Niche Market Testing by Lynn Hamrick, ESCO Energy Services A Primer for Testing Medium-Voltage Breakers in the Industrial Environment D uring its 20-40 year service life, a circuit breaker must be constantly prepared to operate. Typically, long periods of inactivity often elapse during which the breaker’s mechanical and electrical components never move. The circuit breaker is the active link in a fault clearance situation. When a fault occurs on the electrical system, the associated fault current must be interrupted quickly and reliably. This action is referred to as fault clearing. If a breaker fails to clear a faulted circuit, the resulting damage can be very serious in terms of both personnel injury and equipment damage. Even though circuit breakers are comparatively reliable, circuit breaker failures can and do occur. Therefore, circuit breakers must be tested and maintained to ensure proper operation during these faults. Many circuit breakers provide longer service lives than expected. If you can ascertain that a breaker is in good condition, you can continue to use it rather than replace it at its estimated end-of-life. For the remainder of this discussion, we will concentrate on medium-voltage (1 kV up to 35 kV) circuit breakers utilized within an industrial environment. Different Medium-Voltage Breaker Designs There are three basic designs of medium-voltage breakers: Air Circuit Breaker – Air circuit breakers are the prevalent type of medium voltage breaker in an industrial environment due to the typical age of the equipment and their lower cost; however, very few of this type of breaker are still being manufactured. Air circuit breakers are commonly used in medium-voltage electrical distribution systems and include operating mechanisms that are mainly exposed to the environment. Since the air circuit breakers are rated to carry current continuously, the exposure to convection cooling air assists in keeping the operating components within reasonable temperature limits. A typical air circuit breaker includes a main contact assembly, which is either opened (“tripped”), interrupting a path for power to travel from the source to the load, or “closed”, providing a path for power to travel from the source to the load. In many air circuit breakers, the force necessary to open or close the main contact assembly is provided by an arrangement of compression springs. In many air circuit breakers, the mechanism for controlling the compression springs comprised of a configuration of mechanical linkages between a latching shaft and an actuation device. The actuation device may be manually operated, or electrically operated with trip and close coils. In a comwww.netaworld.org mon construction of a medium-voltage air circuit breaker, the movable contact is mounted on a contact arm that is pivoted to open or close the contacts by a spring powered operating mechanism triggered through the trip or closing coils by a control switch or closing relay (i.e., protective relay). Smaller opening springs are put in tension during closing and assist in opening when the trip coil is given tripping energy from the control switch or protective relays. These protective relays may also be used to provide auxiliary functions along with over-current protection. The current interruption capability of air circuit breakers is dependent in part upon their ability to extinguish the arc that is generated when the breaker main contacts open or close. A medium-voltage air circuit breaker in an industrial environment is typically a draw-out type in which a breaker is movable so as to be separated (“racked out”) from the power source in order to facilitate maintenance or connected (“racked in”) to the power source using either a manual or motor-assisted racking capability. Vacuum Circuit Breaker – Vacuum circuit breakers are the most popular type of medium-voltage breaker in an industrial environment due to their smaller size and improved reliability over air circuit breakers. Vacuum circuit breakers are similar to air circuit breakers with the difference being that the main contacts are housed in a vacuum chamber (“bottle”). One of the contacts is fixed relative to the bottle Summer 2010 NETA WORLD 1 and to an external electrical conductor which is interconnected with the circuit to be controlled by the circuit breaker. The other separable main contact is movable. The moveable contact assembly is usually comprised of a stem of circular cross-section having the contact at one end enclosed within a vacuum bottle and a driving mechanism at the other end which is external to the vacuum bottle. An operating rod assembly comprised of a push rod, which is fastened to the end of the stem opposite the moveable contact, and a driving mechanism provide the motive force to move the moveable contact into or out of engagement with the fixed contact. Compression springs are provided in connection with the operating rod assembly in order to be able to separate the moveable contact from the fixed contact and to assure the necessary force so that the contacts will not accidentally open under inappropriate conditions. As with the air circuit breaker, the actuation device may be manually or electrically operated by trip and close coils triggered by a protective relay. These protective relays may also be used to provide auxiliary functions along with over-current protection. Vacuum circuit breakers offer many advantages as compared to other types, including: relatively long life due to controlled contact erosion; maintenance-free operation provided