IMPORTANT INFORMATION Please Read Before Installing ® Stairwell Standard Fixture Installation Instructions Important Notes Figure A: Installation Components 1. Install and wire in accordance with national and local electrical codes, by a qualified professional familiar with the construction and operation of fluorescent luminaire electrical systems and the hazards involved. 2. Fully assembled fixture comes ready to install: • Fixtures are shipped with preset occupied and unoccupied light levels. Light levels may need to be field adjusted to meet local code (see Programming). • Pre-wired LutronR 1% dimming ballast. Reduced-wattage T8 lamps are able to dim to a minimum of 10% with an EcoSystemR reduced-wattage dimming ballast. 32 W T8 ballasts will not operate with reduced-wattage lamps. Lens Wireless Control Device 3. Lamps are not included with this fixture. For optimal performance, install new lamps with installation. Use only with lamps conforming to the IEC 60081/60901 specification. Lutron recommends GE, Sylvania, or Philips lamps that are certified for dimming. Note: Consult lamp manufacturer for lamp burn-in requirements. To burn-in, see Figure D. 4. Compatible with LutronR Radio Powr SavrT wireless occupancy sensors (not included). At a minimum, one sensor per entryway is required. Note: Not compatible with Radio Powr SavrT daylight sensors or PicoR wireless controls. 5. Ambient operating temperature: 50 to 104 °F (10 to 40 °C). 0 to 90% humidity. Non-condensing, indoor/dry location use only. 6. Emergency Ballast Only: The emergency ballast fixture provides an exterior test button with an LED for identification and to verify power. Pressing the button will mimic an emergency power loss situation and illuminate one lamp, verifying that the emergency ballast is properly wired and charged. P/N 041320b 05/2013 www.lutron.com 1 Technical Support: 1.800.523.9466 Installation WARNING! Shock Hazard. May result in serious injury or death. Switch off power to all power feeds via circuit breaker or isolator before wiring or servicing. 1. Turn off power to the fixture location. 4. Reassemble the fixture. 5. Restore power. 2. Remove the existing fixture, preserving the power wiring. Carefully remove the lens and cover plate on the LutronR Stairwell Fixture to access the mounting holes and power wiring. Determine the appropriate mounting method for the new fixture, and secure the fixture to the wall or ceiling. Use appropriate mounting hardware to support a 20 lb (9 kg) fixture. Note: Fixture will default to occupied light level (high-end). 6. Install Radio Powr SavrT occupancy sensors that will be associated to the fixture. See instruction sheet provided with occupancy sensor for proper installation. Note: At a minimum, one sensor per entryway is required. 3. Connect Power Source to the Ballast Disconnect (see Figure B). Note: Ensure all components are properly grounded and check that all wires are securely connected 7. Associate Radio Powr SavrT occupancy sensors to the fixture (see Association). Emergency Ballast Only: – For input power wiring, connect either the Black wire for 120 V~, or the Orange wire for 277 V~ on the emergency ballast to the line/hot input connector of the power source. Cap off the power wire you do not use. –C onnect Emergency Ballast Battery Disconnect prior to restoring power to enable the emergency output. Figure B: Input Power Wiring Wireless Control Device CLASS 2 BUS For lamp wiring, consult the wiring diagram on the ballast. E2 Blue (not used) Orange (Dimmed Hot / DH) E1 Black LINE Ballast White Brass (not used) HOT DH Ballast Disconnect * NEU Line/Hot Neutral Power Source From distribution panel (contractor provided) Emergency Ballast Battery Disconnect * Ballast Disconnect is Emergency Ballast ** Black pre-wired to components Wire Black (120 V~) or Orange (277 V~) and cap off the wire not used. ** Emergency Ballast Line/Hot Orange installation is optional Neutral (white wire) www.lutron.com 2 Technical Support: 1.800.523.9466 Association Figure C: Typical Layout LutronR Radio Powr SavrT Wireless Occupancy Sensors Only Example below shows associated occupancy sensors turning fixtures on to occupied light level (high end). 1. Identify which fixtures will have the same sensor associated to them. Typically, this will include all fixtures within the floor above and the floor below the entryway (see Figure C). Note: Up to nine fixtures can have the same sensor associated to them, and up to nine sensors can be associated to a fixture within RF range. Fixture Wireless sensor 2. Press and hold T on the wireless control device for approximately 6 seconds until the ILs (Indicator Lights) flash (see Figure D). Repeat this step for all fixtures identified in step 1. • Associate only one sensor at a time • Wireless control devices will automatically return to normal operation after 10 minutes of inactivity. Note: RF range (sensor to fixture): - 60 ft (18 m) line of sight - 30 ft (9 m) through normal construction materials 3. Press and hold the " " or "Lights Off" button on the sensor for approximately 6 seconds until the lens on the sensor flashes orange (see Figure E) to complete Association. Figure D: Wireless Programming (Optional) 1. To adjust the desired occupied (high-end) and unoccupied (low-end) light levels of the fixture, enter programming mode on the wireless control device by