Series 105 Signalling devices General Climatic protection The standard versions are suitable for use in the following climates: • Temperate climate cat. 23/50 (DIN 50014) • Wet climate cat. 23/83 (DIN 50015) • Hot wet climate cat. 40/92 (DIN 50015) • Variable wet climate cat. FW 24 (DIN 50016) Standards Signalling devices Series 105 signalling units are used to indicate the electric equipment power supply conditions. For this purpose the devices shall be wired after the main disconnecting switch and clearly in view when the cabinet´s doors are opened. Series 105 DTL devices can be used on three-phase lines with or without the neutral wire or single-phase power lines, indicating the hazardous condition due to the applied voltage. Three luminous red lamps are used. The flashing devices are normally used in combination with limit switches contacts NC type 114FCT03 that provides insertion when the cabinet door are open only. Intro CEI, IEC, VDE, BSI and UTE Approvals A CE, UL, CSA Suggested connections Indicates the presence of 3, 2 or 1 phase only by means of the relative lamp. Indicates the presence of 3 or 2 phases by means of the relative lamp. One phase only is not indicated ( all lamps OFF ) B C 3-phase line with insulated neutral 3-phase line with grounded neutral Indicates both phases with 3 lamps ON at same time. One phase only is not indicated ( all lamps OFF ) Single phase-line (alternative diagram) Single-phase line (general diagram) D 3-phase line without neutral 1. Phase to phase connection on a 3 phase line with grounded neutral. Indicates the presence of 2-phases or 1 only with the 3 lamps ON at the same time. 2. Phase to neutral connection on a 3 phase line with grounded neutral or phase to phase by a matching transformer with one phase grounded. Indicates the presence of the ungrounded phase with the 3 lamps ON at the same time. No indication occur if the ungrounded phase is missing ( all lamps OFF ). E F G Specifications Temperature ranges Operation Storage Degree of protection (according to IEC 529) from -25ºC up to +70ºC from -40ºC up to +70ºC IP 20 H Electrical Rated insulation voltage according to EN 60947.1 Impulse withstand voltage according to EN 60947.1 Electrical input Connections Clamping capacity 690V 4kV 2mA max. Terminal strip with numbered terminals, accessible from outside protected against accidental contacts according to DIN 57106 and IP 20 according to IEC 529 Maximum one flexible conductor 12 AWG (3.3mm2) I J/X Order codes ! pg. F.58 Dimensional drawings ! pg. F.60 F.57 Series 105 Flashing devices Signalling devices Supply voltage Three-phase (50-60Hz) 220V Single-phase (50/60Hz) 110-127V 380-600V 690V 220-350V Cat. no Ref. no. Pack 105DTL220 132230 1 105DTL500 105DTL690 132231 132232 1 1 3 pole limit switch for device control Protection degree IP40 Cables entry PG11 Operation force 8.5 N min. Contacts Cat. no Ref. no. Pack 3NC 114FCT03 130320 25 IP65 PG11 8.5 N min. 3NC 114FCT03T 130321 25 Cat. no Ref. no. Pack 105 PT 132234 50x5 Paralell bridge for 3 poles limit switches Intro A Single door protection unit B C D The unit includes the following components: • one flashing device105DTL220 or 105DTL500. • one 3-pole limit switch 114FCT03 for connection of the flashing device • one electrical interlock device and panel light 105GIL or 105GIL10. • one mounting plate 105PM on which are fitted on the above devices. If two doors have to be protected (as double enclosure closing on the middle) the mounting plate shall be fitted also one limit switch114FCT03 and one device 105GIL or 105GIL10. Approvals: UL (USA) - CSA (Canada) Supply voltage E F G H I J/X F.58 Cat. no Ref. no. Pack Three-phase (50-60Hz) 220V 220V Single-phase (50/60Hz) 110-127V 110-127V Tripping coil Shunt trip Undervoltage trip 105GP1P220 132250 105GP1P220M 132251 1 1 380-600V 380-600V 220-350V 