MSFD-GB-30C2-A Nov 2014 CERTIFIED air performance CERTAIRE TECHNICAL SERVICES,LTD. LISTED , During the products warranty period. /30 o or 350 F o (177 C ) electric actuator shall be installed by the damper manufacturer at the time of damper fabrication. Damper and actuator shall be supplied as a single entity which meets all applicable UL 555S standards for the both dampers and actuator. Each damper shall be rated for leakage and airflow in either direction through the damper. Damper and actuator assembly shall be factory cycled at least 15 times to assure operation. /30 S-Stainless Steel Construction 20 Series 1.1/2 Hrs; 30 Series 3Hrs MFD-GB-20A/R MFD-GB-30A/R; MFD-GB-31A/R; MFD GB-D-20/30A/R MFD-SB-20/30 A; MFD-SB-D-20/30 A /30 meet /SB 0/30A Material BETEC CAD. Model Damper Operation Frame Blade Standard Optional Honeywell / Belimo / Siemens (UL- Listed) Actuator Sleeves : Sleeves for single section damper are either factory installed or installed in field. Sleeves for multiple assembly damper is factory installed. Sleeve thickness as per NFPA table 3-4.6.3. 5 - Visual MFD-GB-20/30/31 A GI GI FC FO MFD-GSB-20/30 A GI SS FC FO MFD-SGB-20/30 A SS GI FC FO MFD-SB-20/30 A SS SS FC FO MFD-GB-D-20/30 A GI GI FC FO MFD-GSB-D-20/30 A GI SS FC FO MFD-SGB-D-20/30 A SS GI FC FO MFD-SB-D-20/30 A SS SS FC FO Acuator Location Standard Left side Optional Inside or Right side Operating Voltage Standard 230 V Optional 120 V / 24 V Actuator Location standard : Left Side From rear view (Jack Shaft view) Note : FC : Fail Close, In event of Fire FO : Fail Open, In event of Fire /30 MFD-GB-20A; MFD-GB-30A; MFD-GB-31A Motorized Fire Damper Module Size ( W x H ) Actuator Options Single 36" x 36" Honeywell 9Nm Single 24" x 48" Single 48" x48" Honeywell 9Nm Seimens 16Nm Honeywell 20Nm Belimo 7.9Nm Seimens 16Nm Honeywell 20Nm Honeywell 9Nm Multiple 144" x96" Seimens 16Nm Honeywell 20Nm Belimo 7.9Nm Size Limitations Module Single Single Single Multiple Size Width x Height Max X Max. 24” x 48” Max X Max. 36” x 36” Max X Max. 48” x 48” Max X Max. 144” x 96” Mounting Position H V/H V/H V/H 6 With Melting Fuse /30 G-Galvanized Steel Construction 1-3V Single Skin Blades; A-Parallel Fire Rating : B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. Static; Model:MFD-GB-F-20/30 A/R MFD-SB-F-20/30A/R MFD GBF-20/30 Series is a high performance UL 555 Classified with 3hr. rating fire damper, to ensure lowest resistance to airflow in HVAC systems. It may be installed vertically or horizontally (with blades running horizontally) and is rated for airflow and leakage in either direction. UL-555 Fire Ratings Fire Rating : 1.1/2 Hrs or 3 Hrs Operational Rating: Actual ratings are size dependent Max. Velocity : up to 2000fpm ( 10.2 M/S) Max Pressure : 4 Inches water gauge ( 1000 Pa) Temperature : 250°F (121°C) *Fusible Temperature : 165°F (74°C) *Operate Voltages: 24V Ac 120V Ac 230V Ac Standard Construction Frame : 16 g(1.5mm) 5"x1 "(125x25mm) Frame (Hat shaped) is made of Galvanized sheet steel. Corners spot/welded joints and are protected by antirust zinc rich primer coating. A low profile head frame is used for uneven heights to maximize free area and performance. Blades : 16 gauge (1.5mm) 3-V type is made of Galvanized Steel. Jamb Seals : Stainless steel jamb seal. Linkages : Mechanical linkages concealed in Frame. Bushes : Bushes :Fire resistant Brass-Bronze bushes Jack Shaft : Ø1/2" (12mm) Galvanized steel round rod. Blade Stop : 18 gauge (1.2mm) galvanized steel angle Drive Shaft : 1/2"x1/2" Square shaft Spring : M.S Spring ( 30lb) TRD : 165°F (72°C)TRD (36TXVE16) (UL - Listed) Fusible Link: 165°F (72°C) (UL Listed) Actuator : Honeywell / Belimo / Siemens (UL - Listed) Actuator Sleeves : Sleeves for single section damper are either factory installed or installed in field . Sleeves for multiple assembly damper is factory installed. Sleeve thickness as per NFPA table 3-4.6.3. MFD-GB-F-30A Model : MFD- GBF/SBF-20/30A UL 555 Damper shall meet the required standards of SMACNA - Sheet Metal and Air Conditioning Contractors National Association NFPA - National Fire Protection Association standards90A, 92A, 92B, 101 & 105. IBC - International Building Codes. BOCA - Building Officials & Code Administrators. ICBO - International Code Building Officials UL - Underwriters Laboratories (UL) certified Material BETEC CAD. Model Damper Operation Frame Blade Standard Optional GI GI FC FO MFD-GSB-F-20/30 A GI SS FC FO MFD-SGB-F-20/30 A SS GI FC FO MFD-SB-F-20/30 A SS SS FC FO MFD-GB-F-20/30 A Acuator Location Standard Left side Optional Inside or Right side Operating Voltage Standard 230 V Optional 120 V / 24 V Actuator Location standard : Left Side from rear view (Jack shaft view) Note : FC : Fail Close, In event of Fire FO : Fail Open, In event of Fire Optional Fittings: Retaining Angles : Minimum 1-1/2"X1-1/2" x16g [40x40x1.5mm] Blade Seals : Not required for Motorized Fire Dampers. (Silicon rubber blade tip seals are Optional). Limit Switches : For BMS open, close indication Indicator : Externally mounted open - close Visual Indicator Note : * Standard Fusible link temperature is 165°F (74°C) above 165°F (74°C) available upon customer request. 7 With Melting Fuse /30 G-Galvanized Steel Construction 1-3V Single Skin Blades; A-Parallel Fire Rating : B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. Static; Model:MFD-GB-F-20/30A : MFD-SB-F-20/30A Fusible link material rated 165°F( 74°C) High tension spring closed during fire Size Limitations Module Single Single Size Width x Height Min X Min. 4” x 4” Max X Max. 36” x 36” Mounting Position H H 8 MSD-GB-20C2-A MSD-GBD-20C2-A Model: MSD-GB-20C2-A UL 555S Material BETEC CAD. Model - Listed : Sleeves for single section damper are either factory installed or installed in field . Sleeves for multiple assembly damper is factory installed. Sleeve thickness as per NFPA table 3-4.6.3. Sleeves Frame Blade Standard Optional MSD - GB-20C2-A GI GI FC FO MSD - GSB-20C2-A GI SS FC FO MSD - SGB-20C2-A SS GI FC FO MSD - SB-20C2-A SS SS FC FO MSD - GBD-20C2-A GI GI FC FO Acuator Location 5 Standard Left side Externally mounted open - close Visual indicator Damper Operation Optional Inside or Right side Operating Voltage Standard 230 V Optional 120 V / 24 V Actuator Location standard : Left Side From rear view (Jack shaft view) Note : FC : Fail Close, In event of Fire FO : Fail Open, In event of Fire 9 MSD-GB-20C2-A; MSD-GBD-20C2-A Motorized Smoke Damper (Optional) (Optional) (Optional) 10 /30 Fire Rating: B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. MSFD-GB-20C2-A MSFD-GB-30C2-A 20/30 Leakage Rating : Class - II MSFD-GB-20/30C2-A UL 555/555S Material BETEC CAD. Model Damper Operation Frame Blade Standard Optional MSFD-GB-20/30C2-A GI GI FC FO MSFD-GSB-20/30C2-A GI SS FC FO MSFD-SGB-20/30C2-A SS GI FC FO MSFD-SB-20/30C2-A SS SS FC FO Acuator Location Standard Left side Listed Sleeves : Sleeves for single section damper are either factory installed or installed in field. Sleeves for multiple assembly damper is factory installed. Sleeve thickness as per NFPA table 3-4.6.3. 