eye wash with stop valve. Supply
lines to mixing valve to be 1/2" I.P.S.
P-67 EMERGENCY WATER FILL CONNECTION
a.
Fixture: Potter-Roemer #5016-D single hose connection inlet with female snoot backing
plate, thread swivel, pin lug plug and chain, chrome plated finish. NOTE: Lettering on
backing plate to read "Emergency Water Fill Connection Only"
P-68 AUTOPSY TABLE (ROUGH-IN ONLY)
a.
Fixture: Autopsy table furnished by Owner. Install complete rough-in, and connections.
b.
Trim: Install 1/2" hot and cold water with supply stops, 2" drain with deep seal trap, loop
vent or regular vent in wall as required.
PLUMBING FIXTURES
22 40 00 - Page 10
Memorial Hermann Best Practices
July, 2013
P-69 ULTRASONIC CLEANER (ROUGH-IN ONLY)
a.
Fixture: Ultrasonic cleaner furnished by Owner. Install complete rough-in, and
connections.
b.
Trim: Install two (2) McGuire #8912, 1-1/2" p-traps, four (4) #H-2165 supply stops. Two
rough-in's required per unit.
c.
Provide polyproethlyene valve on D.I. line serving unit.
P-70 DISPOSER ROUGH-IN ONLY (KITCHEN)
a.
Fixture: Disposer furnished by Others. Install complete rough-in, and connections.
b.
Trim: Install 3/4" globe valve prior to entering solenoid valve, McGuire #8904, 2" p-trap,
provide shock absorber between glove valve and solenoid valve.
P-71 WASHING MACHINE SUPPLY AND DRAIN BOX
a.
Fixture: Guy Gray Washer Box #FBB-200TS Provide p-trap in wall to serve Guy Gray
Box. Mount Box 42" A.F.F. to bottom.
P-72 FILM PROCESSOR PIPING CONNECTION (C.W. ONLY)
a.
Fixture: Chicago Faucet #778-VBGCP, #770-PLCP watts #9D R.P.B.P., #909AG air gap
funnel.
b.
Provide polished chrome plated pipe for exposed piping outside wall and not in dark
room. Backflow preventer, funnel, drain piping, union, and valve shall be exposed in dark
room at connection point. See detail.
P-73 FILM PROCESSOR PIPING CONNECTION (H. & C.W.)
a.
Fixture: Chicago Faucet #778-VBGCP, #770-PLCP, 777-19K (two required) Hammond
Valve Co. #18941 swing check valves. Symmons #T-425 thermometer Watts #9D
R.P.B.P., #909AG air gap funnel.
b.
Provide polished chrome plated pipe for exposed piping outside wall and not in dark
room. Backflow preventer, funnel, drain piping, unions, and valves shall be exposed in
dark room at connection point. See detail.
P-74 PASTEURMATIC MACHINE (ROUGH-IN)
a.
Fixture: Acorn Engineering Company #8181 stainless steel recessed supply and drain
box with 3/4" hot water, 2" drain. Provide trap in wall below box. Mount box 48" A.F.F.
P-75 DECONTAMINATION/EMERGENCY SHOWER
a.
Fixture: Symmons #S96-300-X, shower valve with hand held shower, 12'-0" flexible metal
hose and wall mounting hooks. MIFAB #F-1100-C-S, sediment bucket, polished nickel
bronze top - Provide flashing clamp if drain is installed above slab on grade. Provide trap
primer connection.
P-76 WHIRLPOOL TUB/SHOWER - 32"x60"x16" - LDRP PATIENT
a.
Fixture: Kohler K-783-H, Guardian Bath Whirlpool, cast iron with non-slip bottom; K-9620
handrails; K-9694 whirlpool trim kit; 120v, 1 HP pump.
b.
Trim: Symmons #S-96-2-X-131-L shower valve unit, 3 GPM flow control and built-in
diverter. McGuire #1221-TL-1-1/2" tub drain/overflow unit.
c.
Provide access panel for motor and drain.
P-77 WHIRLPOOL BATH (BIRTHING ROOMS) - LDRP PATIENT
a.
Fixture: Kohler Co. #K-1492-H whirlpool bath, acrylic with fiberglass reinforcement, four
adjustable jets; 120v, 1 hp pump; #K-9694 whirlpool trim kit; #K-1495 apron.
b.
Trim: McGuire #1221-TL-1-1/2" tub drain/overflow unit, Symmons #S-96-2-X-131-L
shower valve unit, 3 GPM flow control and built-in diverter.
c.
Provide access panel for motor and drain.
PLUMBING FIXTURES
22 40 00 - Page 11
Memorial Hermann Best Practices
July, 2013
P-78 PHARMACY SINK - S.S.
a.
