4100DB0301R9/04 09/2004 Lexington, KY, USA Data Bulletin Square D® Load Center Short-Circuit Current Ratings Retain for future use. INTRODUCTION This document defines fully-rated systems, two-tier series short circuit current protection and three-tier series short circuit current protection. It also addresses NEC® requirements and illustrates series rating labels currently provided with Square D® multi-metering and load center equipment. The location of series rating labels applied to Square D load centers is depicted on pages 2 and 4 of this document. Fully-Rated System In a fully rated system, the interrupting rating of all the overcurrent protective devices must be greater than or equal to the available fault current at the line side terminals of each device. Series-Rated System The NEC and UL® permit assigning a short circuit current rating to a tested combination of circuit breakers or fuses that is higher than the individual rating of the downstream overcurrent protective device. Testing by the circuit breaker manufacturer demonstrates that the combination can safely interrupt the available fault current. NEMA defines a series rating as follows: Series Rating - A short-circuit interrupting rating assigned to a combination of two or more overcurrent protective devices which are connected in a series and in which the rating of the downstream device(s) in the combination is less than the series rating. The combination of overcurrent protective devices may be enclosed in a single piece of equipment such as a load center. Three-tier series rated systems are most commonly designed with the supply side device in a separate enclosure, such as metering equipment, that feeds a load center. NOTE: The load-side device is always a circuit breaker. The supply-side device may be either a circuit breaker or a set of current-limiting fuses. Two-Tier Series Rating A two-tier series rating can be used within a single enclosure (Example 1) or in separate enclosures (Example 2). Example 1: QO® Main Circuit Breaker Load Center 22 kA QOM VH 200 A QO 30 A Example 2: MP Meter-Pak™ feeding Homeline Main Lug Load Center 22 kA 10 kA QOM MVH 200 A HOM 30 A 1 Square D® Load Center Short-Circuit Current Ratings Data Bulletin 4100DB0301R9/04 09/2004 Location of Two-Tier Series Ratings Label in Square D Equipment The permitted NEC and UL series ratings are found marked in the equipment. Unless the equipment is marked, one cannot be assured the breaker combination will perform appropriately in the enclosure. Square D marks two-tier series ratings on the inside wall of load centers (See Figure 1). The two-tier series rating labels applied to current production convertible main QO® and Homeline® load centers are depicted in Figures 2 and 3, respectively. NOTE: The information contained in this data bulletin is current at time of printing; however, ratings may change or additional ratings may be added without notice. Refer to the series-connected ratings marked in the equipment. Figure 1: Two-Tier Series Ratings Label Application Two-tier series rating labels are applied to the side wall of current production QO and Homeline load centers. Figure 2: QO Two-Tier Series Ratings Labels for Convertible Main Load Centers SHORT CIRCUIT CURRENT RATING SHORT CIRCUIT CURRENT RATING Integral or Remote Fuse RMS Symmetrical Class or Circuit Breaker Amperes at ___Vac Max. Catalog Designation (Max. A) Branch Circuit Breaker Catalog Designation (Max. A) 5,000 at 240 QO-H 10,000 at 240 QO (125) 10,000 at 240 25,000 at 240 65,000 at 240 QO-VH (100) QO (100) QD (125) QO (125) QO (100) ¥ QOT QO-VH (100) § 22,000 25,000 QOM-VH (125) QO-VH (125) QO (100) ¥ QOT QD (125) QO (100) ¥ QOT QOH QO (100) ¥ QOT QG (125) QO (100) ¥ QOT T3 (125) QJ (125) QO (100) ¥ QOT QH QG (125) QO (125) 100,000 at 240 T3 (125) QO (125) 100,000 at 208Y/120 QJ (125) 1-Pole QO 2-Pole QO (125) 3-Pole QO (30) , 3-Pole QO-VH (100) The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. 