Nablus Municipality Ministry of Social Affairs State of Palestine India, Brazil, and South Africa Forum Nablus Center for Rehabilitation Phase I Technical Specifications Part B - Electrical Works July 2013 NABLUS MUNICIPALITY Construction, Completion and Maintenance of Nablus Center For Intelectual Disbility Phase I & II PART B – Electrical Works VOLUME II May, 2013 SECTION E010 ELECTRICAL GENERAL PROVISIONS PART 1 - GENERAL 1.01 DESCRIPTION A. This Section, Electrical General Provisions applies to all sections of electrical divisions. B. Furnish and install electrical wiring, systems, equipment and accessories in accordance with the specifications and drawings. Capacities and ratings of motors, transformers, cable, switchboards, switchgear, panelboards, motor control centers, and other items and arrangements for the specified items are shown on drawings. C. Electrical service entrance equipment (arrangements for temporary and permanent connections to the power company's system) shall conform to the power company's requirements. Coordinate fuses, circuit breakers and relays with the power company's system, and obtain power company approval for sizes and settings of these devices. D. Wiring capacities specified or shown on the drawings are based on copper conductors, with the conduit and raceways accordingly sized. Aluminum conductors are prohibited. 1.02 MINIMUM REQUIREMENTS A. Standards of the following organizations are minimum installation requirement standards 1. Association of Edison Illuminating Companies (AEIC). 2. American National Standards Institute (ANSI). 3. Institute of Electrical and Electronics Engineers (IEEE). 4. Insulated Cable Engineers Association (ICEA). 5. National Electrical Code (NEC). 6. National Electrical Manufacturers Association (NEMA). 7. National Electrical Safety Code (NESC). 8. National Fire Protection Association (NFPA). 9. Underwriters' Laboratories (UL). 10. British Code (BS) B. Drawings and other specification sections shall govern in those instances where requirements are greater than those specified in the above standards. 1.03 SCOPE OF WORK A. This division of the specifications covers the electrical systems of the project. It includes work performed by the electrical trades as well as trades not normally considered as electrical trades. B. Provide all incidentals, equipment, appliances, services, hoisting, scaffolding, supports, tools, supervision, labor consumable items, fees, licenses, etc., necessary to provide complete systems. Perform start-up and checkout on each item and system to provide fully operable systems. C. Examine and compare the Electrical Drawings with these specifications, and report any discrepancies between them to the Architect/Engineer and obtain from him written instructions for changes necessary in the work. At time of bid the most stringent requirements must be included in the bid. D. Examine and compare the Electrical Drawings and Specifications with the Drawings and Specifications of other trades, and report any discrepancies between them to the Architect/Engineer and obtain from him written instructions for changes necessary in the work. At time of bid, the most stringent requirements must be included in said bid. E. Install and coordinate the electrical work in cooperation with other trades installing interrelated work. Before installation, make proper provisions to avoid interferences in a manner approved by the Architect/Engineer. All changes required in the work of the Contractor, caused by his neglect to do so, shall be made by him at his own expense. E010-1 F. It is the intent of the Drawings and Specifications to provide a complete workable system ready for the Owner's operation. Any item not specifically shown on the Drawings or called for in the Specifications, but normally required to conform to the intent, are to be considered a part of the Contract. G. All materials furnished by the Contractor shall be new and unused (temporary lighting and power products are excluded) and free from defects. All materials used shall bear the Underwriter's Laboratory, Inc. label provided a standard has been established for the material in question. 1.04 TEST STANDARDS A. All materials and equipment shall be listed, labeled or certified by a nationally recognized testing laboratory to meet Underwriters Laboratories, Inc., standards where test standards have been established. Equipment and materials which are not covered by UL Standards will be accepted provided equipment and material is listed, labeled, certified or otherwise determined to meet safety requirements of a nationally recognized testing laboratory. Equipment of a class which no nationally recognized testing laboratory accepts, certifies, lists, labels, or determines to be safe, will be considered if inspected or tested in accordance with national industrial standards, such as NEMA, or ANSI. Evidence of compliance shall include certified test reports and definitive shop drawings. B. Definitions: 1. Listed; equipment or device of a kind mentioned which: a. Is published by a nationally recognized laboratory which makes periodic inspection of production of such equipment. b. States that such equipment meets nationally recognized standards or has been tested and found safe for use in a specified manner. 2. Labeled; equipment or device is when: a. It embodies a valid label, symbol, or other identifying mark of a nationally recognized testing laboratory such as Underwriters Laboratories, Inc. b. The laboratory makes periodic inspections of the production of such equipment. c. The labeling indicates compliance with nationally recognized standards or tests to determine safe use in a specified manner. 3. Certified; equipment or product is which: a. Has been tested and found by a nationally recognized testing laboratory to meet nationally recognized standards or to be safe for use in a specified manner. b. Production of equipment or product is periodically inspected by a nationally recognized testing laboratory. c. Bears a label, tag, or other record of certification. 1.05 QUALIFICATIONS (PRODUCTS AND SERVICES) A. Manufacturers Qualifications: The manufacturer shall regularly and presently produce, as one of the manufacturer's principal products, the equipment and material specified for this project, and shall have manufactured the item for at least three years. B. Product Qualification: 1. Manufacturer's product shall have been in satisfactory operation, on three installations of similar size and type as this project, for approximately three years. 2. The Government reserves the right to require the Contractor to submit a list of installations where the products have been in operation before approval. 1.06 MANUFACTURED PRODUCTS A. Materials and equipment furnished shall be of current production by manufacturers regularly engaged in the manufacture of such items, for which replacement parts shall be available. B. When more than one unit of the same class of equipment is required, such units shall be the product of a single manufacturer. C. Equipment Assemblies and Components: 1. Components of an assembled unit need not be products of the same manufacturer. E010-2 2. Manufacturers of equipment assemblies, which include components made by others, shall assume complete responsibility for the final assembled unit. 3. Components shall be compatible with each other and with the total assembly for the intended service. 4. Constituent parts which are similar shall be the product of a single manufacturer. D. Factory wiring shall be identified on the equipment being furnished and on all wiring diagrams. 1.07 EQUIPMENT REQUIREMENTS A. Where variations from the contract requirements are requested, the connecting work and related components shall include, but not be limited to additions or changes to branch circuits, circuit protective devices, conduits, wire, feeders, controls, panels and installation methods. 1.08 EQUIPMENT PROTECTION A. Equipment and materials shall be protected during shipment and storage against physical damage, dirt, moisture, cold and rain: 1. During installation, enclosures, equipment, controls, controllers, circuit protective devices, and other like items, shall be protected against entry of foreign matter; and be vacuum cleaned both inside and outside before testing and operating and repainting if required. 2. Damaged equipment shall be, as determined by the Resident Engineer, placed in first class operating condition or be returned to the source of supply for repair or replacement. 3. Painted surfaces shall be protected with factory installed removable heavy Kraft paper, sheet vinyl or equal. 4. Damaged paint on equipment and materials shall be refinished with the same quality of paint and workmanship as used by the manufacturer so repaired areas are not obvious. 1.09 WORK PERFORMANCE A. All electrical work must comply with the requirements of NFPA 70 (NEC), NFPA 70B, and NFPA 70E, in addition to other references required by contract. B. Job site safety and worker safety is the responsibility of the contractor. C. Electrical work shall be accomplished with all affected circuits or equipment de-energized. When an electrical outage cannot be accomplished in this manner for the required work, the following requirements are mandatory: 1. Electricians must use full protective equipment (i.e., certified and tested insulating material to cover exposed energized electrical components, certified and tested insulated tools, etc.) while working on energized systems in accordance with NFPA 70E. 2. Electricians must wear personal protective equipment while working on energized systems in accordance with NFPA 70E. 3. Before initiating any work, a job specific work plan must be developed by the contractor with a peer review conducted and documented by the Resident Engineer. The work plan must include procedures to be used on and near the live electrical equipment, barriers to be installed, and safety equipment to be used and exit pathways. D. Coordinate location of equipment and conduit with other trades to minimize interferences. 1.10 EQUIPMENT INSTALLATION AND REQUIREMENTS A. Equipment location shall be as close as practical to locations shown on the drawings. B. Working spaces shall not be less than specified in the NEC for all voltages specified. C. Inaccessible Equipment: 1. Where Resident Engineer determines that the Contractor has installed equipment not conveniently accessible for operation and maintenance, the equipment shall be removed and reinstalled as directed at no additional cost. 2. "Conveniently accessible" is defined as being capable of being reached without the use of ladders, or without climbing or crawling under or over obstacles such as, but not limited to, motors, pumps, belt guards, transformers, piping, ductwork, conduit and raceways. E010-3 1.11 EQUIPMENT IDENTIFICATION A. In addition to the requirements of the NEC, install an identification sign which clearly indicates information required for use and maintenance of items such as panel boards, cabinets, motor controllers (starters), safety switches, separately enclosed circuit breakers, individual breakers and controllers in switchboards, switchgear and motor control assemblies, control devices and other significant equipment. B. Nameplates shall be laminated black phenolic resin with a white core with engraved lettering, a minimum of 6 mm (1/4 inch) high. Secure nameplates with screws. Nameplates that are furnished by manufacturer as a standard catalog item, or where other method of identification is herein specified, are exceptions. 1.12 SUBMITTALS A. Submit in accordance with section 2.03 SAMPLES AND SHOP DRAWINGS. B. The Owner's representative approval shall be obtained for all equipment and material before delivery to the job site. Delivery, storage or installation of equipment or material which has not had prior approval will not be permitted at the job site. C. All submittals shall include adequate descriptive literature, catalog cuts, shop drawings and other data necessary for the Owner's representative to ascertain that the proposed equipment and materials comply with specification requirements. Catalog cuts submitted for approval shall be legible and clearly identify equipment being submitted. D. Submittals for individual systems and equipment assemblies which consist of more than one item or component shall be made for the system or assembly as a whole. Partial submittals will not be considered for approval. 1. Mark the submittals, "SUBMITTED UNDER SECTION__________________". 2. Submittals shall be marked to show specification reference including the section and paragraph numbers. 3. Submit each section separately. E. The submittals shall include the following: 1. Information that confirms compliance with contract requirements. Include the manufacturer's name, model or catalog numbers, catalog information, technical data sheets, shop drawings, pictures, nameplate data and test reports as required. 2. Elementary and interconnection wiring diagrams for communication and signal systems, control system and equipment assemblies. All terminal points and wiring shall be identified on wiring diagrams. 3. Parts list which shall include those replacement parts recommended by the equipment manufacturer, quantity of parts, current price and availability of each part. F. Manuals: 1. Maintenance and Operation Manuals: Submit as required for systems and equipment specified in the technical sections. Furnish four copies, bound in hardback binders, (manufacturer's standard binders) or an approved equivalent. Furnish one complete manual as specified in the technical section but in no case later than prior to performance of systems or equipment test, and furnish the remaining manuals prior to contract completion. 2. Inscribe the following identification on the cover: the words "MAINTENANCE AND OPERATION MANUAL," the name and location of the system, equipment, building, name of Contractor, and contract number. Include in the manual the names, addresses, and telephone numbers of each subcontractor installing the system or equipment and the local representatives for the system or equipment. 3. Provide a "Table of Contents" and assemble the manual to conform to the table of contents, with tab sheets placed before instructions covering the subject. The instructions shall be legible and easily read, with large sheets of drawings folded in. 4. The manuals shall include: a. Internal and interconnecting wiring and control diagrams with data to explain detailed operation and control of the equipment. b. A control sequence describing start-up, operation, and shutdown. c. Description of the function of each principal item of equipment. E010-4 d. e. f. g. h. i. j. Installation and maintenance instructions. Safety precautions. Diagrams and illustrations. Testing methods. Performance data. Lubrication schedule including type, grade, temperature range, and frequency. Pictorial "exploded" parts list with part numbers. Emphasis shall be placed on the use of special tools and instruments. The list shall indicate sources of supply, recommended spare parts, and name of servicing organization. k. Appendix; list qualified permanent servicing organizations for support of the equipment, including addresses and certified qualifications. G. Approvals will be based on complete submission of manuals together with shop drawings. H. After approval and prior to installation, furnish the Resident Engineer with one sample of each of the following: 1. A 300 mm (12 inch) length of each type and size of wire and cable along with the tag from the coils of reels from which the samples were taken. 2. Each type of conduit coupling, bushing and termination fitting. 3. Conduit hangers, clamps and supports. 4. Duct sealing compound. 5. Each type of receptacle, toggle switch, outlet box, manual motor starter, device plate, engraved nameplate, wire and cable splicing and terminating material and single pole molded case circuit breaker. 6. Each type of light fixture specified in Section E510 or shown on the drawings. 1.13 SINGULAR NUMBER Where any device or part of equipment is referred to in these specifications in the singular number (e.g., "the switch"), this reference shall be deemed to apply to as many such devices as are required to complete the installation as shown on the drawings. 1.14 TRAINING A. Training shall be provided for the particular equipment or system as required in each associated specification. B. A training schedule shall be developed and submitted by the contractor and approved by the Resident Engineer at least 30 days prior to the planned training. PART 2 – PRODUCTS 2.01 MATERIALS A. Applicable equipment and materials shall be listed by Underwriters' Laboratories and Manufactured in accordance with ASME, NEMA, ANSI or IEEE standards, and as approved by local authorities having jurisdiction as mentioned in Division 1. B. If products and materials are specified or indicated on the Drawings for a specific item or system, use those products or materials. If products and materials are not listed in either of the above, use first class products and materials, subject to approval of Shop Drawings where Shop Drawings are required or as approved in writing where Shop Drawings are not required. 2.02 SUBSTITUTION OF MATERIALS OR EQUIPMENT A. All requests for substitution of materials or equipment shall be made in writing by the Contractor. The request must be in the Engineers office not less than 10 days prior to the bid date. Samples of proposed substitute materials or equipment shall be submitted to the Engineer for review whenever they are requested. Bids shall be based only upon the specified materials and equipment, or substitutes that have received written acceptance from the Engineer prior to the bid. B. Wherever the words "for approval" or "approved" are used in regard to manufactured specialties, or wherever it is desired to substitute a different make or type of apparatus for that specified, submit all information pertinent to the adequacy and adaptability of the proposed apparatus, and secure Architect/Engineer's acceptance before apparatus is ordered. E010-5 C. Wherever quantities or a definite make and size of apparatus are specified, the make and size of apparatus which is proposed must conform substantially (in regard to the operating results) to that specified or implied. Same shall apply to important dimensions relating to operation of apparatus in coordination with the rest of the system, or to properly fitting it into available space conditions. Any substitution of equipment or apparatus shall include all necessary revisions, as required to complete the installation. D. Acceptance of substitutions, for equipment specified herein, will not be given merely upon submission of manufacturer's names and will be given only after receipt of complete and satisfactory performance data covering the complete range of operating conditions in tabular and graphical form. Furnish complete and satisfactory information relative to equipment dimensions, weight, etc. Acceptance of all equipment specified or shown on the Drawings, or substitutions submitted for that specified or shown on the Drawings, will be granted if such equipment, in the opinion of the Architect/Engineer, conforms to the performance requirements, space conditions, weight requirements and quality requirements. Any additional construction and design costs incurred as a result of any accepted substitution shall be borne by the Contractor. The opinion and judgment of the Architect/Engineer shall be final, conclusive, and binding. 2.03 SHOP DRAWINGS A. Prepare and submit detailed Shop Drawings for materials, systems, and equipment as listed herein, including locations and sizes of all openings in floor decks, walls, and floors. B. The Work described in any Shop Drawing submission shall be carefully checked for all clearances (including those required for maintenance and servicing), field conditions, maintenance of architectural conditions, and proper coordination with all trades on the job. Each submitted Shop Drawing shall include a certification that all related job conditions have been checked and that no conflict exists. C. All drawings shall be submitted sufficiently in advance of field requirements to allow ample time for checking and resubmittal as may be required. All submittals shall be complete and contain all required and detailed information. D. Acceptance of any submitted data or Shop Drawings for material, equipment apparatus, devices, arrangements, and layout shall not relieve Contractor from responsibility of furnishing same of proper dimensions and weight, capacities, sizes, quantity, quality and installation details, to efficiently perform the requirements and intent of the Contract. Such acceptance shall not relieve Contractor from responsibility for errors, omissions, or inadequacies of any sort on submitted data or Shop Drawings. E. Each Shop Drawing shall contain the following information: 1. Provide general information on each copy of the submittal. a. Project title. b. Reference to the applicable drawing and specification article. c. Contractor and supplier identification, addresses and telephone numbers. d. Submittal Date. 2. Certification that the contractor has reviewed the submittal. 3. Refer to individual specification sections for additional information requirements. F. Shop drawing submittals shall be provided for each specific material, system, or equipment as identified herein. 1. As a minimum, make submittals on the following items: a. Raceways, conduit & wire b. Wiring devices and plates c. Switchboards d. Transformers e. Panel boards f. Fuses g. Disconnect switches h. Motor control centers i. Motor controllers, starters, and contactors j. Lighting fixtures, lamps k. Instrumentation, metering equipment E010-6 l. Special systems - fire alarm, security, CCTV, intercom, etc. 2. Refer to individual specification sections for additional submittal requirements. ---END--- E010-7 SECTION E020 ELECTRICAL SERVICES PART 1 - GENERAL 1.01 SUMMARY A. This section pertains to making arrangements for electrical services. 1.02 REFERENCE STANDARDS A. Comply with all service installation standards of the serving utility. PART 2 - ELECTRICAL SERVICE REQUIREMENTS 2.01 SOURCE A. Electrical service will be provided from local power company system. The source characteristics are 400/230 volts, 3 phase, 4 wire, and 50 hertz. 2.02 COORDINATION A. The location of the service entrance, floor trenches, transformers and switchgear pads must be coordinated with the local power company. Provide materials and equipment required to connect the project service to the utility system. PART 3 - EXECUTION 3.01 GENERAL A. Install the utility services as required by local power company and the contract documents. Demonstrate that the electrical system is operational. ---END--- E020-1 SECTION E110 CONDUIT SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. This section specifies the furnishing, installation, and connection of conduit, fittings, and boxes to form complete, coordinated, grounded raceway systems. Raceways are required for all wiring unless shown or specified otherwise. B. Definitions: The term conduit, as used in these specifications, shall mean any or all of the raceway types specified. 1.02 SUBMITTALS In accordance with section E010 (SAMPLES AND SHOP DRAWINGS), furnish the following: A. Shop Drawings: 1. Size and location of main feeders. 2. Size and location of panels and pull boxes. 3. Layout of required conduit penetrations through structural elements. 4. The specific item proposed and its area of application shall be identified on the catalog cuts. B. Certification: Prior to final inspection, deliver to the Resident Engineer four copies of the certification that the material is in accordance with the drawings and specifications and has been properly installed. PART 2 - PRODUCTS 2.01 MATERIAL A. Conduit Size: not less than 20 mm (3/4 inch) unless otherwise shown. B. Conduit: 1. Rigid galvanized steel: Shall Conform to UL 6, ANSI C80.1. 2. Rigid aluminum: Shall Conform to UL 6A, ANSI C80.5. 3. Rigid intermediate steel conduit (IMC): Shall Conform to UL 1242, ANSI C80.6. 4. Electrical metallic tubing (EMT): Shall Conform to UL 797, ANSI C80.3. Maximum size not to exceed 105 mm (4 inch) and shall be permitted only with cable rated 600 volts or less. 5. Flexible galvanized steel conduit: Shall Conform to UL 1. 6. Liquid-tight flexible metal conduit: Shall Conform to UL 360. 7. Direct burial plastic conduit: Shall conform to UL 651 and UL 651A, heavy wall PVC or high density polyethylene (PE). 8. Surface metal raceway: Shall Conform to UL 5. C. Conduit Fittings: 1. Rigid steel and IMC conduit fittings: a. Fittings shall meet the requirements of UL 514B and ANSI/ NEMA FB1. b. Standard threaded couplings, locknuts, bushings, and elbows: Only steel or malleable iron materials are acceptable. Integral retractable type IMC couplings are also acceptable. c. Locknuts: Bonding type with sharp edges for digging into the metal wall of an enclosure. d. Bushings: Metallic insulating type, consisting of an insulating insert molded or locked into the metallic body of the fitting. Bushings made entirely of metal or nonmetallic material are not permitted. e. Erickson (union-type) and set screw type couplings: Approved for use in concrete are permitted for use to complete a conduit run where conduit is installed in concrete. Use set screws of case hardened steel with hex head and cup point to firmly seat in conduit wall for positive ground. Tightening of set screws with pliers is prohibited. E110-1 f. Sealing fittings: Threaded cast iron type. Use continuous drain type sealing fittings to prevent passage of water vapor. In concealed work, install fittings in flush steel boxes with blank cover plates having the same finishes as that of other electrical plates in the room. 2. Electrical metallic tubing fittings: a. Fittings shall meet the requirements of UL 514B and ANSI/ NEMA FB1. b. Only steel or malleable iron materials are acceptable. c. Couplings and connectors: Concrete tight and rain tight, with connectors having insulated throats. Use gland and ring compression type couplings and connectors for conduit sizes 50 mm (2 inches) and smaller. Use set screw type couplings with four set screws each for conduit sizes over 50 mm (2 inches). Use set screws of case-hardened steel with hex head and cup point to firmly seat in wall of conduit for positive grounding. d. Indent type connectors or couplings are prohibited. e. Die-cast or pressure-cast zinc-alloy fittings or fittings made of "pot metal" are prohibited. 3. Flexible steel conduit fittings: a. Conform to UL 514B. Only steel or malleable iron materials are acceptable. b. Clamp type, with insulated throat. 4. Liquid-tight flexible metal conduit fittings: a. Fittings shall meet the requirements of UL 514B and ANSI/ NEMA FB1. b. Only steel or malleable iron materials are acceptable. c. Fittings must incorporate a threaded grounding cone, a steel or plastic compression ring, and a gland for tightening. Connectors shall have insulated throats. 5. Direct burial plastic conduit fittings: a. Fittings shall meet the requirements of UL 514C and NEMA TC3. b. As recommended by the conduit manufacturer. 6. Surface metal raceway fittings: As recommended by the raceway manufacturer. 7. Expansion and deflection couplings: a. Conform to UL 467 and UL 514B. b. Accommodate, 19 mm (0.75 inch) deflection, expansion, or contraction in any direction, and allow 30 degree angular deflections. c. Include internal flexible metal braid sized to guarantee conduit ground continuity and fault currents in accordance with UL 467, and the NEC code tables for ground conductors. d. Jacket: Flexible, corrosion-resistant, watertight, moisture and heat resistant molded rubber material with stainless steel jacket clamps. D. Conduit Supports: 1. Parts and hardware: Zinc-coat or provide equivalent corrosion protection. 2. Individual Conduit Hangers: Designed for the purpose, having a pre-assembled closure bolt and nut, and provisions for receiving a hanger rod. 3. Multiple conduit (trapeze) hangers: Not less than 38 mm by 38 mm (1-1/2 by 1-1/2 inch), 12 gage steel, cold formed, lipped channels; with not less than 9 mm (3/8 inch) diameter steel hanger rods. 4. Solid Masonry and Concrete Anchors: Self-drilling expansion shields, or machine bolt expansion. PART 3 - EXECUTION 3.01 PENETRATIONS A. Cutting or Holes: 1. Locate holes in advance where they are proposed in the structural sections such as ribs or beams. Obtain the approval of the Resident Engineer prior to drilling through structural sections. 2. Cut holes through concrete and masonry in new and existing structures with a diamond core drill or concrete saw. Pneumatic hammer, impact electric, hand or manual hammer type drills are not allowed, except where permitted by the Resident Engineer as required by limited working space. E110-2 B. Fire Stop: Where conduits, wire ways, and other electrical raceways pass through fire partitions, fire walls, smoke partitions, or floors, install a fire stop that provides an effective barrier against the spread of fire, smoke and gases as specified in Section, FIRESTOPPING SYSTEMS, with rock wool fiber or silicone foam sealant only. Completely fill and seal clearances between raceways and openings with the fire stop material. C. Waterproofing: At floor, exterior wall, and roof conduit penetrations, completely seal clearances around the conduit and make watertight. 3.02 INSTALLATION, GENERAL A. Install conduit as follows: 1. In complete runs before pulling in cables or wires. 2. Flattened, dented, or deformed conduit is not permitted. Remove and replace the damaged conduits with new undamaged material. 3. Assure conduit installation does not encroach into the ceiling height head room, walkways, or doorways. 4. Cut square with a hacksaw, ream, remove burrs, and draw up tight. 5. Mechanically and electrically continuous. 6. Independently support conduit at 8’.0” on center. Do not use other supports i.e., (suspended ceilings, suspended ceiling supporting members, lighting fixtures, conduits, mechanical piping, or mechanical ducts). 7. Support within 300 mm of changes of direction, and within 300 mm of each enclosure to which connected. 8. Close ends of empty conduit with plugs or caps at the rough-in stage to prevent entry of debris, until wires are pulled in. 9. Conduit installations under fume and vent hoods are prohibited. 10. Secure conduits to cabinets, junction boxes, pull boxes and outlet boxes with bonding type locknuts. 11. Unless otherwise indicated on the drawings or specified herein, all conduits shall be installed concealed within finished walls, floors and ceilings. 3.03 CONCEALED WORK INSTALLATION 1. Conduit: pliable PVC conduit flammable resistance type 2. Align and run conduit in direct lines. 3. Install conduit through concrete beams only when the following occurs: a. Where shown on the structural drawings. b. As approved by the Resident Engineer prior to construction, and after submittal of drawing showing location, size, and position of each penetration. 4. Installation of conduit in concrete that is less than 75 mm thick is prohibited. a. Conduit outside diameter larger than 1/3 of the slab thickness is prohibited. b. Space between conduits in slabs: Approximately six conduit diameters apart, except one conduit diameter at conduit crossings. c. Install conduits approximately in the center of the slab so that there will be a minimum of 19 mm (3/4 inch) of concrete around the conduits. 3.04 EXPOSED WORK INSTALLATION A. Unless otherwise indicated on the drawings, exposed conduit is only permitted in mechanical and electrical rooms. B. Conduit for Conductors 600 volts and below: 1. Rigid steel, IMC, rigid aluminum, or EMT. Different type of conduits mixed indiscriminately in the system is prohibited. C. Align and run conduit parallel or perpendicular to the building lines. D. Install horizontal runs close to the ceiling or beams and secure with conduit straps. E110-3 E. Support horizontal or vertical runs at not over 2400 mm (eight foot) intervals. F. Surface metal raceways: Use only where shown. 3.09 EXPANSION JOINTS A. Conduits 75 mm (3 inches) and larger, that are secured to the building structure on opposite sides of a building expansion joint, require expansion and deflection couplings. Install the couplings in accordance with the manufacturer's recommendations. B. Provide conduits smaller than 75 mm (3 inches) with junction boxes on both sides of the expansion joint. Connect conduits to junction boxes with sufficient slack of flexible conduit to produce 125 mm (5 inch) vertical drop midway between the ends. Flexible conduit shall have a copper green ground bonding jumper installed. In lieu of this flexible conduit, expansion and deflection couplings as specified above for 375 mm (15 inches) and larger conduits are acceptable. 3.10 CONDUIT SUPPORTS, INSTALLATION A. Safe working load shall not exceed 1/4 of proof test load of fastening devices. B. Use pipe straps or individual conduit hangers for supporting individual conduits. Maximum distance between supports is 2.5 m (8 foot) on center. C. Support multiple conduit runs with trapeze hangers. Use trapeze hangers that are designed to support a load equal to or greater than the sum of the weights of the conduits, wires, hanger itself, and 90 kg. Attach each conduit with U-bolts or other approved fasteners. D. Support conduit independently of junction boxes, pull boxes, fixtures, suspended ceiling T-bars, angle supports, and similar items. E. Bolts supported only by plaster or gypsum wallboard are not acceptable. F. Metal Structures: Use machine screw fasteners or other devices specifically designed and approved for the application. G. Attachment by wood plugs, rawl plug, plastic, lead or soft metal anchors, or wood blocking and bolts supported only by plaster is prohibited. HChain, wire, or perforated strap shall not be used to support or fasten conduit. 3.11 BOX INSTALLATION A. Boxes for Concealed Conduits: 1. Flush mounted. 2. Provide raised covers for boxes to suit the wall or ceiling, construction and finish. B. In addition to boxes shown, install additional boxes where needed to prevent damage to cables and wires during pulling in operations. C. Remove only knockouts as required and plug unused openings. Use threaded plugs for cast metal boxes and snap-in metal covers for sheet metal boxes. D. Outlet boxes in the same wall mounted back-to-back are prohibited. A minimum 600 mm , centerto-center lateral spacing shall be maintained between boxes.) E. Minimum size of outlet boxes for ground fault interrupter (GFI) receptacles is 100 mm square by 55 mm deep, with device covers for the wall material and thickness involved. F. Stencil or install phenolic nameplates on covers of the boxes identified on riser diagrams; for example "SIG-FA JB No. 1". G. On all Branch Circuit junction box covers, identify the circuits with black marker. ---END--- E110-4 SECTION E115 CABLE TRAY PART -1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract. 1.02 SUMMARY A. Perforated hot-dipped galvanized after fabrication steel cable tray. 1.03 SUBMITTALS In accordance with Section E010, SAMPLES AND SHOP DRAWINGS, furnish the following: A. Shop Drawings: 1. Size and location of main feeders; 2. Size and location of panels and pull boxes 3. Layout of required conduit penetrations through structural elements. 4. The specific item proposed and its area of application shall be identified on the catalog cuts. B. Certification: Prior to final inspection, deliver to the Resident Engineer two copies of the certification that the material is in accordance with the drawings and specifications and has been properly installed. PART 2 – PRODUCTS 2.01 2.02 CABLE TRAY A. Cable tray shall be of the perforated type with return flanges for added rigidly and shall be manufactured from hot dip galvanized sheet steel. Minimum metal thickness shall be as follows:1. 1.2 mm for cable tray up to 200 mm wide. 2. 1.5 mm for cable tray above 200 mm wide. B. Each length of cable tray shall be provided with heavy duty galvanized steel joint pieces and joint cover plates. C. Vertical runs of cable tray in electrical switch rooms and shafts shall be provided with clip-on type galvanized sheet covers. D. Provide cable tray complete with all necessary bends. Tees crosses and risers manufactured from hot dip galvanized sheet steel and manufactured by the same factory. E. All exposed cable trays shall be covered. TRAY SUPPORTS A. As recommended by the cable tray manufactured and indicated on the plans. PART 3 – EXECUTION 3.01 CO-ORDINATION A. Co-ordinate layout of cable tray with other services to ensure that there is no conflict. E115-1 B. 3.02 Relocate cable tray as necessary to avoid building obstruction of other services. Installation A. Install cable tray level and plumb according to manufacturer’s written instructions, coordination drawings, original design and referenced standards. B. Remove burrs and sharp edges from cable trays. C. Fasten cable tray supports securely to building structure. D. Make connections to equipment with flanged fittings fastened to cable tray and to equipment. Support cable tray independently of fittings. Do not carry weight of cable tray on equipment enclosure. E. Install expansion connectors where cable tray across a building expansion joint and in cable trays runs that exceed 30 meter space connectors and set gaps as required. F. Make changes in direction and elevation standard fittings. G. Make cable tray connections using standard fittings. H. Install cable I. Seal penetrations through fire and smoke barriers according to “Firestopping” Section. J. Install cable trays with sufficient space to permit access for installing cables. 3.03 CABLE TRAYS A. On completion of cable tray installation, including fittings, inspect exposed finish. Remove burrs, dirt, and construction debris and repair damaged finishes, including chips, scratches, and abrasions. 3.04 PROTECTION A. Provide final protection and maintain conditions, in a manner acceptable to manufacturer and installer, which ensure cable tray is without damage or deterioration at the time of Substantial Completion. a. Repair damage to galvanized finishes with zinc-rich paint recommended by cable tray manufacturer. b. Repair damage to PVC or paint finishes with matching touchup coating recommended by cable tray manufacturer. 3.05 GROUNDING A. Provide a separate ground wire on all runs of cable tray bonded to the appropriate switch gear, cabinets, electrical equipment in accordance with the grounding specification section. B. Provide 10 sq. mm copper bonding jumpers across all joints. C. Test complete system for ground continuity. - - - END - - - E115-2 SECTION E120 WIRING PART 1 - GENERAL 1.01 WORK INCLUDED A. Single core and multicore 600 volt `wiring, 10mm2 and smaller. B. Fixture Wiring C. Signaling Systems Wiring D. Power Distribution wiring 1.02 REFERENCE STANTARDS A. IEC 227 B. IEC 228 C. IEC 502, 540 D. IEC 287 E. BS 6004, 6231, 6346, 7629. 1.03 SUBMITALS A. Submit product data and manufacturers literature C. Submit proposals for color coding of insulation D. Submit completed test sheets. E. Sample of cable pulling lubricant. Part 2 - PRODUCTS 2.01 MATERIALS A. Building Wiring: Concentric lay, uncoated copper with a normal maximum operating temperature of 85 C, 600V, PVC insulation. B. Power and Control wiring: Concentric lay, uncoated copper with a normal maximum operating temperature of 70 C. Insulation to be 600 V PVC with black PVC jacket. Provide white conductor insulation with indelible black numerals at 25mm intervals on control cables. C. Flame Retardant Power and control Wiring: Multi Strand, concentric lay, coated copper with a normal maximum operating temperature of 90 C and 600V flame retardant cross linked polyethylene insulation and overall cable jackets of cholorsulfonated polyethylene, all in accordance with Standards and Codes. Cable jacket to be applied over tape wrapped cable cores. D. Flame Retardant Alarm and instrument Cable: Multi strand, concentric lay, coated copper with a normal maximum operating temperature of 90 C and 600V flame retardant cross linked polyethylene insulation, cable assembly shield of combination aluminum/ mylar tape and 7 strand 0.6 mm² minimum coated copper drain wire applied to achieve 100% cover over insulated conductors and chlorosulfonated polyethylene cable jacket. Twisted pair cables with 60 mm to 90 mm lay staggered. Each pair to be numbered. E. Fixture Wire: Standard round coated copper with an operating temperature of 200 C with 600V silicone rubber insulated and braided glass jacket, all in accordance with Standards and Codes. F. Fire alarm Signal Cable: shall be fire resistant multi-core cable to conform with civil defense regulations and manufacturer recommendations. G. Lighting/Power Cable: Multicore copper conductors 600V grade PVC insulation lighting cable minimum size is 1.5 mm² and power cable minimum size is 2.5 mm². Provide one (1) larger size lighting/power cable (lighting cable size is 2.5mm2 and power cable size is 4mm²) if entire circuit length from Electrical panel board to the last lighting fixture/outlet is more than 30 meters long. E120-1 H. I. J. K. L. Loudspeaker Cable: Single pair with solid copper conductor (1.25mm diameter) in flat configuration with polyethene insulation and PVC jacket. Conductors to have a maximum DC loop resistance at 20 C of 28 ohms per kilometer and a nominal capacitance of 91 picofarads per meter. Microphone Cable: Single pair screened with stranded copper conductors (13/0.2mm) with PVC insulation lapped copper screen and PVC jacket. Conductors to have a maximum DC loop resistance of 45.7 ohms per kilometer and a nominal capacitance of 430 picofarads per meter. Attendant Call Cable: Minimum 2.5 mm² cable as described in Part 2.01A above. Slave Clock Cable: Minimum 1.5 mm² cable as described in Part 2.01A above. Control cable: Multicore 2.5 mm² cable as described in part 2.01A above. Part 3 - EXCUTION 3.01 INSTALLATION A. Ensure conductor lengths for parallel feeders are equal. B. Lace or clip conductor groups at switchgear panels, pull boxes, wire ways, etc. C. Provide grounding conductors and straps in accordance with the grounding specification Section. D. Wiring in conduits only to be installed after concrete, masonry and plastering work is complete and all conduits has been cleaned out and dried. E. Splice cables at accessible junction or outlet boxes only. F. Color codes: all wiring insulation as per equipment identifications specification. G. Terminate cables in accordance with the manufacturers’ recommendations. 1. Secondary service, feeder and branch circuit conductors shall be color coded as follows: Phases: phase "R" Brown, phase "S", Brown/orange, phase "T" Brown/ Black. Neutral : Blue Ground : Green / Yellow in combination or green a. The lighting circuit “switch legs” and 3-way switch “traveling wires” shall have color coding unique and distinct (i.e. pink and purple) from the color coding indicated above. The unique color codes shall be solid and in accordance with the NEC. Field coordinates for a final color coding with the Resident Engineer. 2. Use solid color compound or solid color coating branch circuit conductors and neutral sizes. 4. For modifications and additions to existing wiring systems, color coding shall conform to the existing wiring system. 5. Color code for isolated power system wiring shall be in accordance with the NEC. 3.02 FIELD TESTING Field testing: Insulation resistance of all conductors shall be tested. Each conductor shall have its insulation resistance tested after the insulation is completed and all splices, taps and connections are made except connection to or into its source and point (or points) of termination. Insulation resistance of conductors which are to operate at 600 volts or less shall be tested by using a Biddle Megger of not less than 1000 volts d-c, insulation resistance of conductors rated at 600 volts shall be free of shorts and grounds and have minimum resistance phase-to-phase and phase-to-ground of at least 10 mega ohms. Conductors that do not exceed insulation resistance values listed above shall be removed at Contractor's expense and replaced and test repeated. The Contractor shall furnish all instruments and personnel required for tests, shall tabulate readings observed, and shall forward copies of the test readings to the Owner in accordance with Section E010. These test reports shall identify each conductor tested, date and time of test and weather conditions. Each test shall be signed by the party making the test. - - - END - - - E120-2 SECTION E122 600 VOLT CABLE PART 1 - GENERAL 1.01 WORKED INCLUDED 2 Single and multi core insulated power conductors rated 600 volts, sized 10 mm and greater. 1.02 RELATED WORK A. Grounding and Bonding B. Wiring 1.03 REFERENCE STANDARDS A. B.S. 6360, 6004, 6207, 6476, 6346, 5468 B. IEC 502 C. IEC 228 D. IEC 287 1.04 SUBMITTALS A. Provide Product Data and manufacturers literature B. Provide Operation and Maintenance Data D. Submit completed factory any site test sheets E. Sample of cable pulling lubricant PART 2 - PRODUCTS 2.01 GENERAL A. Cables shall be one, three of four cores consisting of 99% conductivity, bare annealed stranded copper conductors rated at a normal maximum operating temperature of 90 degrees 2 B. Insulation for cables 10 mm and greater shall be of extruded semi-conducting cross-linked polyethylene, meeting standards requirements. A semi-conducting tape may be used under the polyethylene. C. Provide a PVC overall jacket on all cables, with a durable marking on the surface of the jacket at intervals not exceeding 610mm. marking shall include manufacturers name, conductor size and voltage class of cable. D. Cable capacity and electrical characteristics shall conform with specified codes and standards. E. Provide a ground wire with each circuit sized in accordance with the grounding specification Section. Ground wire shall be bare, concentric lay copper. F. Where armoring is required, it shall be steel strip armor on single core cables and galvanized steel or tape armor on multi-core cables. 2.02 SPLICES AND TERMINATIONS A. Cable splices and terminations shall be furnished in kit form and shall conform to the recommendations of the cable manufacturer. All material shall be furnished in factory sealed packages and shall not be opened until required for use. B. Splices shall be suitable for installation in manholes C. Terminal connectors shall be pressure; bolted clamp or compression type. 2.03 CABLE TIES AND CABLE MARKERS A. Lacing material for site installed cable shall be non-releasing nylon ties. E122-1 B. 2.04 Tie-on cable markers shall be provided in accordance with equipment identification specification Section. CU/XLPE/SWA/PVC: A. CU/XLPE/SWA/PVC: 1. To BS 5468, 1000V grade 2 3. 4. 5. 6. 7. 8. 9. 10. 11. 2.05 Conductors: Plain annealed copper to BS 6360 Cables shall comprise of plain copper, stranded circular conductors insulated with an adequate thickness of extruded cross linked polythene (XLPE). Conductors shall be laid up together and wormed circular with suitable pre-formed fillers and worming, bound with polythene terephthalate (PTP) tape and covered with an extruded PVC sheath minimum 1.4 mm thick. Multicore cables shall have steel wire or tape armoring, extruded sheath of black PVC. Single core cables shall be unarmored, unless otherwise specified, with an extruded black PVC outer sheath. Outer sheath of single and multicore shall be at least 2.5mm thick. Design electrical stress at any point in the insulation shall not exceed 3KV per mm. Conductor screen: non-metallic comprising of either: a. Semi-conducting tape; or b. A layer of extruded semi-conducting material. The electro-static screen over insulation shall comprise of a non-metallic layer of semi-conducting tape or extruded semi-conducting material applied over the insulation and in direct contact with it, followed by a layer of copper tape applied helically over the semi- conducting layer to ensure close contact throughout. Prevent void formation in insulation by careful control of its passage through the temperature graded water baths. XLPE/SWA/PVC/LSF A. The electrical supply from the main LV switchboard to the local distribution boards shall be distributed via XLPE/SWA/PVC/LSF cables with copper conductors, installed on cable trays. PART 3 - EXECUTION 3.01 INTERNAL CABLE INSTALLATION A. Support internal horizontal and vertical runs on cable tray using non-ferrous clamps at 1 meter intervals. B. Arrange multicore cables to run parallel on tray with a lateral spacing of the diameter of the largest cable. C. Arrange single core cables with phases in trefoil formation providing one cable diameter space between trefoil groups. D. Where cables are routed through walls or floors, the opening between the cables and the structure shall be sealed such that the fire resistance of the sealing barrier is at least as great as the surrounding structure. 