04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT A p p e n d i x A : L i g h t i n g/ E l e c t r i c a l P l a n s 162 04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT Appendix B: Luminaire/Control Information 163 L1 L2 L3 Litecontrol Ledalite Winona Arcos Perf II Pique Emma Compliance 2.0 P-I-5914T5TCWN-LP 9122-D1SMS-B155S 4621-F/R277-AG7BAL-STD Indirect fluorescent pendant with 1F28T5 (48 in) lamp. Optics: Die- formed steel housing with perforated sections High reflectance specular aluminum center. 7’ mounting height Recessed Dieformed, postpainted, 22 gauge coldrolled steel Optical assembly consists of flat acrylic panels and a center acrylic extrusion, both with a layer of protected MesoOptics® film, which efficiently provides a fully luminous, controlled, low glare batwing distribution. Brushed aluminum and blue art glass compact fluorescent wall sconce.UL listed FP28/830/ECO FT55DL/830/ECO CF32DT/E/IN/830/ECO 277 ICN-2S28@277 ADVANCE 1 Lamp Electronic Ballast (0.98PF) 33 Open Office 277 ICN4S5490C2LS@277 1 Lamp Electronic Ballast (0.90PF) 58 Private Office 277 ICF-2S26-H1-LD@230 ADVANCE 1 Lamp Electronic Ballast (0.98PF) 36 Open Office Zumtobel Slotlight Pro 2 ½” Recessed 4’ length Zumtobel Slotlight Pro 2 ½” Recessed 5’ length L6 Erco Nadir Floor Recessed Luminaire L7 Winona Step 02SQU L4 L5 L8 L9 L10 L11 Mark Architectural Lighting Mark Architectural Lighting Artemide Kurt Versen Magellan Series 12” Magellan Series 24” Itis Table R 7301 Downlight SLR2-IW-1T5-04OLP-DH Recessed “Ribbon of Light” fixture with smooth frosted acrylic lens, extruded aluminum housing, FP28/830/ECO 120V SLR2-IW-1T5-05OLP-DH Recessed “Ribbon of Light” fixture with smooth frosted acrylic lens extruded aluminum housing, FP35/830/ECO 120V LED 3500K Included with luminaire 120V included 3.6 TheaterStage Ramp LED 3000K Included with luminaire 120V Included 3 Theater Steps 33832.023 LED-STEP02-SQUS-001-277-BAL Orientation light used to enhance architectural features Surface mount step light. Extruded aluminum LED module with solid aluminum, ICN2S28@120 ADVANCE Electronic Ballast (0.98 PF) ICN2S28@120 ADVANCE Electronic Ballast (0.98 PF) REZ-2T42M3-BS ADVANCE Electronic Dimming Ballast (0.98 PF) IEZ-2S24D@120 Electronic Dimming Ballast (0.98 PF) 41 41 MG-1-2-8-EDB Cold rolled stel housing, spun steel trim, matte finish, thick white acrylic shielding. Recessed. (2) CFTR32W/GX24Q /830 120V MG-2-3-2-EDB Cold rolled stel housing, spun steel trim, matte finish, thick white acrylic shielding. Recessed. (2) FP24/830/HO /ECO 120V LED 2800 K Included with luminaire 120V - 4 120V IMH-100-A ADVANCE Electronic Ballast (1.0 PF) 82 - R7301-C-Y Podium mounted luminaire for direct task and diffused LED lighting. This unit has a shielding conoid reflector designed for PAR-38 long neck lamps. Use in a variety of ceiling heights for area, task or feature lighting. MCP70PAR30/LN/930/FL/ECOPB 76 57 Theater Walls Theater Walls Theater Walls Theater Walls Podium Stage L12 L13 L14 L15 Kurt Versen Kurt Versen Kurt Versen Kurt Versen P927 Downlight P 958 Wall Washer P949 Downlight P955 Wall Washer P927-Y-DM P958-Y.DM P949Y.DM P955Y. DM Optics and Applications The two reflector optical system features an elliptical primary reflector and a deep parabolic shielding cone designed for use in higher ceilings. Pattern edges blend softly with adjacent units The optical systems utilize triple tube lamps, full circle kicker reflectors and proprietary borosilicate glass prismatic spread lenses to provide even distribution without hot spots or striations Optics and Applications The two reflector optical system features an elliptical primary reflector and a deep parabolic shielding cone designed for use in higher ceilings. Pattern edges blend softly with adjacent units The optical systems utilize triple tube lamps, full circle kicker reflectors and proprietary borosilicate glass prismatic spread lenses to provide even distribution without hot spots or striations (1) CFTR42W/GX24Q/830 CFTR32W/GX24Q /830 (2) CFTR26W/GX24Q /830 (2)CFTR32W/GX24Q /830 120V IDL-2S26-M5LD@120 ADVANCE Electronic Dimming Ballast (0.99 PF) 47 Lower Tier Seating Area 120V REB-2S26M1-BS-DIM Electronic Dimming Ballast (0.80 PF) 35 Upper Tier Seating Area 120V IDL-2S26-M5LD@277 ADVANCE Electronic Dimming Ballast (0.99 PF) 58 Upper Tier Seating Area 120V IDL-2T42-M5BS@277 BSADVANCE Electronic Dimming Ballast (0.99 PF) 75 Lower Tier Seating Area L16 ERCO LED Orientation Luminaire 33790.023 L17 Louis Poulsen Nimbus plant accent 1/35W/120V/ST STEEL/ANTISLIP LOW HEAT L18 ERCO Kubus Floor Washlight 3364.023 L19 ERCO Midipoll Bollard Luminaire 33344.023 L20 Louis Poulsen Kipp Wall KIW1/32W/CFGX24Q3/277/ALU L21 Lithonia Lighting Staggered Strip SS-2-32-277 L22 Louis Poulsen Nyhvan Maxi NYP-MAX1/42CFGX24Q-4 Recessed LED, Clear prismatic diffuser with circular light aperture, Corrosion resistant stainless steel cover (IP68) Clear prismatic diffuser with circular light aperture, Corrosion resistant stainless steel cover (IP68) Corrosion resistan housing and cast plate no rinse surface treatment electronic control gear included Cross shaped aluminum profile and cylindrical housing no rinse surface treatment suitable for wet conditions Symmetric wall sconce with white opal acrylic and die cast aluminum shade, extruded aluminum arm. Aluminum strip light designed with 4” ideal overlap to assure shadow free illumination. Direct illumination provided by die cast aluminum LED 5500K Included with luminaire 120V Included with luminaire 0.3 EXTERIORStar wall 25WMR16 120V Included with luminaire 25 EXTERIORPlant Aim LED 5500K Included with luminaire 120V Included with luminaire 3.3 EXTERIORentryways LED 5500 K Included with luminaire 120V Included with luminaire 10 EXTERIOR – Walkways 277V ICF-2S26-H1LD@230 ADVANCE 1 Lamp Electronic Ballast (0.98PF) 36 FO32/730/ECO 277V VEL-3P32-SC 2 Lamp Electronic Ballst (0.99PF) 65 CFTR42W/GX24Q/830 277v ICF-2S26-H1LD@230 ADVANCE 36 CFTR32W/GX24Q/830 Atrium Walls Ticket Desk Ticket Counter L23 L24 L25 L26 L27 Erco Kurt Versen Erco LC Washlight Lensed Downlight LC Downlight Bega Lighting Large Scale Floodlights Bega Lighting Large Scale Floodlights 22681.023 R5673 22680.023 7873MH.554.SLV 7873MH.554.SLV Pendant pendant suspended with stainless steel cable at a height of 7’ 1 Lamp Electronic Ballast (0.98PF) Low brightness reflector with wallwash scoop to provide wallillumination: aluminum, specular anodized. Cutoff angle 40° from horizontal. Diffuser as lamp cover: glass, frosted. 277V 72C5281 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 94 277V 79W5590 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 210 277V 72C5281 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 94 277V 72C5581 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 205 277V 72C5581 ADVANCE 1 Lamp Electronic Ballast 205 Efficient optical system with Fresnel lens. Lamp position horizontal, aluminum housing. Recessed cast aluminum housing, low brightness reflector with thermal protection. Cut off angle at 40 from horizontal. Two piece diecast aluminum consisting of a reflector housingTwo piece die-cast aluminum consisting of an outer lens frame and a inner accessory holder. 360 glare shielding. Two piece diecast aluminum consisting of a reflector housingTwo piece die-cast aluminum consisting of an outer lens frame MC70T6/UG12/\930PB MP175/C/BU-ONLY MC70T6/UG12/930PB UHI-S150/E26/ ORANGE UHI-S150/E26/ GREEN General General General Dec Roof Lighting Roof Lighting L28 L29 L30 L31 L32 Bega Lighting Bega Lighting Bega Lighting Large Scale Floodlights Large Scale Floodlights Large Scale Floodlights Bega Lighting Small Scale Floodlight Bega Lighting Small Scale Floodlight 7873MH.554.SLV 7873MH.554.SLV 7873MH.554.SLV 7723MH.SLV.313 7722MH.SLV.313 and a inner accessory holder. 360 glare shielding. Two piece diecast aluminum consisting of a reflector housingTwo piece die-cast aluminum consisting of an outer lens frame and a inner accessory holder. 360 glare shielding. Two piece diecast aluminum consisting of a reflector housingTwo piece die-cast aluminum consisting of an outer lens frame and a inner accessory holder. 360 glare shielding. Two piece diecast aluminum consisting of a reflector housingTwo piece die-cast aluminum consisting of an outer lens frame and a inner accessory holder. 360 glare shielding. One piece diecast aluminum with integral cooling fins with aluminum canopy and stainless steel outrigger arm. Elliptical spread lens. 180 degree glare shielding One piece diecast aluminum with integral cooling fins with aluminum canopy and stainless steel outrigger arm. (0.9PF) UHI-S150/E26/ MAGENTA UHI-S150/E26/ BLUE MCP150/U/MED/830PB MC70TC/U/G8.5/930PB MC39TC/U/G8.5/930PB 277V 72C5581 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 205 Dec. Roof Lighting 277V 72C5581 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 205 Dec. Roof Lighting 277V 72C5581 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 205 277V 72C5282 ADVANCE 1 Lamp Electronic Ballast (0.9PF) 94 277V ADVANCE 1 Lamp Electronic Ballast (0.9PF) 56 Roof Lighting Stair Light Stair Light L33 Louis Poulsen Wee Bee Opal Orientation Light WEEBEE-0 18LED BLUE Elliptical spread lens. 180 degree glare shielding Sleeve: Marine grade 316 stainless steel. Glass: Tempered white opal glass. Top plate: Marine grade 316 Blue LED Provided with luminaire 277V INCLUDED 3 Bridges and Stairs Fixture Type: Project name: Arcos™Perf II P-I-5900 & LS-P-I-5900 Pendant-Mounted Indirect 2 3/8" (60) 9 9/16" (243mm) Product Description Control Solutions available Die-formed steel housing with perforated sections and white acrylic diffusing panels behind the perforations. Reflectors are high-reflectance specular aluminum center and side elements. UL Listed. Cradle to Cradle Certified.CM ECSS Ordering Guide Product, lamping, & length Options P P- I - 59 6 6 88 T5HO T5HO TCWM TCWM LP/ELB LP/ELB - TW TW - 2CWQ 2CWQ - ECSS ECSS 120 120 Mounting Distribution Series Lamp Count Nominal Length(ft) Lamp Type Finish Ballast Tandem Wiring Pre-wiring Other Options Volts I Indirect 59 2, 3, 4 4, 6, 8 1, 2, 3 2, 4, 6 4 8 4 8 T8 TCWM (textured matte white) is standard LP/ELB is standard -TW 1CWQ 2CWQ LPD/CS/e LPD/DIO see notes P Pendantmounted LS-P LiteSpeed Pendantmounted Mounting Options - add to end of catalog number see notes T5HO T5 see LiteColors™ in product guide for other finishes Aircraft cables FAI/ACC (field adjustable) standard Stems P6S (stem) SC/P6 (sloped ceiling) EQ/P6 (earthquake) CS/dlh* CS/av/PR CS/av/PL CS/us ECSS F LK LP/EF see Other Options see Ballast Options 120 277 notes: Lamp count = total number of lamps in the fixture Tandem wiring not available for one-lamp cross-section fixtures. See next page for details. For ordering guide information in shaded areas, choose selection by reading ACROSS the shaded areas for correct specifications. *Must include a dimming ballast (LPD/ELB). See next page for details. P-I-5968T5HO-TCWM-LP/ELB-TW-2CWQ-ECSS-120-FAI/ACC is a typical catalog number for a 6-lamp (3 lamps in cross-section), 8-foot long, high-output T5 fixture with textured matte white finish, low-profile electronic ballast, tandem-wired, pre-wired with two-circuit branch wiring and quickconnects, shelf-style end caps, 120 volts, mounted with field adjustable aircraft cables. LiteSpeed Quick-Ship Many configurations of this fixture are available in our Litespeed 10-day quick-ship program. The “10-day” icon in the descriptions below shows which options are available in Litespeed. Litespeed orders are shipped within 10 working days of receipt of a released, cleared order. An “LS” prefix is required in front of the ordering number to have the order handled as Litespeed. Other configurations not indicated here may be available for 10-day shipment; contact Customer Service for availability. Some restrictions may apply to large orders. All Litespeed fixtures are supplied in textured white finish (TCWM). Cross-section lamping 2-T8 1-T5 or T5HO Ballast Options 3-T8 2-T5 or T5HO 4-T8 3-T5 or T5HO To have the fixture enabled for Lutron EcoSystem compatibility: LPD/CS/e EcoSystem low-profile dimming electronic ballasts installed at the factory, along with all required internal EcoSystem wiring. For other configurations of the Lutron EcoSystem components, including custom device connection feeds to enable connection to ceiling-mounted sensors and control devices, consult litecontrol.com/cs or contact the factory. LPD/DIO Universal Lighting Technologies dimming ballast Other Options 2 3/8" (60) 9 9/16" (243mm) av cs us CS/dlh Daylight harvesting solution. See next page for details. CS/av This fixture is compatible with the Litecontrol CS/av control solution. See next page for details. CS/us Ultrasonic occupancy sensor control solution. Only available on / 4- and 8-foot fixtures. See next page for details. ECSS End Cap Shelf-Style. Die-cast shelf-style end caps with no exposed fasteners. F Fuse. Slow or fast blow, determined by Litecontrol. LK Lens kit dust cover (available for T8) LP/EF Low-profile Emergency Fluorescent Ballast. Battery-powered ballast from a UL Listed manufacturer will operate one lamp for 1 1/2 hours. Questions to Ask 1. Row information, including desired fixture lengths? 2. Lamp type? 3. Ballast options? 4. Controls solutions? 5. Other options? 6. 120 or 277 volt? Click on Quick Find revised 5/26/2009 59 litecontrol.com ICN-2S28@277 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Min. Start of Lamp Watts Temp (°F/C) Lamps F14T5 F14T5 F21T5 F21T5 * F28T5 F28T5 F35T5 F35T5 1 2 1 2 1 2 1 2 14 14 21 21 28 28 35 35 Input Current (Amps) 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0.07 0.13 0.10 0.17 0.12 0.23 0.15 0.28 Wiring Diagram Input Power (ANSI Watts) 19 34 26 48 33 63 41 77 CENTIUM T5 Electronic Programmed Start Series 277 50/60 HZ Active Ballast Factor MAX THD % Power Factor MAX Lamp Current Crest Factor B.E.F . 1.07 1.06 1.03 1.02 1.04 1.03 1.01 1.00 20 10 15 10 10 10 10 10 0.90 0.98 0.95 0.98 0.98 0.99 0.98 0.99 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 5.63 3.12 3.96 2.13 3.15 1.63 2.46 1.30 Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 OverAll (L) 16.70 " 16 7/10 42.4 cm Width (W) 1.18 " 1 9/50 3 cm Height (H) Mounting (M) 1.00 " 16.34 " 1 16 17/50 2.5 cm 41.5 cm Revised 03/03/2009 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Pique™ Project Name Spec Type Recessed Notes 2’x2’ 1 TT5 (55W) Order Guide Some combinations of product options may not be available. Consult factory for assistance with your specification. 9122 B155 – – – – Product Series & Size Version Configuration Lamping Housing Wiring Voltage Ballast Pique 2’x2’ D1 D2 A1 A2 ST Standalone CR Continuous Row SMS Standalone Master/Satellite CMS Continuous Row Master/Satellite 1 TT5 (55W) S N C T 1 1 cct 5 1 cct w/ Battery Pack 7 1 cct Dimming 1 120V 2 277V 3 347V E Standard Ballast Standard T-Grid Slot T-Grid Air Return on Standard T-Grid Air Return on Slot T-Grid Standard (22ga.) New York (20ga.) Chicago Plenum Standard w/ Frame Restraint Consult website for complete list of standard wiring options See details on next page Upgrades & Accessories Consult website for ballast manufacturer information Cross Section Please indicate with check mark. Lamps Included Lamps Included & Installed Job Pack Flex Whip 4-3/8" 23-13/16" Can be mounted to wood frame or with hanger wire Drywall Kit Not available in continuous row Side View Wood Frame 24" Hanger Wire 4-3/8" Response Daylight For details visit www.ledalite.com/response 23-11/16" © 2010 Ledalite Phone: 604.888.6811 Fax: 800.665.5332 Web: www.ledalite.com Filename 9122xxxxB155.pdf Rev 1.5 ICN4S5490C2LS@277 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Min. Start of Lamp Watts Temp (°F/C) Lamps * FT55W/2G11 FT55W/2G11 FT55W/2G11 FT55W/2G11 1 2 3 4 55 55 55 55 Input Current (Amps) -20/-29 -20/-29 -20/-29 -20/-29 0.23 0.41 0.61 0.80 Wiring Diagram SW o OR BALLAST GR 2 or 4 lamps (C) LAMP BR YL LAMP RD LAMP OR Same BLUE Input BALLAST BR Wiring BL/WH LAMP LAMP LAMP YL MAX THD % Power Factor MAX Lamp Current Crest Factor B.E.F . 