220-350V Shunt trip Undervoltage trip 105GP1P500 132252 105GP1P500M 132253 1 1 Series 105 Electrical interlock device and cubicle lighting (1) Approvals: UL (U.S.A.) - CSA (Canada) Tripping coil Cat. no Ref. no. Pack Shunt trip 105 GIL 132240 1 Undervoltage trip 105 GIL 10 132241 1 Signalling devices The switch can be directly driven by the enclosure door. If several doors are employed, one switch per door shall be used. When properly connected, the following functions are provided: • Position 1 (pushed) door closed: light OFF, tripping coil of main switch unpowered ( normal equipment operation ) • Position 2. (free) door opening: light ON, tripping coil of main switch powered (equipment shall cut-out automatically). • Position 3 (pulled) door open: light ON, tripping coil of main switch unpowered (adjustment on the equipment of dry checks). When door is closed again, the switch revert automatically from position 2 or 3 to position 1. Terminals have IP2X protection degree according to IEC/EN 60529 Intro A Electrical interlock device (1) The switch is directly driven by the enclosure door. If several doors are employed, one switch per door is needed. When properly connected, the same functions of devices above shall be provided but without enclosure control light. Terminals have IP2X protection degree according to IEC 529 Tripping coil Cat. no Ref. no. Pack Shunt trip 105 CI 132242 B C D 1 E Undervoltage trip 105 CI 10 132243 1 F G Mounting plate Cat. no Ref. no. Pack 105 PM 132244 1 H I (1) For electrical performance and features of contact blocks please see F.42 J/X F.59 Series 105 Signalling devices Dimensional drawings Series 105 - Flashing devices Series 105 - Single door protection unit Series 105 - Electrical interlock and cubicle lighting Series 105 - 3 pole limit switch for device control Series 105 - Electrical interlock device Series 105 - Mounting plate Intro A B C D E F G H I J/X F.60 Series NLT Light towers Signalling devices • Outstanding modular concept. One terminal unit can be combined with up to seven modular signal units. • Steady light units, flashing light units, strobe light units, LED light units. • The buzzer elements emit a clearly audible dual-tone signal for maximum safety. • A bayonet mounting, through a simple manual operation, allows a quick and simultaneous method of joining the signal units together and the electrical connection of them. • Compact dimension Ø70mm. • IP65 for use in extreme conditions. • Captive screw cable connectors, located with terminal unit are easy to reach and guarantee a quick and neat electrical connection. • The special design makes maintenance quick, easy and carried out in complete safety and without tools. • The high quality of materials used to manufacture the lenses ensures the light output is at the highest luminous intensity, combined with a sturdy construction and a good resistance to aging. Intro Marking A B Meaning of optical signals Colour Meaning Operating state C Red Extreme danger Hazardous conditions Immediate action necessary D Yellow / Amber Beware Warning conditions imminent Abnormal state Monitor or action as necessary E Green Normal conditions No actions required Blue Conditions requiring defined action Discontinuity Intervention mandatory White / Clear No particular meaning Other state Can be used as required Signal tone Meaning Operating state Intermittent modulated tone Linear tone Danger Immediate action necessary Safety No actions required F G H I J/X F.62 Meaning of audible signals (EN 981, IEC 73) Series NLT Audio units Light units NLT1... Steady light unit NLT73BD - Protection degree IP54 Tone: pulsating Audio frequency: 2900Hz Pulsating tone frequency: 0,5Hz according to EN 457 - Sound level at 1 m.: 90 dB (A) - Supply voltage: 24V AC/DC - Current consumption: 20mA - With socket BA15D for filament bulbs (7W max.) and LEDs - Supply voltage: 240V AC/DC - Current consumption (with 5W lamps): 24V 210mA 240V 22mA Flashing light unit NLT75AJ - NLT75AN Pulsating or constant tone - With socket BA15D for filament bulbs (7W max.) and LEDs - Supply voltage: 24V AC/DC, 115V AC, 240V AC - Current consumption (with 5W lamps): 24V DC 130mA NLT3... 