3.02 EXTERNAL CABLE INSTALLATION A. Immediately prior to the placement of each cable or cable group, the raceway route to be followed shall be inspected and ascertained to be complete in installation and free of all materials detrimental to the cable or its placement. All cables assigned to a particular duct or conduit shall be grouped and pulled in simultaneously, using cable grips or pulling eyes and acceptable lubricants. E122-2 B. C. D. E. F. G. H. I. J. K. All cables shall be carefully checked both as to size and length before being pulled into conduits or ducts. Cable pulled into the wrong conduit or duct or cut too short to rack, train, and splice as specified herein, shall be removed and replaced. Cable in manholes, Shafts,… etc.: Cable shall be supported at all times without short bends or excessive sags and shall not be permitted to lie on the manhole floor. Cable ends must not be submerged. Cable racks, saddle supports or trays shall be provided for permanent support. Temporary support required during placement shall be with rope slings, timbers, or alternate method acceptable to the Client Engineer. Cable shall be located in manholes to provide minimum interference with other cables to be installed or installation of future cables in spare conduits. Cable Pulling: Pulling shall be done with nylon or rope recommended by cable manufacturer. Cable Grips: Factory installed pulling eyes shall be used for pulling cable where they are 2 available. Woven wire cable grips shall be used to pull all single conductor cable, 70 mm 2 and larger. Pulling loops shall be used to pull single conductor cable smaller than 70 mm . When a cable grip or pulling eye is used for pulling, the area of the cable covered by the grip or seal plus 150 mm shall be cut off and discarded when the pull is completed. Inspection: The outside of each cable reel shall be carefully inspected and protruding nails, fastenings, or other objects which might damage the cable shall be removed. A thorough visual inspection for flaws, breaks, or abrasions in the cable sheath shall be made as the cable leaves the reel, and the pulling speed shall be slow enough to permit this inspection. Damage to the sheath or finish of the cable shall be sufficient cause for rejecting the cable. Cable damaged in any way during installation shall be replaced. Pulling Tension: The pulling tension of any cable shall not exceed the maximum tension recommended by the cable manufacturer. Pulling mechanisms of both the manual and power types used by the Contractor shall have the rated capacity in tons clearly marked on the mechanism. Whenever the capacity of the pulling mechanism exceeds the recommended pulling tension of the cable as given by the cable manufacturer, a dynamometers shall be used to show the tension on the cable and the indicator shall be constantly watched. If any excessive strain develops, the pulling operation shall be stopped at once and the difficulty determined and corrected. Sidewall Pressure: To avoid insulation damage from excessive sidewall pressure at bends in duct and conduit runs, the pulling tension in kilograms at a bend shall not exceed 450 times the radius of the bend in metres. Cable Bends: Extreme care shall be exercised during the placement of all cable to prevent tension and bending conditions in excess of the manufacturer's recommendations. The permanent radius of bend after cable installation shall be in accordance with the cable manufacturer's recommendations. Supports: All cable supports and securing devices shall have bearing surfaces located parallel to the surfaces of the cable sheath and shall be installed to provide adequate support without deformation of the cable jackets or insulation. Final inspection shall be made after all cable is in place and, where supports, bushings, and end bells deform the cable jacket, additional supports shall be provided. Additional cable protection such as a wrapping of light rubber belting, friction tape, or similar materials shall be provided when required. Cable in vertical runs shall be supported by woven wire grips in accordance with the Code requirements. Cable Identification: The Contractor shall identify all cables in the locations specified in the equipment identification spec Section. Moisture Seals: Each cable shall be kept sealed except when termination and splicing work is being performed. The ends of all cables shall be sealed with heat shrinkable caps. Cap sizes shall be as recommended by the cap manufacturer for the cable outside diameter and insulation. Caps shall contain sufficient adhesive that shrinkage of the cap during application results in formation of a positive watertight seal capable of withstanding complete immersion or total exposure without permitting the entrance of moisture. E122-3 L. M. N. 3.03 Before and after pulling, the leading and seal of each length of cable shall be examined and repaired if necessary. All cut cable ends shall be promptly sealed after cutting except those to be spliced or terminated. Crimping Tools: Crimping tools used to secure conductors in compression type connectors or terminal lugs shall be those made for that purpose and for the conductor sizes involved. Crimping tools shall be a product approved by the connector manufacturer. The Contractor shall establish and maintain a tool certification program to ensure that crimping tools are kept in accurate operating condition. Termination: Cable shall be terminated in accordance with the following requirements. - Train cable in place and cut squarely to required length. Avoid sharp bends. - Install terminals or terminal connectors as required, ensuring a firm metal-to-metal contact. - Insulate each connection of cable to an insulated conductor (whether cable, bus, or equipment bushing). The insulation shall cover all exposed surfaces of the conductors; the insulation voltage level of the completed termination shall be not less than the insulation voltage level of the connected conductors. Insulation of terminations shall be as specified in the following paragraphs. Insulation of Termination in 600 volt Cable: Terminations which require insulation in cable rated 600 volts or less shall be insulated in accordance with the following requirements: - All exposed conductor and connector surfaces shall be covered with a minimum of three half-lapped layers of self-vulcanizing rubber insulating tape. - A minimum of three half-lapped layers of polyvinyl chloride electrical tape shall be applied over the rubber tape. The polyvinyl chloride tape shall extend a minimum of two cable diameters over the cable jacket and a similar distance over other conductor insulation or connector requiring insulation. Field Testing Insulation resistance of all conductors shall b tested. Each conductor shall have its isolation resistance tested after the installation is completed and all splices, taps and connections are made except connection to or into its source and point (or points) of termination. Insulation resistance of conductors which are to operate at 600 volts roles shall be tested by using a Biddle Megger of not less than 1000 volts d-c. Insulation resistance of conductors rated at 600 volts shall be free of shorts and grounds and have a minimum resistance phase-to-phase and phase-to-ground of at least 10 mega ohms. Conductors that do not exceed insulation resistance valves listed above shall be removed at Contractor’s expense and replaced and test repeated. The Contractor shall furnish all instruments and personnel required for tests, shall tabulate readings observed, and shall forward copies of the test readings to the Owner in accordance with Section E10. These test reports shall identify each conductor tested, date and time of test and weather conditions. Each test shall be signed by the party making the test. - - - END - - - E122-4 SECTION E125 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. This section specifies the general grounding and bonding requirements for electrical equipment and operations to provide a low impedance path for possible ground fault currents. B. “Grounding electrode system” refers to all electrodes required by NEC, as well as made, supplementary, and lightning protection system grounding electrodes. C. The terms “connect” and “bond” is used interchangeably in this specification and have the same meaning. 1.02 SUBMITTALS A. Submit in accordance with Section E050, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. B. Shop Drawings: 1. Clearly present enough information to determine compliance with drawings and specifications. 2. Include the location of system grounding electrode connections and the routing of aboveground and underground grounding electrode conductors. C. Test Reports: Provide certified test reports of ground resistance. D. Certifications: Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: 1. Certification that the materials and installation are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installation has been properly installed and tested. PART 2 - PRODUCTS 2.01 GROUNDING AND BONDING CONDUCTORS A. Equipment grounding conductors shall be UL 44 or UL 83 insulated stranded copper, except that sizes 6 mm² and smaller shall be solid copper. Insulation color shall be continuous green for all equipment grounding conductors. B. Bonding conductors shall be ASTM B8 bare stranded copper, except that sizes No. 6 mm² and smaller shall be ASTM B1 solid bare copper wire. C. Conductor sizes shall not be less than shown on the drawings, or not less than required by the NEC, whichever is greater. 2.02 GROUND RODS A. Steel or copper clad steel, 0.75 in [19 mm] diameter by 3 Meter long, conforming to UL 467. B. Quantity of rods shall be as required to obtain the specified ground resistance, as shown on the drawings. 2.03 CONCRETE ENCASED ELECTRODE Concrete encased electrode shall be No. 25 mm² bare copper wire, installed per NEC. E125 - 1 2.04 MEDIUM VOLTAGE SPLICES AND TERMINATIONS Components shall meet or exceed UL 467 and be clearly marked with the manufacturer, catalog number, and permitted conductor size(s). 2.05 GROUND CONNECTIONS A. Below Grade: Exothermic-welded type connectors. B. Above Grade: 1. Bonding Jumpers: Compression-type connectors, using zinc-plated fasteners and external tooth lockwashers. 2. Connection to Building Steel: Exothermic-welded type connectors. 3. Ground Busbars: Two-hole compression type lugs, using tin-plated copper or copper alloy bolts and nuts. 4. Rack and Cabinet Ground Bars: One-hole compression-type lugs, using zinc-plated or copper alloy fasteners. 2.06 EQUIPMENT RACK AND CABINET GROUND BARS Provide solid copper ground bars designed for mounting on the framework of open or cabinetenclosed equipment racks with minimum dimensions of 4 mm thick x 19 mm wide. 2.07 GROUND TERMINAL BLOCKS At any equipment mounting location (e.g., backboards and hinged cover enclosures) where racktype ground bars cannot be mounted, provide screw lug-type terminal blocks. 2.08 GROUNDING BUS Pre-drilled rectangular copper bar with stand-off insulators, minimum 6.3 mm thick x 100 mm high in cross-section, length as shown on drawings, with 7.1 mm holes spaced 28 mm apart. PART 3 - EXECUTION 3.01 GENERAL A. Ground in accordance with the NEC, as shown on drawings, and as specified herein. B. System Grounding: 1. Secondary service neutrals: Ground at the supply side of the secondary disconnecting means and at the related transformers. 2. Separately derived systems (transformers downstream from the service entrance): Ground the secondary neutral. C. Equipment Grounding: Metallic structures, including ductwork and building steel, enclosures, raceways, junction boxes, outlet boxes, cabinets, machine frames, and other conductive items in close proximity with electrical circuits, shall be bonded and grounded. 3.02 INACCESSIBLE GROUNDING CONNECTIONS Make grounding connections, which are normally buried or otherwise inaccessible (except connections for which access for periodic testing is required), by exothermic weld. 3.03 MEDIUM VOLTAGE EQUIPMENT AND CIRCUITS A. Switchgear: Provide a bare grounding electrode conductor from the switchgear ground bus to the grounding electrode system. B. Duct Banks and Manholes: Provide an insulated equipment grounding conductor in each duct containing medium voltage conductors, sized per NEC except that minimum size shall be 25 mm². Bond the equipment grounding conductors to the switchgear ground bus, to all manhole E125 - 2 hardware and ground rods, to the cable shielding grounding provisions of medium-voltage cable splices and terminations, and to equipment enclosures. C. Pad-Mounted Transformers: 1. Provide a driven ground rod and bond with a grounding electrode conductor to the transformer grounding pad. 2. Ground the secondary neutral. D. Lightning Arresters: Connect lightning arresters to the equipment ground bus or ground rods as applicable. 3.04 SECONDARY VOLTAGE EQUIPMENT AND CIRCUITS A. Main Bonding Jumper: Bond the secondary service neutral to the ground bus in the service equipment. B. Metallic Piping, Building Steel, and Supplemental Electrode(s): 1. Provide a grounding electrode conductor sized per NEC between the service equipment ground bus and all metallic water pipe systems, building steel, and supplemental or made electrodes. Provide jumper insulating joints in the metallic piping. All connections to electrodes shall be made with fittings that conform to UL 467. 2. Provide a supplemental ground electrode and bond to the grounding electrode system. C. Service Disconnect (Separate Individual Enclosure): Provide a ground bar bolted to the enclosure with lugs for connecting the various grounding conductors. D. Switchgear, Switchboards, Unit Substations, Panel boards, Motor Control Centers and Panel boards, Engine-Generators, and Automatic Transfer Switches: 1. Connect the various feeder equipment grounding conductors to the ground bus in the enclosure with suitable pressure connectors. 2. For service entrance equipment, connect the grounding electrode conductor to the ground bus. 3. Provide ground bars, bolted to the housing, with sufficient lugs to terminate the equipment grounding conductors. 4. Connect metallic conduits that terminate without mechanical connection to the housing, by grounding bushings and grounding conductor to the equipment ground bus. 3.05 RACEWAY A. Conduit Systems: 1. Ground all metallic conduit systems. All metallic conduit systems shall contain an equipment grounding conductor. 2. Non-metallic conduit systems, except non-metallic feeder conduits that carry a grounded conductor from exterior transformers to interior or building-mounted service entrance equipment, shall contain an equipment grounding conductor. 3. Conduit that only contains a grounding conductor, and is provided for its mechanical protection, shall be bonded to that conductor at the entrance and exit from the conduit. 4. Metallic conduits which terminate without mechanical connection to electrical equipment housing by means of locknut and bushings or adapters, shall be provided with grounding bushings. Connect bushings with a bare grounding conductor to the equipment ground bus. B. Feeders and Branch Circuits: Install equipment grounding conductors with all feeders and power and lighting branch circuits. C. Boxes, Cabinets, Enclosures, and Panel boards: 1. Bond the equipment grounding conductor to each pullbox, junction box, outlet box, device box, cabinets, and other enclosures through which the conductor passes (except for special grounding systems for intensive care units and other critical units shown). 2. Provide lugs in each box and enclosure for equipment grounding conductor termination. D. Wire way Systems: E125 - 3 E. F. G. H. I. 1. Bond the metallic structures of wire way to provide 100% electrical continuity throughout the wire way system, by connecting a No. 6 AWG [16 mm²] bonding jumper at all intermediate metallic enclosures and across all section junctions. 2. Install insulated No. 16 mm² bonding jumpers between the wire way system, bonded as required above, and the closest building ground at each end and approximately every 6 Meter. 3. Use insulated No. 16 mm² bonding jumpers to ground or bond metallic wire way at each end for all intermediate metallic enclosures and across all section junctions. 4. Use insulated No. 16 mm² bonding jumpers to ground cable tray to column-mounted building ground plates (pads) at each end and approximately every 15 Meter. Receptacles shall not be grounded through their mounting screws. Ground receptacles with a jumper from the receptacle green ground terminal to the device box ground screw and a jumper to the branch circuit equipment grounding conductor. Ground lighting fixtures to the equipment grounding conductor of the wiring system when the green ground is provided; otherwise, ground the fixtures through the conduit systems. Fixtures connected with flexible conduit shall have a green ground wire included with the power wires from the fixture through the flexible conduit to the first outlet box. Fixed electrical appliances and equipment shall be provided with a ground lug for termination of the equipment grounding conductor. Raised Floors: Provide bonding of all raised floor components. //See details on the drawings. // Panel board Bonding in Patient Care Areas: The equipment grounding terminal buses of the normal and essential branch circuit panel boards serving the same individual patient vicinity shall be bonded together with an insulated continuous copper conductor not less than No. 10 AWG [16 mm²]. These conductors shall be installed in rigid metal conduit. 3.06 CORROSION INHIBITORS When making ground and ground bonding connections, apply a corrosion inhibitor to all contact surfaces. Use corrosion inhibitor appropriate for protecting a connection between the metals used. 3.07 CONDUCTIVE PIPING A. Bond all conductive piping systems, interior and exterior, to the grounding electrode system. Bonding connections shall be made as close as practical to the equipment ground bus. B. In operating rooms and at intensive care and coronary care type beds, bond the gases and suction piping at the outlets directly to the room or patient ground bus. 3.08 LIGHTNING PROTECTION SYSTEM Bond the lightning protection system to the electrical grounding electrode system. 3.09 ELECTRICAL ROOM GROUNDING Building Earth Ground Busbars: Provide ground busbar and mounting hardware at each electrical room and connect to pigtail extensions of the building grounding ring. 3.10 GROUND RESISTANCE A. Grounding system resistance to ground shall not exceed 1 ohm. Make any modifications or additions to the grounding electrode system necessary for compliance without additional cost to the owner. Final tests shall ensure that this requirement is met. B. Resistance of the grounding electrode system shall be measured using a four-terminal fall-ofpotential method as defined in IEEE 81. Ground resistance measurements shall be made before the electrical distribution system is energized and shall be made in normally dry conditions not fewer than 48 hours after the last rainfall. Resistance measurements of separate grounding electrode systems shall be made before the systems are bonded together below grade. The E125 - 4 combined resistance of separate systems may be used to meet the required resistance, but the specified number of electrodes must still be provided. C. Services at power company interface points shall comply with the power company ground resistance requirements. D. Below-grade connections shall be visually inspected by the //Resident Engineer// //COTR// prior to backfilling. The contractor shall notify the //Resident Engineer// //COTR// 24 hours before the connections are ready for inspection. ---END--- E125 - 5 SECTION E130 BOXES PART 1 - GENERAL 1.01 SUMMARY A. This section specifies the furnishing and installation of outlet and switch boxes, floor boxes, junction boxes and pull boxes. 1.02 REFERENCE STANDARDS A. BS4607 PVC boxes B. IEC-670 C. BS 1363 D. BS-4662 1.03 SUBMITTALS A. Provide product data on the following: 1- Floor boxes. 2- Fire-rated poke-through units. PART 2 - PRODUCTS 2.01 OUTLET BOXES A. Flush Wiring Accessories Boxes. Provide PVC boxes of sufficient size to accommodate wiring accessories to be installed at outlet or switch. Provide an extension ring for the device(s) to be installed. Square or rectangular boxes may be used. Unless otherwise noted, provide minimum 3.5 cm deep by 7X7 cm minimum size box. B. Exposed Wiring Accessories Boxes. Provide PVC boxes for surface mounting in areas having exposed rigid PVC conduit systems and metallic boxes for surface mounting in areas having exposed rigid metallic conduits. C. Boxes for Lighting Fixtures. Provide PVC circular boxes as required to properly support ceiling and bracket-type lighting fixtures. Unless otherwise noted, provide 3 cm deep by 6 cm diameter. D. Masonry Boxes. Provide galvanized steel, 3.5 cm deep, and masonry boxes for all devices installed in masonry walls. 2.02 JUNCTION, PULL AND SPLICE BOXES A. Construction. Provide PVC boxes conforming to BS 4607. B. Interior Spaces. Provide BS 4662 type boxes at least 3.5 cm deep. C. Exterior Spaces. Provide BS 4662 12X type boxes at least 3.5 cm deep. D. Embedded. Provide BS 4662 12X cast iron type with flush flanged cover when cast in concrete. 2.03 FIRE-RATED POKE-THROUGH UNITS A. Construction. Through-floor units shall comply with BS 4662. B. Fire Rating. Through-floor units shall be classified with a fire rating of 2 hours in a floor which is 6 cm thick. C. Box and Conduit. Under floor junction box and conduit shall be self supporting without the attachment of an above-floor fitting. The integral fire barrier must incorporate a cold smoke barrier to prevent the passage of smoke when heat is not present. The junction box shall be 12 cm square by 8 cm deep with knockouts to accommodate up to 1-inch conduits. Box and conduit shall be provided with separation barriers for combination power and communication units. Through-floor unit shall allow replacement of original service fittings with different style service fittings of similar or dissimilar service function, including abandonment condition. E130 - 1 D. Above-Floor Fittings. Provide die-cast aluminum above-floor fitting with satin chrome finished cover. Provide a combination power and communication fitting. Power section shall be equipped with a 15ampere, 220-volt. Communication section shall have a cover plate with a 5/8-inch bushed opening. PART 3 – EXECUTION U 3.01 OUTLET BOXES A. Flush Boxes. Unless otherwise indicated, mount all outlet boxes flush within 6 mm of the finished wall or ceiling line. Provide extension rings where required to extend the box forward in conformance to BS and IEC requirements. Attach ring with at least two machine screws. Securely fasten outlet boxes. Provide plaster covers for all boxes in plastered walls and ceilings. B. Fixture Boxes. Where boxes for suspended lighting fixtures are attached to and supported from suspended ceilings, adequately distribute the load over the ceiling support members. C. Mounting Height. Mounting height of a wall-mounted outlet box means the height from finished floor to horizontal center line of the cover plate. Where outlets are indicated adjacent to each other, mount these outlets in a symmetrical pattern with all tops at the same elevation. Where outlets are indicated adjacent, but with different mounting heights, line up outlets to form a symmetrical vertical pattern on the wall. Verify the final location of each outlet with Owner's representative before rough-in. Remove and relocate any outlet box placed in an unsuitable location. D. Back-to-Back Boxes. Do not connect outlet boxes back to back unless approval is obtained from the Owner's representative. Where such a connection is necessary to complete a particular installation, fill the voids around the wire between the boxes with sound insulating material. E. Box Openings. Provide only the conduit openings necessary to accommodate the conduits at the individual location. 3.02 FLOOR BOXES A. Verify locations of all floor boxes with the Owner's representative before installation. Completely envelope floor boxes in concrete except at the top. Increase slab thickness at boxes if required to obtain a minimum of 30 mm of concrete below bottom of box. Adjust covers flush with finished floor. 3.03 JUNCTION AND PULL BOXES A. Installation. Install boxes as required to facilitate cable installation in raceway systems. Generally provide boxes in conduit runs of more than 30 meters or as required in Section E110. B. Covers. Provide boxes so that covers are readily accessible and easily removable after completion of the installation. Include suitable access doors for boxes above inaccessible ceilings. Select a practical size for each box and cover. 3.04 FIRE-RATED POKE-THROUGH UNITS A. Installation. Floor slab or deck shall be core-drilled to accept through floor conduit unit. Install per manufacturer's recommendations. ---END--- E130 - 2 SECTION E140 WIRING ACCESSORIES PART 1 - GENERAL 1.01 DESCRIPTION This section specifies the furnishing, installation and connection of wiring accessories. 1.02 1.03 REFERENCE STANDARDS A. BS 3676, 1363. B. IEC. C. ANSI/UL 20 - General-Use Snap Switches. D. ANSI/UL 498 - Attachment Plugs and Receptacles. E. NEMA WD 1 - General Requirements for Wiring Devices. SUBMITTALS A. In accordance with Section REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, construction materials, grade and termination information. C. Manuals: Two weeks prior to final inspection, deliver two copies of the following to the Resident Engineer: Technical data sheets and information for ordering replacement units. D. Certifications: Two weeks prior to final inspection, submit two copies of the following to the Resident Engineer: Certification by the Contractor that the devices comply with the drawings and specifications, and have been properly installed, aligned, and tested. PART 2 – PRODUCTS 2.01 WALL SWITCHES A. General 1. Body and base shall be fully enclosed type, fire resistant, non-absorptive thermosetting phenolic compound. 2. Mounting yoke shall be corrosion resistant metal with plastic ears. 3. Switches shall be flush mounted and wired with terminals of screw clamp type. Wiring terminal shall be suitable for holding two 4 mm2 wires. 4. Color: all emergency switches shall be red. Coordinate color of all other switches with the site engineer prior to ordering. 5. Rating: 15 Amps, 220 Volts, 50 Hz. B. Lighting Switches: 1. Lighting switches shall be snap type, in accordance with code, heavy duty, general use type, and single pole, double pole, single, two-way or intermediate as shown on the drawings. E140-1 2. 3. 4. 2.02 2.03 Quick-Make, quick-break type with silver alloy contacts in arc resisting molded base, with toggle, rocker or push-button as specified, for inductive or resistive loads up to full rated capacity, and arranged for side and/or back connection. Water Proof Switch: Installed in wet area such as mechanical rooms, outdoors or as shown on drawings, with waterproof plate, water proof outlet box, IP44 enclosure. Double Pole Pilot Switch: rated as shown on the drawings, 230V AC, tumbler operated with red neon pilot light for off position. Switch is to be mounted to flush or surface box, as indicated on the drawings. Provided with cord outlet and cord extension to equipment controlled. RECEPTACLES 1. Generally: all receptacles, unless otherwise indicated, shall have injection molded plastic base with self-adjusting, non-expanding contacts to prevent permanent distortion, flush mounted and arranged for side and/or back connection and with screw terminals accepting at least three parallel branch-circuit wires. 2. Color: all emergency outlets shall be used. Coordinate color of all other outlets with the site engineer prior to ordering. 3. Mounting yokes shall be corrosion resistant metal. 4. Bodies shall be ivory in color. 5. One or more of the following receptacles shall be provided as shown on the drawings: 1. Single receptacle, polarized, grounding type, with three rectangular pin-holes two poles and earth, rated 16A, 230V. Switched, with robust shutter mechanism operated by earth pin. 2. Duplex receptacle: are to be mounted in parallel under one common plate with break-off feature for two circuit connection. 3. Weatherproof receptacle: 16A, 230V, 2 pole plus earth, enclosed in surface mounted cast-metal box and with spring-retained gasket hinged flap cover. Receptacle splash sparkles type and proof to IP54. Outlet is to be used. 4. Sparkless Receptacle: Outlet: type is similar to weather proof outlet, but to be used in operating theaters and without the spring retained gasket hinged flap cover. 5. Power Receptacles: Single Outlet, singe phase, three wire, 30A, 230V, polarized with L-shaped earth contact, splash proof mold cast metal plated and matching plug. Outlet to be provided with an on-off switch. 6. Industrial Socket Outlet: 3 phase, 16 A or 32A, 3P+N+E, 220-250V, single, with aluminum alloy enclosure, interlocked switch and matching plug. 7. Shaver Receptacle: Single receptacle complete with double around isolating transformer with thermal overload protection, on/off switch and pilot light indicator. Receptacle to accept shaver plug tops to British, American and European Standards. DIMMER SWITCH E140-2 1. 2. 3. 4. 5. 2.04 Dimmer switches should be used to control individual incandescent or fluorescent lighting circuits. The dimmer switch shall be of electronic with thermostat control, factory calibrated, of suitable and rated for type and number of lamps indicated on the drawings for operation at 220 volts, 50 Hz. The dimmer switch shall be complete with and on/off toggle switch and a sliding dimmer capable of smooth continuous changes of lighting intensity form 1% for incandescent lamps and from 5% for fluorescent up to 100% light output. Dimmer switch shall be radio frequency interference shielded and capable of operating at 40 degrees C ambient temperature. Components are to be designed, rated and installed so that dimmer operates continuously at any setting. Components are to be installed in separate enclosure or as part of dimmer control panel as indicated on the drawings. WALL PLATES A. Wall plates for switches and receptacles shall be type 302 stainless steel or smooth nylon . Oversize plates are not acceptable. B. Color shall be ivory unless otherwise specified. C. Standard NEMA design, so that products of different manufacturers will be interchangeable. Dimensions for openings in wall plates shall be accordance with NEMA WD 6. D. For receptacles or switches mounted adjacent to each other, wall plates shall be common for each group of receptacles or switches. E. In psychiatric areas, wall plates shall be 302 stainless steel, have tamperproof screws and beveled edges. F. Wall plates for data, telephone or other communication outlets shall be as specified in the associated specification. G. Duplex Receptacles on Emergency Circuit: 1. Bodies shall be red in color. Wall plates shall be red with the word "EMERGENCY" engraved in 6 mm, (1/4 inch) white letters. PART 3 - EXECUTION 3.01 INSTALLATION A. Installation shall be in accordance with the NEC and as shown as on the drawings. B. Ground terminal of each receptacle shall be bonded to the outlet box with an approved green bonding jumper, and also connected to the green equipment grounding conductor. C. Outlet boxes for light and dimmer switches shall be mounted on the strike side of doors. D. Provide barriers in multi gang outlet boxes to separate systems of different voltages, Normal Power and Emergency Power systems, and in compliance with the NEC. E. Coordinate with other work, including painting, electrical boxes and wiring installations, as necessary to interface installation of wiring devices with other work. Coordinate the electrical work with the work of other trades to ensure that wiring device flush outlets are positioned with box openings aligned with the face of the surrounding finish material. Pay special attention to installations in cabinet work, and in connection with laboratory equipment. F. Exact field locations of floors, walls, partitions, doors, windows, and equipment may vary from locations shown on the drawings. Prior to locating sleeves, boxes and chases for roughing-in of conduit and equipment, the Contractor shall coordinate exact field location of the above items with other trades. In addition, check for exact direction of door swings so that local switches are properly located on the strike side. G. Install wall switches 1200mm above floor, OFF position down. H. Install wall dimmers 1200mm above floor; derate ganged dimmers as instructed by manufacturer; do not use common neutral. E140-3 I. Install convenience receptacles 400mm above floor, 152mm above counter backsplash or workbenches. Install specific-use receptacles at heights shown on the drawings. J. Label device plates with a permanent adhesive label listing panel and circuit feeding the wiring device. K. Test wiring devices for damaged conductors, high circuit resistance, poor connections, inadequate fault current path, defective devices, or similar problems using a portable receptacle tester. Correct circuit conditions, remove malfunctioning units and replace with new, and retest as specified above. L. Test GFCI devices for tripping values specified in UL 1436 and UL 943. ---END--- E140-4 SECTION E281 LOW-VOLTAGE POWER FACTOR CAPACITORS PART 1 – GENERAL 1.01 SUMMARY A. Section includes design, supply, install and test power-factor correction capacitors and accessories. 1.02 SUBMITTALS A. Product Data: Submit outline and mounting dimensions, weights, voltage and capacity ratings, fusing and accessories. 1.03 CLOSEOUT SUBMITTALS A. Project Record Documents: Record actual locations, ratings, and connections to distribution system of each capacitor. B. Operation and Maintenance Data: Include cell and fuse replacement instructions. 1.04 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years [documented] experience. 1.05 APPLICABLE STANDARDS A. Radio frequency interference suppression, as BS EN 55014:1993. PART 2 - PRODUCTS 2.01 ENERAL A. The contractor shall supply, install and connect a complete Capacitor Bank with control equipment for automatically controlling the connection and disconnection of capacitances in response to changes in the load power factor. The bank shall be free standing individual unit or part of the switchboard as indicated on the Drawings. The bank shall provide a complete automatic regulation of the connected capacitor power at peak and off peak times. B. The bank shall be fully assembled and internally connected. All equipment shall be suitable for continuous operation within the specified ambient conditions. C. The capacitor banks shall comprise one cubicle for protection and control equipment and steel racks for the capacitor units. D. A discharge resistor shall be fitted in the terminal box of each capacitor unit. E. The set of equipment for one capacitor 'step' shall comprise one triple pole contactor and a three phase fuse unit with fuses. F. The cubicle shall contain busbars for the main supply cable, terminal blocks for leads for the current transformer, control lead fuses. A reactive power regulator, together with capacitor step indicator lamps shall be mounted on the door of the cubicle. A shunt connected harmonic filter shall be included in the capacitor bank assembly. G. The equipment ratings shall be selected to give a generous margin to withstand the high capacitor currents due to harmonics on the system voltage. H. The equipment shall comply with BSEN 55014:1993 with respect to electro- magnetic radio interference. 2.02 CAPACITORS A. Capacitors shall be of proven and established design. Capacitors shall conform to IEC-831-1,2 B. Capacitor elements shall comprise a winding of metalized film dielectric and incorporate an internal fuse link, all resin encapsulated and mounted in plastic container. All capacitors shall be self healing type. C. Capacitors shall be low loss type. Losses shall be less than 0.5 watts per KVAR. D. Capacitors shall have a dielectric voltage rating of 480 V 3 phase, 50 HZ. E281 - 1 E. Capacitor units shall comprise of a sheet steel enclosure incorporating a number of capacitor elements. The enclosure shall be filled with granules or suitable proven alternative to absorb the energy of any major element failure. F. Unit of equal capacitance shall be interchangeable. G. Every capacitor shall be capable of operating for prolonged periods, without damage, at voltage 10 percent higher than the rated voltage. H. All capacitors shall be capable of operating without damage under conditions in which the current through it has an r.m.s. value exceeding by 15 percent the current corresponding to the rated (sinusoidal) voltage and frequency. I. Each capacitor shall be labeled to warn of possible voltage damages. 2.03 ROTECTION A. The capacitor banks shall be equipped with dust-tight, hose-proof terminal boxes, to IP55. B. The surface treatment of the capacitor units and the cubicles shall be suitable for outdoor installations. The sheet-metal surface shall be treated with primer and finished in two-component baked enamel. C. The control equipment cubicle shall be provided with ventilation openings if used in door only. D. Each cubicle and all of the equipment within it shall be so arranged that every item of apparatus is readily accessible of adjustment, where this may be necessary and for maintenance. 2.04 OWER FACTOR REGULATOR A. The power factor regulator shall be microprocessor based and shall be programmable at site. B. The Power Factor Regulator program shall permit different switching circuits depending upon the targeted phase angle. Regulator operation shall be insensitive to harmonics and shall have an automatic no-volt release suitable for operation in temperature up to 70deg. C. C. The power factor regulator shall have "AUTOMATIC" or "MANUAL" control facility. The desired power factor shall be adjustable from 0.9 capacitive to 0.7 inductive. Capacitor switching time shall be adjustable from 1 to 99 seconds. D. The regulator shall be flush mounted in the cubicle door and shall have built in digital power factor meter and fault indicator. LED indications shall be provided to indicate Number of steps switched on, Capacitive or Inductive load. E. The power factor regulator shall have means to adapt itself to network phase rotation and reversal of current transformer terminals. Principle of Operation: A. The power factor regulator shall continuously sense (The reactive power) of the circuit being considered for power factor correction. If the computed power factor differs from the targeted factor for more than 10 seconds, the regulator shall switch a contactor to switch into or out of the circuit. Contactors shall be opened or closed as required to bring the circuit power factor closer to the targeted one. Only one capacitor shall be switched at a time. 2.05 ONTACTORS A. Contactors used in capacitor bank circuits shall be suitable for capacitor switching duty and shall withstand large transient current peaks at high frequency. B. The contactors shall have a life time of minimum 100,000 operations under capacitor switching conditions. Contactors shall be rated for 1.5 times the normal rated current of the capacitors. The contactors shall conform to IEC 947-4-1. 2.06 uses A. Three phase high rupture capacity fuses shall be provided for each capacitor step. Fuses shall be modern industrial design, current limiting type with a breaking capacity exceeding 100 KA. B. Fuses shall conform to the requirement of IEC 269. C. The utilization category of the fuses shall be gG. They shall be plug-in type with proper fuse. ---END--- E281 - 2 SECTION E440 DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.02 FACTORY TESTS: A. Design Tests: Design tests shall have been performed on a type or style of switchboard similar to that being furnished for this project. Tests shall be in accordance with NEMA PB 2 and UL 891. B. Production Tests: Dielectric, mechanical operation, grounding of instrument transformer cases, electrical operation and control wiring, and ground fault sensing equipment tests shall be performed on the switchboards provided for this project. Tests shall be in accordance with NEMA PB 2 and UL 891. 1.03 SUBMITTALS: Submit in accordance with Section, BASIC METHODS AND REQUIREMENTS (ELECTRICAL): A. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, materials, required clearances, terminations, weight, temperature rise, wiring and connection diagrams, plan, front, side, and rear elevations, sectional views, bus work, circuit breaker frame sizes, trip and short-circuit rating, long-time, short-time, instantaneous and ground fault settings, coordinated breaker and fuse curves, accessories, and device nameplate data. 3. Show the size, ampere-rating, number of bars per phase and neutral in each bus run (horizontal and vertical), bus spacing, equipment ground bus, and bus material. B. Manuals: 1. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals including technical data sheets, wiring diagrams, and information for ordering replacement parts. a. Wiring diagrams shall have their terminals identified to facilitate installation, maintenance, and operation. b. Wiring diagrams shall indicate internal wiring for each item of equipment and the interconnection between the items of equipment. c. Provide a clear and concise description of operation, which gives, in detail, the information required to properly operate the equipment. d. Approvals will be based on complete submissions of manuals together with shop drawings. 2. Two weeks prior to final inspection, deliver three copies of the final updated maintenance and operating manuals to the Resident Engineer. a. The manuals shall be updated to include any information necessitated by shop drawing approval. b. Complete "As Installed" wiring and schematic diagrams shall be included which show all items of equipment and their interconnecting wiring. c. Show all terminal identification. d. Include information for testing, repair, trouble shooting, assembly, disassembly, and recommended maintenance intervals. e. Provide a replacement parts list with current prices. Include a list of recommended spare parts, tools, and instruments for testing and maintenance purposes. f. Furnish manuals in loose-leaf binder or manufacturer's standard binder. C. Certifications: E440-1 1. Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: a. Certification by the Contractor that the assemblies have been properly installed, adjusted and tested, including circuit breakers settings. b. Certified copies of all of the factory design and production tests, field test data sheets and reports for the assemblies. PART 2 - PRODUCTS 2.01 GENERAL: A. Switchboards shall be in accordance with NEC, IEEE, and as shown on the drawings. B. Switchboards shall be provided complete, ready for operation including, but not limited to housing, buses, circuit breakers, instruments and related transformers, fuses, and wiring. C. Switchboard dimensions shall not exceed the space provided as shown on the drawings. D. Manufacturer’s nameplate shall include complete ratings of switchboard in addition to the date of manufacture. 2.02 BASIC ARRANGEMENT: A. Type I: Switchboard shall be front accessible with the following features: 1. Device mounting: a. Main breaker: Individually mounted and compartmented or group mounted with feeder breakers. b. Feeder breakers: Group mounted. 2. Section alignment: As shown on the drawings. 3. Accessibility: a. Main section line and load terminals: Front. b. Distribution section line and load terminals: Front. c. Through bus connections: Front . 4. Bolted line and load connections. 5. Full height wiring gutter covers for access to wiring terminals. 6. Short Circuit Current Rating: as shown on the drawings, whichever is higher. 2.03 HOUSING: A. Provide a completely enclosed, free standing, steel enclosure not less than the gage required by the ANSI and UL standards. The enclosure is to consist of the required number of vertical sections bolted together to form one metal enclosed rigid switchboard. The sides, top and rear shall be covered with removable screw on sheet steel plates. B. Provide ventilating louvers where required to limit the temperature rise of current carrying parts. All openings shall be protected against entrance of falling dirt, water, or foreign matter. C. Group the meters and their control switches on a hinged front cover. Provide concealed hinges and latch. D. Enclosure shall be thoroughly cleaned, phosphate treated, and primed with rust-inhibiting paint, Final finish coat to be the manufacturers standard gray. Provide a quart of finish paint for touch-up purposes. 2.04 BUSES: A. General: Buses shall be arranged for 3 phase, 4 wire distribution. Main phase buses (through bus), full size neutral bus, and ground bus shall be full capacity the entire length of the switchboard. Provide for future extensions by means of bolt holes or other approved method. Brace the bus to withstand the available short circuit current at the particular location and as shown on the drawings. No magnetic material shall be used between buses to form a magnetic loop. E440-2 B. Material and Size: Buses and connections shall be hard drawn copper of 98 percent conductivity. Bus temperature rise shall not exceed 65 degrees C . Section busing shall be sized based on UL and NEMA Switchboard Standards. C. Bus Connections: All contact surfaces shall be copper. Provide a minimum of two plated bolts per splice. Where physical bus size permits only one bolt, provide a means other than friction to prevent turning, twisting or bending. Torque bolts to the manufacturer's recommended values. D. Neutral Bus: Provide bare or plated bus and mount on insulated bus supports. Provide neutral disconnect link to permit isolation of neutral bus from the common ground bus and service entrance conductors. E. Ground Bus: Provide an uninsulated 6 mm by 50 mm copper equipment ground bus bar sized per UL 891 the length of the switchboard and secure at each section. 2.05 INTERNALLY INTEGRATED SURGE PROTECTIVE DEVICES: A. Integral Surge Suppressor: 1. SPD (Surge Protective Devices) shall be Component Recognized and listed in accordance with UL 1449 Second Edition to include Section 37.3 highest fault category testing on devices intended for service entrance use. SPD shall also be UL 1283 listed. 2. SPD shall be UL 67 listed, installed by and shipped from the electrical distribution equipment manufacturer’s factory. 3. SPD shall provide surge current diversion paths for all modes of protection; L-N, L-G, N-G, in WYE systems, and L-L, L-G in DELTA systems. 4. SPD shall be modular in design. Each mode shall be fused with a 200kAIC UL recognized surge rated fuse and incorporate a thermal cutout device. 5. SPD shall be integrally mounted to the bus bars of the switchboard. 6. Audible diagnostic monitoring shall be by way of audible alarm. This alarm shall activate upon a fault condition. An alarm on/off switch shall be provided to silence the alarm. An alarm push to test switch shall be provided as well. 7. SPD shall meet or exceed the following criteria: a. Maximum surge current capability (single pulse rated) per phase shall be: 1) Service Entrance Switchboard 250 kA. 2) Distribution Panel boards E0 kA 3) Branch Panel boards E0 kA 4) Service Entrance MCC 240 kA specified. 5) Distribution Class MCC E0 kA b. UL 1449 Second Edition Listed and Recognized Component Suppression Voltage Ratings (SVR’s) for Service Entrance and Distribution Location equipment shall not exceed the following: 8. SPD shall have a minimum EMI/RFI filtering of –50Db at 100 kHz with an insertion ration of 50:1 using MIL-STD-220A methodology. 9. SPD shall have the following diagnostic features: transient counter, status lights on each phase, and one set of 1 NO and 1 NC auxiliary dry contacts for alarming. 10. SPD shall have a warranty for a period of five years, incorporating unlimited replacements of suppressor parts if transients destroy them during the warranty period. Warranty shall be the responsibility of the electrical distribution equipment manufacturer and shall be supported by their respective field service division. 2.06 NAMEPLATES AND MIMIC BUS: A. Nameplates: Provide laminated black phenolic resin with white core with 6 mm (1/4 inch) high engraved lettered nameplates for each circuit breaker (switch) to indicate the feeder, panelboards and equipment served. Mount, with plated screws, on front of the breaker. B. Mimic Bus: Provide an approved mimic bus on the front of the switchboard. Color to be blue (400 volt) or black (220 volt), either factory painted, plastic, or metal strips. Plastic tape shall not be used. Use symbols similar to a one line diagram. (Refer to drawings). Plastic or metal strips shall be mounted with plated screws. E440-3 2.07 METERS AND INSTRUMENT TRANSFORMERS: A. Instrument Transformers: IEEE C57.13, and the following: 1. Potential Transformers: Secondary voltage rating of 230 V and NEMA accuracy class of 0.3 with burdens of W, X, and Y. 2. Current Transformers: Ratios shall be as indicated with accuracy class and burden suitable for connected relays, meters, and instruments. 3. Current Transformers for Neutral and Ground-Fault Current Sensing: Connect secondaries to ground overcurrent relays to provide selective tripping of main and tie circuit breaker. Coordinate with feeder circuit-breaker ground-fault protection. B. Power Circuit Monitoring and Control System: The Power Circuit Monitor shall be a multifunctional, digital, data acquisition and control device. The Power Circuit Monitor shall be metered over 50 values and extensive Min/Max data can be viewed on the LED display. Each Circuit Monitor shall offer true RMS metering and communications standard. Provide 0.2% accuracy true RMS metering and other powerful features such as automatic relay control, waveform capture, on-board event and data logging, and programmable logic for special applications like custom data logging and control function. On-board memory can be expanded to add 512 K or 1024K. Provide input/output modules, status inputs, a pulse output, relay outputs and analog inputs and outputs. 1. Power Circuit Monitor shall be a. Certified ANSI C12.E revenue accuracy st b. True RMS Metering through the 31 harmonic c. High accuracy: 0.2% on current and voltage d. Power quality readings displayed: THD and K-Factor rd e. Harmonic Analysis Data through 63 harmonic f. Automatic Alarm/Relay control g. On-board event and data logging h. Waveform capture i. UL listed, CSA Approved, CE Marketing, NOM Approved j. MV-90 compatible G. Recording Demand Meter: Usable as totalizing relay or as indicating and recording maximumdemand meter with 15-minute interval. Meter shall count and control a succession of pulses entering two channels. House in draw out, back-connected case arranged for semi flush mounting. 2.08 ROVISION FOR FUTURE: A. Where "provision for", "future", or "space" is noted on drawings, the space shall be equipped with bus connections to the future overcurrent device with suitable insulation and bracing to maintain proper short circuit rating and physical clearance. Provide buses for the ampere rating as shown for the future device. 2.09 BREAKER REMOVAL EQUIPMENT: Where draw out circuit breakers are provided, furnish a portable elevating carriage or switchboard mounted device for installation and removal of the breakers. 