3 Ø 3 W Grounded B Phase QO includes QO-GFI, QO-EPD, QO-PL, QO-AS, and QO-AFI. § QO-VH includes QO-VHGFI and QO-VHAFI. Three-Phase QO Load Centers 125 A Max. 2 QO-H 5,000 10,000 QO-H QO-VH (125) § 22,000 at 240 Integral or Remote Fuse Branch Circuit Breaker RMS Symmetrical Class or Circuit Breaker Catalog Designation Amperes at 240 Vac Max. Catalog Designation (Max. A) (Max. A) 42,000 QOH (100) QH 65,000 100,000 The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. 3 Ø 3 W Grounded B Phase ¥ QO includes QO-GFI, QO-EPD, QO-PL, QO-AS, and QO-AFI. § QO-VH includes QO-VHGFI and QO-VHAFI. Single-Phase QO Load Centers 125 A Max. © 2003–2004 Schneider Electric All Rights Reserved Square D® Load Center Short-Circuit Current Ratings Data Bulletin 4100DB0301R9/04 09/2004 Figure 2: (Continued) QO Two-Tier Series Ratings Labels for Convertible Main Load Centers SHORT CIRCUIT CURRENT RATING SHORT CIRCUIT CURRENT RATING Integral or Remote Fuse Branch Circuit Breaker RMS Symmetrical Class or Circuit Breaker Catalog Designation Amperes at 240 Vac Max. Catalog Designation (Max. A) (Max. A) QO-H 5,000 10,000 QO (125) ¥ QOT 22,000 QO-VH (125) § QOM-VH (200) 25,000 42,000 QOM-VH (200) QO-VH QO (125) ¥ QOT QD (200) QO (125) ¥ QOT QOH QOH QO (125) ¥ QOT QG (200) QO (125) ¥ QOT T3 (200) QJ (200) QO (125) ¥ QOT QH 65,000 100,000 Single-Phase QO Feed-Through Load Centers 200 A Max. QO-H 5,000 10,000 QO ¥ QOT QO-VH § 22,000 25,000 QOM-VH QO-VH QO ¥ QOT QD (225) QO ¥ QOT QOH QO (125) ¥ QOT QG (225) QO ¥ QOT T3 (200) QJ (225) QO ¥ QOT QOH 42,000 QH 65,000 100,000 The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. 3 Ø 3 W Grounded B Phase ¥ QO includes QO-GFI, QO-EPD, QO-PL, QO-AS, and QO-AFI. § QO-VH includes QO-VHGFI and QO-VHAFI. Figure 3: Integral or Remote Fuse Branch Circuit Breaker RMS Symmetrical Class or Circuit Breaker Catalog Designation Amperes at 240 Vac Max. Catalog Designation (Max. A) (Max. A) The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. 3 Ø 3 W Grounded B Phase ¥ QO includes QO-GFI, QO-EPD, QO-PL, QO-AS, and QO-AFI. § QO-VH includes QO-VHGFI and QO-VHAFI. Single-Phase QO Load Centers 150 A—225 A Homeline Two-Tier Series Ratings Labels for Convertible Main Load Centers SHORT CIRCUIT CURRENT RATING Integral or Remote Fuse RMS Symmetrical Class or Circuit Breaker Amperes at 240 Vac Max. Catalog Designation (Max. A) Branch Circuit Breaker Catalog Designation (Max. A) 10,000 SHORT CIRCUIT CURRENT RATING Integral or Remote Fuse RMS Symmetrical Class or Circuit Breaker Amperes at 240 Vac Max. Catalog Designation (Max. A) Branch Circuit Breaker Catalog Designation (Max. A) 10,000 22,000 QOM-VH (125) QO-VH (125) 25,000 QD (125) 42,000 QOH 65,000 100,000 22,000 QOM-VH QO-VH 25,000 QD (225) 42,000 QOH QG (125) 65,000 QG (225) QJ (125) 100,000 QJ (225) HOM (100) ¥ HOMT HOM ¥, HOMT The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. ¥ HOM includes HOM-GFI, HOM-EPD, and HOM-AFI. ¥ HOM includes HOM-GFI, HOM-EPD, and HOM-AFI. Homeline Load Centers 125 A Max. Homeline Load Centers 150 A—225 A Max. SHORT CIRCUIT CURRENT RATING Integral or Remote Fuse RMS Symmetrical Class or Circuit Breaker Amperes at 240 Vac Max. Catalog Designation (Max. A) Branch Circuit Breaker Catalog Designation (Max. A) 10,000 22,000 QOM-VH (200) QO-VH 25,000 QD (200) 42,000 QOH 65,000 QG (200) 100,000 QJ (200) HOM ¥, HOMT The rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breakers MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types. ¥ HOM includes HOM-GFI, HOM-EPD, and HOM-AFI. Homeline Universal Main Load Centers © 2003–2004 Schneider Electric All Rights Reserved 3 Square D® Load Center Short-Circuit Current Ratings Data Bulletin Three-Tier Series Rating 4100DB0301R9/04 09/2004 A three-tier series rating consists of three levels of overcurrent protection devices (the furthest load-side device being a circuit breaker). Per NEC 240.86, this three-tier combination of overcurrent protection must be marked on the end-use electrical equipment (load