Time Current Curves TD012038EN Effective April 2014 Series C RD-Frame 800-2500A, 240-600V Contents DescriptionPage Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Digitrip RMS 510/610/810 Electronic Trip Unit types RD, CRD, RDC, CRDC Typical Instantaneous Time-Phase Current Characteristic Curve Based on In . . . . . . . . . . . . SC-5626-93 . . . . . . . . . 4 Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In . . . . SC-5627-93 . . . . . . . . . 5 Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In . . . . . . . . . . SC-5628-93 . . . . . . . . 6 Digitrip OPTIM Electronic Trip Unit with 1600/2000A frame Long Delay I2T, Short Delay I2T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6336-96 . . . . . . . . . 7 Long Delay I2T, Short Delay Flat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6337-96 . . . . . . . . 8 Long Delay I4T, Short Delay Flat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6338-96 . . . . . . . . . 9 Instantaneous and Override, 1600 Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6342-96 . . . . . . . . 10 Instantaneous and Override, 2000 Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6343-96 . . . . . . . . 11 Ground Fault or Ground Fault Alarm Only, 1600 Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6345-96 . . . . . . . . 12 Ground Fault or Ground Fault Alarm Only, 2000 Amperes . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6346-96 . . . . . . . . 13 Digitrip OPTIM Electronic Trip Unit with 2500A frame Long Delay I2T, Short Delay I2T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6339-96 . . . . . . . . Long Delay I2T, Short Delay Flat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6340-96 . . . . . . . Long Delay I4T, Short Delay Flat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6341-96 . . . . . . . . Instanteneous and Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6344-96 . . . . . . . . Ground Fault or Ground Fault Alarm Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SC-6347-96 . . . . . . . . 14 15 16 17 18 Note: Time/Current characteristic curves for Series C R-frame circuit breakers--voltages shown in curve headings are maximum at which the breaker may be applied. Interrupting capacity of inidvidual breaker is tabulated on each curve. Note: The following curves are UL489 Listed for use in North America. The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history. Time Current Curves are engineering reference documents for application and coordination purposes only. For field testing molded case circuit breakers, refer to NEMA AB 4 guidelines. Time Current Curves TD012038EN Series C R-Frame Effective April 2014 Notee: Unless noted below, all curves remain unchanged from their prior revision . Revision 2 Curve Number eaton www.eaton.com Page Date Time Current Curves TD012038EN Series C R-Frame Effective April 2014 Catalog Number Selection This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers or trip units. Table 1. Circuit Breaker/Frame RD 3 16 T53 W Circuit Breaker/ Frame Type RD RDC CRD 2 CRDC 2 Number of Poles 3 = Three-pole 4 = Four-pole Circuit Breaker/Frame Ampere Rating 16 = 1600 amperes 20 = 2000 amperes 25 = 2500 amperes Trip Type T53 T65 T86 T96 T106 T107 1 = Digitrip RMS 510 LS = Digitrip RMS 610 LSG = Digitrip RMS 810 LSIG = Digitrip RMS 910 LSIG = Digitrip OPTIM 1050 LSIG = Digitrip OPTIM 1050 LSIA Suffix W P R K = Without terminals = 100% protected neutral pole = Ground fault remote (310 only) = Molded case switch Notes 1 For complete list of available trip types, refer to Pages V4-T2-233 to V4-T2-242. 