0.89 0.89 0.90 0.90 30 10 10 10 0.90 0.97 0.98 0.98 1.7 1.7 1.7 1.7 1.53 0.80 0.54 0.41 Operates 1 or 3 lamps (B) YL LAMP BL o Ballast Factor Enclosure Operates 2 or 3 lamps (A) RD GN BK WH Input Power (ANSI Watts) 58 111 166 217 CENTIUM T5 Electronic Programmed Start Series/Parallel 277 50/60 HZ Active Same BL/WH Input BALLAST BR Wiring RD (A) SW # Lamps ON ON 3 Lamps ON OFF 2 Lamps ON LAMP LAMP BLUE LAMP (C) (B) # Lamps ON # Lamps ON 3 Lamps ON 4 Lamps ON 1 Lamp ON 2 Lamps ON GN=Green BK=Black WH=White RD=Red GR=Grey OR = Orange BL=Blue BR=Brown YL=Yellow BL/WH=Blue/White The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 OverAll (L) 24 " 24 61 cm Width (W) 1.18 " 1 9/50 3 cm Height (H) Mounting (M) 1" 23.64 " 1 23 16/25 2.5 cm 60 cm Revised 01/31/2007 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 LUMINAIRE SUBMITTAL SHEET MODEL #: 4621 SERIES: 6/17/2004 COMPLIANCE 2.0 MODEL NAME: EMMA TYPE: RECESSED BOX Your Specification: ________ - ____-______-______-_______-______ (Catalog Number) CATALOG NUMBER: 4621 BAL LBP LAMPING: I/R F/R F/ER (Lamping) (Voltage) (Lens) FINISHES: 4621 Recessed Box with (1)60W A-19/Med Recessed Box with (1)CFM26W/GX24q-3 or (1)CFM32W/GX24q-3 or (1)CFM42W/GX24q-4 Recessed Box with (1)CFM26W/GX24q-3 or (1)CFM32W/GX24q-3 or (1)CFM42W/GX24q-4 Triple Tube Fluorescent with Emergency Battery Back-up System VOLTAGE: 120V 120 Volt 277V 277 Volt (Incandescent 120V only) LENS OPTIONS: OA Opal Acrylic (Etched) FAH4 White Vein Hand Painted Faux Alabaster FAH5 Antique Hand Painted Faux Alabaster (Beige) FAH6 Gray Vein Hand Painted Faux Alabaster FAH7 Beige Vein Hand Painted Faux Alabaster FGH Faux Glass AG7 Art Glass (Blue Glass with Texture Detail) CPF CMF (Finish) (Special) SPECIAL/MODIFICATIONS DESC. (MOD only): Standard Brushed Aluminum Light Bronze Paint with Brushed Texture Custom Custom Painted Finish (Consult Factory) Custom Metal Finish (Consult Factory) SPECIAL: STD Standard MOD Modified WEIGHT (lbs): I/R 15 F/R 15 F/ER 18 (Hanging) PROJECT: NOTES: 1. WALL CUT-OUT DIMENSION FOR RECESSED BOX: WIDITH 5” X HEIGHT 7 ¾” 2. WALL CUT-OUT DIMENSION FOR RECESSED BOX AND EMERGENCY INDICATOR LIGHT: RECESSED BOX: WIDITH 5” X HEIGHT 7 ¾” INDICATOR LIGHT: 1 ¼” DIAMETER HOLE LOCATED 7” BELOW BOTTOM OF BOX CUT-OUT AND CENTERED QTY: NOTES: • UL LISTED AND CUL APPROVED. • WINONA LIGHTING PRODUCTS ARE UNION MADE. • CUSTOM SIZES AND FINISHES AVAILABLE UPON REQUEST. • ALL FLUORESCENT FIXTURES AVAILABLE IN 120 V AND 277 V. • INCANDESCENT 120 V ONLY. • WINONA LIGHTING RESERVES THE RIGHT TO MAKE DESIGN CHANGES WITHOUT PRIOR NOTICE. • LAMPS NOT INCLUDED. • BALLAST INFORMATION: MAGNETIC 3760 West Fourth Street - Winona, MN 55987 – 1-800-328-5291 – 507-454-5113 – Fax 507-452-8528 – www.winonalighting.com ICF-2S26-H1-LD@230 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Min. Start of Lamp Watts Temp (°F/C) Lamps CFM26W/GX24Q CFM26W/GX24q * CFM32W/GX24q CFM42W/GX24q CFQ26W/G24q CFQ26W/G24q CFS21W/GR10q FT24W/2G11 1 2 1 1 1 2 2 2 26 26 32 42 26 26 21 24 Input Current (Amps) 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0.13 0.23 0.16 0.20 0.12 0.22 0.22 0.21 Wiring Diagram BLUE BLACK WHITE Ballast Factor MAX THD % Power Factor MAX Lamp Current Crest Factor B.E.F . 1.10 1.00 0.98 0.98 1.00 1.00 1.12 0.93 10 10 10 10 10 10 10 10 0.98 0.99 0.98 0.98 0.98 0.99 0.99 0.99 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 3.79 1.85 2.72 2.13 3.70 1.96 2.20 1.94 Enclosure WIRING: (2) LAMPS LINE Input Power (ANSI Watts) 29 54 36 46 27 51 51 48 SMARTMATE Electronic Programmed Start Series 120-277 50/60HZ Active (1) LAMP BLUE BALLAST YELLOW GREEN RED RED Green Terminal must be Grounded The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0.0 0.0 0.0 0.0 0 cm. in. Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White cm. OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 2.4 " 2 2/5 6.1 cm Height (H) Mounting (M) 1.0 " 4.6 " 1 4 3/5 2.5 cm 11.7 cm Revised 09/02/2004 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 ICN-2S28@120 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Min. Start of Lamp Watts Temp (°F/C) Lamps F14T5 F14T5 F21T5 F21T5 * F28T5 F28T5 F35T5 F35T5 1 2 1 2 1 2 1 2 14 14 21 21 28 28 35 35 Input Current (Amps) 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0.16 0.29 0.21 0.40 0.28 0.55 0.34 0.67 Wiring Diagram Input Power (ANSI Watts) 19 34 26 48 33 64 41 80 CENTIUM T5 Electronic Programmed Start Series 120 50/60 HZ Active Ballast Factor MAX THD % Power Factor MAX Lamp Current Crest Factor B.E.F . 1.07 1.06 1.03 1.02 1.04 1.03 1.01 1.00 20 10 15 10 10 10 10 10 0.98 0.98 0.99 0.98 0.98 0.99 0.98 0.99 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 5.63 3.12 3.96 2.13 3.15 1.61 2.46 1.25 Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 OverAll (L) 16.70 " 16 7/10 42.4 cm Width (W) 1.18 " 1 9/50 3 cm Height (H) Mounting (M) 1.00 " 16.34 " 1 16 17/50 2.5 cm 41.5 cm Revised 08/21/2006 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 ICN-2S28@120 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Lamp Min. Start Input Current Input Power Ballast of Watts Temp (°F/C) (Amps) (ANSI Watts) Factor Lamps 1 14 0/-18 0.16 19 1.07 2 14 0/-18 0.29 34 1.06 1 21 0/-18 0.21 26 1.03 2 21 0/-18 0.40 48 1.02 1 28 0/-18 0.28 33 1.04 2 28 0/-18 0.55 64 1.03 1 35 0/-18 0.34 41 1.01 2 35 0/-18 0.67 80 1.00 F14T5 F14T5 F21T5 F21T5 F28T5 F28T5 * F35T5 F35T5 Wiring Diagram MAX THD % 20 10 15 10 10 10 10 10 CENTIUM T5 Electronic Programmed Start Series 120 50/60 HZ Active Power Factor 0.98 0.98 0.99 0.98 0.98 0.99 0.98 0.99 MAX Lamp B.E.F. Current Crest Factor 1.7 5.63 1.7 3.12 1.7 3.96 1.7 2.13 1.7 3.15 1.7 1.61 1.7 2.46 1.7 1.25 Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. 0 0 0 0 0 0 0 cm. 0 0 0 0 0 0 0 OverAll (L) 16.70 " 16 7/10 42.4 cm Width (W) 1.18 " 1 9/50 3 cm Height (H) Mounting (M) 1.00 " 16.34 " 1 16 17/50 2.5 cm 41.5 cm Revised 08/21/2006 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 E Nadir Recessed floor luminaire Directional luminaire with LED 5" 466666663 97 mm 3 13/16" 4666663 d 125 mm LED Nä ö ü Dry Damp Wet ÄIndoor 33832.023 LED warm white LED 3.6W 90lm 3500K Version 1 Product description Size 4 For mounting in accessories. Housing: corrosion-resistant cast aluminum, No-Rinse surface treatment. Black double powder-coated. Lampholder carrier, 0°-25° tilt, 90° rotation. Electronic control gear 120V, 60Hz. Connection cable, 3xAWG16, L 19 11/14" / 500mm. Replaceable LED module. Aperture mask: aluminum, silver, specular anodized. Softec lens. Safety glass: 1/4" / 6mm, clear. Load: 1124lb.wt / 5kN. Mounting accessories to be ordered separately. Suitable for wet location (IP67): dustproof and protected against immersion damage. To avoid submersion in standing water provide local drainage. Weight 1.98lbs / 0.90kg Temperature on the cover glass 87°F / 30°C ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com 500 cd 150° 150° 120° 120° LED 3.6W 90lm 3500K h(ft) 15 12 9 6 3 E(fc) 2 3 5 10 41 D 19° 5’0" 4’0" 3’0" 2’0" 1’0" Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/33832.023 1/2 STEP02 Square Deco is a surface mount step light with a concealed optic. Eight LED colors are available in both normal and high output configurations. Distribution: Three light distribution patterns are available. Short: For narrow corridors. Medium: For wide corridors. Long: For large area illumination. Construction: Extruded aluminum LED module with solid aluminum, brass, or stainless steel face plates. Mounting: Luminaire is mounted to a 2 1/8” deep octagon box (supplied by others) with hidden fasteners. Integral Driver: Integral non-dimming drivers available for 90-250V AC and 12V AC. Dimmable driver 12V-40V DC only. Finish: Recessed areas always have matte black finish to reduce glare. Face plates in natural metal finishes , except stainless steel, have protective clear top coat. Face plates in painted are finished with a two part wet paint system. Primer only option allows for field painting. Dimming: True 0-100% dimming is available with exclusive LightLink dimming system interface which is compatible with both 0V-10V sink and source-type dimmers. Power Consumption: Luminaire consumes maximum of 4W depending on LED color. UL Listed: Dry Location LED STEP02 SQU SOURCE MOUNT FACE FACE: SQU = SQUARE UL LISTED c UL ® Project Name: Ref #: CODE COLOR 001 WARM WHITE 3000K 001/HO WARM WHITE 3000K 002 COOL WHITE 6200K 002/HO COOL WHITE 6200K 003 AMBER 003/HO AMBER 004 BLUE 004/HO BLUE 005 CYAN 005/HO CYAN 006 GREEN 006/HO GREEN 007 RED-ORANGE 007/HO RED-ORANGE 008 RED 008/HO RED Qty: LED module with concealed optic and integral non-dimming driver. Matte black finish to reduce glare. 4.60 2 1/8" deep octagon box (by others). 18" L Approx 10'-0" M S Approx Approx 4'-0" 3'-0" X DISTRIBUTION LED CODE DISTRIBUTION: S = SHORT M = MEDIUM L = LONG MOUNT: STEP02 = STEP LIGHT See individual drawing for this other option: RND = ROUND STEP02 Square Deco 4.60 LED Type: OUTPUT NORMAL HIGH NORMAL HIGH NORMAL HIGH NORMAL HIGH NORMAL HIGH NORMAL HIGH NORMAL HIGH NORMAL HIGH VOLTAGE: Non-Dimming ND120V = 90V-250VAC ND12V = 12VAC Dimming DM24V = 12V-40VDC* VOLTAGE FINISH OPTIONS SPECIAL FINISH: OPTIONS: SPECIAL: Natural Metal Finishes X = NO OPTIONS STD = STANDARD AB5 = ANTIQUE BRASS MOD = MODIFIED BAL = BRUSHED ALUMINUM BB = BRUSHED BRASS BSS = BRUSHED STAINLESS STEEL CMF = CUSTOM METAL FINISH PB = POLISHED BRASS PSS = POLISHED STAINLESS STEEL MODIFICATIONS: Painted Please use this space to list any modifications. CPF = CUSTOM PAINTED FINISH LBPS = LIGHT BRONZE PAINT SMOOTH PRM = PRIMER ONLY SGB = SEMI-GLOSS BLACK SGW = SEMI-GLOSS WHITE *LightLink dimming system interface maximum fifty luminaires per LightLink, one LightLink per dimming zone. *IES report available for normal & high output. (See website) Revised: 2/28/08 Winona Lighting | 3760 West Fourth Street | Winona, MN 55987 | 800-328-5291 | www.winonalighting.com REZ-2T42-M3-LD Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. of Lamps Rated Lamp Watts * CFTR32W/GX24Q 2 MARK 10 POWERLINE Electronic Dimming Programmed Start Series 120 60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 32 Min. Start Temp (°F/C) 50/10 0.64 20/76 0.05/1.00 10 0.98 1.6 1.32 2 42 50/10 0.82 20/98 0.05/1.00 10 0.98 1.6 1.02 1 57 50/10 0.55 18/66 0.05/1.00 10 0.98 1.6 1.52 1 70 50/10 0.67 18/80 0.05/1.00 10 0.98 1.6 1.25 CFTR42W/GX24Q CFTR57W/GX24Q CFTR70W/GX24Q Wiring Diagram Enclosure DIMMER BLACK WHITE LINE BALLAST RED RED YELLOW YELLOW BLUE BLUE DIAG. 132 The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) OverAll (L) 6.28 " 6 7/25 16 cm Width (W) 3.00 " 3 7.6 cm Height (H) Mounting (M) 1.29 " 6.0 " 1 29/100 6 3.3 cm 15.2 cm Revised 08/17/2006 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 IEZ-2S24-D@120 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. of Lamps Rated Lamp Watts * F24T5/HO FT24W/2G11 2 2 24 24 Min. Start Temp (°F/C) 50/10 50/10 MARK 10 POWERLINE Electronic Dimming Programmed Start Series 120-277 50/60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 0.48 0.48 16/57 16/57 0.05/1.00 0.05/1.00 10 10 0.99 0.99 1.7 1.7 1.75 1.75 Wiring Diagram Enclosure DIMMER BLACK WHITE BALLAST RED YELLOW BLUE LAMP LAMP LINE The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 cm. 0 0 0 0 0 0 0 in. Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White cm. 0 0 0 0 0 0 0 OverAll (L) 16.70 " 16 7/10 42.4 cm Width (W) 1.18 " 1 9/50 3 cm Height (H) Mounting (M) 1.00 " 16.34 " 1 16 17/50 2.5 cm 41.5 cm Revised 09/14/2006 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Itis table ø 4 3/4” ø 12 cm Naoto Fukasawa 2009 15 3/4” 40 cm Table standing luminaire for direct task and diffused LED lighting. re-engineered using stronger newly innovative low energy LED light source to provide a warm (2900k) intense light resulting in a 20% increase in light output yet decreasing energy consumption by 25% • body, base, and head in steel with glossy black or white painted finish • side diffuser in transparent polycarbonate • stem pivots at base up to 90˚ • head rotates up to 180˚ • dimmer switch on base • Awards Reddot Design Award “Best of the Best” 2007 - Essen (Deutschland) Good Design Award The Chicago Atheneum 2007 - Chicago (US) Museums Die Neue Sammlung State Museum of Applied Arts and Design in the Pinakothek fder Modern München (Deutschland) eco design www.artemide.us 13 3/4” 35 cm 11 13/16” 30 cm ø 4 3/4” ø 12 cm 3/8” 1 cm 20” 51 cm Itis table LED source • 7 LEDs/4W supplied Section R fronts_UG 12/2/02 12:19 PM Page 3 Lampholder Branch Circuit Junction Box (Rotated 90 ) Access Covers (2) Housing Top Housing R7301 R3 Downlight 39-70W PAR-30L Metal Halide 57/8" Aperture Optics and Applications This unit has a shielding conoid reflector designed for PAR-30 long neck lamps. Use in a variety of ceiling heights for area, task or feature lighting. Design Features A steel housing protects and positions the lamp and reflector. The aperture frame features a 2" throat for installation in thicker ceilings. Top or bottom service. Accessory Bracket Thermal Protector Alzak Cone Lamp (By Others) Safety Chain Remote Ballast Assembly Finish A specular clear Alzak cone is standard. Optional colors and Softglow® finishes are available. Housing and structural parts are painted optical matte black to suppress stray light leaks. Ballast Standard ballast is encased and potted magnetic. Type HX, HPF, 120V or 277V taps. Shipped for 277V, field conversion to 120V. Thermally protected with auto reset. Temperature -20°F to 105°F. Comes mounted on a plate with 4' of flex. End of life protection not available, replace failed lamps immediately. Service through the aperture requires 15" plenum depth for the ballast to swing up for removal. Optional electronic metal halide ballasts provide more constant lumen and wattage output. They feature thermal protection with auto reset, quiet operation and automatic shutdown at end of life. Service through the aperture. General Fixtures are pre-wired and thermally protected, UL and C-UL listed for eight wire 75°C branch circuit wiring. Union made IBEW. Luminaire Efficiency Ratings (LER) do not apply to fixtures using reflector type lamps. Dimensions and Lamps D A B Number A Depth 1 R7301* C B C Aperture Width 7 10 /2" 5 /8" 267mm 149mm 1 D Length Lamps 1 7 /4" 14 /4" 39-70W PAR-30L MH 184mm 362mm *To specify add watts and volts for proper ballast, e.g. R7301-39277. Matching Units Vertical lamp downlights Horizontal lamp downlight Sloped ceiling downlights Directional downlights Wall washers Pages R4, R5, C6, C7, C8 Page R6 Pages R7, C22, C23 Pages R7, C22, C23 Pages R32, E4, E5, E6, E8 Accessories F Ballast fuse. R2 26" support rails. R5 52" support rails. B Specular black cone. WT White trim flange. G Specular gold cone. H Specular mocha cone. WHT White complete trim. P Specular graphite cone. TLI Emergency 60W lamp. T Specular titanium cone. HL Hexcell louver.† W Specular wheat cone. LL Linear lens.† Y Specular pewter cone. LP Large prism lens.† Z Specular bronze cone. MP Microprism lens.† S Softglow® finishes: add S before color letters. e.g. SW for Softglow® wheat cone, SC for Softglow® clear cone. EBH Electronic ballast, specify watts and volts. V347 347 volt ballast, contact factory. FR Frosted lens. Example LLFR for linear lens frosted.† EC Emergency circuit with mini-can socket and leads.* AO Magnetic ballast restrike Auto-On system.* AOE1 Electronic ballast Auto-On restrike system 120V.* AOE2 Electronic ballast Auto-On restrike system 277V.