center). See Example 3. Example 3: EZM® Fusible Main Device feeding EZM Branch Device feeding Homeline Main Lug Load Center (100 kA Three-Tier Series Rating) 10 kA 100 kA Class T (300 Vac) QO VH 125 A Location of Three-Tier Series Ratings in Square D Equipment HOM 30 A For convertible main load centers, three-tier series ratings labels are applied on the back side of indoor load center covers and on outdoor load center deadfronts (See Figure 4). The information contained on this three-tier series rating label is shown in Figure 5. For single-phase fixed main indoor and outdoor load centers, two-tier and three-tier ratings are printed on the same label. This label is located on the left side wall (See Figure 4). The information contained on the series rating label for single-phase fixed main load centers is depicted in Figure 5. Figure 4: Convertible Main Load Centers Label Locations Three-tier series rating label is applied to the dead front trim of current production convertible main QO and Homeline outdoor load centers. Figure 4a: Three-tier series rating label is applied to the backside of current production convertible main QO and Homeline covers for indoor load centers. Fixed Main Load Center Label Locations Two-tier / three-tier series rating label is applied to left side wall of current production single-phase fixed main QO and Homeline indoor and outdoor load centers. 4 © 2003–2004 Schneider Electric All Rights Reserved Square D® Load Center Short-Circuit Current Ratings Data Bulletin 4100DB0301R9/04 09/2004 Figure 5: Three-Tier Series Ratings Label Applied to Convertible Main QO and Homeline Load Centers THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers SQUARE D Tenant Circuit Breaker (Integral or Remote) Poles Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 100 50 HOM§ 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) 2,3 The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. Figure 6: HOMT HOM § HOMT 30 50 50 30 200 50 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. Two-Tier / Three-Tier Series Rating Label Applied to Fixed Main Homeline Load Centers SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Line Side Square D Circuit Breaker Symmetrical Amperes at Catalog Designation or Fuse Class 120 / 240 Vac Maximum Maximum Ampere Rating Poles Square D Tenant Circuit Breaker (Remote Only) Catalog Designation Poles Square D Circuit Breakers Max. Ampere Rating 1-Pole 2-Pole Catalog Max. Ampere Designation Rating 10,000 22,000 25,000 42,000 42,000 65,000 100,000 42,000 2 QO-VH (125) QD (225) 2 2 QOH 2,3 LA, MA Class T3 2,3 LH, MH, PA (1600) QO-VH 2 125 MHF, Class R, J, T3 (800) 2,3 QD 2,3 2 LA, MA 225 QG (225) 2 65,000 2 LH, MG, MH, PG, PA (1600), RG (2000) QD 2,3 225 QJ (225) 2 100,000 MJ, MHF, PJ, PH (1600), RJ (2000), 225 QD 2,3 2 Class R, J, T6, T3, L (1200) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard wiring diagram for circuit breaker types. See circuit breaker for voltage and interrupting rating. HOM § HOMT 50 30 125 ¶ 50 HOM § HOMT 50 30 100 ¶ 50 HOM § HOMT 50 30 125 ¶ 50 § Catalog Designation HOM includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. ¶ Load centers with 100 A mains rating are limited to 100 A maximum integral main circuit breaker and 70 A maximum branch circuit breaker. Figure 7: Two-tier/Three-Tier Series Ratings Label applied to Single Phase Fixed Main QO Load Centers SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at 120 / 240 Vac Maximum Fuse Class (Max. Ampere Rating) 5,000 10,000 22,000 25,000 42,000 42,000 42,000 65,000 100,000 Square D Tenant Circuit Breaker Square D Circuit Breakers (Remote Only) Line Side Fuse or Square D Circuit Breaker Catalog Designation (Max. Ampere Rating) Poles Catalog Designation Max. A Rating Catalog Poles Max. A Rating Designation 1-Pole 2-Pole QO-H 100 ¶ QO QO-VH (125) QD (225) QOH LA, LH, MA, MH, MHF, PA (1600) R, J, T3 2 2 2 2,3 2,3 LA, MA 2 QG (225) LH, MG, MH, PG, PA (1600), RG (2000) 2,3 2 QJ (225) MJ, MHF, PJ, PH (1600), RJ (2000) 2,3 R, J, T6, T3, L (1200) QO-VH 2 125 QD 2 225 QD 2 225 QD 2 225 70 125 ¶ QOT 20 QO QOT 70 20 125 ¶ QO 70 125 ¶ QOT 20 The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series ¶ Load centers with 100 A mains rating are connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than limited to 100 A maximum integral main circuit breaker and 70 A maximum branch that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard wiring diagram for circuit breaker. circuit breaker types. 