Mounting Instructions

advertisement
Valve Actuators
MVH
MOUNTING INSTRUCTIONS
Hot media hazard. Before removing actuator from valve or opening the valve, ensure that the valve control medium is
isolated and remove the pressure. Work must only be carried out by a competent engineer.
Attention: do not use the actuator disassembled from the valve.
MVH26/36/46/56 models
2
1
Lock the stem extension c on the rack placing the
indicator disk a and the jagged washer b.
3
4
By rotating the manual control knob,
lower the stem extension until it
reaches the valve stem, then rotate
the actuator to screw the stem into
the extension.
Tighten the locknut on the stem and
lock the two nuts on the U-bolt.
Assemble the actuator to the valve by U-bolt and the
two nuts with the washer without locking the nuts.
1st Issue rev. e
01/12
ISO 9001
1
CONTROLLI
16010 SANT’OLCESE Genova - Italy
Tel.: +39 01073061
Fax: +39 0107306870/871
E-mail: info@controlli.eu Web: www.controlli.eu
DIM156e
MVH36A models
1
2
Lock the stem extension c on the rack placing the indicator
disk a and the jagged washer b.
3
Assemble the actuator to the valve
by U-bolt and the two
nuts with the washer
without locking the
nuts.
4
- Lift the valve stem
- Remove the cover and rotate the pivot clockwise so that the rack comes out for
assembling it with the valve stem; the pivot can be locked by a spanner as shown
in the picture
- Rotate the actuator to screw the extension on the valve stem, so lock it tightening
the nut on the stem.
- Tighten the two nuts on the U-bolt to lock the actuator.
- Remove the key from the pivot and mount the small cap. The pivot must be rotated
1/2 turn to assemble 45 mm stroke valves. It is necessary to rotate it with several
turns for valves having lower strokes; as an alternative, it is possible to insert the
nut in place of the jagged washer to lock the stem extension in a lower position.
Thus for assembling the valve rotating the pivot 1/2 turn.
1st Issue rev. e
01/12
2
DIM156e
MVH36C models
1
2
Lock the stem extension c on the rack placing the indicator
disk a and the jagged washer b.
3
- Remove the cover
- Rotate the pivot 1/2 turn counter-clockwise and lock it
by a spanner as shown in the picture.
4
- Lower the valve stem
- Screw the extension on
the valve stem until the
groove on the actuator base
matches with the one on the
valve, so lock the extension
tightening the nut on the
stem.
Assemble the actuator to the valve by U-bolt and
the two nuts with the built-in washer.
1st Issue rev. e
01/12
3
DIM156e
ACTUATOR STROKE CALIBRATION (only for MVH36/56)
- Loosen the locking screws located on the cover and put it off.
- Using a screwdriver, turn counter-clockwise the right potentiometer and clockwise the left one up to their mechanical stop.
- Acting on the manual knob, as shown in fig. 5, bring the indicator disk to both stroke ends and position the related adjustable
indicators.
ELECTRICAL CONNECTIONS
Perform the connections in compliance with existing rules and using max 2,5 mm2 cross section wires.
Follow the instructions by using wire terminals on power supply wires in order to prevent accidental contacts between cables at
different voltages in case of wrong installation. On the power supply line install a protection device compliant to existing rules with
a 125 mA intervention threshold and a minimum 3 mm contact opening. The device is not supplied with the product.
MVH26/46
MVH36/36A/36C/56
Neutral- Supply in N
Supply phase in Y1 (joint up)
Supply phase in Y2 (joint down)
Supply
control
W1
W2 Central
W3
Auxiliary
potentiometer MVH
26/46 (4)
L1 Phase
Supply 24 V ~ + 10%
L2 Neutral
M Common
V+ +15V output
(1)
Y Control signal (2)
S3 0...10V or 0..200uA
S2 10...0V or 200...0uA
S1 Analogue common
N3009
(3)
(1) For MVH36 model, connect the potentiometer central of the controller (165 Ohm) to Y terminal, the extremities to M and V+
terminals.
(2) The joint moves downwards when the jumper on SW3 is in A position and the control signal increases.
(3) Connect the position indicator with input current to S3 (or S2) and S1 terminals. Connect the position indicator with input voltage
to S3 (or S2) and M (max 2 mA) terminals. With joint up between M (S1) and S2 minimum voltage value; between M (S1) and
S3 maximum current (voltage) value.
(4) When the actuator is in upper position, the potentiometer has 0 Ohm between W3 and W2 and 1000 Ohm between W2 and
W1 and a variation of 22.2 Ohm for each mm. of stroke.
The performances stated in this sheet can be modified without any prior notice due to design improvements
1st Issue rev. e
01/12
4
Automatic control systems for:
air conditioning/heating/industrial thermal process.
ISO 9001
DIM156e
Download