Fixture: Just #SLX-2225-A-GR (16"x22"x10-1/2") 18 gauge stainless steel, self-rimming,
single compartment. Special drilled for single faucet hole.
b.
Faucet: Chicago Faucet #930-317CP with built-in vacuum breaker and serrated tip.
c.
Trim: McGuire #151 drain with 1-1/2" tailpiece, #8912 - 1-1/2" p-trap, #H-2165 supply
stops.
P-79 TRENCH DRAIN - KITCHEN
a.
Fixture: Jay R. Smith #2710-1-F-B-ARE-NB cast iron trench drain with porcelain enamel
interior, sediment bucket, nickel bronzer rim and full grate top.
P-80 DIALYSIS SUPPLY BOX
a.
Fixture: Whitehall Manufacturing, Hospital-Ware Model #HW196 stainless steel box with
flange and door; 1/2" polypropolyene, white line, Orion faucet; 2" drain connection.
Provide nipples for flushing of supply piping.
b.
Mount box 18" A.F.F. to bottom of box.
P-81 LASER SUPPLY BOX
a.
Fixture: Whitehall Manufacturing, Hospital-Ware Model #HW195, stainless steel box with
flange and door, 1/2" cold water faucet with vacuum breaker, and 2" drain connection,
screw driver stops.
b.
Mount box 62" A.F.F. to bottom of box.
P-82 HEART PUMP SUPPLY BOX
a.
Fixture: Acorn Engineering Company #8186 stainless steel box with flange and door, 1/2"
hot and cold water faucet with vacuum breaker and 2" drain connection, screw driver
stops.
b.
Mount box 62" A.F.F. to bottom of box.
P-83 DEIONIZED WATER OUTLET
a.
Fixture: Orion Fittings, Inc. #GNF30-VB white line laboratory gooseneck faucet, whiteline
polypropylene materials. Provide ball check valve outlet.
P-85 JANITOR SINK (WALL HUNG)
a.
Fixture: Kohler #K-6718 Bannon enameled cast-iron service sink, with stainless steel rim
guard.
b.
Faucet: Chicago Faucet Co. #911-ISCP faucet, vacuum breaker and stops,
c.
Trim: #K-6673 - p-trap with 3" threaded outlet and strainer.
P-86 FILM PROCESSOR SINK
a.
Fixture: Just #NSFB-130, 24"x30"x12" stainless steel free standing sink, round corners,
S.S. tubular legs, bullet feet. Special drill sink back splash to accept faucet. Special order
sink to accept grid drain specified.
b.
Faucet: Chicago Faucet Company #911-ISCP, with integral stops, less vacuum breaker
and 3/4 inch hose thread end; Watts #9D R.P.B.P.; #909AG Air Gap Funnel; Stern
Williams #T-35 hose and hook; Orion Fitting Inc. #WA-3 waste assembly; Provide
polypropylene tailpiece; Orion Fitting Inc. #UTP - 2" p-trap. See detail on drawings.
P-87 PERINEAL BATH
a.
Fixture: Kohler #K-12515 Brook Haven sitz bath, #K-12517 pedestal, #K-13128 overflow.
b.
Faucet: Symmons #4-500 VTX-ICS shower valve.
c.
Trim: Kohler #K-13023 bell supply and escutcheon.
P-88 HOSE REEL
a.
Fixture: Chicago Faucet Co. #537-NF
PLUMBING FIXTURES
22 40 00 - Page 12
Memorial Hermann Best Practices
July, 2013
b.
c.
Symmons #4-500 VTX-ICS shower valve
Watts #9D R.P.B.P., #909 AG air gap funnel.
P-89 AIR, GAS OR VACUUM OUTLETS
a.
Fixture: Chicago Faucet Co. #986-909-AGVCP
P-90 CART WASH
a.
Fixture: Chicago Faucet Co. #537-NF hose reel Symmons #4-500-VTX-ICS shower valve
Watts #9D RPBP, #909 AG Air Gap Funnel MIFAB #FS-1520-F1-1-5-7 floor drain with
porcelain enamel, interior, N.B. top. Provide clamp device if installed in floor above slab
on grade.
P-91 RECESSED WALL SUPPLY BOX
a.
Fixture: Guy Gray BIM-875.
PART 3 - EXECUTION
3.01
FIXTURE CONNECTIONS
A.
Connect to plumbing fixtures and equipment provided under this and other sections of
specification, architectural drawings, and manufacturer's shop drawings. Provide rough-in
connections as shown on drawings.
B.
Use schedule and details on drawings or manufacturer's shop drawings for connection sizes to
fixtures.
