P H O T O C O N T R O L S
1
1
Throughout the United States and around the world
Dark To Light® (DTL) is recognized by the industry as a provider of high-quality, cost-effective electronic photocontrols to utility, commercial, and municipal customers.
High impact resistant UV stabilized polypropylene covers
High capacity MOV surge protection
Instantaneous turn on, allowing quick glove tests during installation
Hi-temp rated components
2-5 second off delay avoids nuisance switching caused by extraneous light
Cool running, reliable circuit electronics
Sealed relay
More utilities specify Dark To Light ® than any other brand of photocontrol for their superior performance and reliability.
Dark To Light’s patented designs meet or exceed all existing and proposed
ANSI standards.
Reliable electronic circuitry reduces day burners, which saves energy during peak periods and helps to reduce overall maintenance costs.
DTL photocontrols also are more efficient, which means they run cool, increasing the life of the control and photosensor.
Dark To Light ® is an established market leader with the breadth of product to cover all applications including roadway, area lighting, floodlights, security and residential.
FILTERED SILICON – DE SERIES
The DE Series photocontrols utilize premium components, a silicon light sensor and an infrared blocking filter to provide human eye spectral response and consistent turn-on night after night over the life of the control.
SILICON – DP SERIES
The DP Series photocontrols utilize premium components and silicon light sensors which resist long term drift of the turn-on level.
UTILITY PREFERRED – DP1704 / DP1707 SERIES
Utilizing the same premium components as all DP Series controls, the
DP1704 and DP1707 Series photocontrols are configured with the features most commonly selected by utility customers. High volume and limited variation allow for cost effective manufacturing of this extremely robust control.
LED – DSS SERIES
The DSS Series photocontrols were designed for the rigors of electronic and solid state lighting equipment, including LED, Electronic HID, and Induction luminaires.
DIAGNOSTIC – DD SERIES
The DD Series photocontrols were designed specifically to detect and disable cycling HPS lamps. Disabling the fixture when the lamp cycles extends the life of the starter and reduces replacement costs.
PART NIGHT – DPN SERIES
The DPN Series photocontrols were specifically designed to turn the light off halfway through the night to save energy and extend fixture life.
DX SERIES
The DX Series photocontrols are designed for general lighting applications.
DUX SERIES - UL LISTED
The DUX Series photocontrols are designed for general lighting applications.
CADMIUM SULFIDE – D SERIES
The D Series photocontrols utilize a Cadmium Sulfide (CdS) light sensor.
The CdS light sensors closely approximates the spectral response of the human eye without the use of an infrared filter.
BUTTON CONTROL – DBE SERIES
The DBE Series photocontrols are button style controls designed to be installed with lighting that does not use a NEMA receptacle.
SWIVEL CONTROL – DSW SERIES
The DSW Series photocontrol mounts to wall mounted luminaires and electrical boxes. It can swivel 360° around its base and 180° from front to back.
RETROFIT RECEPTACLE KIT – DUR103 SERIES
The DUR103 Series retrofit receptacle kit adapts a light fixture for use with a NEMA locking type photocontrol
SHORTING / OPEN CAPS – CAP SERIES
The CAP Series Shorting and Open caps are used with luminaires where lights are to be on continuously (shorting cap) or left off (open cap).
FREQUENTLY ORDERED NUMBERS*
DE124 1.5 TJ J50
DE124 1.5 TJBK J50
DE124 1.5 TJBR J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DE120 120 Volts (105-130)
DE124 120/240/277 Volts
(105-305)
DE347 347 Volts (300-400)
DE480 480 Volts (420-530)
TURN-ON LEVEL (ftc)
1.0
Energy Saver
1.5
ANSI Standard
2.6
IES Recommended
8.0
Metro-High Ambient
35 FAA
DESIGN DETAILS
• Silicon light sensor with infrared
blocking filter
• MOV surge protection rated for
320 Joules/9,500 Amps
• Sealed relay rated for a minimum
of 5,000 operations at full load
• Turn-Off light level is 1.5 times turn-On level
• 3.4 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene gasket,
brass legs, acrylic window
• Six-year warranty
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient, up to 90° interface per ANSI
• Power consumption: 0.5W
ADDITIONAL FEATURES
The Power-Up Delay option prevents the control from activating for 45-60 seconds after power is applied. This allows lamp warm-up time so the installer can verify the system is working properly.