* FF30-2 Accessory holder for PAR-30. Holds two accessories. Requires cut down cone. CDC Cut down cone. † Requires accessory holder. *Use open rated 60W max. auxiliary incandescent lamp. Kurt Versen Company Point Source Lighting Westwood, New Jersey 07675 Revised: 4/9/2009 Catalog Number: IMH-100-A e-Vision® Electronic For 70W or 100W Metal Halide Lamps ANSI M98, M139, M143, M90 or M140 Ballast for Metal 120-277V 50/60Hz Electronic Halide Lamps Status: RELEASED DIMENSIONS AND DATA Lamp Number Watts Input Volts Catalong Number* Line Current (Amps) Input Power (Watts) Min Power Factor 70 Watt Lamp, ANSI Code M98, M139 or M143 Minimum Starting Temp -30°C/-20°F 120 0.68 82 1 70 IMH-100-A-XXX 1 277 0.30 81 100 Watt Lamp, ANSI Code M90 or M140 Minimum Starting Temp -30°C/-20°F 120 0.9 112 1 100 IMH-100-A-XXX 1 277 0.4 110 Case Figure A/B Overall Length Case Length Case Width Height Mountin Length Mounting Width 140mm 120mm 92mm 38mm 132mm 73mm [5.5"] [4.7"] [3.6"] [1.5"] [5.2"] [2.9"] Fig. Weight (lb) Max. Distance to Lamp (ft) 1 A/B 1.4 5 2 A/B 1.4 5 Wiring Diag MEASURE CASE TEMPERATURE ON RIGHT HEAT SINK CLIP AT BALAST END *Ordering Information INSTALLATION & APPLICATION NOTES: 1. Maximum allowable case temperature is 85°C. See figure above for measurement location 2. Ignition pulse is 4 kV max -LF 3. All leads are 12 inches long 4. Ballast output will shutdown after 20 minutes if lamp fails to ignite 5. Power must be cycled off – then on, after replacing lamp Description Order Suffix -BLS Phased out use IMH70ALF or IMH100BLF Ballast with bottom exit leads and mounting studs Data is based on tests performed by Philips Advance in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. Philips Lighting Electronics N.A. 10275 West Higgins Road • Rosemont, IL 60018 • www.philips.com/advance Tel: 800-322-2086 • Fax: 800-423-1882 • Customer Support: 800-372-3331 • OEM Support: 866-915-5886 Section P fronts_UG 11/13/02 7:55 PM Page 18 Junction Box Vented Housing Vent Slot Lock Socket Vented Top Ballast Rail Support (2) P926 P927 One 26W or 32W Triple Tube Lamp One 42W Triple Tube Lamp Medium Beam 5 7/8" Conoid Apertures Optics and Applications Distribution from a single vertically mounted triple tube lamp is for general lighting. Spacing to mounting height ratios range from .93 to 1.11 depending upon which lamp is mounted. Use in corridors, entries, work stations or open area lighting in low to medium height ceilings. Safety Chain Specular Alzak Cone Lamp (By Others) Cone Retainer Spring Vertical Adjustment Design Features The two reflector optical system is protected by a rigid steel housing which keeps the reflectors in proper relationship to each other. The twist and lock socket prevents the lamp from falling if it is not properly engaged. It is a dependable fail-safe mechanism to prevent injury and litigation. Maximum ceiling thickness is 2". Ballast and lamp service from below. Finish Specular clear Alzak cones are standard. Optional colors and Softglow® finishes are available. Housings and structural parts are painted optical matte black to suppress stray light leaks. Steel parts are phosphate conditioned for corrosion resistance before painting. Ballasts Fully electronic, microprocessor controlled with variable starting current for inrush protection to assure rated lamp life. Input voltage ranges from 120V through 277V. Power factor .98, starting temperature 0° F (-18° C), THD < 10%. Pre-heat start < 1.0 second. End of lamp life protection. Rated for > 50,000 starts. General Fixtures are pre-wired, UL and C-UL listed for eight wire 75°C branch circuit wiring. Union made IBEW. Luminaire Efficiency Rating (LER) data is in the photometric directory located in Section Z. Dimensions and Lamps D A B C Number A Depth* B Aperture C Width D Length Lamps P926 9 3/4" 248mm 5 7/8" 149mm 10 1/2" 267mm 131/4" 337mm 26W or 32W Triple Tube P927 10 1/4" 260mm 5 7/8" 149mm 10 1/2" 267mm 131/4" 337mm 42W Triple Tube *Recess depth increases to 121/2" with EM and DM accessories. Accessories G Gold cone. R2 26" support rails. H Mocha cone. R5 52" support rails. P Graphite cone. WT White trim flange. WHT White complete trim. T Titanium cone. W Wheat cone. V347 347 volt ballast. Y Pewter cone. F Fuse. Z Bronze cone. S Softglow® finishes: add S before color letters. e.g. SW for Softglow® wheat cone, SC for Softglow® clear cone. DM Dimming ballast. Specify watts and volts. EM Emergency power includes integral charger light and test switch visible through aperture. Single lamp operation for 90 minutes. Specify volts. WRL Wattage restriction label, specify wattage. Matching Units Medium wide beam Wall washers Page P52 Pages P61, P62, P63 ** Click for link to pages in blue. Kurt Versen Company Point Source Lighting Westwood, New Jersey 07675 P51 IDL-2S26-M5-LD@120 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. of Lamps Rated Lamp Watts * CFTR42W/GX24Q 1 42 Min. Start Temp (°F/C) 50/10 ROVR Electronic Dimming Programmed Start Series 120-277 50/60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 0.39 09/47 0.03/1.00 10 0.99 1.6 2.13 Wiring Diagram Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 cm. 0 0 0 0 0 0 0 in. Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White cm. 0 0 0 0 0 0 0 OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 3.00 " 3 7.6 cm Height (H) Mounting (M) 1.18 " 4.60 " 1 9/50 4 3/5 3 cm 11.7 cm Revised 10/23/2007 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Section P fronts_UG 11/13/02 9:09 PM Page 32 Vented Housing Socket Bracket Lampholder Lamp (By Others) Vented Venting Rail Top Slot Support P958 P959 One 26W-32W Triple Tube Lamp One 42W Triple Tube Lamp Lens Wall Washers 7 1/4" Conoid Apertures Aperture Frame Lens Specular Alzak Cone Torsion Kicker Vertical Rotated 90¡ Spring Reflector Adjustment Optics and Applications The optical systems utilize triple tube lamps, full circle kicker reflectors and proprietary borosilicate glass prismatic spread lenses to provide even distribution without hot spots or striations. Parabolic cones control spill light and prevent objectionable brightness. Use to light walls, murals, bookcases, paintings, textured surfaces, etc. Design Features Sturdy steel housings protect the optical systems and allow easy access to all components. The cone and lens assemblies are held tightly to the ceiling with constant torsion spring pressure. Vented air flow design assures cool fixture temperature for optimal lamp performance. Maximum ceiling thickness 11/2". Ballast and lamp service from below. Finish Specular clear Alzak cones are standard. Optional colors and Softglow® finishes are available. Housings and structural parts are phosphated for corrosion resistance before being painted optical matte black for control of stray light leaks. Dimensions and Lamps D A C B Number A Depth 61/4" P958 159mm 1/4" 6 P959 159mm B Aperture 71/4" 184mm 71/4" 184mm C Width 13 1/2" 343mm 13 1/2" 343mm Matching Units Medium narrow beam downlights Medium wide beam downlights Cross baffled downlights Slope ceiling downlight Surface mount ** Click for link to pages in blue. D Length 19" 483mm 19" 483mm Page Page Page Page Page Lamp 26-32W Triple Tube 42W Triple Tube P53 P55 P24 P54 P41 Ballasts Fully electronic, microprocessor controlled with variable starting current for inrush protection to assure rated lamp life. Input voltage ranges from 120V through 277V. Operates multiple wattage interchangeably. Power factor .98, starting temperature 0° F (-18° C), THD < 10%. Pre-heat start < 1.0 second. End of lamp life protection. Rated for > 50,000 starts. General Fixtures are pre-wired, UL and C-UL listed for eight wire 75°C branch circuit wiring. Union made IBEW. Luminaire Efficiency Ratings (LER) do not apply to wall washers. Accessories G Gold cone. R2 26" support rails. H Mocha cone. R5 52" support rails. P Graphite cone. WT White trim flange. WHT White complete trim. T Titanium cone. W Wheat cone. V347 347 volt ballast. Y Pewter cone. F Fuse. Z Bronze cone. S Softglow® finishes: add S before color letters. e.g. SW for Softglow® wheat cone, SC for Softglow® clear cone. DM Dimming ballast. Specify watts and volts. EM Emergency power includes integral charger light and test switch visible through aperture. Single lamp operation for 90 minutes. Specify volts. WRL Wattage restriction label, specify wattage. Kurt Versen Company Point Source Lighting Westwood, New Jersey 07675 P66 REB-2S26-M1-BS-DIM Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. of Lamps Rated Lamp Watts CFQ26W/G24Q CFQ26W/G24Q 1 2 1 AMBISTAR Electronic Dimming Rapid Start Series 120 60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 26 26 26 Min. Start Temp (°F/C) 50/10 50/10 50/10 0.23 0.45 0.23 09/27 17/52 09/27 0.15/0.85 0.15/0.85 0.15/0.85 150 150 150 0.80 0.80 0.80 1.7 1.7 1.7 3.15 1.63 3.15 2 26 50/10 0.45 17/52 0.15/0.85 150 0.80 1.7 1.63 1 32 50/10 0.30 10/35 0.15/0.85 150 0.80 1.7 2.43 1 42 50/10 0.40 11/47 0.15/0.85 150 0.80 1.7 1.81 CFTR26W/GX24Q CFTR26W/GX24Q * CFTR32W/GX24Q CFTR42W/GX24Q Wiring Diagram Enclosure Diag. 134 The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. cm. 0 0 0 0 0 0 0 OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 2.4 " 2 2/5 6.1 cm Height (H) Mounting (M) 1.0 " 4.6 " 1 4 3/5 2.5 cm 11.7 cm Revised 09/11/2007 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Section P fronts_UG 11/13/02 7:57 PM Page 24 Socket Bracket Vented Top Lampholder Lamps (2) (By Others) Primary Reflector Venting Slot Rail Support P949 P57 Medium Beam Two 26-32-42W Triple Tube Lamps 8 3/8" Conoid Apertures Optics and Applications The two reflector optical system features an elliptical primary reflector and a deep parabolic shielding cone designed for use in higher ceilings. Pattern edges blend softly with adjacent units. See model P942 on page 56 for shallower recess depth and wider distribution. Safety Vertical Specular Alzak Cone Chain Adjustment Vented Cone Retaining Prism Lens Housing Spring (Optional) Design Features Construction allows easy access to all components. Vented air flow design lowers fixture temperature for optimal lamp performance. Fixtures accept Philips, Osram Sylvania, GE or other compatible lamps despite the variance in lamp bases. Maximum ceiling thickness 2". Ballast and lamp service from below. Finish A specular clear Alzak cone is standard. Optional colors and Softglow® finishes are available. The housing and all structural parts are phosphated for corrosion resistance before being painted optical matte black for control of stray light leaks. Ballast Fully electronic, microprocessor controlled with variable starting current for inrush protection to assure rated lamp life. Input voltage ranges from 120V through 277V. Operates 26W, 32W or 42W triple tube lamps interchangeably. Power factor .98, starting temperature 0° F (-18° C), THD < 10%. Pre-heat start < 1.0 second. End of lamp life protection. Rated for > 50,000 starts. Dimensions and Lamps D A C B Number A Depth B Aperture C Width D Length Lamps P949 91/4" 234mm 8 3/8" 213mm 13 1/2" 343mm 19" 483mm Two 26-32-42W Triple Tube Brightness Number P949 Lamps Plane 85¡ Two 32W Triple Tube Philips 0¡ 12 90¡ 11 Two 42W Triple Tube Philips 0¡ 16 90¡ 75¡ 65¡ 55¡ 45¡ 17 32 58 7031 19 37 54 8534 23 44 74 9398 15 26 50 72 11411 Two 32W Triple Tube 0¡ Osram/Sylvania 90¡ 12 15 23 48 6454 12 25 38 93 7385 Two 42W Triple Tube 0¡ Osram/Sylvania 90¡ 15 21 30 62 8442 16 33 50 121 9661 Data in footlamberts. Photometer readings, Maximum Brightness Method. See note 7 on the other side. General Fixtures are pre-wired, UL and C-UL listed for eight wire 75°C branch circuit wiring. Union made IBEW. Luminaire Efficiency Rating (LER) data is in the photometric directory located in Section Z. Accessories G Gold cone. R2 26" support rails. H Mocha cone. R5 52" support rails. P Graphite cone. WT White trim flange. T Titanium cone. WHT White complete trim. W Wheat cone. DCE Double circuiting. Y Pewter cone. V347 347 volt ballast. Z Bronze cone. F Fuse. S Softglow® finishes: add S before color letters. e.g. SW for Softglow® wheat cone, SC for Softglow® clear cone. DM Dimming ballast, 26 or 32W. Specify watts and volts. DM2 Dimming ballasts, two 42W. Specify volts. LS Lamp shield, acrylic, 26-32W only. LP Prism lens, acrylic, 26-32W only. EM Emergency power includes integral charger light and test switch visible through aperture. Single lamp operation for 90 minutes. Specify volts. WRL Wattage restriction label, specify wattage. Matching Units Sloped ceilings Shallow depth downlight Wall washer Surface cylinder Page Page Page Pages P58 P56 P67 P42, P43 * Click for link to pages in blue. Kurt Versen Company Point Source Lighting Westwood, New Jersey 07675 IDL-2S26-M5-LD@277 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type CFTR26W/GX24Q * CFTR26W/GX24Q Num. of Lamps Rated Lamp Watts 1 2 ROVR Electronic Dimming Programmed Start Series 120-277 50/60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 26 Min. Start Temp (°F/C) 50/10 0.11 08/30 0.03/1.00 10 0.99 1.6 3.33 26 50/10 0.20 13/55 0.03/1.00 10 0.99 1.6 1.82 Wiring Diagram Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 cm. 0 0 0 0 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. cm. 0 0 0 0 0 0 0 OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 3.00 " 3 7.6 cm Height (H) Mounting (M) 1.18 " 4.60 " 1 9/50 4 3/5 3 cm 11.7 cm Revised 10/23/2007 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Section P fronts_UG 11/13/02 9:09 PM Page 33 Lampholder Vented Top Socket Bracket Lamps (2) (By Others) Venting Slot Rail Support P955 P67 Wall Washer Two 26-32-42W Triple Tube Lamps 8 3/8" Conoid Aperture Vented Housing Specular Alzak Cone Kicker Reflector Aperture Frame Vertical Adjustment Optics and Applications A full circle kicker reflector directs a uniform wash light to adjacent walls. The pattern is free from spikes, striations or dropouts and features wide lateral distribution. The downlight component is uniform with a soft edge to blend with nearby units. Use in low to medium height ceilings. Design Features Construction allows easy access to all components. Vented air flow design assures cool fixture temperature for optimal lamp performance. Maximum ceiling thickness 2". Ballast and lamp service from below. Finish A specular clear Alzak cone is standard. Optional colors and Softglow® finishes available. Housing and structural parts are phosphated for corrosion resistance, then painted optical matte black for control of stray light leaks. Ballast Fully electronic, microprocessor controlled with variable starting current for inrush protection to assure rated lamp life. Input voltage ranges from 120V through 277V. Operates 26W, 32W or 42W triple tube lamps interchangeably. Power factor .98, starting temperature 0° F (-18° C), THD < 10%. Pre-heat start < 1.0 second. End of lamp life protection. Rated for > 50,000 starts. General Fixtures are pre-wired, UL and C-UL listed for eight wire 75°C branch circuit wiring. Union made IBEW. Luminaire Efficiency Ratings (LER) do not apply to wall washers. Dimensions and Lamps D A B Number P955 A Depth 7" 178mm C B Aperture 3 8 /8" 216mm C Width D Length Lamps 1 19" 483mm Two 26-32-42W Triple Tube 13 /2" 343mm Accessories G Gold cone. R2 26" support rails. H Mocha cone. R5 52" support rails. P Graphite cone. WT White trim flange. WHT White complete trim. T Titanium cone. W Wheat cone. DCE Double circuiting. V347 347 volt ballast. Y Pewter cone. Z Bronze cone. F Fuse. S Softglow® finishes: add S before color letters. e.g. SW for Softglow® wheat cone, SC for Softglow® clear cone. DM Dimming ballast, 26 or 32W. Specify watts and volts. DM2 Dimming ballasts, two 42W. Specify volts. EM Emergency power includes integral charger light and test switch visible through aperture. Single lamp operation for 90 minutes. Specify volts. WRL Wattage restriction label, specify wattage. L Limited wall wash. D Double wall wash. C 250° corner wall wash. Matching Units Recessed downlight Slope ceiling downlight Surface mount Page P57 Page P58 Pages P42, P43 ** Click for link to pages in blue. Kurt Versen Company Point Source Lighting Westwood, New Jersey 07675 IDL-2T42-M5-BS@277 Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. of Lamps Rated Lamp Watts * CFTR32W/GX24Q 2 ROVR Electronic Dimming Programmed Start Series 120-277 50/60 HZ Active Input Current (Amps) Input Power (Watts) (min/max) Ballast Factor (min/max) MAX THD % Power Factor Lamp Current Crest Factor B.E.F. 32 Min. Start Temp (°F/C) 50/10 0.21 19/75 0.03/1.00 10 0.99 1.6 1.33 2 42 50/10 0.36 18/98 0.03/1.00 10 0.99 1.6 1.02 1 57 50/10 0.24 16/65 0.03/1.00 10 0.99 1.6 1.54 1 70 50/10 0.27 16/75 0.03/1.00 10 0.99 1.6 1.33 CFTR42W/GX24Q CFTR57W/GX24Q CFTR70W/GX24Q Wiring Diagram Enclosure The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0 0 0 0 0 cm. 0 0 0 0 0 0 0 in. Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White cm. 0 0 0 0 0 0 0 OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 3.00 " 3 7.6 cm Height (H) Mounting (M) 1.18 " 2.00 " 1 9/50 2 3 cm 5.1 cm Revised 12/03/2003 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 1 5/8" 4663666666 ∅ 41 mm 2 mm 1/16" 6 666634 70 mm 2 13/16" LED orientation luminaire 466663 E 1 1/16" 43 6 6666666 ∅ 27 mm 1 5/16" 261 ∅ 32 mm LED Lä ö ü Dry Damp Wet ÖOutdoor 33760.023 LED daylight white LED 0.3W 12V DC Product description Housing with gasket: stainless steel. Installation bush with ribs: plastic. Cable, L 19 11/16" / 500mm. Clear prismatic diffuser with circular light aperture. Cover ring: corrosion resistant stainless steel, with 1/4" / 6mm safety glass. Load 1124lb.wt / 5kN. Control gear to be ordered separately. Suitable for wet location (IP68): dustproof. Weight 0.22lbs / 0.10kg ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/33760.023 1/3 LED orientation luminaire E Accessories 33885.023 Recessed housing IP67 for installation in concrete floors or compressed natural ground with 1" / 25mm floor covering. Cast aluminum, black, double powdercoated. 