Doepke The experts in residual current technology l a u d i s e r e v i t i s n e s C D C A r e k a e r b t i u c r i c t n e r r cu B 4 S DF »» Protective separation for smooth DC residual currents and AC residual currents up to 100 kHz »» Comprehensive, standard-compliant protection against personal injury, fire, and damage to property and systems »» Maximum immunity against transient current – guarantees the highest system availability possible »» Rated current up to 125 A in just 4 modules (installation width) allows for easy system conversion »» Application-specific versions can be supplied Doepke Ty pe B: AC- DC se n s itiv e re sidual cu rren t p ro te c tio n DFS 4 B, 30 mA: tripping current frequency response 10000 Residual current (mA) SK 1000 B+ NK 100 10 10 100 Frequency (Hz) 1000 10000 100000 The per fect tr ipping response thr ough var ious char act eri st i c curves AC-DC sensitive protection These days consumers and converters with operating frequencies into the kilohertz range are standard in electro- 1 technical systems. The consideration of protective devices Standard-compliant protection for operating these systems has become more complex For many applications, the use of an AC-DC sensitive over recent years. In particular, protection against residual RCCB is required by VDE regulations and the safety currents must be looked at with new eyes, because con- provisions of health and safety authorities. These sumers and converters can also generate these currents, regulations stipulate that type B residual current circuit The best protection with the DFS 4 B NK or B+ which contain both direct current and frequencies up to tens breakers must be used in systems with operating DFS 4 B+ residual current circuit breakers meet the of kilohertz. Conventional type A residual current circuit equipment that can generate smooth DC currents. The minimum fire protection requirements. The characteristic breakers are not suitable for these kinds of conditions and number of devices that can generate these smooth curve for the tripping current frequency response of these therefore pose a risk to more than just the system operator. DC currents is constantly increasing, and many elec- breakers runs at frequencies up to 20 kHz and maintains High system availability with the DFS 4 B SK trical installations must then be adapted accordingly. a tripping threshold of 420 mA. Modern converters may The SK frequency response has a tripping threshold of A specialist in residual current protection technology, Therefore, choosing an AC-DC sensitive RCCB is an generate residual currents with much higher frequencies, up to 2 A at high frequencies. If system-specific, high- Doepke is a pioneer for AC-DC sensitive residual investment in the future: with it you have equipped your however, which also pose a fire hazard. In these cases frequency leakage currents are unavoidable, the SK current circuit breakers. For years our equipment systems today for the requirements of tomorrow. devices with the NK characteristic curve are recommended. characteristic curve offers the highest possible system Even at frequencies up to 100 kHz, these operate within availability. Devices with this curve provide protection has provided reliable protection against all types of residual currents. The various types of devices Furthermore, it goes without saying that our a conventional upper threshold of 300 mA and therefore against fire and direct contact burns at frequencies up to we offer use simple solutions to meet the complex protective devices meet the relevant national provide increased protection against fire and direct contact 1 kHz. These devices present a solution that combines protection requirements of a wide range of systems. and international standards (IEC) in force. burns. These devices meet all relevant standards. safety and cost-effectiveness even for problematic systems. Doepke Choosi n g t h e ri g h t b r e a k e r Basic circuit for electronic operating equipment in accordance with DIN VDE 0100 530 DFS 4 B NK Will the breaker be used for a plant where fire is a potential hazard? Three-phase full bridge circuit Three-phase star circuit Full bridge circuit between external conductors Single-phase detection with smoothing Systems with frequency converters: ● Pumping, air conditioning and ventilation systems ● Escalators and wheelchair systems ● Medical devices and also ● Solar power plants ● Welding plants ● UPS systems yes yes Examples: yes facilities ● Biogas plants ● Paint shops ● Joineries ● Refuelling systems ● Warehouses ● Agricultural Is a fire protection threshold of 420 mA too high or are frequencies greater than 20 kHz? NK meets conventional required fire protection levels of 300 mA at frequencies up to 100 kHz Result: optimal system protection B+ DFS 4 B+ no meets required fire protection levels of 420 mA at frequencies of only 20,000 Hz or lower Result: limited system protection no no A DFS 4 B SK Use conventional type A RCCB SK With a tripping threshold of 2 A at frequencies above 2 kHz, this breaker protects against high leakage currents. At first glance, choosing the right RCCB requirements by considering but not least, provisions in force for residual current circuit breaker seems how your RCCB will be used and your facility. You can always find the a difficult decision. In actual fact only a what criteria need to be met in order right breaker at Doepke – if you don‘t few easy questions need to be taken to comply with insurance conditions, see one in our range, we will design a into account: you can determine your health and safety regulations and last breaker especially to suit your needs. The selective series for more control The heavy-duty version Device versions with an added Doepke has developed a HD „S“ in the name are suitable for („heavy-duty“), corrosion-resistant providing selective protection in version of breakers for use in adverse Schaltgeräte GmbH systems with main and sub-distri- conditions where corrosive gasses at Stellmacherstraße 11 D-26506 Norden, Germany Postfach 10 01 68 D-26491 Norden, Germany Phone +49 4931 1806-0 Fax +49 4931 1806-101 E-mail:info@doepke.de www.doepke.de bution units. A targeted layout of significant concentration levels must immediate conventional breakers be taken into account. or immediate AC-DC sensitive In principle all Doepke residual current breakers can be arranged, allowing circuit breakers are available in an for graduated system protection. HD version as well, type A and type B. Doepke Art.-Nr. 5900122 V 07/2011 © Doepke Schaltgeräte GmbH Subject to technical modifications. Mo r e v e r s io n s a v a ila b le