Redwood Sensor - Model 3M1 Installation

Redwood Sensor - Model 3M1
Installation Instructions
Model No:
SEN-3M1-W
The Redwood Sensor controls and dims a connected Redwood Ready third-party LED fixture, collects data on light levels, temperature and motion, and transmits this environmental data back to the Redwood Engine. The Engine powers
the Sensor via low voltage cable.
The Redwood Sensor is easily installed in the ceiling tile or junction box near the
fixture and accepts standard category 5e, 6 or 6a cable via RJ45 connectors for
fixture and data connections. In addition, the Sensor can also connect to an
electrical light switch with 18AWG via snap-in connectors to enable manual lighting control.
Redwood Sensor - Model 3M1 requires Redwood Engine 3 - Model 4834 running
3.1 software.
Redwood Sensor 3 Installation Instructions
Specifications
MECHANICAL
•Dimensions: 1" (25.4 mm) inner
diameter x 2.5" (63.5 mm) H x 1.6"
(40.6 mm) outer diameter
• Weight: 0.25lbs (0.11kg)
• For indoor use only
• Operating temp: 32°F to 122°F;
0°C to 50°C
E L E C T R I C A L / D ATA
COMPLIANCE
• Input/output to Redwood Engine:
RJ45 connector to one channel
•Class 2 electrical device
• Input/output to Fixture: RJ45 connector
• UL/cUL listed–File E336145
• Input/output to electrical light switch:
three 18AWG snap-in connector ports
• T-Mark compliant–Certificate No.
T72120409
• Transfers up to 34W per fixture
• Environmental: IEC 60950; Pollution
Degree 2
• Storage temp: –4°F to 140°F;
–20°C to 60°C
• Nominal stand by power consumption: 500mW
• Operating Humidity: 10% to 80% RH
non-condensing
• Maximum power consumption: 10mW
• Storage Humidity: 5% to 95% RH
non-condensing
• Light level sensor for daylight harvesting functionality
•FCC Part 15 Class A
• CE compliant
• RoHS compliant
• Designed for California Title
24-2008 compliance
• Ambient temperature sensor
• UL certified for installation in air- handling spaces per UL 2043
º Accuracy: +/–1.8°F (+/–1°C)
• Made in the U.S.A.
º Range: 32°F to 212°F (0°C to 100°C)
• Passive Infrared (PIR) sensor for
motion detection
Preparation
•For a lay-in fixture (2x2, 2x4 or 600x600), sensors need to be placed in the ceiling tile adjacent to the fixture. For downlights, sensors can be placed in the same ceiling tile. Fixtures
come with attached RJ45 plugs and wires. This wire will limit the distance of the sensor from
the fixture.
• Sensors should be placed close to the fixture, preferably within 2 inches (50.8mm) in order to obtain
accurate light level readings and enact daylight
harvesting accurately. Determine where in the ceiling tile the Redwood Sensor needs to be installed;
refer to the diagram on the next page.
2
Redwood Sensor 3 Installation Instructions
I M P O R TA N T N O T E
• Be sure the Sensor is clear of any other equipment above the tile.
• The plastic Sensor cap should be tight against the ceiling tile.
• The Sensor may be rotated inside the ceiling tile’s hole, but it must remain perpendicular to the tile.
• Redwood recommends that you do no place sensors near heating vents, AC units or any other electrically dynamic
system.
• Sensors should be placed in areas with minimal air movement to ensure proper operation of the DPIR motion sensor.
• The Redwood Sensors have been tested by UL to UL2043 which ensure slow smoke-emitting characteristics and
suitable fire resistance for equipment that may be installed in environmental air-handling spaces, as described in Article
300.22(c) of the NEC (2008).
• When the product is installed in air-handling spaces, such as above some suspended ceilings, the cabling employed
should be suitable under NEC (2008) Article 800.154 and marked accordingly for use in plenums and air-handling
spaces with regard to smoke propagation, such as CMP. The products and wiring should be installed in accordance
with all applicable local regulations and practices.
Installation Instructions
Step 1: Within 2" (50mm) of the fixture, drill a 1" (25.4mm)
diameter hole in the ceiling tile.
Step 2: Carefully push the Sensor through the ceiling tile.
Step 3: Twist and lock the adjusting height Sensor ring to
tighten the Sensor against the tile.
Step 4: Connect fixture to the Sensor 3 white RJ45 jack.
Step 5: Connect the Sensor 3 black RJ45 jack back to the
Redwood Engine using category cable.
RJ45 CABLE BACK
TO ENGINE
SLIDE SENSOR RING OVER
SENSOR POD AND TWIST TO LOCK
SO SENSOR IS TIGHT AGAINST THE TILE
RJ45 CUSTOMER
LUMINAIR CABLE
LUMINAIRE
CEILING TILE
1.0" (25.4mm)
DRILL
HOLE FOR REDWOOD
SENSOR POD
2.0 "
PUSH SENSOR MODULE
THROUGH TILE UNTIL
SENSOR CAP IS FLUSH
I M P O R TA N T N O T E
Mounting Instructions for Redwood Sensor
3
Redwood Sensor 3 Installation Instructions
Connecting an Electrical Light Switch
The Redwood Sensor can be connected to a single pole, single throw (SPST) electrical light switch using 18AWG wire.