240 Vac, 3-Phase 3 W Grounded "B" phase. © 2003–2004 Schneider Electric All Rights Reserved See circuit breaker for voltage and interrupting rating. Catalog Designation QO includes QO-GFI, QO-EPD, QO-PL, QO-AS, and QO-AFI circuit breakers. 5 Square D® Load Center Short-Circuit Current Ratings Data Bulletin How to Read the Three-Tier Series Rating Label Figure 8: 4100DB0301R9/04 09/2004 Read the label from left to right. Select the appropriate short circuit current rating, and then read across the row to select main disconnect, tenant circuit breaker and load center circuit breakers. See example below in Figure 8. Selecting Short Circuit Current Rating THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 42,000 at 240 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) 50 100 30 50 200 50 HOMT 50 30 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. 65 kA HOM § HOMT HOM § 10 kA The highlighted portion in the label above depicts the system shown to the left. LHP36400 QDP22100TM HOM 30 A EZM Main Breaker Device (EZM3400CB) Feeding EZM Branch Device (EZM312225) Downstream Homeline Load Center (HOM20L125C) The same series rating information is supplied on all convertible main QO and Homeline load centers covers. The figures below explain which portions of the label apply to the different types of end use equipment. THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. HOM § 50 100 HOMT 30 HOM § HOMT 50 30 50 200 50 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. For Three-Phase QO Load Centers 6 © 2003–2004 Schneider Electric All Rights Reserved Square D® Load Center Short-Circuit Current Ratings Data Bulletin 4100DB0301R9/04 09/2004 THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. HOM § 50 100 HOMT HOM § HOMT 30 50 200 50 50 30 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. For Single-Phase Convertible Main QO Load Centers Protected with QO-VH Tenant Circuit Breaker THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. HOM § 50 HOMT 30 50 HOM § HOMT 50 30 200 50 100 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. For Single-Phase Convertible Main QO Load Centers Protected with 2-Pole QD Tenant Circuit Breaker THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. HOM § 50 100 HOMT HOM § HOMT 30 50 200 50 50 30 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. For Homeline Convertible Main Load Centers Protected with QO-VH Tenant Circuit Breaker © 2003–2004 Schneider Electric All Rights Reserved 7 Square D® Load Center Short-Circuit Current Ratings Data Bulletin 4100DB0301R9/04 09/2004 THREE-TIER SERIES CONNECTED SHORT CIRCUIT CURRENT RATING Interrupting Rating RMS Symmetrical Amperes at_____Vac Max. 42,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240 42,000 at 240 65,000 at 240 100,000 at 240, 2-Pole 65,000 at 240, 3-Pole 100,000 at 208Y/120, 3-Pole Line Side SQUARE D Circuit Breaker Catalog Designation or Fuse Class (Maximum A Rating) LA, LH, MA, MH, MHF, PA (1600), Class R, J, T3 LA, MA, Class T3 LH, MH, PA (1600) MHF, Class R, J, T3 (800) LA, MA LH, MG, MH, PG, PA (1600), RG (2000) MJ, MHF, PJ, PH (1600), RJ (2000), Class R, J, T6, T3, L (1200) SQUARE D Branch Circuit Breakers QO Load Centers Homeline Load Centers SQUARE D Tenant Circuit Breaker Poles (Integral or Remote) Catalog Designation (Max. A rating) Poles 2,3 QO-VH (125) 2 2,3 QO-VH (125) 2 2,3 Max. Ampere Rating Max. Ampere Rating Catalog Catalog Designation 1-Pole 2-Pole 3-Pole Designation 