24V AC 115V AC 240V AC 145mA 25mA 15mA Strobe light unit - Lamp type: 4 Joule xenon lamp - Supply voltage: 24V AC/DC, 115V AC, 240V AC - Current consumption: 24V DC 75mA Pulsating or constant tone, adjustable by removing or inserting bridge JP1 in the printed circuit. - Protection degree IP54 - Tone: pulsating or constant - Audio frequency: 2600Hz according to EN 457 - Pulsating tone frequency: 1Hz according to EN 457 - Sound level at 1 m.: pulsating tone: 95 dB (A) constant tone: 93 dB (A) - Supply voltage: 115VAC (NLT75AJ) / 240VAC (NLT75AN) - Current consumption: 115VAC 40mA Light towers NLT2... 115V 43mA Pulsating tone Intro 240VAC 30mA A NLT75BD Modulated tone - Protection degree IP54 - Audio frequency: 2500 - 2800Hz according to EN 457 - Sound level at 1 m.: max. 90 dB (A) - Supply voltage: 24V AC/DC - Current consumption: 40mA 24V AC 115V AC 240V AC 135mA 20mA 15mA - Flash frequency: 1,4Hz (84 flashes per min.) according with EN 60073 B C 16 sounds can be selected by means of the dip switch D NLT77BD Pulsating tone - Protection degree IP65 - Audio frequency: 1200 - 2600Hz according to EN 457 - Sound level at 1 m.: max. 84 dB (A) - Supply voltage: 24V AC/DC - Current consumption: 40mA NLT77AJ - NLT77AN Pulsating or constant tone Pulsating or constant tone, adjustable by removing or inserting bridge JP1 in the printed circuit. - Protection degree IP65 - Tone: pulsating or constant - Audio frequency: 2600Hz according to EN 457 - Pulsating tone frequency: 1Hz according to EN 457 - Sound level at 1 m.: pulsating tone: 78 dB (A) constant tone: 75 dB (A) - Supply voltage: 115VAC (NLT77AJ) / 240VAC (NLT77AN) - Current consumption: 115VAC 40mA E F G H I J/X 240VAC 30mA F.63 Series NLT Light units Red Signalling devices Steady light units (bulb not included) Intro Amber Yellow Green Blue Clear Supply voltage Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Pack 12...240V NLT1R 222230 NLT1A 222231 NLT1G 222232 NLT1V 222233 NLT1L 222234 NLT1I 222235 1 Flashing light units 24V AC/DC NLT2BDR 222236 NLT2BDA 222237 NLT2BDG 222238 NLT2BDV 222239 NLT2BDL 222240 NLT2BDI 222241 1 (bulb BA15D 115V AC NLT2AJR 222242 NLT2AJA 222243 NLT2AJG 222244 NLT2AJV 222245 NLT2AJL 222246 NLT2AJI 222247 1 filament) 240V AC NLT2ANR 222248 NLT2ANA 222249 NLT2ANG 222250 NLT2ANV 222251 NLT2ANL 222252 NLT2ANI 222253 1 (bulb included) Flashing light 24V AC/DC NLT2BDLR 222289 NLT2BDLA 222290 NLT2BDLG 222291 NLT2BDLV 222292 NLT2BDLL 222293 NLT2BDLI 222294 1 units (bulb LED) 115V AC NLT2AJLR 222295 NLT2AJLA 222296 NLT2AJLG 222297 NLT2AJLV 222298 NLT2AJLL 222299 NLT2AJLI 242464 1 (bulb included) 240V AC NLT2ANLR 222301 NLT2ANLA 222302 NLT2ANLG 222303 NLT2ANLV 222304 NLT2ANLL 222305 NLT2ANLI 222306 1 A B C D E F G H I J/X F.64 Strobe light units 24V AC/DC NLT3BDR 222254 NLT3BDA 222255 NLT3BDG 222256 NLT3BDV 222257 NLT3BDL 222258 NLT3BDI 222259 1 (bulb included) 115V AC NLT3AJR 222260 NLT3AJA 222261 NLT3AJG 222262 NLT3AJV 222263 NLT3AJL 222264 NLT3AJI 222265 1 240V AC NLT3ANR 222266 NLT3ANA 222267 NLT3ANG 222268 NLT3ANV 222269 NLT3ANL 222270 NLT3ANI 222271 1 Series NLT Audio units Protection degree Supply voltage IP54 24V AC/DC NLT73BD 222278 1 IP65 24V AC/DC NLT77BD 222279 1 IP54 115V AC 240V AC NLT75AJ 222287 NLT75AN 222288 1 1 IP65 115V AC 240V AC NLT77AJ 222280 NLT77AN 222281 1 1 IP54 24V AC/DC NLT75BD 222286 1 Blue White Pulsating tone Pulsating or constant tone Adjustable by removing or inserting bridge JP1 in the printed circuit The audio units can only be mounted as final top unit (top cover