2 No Four0pole for CRD and CRDC. eaton www.eaton.com 3 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical Instantaneous Time-Phase Current Characteristic Curve Based on In I M P O R T A N T Series C R-Frame Circuit Breakers with TRIP UNITS ARE NOT AVAILABLE WITH ONLY INSTANTANEOUS PROTECTION. THIS CURVE MUST BE USED in conjunction WITH Curve No. SC-5627-93 for LONG DELAY (and if applicable SHORT DELAY) PROTECTION to obtain the complete time-current characteristic. DIGITRIP RMS 510/610/810 Trip Units Typical Instantaneous Time-Phase Current Characteristic Curve (I) Available Rating Plugs Marked 50/60 Hz Maximum Ampere Rating CURRENT IN MULTIPLES OF PLUG RATING I n 1000 900 800 700 600 500 .05 .07 .2 .1 .3 .4 .5 .7 1 2 3 4 5 7 20 10 30 400 300 1600 1600 1600 1600 1600 40 50 2000 2000 2000 2000 2000 2500 7 2500 7 2500 7 70 Ampere Rating (In) Frequency 5 Hz 1600 1250 6 1200 1000 800 2000 1600 1250 6 1200 1000 2500 2000 1600 50/60 50 50/60 50/60 50/60 50/60 50/60 50 50/60 50/60 50/60 50/60 50/60 Catalog Number RP6R16A160 RP6R16A125 RP6R16A120 RP6R16A100 RP6R16A080 1000 RP6R20A200 900 RP6R20A160 800 700 RP6R20A125 600 RP6R20A120 500 RP6R20A100 400 RP6R25A250 RP6R25A200 300 RP6R25A160 200 200 Interrupting Rating 100 90 80 70 60 50 Breaker Type RD, CRD RDC, CRDC 40 30 Breaker Type 20 RD, CRD RDC, CRDC 7 M1 M2 3 65 100 50 65 70 60 50 4050/60 Hz IEC 60947-2 rms Sym. kA, 220-240V 380-415V 30500V 125 200 65 100 20 1 10 9 8 7 6 5 4 125 200 2 Tolerances 8 10 9 8 7 6 5 INST Range = 90% to 110% of setting 4 3 Notes: 2 50 65 Utilization Category A Ics = 0.5 Icu Uimp = 8kV TIME IN SECONDS TIME IN SECONDS 9 M2 UL/CSA rms Sym. kA, 50/60 Hz 100 240V 480V 600V90 80 2 1For 2000A Rating Plug. 2For 2500A Rating Plug. 1 .9 .8 .7 .6 .5 .4 .3 .2 3 2 Available Instantaneous Settings 2, 2.5, 3, 4, 5, 6, M1 or M2 x In 3For 800-1600A Rating Plugs. 5 4 2.5 1 6 8 M1 Values for M1 and M2 as marked on Rating Plug Plug Rating (I n ) 800-1600 A 2000 A 2500 A 1 .9 .8 4The end of the curve is determined by the interrupting rating of the circuit breaker. .7 See above tabulation. .6 3 .5 5The Rating Plug is for 50 and 60 Hz applications. .4 6Not UL/CSA listed. M1 M2 8 x In 8 x In 7 x In 10 x In 9 x In 7 x In .3 7 For Types RD and RDC only. .2 10 M2 8 Curves apply from –20°C to +55°C ambient. Temperatures above 95°C cause automatic trip. For possible ampere derating for ambient above 40°C, refer to Eaton. 3 .1 .09 .08 .07 .06 .05 .1 .09 .08 .07 .06 .05 .04 .04 .03 Application Determines End of Curve .02 .01 .05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10 20 30 40 50 70 .03 4 .02 .01 CURRENT IN MULTIPLES OF PLUG RATING I n Figure 1. Typical Instantaneous Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5626-93, October 1997 4 eaton www.eaton.com Time Current Curves TD012038EN Series C R-Frame Effective April 2014 Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on Ir Series C R-Frame Circuit Breakers with DIGITRIP RMS 510/610/810 Trip Units Typical Long Delay and Short Delay Time-Phase Current Characteristic Curve (LS) Available Rating Plugs Marked 50/60 Hz Maximum Ampere Rating 1000 900 800 700 600 500 .05 .07 CURRENT IN MULTIPLES OF LONG DELAY SETTINGS I r .4 .5 .7 1 2 4 3 5 6 8 10 .2 .1 1600 1600 1600 1600 1600 2000 2000 2000 2000 2000 30 2500 7 2500 7 2500 7 20 .3 Available Long Delay (Ir) Settings .5, .6, .7, .8, .85, .9, .95 or 1 x In = Ir Ampere Rating (In) Frequency 5 Hz Catalog Number 1600 1250 6 1200 1000 800 2000 1600 1250 6 1200 1000 2500 2000 1600 50/60 50 50/60 50/60 50/60 50/60 50/60 50 50/60 50/60 50/60 50/60 50/60 RP6R16A160 RP6R16A125 RP6R16A120 RP6R16A100 RP6R16A080 RP6R20A200 RP6R20A160 RP6R20A125 RP6R20A120 RP6R20A100 RP6R25A250 1000 RP6R25A200 900 800 RP6R25A160 700 600 500 Interrupting Rating 400 300 Maximum Total Clearing Time 200 Breaker Type RD, CRD RDC, CRDC 100 90 80 70 60 50 400 UL/CSA rms Sym. kA, 50/60300 Hz 240V 480V 600V 125 200 65 100 50 65 200 IEC 60947-2 rms Sym. kA, 50/60 Hz 100 220-240V 380-415V 500V 90 Breaker Type RD, CRD RDC, CRDC 125 200 80 65 100 50 70 65 60 Utilization Category A 50 Ics = 0.5 Icu 40 Uimp = 8kV 40 30 30 Tolerances 8 Minimum