(This does not apply to connecting the Redwood Dimmer or Scene Control Wall Switch). When connected to an individual sensor in a designated room, the electrical light switch will control all of the fixtures in that room manually.
Preparation
•Determine location for the wall switch and
associate Sensor.
• Lay low-voltage two 18AWG cables from the
Sensor to the wall switch location. Using
18/2 jacketed solid core bell wire is recommended for this application.
• Strip the end of the 18AWG cables by 1/4”
(0.6cm).
• Cut or use an existing standard-sized wallplate opening for a NEMA standard, OTS
electrical switch box with an open back.
Installation Instructions
Step 1: Make sure the light switch is in the “ON” position.
Step 2: Run 18AWG wire from the light switch through the
light switch electrical box.
Step 3: Connect one end of the wire to Port C on Sensor 3.
Step 4: Connect the remaining end to either Port A or Port
B.
Step 5: Place the switch faceplate on top of the light
switch in the electrical switch box and tighten the
screws.
Coverage Diagrams
The motion coverage pattern diagrams of the Redwood Sensor are included below. These assume that a Sensor is
installed in a ceiling that is 10 feet (305cm) in height; the following diagrams illustrate the expected motion sensing
coverage for each Redwood Sensor.
Ceiling
Height
10ft
Average
Desktop
Level
Fine Grain Motion
8ft 6in [260cm]
Coarse Grain Motion
10ft 10in [330cm]
Fine and Coarse Grain Detection Ranges at Ceiling Height of 10 ft (305cm)
Fine Grain Motion
8ft 6in [260cm]
Coarse Grain Motion
10ft 10in [330cm]
Fine and Coarse Detection Ranges at Ceiling Height of 10 ft (305cm)
4
Redwood Sensor 3 Installation Instructions
Ordering Information
Contact Information
Phone Number: (510) 270-5360 (Select Option 1)
Redwood Systems
3839 Spinnaker Court
Fremont, CA, 94538
1-800-840-0709 (USA)
1-510-270-5360 (International)
www.redwoodsystems.com
www.commscope.com
support@redwoodsystems.com
SKU Number
Description
SEN-3M1-W
Redwood Sensor
For RoHS Inquiries:
CommScope Inc.
Corke Abbey, Bray
Co. Dublin, Ireland
Attn: Legal Department
FCC CLASS A REGULATORY STATEMENT — UNITED STATES
Note: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
FCC CLASS A REGULATORY STATEMENT — EUROPE AND AUSTRALIA
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
LIMITED WARRANTY
Redwood warrants during a warranty period of twelve (12) months from delivery that the products as delivered shall be free of material defects and shall conform in all material respects to Redwood’s applicable specifications as set forth in this documentation. As Redwood’s sole and exclusive obligation and Buyer’s sole and exclusive remedy for material breach of the foregoing
warranty, Redwood shall, at its option and in accordance with its standard RMA procedures, refund the purchase price, or repair or replace the nonconforming products, provided proof of purchase and written notice of non-conformance are received by Redwood within the warranty period. This warranty shall not apply to products that Redwood determines have been subjected to
testing for other than specified electrical characteristics or to operating and/or environmental conditions in excess of the maximum values established by Redwood, or have been the subject of
mishandling, misuse, neglect, improper repair, alteration, damage, assembly, or processing that alters physical or electrical properties, or have been damaged in transit. This warranty excludes
all costs of shipping, customs clearance and related charges outside the contiguous 48 United States and Canada. In the event no defect or breach of warranty is discovered by Redwood upon
receipt of returned products, the products will be returned at Buyer’s expense. Any repair or replacement provided to Buyer will not extend the warranty period for the products in question.
Excluded from the foregoing warranty are parts defined by Redwood as “consumable.”
DISCLAIMER OF WARRANTY. THIS WARRANTY EXTENDS TO BUYER ONLY AND NOT TO BUYER’S CUSTOMERS OR USERS OF BUYER’S PRODUCTS AND IS IN LIEU OF, AND REDWOOD EXPRESSLY DISCLAIMS, ALL OTHER WARRANTIES, WHETHER EXPRESS, IMPLIED OR STATUTORY, INCLUDING, BUT NOT LIMITED TO, ANY WARRANTIES OF MERCHANTABILITY, FITNESS FOR
A PARTICULAR PURPOSE, TITLE AND NON-INFRINGEMENT. This warranty shall not be enlarged, and no obligation or liability shall arise out of Redwood’s rendering of technical advice, facilities
or services in connection with the delivery of the products. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not
allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Redwood Systems | www.redwoodsystems.com | © 2014. Redwood Systems, Inc. All rights reserved. All other trademarks are the property of their
respective owners. The Redwood Engine, Director, Sensors and Gateways are designed for commercial use only and are not for household use.
62-10018-01
5