It also allows for the system to be easily tested in the future. When power is shut off and then reconnected
(at the pole base) and the lamp turns on briefly and then turns off, it confirms that the control, fixture, lamp, and voltage supply are working correctly.
TIME DELAY/SURGE PROTECTION POWER-UP DELAY COVER COLOR
TJ 2-5 Second Turn-Off Delay
320J/9500 Amp MOV
(blank)
PD
Std. Operation
45-60 Sec.
Delay blank
BK
BR
ANSI Std. Color
Black
Brown
(See Color Chart on Pg. 11)
PACKAGE QTY.
J12 12 Units
J50 50 Units
FREQUENTLY ORDERED NUMBERS*
DP124 1.5 TJ J50
DP124 1.5 TJGY J50
DP124 1.5 TJBK J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
DESIGN DETAILS
• Silicon light sensor
• MOV surge protection rated for
320 Joules/9,500 Amps
• Sealed relay rated for a minimum of 5,000
operations at full load
• Turn-Off light level is 1.5 times turn-On level
• 3.4 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene gasket,
brass legs, acrylic window
• Six-year warranty
ADDITIONAL FEATURES
The Power-Up Delay option prevents the control from activating for 45-60 seconds after power is applied. This allows lamp warm-up time so the installer can verify the system is working properly. It also allows for the system to be easily tested in the future. When power is shut off and then reconnected (at the pole base) and the lamp turns on briefly and then turns off, it confirms that the control, fixture, lamp, and voltage supply are working correctly.
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
FAIL OFF CONTROLS
The relay is normally open to fail in the off position and prevent day burning fixtures.
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient, up to 90° interface per ANSI
• Power consumption: 0.5W
INVERSE RATIO CONTROLS
This option is ideal for areas where it is important to turn on lights early, but energy costs are a concern. The
Turn-Off level is lower than the Turn-On level.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DP120 120 Volts (105-130)
DP124 120-277 Volts (105-305)
DP240 240 Volts (185-305)
DP347 347 Volts (300-400)
DP480 480 Volts (420-530)
DPR124 Multi-volt Inverse ratio ¹ ² ³
DPF124 Multi-volt Fail Off ¹
TURN-ON LEVEL (ftc) 1
1.0 Energy Saver
1.5 ANSI Standard
2.6 IES Recommendation
8.0 Metro-High Ambient
35 FAA ³
TIME DELAY/SURGE PROTECTION POWER-UP DELAY COVER COLOR
TJ 2-5 Sec. Turn-off Delay
320J/9500 Amp MOV
(blank) Std. Operation
PD 45-60 Sec. Delay
(blank) ANSI Std. Color
BK Black
BR Brown
P Upward facing
(See Color Chart on Pg. 11)
4
Notes: 1) PD option not available on DPR or DPF Series 2) 2.6 Turn-on only 3) Black cover only
PACKAGE QTY.
J12 12 Units
J50 50 Units
FREQUENTLY ORDERED NUMBERS*
FREQUENTLY ORDERED NUMBERS*
DESIGN DETAILS
• Silicon light sensor
• MOV surge protection rated
for 320 Joules/9,500 Amps
• Sealed relay rated for a minimum of
5,000 operations at full load
• Turn-Off light level is 1.5 times Turn-On level
• 3.4 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene gasket,
brass legs, acrylic window
• Brown cover for DP1704 identification
• Black cover for DP1707 identification
• Eight-year warranty
FREQUENTLY ORDERED NUMBERS*
DP124 1.5 1704 J50
DP124 1.0 1707 J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DP124 120 - 277 Volts
DP124 120/208/240/277 Volts
(105-305)
TURN-ON LEVEL (ftc)
1.5
ANSI Standard
1.0
Energy Saver
UTILITY
1704
1707
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient, up to 90° interface per ANSI
PACKAGE QTY.