5 - visual Indicator Optional Inside or Right side Operating Voltage Standard 230 V Optional 120 V / 24 V Actuator Location standard : Left Side From rear view (Jack shaft view) Note : FC : Fail Close, In event of Fire FO : Fail Open, In event of Fire 11 /30 B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. MSFD-GB-20C2-A;MSFD-GB-30C2-A; MSFD-SB-20C2-A;MSFD-SB-30C2-A MOTORIZED FIRE SMOKE DAMPER 12 D MSFD-GBD-20C2-A Leakage Rating : Class-II MSFD-GBD-20C2 Material BETEC CAD. Model Damper Operation Frame Blade Standard Optional MSFD GBD-20C2- A 0 GI GI Acuator Location Standard Left side S Optional Inside or Right side FC FO Operating Voltage Standard 230 V Optional 120 V / 24 V Actuator Location standard : Left Side From rear view Note : FC : Fail Close, In event of Fire FO : Fail Open, In event of Fire ( Sleeves - Listed) : Sleeves for single section damper are either factory installed or installed in field. Sleeves for multiple assembly damper is factory installed. Sleeve thickness as per NFPA table 3-4.6.3. Retaining Angles : Minimum 1-1/2"X1-1/2" x16g [40x40x1.5mm] Limit Switches : For BMS open, close indication Indicator : Externally mounted open - close visual Indicator 13 /30 MSFD-GBD-20C2-A MOTORIZED FIRE SMOKE DAMPER 14 /30 B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. / Motorized Fire / Smoke Damper Side View Honeywell / Siemens / Belimo Note : 1. Non standard intermediate sizes as a Single Module Damper also vailable on request. 2. For Sizes longe than mentioned in the table are available as Multiple modul Damper with the combination sizes given in the table. 3. Sleeve thickness as per NFPA 90A ( Table 3-4.6.3) / UL 555 Standards based on the Damper width or height for break away joints for Duct - Sleeve joints. 4. For Duct - Recommended installation Drawings supplied with Damper Unit. 5. Retaining Angles - Contractors’s Scope Rear View 15 Single / Multiple Module Damper Constructions /30 UL 555 / UL 555S - Rated Damper constructions 1 2 3 4 1. Single Module Damper Construction 24” x 48” - Static / Dynamic Rated. 5 2. Multiple Module Damper Construction Operated with Single Actuator. 48” x 48” - Static / Dynamic Rated. 3. Single Module Damper Construction 36” x 36” - Static / Dynamic Rated. 4. Multiple Module Damper Construction Operated with Multiple Actuator. 72” x 36” - Static / Dynamic Rated. 5. Multiple Module Damper Construction Operated with Multiple Actuator. 72” x 72” - Static / Dynamic Rated. /30 6 6. Multiple Module Damper Construction Operated with Multiple Actuator. 144” x 96” - Static Rated. The above figures show maximum damper section size and assembly configuration for multiple section dampers. Type 1 – Damper Construction Damper Sleeve and the retaining angles are in the scope of site contractor. And strictly should be as recommended by ‘UL 555 / NFPA 90A / Damper Manufacturer / Consultant. Type 2 – Damper Construction The retaining angles are in the scope of site contractor. And strictly should be as recommended by ‘UL 555 / NFPA 90A / Damper Manufacturer / Consultant. Manufacturers Standard Type 3 – Damper Construction Recommended by ‘UL 555 / NFPA 90A / Damper Manufacturer – BETEC CAD. 18 /30 - 19 Motorized Fire / Smoke Damper With Honeywell Dual Auxiliary Switch /30 B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. Motorized Fire / Smoke Damper With Honeywell Dual Auxiliary Switch 20 Actuators Details /30 B-20 Series 1.1/2Hrs; B-30 Series 3Hrs. MS4209F/MS 4109F MS4309F/MS 4109F MS4709F/MS 4609F MS4809F/MS 4609F MS8209F/MS 8109F MS8309F/MS 8109F Module Size ( W x H ) Actuator Options Single 36" x 36" Honeywell 9Nm Honeywell 9Nm Single 24" x 48" Size Limitation Module Size Width x Height Position Max X Max 36" x 36" V/H Max X Max 24" x 48" V/H Max X Max 48" x 48" V/H Max X Max 144" x 96" V/H Seimens 16Nm Honeywell 20Nm Belimo 7.9Nm Single 48" x48" Seimens 16Nm Single Honeywell 20Nm Honeywell 9Nm Multiple 144" x96" Seimens 16Nm Honeywell 20Nm Belimo 7.9Nm Multiple 21 /30 22 /30 23 /30 24 /30 25 /30 DISCLAIMER , During the products warranty period. 26 /30