Total Clearing Time 24 10 9 8 7 6 5 7 8 S2 4 6 4 2.5 3 Available Long Delay Time Settings 1 Shown @ 6 x Ir 2, 4, 7, 10, 12, 15, 20, 24 10 9 8 7 1Long Time Memory function automatically shortens long time delay as overload 6 2With zone interlocking on short delay utilized and no5 restraining signal, the Notes: 2 2 2 3 1 .9 .8 .7 .6 .5 2.5 .5* .4 .3 .3* 5 Available Short Delay Settings 2, 2.5, 3, 4, 5, 6, S1(7) or S2(8) x Ir 6 4 2 7 S1 .3 2 Available I2t Shape Short Delay Time Settings Indicated by * .1 .09 .08 .07 .06 .05 SDM SDM .1* .1 2 .8 .7 2 .4 2 .2 2 Application Determines End of Curve 2 .6 .5 .5 .5 .5 .4 .3 2 .2 .3 .2 3 .1 Available Flat .4 Response .3 Short Delay Time Settings .1, .2, .3, .4, or .5.2 .4 .2 .1 .1 .09 .08 .07 Fixed .06 Instantaneous.054 Override .04 .04 .03 .03 .02 .02 .01 .05 conditions recur. minimum time band SDM applies – regardless of setting. 4 rating of the circuit 3The end of the curve is determined by the interrupting breaker. See above tabulation. 3 4For high fault current levels a fixed instantaneous override is provided at 17,500A (Tolerance ± 15%). 5 The Rating Plug is for 50 and 60 Hz applications. 2 6Not UL/CSA listed. 7 For Types RD and RDC only. 8 Curves apply from –20°C to +55°C ambient. Temperatures above 95°C cause automatic 1 trip. For possible ampere derating for ambient above.9 40°C, refer to Eaton. 4 2 20 LDS Range = 150% to 130% of Setting. LDT Range = 67% to 100% of Setting, at 6 x Ir . SDS Range = 90% to 110% of Setting. TIME IN SECONDS TIME IN SECONDS 20 .07 .1 2 3 .2 4 .35 .4 7 .5 1 0 .7 1 20 2 3 4 5 6 8 10 IMPORTANT 20 30 40 .01 10 20 30 40 CURRENT IN kA 50 .01 70 CURRENT IN MULTIPLES OF LONG DELAY SETTINGS I r Figure 2. Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5627-93, October 1997 eaton www.eaton.com 5 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 510/610/810 Trip Units. Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In Series C R-Frame Circuit Breakers with DIGITRIP RMS 510/610/810 Trip Units CURRENT IN MULTIPLES OF PLUG RATING I n .05 .07 .1 .3 .4 .5 .7 1 2 3 4 5 7 1 Typical Current2Characteristic Curve (G) .2 .4 .5 .3 Time-Ground .7 1 4 3 5 7 10 1000 900 800 700 600 500 Ground Fault Settings (Amperes) ➁➂➃ Code 600 500 A K 400 300 Available Ground Fault Settings (Typical) for Exact Values and Tolerances of Letter Codes, See Chart In plug ratings available 1000 900 800 700 .2 200 A➄ B➄ C➄ D➄ E F H K 800 200 240 280 320 400 480 600 800 1000 250 300 350 400 500 600 750 1000 1200 300 360 420 480 600 720 900 1200 400 1250 312 375 438 500 625 750 938 1200 300 1600 400 480 560 640 800 960 1200 1200 2000 500 600 700 800 1000 1200 1200 1200 2500 625 750 875 1000 1200 1200 1200 1200 200 Notes: 100 90 80 70 60 50 100 90 80 signal, the minimum time 1With zone interlocking on ground fault utilized and no restraining 70 band GDM applies – regardless of setting. 60 50 shown in chart. 2 Except as noted tolerances on current levels are ± 10% of values 40 40 3The rating plug is for 50 Hz and 60 Hz, applications. 30 30 4All tabulated values are based on the use of a residual sensing scheme with the same rated current sensor in all phase and neutral conductors. 20 20 10 9 8 7 6 5 10 9 8 7 6 5 4 4 3 3 TIME IN SECONDS TIME IN SECONDS 5For Testing Purposes Only: When using an external single phase current source to check low level ground fault current settings, it is advisable to use the Auxiliary Power Module (APM). See TEST PROCEDURES in Instruction Leaflet. D 2 2 B I t Shape for Ground Time Delay Settings Indicated by * 2 1 .9 .8 .7 .6 .5 1 .9 .8 .7 .6 .5 A .5 .4 .4 .3 .3 .2 .2 1 1 1 1 Available Ground Fault Time Delay Settings Flat Response GDM .1 .09 .08 .07 .06 .05 .1 .5* 1 .3* 1 .4 Available Ground Fault Time Delay Settings I2t Response .3 .2 GDM .1* 1 .1 .09 .08 .07 1 .06 .05 .04 .04 .03 .03 .02 .02 .01 .05 .07 .1 .2 .3 .4 .5 .7 1 2 3 4 5 7 1 .2 .3 .4 .5 .7 1 2 3 4 5 7 10 .01 CURRENT IN MULTIPLES OF PLUG RATING I n Figure 3. Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In - Curve Number SC-5628-93, October 1997 6 eaton www.eaton.com Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t 1 HOUR 40 50 60 70 80 90 100 30 20 5 6 7 8 9 10 3 2 0.6 0.7 0.8 0.9 1 10,000 0.5 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Available Long Delay Pickup Settings (Ir ) 0.5 to 1 x I n = I r in 0.01 increments 5,000 Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 1600/2000A Digitrip Optim Trip Units 3,000 Response: LONG DELAY I2t, SHORT DELAY I2t 2,000 Available Rating Plugs 1,000 Maximum Total Clearing Time 500 300 Rating Plug Catalog Number Long Delay Pickup Range 0.4 to 1 x In Amperes Short Delay Pickup Range 1.5 to 8 x Ir Amperes 1600 1600 1600 1600 1600 2000 2000 2000 2000 2000 1600 1250 1200 1000 800 2000 1600 1250 1200 1000 ORPL16A160 ORPL16A125 ORPL16A120 ORPL16A100 ORPL16A080 ORPL20A200 ORPL20A160 ORPL20A125 ORPL20A120 ORPL20A100 640 -1600 500 -1250 480 -1200 400 -1000 320 - 800 800 -2000 640 -1600 500 -1250 480 -1200 400 -1000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 480 - 6400 1200 - 16000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 Interrupting Rating 100 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 50 30 20 Minimum Total Clearing Time 24 RD, CRD RDC, CRDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 7 5 4 Available Long Delay Time Settings Shown @ 6 x I r 2-24 seconds +0 ⁄-30% in 0.1 second increments 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV RD, CRD RDC, CRDC 10 Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Notes: 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 3 2 2 Available Short Delay Pickup Settings 1.5 to 8 x Ir ±5% in 0.1 increments 1 .5 1 5.This curve is shown as a multiple of the Long Delay Pickup Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, or a Remote PC (IMPACC System). .5 6.The Long Delay Pickup Point (indicated by a flashing LED on the product).5 nominally occurs above 115% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. .3 7.For additional curve tolerances contact Eaton. .3 NDS .3 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 8. Total clearing times shown include the response times of the trip unit, the breaker opening, .2 and the quenching of the arcing current. .2 Application Determines End of Curve .1 .1 .1 Available I2t Slope Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .05 .05 6000 7000 8000 9000 10,000 4000 5000 3000 2000 500 600 700 800 900 1000 300 50 60 70 80 90 100 40 30 20 5 .01 6 7 8 9 10 .01 4 .02 3 .02 2 .03 0.5 0.6 0.7 0.8 0.9 1 .03 400 T IME IN S E C ONDS Ampere Rating (In) 200 1 MINUT E 200 Maximum Ampere Rating CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 4. Long Delay I2T, Short Delay I2T - Curve Number SC-6336-96, October 1997 eaton www.eaton.com 7 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat 50 60 70 80 90 100 40 30 20 5 6 7 8 9 10 3 2 0.5 0.6 0.7 0.8 0.9 1 10,000 Available Long Delay (Ir ) Settings 0.5 to 1 x I n = I r in 0.01 increments 5,000 Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 1600/2000A Digitrip Optim Trip Units 3,000 Response: LONG DELAY I2t, SHORT DELAY FLAT 2,000 Available Rating Plugs 1,000 Maximum Total Clearing Time 500 300 1 MINUT E 200 Ampere Rating (In) Rating Plug Catalog Number Long Delay Pickup Range 0.4 to 1 x In Amperes Short Delay Pickup Range 1.5 to 8 x Ir Amperes 1600 1600 1600 1600 1600 2000 2000 2000 2000 2000 1600 1250 1200 1000 800 2000 1600 1250 1200 1000 ORPL16A160 ORPL16A125 ORPL16A120 ORPL16A100 ORPL16A080 ORPL20A200 ORPL20A160 ORPL20A125 ORPL20A120 ORPL20A100 640 -1600 500 -1250 480 -1200 400 -1000 320 - 800 800 -2000 640 -1600 500 -1250 480 -1200 400 -1000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 480 - 