J12 12 Units
J50 50 Units
J50 50 Units
FREQUENTLY ORDERED NUMBERS*
DSS124F 1.5 TJJE J12
DSS124N 1.5 TJJE J12
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DESIGN DETAILS
• Enhanced filtered silicon light sensor
The specially selected filtered light sensor
does not “see” LED illumination. The control
is therefore blind to LED light which
simplifies installation in areas with high
ambient light or with close spacing of
LED fixtures
• Surge Protection & Inductive Filtering
DSS employs two MOV’s in conjunction
with additional series inductance and
high frequency filtering, this provides
ANSI Category C (20KV, 10 KA) surge
protection for the control, and also helps
protect the solid state driver from line
transients and “noise”
• Fail-off and Fail-on modes
• Extreme Inrush Protection:
Tested and approved for use with fixtures
that use multiple LED drivers, the DSS can withstand
the high inrush current that these drivers generate.
• 90,000 hour rated life
• Ten-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
• Surge Rated to ANSI C136.10 - Cat. C
OPERATING CHARACTERISTICS
• Average power consumption
is 0.7 watts @ 120V; 2.4 watts @ 277V
• Six Amp load rating
FAILURE MODE TURN-ON LEVEL (ftc)
DSS124 120-277 Volts F Fail Off
N Fail On
*
Notes: * Not acceptable for use with more than three LED drivers with supply voltage of 277V
1.0 Energy Saver
1.5 ANSI Std.
2.6 IES Recommended
8.0 Metro-High Ambient
- TIME DELAY
- SURGE PROTECTION
- ENHANCED AMBIENT SENSING
PACKAGE QTY.
TJJE 3-6 Sec. Turn-Off Delay
- Dual MOV’s
- LED Tuned Photo Sensor
J12 12 Units
J50 50 Units
5
6
FREQUENTLY ORDERED NUMBERS*
DD124 1.5 TJA J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DD124 120-277 Volts
TURN-ON LEVEL (ftc)
1.5
ANSI Standard
DESIGN DETAILS
• After five lamp cycles, the control turns
the lamp off. At dusk of the following day,
the control energizes the fixture and
the cycle detection circuit resets
• Silicon light sensor
• MOV surge protection rated
for 320 Joules/9,500 Amps
• Specified for use with 70-400 watt HPS
• Not for use on incandescent fixtures
• Flashing or steady LED alerts line
crew of problem
• 2-5 second Turn-Off delay
• Sealed relay rated for a minimum
of 5,000 operations at full load
• 3.8 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, Neoprene gasket,
brass legs, acrylic window
• Six-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
OPERATING CHARACTERISTICS
• -40 to +70°C ambient,
up to 90° interface per ANSI
• Power consumption: 0.5W
TIME DELAY (seconds) SURGE PROTECTION CYCLE DETECTION
1
T 2-5 Second Turn-off Delay J 320 J/9500 Amp MOV A
PACKAGE QTY.
J12 12 Units
J50 50 Units
Notes: 1) Cycle Detection Program is set at factory; program cannot be altered in field
FREQUENTLY ORDERED NUMBERS*
DPN124 2.6 TJGN J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
DESIGN DETAILS
• Turns on at dusk and off halfway through
the night. Automatically self adjusts
to seasonal time changes, reducing
maintenance
• Filtered silicon photocell provides long-term,
drift-free light sensing. The infrared blocking
polymer filter gives human eye response
• MOV surge protection
• Reduces light pollution and light
trespass concerns
• Sealed relay rated for 5,000
operations at full load
• 2-5 second off-only time delay is provided
to avoid turn-off from extraneous light
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, Neoprene gasket,
brass legs, acrylic window base rated for 120°C
• Six-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient, up to 90° interface per ANSI
• Power consumption: 0.8 watts
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DPN124 120/240/277 Volts
(105-305)
TURN-ON LEVEL (ftc) 1
2.6
Standard
TIME DELAY (seconds) SURGE PROTECTOR COVER COLOR
T 2-5 Second Turn-off Delay
(standard)
J 320 J/10,000 Amp MOV GN Green (only)
PACKAGE QTY.
