REHEAT OVERVIEW
Page ___________ of ______________
Reznor MAPS Series systems are specifically designed for conditioning 100% outside or mixed air (outside
and return air).
Reheat Options:
You can also choose unit with a reheat option. See chart below for list of models and description.
Reznor MAPSdH Series systems use a dedicated refrigerant system that precools the incoming air under
the lowest dehumidification or cooling demand, while providing continuous reheat. Because the refrigerant
system was optimized for reheating versus cooling, the reheat system is rated in the heating mode similar to
a conventional heat pump.
Reheat Application Overview:
In conventional systems, dehumidification occurs by chilling the air below a desired dewpoint. This typically
means a 55°F dry bulb leaving coil temperature (50% Rh at 75°F).
100% outside air dehumidification will require reheat when the 55°F supply air temperature causes over-cooling of the space and increased space relative humidity.
Specifying the quality (reheat availability under all load conditions), control of reheat (staged or modulating) and
selection of the appropriate reheat system requires a working knowledge of the refrigeration cycle and HVAC
system design. Considerations for the reheat system typically fall into three application types:
Constant Reheat - Applied where the space sensible and latent loads are small in comparison to the outside air load.
When the outside air load dominates the space load, a neutral air (continuous dehumidified air
delivered between 70° and 75°F) approach may be preferred. Typical applications include corridors
and locker rooms.
Variable Reheat - Applied where the space sensible or latent loads vary in comparison to the outside air loads.
Variable sensible heat gains (solar, electric loads, occupancy etc.) affect the amount of reheat required
to maintain space temperature and relative humidity. If the equipment treats both outside air and
maintains space temperature (a sole source unit), a variable reheat system will be required. Typical
examples include surgical rooms and “clean” rooms.
No Reheat - Applied where the space sensible load is constant and much greater than the outside air load.
Typical examples include motor and telecommunications centers .
Dehumidification Model
Description:
MAPSdH units are only applicable in climates where dehumidification is required. Typically, this represents
geographical areas that see a 60°F dewpoint frequency greater than 400 hours per year. To illustrate the performance, compare the performance of a cooling-only Model RCB to the cooling/dehumidifying Model RDB at
95°/78°F dry bulb/wet bulb (See illustrations on next page).
The dehumidification unit Re-Heat Pump™ system uses a basic heat pump refrigeration circuit for dehumidification and reheat. Evaporator capacity is a small part (approximately 15-20%) of the total design capacity,
allowing continuous operation at low loads (between 55 and 60°F ambient dewpoint). The reheat pump™
system precooling evaporator coil is installed upstream of the main evaporator coil, and the reheat pump™
condenser coil is in the downstream position. The upstream precool coil tempers outside air and lowers wet
bulb depression of the air entering the main evaporator coil (86.4/75.3). Heat removed from the precool coil is
rejected to the downstream reheat coil (71.2/61.5 including compressor and fan heat of compression). In this
mode of operation the system is configured as a stand-alone neutral air unit which conditions only the outside
air to the building. If the main evaporator coil were removed, the refrigeration system would resemble a standard residential dehumidifier.
Since the dehumidification unit refrigeration circuit is independent of the main evaporative cooling coil, performance is relatively constant. This translates into ease of commissioning and verification of the Re-Heat
PumpTM system performance under mild or extreme conditions. Other package systems that use hot
gas reheat must maintain higher than needed condenser head pressures for reliable operation and adequate
reheat. Under low load conditions, poor performance of hot gas reheat and subcooling reheat systems can be
caused by compressor unloading. Service, diagnosis, and performance of hot gas reheat systems can be difficult to verify at conditions other than design.
Units with Staged
Control
Cooling Only
Cooling w/Gas Heating
Cooling w/Elec. Heating
MAPS
RCB
RDCB
RECB
MAPSdH
RDB
RDDB
REDB
Units with Modulated
Capacity Scroll
Cooling Only
Cooling w/Gas Heating
Cooling w/Elec. Heating
MAPS
RCC
RDCC
RECC
MAPS
RDC
RDDC
REDC
Cold and Humid
Temperate
and Mixed
Cool and Dry
Cool and Humid
dH
MAPSdH units include dehumidification.
