Definite Purpose Contactors & Starters CR453A Series Contactors CR454A Series Starters Caution: Before installing in a nuclear application, determine that the product is intended for such use. Warning: Disconnect power before installing or servicing. Description GE’s CR453A magnetic contactors provide a 2- or 3-pole device for use in air conditioning units or other general purpose applications. These instructions give information Ratings – Full Voltage, Non-Reversing Frame Size about ratings, installation, accessories and wiring, overload relay may be added if needed. Factory assembled starters CR453AB CR454A include overload relay. CR453AC CR453AD Ratings VAC 120 240 480 600 120 240 480 600 120 240 480 600 FLA 25 30 40 LRA 150 150 125 100 180 180 150 120 240 240 200 160 Resistive Horsepower 1 PH 3 PH 2 3 – – 2 5 – – 3 7.5 – – – 7.5 10 10 – 10 15 15 – 10 20 20 Rating Per Pole 35 40 50 Motor branch circuit and control circuit overcurrent protection should be supplied in accordance with the National Electrical Code or local code as required. CR453A contactors are suitable for use on a circuit capable of delivering not more than 5,000 RMS symmetrical amperes, Typical CR453A Series contactor 600 volts maximum when protected by fuses or a circuit breaker having an interrupting rating not less than 5,000 RMS symmetrical amperes. Power Terminal Tightening Torque (lbs.-in.) Terminal Type Torque Values Box Lug Pressure Plate Binding Screw 40 20 20 Use 75° C copper conductors only. Contactor Installation Starter Installation Before connecting to power supply: 1. Remove all packing. 1. Remove all packing. 2. Motors with service factor of 1.15 or greater. • Select overload relay as per the FLA shown in the 2. Operate movable magnet and operating arm by motor nameplate. pressing down on the operating arm from the front • Adjust the front mounted tripping current setting or side of the contactor to assure free movement. dial to the motor FLA. 3. Mount starter on a sturdy vertical support. 2. Motors with service factor less than 1.15 4. Make electrical connections as per wiring diagram. • Select overload relay as per the formula: Motor FLA For quick connect wiring, use UL recognized insulated (shown in the motor plate) x 0.09. terminals. • Adjust the front mounted tripping current setting dial Mounting Hole Dimensions to the result of the above mentioned motor FLA. 1.70 43,2 3. Operate movable magnet and operating arm by pressing down on the operating arm from the front or side of the contactor to assure free movement. .35 8,9 3.28 83,3 4. Mount starter on a sturdy vertical support. 3.75 95,3 5. Make electrical connections as per wiring diagram. 3.16 80,3 For quick connect wiring, use UL recognized insulated terminals. 6. Select the four modes by means of a front selector lever. 7. Overload relays features tripping indicator, independent MOUNTING HOLES FOR #10 SCREWS(6 PLACES) & double break auxiliary tripping contacts (1NO+1NC) with welding check lever. Contactor Wiring Diagram 8. Overload relay features thermal protection against 3 PHASE LINE CONNECTION balanced overload, differential protection against AUX CONTACT OPTONS FRONT VIEW L1 CONTROL VOLTAGE L2 TYPE L2 unbalanced overloads and also ambient temperature RIGHT SIDE LEFT SIDE C compensation. C 1 SPDT M NC N NC C C N C CR454A Series