2 cable entries with IP67 ports. Through-wiring possible. Suitable for wet location (IP67): dustproof and protected against immersion damage. Weight 1.54lbs / 0.70kg L ä ö ü ÖOutdoor Dry Damp Wet 2 13/16" 4663 104 mm 72 mm 25 mm 1" 90 mm 3 9/16" 4 1/8" 46663 46663 ∅ 27 mm 36646666 1 1/16" 666663664 256 mm 10 1/16" 4666666666663 33856.023 Control gear for max. 40 orientation luminaires. Input voltage 100V-240V AC, 120V250V DC. Output voltage 12V DC. Suitable for wet location (IP65): dustproof and water-jet proof. Weight 1.32lbs / 0.60kg L ä ö B ÖOutdoor Dry Damp Wet 7 1/16" x 5 7/16" 4666666663 180 x 138 mm 33886.023 Recessed housing IP67 for installation in concrete floors or compressed natural ground with 2" / 50mm floor covering. Cast aluminum, black, double powdercoated. 2 cable entries with IP67 ports. Through-wiring possible. Suitable for wet location (IP67): dustproof and protected against immersion damage. Weight 1.54lbs / 0.70kg L ä ö ü ÖOutdoor Dry Damp Wet 33872.000 Housing for recessed mounting for mounting in plaster. Weight 0.20lbs / 0.09kg L 1 1/16" 2" 100 mm 70 mm 50 mm 115 mm 4 9/16" 3664 2 3/4" 4663 4636666 46663 3 15/16" ∅ 33 mm 1 5/16" 100 mm 4663 3 15/16" 50 mm 2" ∅ 27 mm 3664 366664 6666663664 7 1/16" x 5 7/16" 4666666663 180 x 138 mm LED orientation luminaire 33760.023 2/3 Nimbus halogen Design: Louis Poulsen Type: Project: Catalog Number: NOTES: INSTALLATION IS SUBJECT TO LOCAL CODES AND JURISDICTION. PROPER DRAINAGE MUST BE PROVIDED. louis poulsen (3) M5 X 12mm STAINLESS STEEL SOCKET CAP SCREWS HEAT TEMPERED IMPACT RESISTANT CLEAR OR FROSTED SODA LIME GLASS, .315" THICK OR ANTI-SLIP, .370" MINIMUM THICKNESS, WITH TREAD .460" 316 MARINE GRADE STAINLESS STEEL TOP PLATE WITH BEVELED EDGE, .240" THICK WATERTIGHT SILICONE GASKET GROUND LEVEL 316 MARINE GRADE STAINLESS STEEL SLEEVE WITH WELDED BRACKET FOR LUMINAIRE ATTACHMENT Ø5.9" 0.3" TRIM PROJECTION 5.1" SLEEVE MAXIMUM LAMP: 1/20W/35W/50W/ MR-16 (BY OTHERS) LAMPHOLDER: GU5.3 CERAMIC CONNECTOR BLOCK 8.9" HIGH PRESSURE DIE CAST ALUMINUM BODY ANODIZED AND POWDER COATED WITH PAINT CONTAINING PTFE TO PROVIDE MAXIMUM CORROSION PROTECTION WATERTIGHT SILICONE SEAL MOLDED POLYMER TRANSFORMER HOUSING TOP WATERTIGHT SILICONE GASKET 12V ELECTRONIC TRANSFORMER FOR 120V OR 277V OPERATION (SPECIFY) 15.0" MOLDED POLYMER INTEGRAL TRANSFORMER HOUSING RESIN WELL FOR WATERTIGHT WIRE CONNECTION 1/2" NPT NICKEL PLATED BRASS FEMALE CONDUIT CONNECTOR FASTENED INTO CAST BODY BY M20 THREAD COMPARTMENT TO ALLOW FOR AMPLE LENGTH OF CABLE (BY OTHERS) FOR REMOVAL OF INGROUND LUMINAIRE FROM STAINLESS STEEL SLEEVE DURING MAINTENANCE M20 BLANKING PLUG REMOVABLE SLEEVE BOTTOM WITH A Ø.875" HOLE AND A KNOCKOUT WARNING: WIRING COMPARTMENT MUST BE FILLED WITH TWO PARTS RESIN (SUPPLIED) TO PREVENT WATER OR MOISTURE PENETRATION WHICH MAY CAUSE ELECTRICAL SHOCK LIQUID TIGHT STRAIGHT-THRU CONNECTOR, FLEXIBLE CONDUIT, RIGID PVC CONDUIT, AND A 1/2" NPT CONDUIT CONNECTOR (BY OTHERS) Louis Poulsen Lighting, Inc., 3260 Meridian Parkway, Fort Lauderdale, FL 33331 Telephone: (954) 349-2525 Fax: (954) 349-2550 www.louispoulsen.com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ubus Floor washlight 124 mm 4 7/8" 4666663 with LED 4 7/8" 2 11/16" 4666663 4663 124 mm 68 mm LED Nä ö ü Dry Damp Wet ÖOutdoor 33364.023 Graphit m LED daylight white LED 3.3W 300lm 5500K Version 3 Product description Housing and wall plate: corrosionresistant cast aluminum, No-Rinse surface treatment. Double powdercoated. Optimised surface for reduced accumulation of dirt. Electronic control gear 120V, 60Hz. 2 cable entries. Through-wiring possible. 3-pole terminal block. Replaceable LED module: high-power LEDs on metal-core PCB. Collimating lens, plastic, clear. Softec lens as safety glass. Sculpture lens Suitable for wet location (IP65): dustproof and water jet-proof. Weight 2.98lbs / 1.35kg Housing temperature 94°F / 34°C Temperature on the cover glass 96°F / 35°C ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com 2.60ft f=0.80 ft 4 0.1 0.5 5 2 0 2 ft 8 6 4 2 LED 3.3W 300lm 5500K Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/33364.023 1/2 E Kubus Floor washlight Accessories 33975.000 Ground socket Metal, hot-dip galvanised. Cable entry. Weight 3.86lbs / 1.75kg 33983.000 Mounting plate Corrosion-resistant cast aluminum, No-Rinse surface treatment. Graphit m, double powder-coated. Weight 2.20lbs / 1.00kg ä ö ü ÖOutdoor Dry Damp Wet 3 1/4" 666666 36664 220 mm 8 11/16" 466663 502 mm 19 3/4" 4666666663 ∅ 83 mm 5/8" 8 11/16" 466663 3646666 220 mm 2 3/8" 666666666 3664 ∅ 60 mm 15.5 mm 4 7/8" 366664 ∅ 124 mm 800 mm 4666666666663 33363.000 Post Aluminum profile, No-Rinse surface treatment. Double powder-coated. Base plate for mounting on ground socket, concrete anchor or mounting plate: cast aluminum. 2 screwed cable glands M20. Mounting accessories to be ordered separately. Weight 5.95lbs / 2.70kg ä ö ü ÖOutdoor Dry Damp Wet 31 1/2" 200 mm 7 7/8" 46666 3 33979.000 Concrete anchor Mounting plates with threaded bar and fixing screws. Individual parts to be assembled on-site. Weight 0.55lbs / 0.25kg 4 7/8" 11/16" 666666 4663 366346666 124 mm Kubus Floor washlight 33364.023 94 mm 2/2 E Midipoll Bollard luminaire 800 mm 31 1/2" 46666666666663 with LED 4 3/4" 36666666666 4 ∅ 120 mm LED Nä ö ü Dry Damp Wet ÖOutdoor 33344.023 Graphit m LED daylight white LED 10W 420lm 5500K Version 1 Product description For mounting on accessories. Cross-shaped aluminum profile and cylindrical housing: corrosion-resistant cast aluminum, No-Rinse surface treatment. Double powder-coated. Optimised surface for reduced accumulation of dirt. Electronic control gear 120V, 50Hz. 2 cable entries. Through-wiring possible. 3-pole terminal block. Replaceable LED module: high-power LEDs on metal-core PCB with spot reflector-lens system. Cylindrical luminaire head with lower prismatic lens: corrosion-resistant cast aluminum, double powder-coated. Mounting accessories to be ordered separately. Suitable for wet location (IP65): dustproof and water jet-proof. Weight 10.58lbs / 4.80kg Housing temperature 115°F / 46°C Temperature on the cover glass 99°F / 37°C Maximum wind load area 1.08ft2 ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com 2.30ft f=0.80 ft 6 0.1 3 0 5 3 0.5 ft 6 3 0 3 LED 10W 420lm 5500K Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/33344.023 1/2 E Midipoll Bollard luminaire Accessories 33975.000 Ground socket Metal, hot-dip galvanised. Cable entry. Weight 3.86lbs / 1.75kg 33982.000 Mounting plate Corrosion-resistant cast aluminum, No-Rinse surface treatment. Graphit m, double powder-coated. Weight 3.75lbs / 1.70kg ä ö ü ÖOutdoor Dry Damp Wet 3 1/4" 666666 36664 ∅ 260 mm 10 1/4" 46666 3 502 mm 19 3/4" 2 3/8" 4666666663 ∅ 83 mm 15/16" 6666364 24 mm 666666666 3664 ∅ 60 mm 200 mm 7 7/8" 46666 3 33980.000 Concrete anchor Mounting plates with threaded bar and fixing screws. Individual parts to be assembled on-site. Weight 0.66lbs / 0.30kg 4 7/8" 366664 ∅ 124 mm Midipoll Bollard luminaire 33344.023 2/2 Kipp Wall compact f luorescent Design: Alfred Homann Type: Project: Catalog Number: Ø10.8" Ø9.67" Ø0.3" 120° DIE CAST ALUMINUM TOP SHADE WITH NATURAL PAINTED ALUMINUM OR BLACK POWDER COAT FINISH, ALL WITH HIGH REFLECTANCE WHITE PAINTED UNDERSIDE. ENTIRE FIXTURE HEAD IS REMOVABLE FOR RELAMPING 120° MOUNTING PLATE DETAIL OPEN TOP CONICAL SHAPE TRANSLUCENT INJECTION MOLDED HIGH TEMPERATURE WHITE OPAL ACRYLIC DIFFUSER VANDAL RESISTANT HIGH IMPACT INJECTION MOLDED U.V. STABILIZED CLEAR POLYCARBONATE ENCLOSURE DIE CAST THREE-ARM FRAME WITH NATURAL PAINTED ALUMINUM OR BLACK POWDER COATED FINISH MAXIMUM LAMP: 1/26W/32W/CF COMPACT FLUORESCENT (BY OTHERS) LAMPHOLDER: GX24q-3 ELECTRICAL ASSEMBLY WITH ELECTRONIC BALLAST FOR 120-277V OPERATION TAPERED DIE CAST ALUMINUM HOUSING WITH NATURAL PAINTED ALUMINUM OR BLACK POWDER COATED FINISH EXTRUDED ALUMINUM ARM WITH NATURAL PAINTED ALUMINUM OR BLACK POWDER COATED FINISH DIE CAST ALUMINUM WALL PLATE AND EXTRUDED ALUMINUM ARM WITH NATURAL PAINTED ALUMINUM OR BLACK POWDERCOATED FINISH, SECURED TO WALL USING 3 SCREWS @ 120° ON A Ø9.67 BOLT CIRCLE 4" OCTAGONAL JUNCTION BOX (BY OTHERS) Louis Poulsen Lighting, Inc., 3260 Meridian Parkway, Fort Lauderdale, FL 33331 Telephone: (954) 349-2525 Fax: (954) 349-2550 www.louispoulsen.com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rand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type Num. Rated Min. Start of Lamp Watts Temp (°F/C) Lamps CFM26W/GX24Q CFM26W/GX24q * CFM32W/GX24q CFM42W/GX24q CFQ26W/G24q CFQ26W/G24q CFS21W/GR10q FT24W/2G11 1 2 1 1 1 2 2 2 26 26 32 42 26 26 21 24 Input Current (Amps) 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0/-18 0.13 0.23 0.16 0.20 0.12 0.22 0.22 0.21 Wiring Diagram BLUE BLACK WHITE Ballast Factor MAX THD % Power Factor MAX Lamp Current Crest Factor B.E.F . 1.10 1.00 0.98 0.98 1.00 1.00 1.12 0.93 10 10 10 10 10 10 10 10 0.98 0.99 0.98 0.98 0.98 0.99 0.99 0.99 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 3.79 1.85 2.72 2.13 3.70 1.96 2.20 1.94 Enclosure WIRING: (2) LAMPS LINE Input Power (ANSI Watts) 29 54 36 46 27 51 51 48 SMARTMATE Electronic Programmed Start Series 120-277 50/60HZ Active (1) LAMP BLUE BALLAST YELLOW GREEN RED RED Green Terminal must be Grounded The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 0.0 0.0 0.0 0.0 0 cm. in. Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White cm. OverAll (L) 4.98 " 4 49/50 12.6 cm Width (W) 2.4 " 2 2/5 6.1 cm Height (H) Mounting (M) 1.0 " 4.6 " 1 4 3/5 2.5 cm 11.7 cm Revised 09/02/2004 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Catalog Number Notes Type FEATURES & SPECIFICATIONS INTENDED USE For use in retail areas, coves, corridors and lobbies where uninterrupted continuous flow of light is required in displays or coves. Staggered Strip SS NY ATTRIBUTES Designed with ideal 4" overlap of fixtures to assure shadow-free illumination. Utilizes high efficiency T8 lamps and electronic ballasts. CONSTRUCTION Constructed to comply with New York City electric code. Made in USA. Housing formed from cold-rolled steel. FINISH T8, ELECTRONIC BALLAST 2', 3', 4' or 8' Length Five-stage iron-phosphate pretreatment ensures superior paint adhesion and rust resistance. Painted parts finished with high-gloss, baked white enamel. 1 or 2 Lamps ELECTRICAL SYSTEM Thermally protected, resetting, Class P, HPF, non-PCB, UL Listed., CSA Certified ballast is standard. Electronic ballasts are sound rated A. INSTALLATION For unit or row installations, numerous knockouts for easy installation. For surface mounting. LISTING UL Listed. WARRANTY Guaranteed for one year against mechanical defects in manufacture. NOTE: Specifications subject to change without notice. ORDERING INFORMATION For shortest lead times, configure product using standard options (shown in bold). Example: SS 2 32 MVOLT GEB10IS NYC SS Series Number of lamps SS Staggard strip 1 For tandem doublelength unit, add prefix T. Example: TSS 2 Not included. Lamp type 17 25 17W T8 (24") 25W T8 (36") 32 32W T8 (48") Voltage Options MVOLT1 GEB10IS Electronic ballast, <10% THD, instant start EL Emergency battery pack (nominal 300 lumens) See Life Safety Section EL14 NY I.B.E.W. union made, NYC code compliant NY3 I.B.E.W. Local 3 union made Accessories NOTES: Order as separate catalog numbers. 1 MVOLT (120-277 volt). SSASR 1 48WH Asymmetric reflector, 4' white for 1-lamp fixture* SSASR 2 48WH Asymmetric reflector, 4' white for 2-lamp fixture* SSSMR 1 48WH SSSMR 2 48WH Symmetric reflector, 4' white for 1-lamp fixture* Symmetric reflector, 4' white for 2-lamp fixture* * Specular Aluminum (SAR) and Specular Finish Steel (SSR) also available. Substitute SAR or SSR for WH in catalog number. Fluorescent Sheet #: SS-NY NYCFL-650 SS NY MOUNTING DATA DIMENSIONS For continuous row installation, surface or suspended mounting. Inches (centimeters). Subject to change without notice. One endplate per fixture supplied. Channel-to-channel connection uses two spade connectors inserted as shown in Fig A. To determine installed length, deduct 4" for each overlap. Example: Total lamp length of three SS 232's is 156", less 8" for two overlaps. Installed length is 148". Aluminum channels have different mounting details. All size channels have just (2) 7/8" K.O.s, 6" from each end. A = 11/16 (1.74) Dia. K.O. B = 2 (5.08) Dia. K.O.* C = 7/8 (2.22) Dia. K.O. *on 68" channels and longer Lithonia Lighting Sheet # SS-NY ©2008 Acuity Brands Lighting, Inc., Rev. 2/1/09 Fluorescent One Lithonia Way, Conyers, GA 30012 Phone: 800-858-7763 www.lithonia.com VEL-3P32-SC Brand Name Ballast Type Starting Method Lamp Connection Input Voltage Input Frequency Status Electrical Specifications Lamp Type F17T8 F25T8 F25T8 * F32T8 F32T8 F32T8/ES (30W) F32T8/ES (30W) F40T8 Num. Rated Lamp Min. Start Input Current Input Power Ballast of Watts Temp (°F/C) (Amps) (ANSI Watts) Factor Lamps 3 17 0/-18 0.17 47 0.99 2 25 0/-18 0.14 54 1.06 3 25 0/-18 0.24 66 0.93 2 32 0/-18 0.24 65 1.03 3 32 0/-18 0.31 85 0.88 2 30 60/16 0.22 61 1.03 3 30 60/16 0.29 79 0.88 2 40 0/-18 0.31 79 1.01 Wiring Diagram WHITE BLACK MAX THD % 15 20 15 15 15 20 20 15 STANDARD ELEC Electronic Instant Start Parallel 277 60 HZ Active Power Factor 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 MAX Lamp B.E.F. Current Crest Factor 1.7 2.11 1.7 1.96 1.7 1.41 1.7 1.58 1.7 1.04 1.7 1.69 1.7 1.11 1.7 1.28 Enclosure BLUE BALLAST BLUE BLUE RED LAMP LINE LAMP Diag. 70 Insulate unused blue lead for 1000V The wiring diagram that appears above is for the lamp type denoted by the asterisk (*) Enclosure Dimensions Standard Lead Length (inches) Black White Blue Red Yellow Gray Violet in. 25L 25L 31R 37R cm. 63.5 63.5 78.7 94 0 0 0 Yellow/Blue Blue/White Brown Orange Orange/Black Black/White Red/White in. cm. 0 0 0 0 0 0 0 OverAll (L) 9.50 " 9 1/2 24.1 cm Width (W) 1.7 " 1 7/10 4.3 cm Height (H) Mounting (M) 1.18 " 8.90 " 1 9/50 8 9/10 3 cm 22.6 cm Revised 08/21/2002 Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representative of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Nyhavn Maxi Pendant D e s i g n : A l f r e d H o m a n n a n d O l e V. K j æ r compact f luorescent Type: Project: Catalog Number: 4" OCTAGONAL JUNCTION BOX (BY OTHERS) 5.3" DIA. WHITE CEILING CANOPY CEILING LINE 1.0" PVC COVERED POWER CORD 3-CONDUCTOR; 18 AWG; 12' LG. WHITE VERSION: WHITE CORD, NATURAL VERSIONS: BLACK CORD PVC COVERED FINE STAINLESS STEEL AIRCRAFT SUSPENSION CABLE; 12' LG. WHITE VERSION: WHITE COVER NATURAL VERSION: BLACK COVER DIE CAST ALUMINUM TOP WITH WHITE OR NATURAL PAINTED ALUMINUM POWDER COATED FINISH OR NATURAL SHOT PEENED ALUMINUM ELECTRONIC BALLAST FOR 120-277V OPERATION SPUN AND ANODIZED ALUMINUM SOCKET COVER LAMPHOLDER: UNIVERSAL TURN AND LOCK LAMPHOLDER SUITABLE FOR GX24q-3 AND GX24q-4 (2) DIE CAST ALUMINUM ANNULAR RINGS WITH WHITE OR NATURAL PAINTED ALUMINUM POWDER COATED FINISH OR NATURAL SHOT PEENED ALUMINUM 15.0" INJECTION MOLDED OPAL U.V. STABILIZED POLYCARBONATE LAMP ENCLOSURE (REMOVABLE FOR RELAMPING) SPUN ALUMINUM REFLECTOR SHADE WITH WHITE OR NATURAL PAINTED ALUMINUM POWDER COATED FINISH OR NATURAL SHOT PEENED ALUMINUM 22.3" DIA. MAXIMUM LAMP: 1/26/32/42W/CF COMPACT FLUORESCENT (BY OTHERS) Louis Poulsen Lighting, Inc., 3260 Meridian Parkway, Fort Lauderdale, FL 33331 Telephone: (954) 349-2525 Fax: (954) 349-2550 www.louispoulsen.com Nyhavn Maxi Pendant compact f luorescent pendants Report No.: Poulsen Report No.: Luminaire: Lamp: Efficiency: Description: Candlepower Distribution Vertical Angle 0 5 15 25 35 45 55 65 75 90 120 150 180 L3571 NYP-MAX-1-42W-GX24Q-3.IES Nyhavn Maxi Pendant, White 1/42W/GX24Q-3 59.1% All data shown are per 1000 lumens. This report can be used for calculation on all versions Use only actual lumen data when calculating Zonal Lumen Summary Zone 0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180 Candela 138 135 125 126 126 121 116 105 60 4 3 2 1 Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20% Ceiling Reflectance (%) 80 Wall Reflectance (%) 70 50 30 Room Cavity Ratio 0 70 70 70 1 62 59 56 2 56 50 45 3 50 43 38 4 45 38 32 5 41 33 27 6 38 29 24 7 35 26 21 8 33 24 19 9 30 22 18 10 28 20 15 10 70 50 70 53 41 33 27 23 19 17 15 13 12 68 61 54 48 44 40 37 34 31 29 27 68 58 49 42 37 32 29 26 23 21 20 70 Lumens 107 185 383 574 11 13 16 17 591 % Lamp 10.6 18.5 38.3 57.4 1.1 1.3 1.6 1.7 59.1 % Fixture 18.0 31.4 64.8 97.1 1.9 2.3 2.7 2.9 100.0 30 10 50 50 30 10 50 30 30 10 50 10 30 10 0 0 68 55 45 37 31 27 23 21 18 16 15 65 52 41 33 27 23 19 17 15 13 12 65 55 46 40 3 31 27 25 22 21 19 65 52 43 36 30 26 23 20 18 16 15 65 50 40 32 26 22 19 16 14 13 12 62 52 44 38 33 29 26 24 22 20 18 62 50 41 34 29 25 22 19 17 16 14 62 48 38 31 26 22 19 16 14 13 11 59 50 42 36 32 28 25 23 21 19 18 59 48 39 33 28 24 21 19 17 15 14 59 47 37 30 25 21 18 16 14 13 11 57 45 36 29 24 20 17 15 13 11 10 Design Alfred Homann