600 Volt ISO-BOND AC90 Low Voltage Building Wires Description Design Parameters Multiple copper conductors with a low temperature, moisture resistant cross-linked polyethylene (XLPE) insulation and a bare copper or aluminum neutral conductor. Assembly covered with separator tape and interlocked aluminum armour. CONDUCTOR: Multiple, Solid or Class B Compressed or Compact copper strand per ASTM. SpecificationsRatings CSA- CSA C22.2 No. 51 -40°C For 90°C Dry Operation. Options - - Galvanized steel interlocking armour (GSIA) Aluminum (ACM) phase and neutral conductor INSULATION: High dielectric strength low temperature cross-linked polyethylene (XLPE) insulation, exhibiting an optimum balance of mechanical and electrical properties to assure extended cable life. ASSEMBLY: - 2 conductor cable contains black and white circuit conductors, green isolated ground conductor, and a bare copper bonding conductor. - 3 conductor cables contains black, white and red circuit conductors, green isolated ground conductor, and a bare copper bonding conductor. A separator tape is applied over the assembly. ARMOUR: Flexible interlocking aluminum armour applied over the separator tape for mechanical protection. Installation Conduit in Air Isolated in Air Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 1 C115 2016-03-31 Dry Locations 600 Volt ISO-BOND AC90 (A) (B) †A mp aci ty (Am ps) (kg /km ) Ca ble We igh t Conductor Co nd uct or Dia me ter (m m) Ins ula tio nD iam ete r (m m) Arm or Dia me ter (m m) Product Number Ins ula tio n Th ick ne ss (m ils) Low Voltage Building Wires Raceway (C) 600 Volt Copper Two Conductor s QYZ004C 14 AWG CU 30 1.626 3.25 11.58 151 25 s QYZ005C 12 AWG CU 30 2.057 3.68 12.52 192 30 s QYZ006C 10 AWG CU 30 2.591 4.22 13.69 267 40 s Q00700C 8 AWG CU 45 3.404 5.79 17.83 450 55 s Q01700C 6 AWG CU 45 4.293 6.68 20.24 641 75 s QYZ010C 3 AWG CU 45 6.071 8.46 24.18 1101 115 s Q09700C 2 AWG CU 45 6.807 9.19 25.20 1306 130 PRODUCT NOTES: †Ampacities are based on the following: s Items are Prysmian authorized stock. Raceway (Tables 2 of CEC C22.1): Multiple conductors, 85-90°C conductor temperature, and 30°C ambient temperature. The above dimensions are approximate and subject to normal manufacturing tolerances. Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 2 C115 2016-03-31 All metric (SI) dimensions are derived from a soft conversion. 600 Volt ISO-BOND AC90 (A) (B) mp aci ty (Am ps) (kg /km ) †A Conductor Ca ble We igh t Product Number Ins ula tio n Th ick ne ss (m ils) Co nd uct or Dia me ter (m m) Ins ula tio nD iam ete r (m m) Arm or Dia me ter (m m) Low Voltage Building Wires Raceway (C) 600 Volt Copper Three Conductor s QYZ007C 14AWG CU 30 1.626 3.25 12.70 182 25 s QYZ008C 12AWG CU 30 2.057 3.68 13.56 235 30 s QYZ009C 10AWG CU 30 2.591 4.22 15.06 331 40 PRODUCT NOTES: †Ampacities are based on the following: s Items are Prysmian authorized stock. Raceway (Tables 2 of CEC C22.1): Multiple conductors, 90°C conductor temperature, and 30°C ambient temperature (assuming fourth conductor is the neutral of a balanced 3 phase 4 wire system). The above dimensions are approximate and subject to normal manufacturing tolerances. All metric (SI) dimensions are derived from a soft conversion. Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 3 C115 2016-03-31 © PRYSMIAN - A Brand of The Prysmian Group. 2013. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued July 2015.