by enclosure of the contacts within the hermetically sealed housing; excellent operational reliability due to the use of hard contact materials; little or no atmospheric contact contamination, which contamination can detrimentally form oxides and corrosion layers on the contacts; little or no noise during operation due to containment of arcing within the hermetically sealed housing; relatively few environmental effects; and very low current chop, resulting in a minimal induced transient voltage spike during circuit interruption so that surge suppressors are typically not required. A medium-voltage vacuum circuit breaker in an industrial environment is also typically a draw-out type. Oil Circuit Breaker – Oil circuit breakers, which are typically located outdoors, were the past standard but are becoming more rare in the industrial environment as they are being replaced with air or vacuum circuit breakers. Oil circuit breakers have all contacts and mechanism housed within an oil-filled tank, which provides for both an insulation and arc-quenching capability. A typical oil circuit breaker includes the same operational characteristics as an air circuit breaker. A medium-voltage oil circuit breaker in an industrial environment is typically a stand-alone type and requires that oil be drained and the breaker de-tanked to perform maintenance. Suggested Electrical Tests There are three basic electrical tests that should be performed on medium-voltage circuit breakers as part of a preventive maintenance program. Contact resistance – This test should be performed from line-to-load terminals for each phase with the breaker closed. The values should be within 50% of each other and comparable to similar circuit breakers. 2 NETA WORLD Summer 2010 Insulation resistance – This test should be performed phase-to-phase and phase-to-ground (i.e., case, if applicable) with the breaker closed, as well as across the open contacts for each phase. For medium-voltage breakers, the manufacturer should provide the testing voltages and acceptance values for this test. When not available or where no recommendations are provided, the following abbreviated table from ANSI/NETA MTS-2007 may be used. Insulation Resistance Test Values – MV Breakers Nominal Rating of Breaker in Volts Minimum Test Voltage, DC 2,500 1,000 8,000 2,500 5,000 Recommended Minimum Insulation Resistance in Megohms 500 2,500 1,000 15,000 2,500 5,000 35,000 and above 15,000 25,000 5,000 2,000 20,000 100,000 Dielectric withstand voltage – This basically an ac or dc high potential test. This test should be performed from the line side of each phase with the breaker open and the load side of that phase and line and load sides of the other phases tied together and tied to ground. For vacuum circuit breakers, this test will also provide an indication of the vacuum bottle integrity. For medium voltage breakers, the manufacturer should provide the testing voltages for this vacuum bottle integrity. It should be noted that for a medium voltage vacuum breaker, only use of an ac high potential is recommended. When not available or where no recommendations are provided, the following abbreviated table from ANSI/NETA MTS-2007 may be used Dielectric Withstand Test Voltages – MV Breakers Nominal System (Line) Voltage Maximum Field Applied AC Test (kV) Maximum Field Applied DC Test (kV) 1.2 6.0 8.5 4.8 11.4 14.4 20.4 2.4 8.3 18.0 25.0 34.5 9.0 12.7 15.6 22.1 24.0 30.0 42.0 16.1 28.8 33.9 42.4 59.4 www.netaworld.org In addition to these basic tests, the protective relays should be tested for functionality with all implemented protective functions being tested. In an industrial environment, over-current protection is typically the main, and possibly only, function provided by the protective relay; however, if there are other protective functions being provided, they should also be tested. It is also important that the breaker actually be tripped and closed by the manual controls, and tripped by the protective relay to ensure that the relay and breaker are operating correctly. This will functionally test the trip and close coils as well as the protective circuit. Power-factor or dissipation-factor testing should be considered as an additional test of each breaker’s insulation system. For oil circuit breakers, a tank loss index should be determined and, where individual mechanisms are provided by phase for operation, time-travel testing should be considered for each phase. Oil sampling is also recommended annually with oil sample quality analysis being provided for dielectric breakdown, acid neutralization number, interfacial tension, moisture, color, and power factor. Where cubicle heaters are provided, functional testing of the heaters should be verified. In conclusion, even though circuit breakers are reliable when compared to other electrical devices, circuit breaker failures occur. When a breaker fails to operate, the resulting damage can be very serious in terms of both personnel injury and equipment damage. Therefore, circuit breakers must be tested and maintained to ensure proper operation during these faults. As Operations Manager of ESCO Energy Services Company, Lynn brings over 25 years of working knowledge in design, permitting, construction, and startup of mechanical, electrical, and instrumentation and controls projects as well as experience in the operation and maintenance of facilities. Lynn is a Professional Engineer, Certified Energy Manager and has a BS in Nuclear Engineering from the University of Tennessee. www.netaworld.org Summer 2010 NETA WORLD 3