Concept Nyhavn Maxi Pendant creates general illumination, mainly directed downwards by the conical shade. The rings ensure that stray light is controlled, and direct a small amount of light onto the top side of the shade for self-illumination. Finish Copper, brushed. Copper, brushed and lacquered. White or natural painted aluminum, powder coated. Material Canopy: Die cast aluminum or spun aluminum. Shades: Spun aluminum or spun copper. Enclosure: Injection molded clear polycarbonate, injection molded partly frosted polycarbonate or injection molded white opal polycarbonate. Rings: Die cast aluminum or copper plated, die cast red brass. Top: Die cast aluminum or copper plated, die cast red brass. Pendant stem: Extruded aluminum. Mounting Suspension type: 1x PVC covered stainless steel aircraft cable or pendant stem. Suspension length: ³ cord or ³ stem. Canopy: White. Cord type: 3-conductor, 18 AWG PVC power cord. Cord color: Natural and copper version: Black cord or white version: white cord. Cord length: ³ Canopy mounting: Directly to a recessed junction box. Weight Max. 41 lbs. Label cUL, Damp location, Wet location. IBEW. Product code Light source Voltage Finish Suspension Mounting NYP-MAX 1/70W/CMH/T-6 G12 1/100W/MH/ED-17 medium 1/26W/32W/42W/CF GX24q-3/4 120/208/240/277V 120-277V 120/277V COP LAC COP NAT PAINT ALU WHT 12 ft. CORD 3 ft. STEM INDOOR OUTDOOR a. CMH variants provided with a partly frosted enclosure. b. CF variants provided with an opal enclosure. c. MH variants provided with clear enclosures. d. CMH variants provided with one 120/277V remote mounted F-can ballast. e. CF variants provided with a universal wattage socket and 120-277V integral electronic ballast. f. MH variants provided with a recessed ballast box containing one 120/208/240/277V open core and coil ballast. g. 3 ft. pendant stem for outdoor version. h. 12 ft. cord/cable for indoor version. Info notes: I. All enclosures are U.V. stabilized polycarbonate. II. Copper variants for indoor use are brushed and lacquered. III. Copper variants for outdoor use are untreated copper that will develop a verdigris patina. Louis Poulsen Lighting, Inc., 3260 Meridian Parkway, Fort Lauderdale, FL 33331 Telephone: (954) 349-2525 Fax: (954) 349-2550 www.louispoulsen.com E LC Washlight CO ∅ 164 mm 6 11/16" 4663 6666666 ∅ 170 mm T6 447 mm 17 5/8" 466366666666 46666666663 12 mm CO 6 7/16" 145 mm 1/2" 5 6/8" 6666666466364666 for metal halide lamps 20 5/8" 4666666666663 523 mm Size 5 40° Lä ö B Dry Damp Wet ÄIndoor 22681.023 Reflector silver T6 70W G12 7300lm ECG Product description Housing: cast aluminum, designed as heat sink. Mounting ring: cast aluminum, white (RAL9002) powder-coated. 4-point support and screw tightening for fixing to mounting plate. Mounting plate for preinstallation with junction box for through-wiring. Electronic control gear 120V, 60Hz on top of junction box. Snap-in plug for connection between junction box and luminaire. Low brightness reflector with wallwash scoop to provide wall-illumination: aluminum, specular anodized. Cut-off angle 40° from horizontal. Diffuser as lamp cover: glass, frosted. Type Non IC luminaire. Insulation materials must be kept away from the luminaire by a minimum of 3". Thermally protected luminaire. Luminaires protected with disconnecting switch. Suitable for damp location. Removal of reflector allows access to junction box from below. Max. ceiling thickness 3/4". Weight 9.70lbs / 4.40kg ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/22681.023 1/3 LC Washlight E Planning Data Illuminance (fc) Specifications: Number of luminaires n > 5 Light loss factor 0.80 Without indirect component Without peripheral area Wall height (ft) 15 T6 70W G12 7300lm Offset from wall (ft) Luminaire spacing (ft) Distance from ceiling (ft) 0.000 1.500 3.000 4.500 6.000 7.500 9.000 10.500 12.000 13.500 15.000 3 3 below the luminaire 0 27 31 37 34 29 22 18 14 11 9 between the luminaires 0 25 35 31 29 22 17 13 11 9 7 3 4 below the luminaire 0 20 25 29 25 22 18 14 11 9 8 between the luminaires 0 19 25 27 24 19 14 11 9 7 6 LC Washlight 22681.023 4 4 below the luminaire 0 14 16 18 21 20 18 15 12 10 9 between the luminaires 0 14 14 19 18 17 14 11 9 8 7 4 5 below the luminaire 0 11 13 14 17 16 14 13 11 9 7 between the luminaires 0 11 12 17 16 14 12 10 8 7 6 2/3 Metal Halide Lamp Ballast Catalog Number 72C5280 For 70W M85 60 Hz HX-HPF Status: Active DIMENSIONS AND DATA 10.50" 2.63" CASE "F-1" 11.13" 3.19" 11.75" Capacitor: INPUT VOLTS HX-HPF CIRCUIT TYPE 90% POWER FACTOR (min) REGULATION Line Volts ±5% Lamp Watts ±10% LINE CURRENT (Amps) Operating............................................................... Open Circuit........................................................... Starting................................................................... UL TEMPERATURE RATINGS A (105°C) Insulation Class 1029 Coil Temperature Code -20°F or -30°C MIN. AMBIENT STARTING TEMP. 240 NOM. OPEN CIRCUIT VOLTAGE INPUT VOLTAGE AT LAMP DROPOUT................................. 94 INPUT WATTS RECOMMENDED FUSE (Amps)............................................. CORE and COIL Dimension (A) Dimension (B) 8.5 Weight (lbs.) 12" Lead Lengths CAPACITOR REQUIREMENT Microfarads Volts (min.) Fault Current Withstand (amps) 60 Hz TEST PROCEDURES (Refer to Philips Lighting Electronics N.A. TEST Procedure for HID Ballasts - Form 127 High Potential Test (Volts) 1600 1 minute 2000 2 seconds 215-265 Open Circuit Voltage Test (Volts) Short-Circuit Current Test (Amps) 1.05-1.35 Secondary Current Input Current.......................................................... 120 277 0.85 1.70 1.00 0.37 0.75 0.45 A A 100 225 5 2 0.60- 0.251.10 0.50 - - Wiring Diagram: All Lead Lengths 12" 277 V 120V COMMON YELLOW/BLUE The capacitor is included as part of the potted assembly. BLACK BALLAST WHITE RED LAMP GROUND CASE F-Can Wiring Diagram Typical Ordering Information Ignitor: IN CAN (please call Philips Lighting Electronics N.A. for suffix availability) Order Suffix Description The ignitor is included as part of the potted assembly. Ballast to Lamp Distance (BTL) = 10 feet Temp Rating: 90°C Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representitive of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Revised: 06/27/05 - E LC Downlight CO ∅ 164 mm 6 11/16" 4663 6666666 ∅ 170 mm 447 mm 17 5/8" 466366666666 46666666663 12 mm CO 6 7/16" 145 mm 1/2" 5 6/8" 6666666466364666 for metal halide lamps 20 5/8" 4666666666663 523 mm Size 5 40° T6 Lä ö B Dry Damp Wet ÄIndoor 22680.023 Reflector silver T6 70W G12 7300lm ECG Product description Housing: cast aluminum, designed as heat sink. Mounting ring: cast aluminum, white (RAL9002) powder-coated. 4-point support and screw tightening for fixing to mounting plate. Mounting plate for preinstallation with junction box for through-wiring. Electronic control gear 120V, 60Hz on top of junction box. Snap-in plug for connection between junction box and luminaire. Low brightness reflector: aluminum, specular anodized. Cut-off angle 40° from horizontal. Diffuser as lamp cover: glass, frosted. Type Non IC luminaire. Insulation materials must be kept away from the luminaire by a minimum of 3". Thermally protected luminaire. Luminaires protected with disconnecting switch. Suitable for damp location. Removal of reflector allows access to junction box from below. Max. ceiling thickness 3/4". Weight 9.70lbs / 4.40kg ERCO Lighting Inc. 160 Raritan Center Parkway Suite 10 Edison, NJ 08837 USA Tel.: +1 732 225 8856 Fax: +1 732 225 8857 info.us@erco.com 60° 30° 60° 5000 cd 30° T6 70W G12 7300lm Efficiency: 57% Technical Region: 120V/60Hz We reserve the right to make technical and design changes. Edition: 03.11.2009 Current version under www.erco.com/22680.023 1/4 LC Downlight E Planning Data 22680.023 Connected load Connected load per 10fc Number of luminaires per 10fc T6 70W G12 7300lm P: 80 W P*: 0.2 W/ft2 n*: 2.9 1/1000ft2 22680.023 Number of luminaires per 1000ft2 for 22680.023 Module (ft) Illuminance (fc) T6 70W G12 7300lm 4x6 6x6 6x8 146 97 73 Correction table Ceiling 0.70 0.70 Wall 0.70 0.50 Floor 0.50 0.20 k k k k k 0.6 1.0 1.5 2.5 3.0 84 103 117 128 132 67 82 93 100 103 T6 70W G12 7300lm 10fc 20fc 30fc 3 6 9 50fc 15 8x8 55 0.70 0.20 0.20 0.50 0.20 0.10 0 0 0 59 75 87 96 99 59 73 84 91 93 56 70 81 87 90 LC Downlight 22680.023 2/4 Metal Halide Lamp Ballast Catalog Number 72C5281 For 70W M139 60 Hz HX-HPF Status: Active DIMENSIONS AND DATA 10.50" 2.63" CASE "F-1" 11.13" 3.19" 11.75" INPUT VOLTS 120 277 CIRCUIT TYPE HX-HPF 90% POWER FACTOR (min) REGULATION Line Volts ±5% Lamp Watts ±10% LINE CURRENT (Amps) Operating............................................................... 0.85 0.37 Open Circuit........................................................... 1.70 0.75 Starting................................................................... 1.00 0.45 UL TEMPERATURE RATINGS A (105°C) Insulation Class 1029 Coil Temperature Code A A -20°F or -30°C MIN. AMBIENT STARTING TEMP. 240 NOM. OPEN CIRCUIT VOLTAGE INPUT VOLTAGE AT LAMP DROPOUT................................. 100 225 INPUT WATTS 94 RECOMMENDED FUSE (Amps)............................................. 5 2 CORE and COIL Dimension (A) Dimension (B) Weight (lbs.) 8.5 Lead Lengths 12" CAPACITOR REQUIREMENT Microfarads Volts (min.) Fault Current Withstand (amps) 60 Hz TEST PROCEDURES (Refer to Philips Lighting Electronics N.A. TEST Procedure for HID Ballasts - Form 127 High Potential Test (Volts) 1 minute 1500 2 seconds 2500 Open Circuit Voltage Test (Volts) 215-265 Short-Circuit Current Test (Amps) Secondary Current 1.05-1.35 Input Current.......................................................... 0.60- 0.251.10 0.50 - - Capacitor: Wiring Diagram: All Lead Lengths 12" 277 V 120V COMMON YELLOW/BLUE BLACK BALLAST The capacitor is included as part of the potted assembly. WHITE RED LAMP GROUND CASE F-Can Wiring Diagram Typical Ordering Information (please call Philips Lighting Electronics N.A. for suffix availability) Order Suffix Description Ignitor: IN CAN The ignitor is included as part of the potted assembly. Ballast to Lamp Distance (BTL) = 5 feet Temp Rating: 90°C Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representitive of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Revised: 10/11/99 - Large scale floodlights with wide beam light distribution Housing: Two piece die-cast aluminum consisting of a reflector housing with integral yoke mounting flanges and a separate cylindrical ballast housing with cooling fins. Ballast housing is secured to reflector housing by two stainless steel latches which allow easy access to the ballast. All aluminum used in the construction is marine grade and copper free. Type: BEGA Product: Project: Voltage: Color: Options: Modified: Lamp enclosure: Two piece die-cast aluminum consisting of an outer lens frame and a inner accessory holder. The lens is secured between the two die-castings and is hinged to provide easy lamp maintenance. Two captive, stainless steel fasteners seal the lens/frame assembly to reflector housing. Tempered glass lens, 3/16" thick. One piece molded, U-channel, high temperature silicone rubber gasket. Mounting Yoke: 3/16" thick stainless steel allows for full vertical adjustment with die-cast aluminum aiming angle indicators and two (2) heavy duty stainless steel locking bolts. Yoke is provided with mounting holes for various BEGA mounting accessories. Electrical: Lampholders: Medium base porcelain with nickel plated copper screw shell, pulse rated 4 KV. Ballasts are internal, magnetic HPF, available in 120 V, 208 V, 240 V, or 277 V - specify. Provided with at least 8' of 18-3 SJTOW black 300 V cord. Finish: These luminaires are available in four standard BEGA colors: Black (BLK); White (WHT); Bronze (BRZ); Silver (SLV). To specify, add appropriate suffix to catalog number. Custom colors supplied on special order. UL listed, suitable for wet locations. Protection class: IP 67. Mounting options: 435 553 554 550 551 555 762 763 764 766 761 765 Mounting bracket for pole top Ø 3" Pole mount canopy for 5" O.D. pole Wall mount canopy Pole mount arm for for 5" O.D. pole Wall mount arm Pole mount hub for pole top Ø 3" Pole top for 2 floodlights Pole top for 3 floodlights Pole top for 4 floodlights Pole top for 6 floodlights Cross beam for 3 floodlights Cross beam for 6 floodlights A C B Floodlights · wide beam G β Lumen A 7873 MH 1 150 W ED-17 MH * 60° 12 500 13 3⁄4 *Coated lamp required for proper optical performance. Lamp 180° glare shield 360° glare shield B C 16 3⁄8 141⁄8 Louver B Y 659 507 133 108 109 110 Color effect filters β = Beam angle BEGA- US 1000 BEGA Way, Carpinteria, CA 93013 ( 805 ) 684-0533 FAX ( 805 ) 566-9474 www. bega-us . com ©copyright BEGA-US 2008 Updated 4/09 Metal Halide Lamp Ballast Catalog Number 72C5581 For 175/150W M57/M107 60 Hz CWA Status: Active DIMENSIONS AND DATA 10.50" 2.63" CASE "F-1" 3.19" 11.13" 11.75" INPUT VOLTS 120 277 CIRCUIT TYPE CWA 90% POWER FACTOR (min) REGULATION Line Volts ±10% Lamp Watts ±10% LINE CURRENT (Amps) Operating............................................................... 1.75 0.75 Open Circuit........................................................... 2.15 0.92 Starting................................................................... 0.85 0.36 UL TEMPERATURE RATINGS A (105°C) Insulation Class 1029 Coil Temperature Code A A -20°F or -30°C MIN. AMBIENT STARTING TEMP. 300 NOM. OPEN CIRCUIT VOLTAGE INPUT VOLTAGE AT LAMP DROPOUT................................. 60 138 INPUT WATTS 205 RECOMMENDED FUSE (Amps)............................................. 5 3 CORE and COIL Dimension (A) Dimension (B) Weight (lbs.) 14 Lead Lengths 12" CAPACITOR REQUIREMENT Microfarads Volts (min.) Fault Current Withstand (amps) 60 Hz TEST PROCEDURES (Refer to Philips Lighting Electronics N.A. TEST Procedure for HID Ballasts - Form 127 High Potential Test (Volts) 1 minute 1600 2 seconds 2000 Open Circuit Voltage Test (Volts) 270-330 Short-Circuit Current Test (Amps) Secondary Current 1.55-1.90 Input Current.......................................................... 0.56- 0.240.85 0.36 - - Capacitor: Wiring Diagram: All Lead Lengths 12" 277 V 120V COMMON YELLOW/BLUE BLACK BALLAST The capacitor is included as part of the potted assembly. WHITE RED LAMP GROUND CASE F-Can Wiring Diagram Typical Ordering Information (please call Philips Lighting Electronics N.A. for suffix availability) Order Suffix Description Ignitor: NA This ballast does not require the use of an ignitor. Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representitive of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Revised: 09/07/01 - Small scale floodlights Type: Z BEGA Product: Project: Voltage: Color: Options: Modified: Housing: One piece die-cast aluminum with integral cooling fins. Enclosure: Lamp enclosure/optical system consists of a die-cast aluminum clamping ring, clear tempered glass. Fully gasketed for weather tight operation in any mounting orientation using a molded silicone rubber gasket. Mounting: Provided with two piece die-cast aluminum canopy supplied with a stainless steel outrigger swivel arm. 7723 mounts directly to the wall over a 4" octagonal box. Electrical: H.I.D. lampholders are G12, bi-pin porcelain with nickel plated contacts. Ballast is integral and electronic, universal voltage 120V through 277V. 7723 ballast is located in the mounting canopy. Finish: These luminaires are available in four standard BEGA colors: Black (BLK); White (WHT); Bronze (BRZ); Silver (SLV). To specify, add appropriate suffix to catalog number. Custom colors supplied on special order. UL listed, suitable for wet locations. Protection class: IP 65. B C D A G Floodlights with outrigger arm and mounting canopy β Lamp 7723 MH 1 70 W T4 G8.5 MH 180° glare shield Lumen 37° 6400 Color effect filters A B c B Y D 4 1⁄ 4 27 1⁄ 4 5 7⁄ 8 4 1⁄ 4 X 9 1⁄ 2 Exchangeable lenses 264 125 126 127 Wide beam 312 313 Flat beam β = Beam angle BEGA- US 1000 BEGA Way, Carpinteria, CA 93013 ( 805 ) 684-0533 FAX ( 805 ) 566-9474 www. bega-us . com ©copyright BEGA-US 2010 Updated 2/10 Metal Halide Lamp Ballast Catalog Number 72C5282 For 70W M98 60 Hz HX-HPF Status: Active DIMENSIONS AND DATA 10.50" 2.63" CASE "F-1" 11.13" 3.19" 11.75" INPUT VOLTS 120 277 CIRCUIT TYPE HX-HPF 90% POWER FACTOR (min) REGULATION Line Volts ±5% Lamp Watts ±10% LINE CURRENT (Amps) Operating............................................................... 0.85 0.37 Open Circuit........................................................... 1.60 0.75 Starting................................................................... 