Starter Dimensions C 2 SPDT 2.25 57,0 NC OPTIONAL AUX CONTACTS T1 OPTIONAL AUX CONTACTS T2 N NC 13 23 N NC N 33 43 2 NO T2 14 24 34 44 13 21 31 43 14 22 32 44 NC N 1.12 28,5 3.13 79,4 1.71 43,3 .24 6,0 1 NO-1 NC 3 PHASE LINE CONNECTION 3.28 83,3 NOMENCLATURE M-LINE CONTACTOR NO-NORMALLY OPEN NC-NORMALLY CLOSED 3.87 98,2 1.70 43,2 .27 6,9 5.68 144,3 MOUNTING HOLES FOR #10 SCREWS(6 PLACES) Overload Relays Check for Welded Contacts in Overload Relay Disconnect power from device and control wiring from the Contactor terminals of the relay. Connect the bell set or resistancemeasuring instrument across the relay terminals. Depress and release the reset arm to ensure the relay is reset. In this condition there should be continuity between the terminals. In the tripped condition, the circuit between the terminals should be open indicating the contacts are operating CR453AB, AC, AD normally. Remove the bell set or resistance measuring apparatus, rewire the relay terminals and reset the relay for normal operation. Starter Wiring Diagram L3 L2 L1 AUX CONTACT OPTONS TYPE FRONT VIEW WIRE B RIGHT SIDE LEFT SIDE CR453AC, AD CR453AD WIRE A C L2 L1 1 L3 C 1 SPDT REMOTE CONTROL NC N NC C M C Class 20 RT1B RT1C RT1D RT1F RT1G RT1H RT1J RT1K RT1L RT1M RT1N RT1P RT1S RT1T RT1U RT1V RT1W RT12B RT12C RT12D RT12F RT12G RT12H RT12J RT12K RT12L RT12M RT12N RT12P RT12S RT12T RT12U RT12V RT12W C 2 SPDT OPTIONAL AUX CONTACTS 95 96 97 98 NC OPTIONAL AUX CONTACTS T1 T2 T3 N NC N NC N NC 13 23 33 43 14 24 34 44 13 21 31 43 14 22 32 44 N Installation 2 NO 1 NO-1 NC CONTROL CIRCUIT FUSING (IF USED) L1 MOTOR L2 NOMENCLATURE 1 M-LINE CONTACTOR OL-THERMAL OVERLOAD RELAY SPDT-SINGLE POLE DOUBLE THROW NO-NORMALLY OPEN NC-NORMALLY CLOSED 96 NOTE: ADDITIONAL CONTROL CIRCUIT PROTECTION MAY BE REQUIRED.PREFER TO NATIONAL ELECTRIC CODE OR LOCAL CODES. ELEMENTARY L1 L2 OL 1 M FOR SEPERATE CONTROL SOURCE-OMIT WIRES A AND B. CONNECT CONTROL SOURCE TO 1 ON CONTROL DEVICE. AND 96 ON OVERLOAD RELAY. REMOTE CONTROL 95 96 Typical 250V side auxiliary contact kit. Accessory Kit Installation Accessories Accessory Contacts CR453A Accessories Standard (with quick connects on C-2000 side-mount accessories) accessories 600V side-mount aux. contact block 250V side-mount aux contact block 600V front-mount aux. contact block Mechanical interlock, side-mount 1NO-1NC 2NO 1 SPDT 2 SPDT 1NO 1NC CR453XC611 CR453XC620 CR453XC211 CR453XC222 BCLF10 BCLF01 BCLL11 BCLL20 — — BCLF10 BCLF01 2NC CR453XM602 BEL02 Current Range (A) 0.16-0.26 0.25-0.41 0.4-0.65 0.65-1.1 1.0-1.5 1.3-1.9 1.8-2.7 2.5-4.1 4.0-6.3 5.5-8.5 8-12 10-16 14.5-18 17.5-22 21-26 25-32 30-40 For further technical details on overload relays, refer to installation instructions GEH-6237A. N C Catalog No. Class 10 Typical 600V side auxiliary contact kit. Front-Mount Auxiliary Contacts Side-Mount Auxiliary Contacts Assembly 2-Speed Controllers Mechanical interlock Disassembly Overload Relays 1 2 These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should particular problems arise which are not covered sufficiently for the Purchaser’s purposes the matter should be referred to the nearest GE Industrial Systems sales office. GE Industrial Systems e-DEH-40445 0801 General Electric Company 41 Woodford Avenue, Plainville, CT 06062 www.GEindustrial.com © 2001 General Electric Company