09DK-4SB

advertisement
09DK-4SB
09DK054, 064, 074, 084, 094
AIR-COOLED CONDENSERS
— PERFORMANCE DATA
— CERTIFIED DIMENSION PRINT
R 1994 Carrier Corporation • Syracuse, New York 13221
Form 09DK-4SB Supersedes 09DK-3SB
Printed in U.S.A.
199
2-94
Catalog No. 510-932
Date:
Supersedes:
09DK054,064,074,084,094
AIR-COOLED CONDENSERS
JOB NAME:
LOCATION:
BUYER:
BUYER P.O. #
UNIT NUMBER:
MODEL NUMBER:
09DK
Rev.:
-4SB
CARRIER #
PERFORMANCE DATA CERTIFIED BY:
DATE:
DESCRIPTION
These units are used as remote air-cooled condensers with vertical package units, liquid chilling packages
or compressor units. The unit is constructed of pre-painted steel that meets 500 hour salt spray requirements. Condenser fan motors are 3 phase and are protected against single-phasing conditions. Condenser
coils have an integral subcooling circuit.
FEATURES
Standard one-year warranty.
UL and CSA listed.
Pre-painted steel cabinet meets 500 hour salt spray requirement.
3-phase condenser fan motors have internal overload protection.
Hinged doors for control box access.
All refrigerant connections are on one side of the unit.
Coils constructed of aluminum lanced sine-wave fins on mechanically expanded internally enhanced copper tubes.
Base rail construction provides lifting holes and does not require
field-installed mounting legs.
Fan cycling head pressure control.
Small unit footprint for minimal space requirements.
PERFORMANCE DATA
Refrigerant
Ambient Air Temperature
Total Heat of Rejection
Discharge Line Loss
Saturated Condensing Temperature (SCT)
Minimum Ambient Air Temperature
ELECTRICAL DATA
Unit Power Supply
Condenser Fan Motor Input
Volts
Ph
Hz
kW
Minimum Circuit Amps
Maximum Overcurrent Protection Amps
OPTIONS
ACCESSORIES
(Factory Installed)
(Field Installed)
M Copper/Copper Condenser Coil
2
M Motormastert III Low Ambient Head Pressure Controls to
−20° F Ambient
M Fan Sound Reduction Kit
M Condenser Coil Coastal Filter
M Security Grille Packages
M Condenser Coil Hail Guard Package
M Accessory Control Transformer
M Accessory Fan Control Kit
M Motormaster III Relay/Sensor Kit
CUT ALONG DOTTED LINE
CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CERTIFIED DIMENSION PRINT
NOTES:
1. The approximate operating weight of the unit is:
09DK-054--- — 1695 Lbs [769 Kg]
09DK-054--C — 1983 Lbs [900 Kg]
09DK-064--- — 1845 Lbs [837 Kg]
09DK-064--C — 2278 Lbs [1033 Kg]
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
3. All units are shipped with a capacity split tubing kit. This kit may be used by
the field to obtain 100%, 50%/50% and 67%/33% capacity splits. To obtain
a 33%/33%/33% capacity split, coils must be manifolded by the field. Coils
are factory circuited for a 33%/33%/17%/17% capacity split.
UNIT
09DK-054--09DK-054--C
09DK-064--09DK-064--C
DIMENSION Y
DIMENSION X
38-611⁄169
[1084 mm]
38-67⁄89
[1090 mm]
38-63⁄49
[1087 mm]
38-71⁄89
[1095 mm]
48-1⁄89
[1222 mm]
48-5⁄169
[1227 mm]
48-3⁄169
[1224 mm]
48-1⁄29
[1232 mm]
OPERATING CORNER WEIGHTS
A
B
C
D
452 Lbs 425 Lbs 396 Lbs 422 Lbs
[205 Kg] [193 Kg] [180 Kg] [191 Kg]
524 Lbs 497 Lbs 468 Lbs 494 Lbs
[238 Kg] [225 Kg] [212 Kg] [224 Kg]
489 Lbs 462 Lbs 434 Lbs 459 Lbs
[222 Kg] [210 Kg] [197 Kg] [208 Kg]
598 Lbs 571 Lbs 542 Lbs 568 Lbs
[271 Kg] [259 Kg] [246 Kg] [258 Kg]
CAPACITY SPLIT
100%
50%/50%
67%/33%
33%/33%/33%
33%/33%/17%/17%
Type
Hot Gas
Liquid
Hot Gas
Liquid
Hot Gas
Liquid
Hot Gas
Liquid
Hot Gas
Liquid
CONNECTIONS
No. 5
1, 3, 5, 7
2, 4, 6, 8
1, 3
5, 7
2, 4
6, 8
1, 3, 5
7
2, 4, 6
8
1
7
3, 5
2
8
4, 6
1
7
3
5
2
8
4
6
Size
11⁄89 I.D.