Temperate and Humid
Hot and Dry
Hot and Humid
Reheat can apply in all
of these locations.
Form C-MAPS (Version D) - Page 62
DEHUMIDIFICATION (cont’d)
Page ___________ of ______________
REHEAT OVERVIEW (cont’d)
The Model RDB Re-Heat PumpTM downstream reheat (condenser) coil provides a nominal 10 to 17
degrees of “reheat” to the supply airstream. This temperature rise is accomplished with high compressor
COP’s and low air pressure drop coils. For equivalent reheat performance, other technologies, such as
heat pipes or flat plate heat exchangers may have greater than ten times the air pressure drop of the
Re-Heat Pump coils.
Additionally, performance of the heat pump is independent of the main cooling coil, while wrap around heat
pipes or flat plate heat exchangers require an active cooling coil for energy transfer. At part load, the reheat
pump can operate in a stand alone mode to provide both dehumidification and reheat.
While the dehumidification unit compressor consumes additional energy during dehumidification modes, the
year round benefit of reduced fan energy will result in lower annual energy costs.
55.3°F/55.2°F
Supply
Air
to
Space
73.2°F/62.0°F
Upstream Pre-Cool Coil
Outside
Air 95°F/78°F
Intake
Evaporator Coil
Optional
Horizontal or
Vertical (Down)
Supply Air
72.5°F/61.7°F
Model RDB Performance at 95°/78°F Outside Air and a
Nominal Airflow Rate
Downstream Re-Heat Coil
Supply
Air
to
Space
61.2°F/60.1°F
60.2°F/60.0°F
Optional
Horizontal or
Vertical (Down)
Supply Air
Evaporator Coil
Model RCB Performance at 95°/78°F Outside Air and a
Nominal Airflow Rate
Outside
Air 95°F/78°F
Intake
SPACE REHEATING
REQUIREMENTS
The amount of reheat depends on the temperature leaving the cooling coil and the minimum available space
heating gain at part load conditions. A simple approximation is shown below:
APPLICATION NOTES:
The MAPS Series are replacement air systems which treat up to 100% outside air. They can be applied in a
variety of geographical locations and conditions.
The MAPSdH Series include a specialty reheat system and are targeted for temperate and humid climates.
These units are typically applied as a neutral air system that provides dehumidified replacement air between
70° and 75°F.
The following topics summarize typical equipment considerations found in specifying replacement air systems:
Zone Outside Air Changeover Rates
When evaluating the suitability of staged capacity control, the outside air changeover rate to the zone should
be calculated. Use the formula listed below.
High air changeover rates may require special control sequences, air distribution design, and cooling-heating
modulation controls versus step control. As a guideline, modulation should be evaluated when the changeover
rate exceeds 8 ACH (1 outside air change for every 7.5 minutes). Since heating design temperature difference
is typically greater than cooling, modulation of the heating system may be more critical.
Design Temperature Difference
As design extremes increase, staging or modulation of equipment capacity becomes increasingly important.
Examining the lowest stage or step of equipment capacity relative to the lowest load condition can indicate if
capacity modulation is required.
System Type
Generally products that deliver 100% outside air quantities fall into one of three basic system types. They
include:
●● Neutral Air - Outside air is cooled, dehumidified, and heated to room conditions (70 to 75°F).
●● Tempering Air - Outside air is cooled and mixed with conditioned return air.
●● Sole Source - Conditions both outside air and the internal building loads - not recommended tight or critical
space control applications.
Identifying the system type can aid the designer in evaluating the appropriate equipment for each application.
A more detailed discussion can be found in Application Bulletin RZ-T-PC.
The mechanical cooling system uses 3-4 unevenly sized direct expansion compressors and coils to optimize
the number of cooling stages. In addition, the use of interlaced and split coils provide excellent part load
performance.