1.25 0.55 UL TEMPERATURE RATINGS A (105°C) Insulation Class 1029 Coil Temperature Code -20°F or -30°C MIN. AMBIENT STARTING TEMP. 255 NOM. OPEN CIRCUIT VOLTAGE INPUT VOLTAGE AT LAMP DROPOUT................................. 84 194 INPUT WATTS 94 RECOMMENDED FUSE (Amps)............................................. 4 2 CORE and COIL Dimension (A) Dimension (B) Weight (lbs.) 8.5 Lead Lengths 12" CAPACITOR REQUIREMENT Microfarads Volts (min.) Fault Current Withstand (amps) 60 Hz TEST PROCEDURES (Refer to Philips Lighting Electronics N.A. TEST Procedure for HID Ballasts - Form 127 High Potential Test (Volts) 1 minute 1600 2 seconds 2000 Open Circuit Voltage Test (Volts) 230-280 Short-Circuit Current Test (Amps) Secondary Current 0.95-1.20 Input Current.......................................................... 0.55- 0.250.85 0.40 - - Capacitor: Wiring Diagram: All Lead Lengths 12" 277 V 120V COMMON YELLOW/BLUE BLACK BALLAST The capacitor is included as part of the potted assembly. WHITE RED LAMP GROUND CASE F-Can Wiring Diagram Typical Ordering Information (please call Philips Lighting Electronics N.A. for suffix availability) Order Suffix Description Ignitor: IN CAN The ignitor is included as part of the potted assembly. Ballast to Lamp Distance (BTL) = 10 feet Temp Rating: 90°C Data is based upon tests performed by Philips Lighting Electronics N.A. in a controlled environment and is representitive of relative performance. Actual performance can vary depending on operating conditions. Specifications are subject to change without notice. PHILIPS LIGHTING ELECTRONICS N.A. 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018 Tel: 800-322-2086 · Fax: 888-423-1882 · www.philips.com/advance Customer Support/Technical Service: 800-372-3331 · OEM Support: 866-915-5886 Revised: 02/09/10 - WeeBee Opal LED LED straight Design: Paul Sayers Type: Project: Catalog Number: (3) M4 X 12mm STAINLESS STEEL SOCKET CAP SCREWS louis poulsen 316 MARINE GRADE STAINLESS STEEL TOP PLATE STRAIGHT EDGE, .240" THICK HEAT TEMPERED IMPACT RESISTANT OPAL GLASS, .197" THICK Ø2.8" WATERTIGHT SILICONE GASKET GROUND LEVEL Ø3.0" SLEEVE (18) .16W LIGHT EMITTING DIODES (LED) AVAILABLE IN BLUE, AMBER OR WHITE LIGHT EMITTING DIODE (LED) PRINTED CIRCUIT BOARD WITH 120V OR 277V TRANSFORMER (SPECIFY) 3.9" 9.0" HIGH PRESSURE DIE CAST ALUMINUM BODY ANODIZED AND POWDER COATED WITH PAINT CONTAINING PTFE TO PROVIDE MAXIMUM CORROSION PROTECTION 316 MARINE GRADE STAINLESS STEEL SLEEVE WITH WELDED BRACKET FOR LUMINAIRE ATTACHMENT 1/2" NPT NICKEL PLATED BRASS FEMALE CONDUIT CONNECTOR FASTENED INTO CAST BODY BY M16 THREAD 1/2" NPT LIQUID TIGHT STRAIGHT-THRU CONNECTOR (BY OTHERS) COMPARTMENT TO ALLOW FOR AMPLE LENGTH OF CABLE (BY OTHERS) FOR REMOVAL OF INGROUND LUMINAIRE FROM STAINLESS STEEL SLEEVE DURING MAINTENANCE FLEXIBLE CABLE (BY OTHERS) REMOVABLE SLEEVE BOTTOM WITH A Ø.875" HOLE NOTES: 1. FINISH: STAINLESS STEEL 2. VOLTAGE: 120V OR 277V (SPECIFY) 3. INSTALLATION IS SUBJECT TO LOCAL CODES AND JURISDICTION 4. A 1/2" NPT LIQUID TIGHT STRAIGHT-THRU CONNECTOR (BY OTHERS) MUST BE USED TOGETHER WITH THE CONNECTOR SUPPLIED, ENSURING A WATERTIGHT CONNECTION AND PREVENTING MOISTURE INGRESS INTO THE LUMINAIRE HOUSING 5. PROPER DRAINAGE MUST BE PROVIDED LIQUID TIGHT STRAIGHT-THRU CONNECTOR, FLEXIBLE CONDUIT, RIGID PVC CONDUIT AND A 1/2" NPT CONDUIT CONNECTOR (BY OTHERS) 11-06-06 Louis Poulsen Lighting, Inc., 3260 Meridian Parkway, Fort Lauderdale, FL 33331 Telephone: (954) 349-2525 Fax: (954) 349-2550 www.louispoulsen.com COMMERCIAL OCCUPANCY SENSORS & CONTROLS DT-355 Dual Technology Line Voltage Ceiling Sensor Operates at 120, 230, 277 or 347 VAC, 50/60 Hz Architecturally appealing low profile appearance Terminal wiring for quick and easy installation Auto set automatically selects optimal settings for each space Walk-through mode increases savings potential Ultrasonic diffusers give more comprehensive coverage PROJECT LOCATION/TYPE Product Overview Description Auto Set WattStopper’s low profile DT-355 dual technology occupancy sensor combines the benefits of passive infrared (PIR) and ultrasonic technologies. The sensor mounts on the ceiling with a flat, unobtrusive appearance and provides 360 degrees of coverage. The DT-355 requires no adjustment at installation. Auto set continuously monitors the controlled space to identify usage patterns. Using this information, it automatically adjusts the time delay and sensitivity settings for optimal performance and energy efficiency. The sensor assigns short delays (as low as 5 minutes) for times when the space is usually vacant, and longer delays (up to 30 minutes) for busier times. Operation Features The DT-355 is line voltage and operates at 120, 230, 277 or 347 VAC. The sensor turns lighting on when both PIR and ultrasonic technologies detect occupancy. PIR technology senses the difference between infrared energy from a human body in motion and the background space. Ultrasonic technology uses high frequency (40KHz) ultrasound to sense motion within the space. Once lighting is on, detection by either technology holds lighting on. When no occupancy is detected for the length of the time delay, lighting turns off. The DT-355 can also be set so that only one technology is needed to trigger or both technologies are needed to hold lighting on. WattStopper’s patented dual technology has the flexibility to work in a variety of applications, where one technology alone could encounter false triggers. Ideal applications include classrooms, open office spaces, large offices, and computer rooms. In addition, because the DT-355 can be mounted onto a variety of junction boxes, the sensor has the flexibility to be used in a wide range of spaces. The sensors eliminate the need for a power pack by using line voltage wiring. • Advanced control logic based on RISC microcontroller provides: • Ultrasonic diffusion technology spreads coverage to a wider area (patent pending) • Detection Signature Processing eliminates false triggers and provides immunity to RFI and EMI • Walk-through mode turns lights off 3 minutes after the area is initially occupied – ideal for brief visits such as mail delivery • Built-in light level sensor featuring simple, one-step setup www.wattstopper.com 800.879.8585 Application • DIP switch simplifies sensor adjustments • LEDs indicate occupancy detection • Uses existing line voltage wiring and doesn’t require a power pack • Six occupancy logic options give users the ability to customize control to meet application needs • Qualifies for ARRA-funded public works projects Wiring & Mounting • 120/230/277/347 VAC, 50/60 Hz • Ultrasonic frequency of 40kHz • Time delays: Auto set, fixed (5, 10, 15, 20, or 30 minutes), walk-through, test-mode • Sensitivity adjustment: Auto set or reduced sensitivity (for PIR sensitivity); ultrasonic sensitivity is variable with trimpot • Built-in light level sensor – works from 10 to 300 footcandles (107.6 to 3,229.2 lux) DT-355 Wiring Diagram • Multi-level, 360° Fresnel lens for superior occupancy detection • Mounting options: 4 square junction box with double gang mudring; 4 inch octagonal junction box • Dimensions: 4.50” diameter x 1.45” deep (114.3mm x 25.9mm) • UL and cUL listed • Five year warranty Ceiling Mounting 4" Square, 2.25" Deep* Junction Box with Double Gang Mudring attached Neutral Load Drop Ceiling Load Hot CA-1 Adapter Ground Neutral Rear Housing Sensor Flange (Optional) Screws Front Cover Product Controls DIP switches Double gang mudring mounting holes E EC Ultrasonic transducer cones 8 7 6 5 4 3 ON 2 1 PIR Activity LED (Red) Switch# Logic 1 2 3 Standard Option 1 Option 2 Option 3 Option 4 Option 5 Option 6 Option 7 Trigger Standard Option 1 Option 2 Option 3 Option 4 Option 5 Option 6 Option 7 Both Either Either(5) Either Either Either(5) PIR Either Either(5) Both Both Both(5) PIR PIR PIR(5) Ultra Ultra Ultra(5) Man. Either Either(30) Man. Both Both(30) Time Delay 4 5 6 Ultrasonic activity LED (Green) Coverage = ON = OFF Initial Occupancy Maintain Occupancy Re-trigger (seconds duration) Light level pushbutton Keyhole slots (for mounting to 4" octagonal box) Occupancy Logic Ultrasonic sensitivity trimpot DIP Switch Settings Occupancy Controls & Settings PIR lens Coverage Pattern 5 sec/SmartSet 5 minutes 10 min. 10 minutes 15 min. 15 minutes 20 minutes 30 min. LEDs 7 Disabled Enabled PIR Sensitivity 8 Minimum Max./SmartSet = walk-through mode The technology control (occupancy logic) options are adjustable by user. The standard setting (recommended for most applications) is both technologies to trigger on, either to hold on. 44 ft (13.4m) Coverage shown is maximum and represents half-step walking motion. Under ideal conditions, coverage for half-step walking motion can reach up to 1000 ft2 (92.9 m2). 40 ft x 40 ft (12.2m x 12.2m) Ordering Information Catalog No. DT-355 DT-355-U CA-1 Voltage Load Rating Coverage 120 VAC, 50/60 Hz 230/277 VAC, 50/60 Hz 347 VAC, 50/60 Hz 0-800W Ballast/Tungsten 0-1200W Ballast 0-1500W Ballast up to 1000 ft2, (92.9 m2) Cosmetic adapter for ceiling installations with 4” square j-box or Wiremold #V5748-2 box Sensors are white. Pub. No. 15806 rev. 10/2009 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5 COMMERCIAL OCCUPANCY SENSORS & CONTROLS Specifications COMMERCIAL OCCUPANCY SENSORS & CONTROLS PW-100 Passive Infrared Wall Switch Sensor Selectable auto set, walk-through, test and presentation modes for increased energy savings and convenience High sensitivity and dense coverage for exceptional performance Color-matched lens and low profile for appealing design Part of a comprehensive line of PIR, Ultrasonic and Dual Technology wall switch sensors PROJECT LOCATION/TYPE Product Overview Description Auto Set The PW-100 passive infrared (PIR) wall switch sensor turns lights ON and OFF based on occupancy. It is characterized by high sensitivity to small and large movements, appealing aesthetics, and a variety of features. With auto set enabled, the PW-100 continuously monitors the controlled space to identify usage patterns and automatically adjust the time delay for optimal energy efficiency. The sensor assigns short delays (as low as seven minutes) for times when the space is usually vacant, and longer delays (up to 30 minutes) for busier times. Auto set is also able to differentiate electrical noise from human motion for better performance. Operation The PW-100 replaces existing wall switches and fits in a single gang junction box. It uses advanced PIR technology to detect occupancy and turn lighting ON. Once the space is vacated and the time delay elapses, lights automatically turn OFF. DIP switch settings allow for a variety of control options such as Auto-ON or Manual-ON operation, walk-through, and test modes. Features • Detection Signature Processing eliminates false triggers and provides immunity to RFI and EMI • Zero-crossing for long relay life The PW-100 sensor is well suited for small, enclosed spaces with clear line of sight of the occupant. Common applications include small office, small conference room and lunch/break rooms. • In automatic mode, sensor returns automatically to Auto-ON after lights are turned off manually; ideal for presentations • Vandal resistant lens combines precise coverage with durability • LED indicates occupancy detection • Choice of Auto-ON or Manual-ON operation • Override mode allows sensor to operate as a service switch in the unlikely event of a failure • Selectable walk-through mode turns lights off three minutes after the room is initially occupied if no motion is detected after the first 30 seconds • Test mode allows quick and easy adjustments • Selectable audible and/or visual alerts for impending shutoff www.wattstopper.com 800.879.8585 Applications • Optional light level sensing with simple setup • 2-wire and 3-wire models available for applications with or without neutral wire • Sensor coverage tested to NEMA Guide Publication WD 7-2000 • Qualifies for ARRA-funded public works projects Specifications • Coverage: Major motion 35’ x 30’ Minor motion 20’ x 15’ • Sensitivity adjustment: PIR (high/low) • Dimensions: 2.73” x 1.76” x 1.83” (69.3mm x 44.7mm x 46.5mm) L x W x D • UL and cUL listed • Five year warranty Product Controls DIP Switch Settings ON/OFF Button Time Delay ON TRIG GE R ALE R TS R LY 1 M AN R LY 2 MA N DEL AY WALK PIR 50 % Auto/Test 5 minutes 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes override DIP Switches Walk-Through 1 2 3 4 5 6 7 8 9 Audible Alerts Walk-Through PIR Sensitivity PIR Sensitivity 5 High Low, 50% 4 Disabled Enabled Detection LED Relay 1 Mode Visible Not Used Alerts Time Delay 1 2 3 Visible Alert Bypass occupancy & light level functions. Loads are manually controlled with PW-200 buttons. Disabled Enabled =ON Audible Alert Disabled Enabled Relay 1 Mode Auto On Manual On 7 8 6 =OFF =Factory Setting PIR Lens Coverage & Wiring Coverage Pattern Wiring Diagrams Neutral Major motion Load Neutral Load Minor motion PIR Coverage Line 35’ (10.6m) Black Red Neutral White Line Ground Green/Yellow Red Black Ground Green Ground Green 20’ (6.1m) Wiring for PW-100 with no neutral wire run to the switch box. Wiring for PW-101 with a neutral connection in the switch box. 7.5’ (2.2m) 15’ (4.5m) 4’ (1.2m) For best performance, WattStopper recommends using this sensor in spaces no larger than 15’ x 12’. 0 Ordering Information Pub. No. 23303 rev. 10/2009 Catalog No. PW-100-W PW-100-W-U PW-100-W-FTA 20’ (6.1m) Color White 35’ (10.6m) Voltage Load Rating 120/230/277 VAC; 50/60 Hz @ 120 VAC, 0-800 W ballast or tungsten,1/6 hp 2-wire sensor; no neutral @ 230/277 VAC, 0-1200 W ballast connection PW-100-LA Lt. Almond PW-100-I PW-100-I-U PW-100-I-FTA Ivory PW-100-G Grey PW-100-B Black PW-101-W White 120/230/277 VAC; 50/60 Hz @ 120 VAC, 0-800 W ballast or tungsten,1/6 hp PW-101-LA Lt. Almond 3-wire sensor; requires @ 230/277 VAC, 0-1200 W ballast PW-101-I Ivory neutral connection PW-101-G Grey PW-101-B Black PW-100-347-W White PW-100-347-LA Lt. Almond PW-100-347-I Ivory PW-100-347-G Grey PW-100-347-B Black 347 VAC; 50/60 Hz 0-1500 W ballast One ASP-211 single-gang cover plate included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate with switch option (specify color). www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5 COMMERCIAL OCCUPANCY SENSORS & CONTROLS Controls & Settings • PW-100, PW-101: 120/230/277 VAC; 50/60 Hz @ 120 VAC, 0-800 W ballast or tungsten,1/6 hp @ 230/277 VAC, 0-1200 W ballast • PW-100-347: 347 VAC; 50/60Hz; 0-1500 W ballast • Time delays: Auto set, fixed (5, 10, 15, 20, 25 or 30 minutes), walk-through, test-mode WIRELESS LIGHTING CONTROLS MSC-100 Astronomic Time Clock Multiple control channels Provides time-scheduled control Advanced holiday scheduling capability Connects to Room and House Scene Interfaces LCD display screen Automatic daylight savings time adjustment PROJECT LOCATION/TYPE Product Overview Features www.wattstopper.com 800.879.8585 Description Programming WattStopper’s MSC-100 Astronomic Time Clock is a five-channel clock used for fully automating a Wireless Miro lighting control system. It offers simple programming, yet advanced control features. The Time Clock is used with at least one Wireless Miro Scene Interfaces. Programming the MSC-100 is easy. Users simply complete fill-in-the-blank prompts on the device keypad and can follow along on the LCD screen. Each clock channel can be programmed independently. All programming is securely stored in non-volatile memory. Operation Applications The MSC-100 provides ON/OFF control signals based on time of day, day of week, holiday, and calculated sunrise/sunset (astronomic) time. Control signals are transmitted via hardwire connection to relay channels, giving the clock the ability to work in a range of applications from simple to complex. Clock schedules are programmed events that command channels on or off. Each schedule is assigned a number, type, time of day, channel, day, and may include other information for specific clock event operation. Schedules can be assigned to operate any combination of days or holiday types. When used in conjunction with Wireless Miro lighting controls, one MSC-100 will support connection to up to two Scene Interfaces, depending on the number of scenes required. Unused channels can be used to control third-party devices such as fountains or sprinklers. • Single date, perpetual date, perpetual day of week and perpetual Easter holidays • Duration time scheduling from 1 second to 18 hours • 32 holidays, each up to 120 days with three holiday schedule types • Continually self-adjusting astronomic control based on sunrise and sunset times • Temporary schedules that execute once then self-delete • Astronomic offset +/- 120 minutes • Repeating schedule 5 minutes to 10 hours • Selectable 12- or 24-hour format • 120 schedules assignable to one or more weekday or holiday • Adjustable channel stagger from 1-60 seconds • Manual ON/OFF override from keypad System Layout & Wiring • Power-up sequence, executes missed schedules following power outage • Dimensions: 3.6” x 6.7” x 1.3” (91.4mm x 177.8mm x 33mm) L x W x D • FCC compliant; CE certified • One year warranty • Input voltage: 24 VAC or 24 VDC • Five normally open isolated relays rated 1 amp 24 VAC/VDC, assigned to channels 1-5 • Battery backed clock operation for up to 8 years • Non-volatile program memory storage MSC-100 Controls & Wiring miro MRRC3 Room Scene Interface 88T9 Appliance Control All wiring Class 2 05810r1 50 ma max. UL US LISTED Ground Input 1 Input 2 Input 3 C 24VDC Out. FCC ID: Q4B-TDREP 12-24VDC 200 mA maximum MSC-100 In 4 In 3 In 2 Prn Prn Prn NOT USED UP/ ON Power Service Comm Error Prn Tx Rx Net A DOWN/ OFF MENU Net B PREV. Plug-In Port NEXT ENTER Com 5 Com 4 Com 3 Com 2 Com 1 Cnl 5 Cnl 4 Cnl 3 Cnl 2 Cnl 1 Pwr Pwr + Expansion Port 3/#20 The MSC-100 Time Clock interfaces to the Wireless Miro RF network through a Miro Room or House Scene Interface. The Scene Interface supplies 24 VDC to power the Time Clock. Wiring shown is typical for one channel. Ordering Information Catalog No. MSC-100 Product Description 5-channel astronomic time clock Works in conjunction with: Catalog No. Description MRHC3 House Scene Interface MRRC3 Room Scene Interface Pub. No. 22402 rev. 11/2009 www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5 WIRELESS LIGHTING CONTROLS Specifications Photosensor for LightSaver LCD-203 and LCO-203 Controllers Mounts vertically or horizontally Footcandle range from 3 - 6000 Architecturally attractive design PROJECT LOCATION/TYPE Product Overview Description Photosensor Placement WattStopper’s LightSaver LS-290C open loop Photosensor provides the daylight data necessary for operation of the LCD-203 and LCO-203 daylighting control systems. 