C.
Connect wall hung urinals to waste piping with red brass nipples.
D.
Provide separate p-trap for each fixture, floor drain, and piece of equipment.
E.
Provide cast iron p-traps under floor drains.
F.
Provide deep seal traps under floor drains in air conditioning unit plenums, walk-in cooler and
freezer units, storage rooms, toilet rooms, and elsewhere as indicated on drawings.
G.
Where required by local or state energy codes, provide H.W. flow limiting devices to
lavatories/sinks in accordance with ASHRAE 90.1-2004.
H.
Install lavatories and sinks with a minimum of 4" clearance on each side, from a wall or partition.
I.
Install water closets with a minimum of 15" clearance from the centerline of the bowl to each side,
from a wall, partition, divider, or another fixture.
J.
Water closets shall have a minimum of 21" clearance in front of bowl.
K.
Coordinate dimensions required for minimum fixture clearances with other Divisions.
L.
Where automatic electronic flushing devices are specified, coordinate installation with Division 26.
M.
Caulk around joints at fixtures mounted on wall or floor, or backed up to walls.
N.
Mount fixtures rigid to walls as shown on drawings or details.
O.
Accessories: Factory installed grab bars and curtain rod.
PLUMBING FIXTURES
22 40 00 - Page 13
Memorial Hermann Best Practices
July, 2013
P.
Install a dropped eared "L", mounted on treated wood backing for rigid support for all shower
heads.
Q.
Flush valves: Install flush valves on wide side of water closet as required for ADA accessibility.
R.
Fixture supply risers shall be braided stainless steel with metal connectors.
S.
Rough-in (floor ice machine, by Owner):
1.
Rough-in 1/2" cold water with cutoff valve at connection.
2.
Provide funnel floor drain under ice machine and run connection size drain from unit to
floor drain.
3.
Provide 2" air gap between drain line and floor drain.
4.
Floor drains with air gaps shall be readily accessible for maintenance and inspection
purposes.
T.
Wall Hung Ice Machine:
1.
Provide 1/2" cold water connection to ice machine supply/drain box with cutoff valve in
line.
U.
Gooseneck faucets intended for staff and patient, use shall not contain aerators but shall contain
plain end outlet trim ring.
V.
Emergency Showers:
1.
Shall be supplied with tepid (max. 85 degrees F) potable water.
2.
Shall be capable of delivering not less than 20 gpm for a minimum of 15 minutes.
3.
Center of the water pattern shall be at least 16" from any obstruction.
4.
The activating handle shall be no higher than 69" above finished floor.
5.
Location of shower shall be within a well-lit area, marked with a sign, within 10 second
travel time (approximately 50-100 feet), on the same level as the hazard with the route
free from obstructions.
6.
Shall be activated in one second and remain operationally hands free once activated.
7.
Standard wall-mount showers do not meet the criteria for an emergency shower.
8.
A floor drain shall be located at every emergency shower location.
W.
Emergency Eye/Face Wash Stations:
1.
Shall be capable of flushing both eyes simultaneously.
2.
Shall deliver a low pressure/velocity flow that will not cause additional injury to the user.
Shall be provided with dedicated pressure regulating device as required to accommodate
desirable operating pressure.
3.
Nozzles shall be protected from airborne contaminants by use of protective covers. The
covers shall be easily removable, and not require a separate action by the user.
4.
Shall be constructed of material that will not corrode in the presence of flushing fluid.
5.
Shall be supplied with tepid (max. 85 degrees F) potable water.
6.
Shall be capable of delivering not less than 0.4 gpm for eyewashes and 3.0 gpm for
eye/face washes for a minimum of 15 minutes.
7.
Water outlet heads shall be between 33" to 45" above finished floor and at least 6" from
the wall or nearest obstruction.
8.
Location shall be within 10 second travel time (approximately 50-100 feet), on the same
level as the hazard with the route free from obstructions.
9.
Shall be activated in one second and remain operationally hands free once activated.
3.02
A.
TESTING AND CLEANING
Inspect and test work to insure that it is installed in accordance with drawings and specification
and is functioning as designed. Test procedures and pressure as required by other sections.
PLUMBING FIXTURES
22 40 00 - Page 14
Memorial Hermann Best Practices
July, 2013
B.
Correct all deficiencies found and retest.
C.
Turn all work over to Owner in a clean, sanitary condition.
D.
Emergency shower and eye/face wash stations shall be tested and certified for proper location
and operation including flows, temperatures and pressures. Testing/certification documents shall
be included within project closeout documents.
END OF SECTION
PLUMBING FIXTURES
22 40 00 - Page 15