2.10 CONTROL WIRING: Control wiring shall be 600 volt class B stranded SIS. Install all control wiring complete at the factory adequately bundled and protected. Wiring across hinges and between shipping units shall be Class C stranded. Size in accordance with NEC. Provide control circuit fuses. E440-4 2.11 MAIN CIRCUIT BREAKERS: A. Type I Switchboard: Provide UL listed and labeled molded case circuit breakers in accordance with NEC and as shown on the drawings. Circuit breakers shall be the solid state adjustable trip type. 1. Trip units shall have field adjustable tripping characteristics as follows: a. Ampere setting (continuous). b. Long time band. c. Short time trip point. d. Short time delay. e. Instantaneous trip point. f. Ground fault trip point. g. Ground fault trip delay. 2. Trip settings shall be as indicated on the drawings. Final settings shall be as shown on the electrical system protective device study. 3. Breakers, which have same rating, shall be interchangeable with each other. B. Type II Switchboard: 1. Provide UL listed and labeled molded case circuit breakers in accordance with NEC and as shown on the drawings. Circuit breakers shall be the solid state adjustable trip type. a. Trip units shall have field adjustable tripping characteristics as follows: 1) Ampere setting (continuous). 2) Long time band. 3) Short time trip point. 4) Short time delay. 5) Instantaneous trip point. 6) Ground fault trip point. 7) Ground fault trip delay. b. Trip settings shall be as indicated on the drawings. Final settings shall be as shown on the electrical system protective device study. c. Breakers, which have same rating, shall be interchangeable with each other. 2. Provide low voltage AC power circuit breaker, with dead front, stored energy and solid state trip device. Circuit breakers shall be UL listed (category PAQX). a. Rating shall be 3-pole, 600 volts AC, 60-cycle with indicated frame size, trip rating and system voltage. Interrupting rating shall be without instantaneous trip. b. Position indicator: Provide an indicator visible from the front of the unit to indicate whether the breaker is open or closed. c. Trip button: Provide a mechanical trip button accessible from the front of the door to trip the breaker. d. Padlocking: Include provisions for padlocking the breaker in the open position. e. Operation: Unless otherwise shown on the drawings, breakers E00 ampere frame size and less shall be manually operated. Breakers larger than E00 amperes frame size shall be electrically operated. f. Trip devices shall have the following features: 1) Trip device in each pole. 2) Mechanically and electrically trip free. 3) Long time element with adjustable pick-up and selective maximum, intermediate, and minimum time delay bands. 4) Short time element with adjustable pick-up and selective maximum, intermediate, and minimum time delay bands. 5) Ground fault element with adjustable pick-up and selective maximum, intermediate and minimum time delay bands. // 6) Final settings of pick-up and time bands shall be as // shown on the drawings // reflected by the Electrical System Protective Device Study. // E440-5 SPEC WRITER NOTE: Show breaker frame size, trip, voltage, interrupting rating, time bands and pick-up settings on the drawings. 2.12 FEEDER CIRCUIT BREAKERS: A. Provide UL listed and labeled molded case circuit breakers, in accordance with the NEC, as shown on the drawings, and as herein specified. SPEC WRITER NOTE: Select the desired nonadjustable or adjustable circuit breaker paragraph below. B. C. Non-adjustable Trip Molded Case Circuit Breakers: 1. Molded case circuit breakers shall have automatic, trip free, non-adjustable, inverse time, and instantaneous magnetic trips for 100 ampere frame size or less. Magnetic trip shall be adjustable from 3X to 10X for breakers with 600 ampere frame size and higher. Factory setting shall be LOW unless otherwise noted. 2. Breaker features shall be as follows: a. A rugged, integral housing of molded insulating material. b. Silver alloy contacts. c. Arc quenchers and phase barriers for each pole. d. Quick-make, quick-break, operating mechanisms. e. A trip element for each pole, thermal magnetic type with long time delay and instantaneous characteristics, a common trip bar for all poles and a single operator. f. Electrically and mechanically trip free. g. An operating handle which indicates ON, TRIPPED and OFF positions. h. Line and load connections shall be bolted. i. Interrupting rating shall not be less than the maximum short circuit current available at the line. j. An overload on one pole of a multipole breaker shall automatically cause all the poles of the breaker to open. // Adjustable Trip Molded Case Circuit Breakers: 1. Provide molded case, solid state adjustable trip type circuit breakers. 2. Trip units shall have field adjustable tripping characteristics as follows: a. Ampere setting (continuous). b. Long time band. c. Short time trip point. d. Short time delay. e. Instantaneous trip point. f. Ground fault trip point. g. Ground fault trip delay. 3. Trip settings shall be as indicated on the drawings. Final settings shall be shown on the electrical system protective device study. 4. Breakers, which have same rating, shall be interchangeable with each other. // PART 3 - EXECUTION 3.01 INSTALLATION: A. Install switchboards in accordance with the NEC as shown on the drawings and as recommended by the manufacturer. B. Anchor switchboards to the floor with plated with 12.5 mm (1/2 inch) minimum anchor bolts as recommended by the manufacturer. Anchor the switchboards on two 100 mm (4 inch) minimum channel iron sills with plated 12.5 mm (1/2 inch) bolts. Furnish sills to suit the switchboards. Coordinate installation of sills with concrete pour of floor. Sills shall be level and grouted flush with floor. SPEC WRITER NOTE: Include the following paragraph for seismic areas only. C. Seismic bracing for switchgear shall be in accordance with the details shown on the drawings. // E440-6 3.02 INSTRUCTIONS Furnish the services of a competent instructor for one 4 hour period for instructing personnel in the operation and maintenance of the switchboard on the date requested by the Resident Engineer. ---END--- E440-7 SECTION E510 INTERIOR LIGHTING PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies the furnishing, installation and connection of the interior lighting systems. 1.02 SUBMITTALS A. In accordance with Section E010, ELECTRICAL INSTALLATIONS AND REQUIREMENTS, submit the following: B. Product Data: For each type of lighting fixture (luminaire) designated on the LIGHTING FIXTURE SCHEDULE, arranged in order of fixture designation, submit the following information. A. Material and construction details include information on housing, optics system and lens/diffuser. B. Physical dimensions and description. C. Wiring schematic and connection diagram. D. Installation details. E. Energy efficiency data. F. Photometric data based on laboratory tests complying with IESNA Lighting Measurements, testing and calculation guides. G. Lamp data including lumen output (initial and mean), color rendition index (CRI), rated life (hours) and color temperature (degrees Kelvin). H. Ballast data including ballast type, starting method, ambient temperature, ballast factor, sound rating, system watts and total harmonic distortion (THD). C. Manuals: 1. Submit, simultaneously with the shop drawings companion copies of complete maintenance and operating manuals including technical data sheets, and information for ordering replacement parts. 2. Two weeks prior to the final inspection, submit four copies of the final updated maintenance and operating manuals, including any changes, to the Resident Engineer. PART 2 – PRODUCTS 2.01 LIGHTING FIXTURES (LUMINAIRES) A. Lighting Fixture Construction – General 1. Generally construction and wiring of fixtures are to comply with the specifications, Regulations and Standards. Fixtures are to be fabricated, assembled and wired entirely at factory. Manufacturer's name, factory inspection sample and official quality label are to be fixed to each fixture supplied. 2. Sheet Metal: a. Shall be formed to prevent warping and sagging. Housing, trim and lens frame shall be true, straight (unless intentionally curved) and parallel to each other as designed. b. Wireways and fittings shall be free of burrs and sharp edges and shall accommodate internal and branch circuit wiring without damage to the wiring. c. When installed, any exposed fixture housing surface, trim frame, door frame and lens frame shall be free of light leaks; lens doors shall close in a light tight manner. d. Hinged door closure frames shall operate smoothly without binding when the fixture is in the installed position, latches shall function easily by finger action without the use of tools. E510-1 B. C. D. E. F. G. H. I. J. 3. Heat Resistance finishes, wires and components inside fixtures are to be certified materials to resist the temperatures, or other conditions encountered in the fixtures. 2 4. Wiring Inside Fixtures to be not less than 1.5 mm , and insulated to have acceptable characteristics to resist maximum temperatures inside fixtures. Wiring is to be terminated on screw type, fixed, insulating terminal blocks. 5. Hinges fixture with visible frames and hinged diffusers are to have concealed hinges and catches, and stainless steel retaining clips. 6. Suspension Aligners to be provided for pendant fixtures for axial, vertical and horizontal alignment. Vertical adjustment is to be minimum 25 mm. 7. Recessed Fixtures to be constructed to fit into suspended ceilings without distorting fixture or ceiling. Plaster rings are to be provided for plaster or concrete ceilings. 8. Outdoor Fixtures to be non-ferrous metal or specially treated material for outdoor use. 9. Removal of parts for maintenance is to be possible without removing fixture housing. Ballasts shall be serviceable while the fixture is in its normally installed position, and shall not be mounted to removable reflectors or wire way covers unless so specified. Lamp Sockets: 1. Fluorescent: Lamp holder contacts shall be the biting edge type or phosphorous-bronze with silver flash contact surface type and shall conform to the applicable requirements of UL 542. Lamp holders for bi-pin lamps shall be of the telescoping compression type, or of the single slot entry type requiring a one-quarter turn of the lamp after insertion. 2. High Intensity Discharge (H.I.D.): Shall have porcelain enclosures. Recessed fixtures mounted in an insulated ceiling shall be listed for use in insulated ceilings. Mechanical Safety: Lighting fixture closures (lens doors, trim frame, hinged housings, etc.) shall be retained in a secure manner by captive screws, chains, captive hinges or fasteners such that they cannot be accidentally dislodged during normal operation or routine maintenance. Metal Finishes: 1. The manufacturer shall apply standard finish (unless otherwise specified) over a corrosion resistant primer, after cleaning to free the metal surfaces of rust, grease, dirt and other deposits. Edges of pre-finished sheet metal exposed during forming, stamping or shearing processes shall be finished in a similar corrosion resistant manner to match the adjacent surface(s). Fixture finish shall be free of stains or evidence of rusting, blistering, or flaking, and shall be applied after fabrication. 2. Interior light reflecting finishes shall be white with not less than 85 percent reflectance, except where otherwise shown on the drawing. 3. Exterior finishes shall be as shown on the drawings. Lighting fixtures shall have a specific means for grounding metallic wireways and housings to an equipment grounding conductor. Light Transmitting Components for Fluorescent Fixtures: 1. Shall be 100 percent virgin acrylic. 2. Flat lens panels shall have not less than 1/8 inch [3.2mm] of average thickness. The average thickness shall be determined by adding the maximum thickness to the minimum impenetrated thickness and dividing the sum by 2. 3. Unless otherwise specified, lenses, diffusers and louvers shall be retained firmly in a metal frame by clips or clamping ring in such a manner as to allow expansion and contraction of the lens without distortion or cracking. Lighting fixtures in hazardous areas shall be suitable for installation in Class and Group areas as defined in NFPA 70, and shall comply with UL 844. Compact fluorescent fixtures shall be manufactured specifically for compact fluorescent lamps with ballast integral to the fixture. Assemblies designed to retrofit incandescent fixtures are prohibited except when specifically indicated for renovation of existing fixtures (not the lamp). Fixtures shall be designed for lamps as specified. 2.02 BALLASTS A. Linear Fluorescent Lamp Ballasts: electronic type, complying with UL 935 and with ANSI C 82.11, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output unless dimmer or bi-level control is indicated; including the following features: E510-2 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Lamp end-of-life detection and shutdown circuit (T5 lamps only). Automatic lamp starting after lamp replacement. Sound Rating: Class A. Total Harmonic Distortion Rating: 10 percent or less. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better. Operating Frequency: 20 kHz or higher. Lamp Current Crest Factor: 1.7 or less. Ballast Factor: 0.87 or higher unless otherwise indicated. Power Factor: 0.98 or higher. Interference: Comply with 47 CFT 18, Ch.1, Subpart C, for limitations on electromagnetic and radio-frequency interference for non-consumer equipment. 11. To facilitate multi-level lamp switching, lamps within fixture shall be wired with the outermost lamp at both sides of the fixture on the same ballast, the next inward pair on another ballast and so on to the innermost lamp (or pair of lamps). Within a given room, each switch shall uniformly control the same corresponding lamp (or lamp pairs) in all fixture units that are being controlled. 12. Where three-lamp fixtures are indicated, unless switching arrangements dictate otherwise, utilize a common two-lamp ballast to operate the center lamp in pairs of adjacent units that are mounted in a continuous row. The ballast fixture and slave-lamp fixture shall be factory wired with leads or plug devices to facilitate this circuiting. Individually mounted fixtures and the odd fixture in a row shall utilize single-lamp ballast for operation of the center lamp. 13. Dimming ballasts shall be as per above, except dimmable from 100% to 5% of rated lamp lumens. B. Low-Frequency Linear T8 Fluorescent Lamp Ballasts: hybrid electronic-electromagnetic rapidstart type, complying with UL 935 and with ANSI C 82.11, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output; including the following features: 1. Automatic lamp starting after lamp replacement. 2. Sound Rating: Class A. 3. Total Harmonic Distortion Rating: 20 percent or less. 4. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better. 5. Operating Frequency: 50 Hz. 6. Lamp Current Crest Factor: 1.7 or less. 7. Ballast Factor: 0.85 or higher unless otherwise indicated. 8. Power Factor: 0.90 or higher. 9. Interference: Comply with 47 CFT 18, Ch.1, Subpart C, for limitations on electromagnetic and radio-frequency interference for non-consumer equipment. 10. To facilitate multi-level lamp switching, lamps within fixture shall be wired with the outermost lamp at both sides of the fixture on the same ballast, the next inward pair on another ballast and so on to the innermost lamp (or pair of lamps). Within a given room, each switch shall uniformly control the same corresponding lamp (or lamp pairs) in all fixture units that are being controlled. 11. Where three-lamp fixtures are indicated, unless switching arrangements dictate otherwise, utilize a common two-lamp ballast to operate the center lamp in pairs of adjacent units that are mounted in a continuous row. The ballast fixture and slave-lamp fixture shall be factory wired with leads or plug devices to facilitate this circuiting. Individually mounted fixtures and the odd fixture in a row shall utilize single-lamp ballast for operation of the center lamp. C. Compact Fluorescent Lamp Ballasts: electronic type, complying with UL 935 and with ANSI C 82.11, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output unless dimmer or bi-level control is indicated; including the following features: 1. Lamp end-of-life detection and shutdown circuit. 2. Automatic lamp starting after lamp replacement. E510-3 3. 4. 5. 6. 7. 8. 9. 10. Sound Rating: Class A. Total Harmonic Distortion Rating: 10 percent or less. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better. Operating Frequency: 20 kHz or higher. Lamp Current Crest Factor: 1.7 or less. Ballast Factor: 0.95 or higher unless otherwise indicated. Power Factor: 0.98 or higher. Interference: Comply with 47 CFR 18, Ch. 1, Subpart C, for limitations on electromagnetic and radio-frequency interference for non-consumer equipment. 11. Dimming ballasts shall be as per above, except dimmable from 100% to 5 % of rated lamp lumens. D. Ballasts for high intensity discharge fixtures: electromagnetic ballast for high intensity discharge lamps. Comply with ANSI C82.4 and UL 1029. Include the following features unless otherwise indicated: 1. Ballast Circuit: Constant-wattage autotransformer or regulating high-power-factor type. 2. Minimum Starting Temperature: Minus 30 deg C for single-lamp ballasts. 3. Rated Ambient Operating Temperature: 40 deg C. 4. Open-circuit operation that will not reduce average life. 5. Low-Noise Ballasts: Manufacturers' standard epoxy-encapsulated models designed to minimize audible fixture noise. E. Electronic ballast for high intensity discharge metal-halide lamps shall include the following features unless otherwise indicated: 1. Minimum Starting Temperature: Minus 29 deg C for single-lamp ballasts. 2. Rated Ambient Operating Temperature: 54 deg C. 3. Lamp end-of-life detection and shutdown circuit. 4. Sound Rating: Class A. 5. Total Harmonic Distortion Rating: 20 percent or less. 6. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better. 7. Lamp Current Crest Factor: 1.5 or less. 8. Power Factor: 0.90 or higher. 9. Interference: Comply with 47 CFR 18, Ch. 1, Subpart C, for limitations on electromagnetic and radio-frequency interference for non-consumer equipment. 10. Protection: Class P thermal cut. 2.03 FLUORESCENT EMERGENCY BALLAST A. Self-contained, modular, battery-inverter unit, factory mounted within lighting fixture body and compatible with ballast. Comply with UL 924. 1. Emergency Connection: Operate one fluorescent lamp continuously at an output of 1100 lumens each. Connect unswitched circuit to battery-inverter unit and switched circuit to fixture ballast. 2. Test Push Button and Indicator Light: Visible and accessible without opening fixture or entering ceiling space. a. Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability. b. Indicator Light: LED indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle. 3. Battery: Sealed, maintenance-free, nickel-cadmium type. 4. Charger: Fully automatic, solid-state, constant-current type with sealed power transfer relay. 5. Integral Self-Test: Automatically initiates test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing LED. 2.04 EMERGENCY LIGHTING UNIT A. Complete, self-contained unit with batteries, battery charger, one or more local or remote lamp heads with lamps, under-voltage relay, and test switch. Comply with UL 924. E510-4 1. Enclosure: Shall be impact-resistant thermoplastic, which will protect components from dust, moisture, and oxidizing fumes from the battery. Enclosure shall be suitable for the environmental conditions in which installed. 2. Lamp Heads: Horizontally and vertically adjustable, mounted on the face of the unit, except where otherwise indicated. 3. Battery: Shall be maintenance-free nickel-cadmium. Minimum normal life shall be 10 years. 4. Battery Charger: Dry-type full-wave rectifier with charging rates to maintain the battery in fully-charged condition during normal operation, and to automatically recharge the battery within 12 hours following a 1-1/2 hour continuous discharge. 5. Integral Self-Test: Automatically initiates test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing LED. 2.05 LAMPS A. Linear and U-shaped T5 and T8 Fluorescent Lamps: 1. Rapid start fluorescent lamps shall comply with ANSI C78.1; and instant-start lamps shall comply with ANSI C78.3. 2. Chromaticity of fluorescent lamps shall comply with ANSI C78.376. 3. Except as indicated below, lamps shall be low-mercury energy saving type, have a color temperature Refer to Lighting Fixture Schedule, a Color Rendering Index (CRI) of greater than 80, average rated life of 20,000 hours. Low mercury lamps shall have passed the EPA Toxicity Characteristic Leachate Procedure (TCLP) for mercury by using the lamp sample preparation procedure described in NEMA LL 1. B. Compact Fluorescent Lamps: 1. T4, CRI 80 (minimum), color temperature Refer to Lighting Fixture Schedule. C. Long Twin-Tube Fluorescent Lamps: 1. T5, CRI 80 (minimum), color temperature Refer to Lighting Fixture Schedule, 20,000 hours average rated life. D. High Intensity Discharge Lamps: 1. High-Pressure Sodium Lamps: ANSI C78.42, CRI 21 (minimum), color temperature Refer to Lighting Fixture Schedule, and average rated life of 24,000 hours, minimum. 2. Pulse-Start, Metal-Halide Lamps: Minimum CRI 65, and color temperature Refer to Lighting Fixture Schedule. 3. Ceramic, Pulse-Start, Metal-Halide Lamps: CRI 80 (minimum), and color temperature Refer to Lighting Fixture Schedule. 4. Low-Pressure Sodium Lamps: ANSI 78.41, CRI 0, and color temperature Refer to Lighting Fixture Schedule 2.06 RADIO-INTERFERENCE-FREE FLUORESCENT FIXTURES A. Shall be specially designed for suppressing radio-frequency energy produced within the fixtures. The Rules and Regulations of FCC (CFR 47, Part 18) shall apply. B. Lenses shall have a light-transparent layer of metal permanently bonded to them, and in positive contact with the steel housing or equal to prevent the radio-frequency interferences from passing through the lenses. The effective light transmittance of the lenses shall be not less than 75 percent. C. Install line filters within the body of the fixtures and wired in series with the supply circuit conductors to eliminate the transmission of radio frequency energy into the supply circuit. D. Ballasts shall be as specified herein. 2.07 EXIT LIGHT FIXTURES A. Exit light fixtures shall meet applicable requirements of NFPA 101 and UL 924. B. Housing and Canopy: 1. Shall be made of die-cast aluminum. 2. Optional steel housing shall be a minimum 20 gauge thick or equivalent strength aluminum. 3. Steel housing shall have baked enamel over corrosion resistant, matte black or ivory white primer. E510-5 C. D. E. F. Door frame shall be cast or extruded aluminum, and hinged with latch. Finish shall be satin or fine-grain brushed aluminum. There shall be no radioactive material used in the fixtures. Fixtures: 1. Maximum fixture wattage shall be 1 watt or less. 2. Inscription panels shall be cast or stamped aluminum a minimum of 0.090 inch [2.25mm] thick, stenciled with 6 inch [150mm] high letters, baked with red color stable plastic or fiberglass. Lamps shall be luminous Light Emitting Diodes (LED) mounted in center of letters on red color stable plastic or fiberglass. The LED shall be rated minimum 25 years life. 3. Double-Faced Fixtures: Provide double-faced fixtures where required or as shown on drawings. 4. Directional Arrows: Provide directional arrows as part of the inscription panel where required or as shown on drawings. Directional arrows shall be the "chevron-type" of similar size and width as the letters and meet the requirements of NFPA 101. G. Voltages: Refer to Lighting Fixture Schedule. PART 3 – EXECUTION 3.01 INSTALLATION A. Installation shall be in accordance with the NEC, manufacturer's instructions and as shown on the drawings or specified. B. Align, mount and level the lighting fixtures uniformly. C. Fluorescent bed light fixtures shall be attached to the studs in the walls. Attachment to gypsum board only is not acceptable. D. Lighting Fixture Supports: 1. Shall provide support for all of the fixtures. Supports may be anchored to channels of the ceiling construction, to the structural slab or to structural members within a partition, or above a suspended ceiling. 2. Shall maintain the fixture positions after cleaning and relamping. 3. Shall support the lighting fixtures without causing the ceiling or partition to deflect. 4. Hardware for recessed lighting fixtures: a. All fixture mounting devices connecting fixtures to the ceiling system or building structure shall have a capacity for a horizontal force of 100 percent of the fixture weight and a vertical force of 400 percent of the fixture weight. b. Mounting devices shall clamp the fixture to the ceiling system structure (main grid runners or fixture framing cross runners) at four points in such a manner as to resist spreading of these supporting members. Each support point device shall utilize a screw or approved hardware to "lock" the fixture housing to the ceiling system, restraining the fixture from movement in any direction relative to the ceiling. The screw (size No. 10 minimum) or approved hardware shall pass through the ceiling member (T-bar, channel or spline), or it may extend over the inside of the flange of the channel (or spline) that faces away from the fixture, in a manner that prevents any fixture movement. c. In addition to the above, the following is required for fixtures exceeding 20 pounds [9kg] in weight. 1) Where fixtures mounted in ASTM Standard C635-69 "Intermediate" and "Heavy Duty" ceilings and weigh between [9kg and 25kg] provide two 12 gauge safety hangers hung slack between diagonal corners of the fixture and the building structure. 2) Where fixtures weigh over [25kg] they shall be independently supported from the building structure by approved hangers. Two-way angular bracing of hangers shall be provided to prevent lateral motion. d. Where ceiling cross runners are installed for support of lighting fixtures, they must have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners. E510-6 5. Surface mounted lighting fixtures: a. Fixtures shall be bolted against the ceiling independent of the outlet box at four points spaced near the corners of each unit. The bolts (or stud-clips) shall be minimum [6mm] bolt, secured to main ceiling runners and/or secured to cross runners. Non-turning studs may be attached to the main ceiling runners and cross runners with special non-friction clip devices designed for the purpose, provided they bolt through the runner, or are also secured to the building structure by 12 gauge safety hangers. Studs or bolts securing fixtures weighing in excess of [25kg] shall be supported directly from the building structure. b. Where ceiling cross runners are installed for support of lighting fixtures they must have a carrying capacity equal to that of the main ceiling runners and be rigidly secured to the main runners. c. Fixtures less than [6.8kg] in weight and occupying less than two square feet [600mm x 600mm] of ceiling area may, (when designed for the purpose) be supported directly from the outlet box when all the following conditions are met. 1) Screws attaching the fixture to the outlet box pass through round holes (not key-hole slots) in the fixture body. 2) The outlet box is attached to a main ceiling runner (or cross runner) with approved hardware. 3) The outlet box is supported vertically from the building structure. d. Fixtures mounted in open construction shall be secured directly to the building structure with approved bolting and clamping devices. 6. Single or double pendant-mounted lighting fixtures: a. Each stem shall be supported by an approved outlet box, mounted swivel joint and canopy which holds the stem captive and provides spring load (or approved equivalent) dampening of fixture oscillations. Outlet box shall be supported vertically from the building structure. 7. Outlet boxes for support of lighting fixtures (where permitted) shall be secured directly to the building structure with approved devices or supported vertically in a hung ceiling from the building structure with a nine gauge wire hanger, and be secured by an approved device to a main ceiling runner or cross runner to prevent any horizontal movement relative to the ceiling. E. Furnish and install the specified lamps for all lighting fixtures installed and all existing lighting fixtures reinstalled under this project. F. Coordinate between the electrical and ceiling trades to ascertain that approved lighting fixtures are furnished in the proper sizes and installed with the proper devices (hangers, clips, trim frames, flanges), to match the ceiling system being installed. G. Bond lighting fixtures and metal accessories to the grounding system as specified in Section E 450 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS. H. Exercise electronic dimming ballasts over full range of dimming capability by operating the control devices(s) in the presence of the Resident Engineer. Observe for visually detectable flicker over full dimming range. I. Burn-in all lamps that require specific aging period to operate properly, prior to occupancy by owner. Burn-in period to be 40 hours minimum, unless a lesser period is specifically recommended by lamp manufacturer. Burn-in fluorescent and compact fluorescent lamps intended to be dimmed, for at least 100 hours at full voltage. Replace any lamps and ballasts which fail during burn-in. J. At completion of project, relamp/reballast fixtures which have failed lamps/ballasts. Clean fixtures, lenses, diffusers and louvers that have accumulated dust/dirt/fingerprints during construction. Replace damaged lenses, diffusers and louvers with new. ---END--- E510-7 SECTION E560 EXTERIOR LIGHTING PART 1 - GENERAL 1.01 DESCRIPTION A. This section specifies the furnishing, installation, and connection of exterior luminaires, poles, and supports. 1.02 SUBMITTALS A. Submit in accordance with Section E010, ELECTRICAL INSTALLATIONS AND REQUIREMENTS. B. Shop Drawings: 1. Clearly present sufficient information to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting, details, materials, required clearances, terminations, wiring and connection diagrams, photometric data, ballasts, poles, luminaires, lamps, and accessories. C. Manuals: Two weeks prior to final inspection, submit four copies of operating and maintenance manuals to the Resident Engineer. Include technical data sheets, wiring and connection diagrams, and information for ordering replacement lamps, ballasts, and parts. D. Certifications: Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: 1. Certification by the manufacturer that the materials are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installation has been properly installed and tested. 1.03 DELIVERY, STORAGE, AND HANDLING A. Provide manufacturer’s standard provisions for protecting pole finishes during transport, storage, and installation. Do not store poles on ground. Store poles so they are at least 12 in [305 mm] above ground level and growing vegetation. Do not remove factory-applied pole wrappings until just before installing pole. PART 2 - PRODUCTS 2.01 MATERIALS AND EQUIPMENT A. Materials and equipment shall be in accordance with NEC, UL, ANSI, and as shown on the drawings and specified. 2.02 LUMINAIRES A. Per UL 1598 and NEMA C136.17. Luminaires shall be weatherproof, heavy duty, outdoor types designed for efficient light utilization, adequate dissipation of lamp and ballast heat, and safe cleaning and relamping. B. Light distribution pattern types shall be as shown on the drawings. C. Incorporate ballasts in the luminaire housing, except where otherwise shown on the drawings. D. Lenses shall be frame-mounted, heat-resistant, borosilicate glass, with prismatic refractors, unless otherwise shown on the drawings. Attach the frame to the luminaire housing by hinges or chain. Use heat and aging-resistant, resilient gaskets to seal and cushion lenses and refractors in luminaire doors. E560-1 E. Lamp sockets for high intensity discharge (H.I.D) fixture shall have locking-type porcelain enclosures in conformance to the applicable requirements of ANSI C81.61 and UL 496. F. Pre-wire internal components to terminal strips at the factory. G. Bracket-mounted luminaires shall have leveling provisions and clamp-type adjustable slip-fitters with locking screws. H. Materials shall be rustproof. Latches and fittings shall be non-ferrous metal. I. Provide manufacturer's standard finish, as scheduled on the drawings. Where indicated on drawings, match finish process and color of pole or support materials. Where indicated on drawings, provide finishes as indicated in Section 09 06 00, SCHEDULE FOR FINISHES. J. Luminaires shall carry factory labels, showing complete, specific lamp and ballast information. 2.03 LAMPS A. Install the proper lamps in every luminaire installed and every existing luminaire relocated or reinstalled. B. Lamps shall be general-service, outdoor lighting types. C. High-Pressure Sodium (HPS) Lamps: NEMA C78.42, CRI 21 (minimum), wattage as indicated. Lamps shall have minimum average rated life of 24,000 hours. D. Low-Pressure Sodium (LPS) Lamps: NEMA C78.43. E. Metal-Halide Lamps: NEMA C78.43 or NEMA C78.1381. F. Mercury vapor lamps shall not be used. 2.04 HIGH INTENSITY DISCHARGE BALLASTS A. Per NEMA C82.4 and UL 1029. Ballasts shall be encapsulated single-lamp, copper-wound, constant-wattage autotransformer type, designed to operate on the voltage system to which they are connected and capable of open-circuit operation without reducing lamp life. B. Ballasts shall have individual overcurrent protection in each ungrounded supply conductor. C. Ballast shall have an allowable line voltage variation of ±10%, with a maximum 20% lamp wattage regulation spread. D. Power factor shall be not less than 90%. E. Ballast shall have a minimum starting temperature of -30Ëš C, and a normal ambient operating temperature of 40Ëš C. F. Lamp current crest factor shall be 1.8 or less, in accordance with lamp manufacturer recommendations. 2.05 METAL HALIDE CORE AND COIL BALLASTS A. Shall be pulse start, linear reactor type for 277 volt luminaires and constant-wattage autotransformer (CWA) type for other voltage luminaires (if not otherwise specified). B. Ballasts shall have individual overcurrent protection in each ungrounded supply conductor. C. Power factor shall be not less than 90%. D. Ballast shall have an allowable line voltage variation of ±5% for linear reactor type and ±10% for CWA, with a maximum 20% lamp wattage regulation spread. E. Ballast shall have a minimum starting temperature of –40Ëš C. F. Lamp current crest factor shall be 1.8 or less, in accordance with lamp manufacturer recommendations. 2.06 METAL HALIDE ELECTRONIC BALLASTS A. Ballast shall be low-frequency electronic type, and shall operate pulse start and ceramic metal halide lamps at a frequency of 90 to 200 Hz square wave. B. Ballast shall be labeled Type ‘1’ outdoor, suitable for recessed use, Class ‘P’. C. Ballast shall have auto-resetting thermal protector to shut off ballast when operating temperatures reach unacceptable levels. D. Ballast shall have an end of lamp life detection and shut-down circuit. E. Lamp current crest factor shall be 1.5 or less. F. Ballasts shall comply with FCC Title 47 CFR Part 18 Non-consumer RFI/EMI Standards. G. Ballast shall have a minimum ballast factor of 1.0. E560-2 H. I. J. K. Input current THD shall not exceed 20% for the primary lamp. Ballasts shall have ANSI C62.41, category ‘A’ transient protection. Ballasts shall have power factor greater than 90%. Ballast shall have a Class ‘A’ sound rating. 2.07 EXISTING LIGHTING SYSTEMS A. For modifications or additions to existing lighting systems, the new components shall be compatible with the existing systems. B. New poles and luminaires shall have approximately the same configurations and dimensions as the existing poles and luminaires, except where otherwise shown on the drawings. //2.08 SERIES LIGHTING SYSTEMS A. Series-Type Systems: 1. Provide components specifically for constant-current series type lighting systems. 2. Constant-Current Transformers: a. Self-cooled by natural convection, liquid-immersed, fully automatic, outdoor type. b. Liquid shall be oil, conforming to ASTM D3487, except where otherwise shown. c. Temperature rises shall not exceed the following test values for the respective insulation systems: 1) Standard, 131Ëš F [55Ëš C] by resistance and 149Ëš F [65Ëš C] hottest spot. 2) Thermally upgraded, 149Ëš F [65Ëš C] by resistance and 180Ëš F [80Ëš C] hottest spot. d. Core Coil Assemblies: 1) Braced to withstand the stresses caused by the maximum current possible under all conditions and rough handling during shipment. 2) Cores, silicon steel. 3) Coils, continuous windings without splices, except for taps. e. Bring primary and secondary leads out through wet-process, porcelain bushings, pressure-tight. Terminals shall be suitable for the specific cables being connected to them. f. Series-type systems shall have capacitors for power factor improvement. The value of power factor under the percent of full load rating shall be as shown on the drawings. g. Series-type systems shall regulate the secondary current within 1% over the entire load rating range while the primary voltage remains within 5% of the rated voltage. h. Operation of the transformers shall not be adversely affected while the transformers are mounted five degrees off of perpendicular. i. Provide tanks and covers of steel to meet NEMA and ANSI requirements, cleaned, phosphatized, and painted at the factory with primer and the manufacturer's standard extremely durable finish. j. Sound levels shall not exceed 45 db. k. Standard ANSI features and accessories including a pressure relief device, ground pad, lifting provisions, and diagrammatic nameplate. l. Dimensions and configurations shall conform to the spaces designated for installations. m. Install the transformers such that they will have adequate air circulation for heat removal. 3. Controllers: a. Oil-immersed, rated-load-interrupter, outdoor type, with heavy duty, silver-alloy contacts. b. Oil, ASTM D3487. c. Operate at 120 V, 60 Hz. d. Have an auxiliary hand lever for manual operation during emergencies. e. The depth below the oil surface of the contacts shall be not less than the depth of the switch mechanism. f. Bring leads out through wet-process, porcelain bushings, pressure-tight. Terminals shall be suitable for the specific cables being connected to them. g. Provide steel tanks and covers, thoroughly cleaned, phosphatized, and painted at the factory with primer and the manufacturer's standard durable finish. E560-3 h. Dimensions and configurations shall conform to the spaces designed for installations. 4. Provide protective relays to de-energize the control circuits for the controllers, thereby deenergizing the series lighting load circuits when open circuit faults occur in the series lighting load circuits. 5. Transformer, equipment enclosure, lightning arresters, and primary and secondary protection shall be provided. 6. Disconnecting devices shall be watertight, submersible type, suitable for the cables being installed and for use in outdoor lighting systems.// //2.09 OBSTRUCTION LIGHTING A. Refer to Section 26 09 23, LIGHTING CONTROLS for control devices. B. For Buildings: 1. Luminaires shall comply with FAA, AC 70/7460-1K, and AC 150/5345-43E, and be Type L1810 duplex units with red Fresnel lenses and 100 W, type A-21, clear, traffic-signal lamps. 2. Mount the luminaires on galvanized rigid steel pipe masts attached to the roof of the buildings so the luminaires extend 12 in [305 mm] above the level of the highest item on the building, including items attached to the roof. 3. Locate luminaires in accordance with the applicable FAA Standards. C. For Smoke Stacks: Luminaires shall be in accordance with the referenced details shown on the drawings. All lamps shall be the type shown on the drawings. D. For Water Tanks and Cooling Towers: Luminaires shall be FAA, AC 70/7460-1K, and AC 150/5345-43E, Type L-810 duplex units with red Fresnel lenses and 100 W, type A-21, clear, traffic-signal lamps. PART 3 - EXECUTION 3.01 INSTALLATION A. Install lighting in accordance with the NEC, as shown on the drawings, and in accordance with manufacturer’s recommendations. B. Install lamps in each luminaire. C. Adjust luminaires that require field adjustment or aiming. 3.02 GROUNDING A. Ground noncurrent-carrying parts of equipment, including metal poles, luminaires, mounting arms, brackets, and metallic enclosures, as specified in Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS. Where copper grounding conductor is connected to a metal other than copper, provides specially-treated or lined connectors suitable and listed for this purpose . 3.03 ACCEPTANCE CHECKS AND TESTS A. Verify operation after installing luminaires and energizing circuits. ---END--- E560-4 SECTION E520 LIGHTING CONTROLS PART 1 - GENERAL 1.01 DESCRIPTION A. This section specifies the furnishing, installation and connection of the lighting controls. 1.02 SUBMITTALS A. In accordance with Section E010, ELECTRICAL INSTALLATIONS AND REQUIREMENTS, submit the following: B. Product Data: For each type of lighting control, submit the following information. 1. Manufacturer’s catalog data. 2. Wiring schematic and connection diagram. 3. Installation details. C. Manuals: 1. Submit, simultaneously with the shop drawings companion copies of complete maintenance and operating manuals including technical data sheets, and information for ordering replacement parts. 2. Two weeks prior to the final inspection, submit four copies of the final updated maintenance and operating manuals, including any changes, to the Resident Engineer. D. Certifications: 1. Two weeks prior to final inspection, submit four copies of the following certifications to the Resident Engineer: a. Certification by the Contractor that the equipment has been properly installed, adjusted, and tested. PART 2 – PRODUCTS 2.01 ELECTRONIC TIME SWITCHES A. Electronic, solid-state programmable units with alphanumeric display; complying with UL 917. 1. Contact Configuration: //SPST// //DPST// //DPDT//. 2. Contact Rating: //30-A inductive or resistive, 240-V ac// //20-A ballast load, 120/240-V ac//. 3. Astronomical Clock: Capable of switching a load on at sunset and off at sunrise, and automatically changing the settings each day in accordance with seasonal changes of sunset and sunrise. Additionally, it shall be programmable to a fixed on/off weekly schedule. 4. Battery Backup: For schedules and time clock. 2.02 ELECTROMECHANICAL-DIAL TIME SWITCHES A. Electromechanical-dial time switches; complying with UL 917. 1. Contact Configuration: //SPST// //DPST// //DPDT//. 2. Contact Rating: //30-A inductive or resistive, 240-V ac// //20-A ballast load, 120/240-V ac//. 3. Wound-spring reserve carryover mechanism to keep time during power failures. 2.03 TIMER SWITCHES A. Digital switches with backlit LCD display, 120/277 volt rated, fitting as a replacement for standard wall switches. 1. Compatibility: Compatible with all ballasts. 2. Warning: Audible warning to sound during the last minute of “on” operation. 3. Time-out: Adjustable from 5 minutes to 12 hours. 4. Faceplate: Refer to wall plate material and color requirements for toggle switches, as specified in Section E140, WIRING ACCESSORIES. E570-1 2.04 INDOOR OCCUPANCY SENSORS A. Wall- or ceiling-mounting, solid-state units with a power supply and relay unit, suitable for the environmental conditions in which installed. 1. Operation: Unless otherwise indicated, turn lights on when covered area is occupied and off when unoccupied; with a 1 to 15 minute adjustable time delay for turning lights off. 2. Sensor Output: Contacts rated to operate the connected relay. Sensor shall be powered from the relay unit. 3. Relay Unit: Dry contacts rated for 20A ballast load at 120V and 277V, for 13A tungsten at 120V, and for 1 hp at 120V. 4. Mounting: a. Sensor: Suitable for mounting in any position on a standard outlet box. b. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind hinged door. 5. Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor. 6. Bypass Switch: Override the on function in case of sensor failure. 7. Manual/automatic selector switch. 8. Automatic Light-Level Sensor: Adjustable from 21.5 to 2152 lx; keep lighting off when selected lighting level is present. 9. Faceplate for Wall-Switch Replacement Type: Refer to wall plate material and color requirements for toggle switches, as specified in Section E140, WIRING ACCESSORIES. B. Dual-technology Type: Ceiling mounting; combination PIR and ultrasonic detection methods, field-selectable. 1. Sensitivity Adjustment: Separate for each sensing technology. 2. Detector Sensitivity: Detect occurrences of 150mm minimum movement of any portion of a human body that presents a target of not less than 232 sq. cm, and detect a person of average size and weight moving not less than 305 mm in either a horizontal or a vertical manner at an approximate speed of 305 mm/s. 3. Detection Coverage: as scheduled on drawings. 2.05 OUTDOOR MOTION SENSOR (PIR) A. Suitable for operation in ambient temperatures ranging from minus 40 to plus 54 deg C. 1. Operation: Turn lights on when sensing infrared energy changes between background and moving body in area of coverage; with a 1 to 15 minute adjustable time delay for turning lights off. 2. Mounting: a. Sensor: Suitable for mounting in any position on a standard outdoor junction box. b. Relay: Internally mounted in a standard weatherproof electrical enclosure. c. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind hinged door. 3. Bypass Switch: Override the on function in case of sensor failure. 4. Automatic Light-Level Sensor: Adjustable from 11 to 215 lx; keep lighting off during daylight hours. B. Detector Sensitivity: Detect occurrences of 150mm minimum movement of any portion of a human body that presents a target of not less than 232 sq. cm. C. Detection Coverage: as scheduled on drawings. D. Individually Mounted Sensor: Contacts rated to operate the connected relay, complying with UL 773A. Sensor shall be powered from the relay unit. 1. Relay Unit: Dry contacts rated for 20A ballast load at 120V and 277V, for 13A tungsten at 120V, and for 1 hp at 120V. 2. Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor. 2.06 LIGHTING CONTROL PANEL – RELAY TYPE A. Controller: Comply with UL 508; programmable, solid-state, astronomic 365-day control unit with non-volatile memory, mounted in preassembled relay panel with low-voltage-controlled, latching-type, single-pole lighting circuit relays. Controller shall be capable of receiving E570-2 B. C. D. E. inputs from sensors and other sources, and capable of timed overrides and/or blink-warning on a per-circuit basis. Controller communication protocol shall be compatible with the building automation system specified in SECTION 23 09 23 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. Where indicated, a limited number of digital or analog, low-voltage control-circuit outputs shall be supported by control unit and circuit boards associated with relays. Cabinet: Steel with hinged, locking door. Barriers separate low-voltage and line-voltage components. Directory: Identifies each relay as to load controlled. Control Power Supply: Transformer and full-wave rectifier with filtered dc output. Single-Pole Relays: Mechanically held unless otherwise indicated; split-coil, momentarypulsed type, rated 20 A, 125-V ac for tungsten filaments and 20 A, 277-V ac for ballasts, 50,000 cycles at rated capacity. 2.07 LIGHTING CONTROL PANEL – CIRCUIT BREAKER TYPE A. Controller: Panelboard mounted in compliance with UL 916, programmable, solid-state, astronomic 365-day timing and control unit with non-volatile memory. Controller shall be integral to panelboard as specified in Section E450, PANELBOARDS. Controller shall be capable of receiving inputs from sensors and other sources, and capable of timed overrides and/or blink-warning on a per-circuit basis. Controller communication protocol shall be compatible with the building automation system specified in SECTION 23 09 23, DIRECTDIGITAL CONTROL SYSTEM FOR HVAC. Panelboard shall use low-voltage-controlled, electrically operated molded-case branch circuit breakers or molded-case branch circuit breakers with switching accessories. Circuit breakers and a limited number of digital or analog, low-voltage control-circuit outputs shall be individually controlled by control module. Panelboard shall also comply with Section E450, PANELBOARDS. B. Electrically Operated, Molded-Case Circuit-Breaker Panelboard: Per Section E450, PANELBOARDS. C. Electrically Operated, Molded-Case Circuit Breakers: Per Section E450, PANELBOARDS. D. Switching Endurance Ratings: Rated at least 20,000 open and close operations under rated load at 0.8 power factor. PART 3 - EXECUTION 3.01 INSTALLATION: A. Installation shall be in accordance with the NEC, manufacturer's instructions and as shown on the drawings or specified. B. Aim outdoor photocell switch according to manufacturer's recommendations. Set adjustable window slide for 1 footcandle photocell turn-on. C. Aiming for wall-mounted and ceiling-mounted motion sensor switches shall be per manufacturer’s recommendations. D. Set occupancy sensor "on" duration to //5// //10// //15// minutes. E. Locate light level sensors as indicated and in accordance with the manufacturer's recommendations. Adjust sensor for the scheduled light level at the typical work plane for that area. F. Label time switches and contactors with a unique designation. 3.02 ACCEPTANCE CHECKS AND TESTS A. Perform in accordance with the manufacturer's recommendations. B. Upon completion of installation, conduct an operating test to show that equipment operates in accordance with requirements of this section. C. Test for full range of dimming ballast and dimming controls capability. Observe for visually detectable flicker over full dimming range. D. Test occupancy sensors for proper operation. Observe for light control over entire area being covered. E. Program lighting control panels per schedule on drawings. E570-3 ---END--- E570-4 11-09 SECTION E611 INTRUSION DETECTION SYSTEM PART 1 – GENERAL 1.01 DESCRIPTION A. Provide and install a complete Intrusion Detection System, hereinafter referred to as IDS, as specified in this section. 