45˚ DAYL I GHTI N G SE N S O RS & C O NT RO LS LightSaver® LS-290C Photosensor Operation LS-290C Peak sensitivity Utilizing a photodiode element, the LS-290C continuously measures ambient light levels. The Photosensor is positioned to ‘see’ incoming daylight from either a window or skylight without seeing electrical light. Users select the applicable footcandle range by a jumper beneath the front cover. Minimum Distance = 1/3 D2 Maximum Distance = 1/2 D2 D2 Specifications • Three jumper-selectable footcandle ranges: 3-300 fc, 30-3000 fc, 60-6000 fc • Low voltage, Class 2 device • Protective hard plastic cover • 3 conductor 22 AWG twisted cable equal to Belden 8443 • Maximum wire length is 250 feet (76.2m) • Dimensions: 2” diameter x 1.2” deep (50.8mm diameter x 30.5mm deep) • UL and CUL listed • Five year warranty Ordering Information 2" Catalog No. LS-290C Description Footcandle range Open Loop Photosensor 3 - 6000 (32 - 64,000 lux) Pub. No. 9607 rev. 09/2009 Cable to LCD 3 conductor 22 AWG equal to Belden 8443 Ceiling tile or drywall 45˚ 1.2" 60˚ field of view LS-290C 30˚ Qualifies for use on ARRA-funded public works projects. www.wattstopper.com 800.879.8585 Installation and Wiring 30˚ Peak sensitivity Five individually programmable adjustments for each control channel Automatic ON/OFF daylighting control module LCD display of light level readings Multi-level switching DAYL I GHTI N G SE N S O RS & C O NT RO LS LightSaver® LCO-203 ON/OFF Switching Open loop control Push-button programming and automated setup PROJECT LOCATION/TYPE Product Overview Description Multiple Channel Control WattStopper’s LightSaver LCO-203 provides automatic ON/OFF switching control for fluorescent and HID fixtures. It is an open loop controller providing up to three zones of control from a single photocell. Multi-channel control enables gradual, multi-level switching of electric lighting as the daylight contribution increases. The LCO can be used to either switch off individual rows of lamps in a luminaire or entire luminaires. This gradual reduction is likely to provide more balanced lighting while being less distracting to occupants. Operation Features The LCO controller is part of a system that includes the LS-290C photocell and the BT-203 Power Pack. Each of the LCO controller’s three channels connects directly with its own dedicated relay in the power pack. The photocell measures daylight and transmits these data to the LCO controller. When daylight is adequate, the LCO controller switches lighting off. When daylight diminishes below the desired setpoint, the LCO controller switches lighting back on. The ON and OFF delays for each channel are individually adjustable. The LCO controller integrates with occupancy sensors as well as an optional wall switch for manual overrides. Applications • Simplified setup and calibration • Automatic internal calculation of daylight contribution for each channel for simplified setup • Optional wall switch (LS-3C) provides ON/OFF control so users can adjust lighting www.wattstopper.com 800.879.8585 Spaces such as warehouses, storage areas, atriums, lobbies, and open office areas will benefit from use of the LCO controller. • DIN rail mounting • Five individually adjustable parameters for each channel: ON delay, OFF delay, deadband, setpoint, load shed setpoint • Suitable for mounting in low voltage section in control panel • Menu-driven, push-button programming without special tools • Qualifies for use on ARRA-funded public works projects • California Title 24-2008 compliant F21 System Layout & Wiring • • • • • • • • 24VDC supply voltage provided by BT-203 • Dimensions: 3.5” x 2.81” x 2.5” (89mm x 71mm x 64mm) L x W x D • UL and CUL listed • Five year warranty Class 2 low voltage device Photocell range from 3 - 6,000 footcandles Setpoint range from 5-60 fc Programmable deadband from 10%-80% Adjustable ON delay from 5-60 seconds Adjustable OFF delay from 3-60 minutes Load shed setpoint from 5-60 fc System Layout Lamps (up to 3 zones) Zone 1 Zone 2 Zone 3 Auto LightSaver¨ LCO-203 On / Off LightSaver¨ BT-203 Power Pack BT-203 Power Pack 1.800.879.8585 1.800.879.8585 ¥ Timer ¥ Energy management system Control Interlock CON TROL S LCO-203 Wiring and Settings LS-3C Switch Brown to B7 Red to B8 Orange to B6 Blue to B5 White to B4 to A11 to A10 Black to B3 1 2 3 to A12 Green to B2 LS-290C Photocell Display 1 2 3 4 5 6 7 8 9 10 11 12 A 1 2 3 4 5 6 7 8 9 10 11 B LightSaver¨ BT-203 Power Pack A Navigation and 12 B selection buttons LightSaver¨ LCO-203 DIN Rail BT-203 Power Pack LCO-203 Controller 1.800.879.8585 1.800.879.8585 Not Used Not Used D Line Voltage Ordering Information Catalog No. 1 2 D D terminals: 3 4 5 6 0-10VDC dimming ballast control RJ12: quick connect to BT-203 Description Voltage Channels LCO-203 ON/OFF switching control module 24 VDC three LS-290C Photosensor BT-203 Power Pack ON/OFF control system options: Product group Switch Enclosure Pub. No. 9207 rev. 09/2009 Catalog No. LS-3C LS-E8 LS-E12 & Occupancy Sensor LS-290C Photocell SE NS ORS LS-3C Switch LCO Control Module D AY LIG H T ING Specifications Description Wall Switch Screw-cover Enclosure 8” x 8” x 4” (203.2mm x 203.2mm x 101.6mm) Screw-cover Enclosure 12” x 12” x 4” (304.8mm x 308.8mm x 101.6mm) www.wattstopper.com | 8 0 0 . 8 7 9 . 8 5 8 5 Product Data Sheet EE15T3HBCU Energy Efficient Transformer , 3-Phase, 15kVA, 480VAC Delta, 208Y/120VAC List Price $7,956.00 USD Availability Stock Item: This item is normally stocked in our distribution facility. Technical Characteristics Full Capacity Taps (6) 2.5% 2+4- Temperature Rise 80 Degrees C Weathershield WS363 (purchase seperately) Winding Material Copper Enclosure Code 17D Enclosure Material Painted Steel Depth 16.00 Inches Height 27.00 Inches Width 20.00 Inches Enclosure Rating NEMA 2 Enclosure Type Drip Proof (Indoor) Insulation Temperature 220 Degrees C Marketing Trade Name Watchdog Mounting Brackets Wall: WMB361362 - Ceiling: CMB363 Mounting Type Floor - Ceiling or Wall with mounting brackets Phase 3-Phase Primary 480VAC Delta Rating 15kVA Secondary 208Y/120VAC Shipping and Ordering Category 16283 - Discount Schedule PE2E GTIN 00785901864691 Package Quantity 1 Weight 258 lbs. Availability Code Stock Item: This item is normally stocked in our distribution facility. Returnability Y Country of Origin MX As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this document. Generated: 04/08/2010 21:05:06 © 2010 Schneider Electric. All rights reserved. 1 04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT Appendix C: Fuel Cell Information 164 PureCell™ 200 Power System PureCell™ 200 Commercial Fuel Cell Power System The Product UTC Fuel Cells, a unit of UTC Power, manufactures, sells and services the PureCell™ 200 power system (formerly known as the PC25). This clean, efficient and reliable fuel cell power plant produces 200 kilowatts of electricity and heat (900,000 Btus per hour) suitable for cogeneration applications. The complete packaged system includes the fuel cell power module and a dry air cooling module. Since 1991, the PureCell™ 200 fleet of commercial fuel cells has accumulated more than 6 million hours of operational experience. More than 250 PureCell™ 200 power systems have been sold in 19 countries and on five continents, with applications including a New York City police station, a major postal facility in Alaska and a science center in Japan. The systems also power schools, high-rise office buildings, and manufacturing sites. The standard PureCell™ 200 system is a grid-connected unit that operates in parallel with the electric utility grid. The unit can also be purchased to operate either in grid-connected or grid-independent mode switching between modes automatically or on command. In addition, the PureCell™ 200 power system can generate electricity from anaerobic digester gas produced by waste water treatment facilities. PureCell™ 200 power system installation Stockton College, New Jersey Power assurance is available in excess of 99.9999% in multiple unit configurations, and in excess of 99.99% per unit when connected to the electrical grid. Fuel cells represent one of the cleanest fossil-fueled generating technologies available today and are well below air emission standards in every state, including California. In Features Benefits addition, quiet operation allows the fuel • Reliable, assured power • Uninterrupted business operation cells to be located indoors or outdoors in • Ultra low emissions • Environmentally friendly close proximity to occupants and neighbors. • Qualify for financial incentives The remote monitoring option enables our • Low sound profile • Site flexibility service organization to monitor system • Remote monitoring option • System control and optimization performance round-the-clock, which means • High efficiency • Maximizes fuel utilization we can respond quickly if there's ever a • Lower operating costs need, minimizing downtime. System Specifications Power Voltage and Frequency* Cooling Module Noise 200 kW/235 kVA 480 volts, 3-phase, 4-wire 60 Hz Three fan air 60dBA @ 30 ft Emissions (ppmV, 15% O2 Dry) Fuel Type Fuel Flow NOx - <1 CO - <2 SOx, particulates, hydrocarbons - Negligible Natural Gas ADG 2050 scf/hr (avg.) 3500 scf/hr (avg.) Power Module Dimensions H: 121" (307 cm) W: 114" (290 cm) L: 212" (538 cm) Weight * Standard configuration 40,000 lb (18,144 kg) Cooling Module Dimensions H: 50" (127 cm) W: 49" (124 cm) L: 162" (411 cm) Weight 1,700 lb (771 kg) The manufacturer reserves the right to change or modify, without notice, the design or equipment specifications without incurring any obligation either with respect to equipment previously sold or in the process of construction. The manufacturer does not warranty the data on this document. Warrantied specifications are documented separately. IN PARTNERSHIP WITH: P030 R12/16/03 System Options High Grade Heat Recovery - 300,000 Btu/hr at rated power up to 250°F with remaining 450,000 Btu/hr up to 140°F. Remote Data Acquisition and Control - Key software application for monitoring, control, and maintenance activity. 400 Volt, 50 Hz or 480 Volt, 60 Hz Operation - Power plant can be provided to operate at 400 Volt, 50 Hz or 480 Volt, 60 Hz. Double Wall Heat Recovery Heat Exchanger - In domestic hot water applications, ensures that potable water source cannot mix with customer's water stream. Operating Fuel - Power plant can be provided to operate on natural gas or waste methane from anaerobic digester gas. Delete Cooling Module - Cooling tower or other heat sink may be used in lieu of dry cooling module. How It Works A fuel cell is an electrochemical device that combines hydrogen fuel and oxygen from the air to produce electricity, heat and water. Fuel cells operate without combustion, so they are virtually pollution free. Since the fuel is converted directly to electricity, a fuel cell can operate at much higher efficiencies than internal combustion engines, extracting more electricity from the same amount of fuel. The fuel cell itself has no moving parts - making it a quiet and reliable source of power. The fuel cell is composed of an anode (a negative electrode that repels electrons), an electrolyte in the center, and a cathode (a positive electrode that attracts electrons). As hydrogen flows into the fuel cell anode, platinum coating on the anode helps to separate the gas into protons (hydrogen ions) and electrons. The electrolyte in the center allows only the protons to pass through the electrolyte to the cathode side of the fuel cell. The electrons cannot pass through this electrolyte and therefore must flow through an external Heating System circuit in the form of electric current. This current can power an electric load. As oxygen flows into the fuel cell cathode, another platinum coating helps the oxygen, protons, and electrons combine to produce pure water and heat. Individual fuel cells can then be combined into a fuel cell "stack". Commercial Fuel Cell Power System 195 Governor's Highway . South Windsor, CT 06074 . Phone: (866) 900-POWER . Fax: 860-727-2319 . www.utcpower.com Copyright 2003, UTC Power. All Rights Reserved DFC300 Fuel Cell Module Key Features • • • • • High Efficiency Low Environmental Impact Fuel Flexibility High Reliability Quiet Operation Electrical Balance of Plant (EBOP) Advantages The DFC®300™ stationary fuel cell power plant from FuelCell Energy provides high-quality, Ultra-Clean electrical power with 47% efficiency in a small footprint. Designed for commercial and industrial applications, the system offers 24/7 operation, easy transport, quiet and reliable operation, and easy site planning and regulatory approval. Mechanical Balance of Plant (MBOP) 300 kW, 480 VAC, 333 kVA, 50 or 60 Hz Performance Power Output Power @ Plant Rating 300 kW Standard Output AC Voltage 480 V Standard Frequency 60 Hz Optional Output AC Voltages Optional Output Frequency Efficiency LHV Available Heat Exhaust Temperature Exhaust Flow Allowable Backpressure Heat Energy Available for Recovery (to 250°F) (to 120°F) 460, 440, 420, 400, 380 V 50 Hz 47 +/- 2 % Fuel Consumption Natural gas (at 930 Btu/ft3) Heat rate, LHV 39 scfm 7,260 Btu/kWh Water Consumption Average 0.9 gpm Peak during WTS backflush 10 gpm Water Discharge Average Peak during WTS backflush 0.45 gpm 10 gpm 700 +/- 50 °F 3,950 lb/h 5 iwc 480,000 Btu/h 808,000 Btu/h Pollutant Emissions NOx SOx PM10 Greenhouse Gas Emissions CO2 CO2 (with waste heat recovery) 0.01 lb/MWh 0.0001 lb/MWh 0.00002 lb/MWh 980 lb/MWh 520-680 lb/MWh DFC300 Specifications Dimensions Front View A Overall Width 20.0 ft B Height of Air Intake Filter 15.1 ft C Height of Exhaust Stack 14.5 ft (Required on units with no heat recovery) Side View D Overall Length 28.0 ft E Height of EBOP 11.8 ft F Height of Discharge Vent 14.5 ft 27,000 lb Noise Level Standard 72 dB(A) at 10 feet Electrical Balance of Plant 15,000 lb Optional 65 dB(A) at 10 feet Fuel Cell Module 35,000 lb Weights Mechanical Balance of Plant Experience & Capabilities With more than 35 years of experience, FuelCell Energy is recognized as a world leader in the development, manufacture, and commercialization of fuel cells for stationary electric power generation. The result of years of research and the investment of more than $530 million, our patented, carbonate Direct FuelCell products have generated more than 200 million kilowatt hours of electrical energy to date at more than 50 locations worldwide. This brochure provides a