Section II -Technical Specification
Tender Enquiry No : PUR/ID-19/16-17
Name of the Equipment: AC Three Phase Phantom Load Static Source
Note :The Offers should be submitted only in this format otherwise the offer will be liable for rejection
A detailed technical catalogue/literature/phamplet and any other technical details shall be sent in hard copy in a sealed cover superscribing enquiry number
and due date so as to reach the following address with the due date and time. This is very much essential to evaluate your offer.
Name of the Vendor
Offer Number and Date
Sl.No. Parameters
CPRI Specification / Requirements
1
Supply to
CPRI, Bangalore
2
Scope
1) Supply, Installation, Commissioning, Demonstration and Training of “AC
Three Phase Phantom Load Static Source”.
2 Nos.
2) The intended source shall be suitable to perform accuracy test on single phase
and three phase smart meters / prepaid meters / energy meters / wattmeters,
as a standalone unit.
3
Construction
Qty
1) Portable, Modular, Compact & table top mountable.
2) The intended source shall have variable voltage source, variable current
source & variable Phase shifter (for power factor setting). The working concept
shall be on phantom load principle. Test parameters shall be displayable by
large LCD on the front panel of the source.
Page 1 of 5
To be completed by the Bidder
Guaranteed
Deviation/
Technical
Remarks Specify if
Particulars (GTP)
any
3) The intended source shall be operable by easy key operation, provided on the
front panel and / or by remotely from computer. The operation of the source (in
both manual and remote mode) shall be user friendly. The source shall be
provided with continuous display of instantaneous test parameters (viz. voltage,
current, frequency, phase angle (of all three individual phases), power factor (of
all three phases).
4) It shall have a three position portable mounting rack for mounting Single
phase / Three phase meters of 5kg weight each.
4
Types of Meters
intended to be tested
3 Phase 4 Wire LT CT, HT CT PT & Whole current Active, Reactive and Apparent
Energy Meters/Prepaid Meters / Smart Meters (in both balanced and
unbalanced conditions) in both import and export modes.
3 Phase 3 Wire Active, Reactive and Apparent Energy Meters (in both balanced
and unbalanced conditions) in both import and export modes.
1 Phase 2 Wire Whole current Active, Reactive Energy Meters / prepaid meters /
Smart Meters, in both import and export modes.
5
Phantom load Source
It shall be feasible for variation of test values of various parameters (viz.,
voltage, current & phase angle) for all three phases independently by using front
panel key operation and / or remotely in both balanced & unbalanced modes.
6
Output Voltage range
0 to 300V (L-N) continuous
Voltage Accuracy
≤0.05% of range.
Overload voltage output Up to 125%.
7
Voltage output
distortion
Output voltage
compliance
Output current range
< 0.5% (under linear load condition)
Overload current
output
120A
Current accuracy
≤0.05% of range
≥ 100VA
1mA to 100A
Page 2 of 5
Current output
distortion
< 0.5% (under linear load condition)
Output current
compliance
≥ 200VA
Output Voltage to
Current phase shift
0-359.99° in R/Y/B phases.
Predefined power
factor settings
UPF, 0.5 lag, 0.8 lead & ZPF.
Phase angle accuracy
≤ 0.1°
Output frequency
45 to 65 Hz with 0.01Hz resolution.
Accuracy
≤0.1%
10
Output Stability
Better than 0.02% / hr with integration time of 60 sec.
11
Communication
Interface
Suitable communication port RS 232/USB shall be provided on the source for
interfacing to computer. If RS 232 interface is provided, suitable converter i.e.,
RS 232 to USB converter shall be provided.
12
Software
Suitable control software shall be provided compatible for Windows 7 and
higher version. Software shall be user friendly & all the parameters (viz. voltage,
current, frequency, phase angle / power factor, vector. Bidder may indicate
other parameters also) shall be programmable and displayable on the computer
screen. Software shall be supplied in CD media along with Operating manual.
13
Mains
Single Phase AC 240V ± 10%, 48-52 Hz power supply. Mains ON/OFF switch
shall be provided.
14
Protections
Input protection shall be provided by Fuse. Output protection against external
short circuit for voltage circuit & external open circuit for current circuit shall be
provided.
15
Output terminals
Insulated terminals of suitable rating for voltage (R-Y-B-N) and current (R-Y-B)
shall be provided on the source.
16
Three Phase
Isolation Current
Transformer (ICT)
Characteristics:
8
9
Page 3 of 5
16
Three Phase
Isolation Current
Transformer (ICT)
Current range:10mA - 120A
Nominal frequency : 50 Hz
Class 0.1 or better for current ratio and 5min or better for phase
angle error.
Output power: 60VA (max.)
Overload indication shall be provided on the front panel.
Auxiliary supply voltage: Single Phase AC 240V ± 10%, 48-52 Hz
power supply.
17
Ambient conditions
Operating range : 10°C to 40°C
Storage temperature range : 10 °C to 45°C
18
Connecting Cables
Flexible colour coded cables and / or terminals of suitable rating shall be
supplied along with the equipment.
Single phase main supply cable of length 2 meters suitable for connecting to
Indian type sockets shall be provided.
Two sets of output voltage cables (R-Y-B-N) shall be supplied. One end with
safety banana plug and other end with insulated crocodile clip.
One set of current cables (includes incoming and outgoing cables for all three
phases - of current rating 120A continuous) shall be supplied. One end with
suitable pin type lugs of suitable rating for connecting to meter terminals shall
be provided.
19
Calibration certificate
After supply of Phantom load source, calibration will be carried out by CPRI,
Bangalore (before installation & commissioning).The calibration results shall
adhere to the specification of Phantom load source, failing which the equipment
will be rejected. CPRI is NABL accredited laboratory.
20
Accessories
Bidder shall specify and quote separately, if any other required accessories are
required for proper operation of intended source.
21
General Terms and
conditions
After supply, the equipment shall be demonstrated to CPRI engineers.
Page 4 of 5
21
General Terms and
conditions
Operating Manual and Service Manual with trouble shooting chart, cables,
standard accessories, recommended spares, carrying case shall be supplied
along with equipment.
Quotation without detailed specifications / drawings are liable to be rejected.
Bidder shall quote the cost of manuals, cables, accessories, spares, carrying case
etc. separately if they are not included in the basic price.
22
Dimension & weight
To be specified by the bidder.
23
Delivery period
Within 2 months from the date of our purchase order.
24
Warranty
One year from the date of satisfactory installation.
PN : 1. A detailed technical catalogue/literature/pamphlet and any other technical details shall be sent in hard copy in a sealed cover super scribing tender enquiry
number and due date so as to reach the following address within the due date and time. This is very much essential to evaluate your offer.
2. The supplier shall fill all the points in GTP columns as per the above format given in the specification.
3. The supplier shall submit the offer in the above format only with compliant statement, failing which the offer will not be considered for evaluation.