1.02 QUALITY ASSURANCE A. The Contractor shall be responsible for providing, installing, and the operation of the IDS as shown. The Contractor shall also provide certification as required. B. The security system shall be installed and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the security system is stand-alone or a part of a complete Information Technology (IT) computer network. C. The Contractor or security sub-contractor shall be a licensed security Contractor as required within the state or jurisdiction of where the installation work is being conducted. 1.03 SUBMITTALS A. Submit below items in conjunction with Master Specifications, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES, and DEMOLITION. B. Provide certificates of compliance with Section 1.02, Quality Assurance. C. Provide a pre-installation and as-built design package in both electronic format and on paper, minimum size 48 x 48 inches (1220 x 1220 millimeters); drawing submittals shall be per the established project schedule. D. Pre-installation design and as-built packages shall include, but not be limited to: 1. Index Sheet that shall: a. Define each page of the design package to include facility name, building name, floor, and sheet number. b. Provide a list of all security abbreviations and symbols. c. Reference all general notes that are utilized within the design package. d. Specification and scope of work pages for all security systems that are applicable to the design package that will: 1) Outline all general and job specific work required within the design package. 2) Provide a device identification table outlining device Identification (ID) and use for all security systems equipment utilized in the design package. 2. Drawing sheets that will be plotted on the individual floor plans or site plans shall: a. Include a title block as defined above. b. Define the drawings scale in both standard and metric measurements. c. Provide device identification and location. d. Address all signal and power conduit runs and sizes that are associated with the design of the electronic security system and other security elements (e.g., barriers, etc.). e. Identify all pull box and conduit locations, sizes, and fill capacities. f. Address all general and drawing specific notes for a particular drawing sheet. 3. A riser drawing for each applicable security subsystem shall: a. Indicate the sequence of operation. b. Relationship of integrated components on one diagram. C. Include the number, size, identification, and maximum lengths of interconnecting wires. d. Wire/cable types shall be defined by a wire and cable schedule. The schedule shall utilize a lettering system that will correspond to the wire/cable it represents (example: A = 18 AWG/1 Pair Twisted, Unshielded). This schedule shall also provide the manufacturer’s name and part number for the wire/cable being installed. 4. A system drawing for each applicable security system shall: a. Identify how all equipment within the system, from main panel to device, shall be laid out and connected. b. Provide full detail of all system components wiring from point-to-point. E611-1 11-09 c. Identify wire types utilized for connection, interconnection with associate security subsystems. d. Show device locations that correspond to the floor plans. e. All general and drawing specific notes shall be included with the system drawings. 5. A schedule for all of the applicable security subsystems shall be included. All schedules shall provide the following information: a. Device ID. b. Device Location (e.g. site, building, floor, room number, location, and description). c. Mounting type (e.g. flush, wall, surface, etc.). d. Power supply or circuit breaker and power panel number. e. In addition, for the IDS, provide the sensor ID, sensor type and housing model number. 6. Detail and elevation drawings for all devices that define how they were installed and mounted. E. Pre-installation design packages shall be reviewed by the Contractor along with a VA representative to ensure all work has been clearly defined and completed. All reviews shall be conducted in accordance with the project schedule. There shall be four (4) stages to the review process: 1. 35 percent 2. 65 percent 3. 90 percent 4. 100 percent F. Provide manufacturer security system product cut-sheets. Submit for approval at least 30 days prior to commencement of formal testing, a Security System Operational Test Plan. Include procedures for operational testing of each component and security subsystem, to include performance of an integrated system test. G. Submit manufacture’s certification of Underwriters Laboratories, Inc. (UL) listing as specified. Provide all maintenance and operating manuals. 1.04 APPLICABLE PUBLICATIONS A. The publications listed below (including amendments, addenda, revisions, supplement, and errata) form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. American National Standards Institute (ANSI)/Security Industry Association (SIA): PIR-01-00 ................................... Passive Infrared Motion Detector Standard - Features for Enhancing False Alarm Immunity CP-01-00 ................................... Control Panel Standard-Features for False Alarm Reduction C. Department of Justice American Disability Act (ADA) 28 CFR Part 36-90 ..................... ADA Standards for Accessible Design D. National Electrical Manufactures Association (NEMA): 250-03 ........................................ Enclosures for Electrical Equipment (1000 Volts Maximum) E. National Fire Protection Association (NFPA): 70-05 .......................................... National Electrical Code 731-06 ........................................ Standards for the Installation of Electric Premises Security Systems F. Underwriters Laboratories, Inc. (UL): 464-03 ........................................ Audible Signal Appliances 609-96 ........................................ Local Burglar Alarm Units and Systems 634-00 ........................................ Standards for Connectors with Burglar-Alarm Systems 639-97 ........................................ Standards for Intrusion Detection Units 1037-99 ...................................... Standard for Anti-theft Alarms and Devices 1635-96 ...................................... Digital Alarm Communicator System Units G. Uniform Federal Accessibility Standards (UFAS), 1984 1.05 WARRANTY OF CONSTRUCTION. A. Warrant IDS work subject to the Article “Warranty of Construction” of FAR 52.246-21. E611-2 11-09 PART 2 – PRODUCTS 2.01 EQUIPMENT AND MATERIALS A. General 1. All equipment associated within the IDS shall be rated for continuous operation. Environmental conditions (i.e. temperature, humidity, wind, and seismic activity) shall be taken under consideration at each facility and site location prior to installation of the equipment. 2. All equipment shall operate on a 120 or 240 volts alternating current (VAC); 50 Hz or 60 Hz AC power system unless documented otherwise in subsequent sections listed within this specification. All equipment shall have a back-up source of power that will provide a minimum of 96 hours of run time in the event of a loss of primary power to the facility. 3. The system shall be designed, installed, and programmed in a manner that will allow for ease of operation, programming, servicing, maintenance, testing, and upgrading of the system. 4. All IDS components located in designated “HAZARDOUS ENVIRONMENT” areas where fire or explosion could occur due to the presence of natural gases or vapors, flammable liquids, combustible residue, or ignitable fibers or debris, shall be rated Class II, Division I, Group F, and installed in accordance with National Fire Protection Association (NFPA) 70 National Electric Code, Chapter 5. 5. All equipment and materials for the system will be compatible to ensure functional operation in accordance with requirements. 2.02 EQUIPMENT ITEMS A. General: 1. All requirements listed below are the minimum specifications that need to be met in order to comply with the IDS. 2. All IDS sensors shall conform to UL 639, Intrusion Detection Standard. 3. Ensure that IDS is fully integrated with other security subsystems as required to include, but not limited to, the CCTV, PACS, EPPS, and Access Control System and Database Management. The IDS provided shall not limit the expansion and growth capability to a single manufacturer and shall allow modular expansion with minimal equipment modifications. B. IDS Components: The IDS shall consist of, but not be limited to, the following components: 1. Control Panel 2. Exterior Detection Devices (Sensors) 3. Interior Detection Devices (Sensors) 4. Power Supply 5. Enclosures C. Control Panel: 1. The Control panel shall be the main point of programming, monitoring, accessing, securing, and troubleshooting the IDS. Refer to American National Standards Institute (ANSI) CP-01 Control Panel Standard-Features for False Alarm Reduction. 2. The Control Panel shall provide a means of reporting alarms to an Access Control System and Database Management via a computer interface or direct connection to an alarm control monitoring panel. 3. The Control panel shall utilize a Multifunctional Keypad, Input and Output Modules for expansion of alarm zones, interfacing with additional security subsystems, programming, monitoring and controlling the IDS. 4. The Control panel shall meet or exceed the following minimum functional requirements for programming outputs, system response, and user interface: a. Programming Outputs: 1) 2 Amps (A) alarm power at 12 VDC 2) 1.4 A auxiliary power at 12 VDC 3) Four alarm output patterns 4) Programmable bell test 5) Programmable bell shut-off timer E611-3 11-09 b. System Response: 1) Selectable point response time 2) Cross point capability 3) larm verification 4) Watch mode 5) Scheduled events arm, disarm, bypass and un-bypass points, control relays, and control authority levels c. User Interface: 1) Supervises up to eight command points (e.g. Up to 16 unsupervised keypads can be used) 2) Provides custom keypad text 3) Addresses full function command menu including custom functions 4) Allows user authority by defined area and 16-character name 5) Provides for 14 custom authority control levels allowing user’s authority to change, add, delete pass codes, disarm, bypass points, and start system tests. 5. The Control panel shall meet or exceed the following technical characteristics: Input Voltage via 110 VAC or 220 VAC Step-down 16 or 18 VAC Transformer Operating Voltage 12 VDC Output Voltage 12 VDC @ 2 A max Direct Hardwire Zones 7 Partitions 8 Multifunctional Keypads 16 (2 per partition) Communications Port RJ-11 6. A multifunctional keypad shall be utilized as a user interface for arming, disarming, monitoring, troubleshooting, and programming the alarm control panel. 7. Keypads shall have the following features: a. Multiple function keypads suitable for remote mounting, no greater than 4000 ft (1333 m), shall be provided from the control panel and have a light emitting diode (LED) readout of alarm and trouble conditions by zone. b. An alphanumeric English language display, with keypad programmability, and EE-PROM memory, shall also be provided. c. Trouble alarm indicators shall be distinguishable from intrusion alarms. d. A minimum of four (4) zones selectable as entry and exit with programmable time delay. e. Complete system test activated capability at the keypad. f. Capability for opening and closing reports to a remote monitoring location. g. Adjustable entry and exit delay times. h. Capability for a minimum of two (2) multiple function keypads. i. Capability to shunt or bypass selected interior zones while arming perimeter protection and remaining interior zones. j. Capability for a minimum of seven assignable pass-codes that are keypad programmable from a suppressed master code. 8. Keypads shall meet or exceed the following technical characteristics: Connections 4-wire flying lead for data and power Operating Temperature 0°C to +50°C (+32°F to +122°F) Display Window 8-point LED Indicators: Illuminated keys Armed Status-LED Point Status-LED E611-4 11-09 Command Mode-LED Power-LED Voltage Nominal 12 VDC 9. An input module shall be utilized to connect additional detection devices to the control panel. This module will meet or exceed the following technical characteristics: Operating Voltage 8.5 to 14.5 VDC Nominal Zone Inputs Style A (Class B) Supervised Operating Temperature 32 to 140 degrees F (0 to 40 degrees C) 10. An output module shall be utilized to interface the control panel with other security subsystems. The output module shall meet or exceed the following technical characteristics: Operating Voltage 8.5 to 14.5 VDC Nominal Output Relays “Form C” Dry Relay Contracts Relay Contact Rating 4A @ 24 VDC 4A @ 24 VAC 1A @ 70 VAC Operating Temperature 32 to 140 degrees F (0 to 40 degrees C) 11. The control panel shall have a communications port that will allow for communications with a computer for programming, monitoring, and troubleshooting purposes. The communications port will be, at a minimum, and RJ-11 or better. 12. The control panel will have a systems success probability of 95% or better, and shall include the following success considerations: a. False Alarm: Shall not exceed one (1) false alarm per 30 days per sensor zone. b. Nuisance Alarm: Shall not exceed a rate of one (1) alarm per seven (7) days per zone within the first 60 days after installation and acceptance. Sensor adjustments will be made and then shall not exceed one (1) alarm per 30 days. 13. The Control Panel will be able to detect either a line fault or power loss for all supervised data cables. a. Line Fault Detection: Communication links of the IDS shall have an active mode for line fault detection. Fault isolation at the systems level shall have the same geographic resolutions as provided for intrusion detection. The line fault alarm shall be clearly distinguishable from other alarms. b. Power Loss Detection: Provide the capability to detect when critical components experience temporary or permanent loss of power and annunciate to clearly identify the component experiencing power loss. D. Exterior Detection Devices: (Sensors) 1. The IDS shall consist of interior, exterior, and other detection devices that are capable of: a. Locating intrusions at individually protected asset areas or at an individual portal; b. Locating intrusions within a specific area of coverage; c. Locating failures or tampering of individual sensors or components. 2. Audible annunciation shall meet UL 464 Audible Signal Appliance requirements as well as other stated within this specification. IDS shall provide and adjust for devices so that coverage is maximized in the space or area it is installed in. For large areas where multiple devices are required, ensure exterior device coverage is overlapping. 3. Detection sensitivity shall be set up to ensure maximum coverage of the secure area is obtained while at the same time limiting excessive false alarms due to the environment and E611-5 11-09 impact of small animals. All detection devices shall be anti-masking with exception of video motion detection. 4. Dual sensor technology shall be used when possible. Sensor technology shall not be of the same type that is easily defeated by a single method. This will reduce the amount of false alarms. 5. Exterior sensors described in this section are intended for outdoor use for perimeter and fence control monitoring purposes. Some sensors described in the interior sensor section may be utilized that can provide both outdoor and indoor protection. 6. External Sensors Environmental Characteristics: Temperature -25°F - 140°F (-32°C - 60°C) Pressure Sea Level to 15,000 ft. (4573m) above sea level Solar Radiation Six (6) hrs. exposure at dry bulb temp. 120°F (60°C) Rain Two (2) in. (50 mm) per hour Humidity 5% - 95% Fungus Components of non-fungus nutrient materials Salt/fog Atmosphere 5% salinity Snow loading 48 lbs per sq. ft. (234 kg per sq. meter) Ice accumulation Up to ½ in. (12.7 mm) radial ice Wind limitations 50 mph (80 km/h) Gusts to 66 mph (106 km/h) Acoustical Suitability Noise > 110 decibels (dB) 7. Electromechanical Fence Sensors: Shall sense mechanical vibrations or motion associated with scaling, cutting, or attempting to lift standard security chain link fence as follows: Note: Dead zones shall not exist from a monitoring and alarm coverage perspective. a. The sensor zone control unit shall alarm when a sufficient number of sensing unit activations surface within a specified time period. b. Individual sensing units and the alarm thresholds shall be field adjustable (i.e., performed by an authorized technician or trained maintenance personnel). Midrange sensitivity settings shall alarm a sensor when an intruder attempts to scale or climb the fence in areas of reduced sensitivity (e.g. around poles and rigid supports, etc.) and attempted lifting or scaling of a fence, including using assisted methods (e.g. items leaned against the fence, etc.)occur. Sensors shall allow gradual changes in fence positioning due to expansion, settling, and aging, without increased numbers of nuisance alarms taking place. c. Exterior sensor components shall be housed in rugged, corrosion-resistant enclosures, protected from environmental impact and degradation. d. Fence cable support hardware shall be weather-resistant. Interfacing between sensor zones and alarm enunciators, require they be installed in underground conduit and cables. e. Fencing Cable Technical Characteristics: Input voltage 12-30 V DC Current requirement 4 mA quiescent 25 mA (max) in alarm Transient suppression On data, power input lines and on E611-6 11-09 relay output Enclosure Weatherproof Sensor type Inertial band-pass-filter Transponder 4 zone controller Output relays for dry contacts, or RS-485 communication Inputs for weather sensor Sensor spacing 8.2 to 9.9 ft. (2.5 to 3 m) Data I/O RS 485 communications Data output • Vibration alarm (in either line) • Line alarm (in either line) • End of line action • Wind situation • Weather sensor line failure • Enclosure tamper switch • Program fail • A dry contact output with end of line resistor per each of 4 vibration inputs 8. Strain-Sensitive Cable Sensors: These devices shall detect movement on a standard security chain link fence associated with an intruder scaling, cutting through, or attempting to lift the fence fabric. The entire sensor system shall be mounted directly on the fence and able to withstand the same environmental condition exposures. Note: The length of the fence shall also maintain no sensor monitoring dead zones. a. Individual sensing units and the alarm threshold shall be field adjustable (i.e. by authorized technicians or trained maintenance personnel) for compensation of winds up to 25 mph (40 km/h) or by zone without increased nuisance alarms while maintaining specified sensor performance as under ambient conditions. b. Sensor zone control units shall provide an analog audio output for interface to an external audio amplifier to permit remote audio assessment regardless of sensor alarm status. The sensor zone control unit alarm output interface shall be a separately supervised relay contact normally open or normally closed. c. The length of the fence shall be divided into 300 ft. (100 m) zones. d. The sensing unit shall consist of transducer cable capable of achieving specified performance either by attachment directly to the fence fabric by plastic cable every 12 to 18 in. (300 to 455 mm) or by installation inside electrical metallic tubing conduit mounted on the fence. e. The sensing unit shall have equal adjustable sensitivity throughout the entire fence length. Only conventional waterproof coaxial cable connectors shall be used for connections of the sensing unit to avoid electrical magnetic interference. f. The entire sensor system shall be tamper resistant and capable of detecting tampering within each portion of the system by sensor zone. g. Magnetic Sensor Cable Technical Characteristics: Magnetic Sensor Cable Type cable Four (4) conductor magnetically loaded, aluminum foil E611-7 11-09 shield and ground wire Maximum zone length 1000 ft. (300 m) Life expectancy 10 years Sensitivity Uniform over length of cable Audio Bandwidth Five (5) kHz Outer Cover Black Polyurethane, Ultraviolet resistant Insensitive processing) Cable (remote Type cable 2 twisted pair, individually sealed Outer Cover Black Polyurethane, Ultraviolet resistant Dual Channel Signal Processor Input Power 10.2 – 13.8 VDC 65 mA Alarm Output Alarm contacts SPNC 0.75 mA, 200 VDC Indicators Three (3):Alarm, tamper, events Cut processor Sensitivity - 10 settings Time window – 0.5 – 4.5 min Event Counter – nine (9) Climb processor Sensitivity – 10 settings 9. Buried Electromagnetic Cable Sensor: a. The system shall be able to function as a standalone system or as an integral component of a centralized security control system. b. The detection field shall be formed by radio-frequency (RF) signals carried by sensor cables that are buried along the perimeter. c. The RF signals shall form an invisible electromagnetic detection field around the sensor cables that can detect the presence of an intruder passing through the field. d. The system shall detect moving intruders that have a significant electromagnetic field (e.g. humans, vehicles, and other large conductive objects) while rejecting other environmental stimuli such as birds, small animals, weather elements. e. A sensor module shall contain the electronics required to: 1) Transmit and receive the RF signal without the use of an external antenna. 2) Monitor the detection fields of two (2) zones and produce an alarm when an intruder enters the zones. f. Field power modules shall be available for standalone systems and networked systems. g. As a standalone system, the primary operator interface shall be a local interface module that is connected directly to the sensor module. h. As part of a network configuration, the primary operator interface shall be a personal computer (PC) based central controller. The central controller shall monitor the performance of the entire buried coaxial cable outdoor intrusion detection system and any auxiliary sensors. The central controller shall have the capability of acknowledging, processing and reporting alarms. A customized color site map that is displayed on the PC monitor shall be an available option for the system to monitor sensor locations. i. Transmission and reception shall be accomplished without the use of antennae. The RF signal shall be monitored and analyzed by the sensor module for any changes in the detection field properties that would indicate the presence of an intruder. E611-8 11-09 j. Alarms generated by internal electronic processes (cables excluded) shall not exceed one (1) per zone per month. System generated alarms are averaged based on the total number of zones in the system. k. When the system is calibrated in accordance with the manufacturers' recommendations, the detection field shall be continuous and uniform over the protected site perimeter. l. When system sensitivity is calibrated according to manufacturers' recommendations, the detection field shall not detect a valid target that is a minimum of 6.5 ft. (2 m) from the nearest sensor cable. m. Buried Electromagnetic Cable Sensor Technical Characteristics: Burial Medium Clay, sand, soil, asphalt, concrete Snow limitation Up to 1 ft. (30cm) deep Degradation Guaranty Minimum 10 yr. Detection Medium Radio Frequency (RF) Detection Coverage Maximum 656 ft. (200m) per zone Detection Capability Human: >75 lbs. (34 kg) Detection Speed Human walk, crawl, run, roll, jump 1 in./sec. (2.5 cm/sec) – 50 ft./sec. (15 m/sec. regardless of direction across field Velocity Response Programmable Detection Probability Human: 99% with 95% confidence factor Animal: Less than 22 lbs. (10 kg.) Less than 5% with 90% confidence factor Terrain Capabilities Detection Even to uneven ground with maximum (max) grade 13 ft. (4 m) Corner bend radius 22 ft. (6.5m) Detection Section Field Cross Upright walking; Height: 3.2 ft. (1m) above ground Width: 6.5 ft. (2m) single cable 9.75 ft. (3m) double cable Sensing Element Ported (leaky) coaxial cables Cable Construction Abrasion and chemical resistant, high density polyethylene, with flooding compound Cable Requirements Two (2):Transmit cable, receive cable Configurations Available Two (2):Single cable, double cable Cable Lengths 164 ft. (50 m), 328 ft. (100 m), 492 ft. (150 m), 656 ft. (200 m) Zone Length Minimum 33 ft. (10 m) Antenna Requirements None False alarm rate Less than one (1) per day E611-9 11-09 n. Sensor Module: Each sensor module shall transmit, receive and process the electromagnetic detection fields independently from other sensor modules. Failure of one (1) sensor module shall not affect the remainder of the perimeter. The sensor module shall operate as either a standalone unit, or in a network configuration in conjunction with a central controller. The sensor module shall be mounted in a weatherproof enclosure when installed outdoors as follows. 1) The sensor module shall use an adaptive filter to analyze the detection signal and adjust the signal processing to reduce nuisance alarms caused by environmental factors such as rainfall or slow-running water. 2) The sensor module shall identify, by type, sensor, tamper, and failure alarms either locally at the sensor module, or centrally at a central controller. The sensor cables shall provide the data paths between the sensor modules, for the transmission, reception and display of alarm conditions. 3) Each sensor module shall include an internal interface for the collection of auxiliary sensor data. 4) It shall be possible to supply power directly to each unit for applications that require either a single sensor module or multiple sensor modules with independent power sources. 5) The sensor module's response shall be demonstrated by an analog output signal that can be displayed on a voltmeter or on an analog voltage-recording device. The output signal shall be encoded to indicate the alarm trip-point, thereby showing the sensor module’s degree of detection above or below the level required to cause an alarm. 6) Sensor Module Technical Characteristics: Sensor Module Power 12 VDC at 150 milliampere (mA) Output Sensor Module Requirements Power Stand-alone: 12 VDC 500 mA max Network: 48 VDC 175 mA max Sensor capability Two (2) zones independent of other sensor modules Sensor coverage 1,312 ft. (400 m) Calibration Locally and remotely from Central Controller Self Test Via 4 relay drive points Detection coverage Unlimited expansion using multiple modules Nuisance avoidance Adaptive filtering Connectivity RS-485 twisted pair cable Sensor Support Dual redundant data paths Transmission capability Eight (8) contact-closure signals o. The field power module shall be capable of supplying power to sensor modules as follows: 1) In a network configuration where power is supplied redundantly via the sensor cables, the sensor modules shall operate within specifications when power is removed from either of the two (2) sensor cables. 2) Each cable zone shall be capable of being calibrated either locally at the sensor module, or remotely from a central controller. Additional signal processing parameters, including high speed and low speed response, shall be capable of being set from a central controller. E611-10 11-09 3) Detection sensitivity for each zone shall be adjusted either locally at the sensor module with a local interface module, or from a central controller. Access to the local calibration controls shall require the removal of the enclosure’s cover and shall cause a tamper alarm to be generated. 4) Power Module Technical Characteristics: Output support Nine (9) sensor modules max 3,063 yards (yds.) (2,800 m) System block configuration 1,531 yds. (1,400 m) Power Output Stand-alone: 12 VDC 500 mA max Network: 48 VDC 175 mA max 10. Microwave Sensors: The system shall be a modular microwave outdoor intrusion detection sensor based on microwave radar technology. The detection field shall be formed by radio frequency (RF) signals, in the X-band, carried between a transmitter and a receiver. The RF signals shall form an invisible electromagnetic detection field that can detect the presence of an intruder who walks, crawls, rolls, jumps, or runs through a detection field as follows. a. transmitter shall create the RF signals that form the detection field. A receiver shall house the necessary electronics to monitor the detection field and to raise an alarm when an intruder enters the field. The transmitter and receiver shall be powered individually, as a standalone unit. b. An electromagnetic wave is emitted by the antenna of the transmitter and received by the antenna of the receiver. The receiver shall detect changes that are caused by the presence of an intruder. c. The system shall detect moving intruders having a significant electromagnetic crosssection (e.g. humans, vehicles, and other large conductive objects) rejecting other environmental stimuli. d. The system shall be capable of detecting human intruders moving through the detection field regardless of the direction of motion. e. Processor description: The receiver shall contain the necessary electronics to perform the signal processing for the detection zone. The transmitter and receiver shall be operated as a standalone unit with independent power and data. Both the transmitter and receiver shall be installed in weatherproof enclosures. f. Distributed processing: Transmitter-receiver pairs distributed along a perimeter shall provide extended range and fail-safe operation. The failure of one (1) pair shall not affect the coverage of the remainder of the perimeter. g. Alarms: The signal processor shall identify intrusion and tamper/fail alarms locally, at the transmitter or receiver. 1) An alarm caused by opening the outer enclosure of the transmitter or receiver shall be identified as a tamper alarm. Tamper alarms shall be distinctive from intrusion alarms. 2) Alarms caused by power failure or internal electronic failure are fail alarms, distinctive from intrusion alarms. h. Microwave Sensor System Technical Characteristics: Operating voltage 11 – 15 VDC 70mA max. current Transmitter Operating voltage 11 – 15 VDC 30mA max. current Receiver Operating Environment -22F (–30ºC) and 140 F (60ºC) LEDs POWER ON, WRONG CHANNEL, ALARM E611-11 11-09 Maximum zone length 33 ft. (10 m) and a maximum of 1500 ft. (457 m) per zone. Detection Success Probability 75 lbs. (34 kg) 99% with a 95% confidence factor Operating frequency X Band 10.525 ± 0.025 gigahertz (GHz) Type modulation Class A2 with one (1) of six (6) selectable crystal-controlled frequencies. Detection movement speed 2.0 in. sec. (5 cm/sec.) to 26 ft. sec. (8 m/sec.) Audio assessment Via 1/8 in. phone jack on receiver Alarms Tamper, failure, intrusion Tamper/fail alarm Via sealed relay rated one (1) ampere 28 VDC Intrusion field alarm Via sealed relay rated two (2) ampere 28 VDC. Intrusion alarm latch time Adjustable: 0.5 sec and 10 sec Processing Distributed: receiver/transmitter pairs Perimeter Length Single Receiver/transmitter pair: 1500 ft. (457 m) Multiple pairs: Unlimited 11. 12. Taut-wire Sensors: These sensors shall consist of a perimeter intrusion detection sensor incorporated into a wire security fence. Intrusion detection shall be achieved by sensing the cutting of any single wire or deflection of the fence, such as by climbing. a. Sensor zone: Includes one (1) or more 200 ft. (61 m) maximum sections of seven (7) ft.(2.3 m) high parallel fence. Each sector shall consist of 13 horizontal barbed wires attached to the taut-wire fence posts, and three (3) strands as outriggers, and an "antiladder" trip wire supported by rods extending from the outriggers for a total vertical height of approximately eight (8) ft. (2.6 m). b. Displacement switches for each horizontal wire shall be mounted within a pre-wired channel fastened to the fabric fence post at the midpoint of each section. Outrigger barbed wire and tripwire may share the same switch in these locations. c. Abnormal displacement of a switch lever resulting from cutting or deflecting its attached wire, as by climbing on or through fence strands, shall initiate an alarm condition. A damping mechanism within the sensor shall reduce alarm thresholds due to slowly changing environmental phenomena such as the ground shifting, daily and seasonal temperature variations, winds changes, etc. d. Sensor switches shall be provided with electrical contact closures as a means for initiating an alarm condition. e. The system shall provide relay outputs to interface alarm outputs with the overall IDS. f. Taut-wire Sensor Technical Characteristics: Power requirements Input: 120 – 208 VAC Sensor zone control unit capability Up to 10 zones Sensitivity 0.75 in. (19 mm) Environment Limits Winds up to 35 mph (56 km/h) Electrostatic Field Sensors: These sensors generate an electrostatic field around one (1) or more horizontal wires and detect intrusion of the electrostatic field as follows. a. Sensors shall initiate an alarm when an intruder attempts to approach or scale a fence or physical barrier. Electrostatic field sensors shall detect human presence by generating an E611-12 11-09 electric field around one (1) or more horizontal wires that detects the induced signal in parallel sensing wires. b. Sensors shall monitor the induced signal for changes that result from the presence of a human body, which distorts coupling between transmitting and sensor wires. c. Sensor components shall consist of one (1) or more signal generator field wires and mounting hardware, sensing wires, an amplifier/signal processors, power supplies, and necessary circuitry hardware. Mounting and support hardware shall be provided by the equipment manufacturer. d. Wires shall be spring tension-mounted and provided with end-of-line terminators to detect cutting, shorting, or breaking of the wires. e. Sensor configuration shall be able to detect an intruder that may crawl under the bottom wire, through the wires, or over the top wire by divided sensor zones. f. Signal processing circuitry shall provide filtering to distinguish nuisance alarms. g. Sensor configuration shall incorporate balanced, opposed field construction to eliminate distant field noise. h. Sensor sensitivity shall be adjustable. Adjustment controls shall be inaccessible to operating personnel and system sensitivity controls shall be set at approximately midrange. i. Sensors shall provide some means of indicating an alarm condition at the protected perimeter to facilitate installation and calibration. j. The sensor system shall include an indicator disabling device within a tamperproof enclosure. k. Electrostatic Field Sensor Technical Characteristics: Power 115 -120 VAC transformer Operating Requirements Power 16-22 VAC, 225 mA single zone 275 dual zone Detection Sensitivity 77 lbs within 3 ft. (915 mm)- midrange setting Detection Velocity 0.1 ft. (30 m) - 10 ft. (300 m) per sec Supervision AC Monitoring of fence and field wires – open, short, and grounded circuits Tamper Switch One (1)-pole, two (2) position Lightening arrestor Transistors on all relay output and power inputs Battery Charger Built-in Processor Enclosure Base plate, steel NEMA enclosure Weather resistant 13. Gate Sensors: They shall be provided in accordance with specific fence sensor manufacturer's recommendations to ensure continuous fence sensor zone protection for the entire protected perimeter. a. When gate units are not provided by the fence sensor manufacturer, provide separately zoned Balanced Magnetic Switch (BMS) gate sensors. b. Sensors shall perform as specified in Section 2.03-E.6 entitled "Balanced Magnetic Switches (BMS)." E. Interior Detection Devices: (Sensors) 1. The IDS shall consist of interior, exterior, and other detection devices that are capable of: a. Locating intrusions at individually protected asset areas or at an individual portal; b. Locating intrusions within a specific area of coverage; c. Locating failures or tampering of individual sensors or components. E611-13 11-09 2. Provide and adjust for devices so that coverage is maximized in the space or area it is installed in. For large rooms where multiple devices are required, ensure device coverage is overlapping. 3. Detection sensitivity shall be set up to ensure maximum coverage of the secure area is obtained while at the same time limiting excessive false alarms due to the environment and impact of small animals. All detection devices shall be anti-masking with exception of video motion detection. 4. Dual sensor technology shall be used when possible. Sensor technology shall not be of the same type that is easily defeated by a single method. This will reduce the amount of false alarms. 5. Interior Environmental Conditions: Systems shall be able to operate in environmentally protected interior areas and shall meet operational performance requirements for the following ambient conditions: a. If components are installed in unheated areas they shall be able to operate in temperatures as low as -17 C; b. Interior Sensor Environmental Characteristics: Temperatures 0 to 50 C Pressure Sea Level to 15,000 ft. (4573m) above sea level Humidity 5% - 95% Fungus Components of non-fungus nutrient materials Acoustical Noise Suitable for high noise environments above 100db 6. Balanced Magnetic Switches (BMS) a. BMS switches shall be surface or recessed mounted according to manufacture’s instructions. Recessed mounted is the preferred method to reduce tampering or defeating of the system. Switches shall activate when a disturbance in the balanced magnetic field occurs. b. Switches shall have a minimum of two (2) encapsulated reed switches. c. Contractor shall provide each BMS with a current protective device, rated to limit current to 80% of the switch capacity. d. Surface Mounted BMS: For exterior application, components shall be housed in weatherproof enclosures. e. BMS field adjustments in the fixed space between magnet and switch housing shall not be possible. Attempts to adjust or disturb the magnetic field shall cause a tamper alarm. f. BMS Technical Characteristics: Maximum current .25 amperes Maximum voltage 30 VDC Maximum power 3.0 W (without internal terminating resistors). resistors). Components 1.0 W (with internal Three (3) pre-adjusted reed switches Three (3) pre-adjusted magnets Output contacts Transfer type SPDT Contact rating 0.5 amperes, 28 VDC Switch mechanism Internally adjustable E611-14 terminating 11-09 ¼ - ½ in. (6-13 mm) Wiring Two (2) wires #22 American Wire Gauge (AWG), three (3) or 11 foot attached cable Activation lifetime 1,000,000 activations Enclosure Nonferrous materials Tamper alarm activation Cover opened 1/8 in. (3 mm) and inaccessible until actuated 7. Window Intrusion Detection: These IDS devices shall detect intrusions thru inertia (shock) or by sound, and shall utilize either a Breakwire Sensor or Acoustic and Seismic Sensor. a. Breakwire Sensors (wire trap): 1) Detect intrusion thru shock or breakage of window glazing. Also used for the protection of utility openings. 2) Sensors shall consist of fine wire embedded in or affixed to interior of glazing. Breakage of protected glazing shall result in wire breakage. 3) Wire shall be hard-drawn copper up to #26 AWG diameter. 4) If sensors are affixed to glazing the sensor shall be protected by a clear coating which shall not affect sensor functioning. 5) Sensor shall be terminated in insulated connectors which are concealed and tamper resistant. 6) Protection of inlet openings: a) Shall consist of up to 26 AWG hard-drawn copper wire with a tensile strength of 17.8 N 4 pounds maximum. b) Wire shall be interlaced throughout the opening such that no opening between wires shall be larger than 4 in. (100 mm) on center. c) Sensors shall be terminated so that attempts to cut the wire or otherwise enlarge openings between wires shall cause an alarm. d) Sensors shall be terminated in insulated connectors which are concealed and tamper resistant. b. Acoustic and Seismic Glass Break Detectors: 1) Detects intrusion thru the use of audible sound and vibration emitted from the breaking of glass using a tuned frequency range and sound pattern recognition. This initiates an alarm when glass they protect is broken or cracked. 2) Detectors shall be installed in strict conformance with manufacture’s installation instructions. 3) The detector’s power circuit shall be switched via an output relay on the control panel to provide latching alarm LED reset capability. 4) Sensors shall be contained in a fire-resistant ABS plastic housing and must be mounted in contact with a window. 5) Sensing shall be accomplished through the use of a mechanical filtered piezoelectric element. 6) Sensors shall have a sensitivity adjustment controlling output voltage from the piezoelectric element which triggers a solid-state latching device. 7) Sensors shall selectively filter input to minimize false alarms and not initiate alarm in response to ambient seismic vibrations or other ambient stimuli. 8) A manufacture’s test unit will be used to validate the sensor by simulating glass breakage. 9) The Contractor shall provide sensors for adjusting sensitivity and two-sided polyurethane tape with acrylic adhesive for window attachment. 10) Sensor shall include exterior label to protect adhesive tape from direct sunlight. 11) Window Intrusion Detection Sensor Technical Specifications: E611-15 11-09 Power Auxiliary power supply 12 VDC @ 25 mA (+/-) 10% Power Input 10 – 15 VDC at 16mA protected against reverse polarity, 20 mA during relay closure Relay Output Rating Minimum of 25 VDC mA Coverage Audio 6,000 Square ft. Coverage Glass Break 25 ft. (7.5 m) wide by 25 ft. wide (7.5 m) Minimum: 25 feet (7.62 m) from the detector to the furthest point on protected glass. Audio Output 300 – 12,000 HZ Alarm Output Relay NO or NC selectable Interconnection 12 pin Panduit connector, 22 AWG Radio Frequency Interface No alarm or setup on between frequencies 26 – 100 MHz 50 v/m Immunity to mobile RF interference 100 watts @ 9.8 Ft. (3 m) in 27-100 MHz range Alarm period Two (2) to three (3) Mounting Ceiling, same wall, adjacent wall, opposite wall Features Test and alarm LEDs for acoustic seismic and alarm condition latching, Alarm LED and tamper switch on cover. Alarm verification Digital signal processing processing technologies Detection ability Single and multi-pane glass, wired glass, tempered and laminated glass to ¼ inch (6 mm) or thickness or dual acoustic 8. Screening: This material shall be used on windows to protect and detect intrusion as follows. a. Security screens shall be constructed from a maximum of 26 AWG insulated hard-drawn copper. b. Screens shall be connected to an alarm circuitry by means of flexible armored cords. Security screen circuitry shall provide end-of-line resistors in series or equivalent methods ensuring alarm activation if short-circuiting of the screen is attempted. c. If unable to install a break wire sensor (wire traps), then tamper switches will be provided. d. Contractor shall provide tamper switches in the frames as required with not less than one (1) switch on each side if dimensions are two (2) ft. square (610 mm) or less, and two (2) switches if dimensions exceed two (2) ft. square (610 mm). Tamper switches shall be corrosion-resistant, spring-operated, and shall initiate an alarm with a movement of two (2) in. (50 mm) or less before access to the switch is possible. e. Electrical characteristics of the switch shall match the alarm system requirements. 9. Vibration Sensors: These sensors shall initiate alarms upon detecting drilling, cutting, or blasting through walls, or other methods of forced entry through a structure as follows. E611-16 11-09 a. Sensors shall detect and selectively amplify signals generated by forced penetration of a protective structure. b. Sensors shall be designed to give peak response to structurally conveyed vibrations associated with forcible attack on the protected surface. c. Sensors will initiate an alarm if attempts are made to remove them from the surface of the wall. d. Sensors shall be enclosed in protective mountings. e. Sensors shall include an adjustable alarm discriminator to prevent incidental vibrations which may occur from triggering the alarm circuit. f. Sensors shall be provided with a tamper switch. g. Sensor sensitivity shall be individually adjustable unless a sensor is designed to accommodate vibration ranges of specific surface type on which it will be mounted. Sensitivity adjustments shall not be accessible without removing the sensor cover. Also, a sensor shall not be responsive to airborne sound. h. Vibration Sensor Technical Characteristics: Power requirements External DC power source Eight (8)- 14.5 VDC, two (2) volt max peak to peak ripple Alarm output Form C (NO/C/NC) solid state alarm relay, rated 100 mA, 28 VDC Tamper Connection Tamper switch and external magnetic Current rating and alarm output No alarm state 20mA SPDT relay contact rating (Form C) Sensor range Concrete (poured) 13.2 ft. (4 m) Concrete block 6.6 ft. (2 m) Brick block 3.3 ft. (1 m) Frequency range 3kHz-20kHz (-15db) 7kHz-10kHz (-10db) Adjustable Sensitivity eight (8) steps Alarm response 0-30 sec 10. Passive Infrared Motion Sensors (PIR): These sensors shall detect an intruder presence by monitoring the level of infrared energy emitted by objects within a protected zone and meet ANSI PIR-01 Passive Infrared Motion Detector Standards Features for Enhancing False Alarm Immunity. An alarm shall be initiated when motion and temperature changes within set patterns are detected as follows. a. The detector shall provide multiple detection zones distributed at a variety of angles and distance. b. Sensors shall be passive in nature; no transmitted energy shall be required for detection. c. Sensors shall be sensitive to infrared energy emitted at wavelengths corresponding to human body and other objects at ambient temperatures. d. Sensors shall not alarm in response to general area thermal variations and shall be immune to radio frequency interference. e. Sensors shall not be susceptible to changes in temperature due to an air conditioner being turned on or off. f. Sensors shall be housed in a tamper-alarmed enclosure. g. Sensor detectors shall include motion analyzer processing, adjustable lens, and walk test LED’s visible from any angle. E611-17 11-09 h. Sensors shall provide some means of indicating an alarm condition during installation and calibration. A means of disabling the indication shall be provided within the sensor enclosure. i. Sensor detectors shall include a motion monitoring verification circuit that will signal trouble or alarm if the detector fails to detect motion for an extended period. j. PIR Technical Characteristics: Power Six (6) – 12 VDC 25 mA continuous current draw 38 mA peaks Alarm Velocity Five (5) ft. (1500 mm) at a velocity of 0.1 ft. (30 mm) per second, and one (1) step per second, assuming 6 in. (150 mm) per step. Also, faster than 0.1 foot (30 mm) per second, up to 10 feet (3000 mm) per second 11. Maximum detection range 35 ft.(10.6 m) Frequency rangeactivation or setup use 26 to 950 MHz using a 50 watt transmitter located 1 ft. from the unit or attached wiring non Infrared detection 3°F (1 1/2°C) different from the background temperature Detection Pattern 180 degrees for volumetric units, non PIR 360 PIR 360°Detection Pattern Programmable 60 detection zones including one directly below Mounting Ceiling and walls Ceiling heights Eight (8) ft. (2.4 m) – 18 ft (5.4 m) Sensitivity adjustments Three (3) levels Microwave-Passive Infrared Detector: This sensor shall be designed to detect the motion of a human body within a protected area by means of a combination of microwave sensing technology and passive infrared (MPIR) sensing technology as follows. a. The sensor shall require both technologies to sense intrusion before an alarm may occur. b. The sensor shall be designed for wall mounting on swivel bracket. A high-security gimbaled bracket shall be provided. c. The PIR fields of view shall be focused on the pyroelectric element by means of an internal multi-faceted mirror. d. The sensor shall incorporate a look-down lens system that detects the passing of an intruder directly beneath the sensor. e. The sensor shall incorporate a microwave supervision system which shall activate the trouble output if the device technology fails. f. The sensor shall incorporate self-diagnostics which shall monitor the sensor systems and report a trouble to the control panel if any system device fails. g. The sensor shall have compensation against loss of sensitivity as the ambient temperature nears human body temperature. E611-18 11-09 h. MPIR Technical Characteristics: Technology Microwave and Passive Infrared Power Nine (9) – 15 VDC max current consumption 22 mA at 12 VDC Operating Temperature 32°F (0° C) – 120° F (49° C) Detection Area 98 ft. (30 m) long by 9.8 ft. (3 m) wide or 69 ft. (21 m) long by 69 ft. (21m) wide Electronics Microcontroller based Alarm Contact Form-C rated 125 mA, 28 VDC Tamper Contact 125 mA, 28 VDC Trouble Contact Form-B rated 25 mA, 30 VDC Microwave Frequency 12. Operating 10.525 GHz Microwave Sensitivity Adjustable on circuit board Detection pattern adjustment Changing of internal lens Sensing element Pyro-electric LED Indicators PIR, microwave, alarm Bug and Dust protection zero-clearance, gasket bug guard Lens Interchangeable: standard 60x80 ft. (18x24 m), corner mounting, ultra-wide, pet alley, long range, room and corridor combo, room and ceiling combo, creep zone Ultrasonic Sensors: These sensors shall transmit ultrasonic energy into a protected zone, receiving the direct and reflected energy, and monitoring frequency shift between transmitted and received signals as follows. a. Sensors shall automatically adapt to changing levels of air turbulence and shall consist of a control unit and as many transceivers as required to protect a zone within limitations of the control unit per manufacture’s instructions. b. Ultrasonic system sensors shall provide a means of indicating an alarm condition at the protected zone during installation and calibration. This indication shall be provided with a disabling device within the sensor enclosure. c. Transceivers shall consist of an adjustable-gain preamplifier, an ultrasonic-to-electrical transducer, and an electrical-to-ultrasonic transducer in a single enclosure. Transducers shall be adjustable in position to allow adequate adjustment and directivity. d. Each sensor will consist of sensitivity adjustments. Controls shall be inaccessible to operating personnel and sensitivity requirements shall be set approximately at midrange. e. Sensor elements shall be housed in a tamper-alarmed enclosure. f. Ultrasonic Sensor Technical Characteristics: Power output Peak not to exceed 105 dB at three (3) ft. (900 mm) Transceiver protection zone 20 ft. (6 m) by 30 ft. (9.2 m) in a zone with an 8 ft. (2440 mm) to 12 ft. (3660 mm) ceiling Nuisance alarm reduction Selective filtering Detection frequency range Above 24 kHz and below 30 kHz (nominally 26 E611-19 11-09 kHz) Detection velocity 5 ft. (1500 mm) at a velocity of 0.5 ft. (150 mm) per second to 15 feet (4570 mm) per second, also Higher than 0.5 foot (150 mm) per second, up to eight (8) ft. (2440 mm) per second 13. Photoelectric Sensors: The sensor devices shall be able to detect an intruder presence by sending out a series of infrared or ultraviolet beams. Intrusion is based on disruption of the signal beams as follows. a. Sensors shall consist of a modulating transmitter, focusing lenses, mirrors, demodulating receiver, power supply, and interconnecting lines. b. Beam transmitters shall be designed to emit light. Beams may be reflected by one (1) or more mirrors before being received and amplified. c. The photoelectric sensor shall initiate an alarm when the beam is interrupted with monitoring controls set at midrange. d. Transmitted beams shall be uniquely modulated to prohibit defeat of the IDS system by shining another light source into the receiver. e. Sensors shall provide a means of local alarm indication on the detector for use at the protected zone during installation and calibration. f. Sensors shall include an indicator-disabling device within the sensor enclosure. g. Sensors shall utilize automatic gain control or be provided with sensitivity adjustments to allow for various beam lengths. h. Sensor controls shall be inaccessible to operating personnel. i. Sensors that use multiple beams shall be tested by attempting to crawl under and jump through and over beams. Each system sensor shall provide cutoffs of at least 90% to handle a high percentage of light cutoffs prior to initiating an alarm. j. Sensor components shall be housed in tamper-alarmed enclosure. k. Photoelectric Sensor Technical Characteristics: Power requirements Nine (9)-16 VDC, protected against reverse polarity Relay output Normally closed. 