Relays MC line General Characteristics The MC line has been designed to offer to the market a very competitive protective relay responding to the latest requirements in terms of control and communication capabilities with an extremely high level of modularity. Each relay includes a limited number of protective functions but, thanks to their very compact sizes, different units can be combined in a modular enclosure to satisfy the most demanding needs. Measurements • Real Time Measurements • Trip Recording (last 20 trips with date & time) • Event recording (last 10 trips) Control • 4 Output Relays (programmable) • 3 Digital Inputs • Time tagged multiple event recording • Oscillographic wave form capture • Blocking Outputs and Blocking Input for pilot wire selectivity coordination • Associate C.B. control Technical Characteristics • Complete self diagnosis program • Display LCD 16 (2x8) characters • 4 Leds for signalization Communications • 1 RS485 Serial communication port on rear side • 1 RS232 Serial communication port on front panel • Modbus RTU/IEC870-5-103/IEC61850 Communication Protocols Expansion Modules (optional) • “UX10-4” 10 Digital Input and 4 Output Relays • “14DI” 14 Digital Inputs • “14DO” 14 Output Relays Execution • 1 Module box (2 modules with expansion) • Totally draw-out execution • IP44 protection case (on request IP54) Software • MSCom2 Program interface for device management Relays Type MC1V MC3V MC20 MC30 MC40 MC20-R MC30-R MC30-BC MCDC-I MCDC-V MCM Multifunction Single Phase Overvoltage/Undervoltage Relay: 59, 27, 81>, 81< Multifunction Three Phase Overvoltage/Undervoltage Relay: 59, 27, 81>, 81<, 59Vo, 59V2, 27V1 Overcurrent & Earth Fault Relay: 50/51, 50N/51N, 51BF Three Phase Overcurrent & Earth Fault Relay: 49, 50/51, 50N/51N, 51BF Three Phase Overcurrent & Earth Fault (connection with 4 CT ‘s): 49, 50/51, 50N/51N, 51BF Overcurrent & Earth Fault Relay: 50/51, 50N/51N, 51BF, 79 Three Phase Overcurrent & Earth Fault with reclosing function Relay: 50/51, 50N/51N, 51BF, 79 Three Phase Overcurrent & Earth Fault + Broken Conductor Relay: 50/51, 50N/51N, 51BF, BC (I2/I2) D.C. Current Relay: 76/32, 49, 51BF D.C. Voltage Relay: 45, 80 Motor Protection Relay: 37, 46, 47, 48, 49, 50/51, 51LR, 64S, 66, 68 Wiring Diagram 6 7 6 7 7 5 8 4 5 Ion= 1A 1A 1A 1A 1/5A 1/5A 9 R2 R2 18 R3 17 OUTPUT 14 RELAYS F50 F51 F50N F51N R1 R1 R2 F50N R4 F51N R4 17 R4 OUTPUT 14 RELAYS 15 R3 INT.FAULT D3 D2 D1 R4 12 15 13 12 13 R2 R3 INT.FAULT 18 F50 R3 F51 FUNCTION 1/5A 9 16 16 FUNCTION MICROP. 1/5A 8 8 9 R1 MC20 5 5 9 In= In= Ion= 4 4 8 MC20 DISPLAY 1/5A R1 MICROP. 1/5A 7 6 4 DISPLAY 6 D3 D2 20 D1 21 DIGITAL 19 INPUTS 20 21 DIGITAL 19 INPUTS 22 22 5A 5A5A 5A 10 AUXILIARY AUXILIARY SUPPLYSUPPLY 11 C A (S+) B (S-) 10 11 KEYBOARD MS-SCE1828-R1 MS-SCE1828-R1 BPMC 3 2 1 RS485 C A (S+) B (S-) 3 2 1 RS485 KEYBOARD BPMC 135 164 Overall Dimensions: mm 83 1 MODULE PANEL CUT-OUT 64X137 (LXH) 2 195 213 225 Microelettrica Scientifica S.p.A. Via Lucania, 2 20090 Buccinasco - Italy Tel.: +39 02 575731 Fax: +39 02 57510940 - sales.relays@microelettrica.com - www.microelettrica.com