J12 12 Units
J50 50 Units
Notes: 1) Other options available, please contact your local Acuity Brands Controls representative
DESIGN DETAILS
• Silicon light sensor
• Standard 160 joule, 6,500 Amp
• Sealed relay rated for 5,000 operations
at full load
• 3.4 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene
gasket, brass legs, acrylic window
• Six-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient, up to
90° interface per ANSI
• Power consumption: 0.5W
FREQUENTLY ORDERED NUMBERS*
DX124 12A J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DX120 120 Volts (105-130)
DX124 120/240/277 Volts
(105-305)
DX347 347 Volts (300-400)
DX480 480 Volts (420-530)
TURN-ON LEVEL (ftc) SENSOR COVER COLOR
1 1.2-3 ftc Turn-on (standard) 2 Silicon Sensor, Time Delay
(2-5 seconds)
A ANSI Standard Color
(See Color Chart on Pg. 11)
PACKAGE QTY.
J12 12 Units
J50 50 Units
DESIGN DETAILS
• Silicon light sensor
• Standard 160 joule, 6,500 Amp MOV
• Sealed relay rated for 5,000 operations
at full load
• 3.4 ounces each
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene
gasket, brass legs,
• Six-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
• RoHS compliant
• DUX is UL Listed
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient,
up to 90° interface per ANSI
• Power consumption: 0.5W
FREQUENTLY ORDERED NUMBERS*
DUX124 12A J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DUX120 120 Volts (105-130)
DUX124 120/240/277 Volts
(105-305)
DUX480 480 Volts (420-530 )
TURN-ON LEVEL (ftc) SENSOR COVER COLOR
1 1.0-2.0 FTC Turn-on 2 Silicon Sensor, Time Delay
(2-5 seconds)
A
P
ANSI Standard
Upward facing
(See Color Chart on Pg. 11)
PACKAGE QTY.
J12 12 Units
J50 50 Units
7
DESIGN DETAILS
• Cadmium sulfide light sensor
• MOV rated for 320 joule/9,500 Amp
• Sealed relay rated for a minimum
of 5,000 operations at full load
• Turn-Off light level is 1.5 times Turn-ON
• Dielectric strength: 5000V per ANSI
• Polypropylene cover, neoprene gasket,
brass legs, acrylic window
• Long life; six-year warranty
OPERATING CHARACTERISTICS
• Load rating: 1000W, 1800 VA ballast
• -40 to +70°C ambient,
up to 90° interface per ANSI
• Power consumption: 0.5W
FREQUENTLY ORDERED NUMBERS*
D124 1.0 STJ J50
D124 1.0 STJGY J50
D124 1.5 STJ J50
D124 1.5 STJBK J50
D124 1.5 STJGY J50
D124 1.5 STJMR J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
D120 120 Volts (105-130 )
D124 120/240/277 Volts
(105-305)
D240 240 Volts (205-265)
TURN-ON LEVEL (ftc)
1.0
Energy Saver
1.5
ANSI Standard
2.6
IES Recommended
REGULATORY LISTINGS
• Complies with ANSI C136.10-1996
LIGHT SENSOR TIME DELAY (seconds) SURGE PROTECTION COVER COLOR
S Standard
Cadmium Sulfide
(blank) Instant on and off
T 2-5 second
Turn-off Delay
J 320 J/9500 Amp
MOV (standard)
(blank) ANSI Standard
Color
BK Black
BR Brown
P Upward Facing
(See Color Chart on Pg. 11)
PACKAGE QTY.
J12 12 Units
J50 50 Units
DESIGN DETAILS
• Filtered silicon light sensor
• MOV rated for 190 joule/4,500 Amp
• Instant turn-on, standard 5-10
second turn-off time delay
• 12”, 200°C, 16 gauge stranded leads
• Six-year warranty
REGULATORY LISTINGS
• Complies with ANSI C136.24
• UL and CSA Listed models available
FREQUENTLY ORDERED NUMBERS*
DBE124 1.5 T J12 DBE124 1.5 TUL J12
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
OPERATING CHARACTERISTICS
• Voltages 120–347
SERIES CODE & VOLTAGE
DBE120 120 Volts (105-130)
DBE124 120 - 277 Volts (105-305)
DBE347 347 Volts (300-400)
TURN-ON LEVEL (ftc)
1.5
ANSI Standard
TIME DELAY CERTIFICATION
T 5-10 Second Turn-off Delay U CSA Listed
UL UL Listed 2
1
8
Notes: 1) DBE347 & DBE120 Only 2) DBE 124 Only
PACKAGE QTY.