18 ohm resister in series with contacts. 0.5 amperes resistance/24 VDC Current Transmitter 15 mA, Receiver 15 mA LED Alignment, walk-test alarm, off Range Indoor: 130 ft. (39 m) Outdoor: 65 ft. (19.5 m) Alarm relay contacts Two (2) amperes at 120 VAC minimum Enclosure High impact acrylic Type Dual beam Mounting Wall, corner, flush Beam width Six (6) degrees Receiver field of view Six (6) degrees horizontal and vertical Adjustments Vertical +10 – 20 degrees Horizontal 30 degrees E611-20 11-09 14. 15. Alarm period Two (2) – three (3) sec Infrared source Long-life Gallium Arsenide LED Infrared sensor PIN photodiode Transmitter Frequency One (1) kHz 10 microsecond pulse width IR Wavelength 950 nm CCTV Video Motion Detection Sensors: Refer to Section 28 23 00 VIDEO SURVEILLANCE that outlines related video motion detection requirements. Pressure Mat Detectors: These devices shall be able to detect the presence of people in a localized zone. Pressure from standing or walking across an area where a mat is place detects a closed circuit as follows. a. The mat shall be easily interfaced directly to a micro-sensor controller. b. Shall be sealed on all edges and pre-wired and made of durable material that is waterproof for indoor/outdoor use. c. This pressure sensitive mat shall be capable of being easily hidden under existing carpet or other entry mat without effecting operation, to include the prevention of false or nuisance alarms. d. Shall have a slip resistant surface with four (4) lead fail-safe wiring. e. Mat detectors shall be resistant to water and dust and the wiring circuitry shall be capable of direct supervision. f. Pressure Mat Detector Technical Characteristics: Operating Voltage 15 VDC AC with max current 20 mA Activation Weight 80 lbs. (36.28kg. per 3 in. (76.2mm) square Activation Lifespan 500,000 activations without failure 16. Tamper Alarm Switches: The following IDS sensors shall be used to monitor and detect potential tampering of sensors, control panels and enclosures. a. Tamper Switches: All enclosures including cabinets, housings, boxes, raceways, and fittings with hinged doors or removable covers containing circuits and power supplies related to the IDS shall include corrosion-resistant tamper switches. b. Tamper alarms shall be annunciated to be clearly distinguishable from IDS alarms. c. Tamper switches will not be in a viewable from a direct line of sight perspective. The minimum amount of time the tamper switch becomes active and sends a signal after an enclosure is opened or panel removable is attempted, shall be one (1) second. d. Tamper switches will initiate when enclosure doors or covers is removed as little as 1/4 in. (6.35 mm) from the closed position unless otherwise indicated. Tamper switches shall be: 1) Push/pull automatic reset type; 2) Inaccessible until switch is activated; 3) Spring-loaded and held in closed position by door or cover; and 4) Wired to break a circuit when door or cover is removed with each sensor annunciated individually at a central reporting processor. e. Fail-Safe Mode: Shall provide the capability to detect and annunciate diminished functional capabilities and perform self-tests. Fail-safe alarms shall be annunciated to be clearly distinguishable from other types of alarms. F. Power Supply 1. A power supply shall only be utilized if the control panel is unable to support the load requirements of the IDS system. E611-21 11-09 2. All power supplies shall be UL rated and able to adequately power two entry control devices on a continuous base without failure. 3. Power supplies shall meet the following minimum technical characteristics: INPUT POWER 110 VAC 60 HZ 2 amp OUTPUT VOLTAGE 12 VDC Nominal (13.8 VDC) 24 VDC Nominal (27.6 VDC) Filtered and Regulated BATTERY Dependant on Output Voltage shall provide up to 14 Ah, rechargeable OUTPUT CURRENT 4 amp max. @ 13.8 VDC 3 amp max. @ 27.6 VDC BATTERY FUSE SIZE 3.5 A @ 250 VAC CHARGING CIRCUIT Built-in standard G. Enclosures: 1. All control panels, input and output modules, and power supplies shall be housed inside a metal enclosure in accordance with National Electrical Manufactures Association (NEMA) 250 Enclosures for Electrical Equipment. 2. The enclosure shall be UL rated, lockable and alarmed with a tamper alarm switch that is monitored by the control panel. 3. The enclosures will be NEMA 4 rated if exterior mounted. 4. All connections to the enclosure shall meet or exceed the requirements set forth in the NEC. 2.03 INSTALLATION KIT A. General 1. The kit shall be provided that, at a minimum, includes all connectors and terminals, labeling systems, audio spade lugs, barrier strips, punch blocks or wire wrap terminals, heat shrink tubing, cable ties, solder, hangers, clamps, bolts, conduit, cable duct, and/or cable tray, etc., required to accomplish a neat and secure installation. All wires shall terminate in a spade lug and barrier strip, wire wrap terminal or punch block. Unfinished or unlabeled wire connections shall not be allowed. All unused and partially opened installation kit boxes, coaxial, fiberoptic, and twisted pair cable reels, conduit, cable tray, and/or cable duct bundles, wire rolls, physical installation hardware shall be turned over to the Contracting Officer. The following sections outline the minimum required installation sub-kits to be used: 2. System Grounding a. The grounding kit shall include all cable and installation hardware required. All head end equipment and power supplies shall be connected to earth ground via internal building wiring, according to the NEC. b. This includes, but is not limited to: 1) Coaxial Cable Shields 2) Control Cable Shields 3) Data Cable Shields 4) Equipment Racks 5) Equipment Cabinets 6) Conduits 7) Cable Duct blocks 8) Cable Trays 9) Power Panels 10) Grounding 11) Connector Panels E611-22 11-09 3. Coaxial Cable: The coaxial cable kit shall include all coaxial connectors, cable tying straps, heat shrink tabbing, hangers, clamps, etc., required to accomplish a neat and secure installation. 4. Wire and Cable: The wire and cable kit shall include all connectors and terminals, audio spade lugs, barrier straps, punch blocks, wire wrap strips, heat shrink tubing, tie wraps, solder, hangers, clamps, labels etc., required to accomplish a neat and orderly installation. 5. Conduit, Cable Duct, and Cable Tray: The kit shall include all conduit, duct, trays, junction boxes, back boxes, cover plates, feed through nipples, hangers, clamps, other hardware required to accomplish a neat and secure conduit, cable duct, and/or cable tray installation in accordance with the NEC and this document. 6. Equipment Interface: The equipment kit shall include any item or quantity of equipment, cable, mounting hardware and materials needed to interface the systems with the identified sub-system(s) according to the OEM requirements and this document. 7. Labels: The labeling kit shall include any item or quantity of labels, tools, stencils, and materials needed to label each subsystem according to the OEM requirements, as-installed drawings, and this document. 8. Documentation: The documentation kit shall include any item or quantity of items, computer discs, as installed drawings, equipment, maintenance, and operation manuals, and OEM materials needed to correctly provide the system documentation as required by this document and explained herein. PART 3 - EXECUTION 3.01 INSTALLATION A. IDS installation shall be in accordance with Underwriters Laboratories (UL) 639 Standards for Intrusion Detection Units and UL 634 Standards for Connectors with Burglar Alarm Systems, and appropriate manufacture’s installation manuals for each type of IDS. B. Components shall be configured with appropriate “service points” to pinpoint system trouble in less than 30 minutes. C. The Contractor shall install all system components including VA furnished equipment, and appurtenances in accordance with the manufacturer's instructions and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable system. D. The IDS will be designed, engineered, installed, and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the system is a stand alone or designed as a computer network. E. The IDS shall be able to be integrated with other security subsystems. Integration with these security subsystems shall be achieved by computer programming and the direct hardwiring of the systems. Determination for methodology shall be outlined when the system(s) is/are being designed and engineered. For installation purposes, the IDS shall utilize an output module for integration with other security subsystems. The Contractor will ensure all connections are per the OEM and that any and all software upgrades required to integrate the systems are installed prior to system start-up. F. For programming purposes, the Contractor shall refer to the manufacturer’s requirements and Contracting Officer instructions for correct system operations. This includes ensuring computers being utilized for system integration meet or exceeds the minimum system requirements outlined in the IDS software packages. G. Lightening and power surges to the central alarm reporting and display unit shall be protected at both ends against excessive voltages. This requirement shall apply for circuits that are routed both in underground conduits and overhead runs. H. At a minimum, the Contractor shall install primary detection devices, such as three electrode gastype surge arresters, and secondary protectors to reduce dangerous voltages to levels that will cause no damage. Fuses shall not be permitted as protection devices. I. The Contractor shall provide fail-safe gas tube type surge arresters on exposed IDS data circuits. In addition, transient protection shall protect against spikes up to 1000 volts peak voltage with a one-microsecond rise time and 100-microsecond decay time, without causing false alarms. The E611-23 11-09 protective device shall be automatic and self-restoring. Also, circuits shall be designed or selected assuming a maximum of 25 ohms to ground. J. Product Delivery, Storage and Handling: 1. Delivery: Deliver materials to the job site in OEM's original unopened containers, clearly labeled with the OEM's name, equipment model and serial identification numbers, and UL logo. The Contracting Officer may inventory the IDS equipment at the time of delivery and reject items that do not conform to this requirement. 2. Storage and Handling: Store and protect equipment in a manner that will preclude damage as directed by the Contracting Officer. K. Cleaning and Adjustments: 1. Cleaning: Subsequent to installation, clean each system component of dust, dirt, grease, or oil incurred during installation in accordance to manufacture instructions. 2. Prepare for system activation by following manufacturer’s recommended procedures for adjustment, alignment, or synchronization. Prepare each component in accordance with appropriate provisions of the component’s installation, operations, and maintenance instructions. L. Tamper Switches 1. Install tamper switches to initiate an alarm signal when a panel, box, or component housing door or cover is moved as little as 6.35 mm 1/4 inch from the normally closed position unless otherwise specified. 2. Locate tamper switches within enclosures, cabinets, housings, boxes, raceways, and fittings to prevent direct line of sight to any internal components and to prevent tampering with switch or circuitry. 3. Conceal tamper switch mounting hardware so that the location of the switch within the enclosure cannot be determined from the exterior. M. Unique IDS Installation Components: 1. BMS Surface Mounted: a. Surface mounted BMS housing for the switch element shall have the capability to receive threaded conduit. Housing covers for surface mounted BMS, if made of cast aluminum, shall be secured by stainless steel screws. Magnet housing cover shall not be readily removable and BMS housings shall be protected from unauthorized access by a cover operated, corrosion-resistant tamper device. b. Conductors running from a door to alarm circuits shall be contained within a flexible armored cord constructed from corrosion-resistant metal. Each end of the armored cord shall terminate in a junction box or other enclosure. Armored cord ends shall be mechanically secured to the junction boxes by clamps or bushings. Conductors within the armored cord shall be provided with lug terminals at each end. Conductors and the armored cord shall experience no mechanical strain as the door is removed from fully open to closed position. Switch circuits shall initiate an alarm if a short circuit is applied to the door cord. c. For exterior application on double gates, both BMS elements must be mounted on the gate. Flexible armored cord constructed from corrosion-resistant metal shall be used to provide electrical connection. 2. BMS Recessed Mounted: a. Ball bearing door trips shall be mounted within vault door headers such that when the locking mechanism is secured, the door bolt engages an actuator, mechanically closing the switch. b. Door bolt locking mechanisms shall be fully engaged before the ball bearing door trip is activated. Also, circuit jumpers from the door shall be provided. 3. Vibration Sensors: a. Mount vibration sensors directly contacting the surface to be protected. b. Provide at least one (1) sensor on each monolithic slab or wall section, even though spacing closer than that required for midrange sensitivity may result. c. House sensors in protective mountings and fasten to surface with concealed mounting screws or an epoxy. E611-24 11-09 4. 5. 6. 7. d. Adjust discriminator on the job to precise needs of application. Connect sensors to an electronic control unit by means of wiring or fiber optics cable run in rigid steel conduit or electrical metallic tubing (EMT). Ultrasonic Sensors: a. Installation shall ensure that transceiver zones slightly overlap. b. Care shall be taken to ensure adequate sensitivity in area abundant in acousticabsorbing materials such as carpets and drapes. c. When the protected zone is broken up by furniture or large objects, it shall not be possible to traverse the zone undetected by moving the blind zones created by the objects. Passive Infrared Detectors: (PIR) a. The protective beam shall be focused in a straight line. b. Installed beam distance from transmitter to receiver shall not exceed 80% of the manufacturer's maximum recommended rating. c. Mirrors may be used to extend the beam or to establish a network of beams. Each mirror used shall not lower the rated maximum system range by more than 50%. d. Mirrors and photoelectric sources used in outdoor applications shall have self-heating capability to eliminate condensation and shall be housed in weatherproof enclosures. Taunt-Wire: a. Housing for switch assembly shall be covered by a neoprene cap to retain the center bolt (lever arm), which functions as a lever to translate movement of the attached horizontal wire into contact closure. When the neoprene cap is firmly seated on the cup-shaped polycarbonate housing, it shall function as the fulcrum for the lever (bolt). b. Upper exposed end of the lever shall be threaded to accommodate clamping to the horizontal wire. The lower end of the lever, which is fashioned to serve as the movable electrical contact, shall be held suspended in a small cup-shaped contact that floats in a plastic putty material. c. Plastic putty used shall retain a degree of elasticity under varying temperature conditions and provide the sensor switch with a self-adjusting property. This provides the switch with a built-in compensating mechanism that ignores small, very slow changes in lever alignment (i.e. which may result from environmental changes such as extreme temperature variations and ground seepage due to weather conditions) and to react to fast changes only, as caused by manual deflection or cutting of the wires. d. Contractor shall provide metal slider strips having slots through which the barbed wires pass. Wires shall be prevented from leaving the slots by rivets. A slider strip shall be used to translate normal forces to the barbed wire and to the horizontal displacement of the sensor. e. Install one (1) slider strip pair, upper and lower, on every fence post except where sensor posts or anchor strips are installed. f. Separation between slider elements along the fence shall be 10 feet (3000 mm). g. Attach wires of sensor to existing, specially installed fence posts, called anchor posts, located equidistant on both sides of sensor posts and at ends of sensor zone run. h. Anchor strip shall be a strip of steel plate on which fastening plates are installed. Weld or otherwise attach the strip to anchor post and ends of tensed barbed wires wrapped around the fastening plates. Attempts to climb on fastening plates or on the attached barbed wires shall cause plates to break off, creating an alarm and making it impossible to defeat the system by climbing at the anchor post. i. The use of barbed wire as part of the IDS system shall be suitable for installation under a preload tension of approximately 392 N 88 pounds and be flexible enough for convenient manipulation during tensioning. Double-strand 15 1/2-gage barbed wire shall be the minimum acceptable. Electromechanical Fence Sensors: a. The fence length shall be divided into 300 ft. (100 m) or zones. b. Sensors shall consist of individual electromechanical sensing units mounted every threethousand and 10 ft. (3045 mm) on the fence fabric or posts and wired in series to a sensor zone control unit and associated power supply. E611-25 11-09 8. Electrostatic Field Sensors: a. Sensors shall be capable of following irregular contours and barrier bends without degrading sensitivity below the specified detection level. B In no case shall a single sensor zone exceed 300 ft. (100 m) or be long enough to significantly degrade sensitivity. c. Adjacent zones shall provide continuous coverage to avoid a dead zone. Adjacent zones shall be designed to prevent crosstalk interference. d. Exterior components shall be housed in rugged corrosion-resistant enclosures, protected from environmental degradation and include tamper switches. e. Interfacing between exterior units shall be carried in underground cables. f. Exterior support hardware shall be stainless or galvanized to avoid tension degradation. g. Sensor and field wires shall be stainless steel. Wire spacing for various configurations shall be maintained constant throughout each zone and shall be uniform with respect to the ground and follow manufacturer's specifications. h. Signal processing equipment shall be separately mounted such that no desensitized zones are created within the zone of detection. 9. Microwave: Do not install microwave sensors where fluorescent lights may pose a problem due to radiated ionization from lights. 3.02 TESTS AND TRAINING A. All testing and training shall be compliant with the VA General Requirements. ---END--- E611-26 Section E620 PACKAGED ENGINE GENERATOR SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. 1.02 1.03 1.04 This section specifies the furnishing and installation of generator Nablus Rehabilitation Center. for REFERENCE STANDARDS A. ANSI/NEMA MG 1 - Motors and Generators. B. NFPA 70 - National Electrical Code. C. NFPA 99 - Health Care Facilities. SUBMITTALS A. Product Data: Submit brochures on engine, radiator, sound enclosure, muffler, battery, battery charger, control panel, and any accessory equipment showing ratings, construction features, noise level in dba with engine room and performance characteristics. Indicate fuel consumption at full load. B. Dimensional Drawings: Submit dimensional drawings of packaged unit and any separately mounted accessory equipment such as batteries and charger. Include weight of the packaged unit. C. Electrical Diagrams: Submit schematic and wiring diagrams of the electrical system showing all factory wiring and clearly indicating all wiring and connections to be made in the field. Include internal wiring diagrams of any packaged controllers. Indicate wattage and voltage of any electrical strip heaters. Also submit fully detailed interconnection drawings indicating each individual connection to any remote equipment, including a separate connection drawing to show point-to-point electrical wiring connections. D. Mechanical and Piping Diagrams. Submit detailed drawings showing all piping connections to be made in the field. Indicate sizes and point-to-point piping connections between unit and remote equipment (i.e. daily service and storage fuel tanks). E. Construction details of bulk fuel tanks and daily service tanks. SUBMITTALS AFTER MANUFACTURE A. Factory and Field Tests: Submit two copies of each factory and field test report on the actual packaged electric generating plant provided, indicating results for all tests described herein. B. Operation and Maintenance Manuals: Two weeks prior to final inspection, deliver two sets of the manufacturer's operation and maintenance manuals pertaining directly to the unit provided. Bind each set in a substantial binder, with each item properly indexed. Include the following information: 1. Project record drawings clearly indicating operating features and including asbuilt shop drawings, outline drawings, and schematic and wiring diagrams. E620 - 1 2. Instructions for erection, alignment including tolerances, and preparation for use. 3. Complete description of safety equipment, safety procedures and safety precautions. 4. Starting, normal running, emergency, and shutdown procedures. 5. Normal maintenance, inspection and lubrication procedures. 6. Recommended spare parts list. 1.05 WARRANTY A. Provide manufacturer's 2-years warranty for complete generator set assembly. PART 2 - PRODUCTS U 2.01 MANUFACTURER A. Acceptable manufacturers are Caterpillar, FG-Wilson, and Cummins, (Onan) and must have a factory-approved service organization. B. Local Representative: Provide evidence that proposed equipment manufacturer has a locally established and authorized organization which cab be called upon for professional advice and maintenance as may be required, and which can immediately supply spare parts to support day to day and emergency maintenance requirements. Failure to satisfy will disqualify a manufacturer. 2.02 DESCRIPTION A. Provide a complete, packaged, required diesel generator set. Make the packaged system of new, unused equipment of the manufacturer's latest design. Include all necessary instruments, devices, switches, and other appurtenances for proper operation of the unit. Supply steel safety guards around all external rotating parts. Provide a unit on which adjustments, repairs and normal maintenance are possible without the use of special tools. Provide an overall, sound attenuating housing as further described in this section. The supplier will be responsible for the proper performance of the complete unit and support systems. Transition time from the instant of failure of the normal power source to the generator source shall not exceed 10 seconds as required by NEC paragraph 700-6(b)(1). 2.03 ENGINE A. Type: Provide a stationary, liquid-cooled, full diesel, compression ignition engine, either naturally aspirated or turbocharged. Supply a unit suitable for operation on No. 2 diesel fuel oil. B. Rating: Provide an engine with brake horsepower not less than 10 percent greater than required by the full load rating of the generator, including losses, and with all accessories attached. E620 - 2 1. Speed. Make engine speed suitable for direct connection to the generator without exceeding engine manufacturer's published curves. Speed must not exceed 10 rpm. Provide governor of the full hydraulic type, Woodward EGP3 with a 2301A speed controller or an approved substitution, to maintain frequency stability of any constant load, including no load, within plus or minus 1/4 percent, and to maintain frequency regulation between no load steadystate and full load steady-state within 3 percent. 2. Accessories. Provide all accessories, devices and appurtenances necessary for proper operation, including but not limited to the following: a. Lubrication System. 1. Positive displacement mechanical lube oil pump. 2. Full flow replaceable element oil filter. b. Air System. Replaceable dry element air intake filter. c. Starting System. A. Heavy-duty, battery-driven electric starter motor. B. Fully charged, lead-calcium, impact-resistant, plastic-cased, storage battery or batteries mounted on the unit or in a separate corrosionproof rack near the unit. Make battery capacity sufficient for four cranking cycles at firing speed of 30 seconds duration each with 15second rest periods. Provide all battery cables, connections, electrolyte, water and a hydrometer. C. Static, solid-state type battery charger unit which automatically controls the charge rate. Include a charging rate ammeter, a voltmeter, and a manual reset, thermal overload circuit breaker to protect the rectifier assembly and transformer. Select a charger suitable for operation at 230 volts, single phase, 50 hertz. Make full charging time be 24 hours maximum. Mount charger on unit, using adequate vibration devices. D. Engine-driven alternator with full-wave rectifier and transistorized voltage regulator for charging battery when engine is running. 3. Coolant System. Closed, liquid coolant system complete with radiator, fan, coolant manifold, coolant expansion chamber (overflow tank), temperature control valve, and engine-driven coolant circulating pump. 4. Exhaust System. High degree, critical-rated muffler with maximum silencing capacity mounted horizontally on top of unit. Include a 50 cm length of flexible stainless steel exhaust tubing for mounting on outlet side of muffler. Provide exhaust condensation trap and a rain cap on exhaust end of tubing. The generator engine exhaust, with the muffler in place, shall have the following maximum permissible sound pressure levels: Octave Band Center Frequency, Hz 50 63 125 250 500 1000 2000 4000 Max. Sound Pressure 71 71 62 88 74 74 72 70 E620 - 3 -12 Level, dB re 10 5. 2.04 watts Fuel System. A. Engine-driven, self-priming fuel injection pump suitable for injecting fuel from the day tank to the engine. B. Day tank with float switch mounted in skid base of unit and having a minimum capacity for operating unit at full load for 1-4 hours. C. Full flow replaceable element fuel filter. D. Flexible fuel connection lines between day tank and engine. E. Check valve in fuel line at day tank to prevent fuel line from emptying back into tank. F. Tank shall be tank-in-tank construction. Interstitial space shall have a fuel sensor to detect a leak in the inner tank. The alarm shall be on the remote alarm panel. G. Field Connections. Flanges for all field connection shall be flush with the surface of the acoustical enclosure. No field connections are to be made inside the enclosure. All mechanical flex connectors between the enclosure and field piping are to be provided by the manufacturer. GENERATOR A. Furnish a direct-coupled, synchronous, brushless-type generator, revolving field P.M.G., exciter, 2/3 pitch built-in static rectifier and automatic voltage regulator. B. Rating. A. Voltage. 400/230, three phases, four wires, grounded neutral. B. Frequency. 50 hertz. C. Kilowatts. 48Kw. D. Power Factor. 0.8 lagging E. Duty. Standby duty, used with large non-linear loads. F. Overload. Generator shall be sized to accommodate a 110 percent load for 8 hours. 3. Insulation System. Class F. 4. Temperature Rise. Class B (80B C rise over a 40B C ambient). 5. Instantaneous Voltage Dip. Less than 15 percent when a full load is applied. Less than 15 percent when a full load is removed. 6. Voltage Regulator. Voltage regulator: solid state, volts/Hz type, utilizing silicon semi-conductor devices in control and power stages, with built-in electro-magnetic interference suppression and designed for single or E620 - 4 parallel operation. Manual adjustment to +/-5% of regulated voltage level is to be possible by a potentiometer at control panel. All components are to be sealed, moisture and heat resistant, with a suitable environmentally protected enclosure. Voltage regulator is to automatically reduce voltage is load exceeds capacity of generator an is to sustain a 3-phase short circuit current at the generator terminals for the period for which the shortcircuit protection operates and at least for 3 seconds. Voltage regulator power is to be supported by generator voltage and current to maintain excitation field power. 7. Enclosure. Drip-proof. 8. Stator. Shall be 2/3 pitch. Windings must be true form-wound coils incorporating rectangle wire, V.P.I.. 9. Coupling. From engine, drive rotor through a semi-flexible coupling to ensure permanent alignment. 10. Space Heaters. Provide thermostatically controlled, low surface temperature, 240-volt heaters to prevent condensation. Size heaters so that kW rating is not less than twice the value given in the Appendix to IEEE Standard 43, paragraph A1.3. 11. Provide under-frequency protection for the generator. 12. Provide an oversized generator termination cabinet. 2.05 CONTROL PANEL Mount control panel on unit and include, but do not limit to, the following instruments and protective devices. 1. Digital multimeter. 2. Automatic solid-state voltage regulator. 3. Frequency meter. 4. Non-resettable elapsed time meter. 5. Coolant temperature gauge. 6. Battery charge-rate ammeter or voltmeter. 7. Oil pressure gauge. 8. Main circuit breaker, 100 percent rated, with trip set as recommended by generator manufacturer, with ground fault indication. 9. Combination alarm-shutdown system with manual reset and indicating lights for high engine temperature, low engine temperature, low oil pressure, engine overspeed and engine failed to start. Include an additional set of contacts for remote alarms. 10. HAND-OFF-AUTOMATIC selector switch for control of engine. 11. Battery-operated panel lights. E620 - 5 12. Vibration isolators for control panel. 2.06 ENGINE START-STOP CONTROLS Provide controls in the control panel for starting and stopping the engine, including the following: 1. Three-Position Selector Switch. Mount on front of the control panel with the following positions labeled. A. HAND: To permit starting the engine from the panel for test purposes, without load transfer. B. OFF: To stop engine and disconnect control for prevention of start during maintenance and to reset automatic controls. Provide extra contact for remote alarm. C. AUTOMATIC: To set up circuits for automatic start and stop on demand of remote mounted transfer switch or exerciser. 2. Cool-down Period. An adjustable from 5 to 30 minute time delay for unloaded running of the engine generator after retransfer of the load to the norm source. 2.07 BASE A. Mount the assembled packaged unit on a skid base of welded structural steel, box-type construction. Use vibration isolators of either steel spring or neoprene construction. Prime all exposed metal parts with a rust inhibitor and finish in durable machinery enamel. Vibration isolation shall be provided and shall be sized for 10 cm of static deflection maximum acceptance vibration transmission to building throughout the operating vibration frequency range is 0.04 mm amplitude. 2.08 HOUSING A. Construction. Provide a housing with removable side panels and a hinged, padlockable meter panel door. B. Painting. Prime all exposed metal parts with a suitable rust inhibitor applied to the clean bare metal. C. Acoustical Treatment. Cover the interior of all housing sheet metal with a 1/32-inch layer of "Shield" acoustical material as manufactured by Cominco, Ltd., Oakville, Ontario, Canada, or approved substitution. 2.09 SOUND ATTENUATION HOUSING A. Construction. Provide an overall housing with removable side panels and a hinged, padlockable meter panel door. Unitized construction between the stud and the acoustical enclosure. The maximum sound level measured one meter from the enclosure in free field conditions under full load shall not exceed 72 dBA. B. Painting. Prime all exposed metal parts with a suitable rust inhibitor applied to the clean bare metal. 1. Acoustical Treatment. Intake and exhaust silencers shall be provided at the ends of the skid. 2 Ventilation Fans. A ventilation fan or fans shall be provided in the enclosure. 3. The fans shall provide the CFM requirements for the combustion air and for E620 - 6 removing radiant heat from the generator and the engine and maintain a 30EF temperature rise in the enclosure. In addition to the static pressure requirements for the enclosure, the fans shall also be able to overcome an additional 10mm of water in static pressure. All motor starters and associated control and wiring shall be included. Power for the fans shall be derived from the generator. The ventilation flow shall be from the generator end to the engine end. An acoustic treated duct shall be provided between the exhaust silencer and the louver in the wall. 2.10 FACTORY TESTS A. Before delivery to the job site, have the engine generating plant with enclosure and radiator satisfactorily tested as a unit as described in the following paragraphs and in accordance with the manufacturer's design parameters. The test procedure shall simulate the head requirements for the cooling water that are required to be met in the field conditions. B. Shutdown Tests. Bring the engine generator to stable operation and then create the following conditions in turn to cause alarm and shutdown. 1. High engine temperature. 2. Low engine temperature. 3. Low oil pressure. 4. Engine overspeed. C. Voltage and Frequency Stability Tests. Have the engine generator carry rated kW load at 0.8 power factor for 1 hour. During this test, frequency and voltage must not vary more than parameters stated in this section. D. Full Load Tests. Start the generator under no load and then have full rated kW at 0.8 power factor applied in a single increment within 10 seconds of start-up. Remove the load from the unit 5 minutes after start-up and then reapply full rated kW at 0.8 power factor 30 seconds later. Run the unit an additional 5 minutes under load before shutdown. During this test, the instantaneous voltage dip must not exceed that stated in paragraph 2.4E of this section, and frequency and voltage regulation must not vary more than parameters stated in this section with strip chart recorders. Unit shall be tested for 6 hours at 100 percent rated load and then at 110 percent of rated load for 2 hours with enclosure installed and using the radiator to be furnished with the unit. PART3 - EXECUTION 3.01 INSTALLATION A. Follow manufacturer's installation procedures. Have installation supervised and approved by a qualified representative of the unit manufacturer. 3.02 ENGINE EXHAUST A. Install an 50 cm length of exhaust tubing between engine exhaust outlet and muffler inlet. Turn muffler tailpipe up and terminate with rain cap. E620 - 7 3.02 FAN DISCHARGE A. 3.05 Provide an acoustically lined elbow to direct radiator fan discharge up. Brace elbow structurally with steel that has been hot-dip galvanized after all cuts and holes have been made. Support system must be approved for strength, finish and appearance. PIPING SYSTEM A. Using carbon dioxide or nitrogen from pressurized cylinder, test each system to 1.5 times normal operating pressure. Do not subject equipment, apparatus or devices to pressure exceeding prescribed test pressure obtained from nameplate data or from manufacturer=s published data. Apply tests before connecting piping to equipment. Remove or disconnect and blank off relief valves, instruments and devices that might be damaged by test pressure. Maintain test pressure on system for 24 hours during which time there is to be no noticeable drop in pressure. Check for leaks using soap solution. Isolate source of pressure during testing. 3.06 START UP AND TESTING A. Provide the services of a factory-authorized, factory-trained representative of the diesel engine-generator set manufacturer to inspect field-assembled components, and equipment installation and supervise the field tests B. When the complete auxiliary electrical power system has been installed and prior to the final inspection, tests all components of the system in the presence of the engineer for proper operation of the individual components and the complete system and to eliminate electrical and mechanical defects. C. Furnish fuel oil, lubricating oil, anti-freeze liquid, water treatment and rust inhibitor and load bank for testing of the diesel engine-generator set. D. Field Tests for the Diesel Engine-Generator Set: 1. Test the engine generator set for six hours of continuous operation as follows: a. First four hours while the set is delivering 100 percent of its specified KW rating. b. Last two hours while the set is delivering 110 percent of its specified KW rating. c. If during the 6-hour continuous test a failure occurs, either the diesel engine shuts down or the full KW rating of the load bank is not achieved, the test is null and void. The test(s) shall be repeated until the satisfactory results are attained. 2. Record the following test data at 30-minute intervals: a. Time of day, also reading of running time indicator. b. KW. c. Voltage on each phase. d. Amperes on each phase. e. Engine RPM. f. Frequency. g. Engine water temperature. h. Fuel pressure i. Oil pressure. j. Outdoor temperature k. Average ambient temperature in the vicinity of the diesel engine. l. Average ambient temperature in the vicinity of the starting batteries. 3. Demonstrate that the generator set will attain proper voltage, frequency and will accept 100 percent block load within 10 seconds from a cold start after the closing of a single contact. E620 - 8 E. F. G. H. I. 3.07 4. Furnish a resistance type load for the testing of the generator: a. When approved in writing by the engineer prior to the testing, the Contractor may use connected loads in the building (resistant plus other types) as part of the test load provided the Contractor assumes complete responsibility for the use of the connected loads, including personnel injuries and property damage. b. Test loads shall always include adequate resistance to assure stability of the loads and equipment during all of the testing operations. The test load KW rating: 1) Shall not be less than 110 percent of the specified KW rating of the largest generator set. 2) Shall not be less than 35 percent of the sum of the specified KW ratings of the all generator sets in a paralleling system. Battery and Starting System Test: 1. Demonstrate that the batteries and cranking motor are capable of 5 starting attempts of 10 second cranking each at 10 second intervals with the battery charger turned off. Test local panels: Simulate engine failures while checking for proper operation of each indicating lamp, alarm device and reset button. At the completion of the field tests, fill the underground storage tank with fuel of grade and quality as recommended by the manufacturer of the engine. When any defects are detected during the tests, correct all the deficiencies and repeat all or part of the 6-hour continuous test as requested by Engineer, at no additional cost to Arab Bank. Provide test and inspection results in writing to the Resident Engineer. TRAINING A. Formal training for the operation and maintenance of all packaged electric generating plant equipment and each system specified herein shall be given to the Owners maintenance staff by factory trained and certified personnel at the project site. The training shall consist of a minimum of three 3-hour training sessions. A minimum of 3 bound copies of training material and operating manuals shall be provided at the time of training, with four additional copies submitted at the time of Substantial Completion. - - - END - - - E620 - 9 SECTION E670 LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 SCOPE A. Provide and install a complete lightning protection system as indicated on the drawings and as specified. B. The system shall comprise of copper tape meshes, down conductors, test clamps, and earth termination. 1.02 REFERENCE STANDARDS A. IEC-1024 B. BS EN 62305:2006 1.03 SUBMITTALS A. Refer to section E010 – Electrical General Provision. B. Manufacturer’s product data, technical literature and wiring diagrams. C. Shop drawings, including cut sheets of each component and each material utilized in the installation for the system. PART 2 - PRODUCTS 2.01 AIR TERMINATION AND ROOF MESHES A. Conductors of roof tapes networks shall be of 20 x 3 mm copper unless otherwise specified or required by code and fastened by means of single fixing polypropylene clamps. 2.02 DOWN CONDUCTORS A. A 8mm Dedicated continuous reinforced bar in structural columns shall be used as a down conductor, where such arrangement cannot be satisfied down conductors shall be 50mm2 stranded bare copper conductors installed in PVC conduits with suitable size concealed in walls. B. Down conductor systems should take the most direct route from the air termination network to the earth termination network. Ideally they should be symmetrically installed around the outside walls of the structure starting from the corners. Routing to avoid side flashing should always be given particular attention. C. Down conductors should be positioned no more than 20 m apart around the perimeter at roof or ground level, whichever is the greater. If the structure is over 20 m height, then the spacing is reduced to every 10 m or part thereof. D. The length of the conductor forming the loop should not exceed eight times the width of the open side of the loop. 2.03 GROUNDING A. Types of earth termination networks. 1- Deep Driven Earth Electrode. A soil resistivity survey indicating lower resistivity at greater depths will make the deep driven 19 mm2 earth electrode a logical choice. 2- Parallel Earth Rod Electrodes. Where ground conditions make deep driving of earth rods impossible, a matrix arrangement of rods coupled to one another by conductors can be used. If possible, the earth rods must be spaced at least equal to their driven depth. 3- Radial Strip Electrodes. Ground that has one meter depth of soil before encountering bedrock will best be suited to a buried radial electrode. Install the system below the area that is subject to seasonal weather changes. E670-1 B. Testing Grounding System. 1- An earth electrode should be connected to each down conductor with a test link incorporated into every down conductor path. With the test link removed and without any bonding to other services, etc. the earth resistance of each individual earth electrode should be measured. The resistance, in ohms, should not exceed ten times the number of down conductors on the structure. For example, if there are fifteen down conductors equally spaced around building, then the resistance for each electrode with the test link removed should not exceed 10x15 = 150 ohms. 2- With the test links replaced the resistance to earth of the complete lightning protection system is measured at any point on the system. The reading from this test should not exceed ten ohms. This is still without any bonding to other services. 2.04 BONDING A. All exposed metal work on or around the structure must be bonded to the lightning protection system if side-flashing is to be avoided. Any metal work connected to the lightning network shall not be connected to the main earth busbar. Aluminum or copper metal lightning system may be used but not both into one system. PART 3 - EXECUTION 3.01 INSTALLATION A. The routing of the down conductors must be as straight as possible, avoiding all sharp bends or potential backup. The curve radius of a section of the lead running around an obstacle shall not be less than 200 mm. B. The external metal mass located less than one meter from the down conductor must be electrically connected to these leads (connection by riveting at 4 places) with conductors of the same cross section as the strip itself. C. The Mechanical equipment which is located on the roof of a construction shall be connected to the copper meshes on the same construction. D. The lightning down conductors must include a control junction box or a cut-off bar, in order to allow measurement of the grounding system resistance and of the down conductor electrical continuity. The control junction will be located 2 meters above ground level in order to be accessible only when measurements are made. The control junction box shall not change or interfere with the architectural aspect. E. The liaison between the down conductor and the grounding system and the control junction must be made by riveting at 4 places. After any check of the installation it is necessary to verify that the connections are correct. F. The strip will be protected between the control junction and the ground by a PVC pipe inside the wall, this PVC pipe is two meter high from above finished floor. G. When installing the grounding system, care should be exercised to make sure that it directed towards the outside of the building and as distant as possible from the building. The earthing system should be at least 3 meters from any buried electrical conduit. H. A separate grounding system shall be provided to the fuel tank and shall comply with the local codes and standards and as per drawings. 3.02 TESTING AND COMMISIONING A. All tests required by local codes and regulations shall be carried out by the Contractor. B. Tests on ground continuity as mentioned in the above rules and regulations shall be carried out by the contractor on completed installation. E670-2 C. The expenses for the above tests shall be carried out by the Contractor. D. All tests must be carried out in the presence of the Engineer or the person appointed for this purpose, but the Contractor alone will be responsible to the authorities as to the installation’s compliance with rules and regulations. E. The Contractor shall provide precise instruments and all labor for the testing. Test results shall be submitted to the Engineer within 14 days of the test, and the Contractor shall issue the Certificate upon completion, as required under the above mentioned regulations. F. Any defects, faults or omissions of the installations made apparent by such test, shall be corrected by the Contractor at his own expense. G. Final tests to be carried out in the presence of the Engineer and to start upon the completion of the work and the contractor must submit to the Engineer a detailed test procedure and time schedule for the test. ---END--- E670-3 SECTION E710 FIRE ALARM SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and electrical Specification Sections, apply to this Section. 1.02 SUMMARY A. This section specifies the furnishing, installation, connection and testing of a complete, operative and coordinated 24 Volt, networked fire alarm system. The system shall include but not be limited to, alarm initiating devices, alarm notification appliances, Network Fire Alarm Control Panels (FACP), auxiliary control devices, annunciators, and wiring as shown on the drawings and specified herein. 1.03 REFRENCE STANDARDS A. The fire alarm system shall comply with requirements of NFPA 72, the system shall be electrically supervised and monitor the integrity of all conductors. B. The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the requirements of BS EN9001: ANSI/ASQC Q9001-1994. C. The FACP and peripheral devices shall be manufactured 100% by a single manufacturer (or division thereof). D. The system and its components shall be Underwriters Laboratories, Inc. listed under the appropriate UL testing standard as listed herein for fire alarm applications and shall be in compliance with the UL listing. 1.04 SCOPE A. A network intelligent reporting, microprocessor controlled fire detection and emergency voice alarm communication network shall be installed in accordance with the specifications and drawings. B. Basic Performance: 1. The connection between network control panels shall be Arcnet-based or other recognized network communication scheme and shall be wired in a Class A, Style 7 fashion. 