included) Bulbs Supply voltage LED - BA15D Red Amber Yellow Green Light towers Modulated tone 16 sounds can be selected by means of dip switch Cat. no. Ref. no. Pack Intro Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Cat. no. Ref. no. Pack 24V AC/DC BA15D24LR 222330 BA15D24LA 222331 BA15D24LG 222332 BA15D24LV 222333 BA15D24LL 222334 BA15D24LB 222335 115V AC BA15D115LR222336BA15D115LA222337BA15D115LG222338BA15D115LV 222339 BA15D115LL 222340BA15D115LB222341 240V AC BA15D230LR222342BA15D230LA222343BA15D230LG222344BA15D230LV 222345 BA15D230LL 222346BA15D230LB222347 1 1 1 A B Incandescent BA15D Supply voltage 12V 24V 30V 115V 240V Clear Cat. no. Ref. no. Pack BA15D125 222348 BA15D245 222349 BA15D305 222350 BA15D1155 222351 BA15D2305 222352 5 5 5 5 5 C D E Terminal Cat. no. Ref. no. Pack Terminal unit with top cover NLT9TC 222282 1 F G Base with tube H Cat. no. Ref. no.Pack NLT5BT Base + tube height 100mm Base + tube height 100mm, 90° fixing NLT90BT 222307 1 1 Tube height extension 100mm NLT5ET 222285 1 222284 I J/X F.65 Series NLT Technical data Conformity to standards Signalling devices Materials Intro Rated insulated voltage Operating temperature Protection degree (according to EN 60529) Colours (according to EN 60073) Lamp type Steady/flashing units Strobe units Nr. of combined units Connection Connection identification code EEC regulation 89/336 electromagnetic compatibility EEC regulation 73/23 low voltage, including amendment EEC 93/68 All NLT range are made and tested in full compliance with: EN 60947-5-14 (VDE 0470, IEC 60947) CE, cUL US Polycarbonate Visual and audio signal units, terminal unit, top cover, base and extension tubes 250V max. -20°C ... +60°C (except version with bulb 12V = 40°C) IP65 (IP54 for audio units types NLT73xx and NLT75xx) (indicators must be correctly assembled with top cover, gasket or PG conduit fitting) Amber, Blue, Yellow, Clear, Red and Green Bayonet type BA15D socket: filament (7W max.) or LED Xenon lamps Up to 7 modular units Captive screw cable connectors (max. cable size 1.5mm2) inside terminal sleeve «C» is common to allsignal units. They are numbered 1/7 from base to top Mechanical characteristics Mounting of the units Average torque Unfastening of the units Average torque Vibration resistance Mounting 2.4Nm 2.3Nm 2g min. (10-150Hz) according to IEC 68-2-6 Direct through terminal unit or with base and tube A B Dimensions C Base mounting Terminal unit mounting Base mounting 90º fixing Drilling and mounting Dimensions with base Ø70 D E F G H I J/X F.66 Drilling and fixing dimensions with terminal unit. Two separate hole spacings. Series NLT Modular system Place signal beacon unit onto terminal unit (1) align guide marks and twist clockwise till they are locked (2) + (3) (1) (2) (3) Light towers Intro Follow the same steps to add more signal units (4) + (5) + (6) The audible element can be mounted as final top unit, as it is complete with a top cover. (4) (5) (6) A B C D E To fix extension tube (base always included), insert it into opening on the underside of the terminal unit and tighten screw on the side (7). To reach the screw cable clamp terminals, remove black disc first, prising with a small screwdriver (8). Connect to terminals (coloured units are numbered from base to top). To place terminal back into position, align the guiding marks (9) and press inwards. (7) (8) F G (9) H I J/X F.67 Series IP Foot switches General Control and signalling units Foot switches , for intensive services suitable for controlling and monitoring of low voltage AC and DC electrical circuits. Intro A Climatic protections The standard versions are suitable for use in the following climates: • Temperate climate cat. 23/50 (DIN 50014) • Wet climate cat. 23/83 (DIN 50015) • Hot wet climate cat. 40/92 (DIN 50015) • Variable wet climate cat. FW 24 (DIN 50016) Standards IEC 