J12 12 Units
J25 25 Units
FREQUENTLY ORDERED NUMBERS*
DESIGN DETAILS
• Filtered silicon light sensor
• 190 Joule MOV surge protection
• 1/2” straight pipe thread fits standard
• 1/2” knock-out or threaded connector
• 12”, 200ºC, 16 gauge wire leads
• Swivel mechanism rotates 180º on
a single axis for optimal orientation
• Polycarbonate enclosure
• Instant Turn-on, 5-10 second
Turn-off time delay
• Six-year warranty
REGULATORY LISTINGS:
• Complies with ANSI C136.24, where applicable
• UL listed
OPERATING CHARACTERISTICS:
• Voltages 120–277
FREQUENTLY ORDERED NUMBERS*
DSW124 12A J12
DSW124 12A J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DSW124 120-277 Volts
TURN-ON LEVEL (ftc) SENSOR COVER COLOR
1 1.0-2.0 ftc Turn-on 2 Silicon Sensor,
5-10 second off-time delay
A Gray
PACKAGE QTY.
U 1 Unit
J12 12 Units
J50 50 Units
9
10
FREQUENTLY ORDERED NUMBERS*
DUR103 J6
DUR103 J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
DESIGN DETAILS
• Aluminum
Mounting Bracket
• Leads – 14” long,
14 gauge stranded,
rated for 105°C
• Cup - Rotating
polycarbonate
cup with locknut
REGULATORY LISTINGS
• UL Recognized component
• Meets NEMA standards
• Meets ANSI standards
• ROHS compliant
ORDERING INFORMATION
SERIES CODE & VOLTAGE
DUR 103 120- 480 Volts
PACKAGE QTY.
U 1 Unit
J6 6 Units
J50 50 Units
OPERATING CHARACTERISTICS
• Electrical rating – 15 Amp,
480VAC Max., 50/60 Hz
• Leads
14 gauge, stranded 14”
Leads are rated 105 C
• Red = Load
Black = Line
White = Common
DESIGN DETAILS
• MOV Rated for
265Joule/6000 Amp
(shorting cap only)
• Neoprene Base Gasket
has a continuous use
temperature of 105°C
• Brass Legs
• Polypropylene Cover
FREQUENTLY ORDERED NUMBERS*
DSHORT SBK J12
DSHORT SBK J50
DSHORT VBK J12
DSHORT VBK J50
DOPEN SRD J50
* Frequently Ordered Numbers are products that are generally in stock. Ordering other catalog number configurations may impact pricing and lead-time.
ORDERING INFORMATION
SERIES CODE SURGE PROTECTION
DSHORT
DOPEN
SBK Shorting Cap, Black cover
VBK Shorting Cap, 265J MOV, Black cover
PACKAGE QTY.
J12 12 Units
J50 50 Units
SRD Open Cap, Red cover
REGULATORY LISTINGS
Exceeds ANSI C136.10-1996
OPERATING CHARACTERISTICS
• Voltage 105 to 530 VAC,
50/60Hz
• -40 to +70°C ambient
WORST CHOICE
WITH SILICON
SENSORS, RESULT
IS LATE TURN-ON
AND LATE TURN-OFF
As North America’s largest lighting manufacturer,
Acuity Brands® brings together the industry’s most innovative lighting and control brands to offer the right light for every application.
Acuity Brands Controls —consisting of ROAM®,
Dark To Light®, Lighting Control & Design® (LC&D),
Sensor Switch®, RELOC®, Power Sentry®, and
Synergy Lighting Controls®—provides innovative control solutions for customers demanding efficiency, flexibility, quality and excellent service.
EARLY TURN-ON
AND EARLY TURN-OFF
MAKES MOST
CON TROLS ACT
LIKE INVERSE RATIO
CONTROLS
VOLTAGE RATING, VOLTS (60Hz)
120
120
240
240
120 - 277
480
OPERATING VOLTAGE RANGE, VOLTS
105 - 130
105 - 130
185- 305
185 - 305
105 - 305
420 - 530
COLOR CODING
Gray or Clear
Orange
Maroon
Green
Blue
Yellow
12
®
Dark To Light | 1-800-442-6745 | darktolight.com
©2011 Acuity Brands Lighting, Inc. All Rights Reserved. 06/11 Form No. 1354.04