2. Alarm and trouble signals from the FACP, shall be digitally encoded by a listed electronic devices onto a NFPA Style 6 looped multiplex communication system. 3. Alarm, trouble and supervisory signals from all intelligent reporting devices shall be encoded onto NFPA Style 4 (Class B) Signaling Line Circuits (SLC). 4. Initiation Device Circuits (IDC) shall be wired Class A (NFPA Style D). 5. Notification Appliance Circuits (NAC) shall be wired Class A (NFPA Style Z). 6. Power for initiating devices and notification appliances must be from the main fire alarm control panel, the transponder to which they are connected or to a Field Charging Power Supply (FCPS). 7. A single ground or open on any system signaling line circuit, initiating device circuit, or notification appliance circuit shall not cause system malfunction, loss of operating power or the ability to report an alarm. 8. Alarm signals arriving at the main FACP shall not be lost following a power failure (or outage) until the alarm signal is processed and recorded. 9. Digitized electronic signals shall employ check digits or multiple polling. 10. Transponder devices are to consist of low current, solid-state integrated circuits, and shall be powered locally from a primary power and standby power source. 11. Two-way telephone communication circuits shall be arranged to allow communication between the fire alarm control panel at first basement floor and up to ten (10) remote telephone locations simultaneously. C. Basic System Operation 1. When a fire alarm condition is detected and reported by one of the system initiating devices or appliances, the following functions shall immediately occur: E710-1 a. The FACP alarm LED on the FACP shall flash. b. A local piezo-electric signal in the FACP shall sound. c. The 80-character LCD display on the local FACP node and on the network displays shall indicate all information associated with the fire alarm condition, including the type of alarm point, and its location within the protected premises. This information shall also be displayed on the network reporting terminal. d. Printing and history storage equipment shall log the information associated with the fire alarm control panel condition, along with the time and date of occurrence. e. All system output programs assigned via control-by-event interlock programming to be activated by the particular point in alarm shall be executed, and the associated system outputs (alarm notification appliances and/or relays) shall be activated on either local outputs or points located on other network nodes. 2. When a supervisory condition is detected and reported by one of the system initiating devices or appliances, the following functions shall immediately occur: a. The FACP supervisory LED on the FACP shall flash. b. A local piezo-electric signal in the FACP control panel shall sound. c. The 80-character LCD display on the local FACP node and on the network displays shall indicate all information associated with the condition, including the type of point, and its location within the protected premises. This information shall also be displayed on the network reporting terminal. d. Printing and history storage equipment shall log the information associated with the fire alarm control panel condition, along with the time and date of occurrence. e. All system output programs assigned via control-by-event interlock programming to be activated by the particular point shall be executed, and the associated system outputs (alarm notification appliances and/or relays) shall be activated on either local outputs or points located on other network nodes. 3. When a trouble condition is detected and reported by one of the system initiating devices or appliances, the following functions shall immediately occur: a. The FACP trouble LED on the FACP shall flash. b. A local piezo-electric signal in the FACP control panel shall sound. c. The 80-character LCD display on the local FACP node and on the network displays shall indicate all information associated with the condition, including the type of point, and its location within the protected premises. This information shall also be displayed on the network reporting terminal. d. Printing and history storage equipment shall log the information associated with the fire alarm control panel condition, along with the time and date of occurrence. e. All system output programs assigned via control-by-event interlock programming to be activated by the particular point shall be executed, and the associated system outputs (alarm notification appliances and/or relays) shall be activated on either local outputs or points located on other network nodes. 1.05 SUBMITTALS A. General: All substitute equipment proposed as equal to the equipment specified herein, shall meet or exceed the following standards. For equipment other than that specified, the contractor shall supply proof that such substitute equipment does in fact equal or exceed the features, functions, performance, and quality of the specified equipment. B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include manufacturer's name(s), model numbers, ratings, power requirements, equipment layout, device arrangement, complete wiring point-to-point diagrams, and conduit layouts. 3. Show annunciator layout and main control panel module layout, configurations and terminations. C. Manuals: 1. Submit simultaneously with the shop drawings, complete operating and maintenance manuals listing the manufacturer's name(s) including technical data sheets. E710-2 2. Wiring diagrams shall indicate internal wiring for each item of equipment and the interconnections between the items of equipment. 3. Provide a clear and concise description of operation which gives the information required to properly operate the equipment and system. D. Software Modifications 1. Provide the services of a factory trained and authorized technician to perform all system software modifications, upgrades or changes. Response time of the technician to the site shall not exceed 4 hours. 2. Provide all hardware, software, programming tools and documentation necessary to modify the fire alarm network on site. Modification includes addition and deletion of devices, circuits, zones and changes to system operation and custom label changes for devices or zones. The system structure and software shall place no limit on the type or extent of software modifications on-site. Modification of software shall not require power-down of the system or loss of system fire protection while modifications are being made. E. Certifications: Together with the shop drawing submittal, submit a certification from the equipment manufacturer indicating that the proposed supervisor of installation and the proposed performer of contract maintenance is an authorized representative of the equipment manufacturer and trained on network applications. 1.06 GUARANTY: A. All work performed and all material and equipment furnished under this contract shall be free from defects and shall remain so for a period of at least Two (2) years from the date of acceptance. The full cost of maintenance, labor and materials required to correct any defect during these Two years period shall be included in the submittal bid. 1.07 APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification. The publications are referenced in text by the basic designation only. A. The fire alarm system shall comply with requirements of NFPA 72 for protected premises signaling systems except as modified and supplemented by this specification. The system field wiring shall be supervised either electrically or by software-directed polling of field devices. B. Local and State Building Codes. C. All requirements of the Authority Having Jurisdiction (AHJ). 1.08 APPROVALS: A. The system must have proper listing and/or approval from the following nationally recognized agencies: UL Underwriters Laboratories Inc FM Factory Mutual MEA Material Equipment Acceptance (NYC) CSFM California State Fire Marshal Local Civil Defense Authorities PART 2 - PRODUCTS 2.01 EQUIPMENT AND MATERIAL, GENERAL A. All equipment and components shall be new, and the manufacturer's current model. The materials, appliances, equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a protected premises protective signaling (fire alarm) system. The authorized representative of the manufacturer of the equipment shall be responsible for the satisfactory installation of the complete system. B. All equipment and components shall be installed in strict compliance with manufacturer's recommendations. Consult the manufacturer's installation manuals for all wiring diagrams, schematics, physical equipment sizes, etc. before beginning system installation. Refer to the riser/connection diagram for all specific system installation/termination/wiring data. E710-3 C. All equipment shall be attached to walls and ceiling/floor assemblies and shall be held firmly in place. (e.g., detectors shall not be supported by suspended ceilings). Fasteners and supports shall be adequate to support the required load. 2.02 CONDUIT AND WIRE A. Conduit: 1. Conduit shall be in accordance with the National Electrical Code (NEC) and local requirements. All wiring shall be installed in conduit. Conduit fill shall not exceed 40 percent of interior cross sectional area where three or more cables are contained within a single conduit. 3. Cable must be separated from any open conductors of power, or Class 1 circuits, and shall not be placed in any conduit, junction box or raceway containing these conductors, per NEC Article 760-29. 4. Conduit shall not enter any FACP, or any other remotely mounted control panel equipment or back boxes, except where conduit entry is specified by the FACP manufacturer. 5. Conduit shall be 3/4 inch (19.1 mm) minimum. B. Wire: 1. All fire alarm system wiring must be new, unless specified herein. 2. Wiring shall be in accordance with local and national codes (e.g., NEC Article 760) and as recommended by the manufacturer of the fire alarm system. Number and size of conductors shall be as recommended by the fire alarm system manufacturer, but not less than 18 AWG (1.02 mm) for initiating device circuits and signaling line circuits, and 16 AWG (1.32 mm) for notification appliance circuits. 3. All wire and cable shall be listed and approved by a recognized testing agency for use with a protective signaling system. 4. Wire and cable not installed in conduit (if any) shall have a fire resistance rating suitable for the installation as indicated in NFPA 70 (e.g., FPLR). 5. Wiring used for the signaling line circuit (SLC) multiplex communication loop shall be twisted and shielded and installed in conduit unless specifically accepted by the fire alarm equipment manufacturer. 6. All field wiring shall be completely supervised. C. Network Media 1. General: The network shall be capable of communicating via wire. A wire network shall include a fail safe means of isolating the nodes in the unlikely event of complete power loss to a node. The fail safe design shall allow the network communications signal to bypass the failed node which allows the continuation of normal communications activity if specified wiring distances are maintained. 2. Twisted Pair (wire) Communication: The dedicated twisted pair shall utilize 12 to 24 AWG wire and support distances of up to 1,000 meter between nodes. D. Terminal Boxes, Junction Boxes and Cabinets: All boxes and cabinets shall be UL listed for their intended purpose. E. Initiating circuits shall be arranged to serve like categories (manual, smoke, water flow). Mixed category circuitry shall not be permitted except on signaling line circuits connected to intelligent reporting devices. F. The FACP(s) shall be connected to a separate dedicated branch circuit, maximum 20 amperes. This circuit shall be labeled at the main power distribution Panel as FIRE ALARM. Fire alarm control panel primary power wiring shall be 4 mm². The FACP cabinet shall be grounded securely to either a cold water pipe or grounding rod. 2.03 FIRE ALARM CONTROL PANELS: A. Each network FACP shall contain a microprocessor-based central processing unit (CPU). The FACP shall communicate with and control the following types of equipment used to make up the system: intelligent detectors, addressable modules, transponders, local and remote operator terminals, printers, annunciators, emergency voice communication systems, and other system controlled devices. Each FACP on the network shall perform the following functions: 1. Supervise and monitor all intelligent/addressable detectors and monitor modules connected to the system for normal, trouble and alarm conditions. E710-4 2. Supervise all initiating signaling and notification circuits throughout the facility by way of connection to transponders. 3. Detect the activation of any initiating device and the location of the alarm condition. Operate all notification appliances and auxiliary devices as programmed. 4. Visually and audibly annunciate any trouble, supervisory or alarm, condition on operator's terminal, panel display, and annunciators. B. General FACP Operation 1. Each FACP node shall include a full featured operator interface control and annunciation panel which shall include a backlit Liquid Crystal Display (LCD), individual, color coded system status LEDs, and an alpha-numeric keypad for field programming and control of the node. 2. All programming or editing of the existing programing in the system shall be achieved without special equipment or interrupting the alarm monitoring functions of the fire alarm control panel. 3. The system shall include emergency voice communications utilizing distributed amplification and intelligence such that loss of operation by the main FACP will not result in the loss of evacuation signal throughout the balance of the building. 4. Each FACP node shall be capable of providing the following features: Block Acknowledge for Trouble Conditions Rate Charger Control Control-By-Time (Delay, Pulse, time of day, etc.) Automatic Day/Night Sensitivity Adjust (high/low) Device Blink Control (turn of detector LED strobe) Environmental Drift Compensation (selectable ON or OFF) Smoke Detector Pre-alarm Indication at Control Panel NFPA 72 Smoke Detector Sensitivity Test System Status Reports Alarm Verification, by device, with tally Multiple Printer Interface Multiple CRT Display Interface Non-Fire Alarm Module Reporting Automatic NFPA 72 Detector Test Programmable Trouble Reminder Upload/Download System Database to PC Computer One-Man Walk Test Smoke Detector Maintenance Alert Security Monitor Points Alpha-numeric Pager Interface On-line or Off-line programming C. FACP Central Processing Unit (CPU): 1. Each FACP network node shall include a central processing unit. The CPU shall communicate with, monitor, and control all other modules within the control panel. Removal, disconnection or failure of any control panel module shall be detected and reported to the system display by the CPU. 2. Each CPU shall contain and execute all control-by-event interlock for specific local and network action to be taken if an alarm condition is detected by the system. Control-byevent programs shall be held in non-volatile programmable memory, and shall not be lost even if system primary and secondary power failure occurs. 3. The central processing unit shall also provide a real-time clock for time annotation of all system displays. The time-of-day and date shall not be lost if system primary and secondary power supplies fail. D. Loop Interface Board (LIB): 1. Loop interface boards shall be provided to monitor and control each of the Signaling Line Circuit (SLC) loops in the network node. The loop interface board shall contain its own microprocessor and shall be capable of operating in local mode in the case of a failure in the main CPU of the control panel. In local mode, the loop interface board shall detect alarms and activate output devices on its own SLC loop. E710-5 E. F. G. L. M. 2. The LIB shall not require any jumper cuts or address switch settings to initialize SLC Loop operations. 3. The loop interface board shall provide power to, and communicate with, all of the intelligent detectors and addressable modules connected to its SLC Loop over a single pair of wires. This SLC Loop shall be capable of operation as NFPA Style 4, Style 6, or Style 7. 4. The LIB shall be able to drive two Style 4 SLC loops, each up to 3000 meters in length, for an effective loop span of 6000 meters. 5. The loop interface board shall receive analog information from all detectors and shall process this information to determine whether normal, alarm, or trouble conditions exist for that particular detector. The loop interface board software shall include software to automatically adjust and compensate for dust accumulation to maintain detector performance as it is affected by environmental factors. The analog information may also be used for automatic detector testing and for the automatic determination of detector maintenance requirements. 6. The LIB shall communicate with each intelligent addressable detector and addressable module on its SLC loop and verify proper device function and status. Communication with up to 198 intelligent devices shall be performed every 6 seconds or less. Enclosures: 1. Control panels shall be housed in UL-listed cabinets suitable for surface or semi-flush mounting. Cabinets shall be corrosion protected, given a rust-resistant prime coat, and the manufacturer's standard finish. 2. The back box and door shall be constructed of 0.060 steel with provisions for electrical conduit connections into the sides and top. 3. The door shall provide a key lock and include a transparent opening for viewing all indicators. For convenience, the door shall have the ability to be hinged on either the right or left-hand side. 4. The control unit shall be modular in structure for ease of installation, maintenance, and future expansion. The CPU and associated equipment are to be protected so that they will not be affected by voltage surges or line transients including RFI and EMI. FACP Power Supplies: 1. Main power supplies shall operate on 230 VAC, 50Hz, and shall provide all necessary power for the FACP. 2. Each main supply shall provide 3.0 amps of usable notification appliance power, using a switching 24 VDC regulator. 3. The main power supply shall be expandable for additional notification appliance power in 3.0 ampere steps. 4. Each main power supply shall provide a battery charger for 24 hours of standby using dual-rate charging techniques for fast battery recharge. It shall charge 60 Amp hour batteries within a 48-hour period. 5. The supply shall provide a very low frequency sweep earth detect circuit, capable of detecting earth faults. 6. It shall provide meters to indicate battery voltage and charging current. 7. The main power supply shall be power-limited per UL864 requirements. Field Charging Power Supply: The FCPS is a device designed for use as either a remote 24 volt power supply or used to power Notification Appliances. 1. The FCPS shall offer up to 6.0 amps (4.0 amps continuous) of regulated 24 volt power. It shall include an integral charger designed to charge 7.0 amp hour batteries and to support 60 hour standby. 2. The Field Charging Power Supply shall have two input triggers. The input trigger shall be a Notification Appliance Circuit (from the fire alarm control panel) or a relay. Four outputs (two Style Y or Z and two style Y) shall be available for connection to the Notification devices. 3. The FCPS shall include an attractive surface mount backbox. 4. The Field Charging Power Supply shall include the ability to delay the AC fail delay per NFPA requirements. 5. The FCPS include power limited circuitry, per UL standards. System Circuit Supervision: E710-6 N. O. P. Q. 1. Each FACP node shall supervise all circuits to intelligent devices, transponders, annunciators and peripheral equipment and annunciate loss of communications with these devices. The FACP CPU shall continuously scan the above devices for proper system operation and upon loss of response from a device shall sound an audible trouble, indicate which device or devices are not responding and print the information on the printer. Field Wiring Terminal Blocks For ease of service, all wiring terminal blocks shall be the plug-in type and have sufficient capacity for 18 (0.75 mm²) to 12 AWG (3.25 mm²) wire. Fixed terminal blocks are not acceptable. Emergency Two-Way Telephone Control Switches/Indicators 1. The emergency telephone circuit control panel shall include visual indication of active and trouble status for each telephone circuit in the system. 2. The telephone circuit control panel shall include switches to manually activate or deactivate each telephone circuit in the system. Operators Terminal: Provide the following functions in addition to any other functions required for the system. 1. Acknowledge (ACK/STEP) Switch: a. Activation of the control panel Acknowledge switch in response to a single new Alarm and/or trouble condition shall silence the local panel piezo electric signal and change the system alarm or trouble LED from flashing mode to steady-ON mode. If additional new alarm or trouble conditions exist or are detected and reported in the system, depression of this switch shall advance the 80-character LCD display to the next alarm or trouble condition. b. Depressing the acknowledge switch shall also silence all remote annunciator piezo sounders. 2. Signal Silence Switch: Activation of the signal silence switch shall cause all programmed alarm notification appliances and relays to return to the normal condition after an alarm activation. The selection of notification circuits and relays which are silenceable by this switch shall be fully field programmable within the confines of all applicable standards. 3. System Reset Switch: Activation of the system reset switch shall cause all local electronically-latched initiating devices, software zones, output devices and circuits, to return to their normal condition. If an alarm condition(s) still exists, or if they reoccur in the system after system reset switch activation, the system shall then resound the alarm conditions. 4. System Test Switch. Activation of the system test switch shall initiate an automatic test of all intelligent/addressable detectors in the local system. The system test shall activate the electronics in each intelligent sensor, simulating an alarm condition and causing the transmission of the alarm condition from that sensor to the fire alarm control panel. The fire alarm control panel shall interpret the data from each sensor installed in the system. A report summarizing the results of this test shall be displayed automatically on the system LCD and on any CRTs or printers in the system. 5. Lamp Test Switch: Activation of the lamp test switch shall sequentially turn on all LED indicators, system liquid crystal display and local piezo signal, and then automatically return the fire alarm control panel to the previous condition. Field Programming 1. The system shall be programmable, configurable and expandable in the field without the need for special tools or electronic equipment and shall not require field replacement of electronic integrated circuits. 2. All local FACP node programming shall be accomplished through the FACP keyboard or through the video display terminal. 3. All field defined programs shall be stored in non-volatile memory. 4. The programming function shall be enabled with a password that may be defined specifically for the system when it is installed. Two levels of password protection shall be provided in addition to a key-lock cabinet. One level is used for status level changes such as E710-7 zone disable or manual on/off commands. A second (higher-level) is used for actual change of program information. R. Specific System Operations 1. Smoke Detector Sensitivity Adjust: Means shall be provided for adjusting the sensitivity of any or all analog intelligent detectors in the FACP node from each system keypad or from the keyboard of the video terminal. Sensitivity range shall be within allowed UL limits. 2. Alarm Verification: Each of the intelligent addressable detectors in the system may be independently selected and enabled for alarm verification. Each FACP shall keep a count of the number of times each detector has entered the verification cycle. These counters may be displayed and reset by the proper operator commands. 3. System Point Operations a. All devices in the FACP node may be enabled or disabled through the local keypad or video terminal. b. Any FACP node output point may be turned on or off from the local system keypad or the video terminal. 4. Point Read: The FACP node shall be able to display the following point status diagnostic functions without the need for peripheral equipment. Each point will be annunciated for the parameters listed: a. Device Status b. Device Type c. Custom Device Label d. Software Zone Label e. Device Zone Assignments f. Detector Analog Value g. All Program Parameters 5. System Status Reports: Upon command from a password-authorized operator of the system, a status report will be generated, and printed, listing all local FACP system status. 6. System History Recording and Reporting: Each FACP node shall contain a history buffer that shall be capable of storing a minimum of 400 system events. Each local activation will be stored and time and date stamped with the actual time of the activation, until an operator requests that the contents be either displayed or printed. The contents of the history buffer may be manually reviewed, one event at a time, and the actual number of activations may also be displayed and or printed. The history buffer shall use non-volatile memory. Systems which use volatile memory for history storage are not acceptable. 7. Automatic Detector Maintenance Alert: Each FACP node shall automatically interrogate each intelligent system detector and shall analyze the detector responses over a period of time. If any intelligent detector in the system responds with a reading that is below or above normal limits, then the system will enter the trouble mode, and the particular intelligent detector will be annunciated on the system display, network display and printed on the optional system printer. This feature shall in no way inhibit the receipt of alarm conditions in the system, nor shall it require any special hardware, special tools or computer expertise to perform. 2.04 NETWORK MONITORING DEVICES A. INTELLIGENT NETWORK ANNUNCIATOR 1. An intelligent network annunciator shall be provided to display all system intelligent points. The INA shall be capable of displaying all information for all 200,000 possible points on the network. Network display devices which are only capable of displaying a subset of network points shall not be suitable substitutes. 2. The INA shall include a minimum of 80 characters, backlit by a long life solid state LCD display. The network display shall mount in any of the network node fire alarm control panels. Optionally, the network display may mount in an attractive backbox designed for this use, or may mount in an industry standard 19-inch (482.6 mm) rack. The network shall support over 103 network display annunciators (not to exceed total node capacity) and shall connect to the network over either a wire or fiber interface. E710-8 3. The intelligent network annunciator shall have a history buffer capable of storing a minimum of 400 events in non-volatile memory. 4. The INA shall include two optically isolated, 2400 baud, industry standard EIA-232 ports for UL864 listed printers and CRT's. These peripheral devices shall print or display network activity. 5. The intelligent network annunciator shall include five control switches for system wide control of signal Silence, Reset, Activate Signals (Drill), and Lamp Test (local). A means by which the controls switches are "locked out", such as a key, shall be available. 6. The INA shall include long life LEDs to display Power, Fire Alarm, Security Alarm, System Trouble, Supervisory, Signals Silenced, and CPU Failure. 7. The intelligent network annunciator shall include two software assignable passwords, up to five digits in length. 8. For time keeping purposes the INA shall include a time of day clock. 9. Each INA shall support up to 32 additional 80 character remote display annunciators for displaying network activity. These "Terminal Mode" displays will mimic the activity appearing on the corresponding INA. 2.05 SYSTEM COMPONENTS - CONVENTIONAL A. Programmable Electronic Sounders: 1. Electronic sounders shall operate on 24 VDC nominal. 2. Electronic sounders shall be field programmable without the use of special tools, to provide slow whoop, continuous, or interrupted tones with an output sound level of at least 90 dBA measured at 10 feet (3 meters) from the device. 3. Shall be flush or surface mounted as show on plans. B. Strobe lights shall meet the requirements of UL and shall meet the following criteria: 1. The maximum pulse duration shall be 2/10 of one second. 2. Strobe intensity shall meet the requirements of UL 1971. 3. The flash rate shall meet the requirements of UL 1971. C. Fire Man Telephone 1. The telephone cabinet shall be painted red and clearly labeled as cabinets shall be located where shown on drawings. 2. Handset cradle shall have a switch connection so that lifting cradle shall send a signal to the NET WORK ANNUCIATOR. 3. On activating the remote phone, the phone earpiece shall sound at the master handset is lifted. 4. The two-way emergency telephone system shall support a minimum of without degradation of the signal. 5. Provide one portable telephone handset. 2.06 SYSTEM COMPONENTS, INTELLIGENT A. Addressable Devices - General 1. Addressable devices shall use simple to install and maintain decade (numbered 0 to 9) type address switches. 2. Addressable devices which use a binary address setting method, such as a Dip switch, are not an allowable substitute. 3. Detectors shall be analog and addressable, and shall connect with two wires to the FACP signaling line circuit. 4. Addressable smoke and thermal detectors shall provide dual alarm and power/polling LEDs. Both LEDs shall flash under normal conditions, indicating that the detector is operational and in regular communication with the control panel, and both LEDs shall be placed into steady illumination by the control panel, indicating that an alarm condition has been detected. If required, the LED flash shall have the ability to be removed from the system program. An output connection shall also be provided in the base to connect an external remote alarm LED. 5. The fire alarm control panel shall permit detector sensitivity adjustment through field programming. Sensitivity shall be automatically adjusted by the panel on a time-of-day basis. 6. Using software in the FACP, detectors shall automatically compensate for dust accumulation and other slow environmental changes that may affect their performance. The detec- E710-9 B. C. D. E. F. G. tors shall be listed by UL as meeting the calibrated sensitivity test requirements of NFPA 72, Chapter 7. 7. The detectors shall be ceiling-mount and shall include a separate twist-lock base with tamper proof feature. 8. The detectors shall provide a test means whereby they will simulate an alarm condition and report that condition to the control panel. Such a test may be initiated at the detector itself (by activating a magnetic switch) or initiated remotely on command from the control panel. 9. Detectors shall also store an internal identifying type code that the control panel shall use to identify the type of device (ION, PHOTO, THERMAL). 10. Detectors will operate in an analog fashion, where the detector simply measures its designed environment variable and transmits an analog value to the FACP based on realtime measured values. The FACP software, not the detector, shall make the alarm/normal decision, thereby allowing the sensitivity of each detector to be set in the FACP program and allowing the system operator to view the current analog value of each detector. 11. Addressable devices shall provide address-setting means using decimal switches and shall also store an internal identifying code that the control panel shall use to identify the type of device. LED(s) shall be provided that shall flash under normal conditions, indicating that the device is operational and is in regular communication with the control panel. 12. A magnetic test switch shall be provided to test detectors and modules. Detectors shall report an indication of an analog value reaching 100% of the alarm threshold. Addressable Pull Box (manual station) 1. Addressable pull boxes shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. They shall use a key operated test-reset lock, and shall be designed so that after actual emergency operation, they cannot be restored to normal use except by the use of a key. 2. All operated stations shall have a positive, visual indication of operation and utilize a key type reset. 3. Manual stations shall be constructed of Lexan with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches (44 mm) or larger. Analog Photoelectric Smoke Detector 1. The detectors shall use the photoelectric (light-scattering) principal to measure smoke density and shall, on command from the control panel, send data to the panel representing the analog level of smoke density. Analog Ionization Smoke Detector 1. The detectors shall use the dual-chamber ionization principal to measure products of combustion and shall, on command from the control panel, send data to the panel representing the analog level of products of combustion. Analog Thermal Detectors 1. Thermal detectors shall be Analog addressable devices rated at 135 degrees Fahrenheit (58 degrees Celsius) and have a rate-of-rise element rated at 15 degrees F (9.4 degrees C) per minute. It shall connect via two wires to the fire alarm control panel signaling line circuit. Addressable Dry Contact Monitor Module 1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional alarm initiating devices (any N.O. dry contact device) to one of the fire alarm control panel SLCs. 2. The monitor module shall mount in a 4-inch square (101.6 mm square), 2-1/8 inch (54 mm) deep electrical box. 3. The IDC zone shall be suitable for Style D or Style B operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel. 4. For difficult to reach areas, the monitor module shall be available in a miniature package and shall be no larger than 2-3/4 inch (70 mm) x 1-1/4 inch (31.7 mm) x 1/2 inch (12.7 mm). This version need not include Style D or an LED. Two Wire Detector Monitor Module E710-10 1. Addressable monitor modules shall be provided to connect one supervised IDC zone of conventional 2-wire smoke detectors or alarm initiating devices (any N.O. dry contact device). 2. The two-wire monitor module shall mount in a 4-inch square (101.6 mm square), 2-1/8 inch (54 mm) deep electrical box or with an optional surface backbox. 3. The IDC zone may be wired for Class A or B (Style D or Style B) operation. An LED shall be provided that shall flash under normal conditions, indicating that the monitor module is operational and in regular communication with the control panel. H. Addressable Control Module 1. Addressable control modules shall be provided to supervise and control the operation of one conventional NACs of compatible, 24 VDC powered, polarized audio/visual notification appliances. For fan shutdown and other auxiliary control functions, the control module may be set to operate as a dry contract relay. 2. The control module shall mount in a standard 4-inch square (101.6 mm square), 2-1/8 inch (54 mm) deep electrical box, or to a surface mounted backbox. 3. The control module NAC may be wired for Style Z or Style Y (Class A/B) with up to 1 amp of inductive A/V signal, or 2 amps of resistive A/V signal operation, or as a dry contact (Form-C) relay. The relay coil shall be magnetically latched to reduce wiring connection requirements, and to insure that 100% of all auxiliary relay or NACs may be energized at the same time on the same pair of wires. 4. Audio/visual power shall be provided by a separate supervised power circuit from the main fire alarm control panel or from a supervised, UL listed remote power supply. 5. The control module shall be suitable for pilot duty applications and rated for a minimum of 0.6 amps at 30 VDC. I. Isolator Module 1. Isolator modules shall be provided to automatically isolate wire-to-wire short circuits on an SLC Class A or Class B branch. The isolator module shall limit the number of modules or detectors that may be rendered inoperative by a short circuit fault on the SLC loop segment or branch. At least one isolator module shall be provided for each floor or protected zone of the building. 2. If a wire-to-wire short occurs, the isolator module shall automatically open-circuit (disconnect) the SLC. When the short circuit condition is corrected, the isolator module shall automatically reconnect the isolated section. 3. The isolator module shall not require any address-setting, and its operations shall be totally automatic. It shall not be necessary to replace or reset an isolator module after its normal operation. 4. The isolator module shall mount in a standard 4-inch (101.6 mm) deep electrical box or in a surface mounted back box. It shall provide a single LED that shall flash to indicate that the isolator is operational and shall illuminate steadily to indicate that a short circuit condition has been detected and isolated. J. Serially Connected Annunciator Requirements 1. The annunciator shall communicate to the fire alarm control node or INA via an EIA 485 (multi-drop) two wire communications loop. The FACP node shall support two 6,000 ft (1828.8 m). EIA-485 wire runs. Up to 32 annunciators, each configured up to 64 points, may be connected to connections, for a system capacity of 2,048 points of annunciation. 2. An EIA-485 repeater shall be available to extend the EIA-485 wire distance in 3,000 ft. increments. An optional (UL 864 listed) version shall allow the EIA-485 circuit to be transmitted over Fiber optics. 3. Annunciator switches may be programmed for system control such as, global acknowledge, global signal silence, global system reset, and on/off control of any control point in the system. 4. An optional module shall be available utilizing annunciator points to drive EIA-485 driven relays. This shall extend the system point capacity by 2,048 remote contacts. K. LCD Alphanumeric Display Annunciator: 1. The alphanumeric display annunciator shall be a supervised, back-lit LCD display containing a minimum of eighty (80) characters for alarm annunciation in clear English text. E710-11 2. The LCD annunciator shall display all alarm and trouble conditions from either the network node or complete network, via the INA. 3. Up to 32 LCD annunciators may be connected to a specific (terminal mode) EIA 485 interface. LCD annunciators shall not reduce the annunciation capacity of the system. Each LCD shall include vital system wide functions such as, system acknowledge, silence and reset. 4. LCD display annunciators shall mimic the local control panel 80-character display or network annunciator and shall not require special programming. 2.07 BATTERIES AND EXTERNAL CHARGER A. Battery: 1. Batteries shall be 12 volt, Gell-Cell type. 2. The battery shall have sufficient capacity to power the fire alarm system for not less than 24 hours plus 5 minutes of alarm upon a normal AC power failure. 3. The batteries are to be completely maintenance free. No liquids are required. Fluid level checks for refilling, spills and leakage shall not be required. PART 3 - EXECUTION 3.01 INSTALLATION: A. Installation shall be in accordance with the NEC, NFPA 72, local codes, as shown on the drawings, and as recommended by the equipment manufacturer. B. All conduit, junction boxes, conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas. Smoke detectors shall not be installed prior to the system programming and test period. If construction is ongoing during this period, measures shall be taken to protect smoke detectors from contamination and physical damage. C. All fire detection and alarm system devices, control panels and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas. D. Manual Pull Stations shall be suitable for surface mounting or semi flush mounting and shall be installed not less than 42 inches (1067 mm), nor more than 48 inches (1219 mm) above the finished floor. 3.02 TYPICAL OPERATION: A. Actuation of any manual station, smoke detector, heat detector or water flow switch shall cause the following operations to occur unless otherwise specified: 1. Activate all programmed speaker circuits. 2. Actuate strobe units until the panel is reset. 3. Light the associated indicators corresponding to active speaker circuits. 4. Where required, return all elevators to the primary or alternate floor of egress. 5. A smoke detector in any elevator lobby shall, in addition to the above functions, return all elevators to the primary or alternate floor of egress. 6. Smoke detectors in the elevator machine room or top of hoist way shall return all elevators in to the primary or alternate floor. Smoke detectors or heat detectors installed to shut down elevator power shall do so in accordance with ANSI A17.1 requirements and be coordinated with the electrical contractor. 7. Duct type smoke detectors shall, in addition to the above functions, shut down the ventilation system or close associated control dampers as appropriate. 8. Activation of any sprinkler system low pressure switch, on valve tamper switch, shall cause a system supervisory alarm indication. B. HVAC/Smoke Control System Operation: 1. On/Auto/Off switches and status indicators (LEDS) shall be provided for monitoring and manual control of each fan, damper, HVAC control unit, stairwell pressurization fan, and smoke exhaust fan. To ensure compliance the units supplied shall meet the following UL categories: UUKL, PAZX, UDTZ, QVAX as well as the requirements of NFPA 90A, HVAC, and NFPA 92A & 92B, Smoke Control. The control System shall be field programmable for either 90A operation or 92A/B operation to allow for future use and system expansion. 2. The OFF LED shall be Yellow, the ON LED shall be green, the Trouble/Fault LED shall be Amber/Orange for each switch. The Trouble/Fault indicator shall indicate a trouble in the E710-12 control and/or monitor points associated with that switch. In addition, each group of eight switches shall have two LEDS and one momentary switch which allow the following functions: An Amber LED to indicate an OFF-NORMAL switch position, in the ON or OFF position; A Green LED to indicate ALL AUTO switch position; A Local Acknowledge/Lamp Test momentary switch. 3. Each switch shall have the capability to monitor and control two addressable inputs and two addressable outputs. In all modes, the ON and OFF indicators shall continuously follow the device status not the switch position. Positive feedback shall be employed to verify correct operation of the device being controlled. Systems that indicate on/off/auto by physical switch position only are not acceptable. 4. All HVAC switches (i.e., limit switches, vane switches, etc.) shall be provided and installed by the HVAC contractor. 5. It shall be possible to meet the requirements mentioned above utilizing wall mounted custom graphic annunciators if the project requires such. 3.03 TEST The service of a competent, factory-trained engineer or technician authorized by the manufacturer of the fire alarm equipment shall be provided to technically supervise and participate during all of the adjustments and tests for the system. A. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation. B. Close each sprinkler system flow valve and verify proper supervisory alarm at the FACP. C. Verify activation of all flow switches. D. Open initiating device circuits and verify that the trouble signal actuates. E. Open signaling line circuits and verify that the trouble signal actuates. F. Open and short notification appliance circuits and verify that trouble signal actuates. G. Open and short (wire only) network communications and verify that trouble signals are received at network annunciators or reporting terminals. H. Ground initiating device circuits and verify response of trouble signals. I. Ground signaling line circuits and verify response of trouble signals. J. Ground notification appliance circuits and verify response of trouble signals. K. Check alert tone and prerecorded voice message to all alarm notification devices. L. Check installation, supervision, and operation of all intelligent smoke detectors using walk test. M. Each of the alarm conditions that the system is required to detect should be introduced on the system. Verify the proper receipt and the proper processing of the signal at the FACP and the correct activation of the control points. N. When the system is equipped with optional features, the manufacturer's manual should be consulted to determine the proper testing procedures. This is intended to address such items as verifying controls performed by individually addressed or grouped devices, sensitivity monitoring, verification functionality and similar. 3.04 FINAL INSPECTION A. At the final inspection, a factory-trained representative of the manufacturer of the major equipment shall demonstrate that the system functions properly in every respect. 3.05 INSTRUCTION A. Instruction shall be required for operating the system. Hands-on demonstrations of the operation of all system components and the entire system including program changes and functions shall be provided. B. The contractor and/or the systems manufacturer's representatives shall provide a typewritten "Sequence of Operation." ---END--- E710-13 SECTION E725 SATELLITE & MASTER ANTENNA TV SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section includes television antennas; television distribution equipment; coordination with other utilities. 1.02 SYSTEM DESCRIPTION A. Type satellite master antenna system. 1.03 PERFORMANCE REQUIREMENTS A. Local TV channels and FM radio. B. Signal at each outlet: should be at 60-80 dBv. 1.04 SUBMITTALS A. Shop Drawings: Indicate electrical characteristics and connection requirements. Show installation details, cable routing, and system configuration. B. Product Data: Submit catalog data showing electrical characteristics and connection requirements for each component. C. Test Reports: Indicate procedures and results for specified field testing and inspection. D. Manufacturer's Field Reports: Indicate activities on site, adverse findings, and recommendations. 1.05 CLOSEOUT SUBMITTALS A. Project Record Documents: Record actual locations of outlets, devices, and cable routing. B. Operation and Maintenance Data: Submit instructions for setting and tuning channels, and for basic trouble-shooting procedures. 1.06 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. B. Supplier: Authorized distributor of specified manufacturer with minimum three years documented experience. 1.07 PRE-INSTALLATION MEETINGS A. Convene minimum one week prior to commencing work of this section. 1.08 MAINTENANCE SERVICE A. Furnish service and maintenance of television equipment as per project contract from Date of substantial Completion. 1.09 COORDINATION A. Coordinate with utility company relocation of overhead of underground lines interfering with construction. PART 2 PRODUCTS U 2.01 VHF ANTENNA A. Product Description: Broadband UHF/VHF antenna for television channels required. B. Antenna Type: 10 element Yagi type. C. Gain: 13dB over tuned dipole. D. Front-to-Back Ratio: 20dB, minimum. E. Beam Width: 52 degrees vertical x 63 degrees horizontal minus 3 dB. F. Return Loss: 17 dB, minimum over entire channel. G. Construction: Tubular metal elements. E725 - 1 H. Mounting Hardware: Suitable for stacking; minimum separation, 1/2 wavelength. I. Wind Resistance: Withstand 100 mph, 160 kph wind. 2.02 SATELLITE EARTH STATION A. Product Description: 1.8 meter satellite earth station. B. Gain: 38.1 dBi at 10.75 GHz., 38.7 dBi at 11.75 GHz, 39.5 dBi at 12.75 GHz C. Beamwidth (Half Power): less than 2 degrees. D. VSWR: 1.3: 1, maximum. A. Consolidated Consultants 16725 - 3 E. Cross polarization: should be over 27 dB. F. Feeds: multi-feed polarization. G. Construction: Aluminum 1.4 mm. H. Mounting: Elevation (15-50) degrees over azimuth (0-360) degrees. I. Wind load at a speed of wind by 216 km/h : min. 192 kg. 2.03 EARTH STATION DOWN CONVERTER A. Product Description: Converter with frequency range of 10.7-11.7 & 11.7-12.75 GHz. B. Output Frequency range: 950 to 2150 MHz. C. Noise Temperature: 60 degrees K Maximum at 23 degrees C. D. Overall Gain: 50-64 dB. E. System noise figure: 0.3 dB. F. Output/impedance: F connector/75 ohm. G. Supply voltage: 11.5-9 v H. Ambient temperature: -40 C to +60 C I. Switching threshold: 14/16v/22 KHz 2.04 VHF PREAMPLIFIER A. Product Description: Broadband pre-amplifier for channels required. B. Impedance: 75 ohm. C. Elements: 13 D. Gain: 13 dB, minimum. E. Signal-to-Noise Ratio: 3 db maximum. F. Beam width: -/+ 18 degrees G. Front to back ratio: > 25 dB 2.05 VHF/UHF AMPLIFIER A. Product Description: One single channel UHF/ rest. VHF/UHF. B. Impedance: 75 ohm. C. Noise figure(VHF/UHF) : 4. D. Maximum output level: 116 dB. E. Input : 2. F. Output : 1 G. Gain: 20 dB. H. Noise: 4 db maximum. 2.06 TAP A. Product Description: All-channel, back-matched tap. B. Recessed, suitable for mounting with standard duplex receptacle wall plate, C. Through Loss: 5 dB, maximum. D. Directional Loss: 20 dB minimum. E. Frequency range : 5-2400 MHz F. Tap loss : 8.5 - 20 dB G. Connector: F type coaxial connector. 2.07 ACTIVE SPLITTER E725 - 2 A. B. C. D. E. Frequency range: 5-2400 MHz Product Description: In-line, channel, back-matched splitter. Through Loss: 3.5dB for two-way; 6.7dB for four-way. Isolation: 10-20 dB. Return loss: greater dB 2.08 CASCADABLE MULTI-SWITCH A. 16 SAT –IF- polarization & terrestrial signal to 16 subscribers. B. Uses the switching criteria 14/18 v & 0/22 KHz for input selection. C. Terrestrial range is fully passive & allows reception without sat receiver. D. Frequency range: terrestrial 47-862, SAT 950-2150. E. Maximum output level: 100 dB. F. Isolation: SAT/SAT H/V > 30 dB, SAT/Terr. >25 dB. G. Tap loss: 5 dB for SAT, 20 dB for terrestrial. H. Through loss: 2 dB for SAT & Terrestrial. I. Control signal: 14/18 v & 0/22 KHz. 2.09 DISTRIBUTION CABLE A. Main Distribution Cable: RG 6/U RF. B. Branch Distribution Cable: RG 6/U RF. 2.10 SAT AMPLIFIERS A. Gain: SAT line 32 dB, SAT tap 25 dB, terr. line 25 dB, terr. Tap 15 dB. B. Maximum output level: max 114 dBmv for sat, max 114 dBmv for terrestrial. C. Noise figure: 8 dB D. Return Loss: 10 dB 2.11 EQUIPMENT RACK A. Product Description: Surface-mounted cabinet with adequate ventilation. B. Size: Selected by equipment manufacturer. C. Cabinet Finish: Selected by equipment manufacturer. PART 3 EXECUTIONS 3.01 FIELD QUALITY CONTROL A. Measure signal level at each outlet. 