7⁄89 I.D.
11⁄89 I.D.
7⁄89 I.D.
11⁄89 I.D.
7⁄89 I.D.
11⁄89 I.D.
7⁄89 I.D.
11⁄89 I.D.
7⁄89 I.D.
3
4
CERTIFIED DIMENSION PRINT
NOTES:
1. The approximate operating weight of the unit is:
09DK-074--- — 2200 Lbs [998 Kg]
09DK-074--C — 2617 Lbs [1187 Kg]
09DK-084--- — 2421 Lbs [1098 Kg]
09DK-084--C — 3099 Lbs [1406 Kg]
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
3. All units are shipped with a capacity split tubing kit. This kit may be used by the field to obtain
100%, 50%/50% and 67%/33% capacity splits. To obtain a 33%/33%/33% capacity split,
coils must be manifolded by the field. Coils are factory circuited for a 33%/33%/17%/17%
capacity split.
UNIT
09DK-074--09DK-074--C
09DK-084--09DK-084--C
DIMENSION Y
DIMENSION X
38-61⁄29
[1080 mm]
38-613⁄169
[1087 mm]
38-65⁄89
[1082 mm]
38-79
[1092 mm]
48-811⁄169
[1440 mm]
48-93⁄89
[1458 mm]
48-91⁄89
[1450 mm]
48-101⁄89
[1476 mm]
OPERATING CORNER WEIGHTS
A
B
C
D
618 Lbs 526 Lbs 486 Lbs 571 Lbs
[280 Kg] [239 Kg] [220 Kg] [259 Kg]
722 Lbs 630 Lbs 589 Lbs 675 Lbs
[328 Kg] [286 Kg] [267 Kg] [306 Kg]
673 Lbs 581 Lbs 541 Lbs 626 Lbs
[305 Kg] [264 Kg] [245 Kg] [284 Kg]
843 Lbs 751 Lbs 709 Lbs 796 Lbs
[382 Kg] [341 Kg] [322 Kg] [361 Kg]
CAPACITY SPLIT
100%
50%/50%
67%/33%
33%/33%/33%
33%/33%/17%/17%
CONNECTIONS
Type
No. 5
Size
Hot Gas
1, 3, 5, 7
13⁄89 I.D.
Liquid
⁄ 9 I.D.
2, 4, 6, 8
78
Hot Gas
1, 3
5, 7
Liquid
2, 4
6, 8
Hot Gas
1, 3, 5
7
Liquid
2, 4, 6
8
Hot Gas
1
Liquid
7
2
8
13⁄89 I.D.
⁄ 9 I.D.
78
13⁄89 I.D.
⁄ 9 I.D.
78
13⁄89 I.D.
3, 5
⁄ 9 I.D.
4, 6
78
Hot Gas
1
7
3
5
Liquid
2
8
4
6
13⁄89 I.D.
⁄ 9 I.D.
78
CUT ALONG DOTTED LINE
CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
→ CERTIFIED DIMENSION PRINT
NOTES:
1. The approximate operating weight of the unit is:
09DK-094--- — 2850 Lbs [1294 Kg]
09DK-094--C — 3560 Lbs [1615 Kg]
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended
for mounting unit to spring isolators. If spring isolators are used, a perimeter support
channel between the unit and the isolators is recommended.
UNIT
09DK-094--09DK-094--C
DIMENSION Y DIMENSION X
58-27⁄89
[1597 mm]
58-27⁄89
[1597 mm]
38-93⁄169
[1148 mm]
38-93⁄169
[1148 mm]
OPERATING CORNER WEIGHTS
A
B
C
D
769 Lbs 676 Lbs 658 Lbs 747 Lbs
[349 Kg] [307 Kg] [299 Kg] [339 Kg]
960 Lbs 845 Lbs 821 Lbs 934 Lbs
[436 Kg] [383 Kg] [372 Kg] [424 Kg]
199
HOT GAS
5
Download