1-Pole 2-Pole 70 100 QO QOT 20 2 QO QOT 70 20 200 QO QO-VH QO-H 70 125 3 QD (225) The Short Circuit Current Rating is equal to the lowest interrupting rating of any circuit breaker installed or combination series connected circuit breaker. Additional or replacement circuit breaker(s) MUST have an interrupting rating equal to or greater than that of the circuit breaker with the lowest interrupting rating presently installed. See panelboard interior for circuit breaker types that may be used in this panelboard. See circuit breaker for voltage and interrupting rating. HOM § 50 HOMT 30 50 HOM § HOMT 50 30 200 50 100 30 100 100 Catalog Designation QO includes § Catalog Designation HOM QO-GFI, QO-EPD, QO-PL, QO-AS, includes HOM-GFI, HOM-EPD, and HOM-AFI circuit breakers. and QO-AFI circuit breakers. 100 A maximum branch circuit breaker in load centers with 125 A maximum mains rating. For Homeline Convertible Main Load Centers Protected with 2-Pole QD Tenant Circuit Breaker NEC Requirements Figure 9: Example of Label Provided Two sections of the NEC address markings of series ratings: Section 110.22 and Section 240.86(a). Per Section 110.22, the equipment must be legibly marked in the field to indicate the equipment has been applied with a series combination rating. The intent of this section is to alert the installer that the circuit breakers were installed based on a series rating, and to mark the equipment with the short circuit current rating being applied in the series combination. Square D provides a label for this purpose with all MP Meter-Pak™ Meter Centers and EZ Meter-Pak® Meter Center Branch Devices (See Figure 9). The label is not applied by Square D, but is provided loose in these devices for application when series ratings are applied by the installer. CAUTION / PRECAUCION SERIES COMBINATION SYSTEM SISTEMA COMBINADO EN SERIE RATED _____________ AMPERES. CORRIENTE NOMINAL: _________ A ID E N T I F I E D R E P L A C E M E N T ES NECESARIO IDENTIFICAR EL COMPONENTE DE REPUESTO COMPONENTS REQUIRED. Additional or replacement circuit breakers must be manufactured by Square D and have a short circuit current rating equal to or greater than that of the circuit breaker(s) presently installed. Refer to additional information provided with this equipment. Failure to do so can result in electrical explosion and fire. Los interruptores automáticos adicionales o de repuesto deben ser productos de Square D; su corriente nominal de cortocircuito debe ser igual que o mayor que la de los interruptores automáticos actualmente instalados. Consulte la información adicional incluida con el equipo. El incumplimiento de esta instrucción puede causar una explosión eléctrica e incendio. Section 240.86(a) requires that the series combination of overcurrent protective devices be marked on the end use equipment. This marking is applied by the manufacturers of switchboards, panelboards, load centers, etc. Square D marks load center enclosures and covers with series ratings per Figures 1, 4 and 4a. Conclusion Schneider Electric USA 1601 Mercer Road Lexington, KY 40511 USA 1-888-SquareD (1-888-778-2733) www.SquareD.com A series rated system is an affordable, viable alternative to a fully rated system. Series ratings can be two-tiered or multi-tiered, depending on the levels of overcurrent protection tested and certified. Series ratings include circuit breaker/circuit breaker combinations and also fuse/circuit breaker combinations, but the furthest load side overcurrent protective device is always a circuit breaker. Overcurrent protective device combinations used in series rated systems should be marked on the end use equipment by the electrical distribution product manufacturer. Equipment installed as part of a series rated system must be marked in the field to indicate the short circuit current rating being applied in the series combination. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2003–2004 Schneider Electric All Rights Reserved