3.02 MANUFACTURER'S FIELD SERVICES A. Supervise final adjustments and tuning of system. 3.03 ADJUSTING A. Adjust each antenna using field strength meter to orient for maximum signal reception. B. Adjust amplifier gain and make other system adjustments to achieve specified output levels at each outlet. 3.04 DEMONSTRATION AND TRAINING A. Furnish 24 hours of instruction each for two persons, to be conducted at Project site with manufacturer's representative. B. It is the contractor responsibility to attain the right and accepted signal strength at every TV outlet whether the signal is SAT and/or terrestrial (RF). It is the contractor responsibility to decide the right amplifiers ratings where he needs to submit calculations regarding the losses and how it is compensated by the amplifiers. E725 - 3 ---END--- E725 - 4 SECTION E729 SURVEILLANCE CAMERAS AND CCTV SYSTEM PART 1 – GENERAL 1.01 DESCRIPTION A. Provide and install a complete Video Surveillance System, which is identified as the Closed Circuit Television System hereinafter referred to as the CCTV System as specified in this section. 1.02 QUALITY ASSURANCE A. The Contractor shall be responsible for providing, installing, and the operation of the CCTV System as shown. The Contractor shall also provide certification as required. B. The security system shall be installed and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the security system is stand-alone or a part of a complete Information Technology (IT) computer network. 1.03 SUBMITTALS A. In accordance with Section E010, ELECTRICAL INSTALLATIONS AND REQUIREMENTS, submit the following: B. Provide certificates of compliance with Section 1.3, Quality Assurance. C. Provide a pre-installation and as-built design package in both electronic format and on paper, minimum size 48 x 48 inches (1220 x 1220 millimeters); drawing submittals shall be per the established project schedule. D. Pre-installation design and as-built packages shall include, but not be limited to: 1. Index Sheet that shall: a. Define each page of the design package to include facility name, building name, floor, and sheet number. b. Provide a list of all security abbreviations and symbols. c. Reference all general notes that are utilized within the design package. d. Specification and scope of work pages for all security systems that are applicable to the design package that will: 1) Outline all general and job specific work required within the design package. 2) Provide a device identification table outlining device Identification (ID) and use for all security systems equipment utilized in the design package. 2. Drawing sheets that will be plotted on the individual floor plans or site plans shall: a. Include a title block as defined above. b. Define the drawings scale in both standard and metric measurements. c. Provide device identification and location. d. Address all signal and power conduit runs and sizes that are associated with the design of the electronic security system and other security elements (e.g., barriers, etc.). e. Identify all pull box and conduit locations, sizes, and fill capacities. f. Address all general and drawing specific notes for a particular drawing sheet. 3. A riser drawing for each applicable security subsystem shall: a. Indicate the sequence of operation. b. Relationship of integrated components on one diagram. c. Include the number, size, identification, and maximum lengths of interconnecting wires. d. Wire/cable types shall be defined by a wire and cable schedule. The schedule shall utilize a lettering system that will correspond to the wire/cable it represents. This schedule shall also provide the manufacturer’s name and part number for the wire/cable being installed. 4. A system drawing for each applicable security system shall: a. Identify how all equipment within the system, from main panel to device, shall be laid out and connected. b. Provide full detail of all system components wiring from point-to-point. c. Identify wire types utilized for connection, interconnection with associate security subsystems. E729-1 d. Show device locations that correspond to the floor plans. e. All general and drawing specific notes shall be included with the system drawings. 5. A schedule for all of the applicable security subsystems shall be included. All schedules shall provide the following information: a. Device ID. b. Device Location (e.g. site, building, floor, room number, location, and description). c. Mounting type (e.g. flush, wall, surface, etc.). d. Power supply or circuit breaker and power panel number. e. In addition, for the CCTV Systems, provide the camera ID, camera type (e.g. fixed or pan/tilt/zoom (P/T/Z), lens type (e.g. for fixed cameras only) and housing model number. 6. Detail and elevation drawings for all devices that define how they were installed and mounted. E. Pre-installation design packages shall be reviewed by the Contractor along with a owner representative to ensure all work has been clearly defined and completed. All reviews shall be conducted in accordance with the project schedule. There shall be four (4) stages to the review process: 1. 35 percent 2. 65 percent 3. 90 percent 4. 100 percent F. Provide manufacturer security system product cut-sheets. Submit for approval at least 30 days prior to commencement of formal testing, a Security System Operational Test Plan. Include procedures for operational testing of each component and security subsystem, to include performance of an integrated system test. G. Submit manufacture’s certification of Underwriters Laboratories, Inc. (UL) listing as specified. Provide all maintenance and operating manuals. PART 2 – PRODUCTS 2.01 EQUIPMENT AND MATERIALS A. All equipment associated within the CCTV System shall be UL 3004 compliant and rated for continuous operation. Environmental conditions (i.e. temperature, humidity, wind, and seismic activity) shall be taken under consideration at each facility and site location prior to installation of the equipment. B. All equipment shall operate on 230 volts alternating current (VAC); 50 Hz AC power system unless documented otherwise in subsequent sections listed within this specification. All equipment shall have a back-up source of power that will provide a minimum of 96 hours of run time in the event of a loss of primary power to the facility. C. The system shall be designed, installed, and programmed in a manner that will allow for easy of operation, programming, servicing, maintenance, testing, and upgrading of the system. D. All equipment and materials for the system will be compatible to ensure correct operation. 2.02 EQUIPMENT ITEMS A. CCTV system shall meet following requirements: B. All Cameras will be EIA 330 and UL 983 compliant as well as: 1. Will be charge coupled device (CCD) cameras and shall conform to Pal formatting. 2. Fixed cameras shall be color and the primary choice for monitoring following the activities described below. 3. Shall be powered by either 12 volts direct current (VDC) or 24 VAC. Power supplies shall be Class 2 and UL compliant and have a back-up power source to ensure cameras are still operational in the event of loss of primary power to the CCTV System. 4. Shall be rated for continuous operation under the following environmental conditions: a. Ambient temperatures of minus 10 degrees C to 55 degrees C utilizing equipment that will provide automatic heating and cooling. E729-2 5. 6. 7. 8. 11. 12. 13. 14. b. Humidity, wind gusts, ice loading, and seismic conditions specified or encountered for locations where CCTV cameras will be utilized. Each function and activity shall be addressed within the system by a unique twenty (20) character user defined name. The use of codes or mnemonics identifying the CCTV action shall not be accepted. Shall come with built-in video motion detection that shall automatically monitor and process information from each camera. The camera motion detection shall detect motion within the camera's field of view and provide automatic visual, remote alarms, and motion-artifacts as a result of detected motion as follows: a. Motion-detection settings shall include adjustable object size and velocity, as well as a selectable detection area of 132 zones in a twelve (12) x eleven (11) grid. b. Sensors shall accept video signals from CCTV cameras and when synchronizing is required, it shall be in composite synchronization. c. Sensor processors shall detect motion by digitizing multiple pixels within each video scene and by comparing the gray scale of the pixels to a previously stored reference. The number of pixels digitized depends on the application. The designer of the system shall consider cost effectiveness as a factor since digitizing a large number of pixels could increase cost dramatically with little additional actual detection capability for a specific application. d. An alarm shall be initiated when the comparison varies by six (6) percent or more. Appropriate signage shall be designed, provided, and posted that notifies people that an area is under camera surveillance. Shall be programmed to digitally flip from color to black and white at dusk and vise versa at dawn. Will be fitted with auto-iris lenses to ensure the image is maintained in low light. Lightning protection shall be IEEE C62.41 compliant and provided for all cameras. Either surge protectors or a lightning grid may be utilized. Ensure all lightning protection equipment is compliant with Article 780 of the National Electrical Code (NEC). The use of Fuses and Circuit Breakers as a means of lightning protection shall not be allowed. If using the camera as part of a CCTV network a video encoder shall be used to convert the signal from Pal to (H264) format. Fixed Color Cameras Technical Characteristics: Sensor Type 1/3-inch CCD, WDR, dual shutter Active Pixels (PAL) 752 x 582 Active Pixels (NTSC) 768 x 494 Video Video compression H.264 (ISO/IEC 14496-10); M-JPEG, JPEG Data rate 9.6 Kbps to 6 Mbps Resolution Horizontal x vertical (PAL/NTSC ips) • 4CIF 704 x 576/480 (25/30 ips) • CIF 352 x 288/240 (25/30 ips) Overall IP Delay Min.120 ms, Max. 240 ms GOP structure I, IP Frame rate 1 to 50/60 (PAL/NTSC) H.264 1 to 25/30 (PAL/NTSC) M-JPEG Video Out E729-3 Signal Analog composite (NTSC or PAL) for service Connector 2.5 mm jack, 75 Ohm Horizontal resolution 540 TVL Video S/N 50 dB Optical Varifocal lens IR corrected, manual zoom and focus adjustment Iris control Automatic iris control Viewing angle 2.8 to 10 mm Wide 100.8 x 73.7º (H x V) Tele 28.5º x 21.4º (H x V) 9 to 22 mm Wide: 31.2º x 22.8º (H x V) Tele: 12.8º x 9.6º (H x V ) Mechanical Weight 0.67 kg (1.48 lb) +SMB: 1.29 kg (2.84 lb) Mounting Flush mount or surface mount Color White (RAL9010) trim ring with black inner liner Adjustment range 360º pan, 90º tilt, ±90º azimuth Dome bubble Polycarbonate, clear with UV blocking antiscratch coating Trim ring Aluminum C. Lenses: Shall be utilized in a manner that provides maximum coverage of the area being monitored by the camera. The lenses shall: 1. Be 1/3” to fit CCD fixed camera. 2. Be all glass with coated optics. 3. Have mounts that are compatible with the camera selected. 4. Be packaged and supplied with the camera. 5. Have a maximum f-stop of f/1.3 for fixed lenses, and a maximum f-stop of f/1.6 for variable focus lenses. 6. Be equipped with an auto-iris mechanism. 7. Have sufficient circle of illumination to cover the image sensor evenly. 8. Not be used on a camera with an image format larger than the lens is designed to cover. 9. Be provided with pre-set capability. D. Two types of lenses shall be utilized for both interior and exterior fixed cameras: 1. Manual Variable Focus 2. Auto Iris Fixed E. Auto Iris Fixed 1. Shall be utilized in areas where a small specific point of reference is to be monitored. Examples of this are doorways, elevators, cashier booths, etc. 2. To determine the exact size of the fixed lens required, complete a focal length calculation using either a focal length calculator or a focal length chart provided by the product manufacturer. 3. Technical Characteristics: Image format 1/3 inch 1/3 inch 1/3 inch Focal length 2.8 mm 4 mm 8 mm Iris range F1.2 – 200 E729-4 F1.2 – 200 F1.2 - 200 Min. Object Lens mount Angle of view Focus control 0.3 m (1 ft) CS-mount 94 X 72 Manual 0.3 m (1 ft) CS-mount 64 X 49 Manual 0.3 m (1 ft) CS-mount 33 x 25 manual F. Video Display Equipment 1. Will consist of color monitors and shall be EIA 375A compliant. 2. Shall be able to display analog, digital, and other images in either Pal or MPEG format associated with the operation of the Security Management System (SMS). 3. Shall: a. Have front panel controls that provide for power on/off, horizontal and vertical hold, brightness, and contrast. b. Accept multiple inputs, either directly or indirectly. c. Have the capabilities to observe and program the CCTV System. d. Be installed in a manner that they cannot be witnessed by the general public. 5. Liquid Crystal Display (LCD) Flat Panel Display Monitor a. Technical Characteristics: Sync Format PAL/NTSC LCD Panel TFT LCD Resolution 1280 x 1024 pixels; 500 TV Contrast Ratio (CR) 500:1 Viewing Angle 140° horizontal, 130° vertical Video Input (CVBS) 1.0 Vp-p (0.5–1.5 Vp-p), 75 Ohm Y/C (S-video) 0.7 Vp-p, 0.3 Vp-p, 75 Ohm Video 1 Composite video two (2) BNC (1 in, 1 out) Video 2 Composite video two (2) BNC (1 in, 1 out) Y/C (S-video) two (2) mini-dins, 4-pin (1 in, 1 out) G. Camera Housings and Mounts: 1. This section pertains to all interior and exterior housings, domes, and applicable wall, ceiling, corner, pole, and rooftop mounts associated with the housing. Housings and mounts shall be specified in accordance to the type of cameras used. 2. All cameras and lenses shall be enclosed in a tamper resistant housing. Any additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing. 3. The camera and lens contained inside the housing shall be installed on a camera mount. All additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing. 4. Environmentally Sealed a. Shall: 1) Be designed in manner that it provides a condensation free environment for correct camera operation. 2) Operate in a 100 percent condensing humidity atmosphere. 3) Be constructed in a manner that: a) Has a fill valve to allow for the introduction of nitrogen into the housing to eliminate existing atmospheric air and pressurize the housing to create moisture free conditions. b) Has an overpressure valve to prevent damage to the housing in the event of over pressurization. E729-5 c) Is equipped with a humidity indicator that is visible to the eye to ensure correct atmospheric conditions at all times. d) The leak rate of the housing is not to be greater than 13.8kPa or 2 pounds per square inch at sea level within a 90 day period. e) It shall contain camera mounts or supports as needed to allow for correct positioning of the camera and lens. f) The housing and sunshield are to be white in color. b. All electrical and signal cables required for correct operations shall be supplied in a hardened carrier system from the controller to the camera. c. The mounting bracket shall be adjustable to allow for the housing weight of the camera and the housing unit it is placed in. d. Accessibility to the camera and mounts shall be taken into consideration for maintenance and service purposes. 6. Indoor Mounts a. Ceiling Mounts: 1) This enclosure and mount shall be installed in a finished or suspended ceiling. 2) The enclosure and mount shall be fastened to the finished ceiling, and shall not depend on the ceiling tile grid for complete support. b. Wall Mounts: 1) The enclosure shall be installed in manner that it matches the existing décor and placed at a height that it will be unobtrusive, unable to cause personal harm, and prevents tampering and vandalism. 2) The mount shall contain a manual pan/tilt head that will provide 360 degrees of horizontal and vertical positioning from a horizontal position, and has a locking bar or screw to maintain its fixed position once it has been adjusted. 7. Interior Domes a. The interior dome shall be a pendant mount, pole mount, ceiling mount, surface mount, or corner mounted equipment. b. The lower portion of the dome that provides camera viewing shall be made of black opaque acrylic and shall have a light attenuation factor of no more that 1 f-stop. c. The housing shall be equipped with integral pan/tilt capabilities complete with wiring, wiring harness, connectors, receiver/driver, pan/tilt control system, pre-position cards, or any other hardware and equipment as needed to fully provide a fully functional pan/tilt dome. 9. Exterior Wall Mounts a. Shall have an adjustable head for mounting the camera. b. Shall be constructed of aluminum, stainless steel, or steel with a corrosion-resistant finish. c. The head shall be adjustable for not less than plus and minus 90 degrees of pan, and not less than plus and minus 45 degrees of tilt. If the bracket is to be used in conjunction with a pan/tilt, the bracket shall be supplied without the adjustable mounting head, and shall have a bolt-hole pattern to match the pan/tilt base. d. Shall be installed at a height that allows for maximum coverage of the area being monitored. H. Controlling Equipment 1. Shall be utilized to call up, operate, and program all cameras associated CCTV System components. 2. Will have the ability to operate the cameras locally and remotely. A digital video recorder or a network server shall be utilized as the CCTV System controller. 3. The controller shall be able to fit into a standard 19” (47.5 cm) equipment rack. 4. Control and programming keyboards shall be provided with its own type of switcher. All keyboards shall: a. Be located at each monitoring station. b. Be addressable for programming purposes. c. Provide interface between the operator and the CCTV System. E729-6 I. d. Provide full control and programming of the switcher. e. Have the minimum following controls: 1) Programming 2) Switching 3) Lens function 4) P/T/Z 5) Environmental housing 6) Annotation Recording Devices 1. All cameras on the CCTV System shall be recorded in real time using a Digital Video Recorder (DVR),. The type of recording device utilized should be determined by the size and type of CCTV System designed and installed, and to what extent the system is to be utilized. 2. All recording devices shall be 19“(47.5 cm) rack-mountable. 3. All DVR’s are viewable over an Intranet or Internet will be routed through an encryptor. Encryptors shall: a. Comply with FIPS PUB 140-2. b. Support TCP/IP. c. Directly interfaces to low-cost commercial routers. d. Provide packet-based crypto synchronization. e. Encrypt source and destination IP addresses. f. Support web browser based management requiring no additional software. g. Have a high data sustained throughput — 1.544 Mbps (T1) full duplex data rate. h. Provide for both bridging and routing network architecture support. i. Support Electronic Key Management System (EKMS) compatible. j. Have remote management ability. k. Automatically reconfigure when secure network or wide area network changes. 4. Digital Video Recorder (DVR): a. Shall record video to a hard drive-based digital storage medium in H264 format. b. Shall meet the following minimum requirements: 1) Record at minimum rate of 25 images per second (IPS). 2) Have a minimum to 16 looping inputs. 3) Have a minimum of eight (8) to 16 alarm inputs and two (2) relay outputs. 4) Shall provide instantaneous playback of all recorded images. 5) Be IP addressable, if part of a CCTV network. 6) Have built-in digital motion detection with masking and sensitivity adjustments. 7) Provide easy playback and forward/reverse search capabilities. 8) Complete audit trail database, with minimum of a six-month history that tracks all events related to the alarm; specifically who, what, where and when. 9) DVR management capability providing automatic video routing to a back-up spare recorder in case of failure. 10) Accessible locally and remotely via the Internet, Intranet, or a personal digital assistant (PDA). 11) Records all alarm events in real time, ensuring 60 seconds before and after the event are included in the recording. 12) Utilize RS-232 or fiber optic connections for integration with the SMS computer station via a remote port on a network hub. 13) Allow for independently adjustable frame rate settings. c. Technical Characteristics: i. Playback Requirements: 1. The hybrid DVR shall allow playback of the stored video in the forward or reverse direction, frame by frame, and from beginning or end of the clip using standard VCR-like buttons. Reviewed video clips or still images can be zoomed in or out. The images can be sent to a printer connected to the parallel port of the local recorder or to a network printer. An image displayed in the image window can be saved as a single JPEG, BMP, or HTML file. E729-7 2. The hybrid DVR shall have an instant playback function that allows instant recall of recorded images from 10 to 300 seconds in the past to be replayed at the same rate the images were recorded. Live images continue to be simultaneously displayed along with the recorded images. ii. Exporting Video Images: 1. The hybrid DVR will be capable of exporting video clips to the CD/DVD drive or network drive. a. Images can be exported along with a stand-alone player. Playback of the exported images with the player will be possible from any Windows based PC. This proprietary format provides video authentication to assure that images are not altered in any way. b. Images can also be exported in a format that can be played back with a default software program such as Windows Media Player. 2. The DVR shall provide an export video scheduler function that allows previous days recorded video to be exported for back up to a designated target drive. Images from the current day can also be exported up to the time that the export program job is activated. iii. Remote Access 1. The hybrid DVR will support login of users in LDAP (Lightweight Directory Access Protocol) groups. 2. The hybrid DVR will provide embedded Internet Web Browser access that allows up to five (5) remote PCs using Windows Explorer 6.0 or higher to communicate with the recorder via a network. The browser will be a secure connection using log-on and authorization levels during transmission. From the remote site using the browser, the live video images will be displayed in single or multi-screen format; video displayed as single screen sequences; status of the inputs will be displayed; remote relays will be controllable; and compatible P/T/Z cameras will be controllable. 3. Optional remote receiver software programs will be available from the specified digital recorder manufacturer that will operate on a remote Windows XP based PC. Operation of these remote receiver software programs will require installation of a manufacturer supplied Dongle key to the remote PC. 4. The optional remote receiver shall have the ability to display the database information from a DVR. 5. The optional remote receiver shall be able to receive and record alarm video from the DVR to its local drive iv. Alarm and Trigger Input Capability 1. The hybrid DVR will be capable of automatically displaying incoming camera alarms, with the option of displaying alarms when in playback mode. The DVR will also allow the option to manually acknowledge an alarm to silence, or to delete an alarm. All alarm acknowledgements and deletions will be saved to a log file. 2. The hybrid DVR will be capable of hiding a camera during normal operation, only to display the camera during an alarm when the camera is part of the alarm. 3. The hybrid DVR will have the capability to send an e-mail notification on the following events: an alarm, motion detection, video loss, or a reference image check failure. E729-8 4. The hybrid DVR will be capable of handling up to 32 N/O or N/C alarm inputs and providing up to 16 relay outputs where 1 of those relays will be designated as a malfunction relay. 5. The hybrid DVR will be capable of recording pre-alarm video on an alarm or motion detection for a time period from 0 to 120 seconds. Post alarm recording time will be selectable from 0 to 999 seconds. The DVR will be capable of having pre and post alarm video recorded from the analog and compatible MPEG4 and JPEG cameras. 6. The hybrid DVR will be capable of transmitting live video images via a network upon an alarm or triggered event to a remote location(s) that is running the specified manufacturer’s DVR remote software program. The DVR will maintain a list of remote sites in order of priority so that an attempt is made to establish communication with the first site on the list. If the attempt fails, the DVR will move to the next remote site on the list to establish connection. Once communication is established, the DVR will initially alert the operator at the remote station via a flashing icon and audible tone (or selected wav file) that an alarm has occurred. The operator will then have the option to acknowledge the alarm and display the live video at the workstation. The DVR will also have the capability to be programmed to establish communication with multiple remote sites upon an alarm. 7. The hybrid DVR will provide motion detection sensing of the connected analog cameras. Sensitive areas of the camera’s field of view may be programmed within the DVR. The DVR will also react to Bosch IP cameras and encoders on the network that have been programmed to detect video motion. 8. The hybrid DVR will be capable of automatically commanding Bosch AutoDome pan/tilt/zoom cameras to move to preprogrammed preset positions. 9. The hybrid DVR will provide 32 virtual alarm inputs that can be controlled via the browser interface to execute preprogrammed jobs within the DVR such as controlling relay outputs, camera sequences, alarm recording, etc. 10. The hybrid DVR will interface to a Bosch G-Series Alarm Panel via an RS232 interface. v. DVR Setup and Configuration 1. The hybrid DVR will provide the following two methods of system setup and configuration: a. A Quick Configuration Wizard will be provided and intended for the inexperienced user who must create a basic system configuration and operate the recorder in a minimum amount of time. The quick configuration will allow setup of the following system parameters: i. Time and date. ii. Authorization levels and users. iii. Network settings including the capability to limit the bandwidth to a value that the system does not exceed. iv. Display analog cameras that were automatically detected during the initial startup of the configuration wizard. E729-9 v. A graphical time planner to allow the record rates, quality of recording, and type of recording to be assigned to specific days of the week and times. vi. A dialog box to determine the type of recordings, rate of recording, and quality of recording desired including up to 30 minutes of pre-alarm recording. b. A Default (customized) Configuration shall be provided to allow for programming of more complex applications of the specified DVR. A configuration menu will be displayed in a Windows tree format to allow the user to create the system configuration setup by going from top to bottom of the menu and making the corresponding entries in the dialog boxes. The Default Configuration will provide, but not be limited to, the following configuration selections: i. Connection and disconnection of local and network hard drives. Displays total storage capacity, used storage capacity, and available storage. ii. Provides an overview of the local recorder including cameras and audio inputs. Allows addition, deletion, editing of cameras and audio inputs, including JPEG and MPEG4 IP cameras, pre-position, and setup of pre-position scenes, motion detection, and sequence programming for two analog monitors. iii. Recording setup – On a camera by camera basis, allows setup of IPS rate and type of recording such as continuous, motion, or alarm. Time profiles can be assigned to these setups. iv. Graphical time planner provides eight profiles that can be assigned to any day of the week, holiday, or special day. v. The recorder provides activation and deactivation of up to 32 N/O or N/C alarm contacts to the input. Up to 16 relay outputs will be available at the local station that can be activated from a manufacturer provided remote station software package or via a browser. A malfunction relay is also provided. Four alarm inputs can be used for alarm simulation purposes. vi. The recorder can be compatible with the Bosch G Series Panel to allow selection of up to 32 software inputs from the panel. vii. Jobs may be created that are started by input triggers, cameras using motion detection, or a virtual input. Jobs can also be assigned a time profile. Jobs created can 1) control up to 4 dome cameras 2) control relay outputs 3) control camera sequences for two analog monitors and 4) start alarm recording. viii. Allow setup of connection between local recorder and remote stations. E729-10 ix. The DVR specified will transmit images and/or messages to other locations upon an alarm or trigger event. x. Video authentication. 2. The hybrid DVR will support an optional feature that allows the hybrid DVR to: a. Integrate with a Bosch ATM/POS Bridge. b. Connect to an IP server that sends data (for example a POS server) and to record this data as metadata along with the camera image. J. Wires and Cables 1. Shall meet or exceed the manufactures recommendation for power and signal. 2. Will be carried in an enclosed conduit system, utilizing electromagnetic tubing (EMT) to include the equivalent in flexible metal, rigid galvanized steel (RGS) to include the equivalent of liquid tight, polyvinylchloride (PVC) schedule 40 or 80. 3. All conduits will be sized and installed per the NEC. All security system signal and power cables that traverse or originate in a high security office space will contained in either EMT or RGS conduit. 4. All conduit, pull boxes, and junction boxes shall be clearly marked with colored permanent tape or paint that will allow it to be distinguished from all other conduit and infrastructure. 5. Conduit fills shall not exceed 50 percent unless otherwise documented. 6. A pull string shall be pulled along and provided with signal and power cables to assist in future installations. 7. At all locations where there is a wall penetration or core drilling is conducted to allow for conduit to be installed, fire stopping materials shall be applied to that area 8. High voltage and signal cables shall not share the same conduit and shall be kept separate up to the point of connection. High voltage for the security system shall be defined as any cable or sets of cables carrying 30 VDC/VAC or higher. 9. For all equipment that is carrying digital data between the Access Control System and Database Management or at a remote monitoring station, shall not be less that 20 AWG and stranded copper wire for each conductor. The cable or each individual conductor within the cable shall have a shield that provides 100% coverage. Cables with a single overall shield shall have a tinned copper shield drain wire. 10. All cables and conductors, except fiber optic cables, that act as a control, communication, or signal lines shall include surge protection. Surge protection shall be furnished at the equipment end and additional triple electrode gas surge protectors rated for the application on each wire line circuit shall be installed within one (1) m. of the building cable entrance. The inputs and outputs shall be tested in both normal and common mode using the following wave forms: a. A 10 microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 watts and peak current of 60 amperes. b. An 8 microsecond rise time by 20 microsecond pulse width wave form with a peak voltage of 1000 volts and peak current of 500 amperes. 11. The surge suppression device shall not attenuate or reduce the video or sync signal under normal conditions. Fuses and relays shall not be used as a means of surge protection. 12. Coaxial Cables a. All video signal cables for the CCTV System, with exception to the PoE cameras, shall be a coaxial cable and have a characteristic impedance of 75 ohms plus or minus 3 ohms. b. For runs up to 750 feet use of an RG-59/U is required. The RG-59/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 23 AWG, polyethylene insulation, and black non-conductive polyvinylchloride (PVC) jacket. c. For runs between 750 feet and 1250 feet, RG-6/U is required. RG-6/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 18 AWG, polyethylene insulation, and black non-conductive polyvinylchloride (PVC) jacket. E729-11 d. For runs of 1250 to 2750 feet, RG-11/U is required. RG-11/U shall be shielded which provides a minimum of 95 percent coverage, with a stranded copper center conductor of a minimum 14 AWG, polyethylene insulation, and black non-conductive polyvinylchloride (PVC) jacket. e. All runs greater than 2750 feet will be substituted with a fiber optic cable. If using fiber optics as a signal carrier then the following equipment will be utilized: 1) Multimode fiber optic cable a minimum size of 62 microns 2) Video transmitter, installed at the camera that utilizes 12 VDC or 24 VAC for power. 3) Video receiver, installed at the switcher. f. RG-59/U Technical Characteristics AWG Stranding Conductor Diameter Conductor Material Insulation Material Insulation Diameter Outer Shield Type Outer Jacket Material Overall Nominal Diameter UL Temperature Rating Nom. Characteristic Impedance Nom. Inductance Nom. Capacitance Nom. Velocity of Propagation Nom. Delay Nom. Conductor DC Resistance @ 20°C Nom. Outer Shield DC Resistance @ 20°C Max. Operating Voltage 22 7x29 .031 in. BCC Gas-injected FHDPE .145 in. Braid/Braid PVC .242 in. 75°C 75 Ohms 0.094 μH/ft Conductor to Shield 17.0 pF/ft 80 % 1.3 ns/ft 12.2 Ohms/1000 ft 2.4 Ohms/1000 ft UL 300 V RMS 14. Power Cables a. Will be sized accordingly and shall comply with the NEC. High voltage power cables will be a minimum of three conductors, 14 AWG, stranded, and coated with a non-conductive polyvinylchloride (PVC) jacket. Low voltage cables will be a minimum of 18 AWG, stranded and non-conductive polyvinylchloride (PVC) jacket. b. Will be utilized for all components of the CCTV System that require 220 VAC 50 Hz input. Each feed will be connected to a dedicated circuit breaker at a power panel that is primarily for the security system. c. All equipment connected to AC power shall be protected from surges. Equipment protection shall withstand surge test waveforms described in IEEE C62.41. Fuses shall not be used as a means of surge protection. d. Shall be rated for 220 VAC, 50 Hz, and shall comply with VA Low Voltage Electrical Power Conductors and Cables (600 Volts and Below). e. Low Voltage Power Cables 1) Shall be a minimum of 18 AWG, Stranded and have a polyvinylchloride outer jacket. 2) Cable size shall determined using a basic voltage over distance calculation and shall comply with the NEC’s requirements for low voltage cables. E729-12 2.03 INSTALLATION KIT A. General: 1. The kit shall be provided that, at a minimum, includes all connectors and terminals, labeling systems, audio spade lugs, barrier strips, punch blocks or wire wrap terminals, heat shrink tubing, cable ties, solder, hangers, clamps, bolts, conduit, cable duct, and/or cable tray, etc., required to accomplish a neat and secure installation. All wires shall terminate in a spade lug and barrier strip, wire wrap terminal or punch block. Unfinished or unlabeled wire connections shall not be allowed. All unused and partially opened installation kit boxes, coaxial, fiberoptic, and twisted pair cable reels, conduit, cable tray, and/or cable duct bundles, wire rolls, physical installation hardware shall be turned over to the Contracting Officer. The following sections outline the minimum required installation sub-kits to be used: 2. System Grounding: a. The grounding kit shall include all cable and installation hardware required. All head end equipment and power supplies shall be connected to earth ground via internal building wiring, according to the NEC. b. This includes, but is not limited to: 1) Coaxial Cable Shields 2) Control Cable Shields 3) Data Cable Shields 4) Equipment Racks 5) Equipment Cabinets 6) Conduits 7) Cable Duct blocks 8) Cable Trays 9) Power Panels 10) Grounding 11) Connector Panels 3. Coaxial Cable: The coaxial cable kit shall include all coaxial connectors, cable tying straps, heat shrink tabbing, hangers, clamps, etc., required to accomplish a neat and secure installation. 4. Wire and Cable: The wire and cable kit shall include all connectors and terminals, audio spade lugs, barrier straps, punch blocks, wire wrap strips, heat shrink tubing, tie wraps, solder, hangers, clamps, labels etc., required to accomplish a neat and orderly installation. 5. Conduit, Cable Duct, and Cable Tray: The kit shall include all conduit, duct, trays, junction boxes, back boxes, cover plates, feed through nipples, hangers, clamps, other hardware required to accomplish a neat and secure conduit, cable duct, and/or cable tray installation in accordance with the NEC and this document. 6. Equipment Interface: The equipment kit shall include any item or quantity of equipment, cable, mounting hardware and materials needed to interface the systems with the identified sub-system(s) according to the OEM requirements and this document. 7. Labels: The labeling kit shall include any item or quantity of labels, tools, stencils, and materials needed to correctly label each subsystem according to the OEM requirements, asinstalled drawings, and this document. 8. Documentation: The documentation kit shall include any item or quantity of items, computer discs, as installed drawings, equipment, maintenance, and operation manuals, and OEM materials needed to correctly provide the system documentation as required by this document and explained herein. PART 3 - EXECUTION 3.01 INSTALLATION A. System installation shall be in accordance with NECA 303, manufacturer and related documents and references, for each type of security subsystem designed, engineered and installed. B. Components shall be configured with appropriate “service points” to pinpoint system trouble in less than 30 minutes. E729-13 C. The Contractor shall install all system components including Government furnished equipment, and appurtenances in accordance with the manufacturer's instructions, documentation listed in Sections 1.4 and 1.5 of this document, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable system. D. The CCTV System will be designed, engineered, installed, and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the system is a stand alone or a complete network. E. For integration purposes, the CCTV System shall be integrated where appropriate with the following associated security subsystems: 1. PACS: a. Provide 24 hour coverage of all entry points to the perimeter and agency buildings, as well as all emergency exits utilizing a fixed color camera. b. Record cameras on a 24 hours basis. c. Be programmed go into an alarm state when an emergency exit is opened, and notify the Access Control System and Database Management of an alarm event. d. For additional CCTV System requirements as they relate to the PACS, refer to Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS. 2. IDS: a. Provide a recorded alarm event via a color camera that is connected to the IDS system by either direct hardwire or a security system computer network. b. Record cameras on a 24 hours basis. c. Be programmed to go into an alarm state when an IDS device is put into an alarm state, and notify the. d. For additional CCTV System requirements as they relate to the IDS, refer to Master Specification 28 16 11. 3. Security Access Detection: a. Provide full coverage of all vehicle and lobby entrance screening areas utilizing a fixed color camera. b. Record cameras on a 24 hours basis. c. The CCTV System should have facial recognition software to assist in identifying individuals for current and future purposes. d. For additional CCTV System requirements as they relate to the Security Access Detection, refer to Master Specification 28 13 53. 4. EPPS: a. Provide a recorded alarm event via a color camera that is connected to the EPPS system by either direct hardwire or a security system computer network. b. Record cameras on a 24 hours basis. c. Be programmed to go into an alarm state when an emergency call box or duress alarm/panic device is activated, and notify the Access Control System and Database Management of an alarm event. d. For additional CCTV System requirements as they relate to the EPPS, refer to Master Specification 28 26 00. F. Integration with these security subsystems shall be achieved by computer programming or the direct hardwiring of the systems. G. For programming purposes refer to the manufacturers requirements for correct system operations. Ensure computers being utilized for system integration meet or exceed the minimum system requirements outlined on the systems software packages. H. A complete CCTV System shall be comprised of, but not limited to, the following components: 1. Cameras 2. Lenses 3. Video Display Equipment 4. Camera Housings and Mounts 5. Controlling Equipment 6. Recording Devices 7. Wiring and Cables E729-14 I. J. K. L. M. N. O. P. Q. The Contractor shall visit the site and verify that site conditions are in agreement/compliance with the design package. The Contractor shall report all changes to the site or conditions that will affect performance of the system to the Contracting Officer in the form of a report. The Contractor shall not take any corrective action without written permission received from the Contracting Officer. Enclosure Penetrations: All enclosure penetrations shall be from the bottom of the enclosure unless the system design requires penetrations from other directions. Penetrations of interior enclosures involving transitions of conduit from interior to exterior, and all penetrations on exterior enclosures shall be sealed with rubber silicone sealant to preclude the entry of water and will comply with VA Master Specification 07 84 00, Firestopping. The conduit riser shall terminate in a hot-dipped galvanized metal cable terminator. The terminator shall be filled with an approved sealant as recommended by the cable manufacturer and in such a manner that the cable is not damaged. Cold Galvanizing: All field welds and brazing on factory galvanized boxes, enclosures, and conduits shall be coated with a cold galvanized paint containing at least 95 percent zinc by weight. Interconnection of Console Video Equipment: The Contractor shall connect signal paths between video equipment as specified by the OEM. Cables shall be as short as practicable for each signal path without causing strain at the connectors. Rack mounted equipment on slide mounts shall have cables of sufficient length to allow full extension of the slide rails from the rack. Cameras: 1. Install the cameras with the focal length lens as indicated for each zone. 2. Connect power and signal lines to the camera. 3. Set cameras with fixed iris lenses to the f-stop to give full video level. 4. Aim camera to give field of view as needed to cover the alarm zone. 5. Aim fixed mounted cameras installed outdoors facing the rising or setting sun sufficiently below the horizon to preclude the camera looking directly at the sun. 6. Focus the lens to give a sharp picture (to include checking for day and night focus and image quality) over the entire field of view; and synchronize all cameras so the picture does not roll on the monitor when cameras are selected. Dome cameras shall have all preset positions defined and installed. Monitors: 1. Install the monitors as shown and specified in design and construction documents. 2. Connect all signal inputs and outputs as shown and specified. 3. Terminate video input signals as required. 4. Connect the monitor to AC power. Video Recording Equipment: 1. Install the video recording equipment as shown in the design and construction documents, and as specified by the OEM. 2. Connect video signal inputs and outputs as shown and specified. 3. Connect alarm signal inputs and outputs as shown and specified. 4. Connect video recording equipment to AC power. Camera Housings, Mounts, and Poles: 1. Install the camera housings and mounts as specified by the manufacturer and as shown, provide mounting hardware sized appropriately to secure each camera, housing and mount with maximum wind and ice loading encountered at the site. 2. Provide a foundation for each camera pole as specified and shown. 3. Provide a ground rod for each camera pole and connect the camera pole to the ground rod as specified in Division 26 of the VA Master Specification and the VA Electrical Manual 730. 4. Provide electrical and signal transmission cabling to the mount location via a hardened carrier system from the Access Control System and Database Management to the device. 5. Connect signal lines and AC power to the housing interfaces. 6. Connect pole wiring harness to camera. System Start-Up 1. The Contractor shall not apply power to the CCTV System until the following items have been completed: E729-15 a. CCTV System equipment items and have been set up in accordance with manufacturer's instructions. b. A visual inspection of the CCTV System has been conducted to ensure that defective equipment items have not been installed and that there are no loose connections. c. System wiring has been tested and verified as correctly connected as indicated. d. All system grounding and transient protection systems have been verified as installed and connected as indicated. e. Power supplies to be connected to the CCTV System have been verified as the correct voltage, phasing, and frequency as indicated. 2. Satisfaction of the above requirements shall not relieve the Contractor of responsibility for incorrect installation, defective equipment items, or collateral damage as a result of Contractor work efforts. R. Supplemental Contractor Quality Control 1. The Contractor shall provide the services of technical representatives who are familiar with all components and installation procedures of the installed CCTV System; and are approved by the Contracting Officer. 2. The Contractor will be present on the job site during the preparatory and initial phases of quality control to provide technical assistance. 3. The Contractor shall also be available on an as needed basis to provide assistance with follow-up phases of quality control. 4. The Contractor shall participate in the testing and validation of the system and shall provide certification that the system installed is fully operational as all construction document requirements have been fulfilled. ---END--- E729-16 SECTION E738 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. 1.02 REFERENCES A. EIA/TIA 568 (Electronic Industries Association/Telecommunications Industries Association) Commercial Building Telecommunication Wiring Standard. B. EIA/TIA 569 (Electronic Industries Association/Telecommunications Industries Association)Commercial Building Standard for Telecommunications Pathways and Spaces. C. NETA ATS (International Electrical Testing Association) - Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems. 1.03 SUMMARY A. Section Includes: 1. Pathways. 2. UTP cabling. 3. 50/125-micrometer, optical fiber cabling. 4. Coaxial cable. 5. Multiuser telecommunications outlet assemblies. 6. Cable connecting hardware, patch panels, and cross-connects. 7. Telecommunications outlet/connectors. 8. Cabling system identification products. 9. Cable management system 10. Manufacturers. B. Related Sections: 1. Section E740 "Communications Backbone Cabling" for voice and data cabling 2. Section E813 "Conductors and Cables for Electronic Safety and Security" for voice and data cabling associated with system panels and devices. 1.04 DEFINITIONS A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. B. BICSI: Building Industry Consulting Service International. C. Channel Cable Tray: A fabricated structure consisting of a one-piece, ventilated bottom or solidbottom channel. D. Consolidation Point: A location for interconnection between horizontal cables extending from building pathways and horizontal cables extending into furniture pathways. E. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. F. EMI: Electromagnetic interference. G. IDC: Insulation displacement connector. H. Ladder Cable Tray: A fabricated structure consisting of two longitudinal side rails connected by individual transverse members (rungs). I. LAN: Local area network. J. MUTOA: Multiuser telecommunications outlet assembly, a grouping in one location of several telecommunications outlet/connectors. K. Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates. L. RCDD: Registered Communications Distribution Designer. M. Solid-Bottom or Non-ventilated Cable Tray: A fabricated structure consisting of longitudinal side rails and a bottom without ventilation openings. E738-1 N. Trough or Ventilated Cable Tray: A fabricated structure consisting of longitudinal side rails and a bottom having openings for the passage of air. O. UTP: Unshielded twisted pair. 1.05 HORIZONTAL CABLING DESCRIPTION A. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called "permanent link," a term that is used in the testing protocols. 1. TIA/EIA-568-B.1 requires that a minimum of two telecommunications outlet/connectors be installed for each work area. 2. Horizontal cabling shall contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications outlet/connector. 3. Bridged taps and splices shall not be installed in the horizontal cabling. 