pressing and holding the T and buttons for approximately 3 seconds until an IL starts flashing (see Figure D). Press and hold “ ” or “Lights Off” button. Tap Button T Raise * Lower 2. Use / to adjust the desired occupied (high-end) light level. Press T once to continue. Use / to adjust to the desired unoccupied (low-end) light level. Figure F shows the approximate light level increments, as displayed by the ILs. 3. Press T to save the light level settings and return the wireless control device to normal operation. • The wireless control device will automatically exit programming mode after 30 seconds if no buttons are pressed. The new settings will be saved only if all steps are completed. • During normal operation, the ILs on the wireless control device will not match Figure F. Figure E: Lights Off Button Control Device FASST (Front-Accessible Service Switch) For burn-in or emergency mode, pull out to send fixture to 100% light level. Indicator Lights ( IL ) Figure F: Wireless Control Device Display Chart * IL Display = on = off Notes: – Default settings for occupied/unoccupied light levels are dependent upon model purchased (50/10 or 80/20). Occupied – Timeout is the time delay until lights go to low-end after no occupancy is detected. To change the timeout of the Radio Powr SavrT occupancy sensor, see instruction sheet provided with sensor. 40% 50% 60% 70% 80% 90% 100% (High-end) Unoccupied 1%** 5% 10% 20% 30% 40% 50% (Low-end) ** To achieve 10% unoccupied light level on a reduced wattage T8, the wireless control device requires field adjustment to 1% unoccupied light level. www.lutron.com 3 Technical Support: 1.800.523.9466 Return to Factory Settings Performing these steps will disassociate all sensors that were previously associated to the fixture and return the occupied and unoccupied light levels to their factory settings. 1. On the wireless control device, quickly press T 3 times. Hold T on the 3rd press for approximately 3 seconds until the lights cycle up and down. 2. Release T , then immediately tap T 3 times quickly. 3. The lights will cycle up and down 3 times to verify that the device has been returned to factory settings. Troubleshooting Symptoms Solution(s) The light is flickering, flashing, dropping out, or does not turn on. • Check all wires, lamp connections, and sockets to ensure that they are properly connected • Ensure that 120-277 V~ power is present and properly connected to the fixtures • Ensure ambient temperature is within the specified range Lights remain at one level and do not change. • • • • Sensor cannot be associated. • Ensure that 120-277 V~ power is present and properly connected to the fixtures • Ensure the wireless control device is in programming mode and all ILs are flashing • Consult troubleshooting section of sensor instruction sheet for more solutions, or visit www.lutron.com/rps Wireless control device does not respond to button presses. • The wireless control device does not respond to manual control once a sensor is associated to it (except for re-association and programming) • Ensure that 120-277 V~ power is present and properly connected to the fixtures • Verify that ILs are illuminated on the wireless control device • Press the “ ” or "Lights Off" button on the sensor to verify that association is still active and that fixture is functioning properly Wireless control device has top and bottom ILs flashing. • Verify that all sensors are present and within RF range * • Pull out and push in FASST then press the “ ” or "Lights Off" button on each associated sensor to verify sensor battery life and association Sensor lens is flashing orange. • Sensor battery requires replacement • Sensor may be in test mode for coverage detection, press "Test" button on sensor to exit test mode Verify that all sensors are present and within RF range * Press the “ ” or "Lights Off" button on the sensor to verify that association is still active and that fixture is functioning properly Ensure that the FASST is pushed in Pull the FASST out to verify that the fixture proceeds to occupied (high-end) light level within 10 seconds * If a sensor is missing or out of RF range for two hours, the fixtures will turn on to the occupied light level and the top and bottom ILs on the wireless control devices will flash. If a sensor requires replacement, all fixtures that it was associated to will need to be returned to factory settings. The new sensor and any overlapping sensors will need to be associated/re-associated to the appropriate fixtures. Worldwide Headquarters USA Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA TEL: +1.610.282.3800 FAX: +1.610.282.1243 Technical support: 1.800.523.9466 or +1.610.282.6701 Toll-free: 1.888.LUTRON1 European Headquarters United Kingdom Lutron EA Ltd 6 Sovereign Close London, E1W 3JF, UK TEL: +44.(0)20.7702.0657 FAX: +44.(0)20.7480.6899 Technical support: +44.(0)20.7680.4481 FREEPHONE: 0800.282.107 Asian Headquarters Singapore Lutron GL Ltd 15 Hoe Chiang Road Tower Fifteen Singapore, 089316 TEL: +65.6220.4666 FAX: +65.6220.4333 Technical support: 800.120.4491 Warranty: www.lutron.com/TechnicalDocumentLibrary/Warranty_CommercialSystems.pdf Lutron, , EcoSystem and Pico are registered trademarks and Radio Powr Savr and FASS are trademarks of Lutron Electronics Co., Inc. ® © 2013 Lutron Electronics Co., Inc. www.lutron.com 4 Technical Support: 1.800.523.9466