general overview of FuelCell Energy products and services. This brochure is provided for informational purposes only. Warranties for FuelCell Energy products and services are provided only by individual sales and service contracts, and not by this brochure. This brochure is not an offer to sell any FuelCell Energy products and services. Contact FuelCell Energy for detailed product information suitable for your specific application. FuelCell Energy reserves the right to modify our products, services, and related information at any time without prior notice. FuelCell Energy’s fleet of Direct FuelCell power plants are certified to or comply with a variety of commercial and industrial standards: ANSI/CSA America FC-1, UL 1741, CARB 2007, OSHA 29 CFR Part 1910, IEEE 1547, NFPA 70, NFPA 853, and California Rule 21. ©2008 FuelCell Energy, Inc. FuelCell Energy, Inc. 3 Great Pasture Road Danbury, CT 06813-1305 203 825-6000 www.fuelcellenergy.com 04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT Appendix D: Utility Rate Information 165 SUMMARY REPORTS OF ENERGY USE AND FUEL BILL ------------------------------------------NAME OF BUILDING : CT CENTER FOR SCIENCE EXPLORATION MODEL DESCRIPTION : AlNHR: Design w/o Heat Recovery REPORT-1: ANNUAL ENERGY USE STATISTICS ******************************************************************************* HEATING COOLING COOLING DOMESTIC MISC. VERTICAL TOTAL FUEL TYPE EQUIP. EQUIP. TWR/CNDSR FANS PUMPS WATER LIGHTING EQUIP. TRANS. FUEL USE -------------------- -------- --------- ------- -------- -------- --------- ------- -------- -------ELECTRICITY (KWH) 0 0 0 798332 53797 0 1284151 148450 9044 2293774 NATURAL GAS (CCF) 0 0 0 0 0 0 0 327 0 327 STEAM (MMBTU) 3510 0 0 0 0 954 0 0 0 4464 CHILLED WATER (TON-HR) 0 330348 0 0 0 0 0 0 0 330348 REPORT-2: MONTHLY AND ANNUAL FUEL BILLS ****************************************************************************** MONTH -----JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC -----TOTAL ELECTRIC KWH -------184292 187522 197129 194883 204775 202929 215246 212658 153673 182671 165586 192422 -------2293774 ELECTRIC ELECTRIC KW BILL ($) --------- ------601 18046 603 18374 606 19044 613 19055 641 19625 661 19826 679 20642 676 20380 624 16498 614 18043 695 17256 603 18724 --------- ------695 225514 NAT. GAS CCF -------0 0 0 0 0 0 0 0 0 0 0 0 -------327 NAT. GAS BILL ($) -------25 28 29 29 31 29 30 30 20 27 23 27 -------327 C. WATER C. WATER TON-HR BILL ($) --------- ------0 0 0 0 0 0 13204 2113 33860 5418 60760 9722 94941 15191 83589 13374 28783 4605 15210 2434 0 0 0 0 --------- ------330348 52856 STEAM STEAM MMBTU MMBTU/HR -------- -------0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -------- -------4464 0 Connecticut Center for Science and Exploration, Hartford, CT Energy Analysis Report - May 16, 2006 STEAM BILL ($) -------8316 5373 4280 2573 1983 1490 1305 1297 1590 2722 3245 6447 -------40621 TOTAL FUEL BILL ($) --------26387 23775 23353 23770 27057 31067 37168 35081 22713 23226 20524 25198 --------319318 21 THE CONNECTICUT LIGHT AND POWER COMPANY INTERMEDIATE TIME-OF-DAY ELECTRIC SERVICE NON-MANUFACTURERS RATE 56 Page 1 of 4 AVAILABLE for the electrical requirements of customers delivered at one point and at one standard voltage through one installation of transformers supplied by the Company. Service will be metered at one point by one installation of meters. The meter location will be determined by the Company. Where the Company deems it impractical to deliver electricity through one service, or where more than one meter has been installed for billing under a withdrawn rate, then the measurement of electricity may be by two or more meters. APPLICABLE to customers who are not manufacturers, as defined by Connecticut General Statute 12-412 (3) (A) (ii) and (iii), or who are not engaged in manufacturing as defined in PA 92-193 amending Subsections 12-81 (72) and 12-94c, and are taking service on the effective date of this rate whose demand equaled or exceeded in the last twelve months, or shall equal or exceed in the next twelve months, 350 kW but less than 1,000 kW. However, a customer on this rate whose maximum demand does not exceed 350 kW for 12 consecutive months, or whose prospective maximum demand shall not exceed 350 kW due to demonstrable conservation and load management measures may elect to take service under Rate 35 or Rate 37. Customers whose meters are not yet capable of measuring kilovolt-ampere (kVA) demand will be measured on a kW basis. Customers who migrate to this rate due to the withdrawal of Rates 985 and 39 have the option to be measured on a kW basis. In such cases the Distribution Demand Charge will be divided by .906 and the Production/Transmission Demand charges will be divided by .906. MONTHLY RATE: ON-PEAK (Weekdays 12 Noon - 8 p.m. during Eastern Standard Time) (Weekdays 1 p.m. – 9 p.m. during Daylight Savings Time) OFF-PEAK (All other hours) DISTRIBUTION SERVICE RATE: CUSTOMER CHARGE DIST. DEMAND CHARGE $420.00 $5.59 per kVA TRANSMISSION SERVICE RATE: PROD./TRAN. DEMAND CHARGE $5.09 per kVA SYSTEMS BENEFITS CHARGE: CHARGE PER kWh Supersedes Rate 56 Effective October 1, 2009 by Letter Ruling dated September 14, 2009 Docket No. 09-10-02 Rate 56.01-01-10.doc $0.00135 Effective January 1, 2010 by Letter Ruling dated December 28, 2009 Docket No. 10-01-01 THE CONNECTICUT LIGHT AND POWER COMPANY INTERMEDIATE TIME-OF-DAY ELECTRIC SERVICE NON-MANUFACTURERS RATE 56 Page 2 of 4 COMPETITIVE TRANSITION ASSESSMENT: PROD./TRAN. DEMAND CHARGE CHARGE PER kWh ON-PEAK CHARGE PER kWh OFF-PEAK $3.00 per kVA $0.00233 $0.00214 CONSERVATION CHARGE: CHARGE PER kWh $0.00300 RENEWABLE ENERGY: CHARGE PER kWh $0.00100 FMCC DELIVERY CHARGE: (as per FMCC tariff) CHARGE PER kWh ON-PEAK CHARGE PER kWh OFF-PEAK $0.00624 $0.00140 SUPPLIER SERVICE OPTIONS: (as per the Generation Services tariff) GENERATION SERVICE: STANDARD SERVICE (max demand less than 500 kW) CHARGE PER kWh ON-PEAK CHARGE PER kWh OFF-PEAK $0.13463 $0.10463 GENERATION SERVICE: LAST RESORT SERVICE (max demand equal to or greater than 500 kW) CHARGE PER kWh ON-PEAK January 2010 February 2010 March 2010 $0.09249 $0.09411 $0.09433 CHARGE PER kWh OFF-PEAK January 2010 February 2010 March 2010 $0.09249 $0.09411 $0.09433 THIRD-PARTY SERVICE as per contract Supersedes Rate 56 Effective October 1, 2009 by Letter Ruling dated September 14, 2009 Docket No. 09-10-02 Effective January 1, 2010 by Letter Ruling dated December 28, 2009 Docket No. 10-01-01 Rate 56.01-01-10.doc THE CONNECTICUT LIGHT AND POWER COMPANY INTERMEDIATE TIME-OF-DAY ELECTRIC SERVICE NON-MANUFACTURERS RATE 56 Page 3 of 4 FMCC GENERATION CHARGE: (as per FMCC tariff – not applicable to customers taking THIRD-PARTY SERVICE above) CHARGE PER kWh $0.00300 POWER FACTOR: If a customer is found to have a power factor of less than 90% lagging, the Company may require correction to at least 90% lagging as a condition of service. If the customer does not correct the power factor to at least 90% lagging and the Company corrects the condition, the customer will reimburse the Company for all costs which it incurs. COMBINED PUBLIC BENEFITS CHARGE: Pursuant to Conn. Agencies Regs. § 16-245-1(a)(2)(A) the Systems Benefits Charge, the Conservation Charge, and the Renewable Energy Charge are combined for billing purposes into the Combined Public Benefits Charge effective January 31, 2006. DETERMINATION OF PRODUCTION/TRANSMISSION DEMAND: The production/transmission demand shall be the highest average 30-minute kilovolt-ampere (kVA) demand recorded during the billing month in the on-peak hours as defined above. DETERMINATION OF DISTRIBUTION DEMAND: The distribution demand shall be the highest average 30-minute kilovolt-ampere (kVA) demand in the current month or the preceding eleven (11) months. The customer may, upon not less than three (3) months' prior written notice to the Company, decrease the Distribution Demand ratchet solely to reflect lower load levels resulting from demonstrable conservation and load management. SPECIAL PROVISIONS: 1. Primary Metering: If the service is metered on the primary side of the transformers supplying the customer, 2% of the metered kilowatt-hours will be deducted in computing the bill. 2. Facilities Ownership: If the service is taken at the property line and the Company is relieved of owning and maintaining all electrical distribution equipment on private property, except the metering equipment, a credit shall be applied to the bill equal to $.20 per kW of the Distribution Demand billed. 3. Transmission Voltage Delivery Allowance: Where service is supplied at transmission voltage, 69,000 volts and higher, and the Company is relieved of all investment on the customer's property, except the metering equipment, the Distribution Demand Charge under the Distribution Service Rate shall be waived, and all Energy Charges adjusted for Supersedes Rate 56 Effective October 1, 2009 by Letter Ruling dated September 14, 2009 Docket No. 09-10-02 Rate 56.01-01-10.doc Effective January 1, 2010 by Letter Ruling dated December 28, 2009 Docket No. 10-01-01 THE CONNECTICUT LIGHT AND POWER COMPANY INTERMEDIATE TIME-OF-DAY ELECTRIC SERVICE NON-MANUFACTURERS RATE 56 Page 4 of 4 the differential between line losses at transmission and primary distribution service. This Energy Charge shall be implemented by multiplying on-peak and off-peak charges by .9735 and .9787 respectively. Service supplied at transmission voltage is unregulated. RATE ADJUSTMENTS: This rate will be adjusted as provided in the Company’s Energy and Transmission Adjustment Clauses. COMPETITIVE TRANSITION ASSESSMENT COST ADJUSTMENT: Competitive Transition Assessment (CTA) charges and terms under this rate includes a CTA Cost Adjustment Charge set in accordance with the Company's CTA Cost Adjustment. SYSTEMS BENEFITS COST ADJUSTMENT: Systems Benefits service charges for all customers taking service under this rate shall be set in accordance with the Company’s Systems Benefits Cost Adjustment. MINIMUM CHARGE: The minimum charge is the customer charge plus the distribution demand charges in any rate category. TELEMETERING REQUIREMENT: The customer agrees that it is necessary to install telemetering equipment for the Company to read the meter(s). The location of such facilities shall be at the sole discretion of the Company. The customer will choose to either provide a dedicated direct dial analog phone line or elect for the Company to connect to their existing phone line. The provision of a suitable dedicated direct dial analog telephone line in the reasonable proximity of the electric meter as determined by the Company’s specifications is the sole responsibility of the customer. The customer shall be the owner of all telephone lines and shall maintain them in operable condition at all times. The Company will be responsible for the installation and maintenance of the connection between the telemetering equipment and the customer’s telephone line. TERM OF CONTRACT: notice. One year and thereafter unless canceled by one month's written Supersedes Rate 56 Effective October 1, 2009 by Letter Ruling dated September 14, 2009 Docket No. 09-10-02 Rate 56.01-01-10.doc Effective January 1, 2010 by Letter Ruling dated December 28, 2009 Docket No. 10-01-01 04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT Appendix E: Photovoltaic Information 166 BP 380 80 Watt Photovoltaic Module High-efficiency photovoltaic module using silicon nitride multicrystalline silicon cells. Performance Rated power (Pmax) Power tolerance Nominal voltage Limited Warranty1 Configuration 80W ± 5% 12V 25 years N BP 380N Clear universal frame with WireholdTM J-Box and polarized Multicontact (MC) connectors J BP 380J Clear universal frame and standard J-Box Electrical Characteristics2 Maximum power (Pmax)3 Voltage at Pmax (Vmp) Current at Pmax (Imp) Warranted minimum Pmax Short-circuit current (Isc) Open-circuit voltage (Voc) Temperature coefficient of Isc Temperature coefficient of Voc Temperature coefficient of power NOCT (Air 20°C; Sun 0.8kW/m2 ; wind 1m/s) Maximum series fuse rating Maximum system voltage BP 380 BP 375 80W 75W 17.6V 17.2V 4.55A 4.35A 76.0W 71.25W 4.8A 4.75A 22.1V 21.8V (0.065±0.015)%/ °C -(80±10)mV/°C -(0.5±0.05)%/ °C 47±2°C 15A (S, L); 20A (J) 600V (U.S. NEC ) 1000V (TÜV Rheinland & IEC 61215) Mechanical Characteristics Dimensions Length: 1209mm (47.6”) Width: 537mm (21.1”) Depth: 50mm (1.97”) Weight 7.7 kg (17.0 pounds) Solar Cells 36 cells (125mm x 125mm) in a 4x9 matrix connected in series Output Cables N RHW AWG# 12 (3.3mm2) cable with polarized weatherproof DC rated Multicontact connectors; asymmetrical lengths - 900mm (-) and 800mm (+) Junction Box J J-Version junction box with 6-terminal connection block; IP 65, accepts PG 13.5, M20, ½ inch conduit, or cable fittings accepting 6-12mm diameter cable. Terminals accept 2.5 to 10mm2 (8 to 14 AWG) wire. Diodes IntegraBusTM technology includes Schottky by-pass diodes Integrated into the printed circuit bus Construction Front: High-transmission 3mm (1/8th inch) tempered glass; Back: White back sheet; Encapsulant: EVA Frame Clear anodized aluminum alloy type 6063T6 Universal frame; Color: silver 1. Module Warranty: 25-year limited warranty of 80% power output; 12-year limited warranty of 90% power output; 5-year limited warranty of materials and workmanship. See your local representative for full terms of these warranties. 2. This data represents the performance of typical BP modules, and are based on measurements made in accordance with ASTM E1036 corrected to SRC (STC.) 3. During the stabilization process that occurs during the first few months of deployment, module power may decrease by approx. 1% from typical Pmax. BP Solar 2008 6802.0005 Rev. E 07/08 Quality and Safety Manufactured in ISO 9001-certified factories; conforms to European Community Directives; certified to IEC 61215 Module power measurements calibrated to World Radiometric Reference through ESTI (European Solar Test Installation at Ispra, Italy) Framed modules certified by TÜV Rheinland as Safety Class II (IEC 61730) equipment for use in systems up to 1000 VDC Framed modules listed by Underwriter’s Laboratories for electrical and fire safety (Class C fire rating) 5.0 4.0 Current (A) ESTI BP 380 I-V Curves 3.0 t=0C t=25C t=50C t=75C 2.0 1.0 Approved by Factory Mutual Research in NEC Class 1, Division 2, Groups C & D hazardous locations (J version only) 0.0 0 5 10 15 20 25 Voltage (V) Qualification Test Parameters Temperature cycling range Humidity freeze, damp heat Static load front and back (e.g. wind) Front loading (e.g. snow) Hailstone impact -40°C to +85°C (-40°F to 185°F) 85% RH 2400 pa (50psf) 5400 pa (113psf) 25mm (1 inch) at 23 m/s (52mph) Module Diagram Dimensions in brackets are in inches. Un-bracketed dimensions are in millimeters. Overall tolerances ±3mm (1/8”) Front View BPJB Back View MC L-Version MC S-Version Section A-A Included with each module: self-tapping grounding screw, instruction sheet, and warranty document. Note: This publication summarizes product warranty and specifications, which are subject to change without notice. Additional information may be found on our web site: www.bpsolar.com BP Solar 2008 6802.0005 Rev. E 07/08 RETScreen Energy Model - Power project Show alternative units Proposed case power system Incremental initial costs Technology Photovoltaic Method 1 Method 2 Analysis type Photovoltaic Power capacity Manufacturer Model Capacity factor Electricity delivered to load Electricity exported to grid Fuel rate - proposed case power system Electricity export rate kW % MWh MWh $/MWh $/MWh 60.50 BP Solar BP380 15.0% 0 79.5 $ 1,294,650 See product database 756 unit(s) 0.00 Emission Analysis Financial Analysis Financial parameters Inflation rate Project life Debt ratio % yr % 3.0% 25 0% Initial costs Power system Other Total initial costs $ $ $ 1,294,650 1,294,650 100.0% 0.0% 100.0% Incentives and grants $ 319,750 0.0% $ $ $ $ -11,465 0 Total annual costs Annual savings and income Fuel cost - base case Cumulative cash flows graph 0 -11,465 Total annual savings and income $ $ $ 0 0 Financial viability Pre-tax IRR - assets Simple payback Equity payback % yr yr -5.0% 85.0 > project 0 Cumulative cash flows ($) Annual costs and debt payments O&M (savings) costs Fuel cost - proposed case 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 -200,000 -400,000 -600,000 -800,000 -1,000,000 -1,200,000 Year 4/3/2010 RETScreen4-1 04-07-2010 JENNA STAUFFER LIGHTING/ELECTRICAL FINAL THESIS REPORT CONNECTICUT SCIENCE CENTER HARTFORD, CONNECTICUT Appendix F: Roof Garden Structural 167