Detailed Specifications &
Technical Data
YJ55204
High Paired – Category 3 Unbonded – Armored Double PE Jacket Cable
For more information please
call
1-800-Belden1
See Put-ups and Colors
Related Documents: No.8 for
Data Twist Cables (Modified
Western Electric).pdf
Description:
24 AWG solid bare copper conductors, non-plenum, Polyolefin insulation, twisted pairs, see color code chart (below), Flooding, foil
shield, PE inner jacket, steel wire armor (SWA) and PE outer jacket (black).
PHYSICAL CHARACTERISTICS:
CONDUCTOR:
Number of Pairs
25
Total Number of Conductors
50
AWG
24
Stranding
Solid
Conductor Material
BC - Bare Copper
INSULATION:
Insulation Material
PO – Polyolefin
Pair Color Code Chart
Pair Number
Insulation Color
Wire 1
Wire 2
1
White/Blue
Blue/White
2
White/Orange
Orange/White
3
White/Green
Green/White
4
White/Brown
Brown/White
5
White/Grey
Grey/White
6
Red/Blue
Blue/Red
7
Red/Orange
Orange/Red
8
Red/Green
Green/Red
9
Red/Brown
Brown/Red
10
Red/Grey
Grey/Red
11
Black/Blue
Blue/Black
12
Black/Orange
Orange/Black
13
Black/Green
Green/Black
Page 1 of 4
Detailed Specifications &
Technical Data
YJ55204
High Paired – Category 3 Unbonded – Armored Double PE Jacket Cable
14
Black/Brown
Brown/Black
15
Black/Grey
Grey/Black
16
Yellow/Blue
Blue/Yellow
17
Yellow/Orange
Orange/Yellow
18
Yellow/Green
Green//Yellow
19
Yellow/Brown
Brown/Yellow
20
Yellow/Grey
Grey/Yellow
21
Violet/Blue
Blue/Violet
22
Violet/Orange
Orange/Violet
23
Violet/Green
Green/Violet
24
Violet/Brown
Brown/Violet
25
Violet/Grey
Grey/Violet
OVERALL CABLING:
Overall Cabling Core Configuration
6 × 4 Pairs+ 1 Pair
Flooding Material
Non-drip Flooding Compound
Overall Cabling Core Wrap
Polyester Tape
OUTER SHIELD:
Outer Shield Type
Tape
Outer Shield Material
Polyester – Aluminum Foil – Polyester Tape
Outer Shield % Coverage
100 %
INNER JACKET:
Inner Jacket Material
PE – Polyethylene
Inner Jacket Nom. Wall Thickness
1.0 mm
Inner Jacket Color
Black
ARMORING:
Armor Material
Steel Wire
Steel Wire Nom. Diameter
1.2 mm
OUTER JACKET:
Outer Jacket Material
PE – Polyethylene
Outer Jacket Nom. Wall Thickness
1.8 mm
Outer Jacket Color
Black
OVERALL NOMINAL DIAMETER:
Overall Nominal Diameter
23.0 mm
MECHNICAL CHARACTERISTICS:
Bulk Cable Weight
845 kg/km
Max. Recommended Pulling Tension
1000 N
Page 2 of 4
Detailed Specifications &
Technical Data
YJ55204
High Paired – Category 3 Unbonded – Armored Double PE Jacket Cable
Min. Bend Radius (Install)
460 mm
APPLICABLE SPECIFICATION AGENCY COMPLIANCE:
APPLICABLE STANDARDS:
IEC Specification
IEC 11801 Category 3
TIA/EIA Specification
ANSI/EIA/TIA-568-B.2 Category 3
EU CE Mark (Y/N)
N
EU RoHS Compliant (Y/N)
Y
EU RoHS Compliance Date
Sept 2008
FLAME TEST:
Flame Test(Y/N)
N
PLENUM/NON-PLENUM:
Plenum (Y/N)
N
ELECTRICAL CHARACTERISTICS:
Nom. Mutual Capacitance @ 1 KHz
6.6 nF/100m
Maximum Capacitance Unbalance to Ground
330 pF/100m
Maximum Delay @ 16 MHz
598 ns/100m
Maximum Delay Skew
45 ns/100m
Maximum Conductor DC Resistance @ 20 Deg.C
9.5 Ohms/100m
Maximum DCR Unbalance @ 20 Deg.C
5%
ELECTRICAL CHARACTERISTICS - PREMISES:
Premise Cable Electricals Table 1:
Frequency
(MHz)
Max. Attenuation
(dB/100m)
Min. NEXT
(dB)
Min. Structural
Return Loss (dB)
0.772
2.2
43
12
Fitted Impedance
(Ohms)
100 ± 15
1
2.6
41
12
100 ± 15
4
5.6
32
12
100 ± 15
10
9.7
26
12
100 ± 15
16
13.1
23
10
100 ± 15
NOTES:
Notes
Jacket sequentially meter marked.
PUT-UPS AND COLORS:
Item
Description
Put-Up (metre)
Jacket Color
YJ55204 0101000M
25 PR #24 PO SH FL PE SWA PE CAT3
1000M
BLACK
* Other put-ups available upon request.
Page 3 of 4
Detailed Specifications &
Technical Data
YJ55204
High Paired – Category 3 Unbonded – Armored Double PE Jacket Cable
Revision Number: 1
Revision Date: 11/24/2010
___________________________________________________________________________________________
©Copyright 2010 Belden, Inc
All Rights Reserved.
Although Belden ("Belden") makes every reasonable effort to ensure their accuracy at the time of this publication, information and
specifications described herein are subject to error or omission and to change without notice, and the listing of such information and
specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether
express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special,
punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an
action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information
or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with the following environmental regulations: California Proposition 65 Consent
Judgment For Wire & amp; Cable Mfgs.(San Francisco Superior Court Nos. 312962 And 320342); EU RoHS (Directive 2002/95/EC,
27-Jan2003); Material manufactured prior to the compliance date may still be in stock at Belden facilities and in our Distributor's
inventory. EU ELV (Directive 2000/53/EC, 18-Sept-2000); EU WEEE (Directive 2002/96/EC, 27-Jan-2003); And EU BFR
(Directive 2003/11/EC, 6-Feb2003). The information provided in this Product Disclosure, and the identification of materials listed as
reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge, information and belief at the date
of its publication. The information provided in the Product Disclosure is designed only as a general guide for the safe handling,
storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be
considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible
for determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive
93/68/EEC.
Page 4 of 4