4. Splitters shall not be installed as part of the optical fiber cabling. B. A work area is approximately 9.3 sq. m, and includes the components that extend from the telecommunications outlet/connectors to the station equipment. C. The maximum allowable horizontal cable length is 90 m. This maximum allowable length does not include an allowance for the length of 4.9 m to the workstation equipment. The maximum allowable length does not include an allowance for the length of 4.9 m in the horizontal crossconnect. 1.06 PERFORMANCE REQUIREMENTS A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard. 1.07 SUBMITTALS A. Product Data: For each type of product indicated. 1. For coaxial cable, include the following installation data for each type used: a. Nominal OD. b. Minimum bending radius. c. Maximum pulling tension. 2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software. 3. Cabling administration drawings and printouts. 4. Wiring diagrams to show typical wiring schematics, including the following: a. Cross-connects. b. Patch panels. c. Patch cords. 5. Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components. 6. Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following: a. Vertical and horizontal offsets and transitions. b. Clearances for access above and to side of cable trays. c. Vertical elevation of cable trays above the floor or bottom of ceiling structure. d. Load calculations to show dead and live loads as not exceeding manufacturer's rating for tray and its support elements. B. Field quality-control reports. C. Maintenance Data: For splices and connectors to include in maintenance manuals. D. Software and Firmware Operational Documentation: 1. Software operating and upgrade manuals. 2. Program Software Backup: On magnetic media or compact disk, complete with data files. 3. Device address list. E738-2 4. Printout of software application and graphic screens. 1.08 QUALITY ASSURANCE A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff. 1. Layout Responsibility: Preparation of Shop Drawings Cabling Administration Drawings, and field testing program development by an RCDD. B. Testing Agency Qualifications: An NRTL. 1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD to supervise onsite testing. C. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. E. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A. F. Grounding: Comply with ANSI-J-STD-607-A. 1.09 DELIVERY, STORAGE, AND HANDLING A. Test cables upon receipt at Project site. 1. Test optical fiber cables to determine the continuity of the strand end to end. 2. Test each pair of UTP cable for open and short circuits. 1.10 PROJECT CONDITIONS A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. 1.11 COORDINATION A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers. B. Coordinate telecommunications outlet/connector locations with location of power receptacles at each work area. 1.12 SOFTWARE SERVICE AGREEMENT A. Technical Support: Beginning with Substantial Completion, provide software support for two years. B. Upgrade Service: Update software to latest version at Project completion. Install and program software upgrades that become available within two years from date of Substantial Completion. Upgrading software shall include operating system. Upgrade shall include new or revised licenses for use of software. PART 2 - PRODUCTS 2.01 PATHWAYS A. General Requirements: Comply with TIA/EIA-569-A. B. Cable Support: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable. 1. Support brackets with cable tie slots for fastening cable ties to brackets. 2. Lacing bars, spools, J-hooks, and D-rings. 3. Straps and other devices. C. Cable Trays: 1. Cable Tray Materials: Metal, suitable for indoors, and protected against corrosion by hot-dip galvanizing, complying with ASTM A 123/A 123M, Grade 0.55, not less than 0.055 mm thick. E738-3 a. Basket Cable Trays: 150 mm wide and 50 mm deep. Wire mesh spacing shall not exceed 50 by 100 mm. b. Through Cable Trays: Nominally 150 mm wide. c. Ladder Cable Trays: Nominally 300 mm wide. d. Channel Cable Trays: One-piece construction, nominally 100 mm wide. Slot spacing shall not exceed 115 mm o.c. e. Solid-Bottom Cable Trays: One-piece construction, nominally 305 mm wide. D. Conduit and Boxes: Comply with requirements in Division 16 Section "Raceways and Boxes." Flexible metal conduit shall not be used. 1. Outlet boxes shall be no smaller than 50 mm) wide, 75 mm high, and 64 mm deep. 2.02 BACKBOARDS A. Backboards: Plywood, fire-retardant treated, 19 by 1220 by 2440 mm. Comply with requirements in Section "Rough Carpentry" for plywood backing panels. 2.03 UTP CABLE A. Description: 100-ohm, 4-pair UTP, formed into 25-pair, binder groups covered with a blue thermoplastic jacket. 1. Comply with ICEA S-90-661 for mechanical properties. 2. Comply with TIA/EIA-568-B.1 for performance specifications. 3. Comply with TIA/EIA-568-B.2, Category 6a. 4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types: 2.04 UTP CABLE HARDWARE A. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568- B.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher. B. Connecting Blocks: 110-style IDC for Category 6a. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated. C. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables. 1. Number of Jacks per Field: One for each four-pair conductor group of indicated cables, plus spares and blank positions adequate to suit specified expansion criteria. D. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals. E. Patch Cords: Factory-made, four-pair cables in 48-inch, 1200-mm lengths; terminated with eightposition modular plug at each end. 1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6a performance. Patch cords shall have latch guards to protect against snagging. 2.05 OPTICAL FIBER CABLE A. Description: Multimode, 50/125-micrometer, 4-fiber, nonconductive, tight buffer, optical fiber cable. 1. Comply with ICEA S-83-596 for mechanical properties. 2. Comply with TIA/EIA-568-B.3 for performance specifications. 3. Comply with TIA/EIA-492AAAA-B for detailed specifications. 4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444, UL 1651, and NFPA 70 for the following types: 5. Maximum Attenuation: 3.50 dB/km at 850 nm; 1.5 dB/km at 1300 nm. 6. Minimum Modal Bandwidth: 160 MHz-km at 850 nm; 500 MHz-km at 1300 nm. B. Jacket: E738-4 1. Jacket Color: Aqua for 50/125-micrometer cable. 2. Cable cordage jacket, fiber, unit, and group color shall be according to TIA/EIA-598-B. 3. Imprinted with fiber count, fiber type, and aggregate length at regular intervals not to exceed 1000 mm. 2.06 OPTICAL FIBER CABLE HARDWARE A. Patch Cords: Factory-made, dual-fiber cables in 900-mm lengths. B. Cable Connecting Hardware: 1. Comply with Optical Fiber Connector Intermateability Standards (FOCIS) specifications of TIA/EIA-604-2, TIA/EIA-604-3-A, and TIA/EIA-604-12. Comply with TIA/EIA-568-B.3. 2. Quick-connect, simplex and duplex, Type SC or Type ST Connectors. Insertion loss not more than 0.75 dB. 3. Type SFF connectors may be used in termination racks, panels, and equipment packages. 2.07 COAXIAL CABLE A. Cable Characteristics: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 Db maximum from 7 to 806 MHz. B. RG-6/U: NFPA 70, Type CATV or CM. 1. No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation. 2. Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid. 3. Jacketed with black PVC or PE. 4. Suitable for indoor installations. 2.08 COAXIAL CABLE HARDWARE A. Coaxial-Cable Connectors: Type BNC, 75 ohms. 2.09 CONSOLIDATION POINTS A. Description: Consolidation points shall comply with requirements for cable connecting hardware. 1. Mounting: Recessed in ceiling or Wall. 2. NRTL listed as complying with UL 50 and UL 1863. 3. When installed in plenums used for environmental air, NRTL listed as complying with UL 2043. B. Description: MUTOAs shall meet the requirements for cable connecting hardware. 1. Mounting: Recessed in ceiling or Wall. 2. NRTL listed as complying with UL 50 and UL 1863. 3. Label shall include maximum length of work area cords, based on TIA/EIA-568-B.1. 4. When installed in plenums used for environmental air, NRTL listed as complying with UL 2043. 2.10 TELECOMMUNICATIONS OUTLET/CONNECTORS A. Jacks: 100-ohm, balanced, twisted-pair connector; four-pair, eight-position modular. Comply with TIA/EIA-568-B.1. B. Workstation Outlets: one or two-port-connector assemblies mounted in multigang faceplate. 2.11 GROUNDING A. Comply with requirements in Division 16 Section "Grounding and Bonding" for grounding conductors and connectors. B. Comply with ANSI-J-STD-607-A. 2.12 IDENTIFICATION PRODUCTS A. Comply with TIA/EIA-606-A and UL 969 for labeling materials, including label stocks, laminating adhesives, and inks used by label printers. B. Comply with requirements in Division 16 Section "Electrical Identification." E738-5 2.13 CABLE MANAGEMENT SYSTEM A. Description: Computer-based cable management system, with integrated database capabilities. B. Document physical characteristics by recording the network, TIA/EIA details, and connections between equipment and cable. C. Information shall be presented in database view. D. System shall interface with the following testing and recording devices: 1. Direct upload tests from circuit testing instrument into the personal computer. 2. Direct download circuit labeling into labeling printer. 2.14 SOURCE QUALITY CONTROL A. Factory test UTP and optical fiber cables on reels according to TIA/EIA-568-B.1. B. Factory test UTP cables according to TIA/EIA-568-B.2. C. Factory test multimode optical fiber cables according to TIA/EIA-526-14-A and TIA/EIA-568-B.3. D. Factory-sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the frequency response or attenuation over frequency, of a cable by generating a voltage whose frequency is varied through the specified frequency range and graphing the results. E. Cable will be considered defective if it does not pass tests and inspections. F. Prepare test and inspection reports. PART 3 – EXECUTION 3.01 ENTRANCE FACILITIES A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider. 3.02 WIRING METHODS A. Wiring Method: Install cables in raceways and cable trays except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, in attics, and in gypsum board partitions where unenclosed wiring method may be used. Conceal raceway and cables except in unfinished spaces. 1. Install plenum cable in environmental air spaces, including plenum ceilings. 2. Comply with requirements for raceways and boxes specified in Division 16 Section "Raceways and Boxes." B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible. C. Wiring within Enclosures: Bundle, lace, and train cables to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. 3.03 INSTALLATION OF PATHWAYS A. Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A-7. B. Comply with requirements for demarcation point, pathways, cabinets, and racks specified in Division 16 Section "Communications Equipment Room Fittings." Drawings indicate general arrangement of pathways and fittings. C. Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends between pull points. D. Comply with requirements in Division 16 Section "Raceways and Boxes" for installation of conduits and wireways. E. Install manufactured conduit sweeps and long-radius elbows whenever possible. F. Pathway Installation in Communications Equipment Rooms: 1. Position conduit ends adjacent to a corner on backboard where a single piece of plywood is installed, or in the corner of room where multiple sheets of plywood are installed around perimeter walls of room. 2. Install cable trays to route cables if conduits cannot be located in these positions. 3. Secure conduits to backboard when entering room from overhead. 4. Extend conduits 76 mm above finished floor. E738-6 5. Install metal conduits with grounding bushings and connect with grounding conductor to grounding system. G. Backboards: Install backboards with 2440 mm dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints. 3.04 INSTALLATION OF CABLES A. Comply with NECA 1. B. General Requirements for Cabling: 1. Comply with TIA/EIA-568-B.1. 2. Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices." 3. Install 110-style IDC termination hardware unless otherwise indicated. 4. MUTOA shall not be used as a cross-connect point. 5. Consolidation points may be used only for making a direct connection to telecommunications outlet/connectors: a. Do not use consolidation point as a cross-connect point, as a patch connection, or for direct connection to workstation equipment. b. Locate consolidation points for UTP at least 15 m from communications equipment room. 6. Terminate conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, crossconnects, and patch panels. 7. Cables may not be spliced. Secure and support cables at intervals not exceeding 760 mm and not more than 150 mm from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 8. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 9. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices" Chapter. Install lacing bars and distribution spools. 10. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 11. Cold-Weather Installation: Bring cable to room temperature before drilling. Heat lamps shall not be used for heating. 12. In the communications equipment room, install a 3 m long service loop on each end of cable. 13. Pulling Cable: Comply with BICSI ITSIM, Ch. 4, and “Pulling Cable." Monitor cable pull tensions. C. UTP Cable Installation: 1. Comply with TIA/EIA-568-B.2. 2. Do not untwist UTP cables more than 12 mm from the point of termination to maintain cable geometry. D. Optical Fiber Cable Installation: 1. Comply with TIA/EIA-568-B.3. 2. Cable may be terminated on connecting hardware that is rack or cabinet mounted. E. Open-Cable Installation: 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. 2. Suspend UTP cable not in a wireway or pathway a minimum of 200 mm above ceilings by cable supports not more than 1524 mm apart. 3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. F. Installation of Cable Routed Exposed under Raised Floors: 1. Install plenum-rated cable only. 2. Install cabling after the flooring system has been installed in raised floor areas. 3. Coil cable 1800 mm long not less than 300 mm in diameter below each feed point. G. Outdoor Coaxial Cable Installation: 1. Install outdoor connections in enclosures complying with NEMA 250, Type 4X. Install corrosionresistant connectors with properly designed O-rings to keep out moisture. 2. Attach antenna lead-in cable to support structure at intervals not exceeding 915 mm. H. Group connecting hardware for cables into separate logical fields. E738-7 I. Separation from EMI Sources: 1. Comply with BICSI TDMM and TIA/EIA-569-A for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment. 2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm). b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches (300 mm). c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (610 mm). 3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm). b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches (150 mm). c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm). 4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: No requirement. b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches (76 mm). c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm). 5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches (1200 mm). 6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm). 3.05 FIRESTOPPING A. Comply with requirements in Division 7 Section "Penetration Fire stopping." B. Comply with TIA/EIA-569-A, Annex A, "Firestopping." C. Comply with BICSI TDMM, "Firestopping Systems" Article. 3.06 GROUNDING A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" chapter. B. Comply with ANSI-J-STD-607-A. C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 50 mm clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground. D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor. 3.07 IDENTIFICATION A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification. 1. Administration Class: 2. 2. Color-code cross-connect fields. Apply colors to voice and data service backboards, connections, covers, and labels. B. Using cable management system software specified in Part 2, develop Cabling Administration Drawings for system identification, testing, and management. Use unique, alphanumeric designation for each cable and label cable, jacks, connectors, and terminals to which it connects with same designation. At completion, cable and asset management software shall reflect as-built conditions. C. Comply with requirements of "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label. D. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 2 level of administration. E. Cable Schedule: Post in prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project. E738-8 F. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, backbone pathways and cables, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. Follow convention of TIA/EIA-606A. Furnish electronic record of all drawings, in software and format selected by Owner. G. Cable and Wire Identification: 1. Label each cable within 100 mm of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated. 2. Each wire connected to building-mounted devices is not required to be numbered at device if color of wire is consistent with associated wire connected and numbered within panel or cabinet. 3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 4.5 m. 4. Label each terminal strip and screw terminal in each cabinet, rack, or panel. a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group being extended from a panel or cabinet to a building-mounted device shall be identified with name and number of particular device as shown. b. Label each unit and field within distribution racks and frames. 5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service. 6. Uniquely identify and label work area cables extending from the MUTOA to the work area. These cables may not exceed the length stated on the MUTOA label. H. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA- 606-A. 1. Cables use flexible vinyl or polyester that flex as cables are bent. 3.08 FIELD QUALITY CONTROL A. Testing Agency: Engage a qualified testing agency to perform tests and inspections. B. Perform tests and inspections. C. Tests and Inspections: 1. Visually inspect UTP and optical fiber cable jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-B.1. 2. Visually confirm Category 6, marking of outlets, cover plates, outlet/connectors, and patch panels. 3. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. 4. Test UTP backbone copper cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection. a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.2. Perform tests with a tester that complies with performance requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. 5. Optical Fiber Cable Tests: a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.1. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. b. Link End-to-End Attenuation Tests: 1) Horizontal and multimode backbone link measurements: Test at 850 or 1300 nm in 1 direction according to TIA/EIA-526-14-A, Method B, One Reference Jumper. 2) Attenuation test results for backbone links shall be less than 2.0 dB. Attenuation test results shall be less than that calculated according to equation in TIA/EIA-568-B.1. 6. UTP Performance Tests: E738-9 a. Test for each outlet and MUTOA. Perform the following tests according to TIA/EIA-568-B.1 and TIA/EIA-568-B.2: 1) Wire map. 2) Length (physical vs. electrical, and length requirements). 3) Insertion loss. 4) Near-end crosstalk (NEXT) loss. 5) Power sum near-end crosstalk (PSNEXT) loss. 6) Equal-level far-end crosstalk (ELFEXT). 7) Power sum equal-level far-end crosstalk (PSELFEXT). 8) Return loss. 9) Propagation delay. 10) Delay skew. 7. Optical Fiber Cable Performance Tests: Perform optical fiber end-toend link tests according to TIA/EIA568-B.1 and TIA/EIA-568-B.3. 8. Coaxial Cable Tests: Conduct tests according to Section "Master Antenna Television System." 9. Final Verification Tests: Perform verification tests for UTP and optical fiber systems after the complete communications cabling and workstation outlet/connectors are installed. a. Voice Tests: These tests assume that dial tone service has been installed. Connect to the network interface device at the demarcation point. Go off-hook and listen and receive a dial tone. If a test number is available, make and receive a local, long distance, and digital subscription line telephone call. b. Data Tests: These tests assume the Information Technology Staff has a network installed and is available to assist with testing. Connect to the network interface device at the demarcation point. Log onto the network to ensure proper connection to the network. D. Document data for each measurement. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred from the instrument to the computer, saved as text files, and printed and submitted. E. End-to-end cabling will be considered defective if it does not pass tests and inspections. F. Prepare test and inspection reports. 3.09 DEMONSTRATION A. Train Owner's maintenance personnel in cable-plant management operations, including changing signal pathways for different workstations, rerouting signals in failed cables, and keeping records of cabling assignments and revisions when extending wiring to establish new workstation outlets. ---END--- E738-10 SECTION E739 COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 – GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. 1.02 REFERENCES A. EIA/TIA 568 (Electronic Industries Association/Telecommunications Industries Association) Commercial Building Telecommunication Wiring Standard. B. EIA/TIA 569 (Electronic Industries Association/Telecommunications Industries Association)Commercial Building Standard for Telecommunications Pathways and Spaces. C. NETA ATS (International Electrical Testing Association) - Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems. 1.03 SUMMARY A. Section Includes: 1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Telecommunications service entrance pathways. 5. Grounding. 1.04 DEFINITIONS A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. B. BICSI: Building Industry Consulting Service International. C. Channel Cable Tray: A fabricated structure consisting of a one-piece, ventilated bottom or solidbottom channel not exceeding 152 mm in width. D. Ladder Cable Tray: A fabricated structure consisting of two longitudinal side rails connected by individual transverse members (rungs). E. LAN: Local area network. F. RCDD: Registered Communications Distribution Designer. G. Solid-Bottom or Non-ventilated Cable Tray: A fabricated structure consisting of a bottom without ventilation openings within integral or separate longitudinal side rails. H. Trough or Ventilated Cable Tray: A fabricated structure consisting of integral or separate longitudinal rails and a bottom having openings sufficient for the passage of air and using 75 percent or less of the plan area of the surface to support cables. 1.05 PERFORMANCE REQUIREMENTS A. Seismic Performance: Floor-mounted cabinets and cable pathways shall withstand the effects of earthquake motions determined according to SEI/ASCE 7 1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event." 1.06 SUBMITTALS A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for equipment racks and cabinets. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. E739-1 B. Shop Drawings: For communications equipment room fittings. Include plans, elevations, sections, details, and attachments to other work. 1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 2. Equipment Racks and Cabinets: Include workspace requirements and access for cable connections. 3. Grounding: Indicate location of grounding bus bar and its mounting detail showing standoff insulators and wall mounting brackets. 1.07 QUALITY ASSURANCE A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. C. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A. D. Grounding: Comply with ANSI-J-STD-607-A. 1.08 PROJECT CONDITIONS A. Environmental Limitations: Do not deliver or install equipment frames and cable trays until spaces are enclosed and weathertight, wet work in spaces is complete and dry, and work above ceilings is complete. 1.09 COORDINATION A. Coordinate layout and installation of communications equipment with Owner's telecommunications and LAN equipment and service suppliers. Coordinate service entrance arrangement with local exchange carrier. 1. Meet jointly with telecommunications and LAN equipment suppliers, local exchange carrier representatives, and Owner to exchange information and agree on details of equipment arrangements and installation interfaces. 2. Record agreements reached in meetings and distribute them to other participants. 3. Adjust arrangements and locations of distribution frames, cross-connects, and patch panels in equipment rooms to accommodate and optimize arrangement and space requirements of telephone switch and LAN equipment. 4. Adjust arrangements and locations of equipment with distribution frames, cross-connects, and patch panels of cabling systems of other communications, electronic safety and security, and related systems that share space in the equipment room. B. Coordinate location of power raceways and receptacles with locations of communications equipment requiring electrical power to operate. PART 2 – PRODUCTS 2.01 PATHWAYS A. General Requirements: Comply with TIA/EIA-569-A. B. Cable Support: NRTL labeled. Cable support brackets shall be designed to prevent degradation of cable performance and pinch points that could damage cable. Cable tie slots fasten cable ties to brackets. 1. Comply with NFPA 70 and UL 2043 for fire-resistant and low-smoke producing characteristics. 2. Support brackets with cable tie slots for fastening cable ties to brackets. 3. Lacing bars, spools, J-hooks, and D-rings. 4. Straps and other devices. C. Cable Trays: E739-2 1. Cable Tray Materials: Metal, suitable for indoors and protected against corrosion by hot-dip galvanizing, complying with ASTM A 123/A 123M, Grade 0.55, not less than 0.05mm thick. a. Basket Cable Trays: 150 mm wide and 50 mm deep. Wire mesh spacing shall not exceed 50 by 100 mm. b. Trough Cable Trays: Nominally 150 mm wide. c. Ladder Cable Trays: Nominally 300 mm wide. d. Channel Cable Trays: One-piece construction, nominally 100 mm wide. Slot spacing shall not exceed 115 mm o.c. e. Solid-Bottom Cable Trays: One-piece construction, 305 mm wide. D. Conduit and Boxes: Comply with requirements in Division 16 Section "Raceways and Boxes." Flexible metal conduit shall not be used. 2.02 BACKBOARDS A. Backboards: Plywood, fire-retardant treated, 19 by 1220 by 2440 mm. Comply with requirements for plywood backing panels specified in Section "Rough Carpentry." 2.03 EQUIPMENT FRAMES A. General Frame Requirements: 1. Distribution Frames: Freestanding and wall-mounting, modular-steel units designed for telecommunications terminal support and coordinated with dimensions of units to be supported. 2. Module Dimension: Width compatible with EIA 310 standard, 19-inch panel mounting. 3. Finish: Manufacturer's standard, baked-polyester powder coat. B. Floor-Mounted Racks: Modular-type, steel or aluminum construction. 1. Vertical and horizontal cable management channels, top and bottom cable troughs, grounding lug, and a power strip. 2. Baked-polyester powder coat finish. C. Modular Freestanding Cabinets: 1. Removable and lockable side panels. 2. Hinged and lockable front and rear doors. 3. Adjustable feet for leveling. 4. Screened ventilation openings in the roof and rear door. 5. Cable access provisions in the roof and base. 6. Grounding bus bar. 7. 260-L/s fan with filter. 8. Power strip. 9. Baked-polyester powder coat finish. 10. All cabinets keyed alike. D. Modular Wall Cabinets: 1. Wall mounting. 2. Steel or aluminum construction. 3. Treated to resist corrosion. 4. Lockable front and rear doors. 5. Louvered side panels. 6. Cable access provisions top and bottom. 7. Grounding lug. 8. 118-L/s fan. 9. Power strip. 10. All cabinets keyed alike. E. Cable Management for Equipment Frames: 1. Metal, with integral wire retaining fingers. 2. Baked-polyester powder coat finish. 3. Vertical cable management panels shall have front and rear channels, with covers. E739-3 4. Provide horizontal crossover cable manager at the top of each relay rack, with a minimum height of two rack units each. 2.04 POWER STRIPS A. Power Strips: Comply with UL 1363. 1. Rack mounting. 2. Six, 16-A, 230-V ac receptacles, cord connected with 4.5m line cord and 13 kA. 3. LED indicator lights for power and protection status. 4. LED indicator lights for reverse polarity and open outlet ground. 5. Rocker-type on-off switch, illuminated when in on position. 6. Peak Single-Impulse Surge Current Rating: 13 kA per phase. 7. Protection modes shall be line to neutral, line to ground, and neutral to ground. UL 1449 clamping voltage for all 3 modes shall be not more than 330 V. 2.05 GROUNDING A. Comply with requirements in Division 16 Section "Grounding and Bonding" for grounding conductors and connectors. B. Telecommunications Main Bus Bar: 1. Connectors: Mechanical type, cast silicon bronze, solderless compression - type wire terminals, and long-barrel, two-bolt connection to ground bus bar. 2. Ground Bus Bar: Copper, minimum 6 mm thick by 100 mm wide with 7.14- mm holes spaced 28 mm apart. 3. Stand-Off Insulators: Comply with UL 891 for use in switchboards, 600 V. Lexan or PVC, impulse tested at 5000 V. C. Comply with ANSI-J-STD-607-A. 2.06 LABELING A. Comply with TIA/EIA-606-A and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers. PART 3 – EXECUTION 3.01 ENTRANCE FACILITIES A. Install underground pathways complying with recommendations in TIA/EIA-569-A, "Entrance Facilities" Article. 1. Install underground entrance pathway complying with Division 16 Section "Raceways and Boxes." 3.02 INSTALLATION A. Comply with NECA 1. B. Comply with BICSI TDMM for layout and installation of communications equipment rooms. C. Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A-7. D. Bundle, lace, and train conductors and cables to terminal points without exceeding manufacturer's limitations on bending radii. Install lacing bars and distribution spools. 3.03 FIRESTOPPING A. Comply with requirements in Division 7 Section "Through-Penetration Firestop Systems." B. Comply with TIA/EIA-569-A, Annex A, "Firestopping." C. Comply with BICSI TDMM, "Firestopping Systems" Article. 3.04 GROUNDING E739-4 A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" Chapter. B. Comply with ANSI-J-STD-607-A. C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 50-mm clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground. D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor. 1. Bond the shield of shielded cable to the grounding bus bar in communications rooms and spaces. 3.05 IDENTIFICATION A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements in Division 16 Section "Electrical Identification." B. Comply with requirements in Division 9 Section "Interior Painting" for painting backboards. For fire-resistant plywood, do not paint over manufacturer's label. C. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 2 level of administration. D. Labels shall be preprinted or computer-printed type. ---END--- E739-5 SECTION E740 COMMUNICATIONS BACKBONE CABLING PART 1 – GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. 1.02 REFERENCES A. EIA/TIA 568 (Electronic Industries Association/Telecommunications Industries Association) Commercial Building Telecommunication Wiring Standard. B. EIA/TIA 569 (Electronic Industries Association/Telecommunications Industries Association)Commercial Building Standard for Telecommunications Pathways and Spaces. C. NETA ATS (International Electrical Testing Association) - Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems. 1.03 SUMMARY A. Section Includes: 1. Pathways. 2. UTP cable. 3. 50/125-micrometer, optical fiber cabling. 4. Coaxial cable. 5. Cable connecting hardware, patch panels, and cross-connects. 6. Cabling identification products. B. Related Sections: 1. Division 16 Section "Conductors and Cables for Electronic Safety and Security" for voice and data cabling associated with system panels and devices. 1.04 DEFINITIONS A. BICSI: Building Industry Consulting Service International. B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. C. EMI: Electromagnetic interference. D. IDC: Insulation displacement connector. E. LAN: Local area network. F. RCDD: Registered Communications Distribution Designer. G. UTP: Unshielded twisted pair. 1.05 BACKBONE CABLING DESCRIPTION A. Backbone cabling system shall provide interconnections between communications equipment rooms, main terminal space, and entrance facilities in the telecommunications cabling system structure. Cabling system consists of backbone cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for backbone-to-backbone crossconnection. B. Backbone cabling cross-connects may be located in communications equipment rooms or at entrance facilities. Bridged taps and splitters shall not be used as part of backbone cabling. 1.06 PERFORMANCE REQUIREMENTS A. General Performance: Backbone cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard. 1.07 SUBMITTALS E740-1 A. Product Data: For each type of product indicated. 1. For coaxial cable, include the following installation data for each type used: a. Nominal OD. b. Minimum bending radius. c. Maximum pulling tension. B. Shop Drawings: 1. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software. 2. Cabling administration drawings and printouts. 3. Wiring diagrams to show typical wiring schematics including the following: a. Cross-connects. b. Patch panels. c. Patch cords. 4. Cross-connects and patch panels. Detail mounting assemblies, and show elevations and physical relationship between the installed components. 5. Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following: a. Vertical and horizontal offsets and transitions. b. Clearances for access above and to side of cable trays. c. Vertical elevation of cable trays above the floor or bottom of ceiling structure. d. Load calculations to show dead and live loads as not exceeding manufacturer's rating for tray and its support elements. C. Qualification Data: For qualified layout technician, installation supervisor, and field inspector. D. Source quality-control reports. E. Field quality-control reports. F. Maintenance Data: For splices and connectors to include in maintenance manuals. G. Software and Firmware Operational Documentation: 1. Software operating and upgrade manuals. 2. Program Software Backup: On magnetic media or compact disk, complete with data files. 3. Device address list. 4. Printout of software application and graphic screens. 1.08 QUALITY ASSURANCE A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff as an RCCD. B. Testing Agency Qualifications: An NRTL. 1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD to supervise onsite testing. C. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A. D. Grounding: Comply with ANSI-J-STD-607-A. E. Products: NRTL listed and labeled. 1.09 DELIVERY, STORAGE, AND HANDLING A. Test cables upon receipt at Project site. 1. Test optical fiber cable to determine the continuity of the strand end to end 2. Test optical fiber cable while on reels. Use an optical time domain reflectometer to verify the cable length and locate cable defects, splices, and connector, including the loss value of each. Retain test data and include the record in maintenance data. 3. Test each pair of UTP cable for open and short circuits. 1.10 PROJECT CONDITIONS A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining E740-2 ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period. 1.11 COORDINATION A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers. PART 2 - PRODUCTS 2.01 PATHWAYS A. General Requirements: Comply with TIA/EIA-569-A. B. Cable Support: NRTL labeled for support of Category 6a cabling, designed to prevent degradation of cable performance and pinch points that could damage cable. 1. Support brackets with cable tie slots for fastening cable ties to brackets. 2. Lacing bars, spools, J-hooks, and D-rings. 3. Straps and other devices. C. Cable Trays: 1. Cable Tray Material: Metal, suitable for indoors, and protected against corrosion by hot-dip galvanizing, complying with ASTM A 123/A 123M, Grade 0.55, not less than 0.055 mm thick. a. Basket Cable Trays: 150 mm wide and 50 mm deep. Wire mesh spacing shall not exceed 50 by 100 mm. b. Trough Cable Trays: Nominally 150 mm wide. c. Ladder Cable Trays: Nominally 900 mm wide. d. Channel Cable Trays: One-piece construction, nominally 100 mm wide. Slot spacing shall not exceed 115 mm o.c. e. Solid-Bottom Cable Trays: One-piece construction, nominally 305 mm wide. D. Conduit and Boxes: Comply with requirements in Division 16 Section "Raceways and Boxes. "Flexible metal conduit shall not be used. 1. Outlet boxes shall be no smaller than 50 mm wide, 75 mm high and 64 mm deep. 2.02 BACKBOARDS A. Backboards: Plywood, fire-retardant treated, 19 by 1220 by 2440 mm. Comply with requirements in Section "Rough Carpentry" for plywood backing panels. 2.03 UTP CABLE A. Description: 100-ohm, 100 pair UTP, formed into 25-pair binder groups covered with a gray thermoplastic jacket. 1. Comply with ICEA S-90-661 for mechanical properties. 2. Comply with TIA/EIA-568-B.1 for performance specifications. 3. Comply with TIA/EIA-568-B.2, Category 6a. a. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70. 2.04 UTP CABLE HARDWARE A. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568- B.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher. B. Connecting Blocks: 110-style IDC for Category 6a. Provide blocks for the number of cables terminated on the block, plus 25 percent spare. Integral with connector bodies, including plugs and jacks where indicated. E740-3 C. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables. 1. Number of Jacks per Field: One for each four-pair D. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals. E. Patch Cords: Factory-made, 4-pair cables in 1200-mm lengths; terminated with 8- position modular plug at each end. 1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure Category 6a performance. Patch cords shall have latch guards to protect against snagging. 2.05 OPTICAL FIBER CABLE A. Description: Multimode, 50/125-micrometer, 4-fiber, nonconductive tight buffer, optical fiber cable. 1. Comply with TIA/EIA-492AAAA-A for detailed specifications. 2. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444, UL 1651, and NFPA 70 for the following types: B. Jacket: 1. Jacket Color: Aqua for 50/125-micrometer cable. 2. Cable cordage jacket, fiber, unit, and group color shall be according to TIA/EIA-598-B. 3. Imprinted with fiber count, fiber type, and aggregate length at regular intervals not to exceed 1000 mm 2.06 OPTICAL FIBER CABLE HARDWARE A. Patch Cords: Factory-made, dual-fiber cables in 900-mm lengths. B. Cable Connecting Hardware: 1. Comply with Optical Fiber Connector Intermateability Standards (FOCIS) specifications of TIA/EIA-604 2, TIA/EIA-604-3-A, and TIA/EIA-604-12. Comply with TIA/EIA-568-B.3. 2. Quick-connect, simplex and duplex, Type SC or Type ST connectors. Insertion loss not more than 0.75 dB. 3. Type SFF connectors may be used in termination racks, panels, and equipment packages. 2.07 COAXIAL CABLE A. General Coaxial Cable Requirements: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz. B. RG-11/U: NFPA 70, Type CATV. 1. No. 14 AWG, solid, copper-covered steel conductor. 2. Gas-injected, foam-PE insulation. 3. Double shielded with 100 percent aluminum polyester tape and 60 percent aluminum braid. 4. Jacketed with sunlight-resistant, black PVC or PE. 5. Suitable for outdoor installations in ambient temperatures ranging from minus 40 to plus 85 deg C. 6. NFPA and UL compliance, listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 1655 and with NFPA 70, "Radio and Television Equipment" and "Community Antenna Television and Radio Distribution" Articles. 2.08 COAXIAL CABLE HARDWARE A. Coaxial-Cable Connectors: Type BNC, 75 ohms. 2.09 GROUNDING A. Comply with requirements in Division 16 Section "Grounding and Bonding" for grounding conductors and connectors. B. Comply with ANSI-J-STD-607-A. E740-4 2.10 IDENTIFICATION PRODUCTS A. Comply with TIA/EIA-606-A and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers. 2.11 MANUFACTURERS A. Approved Fiber-Optic cable manufacturers are: AMP Berk-Tek Corning (or approved equivalent). B. Approved Category 6a 4-pair UTP copper cable manufacturers are: AMP Cat-6a Belden Data Twist 6a Berk-Tek LANmark-1000 (or approved equivalent). C. Approved coaxial cable manufacturers are : Belden CommScope (or approved equivalent). D. The cable manufacturer(s) must be ISO 9001 Registed. E. Approved Equipment manufacturer is Chatsworth (or approved equivalent). F. Approved components Manufacturers are : AMP Ortronics Leviton (or approved equivalent). PART 3 – EXECUTION 3.01 ENTRANCE FACILITIES A. Coordinate backbone cabling with the protectors and demarcation point provided by communications service provider. 3.02 WIRING METHODS A. Wiring Method: Install cables in raceways and cable trays except within consoles, cabinets, desks, and counters except in accessible ceiling spaces and attics. Conceal raceway and cables except in unfinished spaces. 1. Install plenum cable in environmental air spaces, including plenum ceilings. 2. Comply with requirements for raceways and boxes specified in Section "Raceways and Boxes." B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible. C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. 3.03 INSTALLATION OF PATHWAYS A. Cable Trays: Comply with NEMA VE 2 and TIA/EIA-569-A. B. Comply with requirements for demarcation point, pathways, cabinets, and racks specified in Section E739 "Communications Equipment Room Fittings." Drawings indicate general arrangement of pathways and fittings. C. Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends between pull points. D. Comply with requirements in Division 16 Section "Raceways and Boxes" for installation of conduits and wireways. E. Install manufactured conduit sweeps and long-radius elbows whenever possible. F. Pathway Installation in Communications Equipment Rooms: 1. Position conduit ends adjacent to a corner on backboard where a single piece of plywood is installed, or in the corner of room where multiple sheets of plywood are installed around perimeter walls of room. 2. Install cable trays to route cables if conduits cannot be located in these positions. 3. Secure conduits to backboard when entering room from overhead. 4. Extend conduits 76 mm above finished floor. 5. Install metal conduits with grounding bushings and connect with grounding conductor to grounding system. E740-5 G. Backboards: Install backboards with 2440-mm dimension vertical. Butt adjacent sheets tightly, and form smooth gap-free corners and joints. 3.04 INSTALLATION OF CABLES A. General Requirements for Cabling: 1. Comply with TIA/EIA-568-B.1. 2. Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices." 3. Install 110-style IDC termination hardware unless otherwise indicated. 4. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. 5. Cables may not be spliced. Secure and support cables at intervals not exceeding 760 mm and not more than 150 mm from cabinets, boxes, fittings, outlets, racks, frames, and terminals. 6. Install lacing bars to restrain cables, to prevent straining connections, and to prevent bending cables to smaller radii than minimums recommended by manufacturer. 7. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices" Chapter. Use lacing bars and distribution spools. 8. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation and replace it with new cable. 9. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating. 10. In the communications equipment room, install a 3-m long service loop on each end of cable. 11. Pulling Cable: Comply with BICSI ITSIM, Ch. 4, "Pulling Cable." Monitor cable pull tensions. B. UTP Cable Installation: 1. Comply with TIA/EIA-568-B.2. 2. Do not untwist UTP cables more than 12 mm from the point of termination to maintain cable geometry. C. Optical Fiber Cable Installation: 1. Comply with TIA/EIA-568-B.3. 2. Cable may be terminated on connecting hardware that is rack or cabinet mounted. D. Open-Cable Installation: 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. 2. Suspend UTP cable not in a wireway or pathway, a minimum of 12 mm above ceilings by cable supports not more than 1524 mm apart. 3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. E. Installation of Cable Routed Exposed under Raised Floors: 1. Install plenum-rated cable only. 2. Install cabling after the flooring system has been installed in raised floor areas. 3. Coil cable 1800 mm long not less than 300 mm in diameter below each feed point. F. Outdoor Coaxial Cable Installation: 1. Install outdoor connections in enclosures complying with NEMA 250, Type 4X. Install corrosionresistant connectors with properly designed Orings to keep out moisture. 2. Attach antenna lead-in cable to support structure at intervals not exceeding 915 mm. G. Group connecting hardware for cables into separate logical fields. H. Separation from EMI Sources: 1. Comply with BICSI TDMM and TIA/EIA-569-A recommendations for separating unshielded copper voice and data communication cable from potential EMI sources, including electrical power lines and equipment. E740-6 2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 127 mm. b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 300 mm. c. Electrical Equipment Rating More Than 5 kVA: A minimum of 610 mm. 3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 610 mm. b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 150 mm. c. Electrical Equipment Rating More Than 5 kVA: A minimum of 300 mm. 4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: a. Electrical Equipment Rating Less Than 2 kVA: No requirement. b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 76 mm. c. Electrical Equipment Rating More Than 5 kVA: A minimum of 150 mm. 5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 1200 mm. 6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 127 mm. 3.05 FIRESTOPPING A. Comply with requirements in Section "Penetration Fire stopping." B. Comply with TIA/EIA-569-A, Annex A, "Firestopping." C. Comply with BICSI TDMM, "Firestopping Systems" Article. 3.06 GROUNDING A. Install grounding according to BICSI TDMM, "Grounding, Bonding, and Electrical Protection" Chapter. B. Comply with ANSI-J-STD-607-A. C. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall allowing at least 50-mm clearance behind the grounding bus bar. Connect grounding bus bar with a minimum No. 4 AWG grounding electrode conductor from grounding bus bar to suitable electrical building ground. D. Bond metallic equipment to the grounding bus bar, using not smaller than No. 6 AWG equipment grounding conductor. 3.07 IDENTIFICATION A. Identify system components, wiring, and cabling complying with TIA/EIA-606-A. Comply with requirements for identification specified in Division 16 Section "Electrical Identification." 1. Administration Class: 2 2. Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels. B. Comply with requirements in Division 9 Section "Interior Painting" for painting backboards. For fireresistant plywood, do not paint over manufacturer's label. C. Paint and label colors for equipment identification shall comply with TIA/EIA-606-A for Class 2 level of administration including optional identification requirements of this standard. D. Comply with requirements in Division 16 Section "Communications Horizontal Cabling" for cable and asset management software. E. Cable Schedule: Install in a prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project. F. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, backbone pathways and cables, entrance pathways and cables, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors. E740-7 G. Cable and Wire Identification: 1. Label each cable within including optional identification requirements of this standard of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated. 2. Each wire connected to building-mounted devices is not required to be numbered at device if color of wire is consistent with associated wire connected and numbered within panel or cabinet. 3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 4.5 m. 4. Label each terminal strip and screw terminal in each cabinet, rack, or panel. a. Individually number wiring conductors connected to terminal strips and identify each cable or wiring group being extended from a panel or cabinet to a building-mounted device with name and number of particular device as shown. b. Label each unit and field within distribution racks and frames. 5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service. H. Labels shall be preprinted or computer-printed type with printing area and font color that contrasts with cable jacket color but still complies with requirements in TIA/EIA 606-A, for the following: 1. Cables use flexible vinyl or polyester that flexes as cables are bent. 3.08 FIELD QUALITY CONTROL A. Testing Agency: Engage a qualified testing agency to perform tests and inspections. B. Perform tests and inspections. C. Tests and Inspections: 1. Visually inspect UTP and optical fiber jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with TIA/EIA-568-B.1. 2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components. 3. Optical Fiber Cable Tests: a. Test instruments shall meet or exceed applicable requirements in TIA/EIA-568-B.1. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration. b. Link End-to-End Attenuation Tests: 1) Horizontal and multimode backbone link measurements: Test at 850 or 1300 nm in 1 direction according to TIA/EIA-526-14-A, Method B, One Reference Jumper. 2) Attenuation test results for backbone links shall be less than 2.0 dB. Attenuation test results shall be less than that calculated according to equation in TIA/EIA-568-B.1. D. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similar to Table 10.1 in BICSI TDMM, or transferred from the instrument to the computer, saved as text files, and printed and submitted. E. Remove and replace cabling where test results indicate that they do not comply with specified requirements. F. End-to-end cabling will be considered defective if it does not pass tests and inspections. G. Prepare test and inspection reports. ---END--- E740-8