947-5-1, CEI EN 60947.5.1 VDE 0660 Approvals CSA, UL B Specifications Temperature ranges C D E F Operation Storage Degree of protection (according to IEC 529) Vibration resistance Mechanical endurance Electrical Rated insulation voltage according to EN 60947.1 Insulation class according to VDE 0110 Electric shock protection according to IEC 536 Short-circuit prot. according to IEC 269.1 and 269.3 Electrical performances of the contact blocks Voltage Current Ue Ie (V) (A) 24 6 48 6 110 6 220 6 380 4 Snap action contacts Category AC 15 Voltage Current Ue Ie (V) (A) 24 6 48 6 110 6 220 5 380 4 Category DC 13 Voltage Current Ue Ie (V) (A) 24 1 48 0,8 110 0,7 220 0,3 Connection Cables entries IPA1, IPA2, IPB1, IPB2 IPA1-P I J/X Order codes ! pg. F.69 Dimensional drawings ! pg. F.69 F.68 500V Group C Class I 10A gL fuses Rated thernal current (Ith) Performances according to EN 60947.5.1 Slow motion contacts Category AC 15 G H from -30ºC up to +80ºC from -30ºC up to +80ºC IP 65 20g (10 up to 55Hz) 2 x 107 for all the types 10A Same polarity for both slow motion and snap action contacts 1 x M20 2 x M20 Series IP Foot switches - order codes Slow break Snap action Function (1) N Cat. no Ref. no. Cat. no Ref. no. Cat. no Ref. no. Cat. no Ref. no. Pack IPA1-N211B 132170 – – IPA1-N411B 132198 IPA1-N422B 132213 1 N D R IPB1-N211B – – 132172 IPB1-N411B – IPB1-R411B 132201 – 132203 IPB1-N422B IPB1-D422B – 132215 132216 1 1 1 N211B 116113 N411B 116663 N422B 116665 1 ONE pedal Without guard Spare microswitches IPB1-N222B 132186 – – – – N222B 116664 (1) Function N Normal operation. When the pedal is pressed the contacts change position. When released they return to their position. Function D Two-stage operation. Used with two contacts blocks. When the pedal is pressed to the first point, the contacts of the first block switch; when pressed as far as the second point the contacts of the second block switch and the first block stays in the same position. Function R Normal operation with potentiometer. When the pedal is pressed, the contacts change position at the same time as the potentiometer is operated. When released, the contacts and potentiometer return to their initial position. Positive opening. Foot switches ONE pedal With guard Intro A B C Dimensional drawings Foot switches without protective guard One pole D Foot switches with protective guard One pole E F G H I J/X F.69 Series IP Safety foot switches Control and signalling units Operation 1 Pedal operation up to the trigger point The operating contact is closed, the operating process is started 2 Operation past the trigger point in emergency cases The operating contact is opened and latched and the process is stopped. Also if the device is unused, the latch remains in the off-position in this phase. Uncontrolled restart is prevented 3 Reset function Only after the danger has passed can the contacts be manually unlatched (push-button on the side). The operating process can now be restarted by pushing the pedal up to the triggering point. OFF Approvals Intro 1 A ON Standards EN 60947-1 / IEC 60947-5-1 B C 2 Emergency stop Features 3 D Enclosed in metal with aluminium protection cover, safety latch function “OFF-ON-OFF” with manual reset. E Technical data Order codes Cat. no. Ref. no. Pack IPSF1 223000 1 Switching diagram F 1) Trigger point 2) Latched position 1) 2) G H I J/X F.70 Rated insulation voltage Ui Thermal continuous current Ithe Switching frequency Mechanical operational life number of switching cycles Ambient temperature Cable conduits Protection degree Actuating force (approx.) Trigger point Weight - Slow-action contact - Snap-action contact - Trigger point - Latch function - Making current according to: EN/IEC 60947-5-1 AC15/240V/3A max. 400VAC max. 10A max. 50/min. 10 x 106 -30°C to +80°C (3x) M20x1.5 IP65 10N 200N 1.5 kg Dimensional drawings