6400 1200 - 16000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 Interrupting Rating 100 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 50 30 20 Minimum Total Clearing Time 24 RD, CRD RDC, CRDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V Available Long Delay Time Settings Shown @ 6 x I r 2-24 seconds +0 ⁄-30% in 0.1 second increments 7 5 4 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV RD, CRD RDC, CRDC 10 T IME IN S E C ONDS Maximum Ampere Rating Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Notes: 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 3 2 2 Available Short Delay Pickup Settings 1.5 to 8 x Ir ±5% in 0.1 increments 1 .5 .3 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 1 5.This curve is shown as a multiple of the Long Delay Pickup Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, or a Remote PC (IMPACC System). .5 6.The Long Delay Pickup Point (indicated by a flashing LED on the product) nominally occurs .5 above 115% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. .3 7.For additional curve tolerances contact Eaton. .3 8. Total clearing times shown include the response times of the trip unit, the breaker opening, .2 and the quenching of the arcing current. .2 Application Determines End of Curve .1 .1 .1 .05 .05 Available Flat Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .03 .03 CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 5. Long Delay I2T, Short Delay Flat - Curve Number SC-6337-96, October 1997 8 eaton www.eaton.com 4000 5000 3000 2000 500 600 700 800 900 1000 300 400 200 60 70 80 90 100 50 40 30 20 5 6 7 8 9 10 4 .01 3 .01 2 .02 0.5 0.6 0.7 0.8 0.9 1 .02 6000 7000 8000 9000 10,000 1 HOUR 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 1600/2000A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat 40 50 60 70 80 90 100 30 20 5 6 7 8 9 10 3 2 0.6 0.7 0.8 0.9 1 0.5 10,000 Available Long Delay Pickup Settings (Ir) 0.5 to 1 x I n = I r in 0.01 increments 5,000 Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 1600/2000A Digitrip Optim Trip Units 3,000 Response: LONG DELAY I2t, SHORT DELAY FLAT 2,000 Maximum Total Clearing Time Available Rating Plugs 1,000 500 300 Ampere Rating (In) Rating Plug Catalog Number Long Delay Pickup Range 0.4 to 1 x In Amperes Short Delay Pickup Range 1.5 to 8 x Ir Amperes 1600 1600 1600 1600 1600 2000 2000 2000 2000 2000 1600 1250 1200 1000 800 2000 1600 1250 1200 1000 ORPL16A160 ORPL16A125 ORPL16A120 ORPL16A100 ORPL16A080 ORPL20A200 ORPL20A160 ORPL20A125 ORPL20A120 ORPL20A100 640 -1600 500 -1250 480 -1200 400 -1000 320 - 800 800 -2000 640 -1600 500 -1250 480 -1200 400 -1000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 480 - 6400 1200 - 16000 960 - 12800 750 - 10000 720 - 9600 600 - 8000 Interrupting Rating 100 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 50 30 RD, CRD RDC, CRDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V RD, CRD RDC, CRDC T IME IN S E C ONDS 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV 20 10 65 100 Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Notes: 5 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 5 3 2 1 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Available Long Delay Time Settings Shown @ 6 x I r 1-5 seconds +10 ⁄-40% in 0.1 second increments Available Short Delay Pickup Settings 1.5 to 8 x Ir ±5% in 0.1 increments 1 .5 .5 .3 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 1 5.This curve is shown as a multiple of the Long Delay Pickup Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, or a Remote PC (IMPACC System). 6.The Long Delay Pickup Point (indicated by a flashing LED on the product).5nominally occurs above 115% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. .3 7.For additional curve tolerances contact Eaton. T IME IN S E C ONDS 1 MINUT E 200 Minimum Total Clearing Time Maximum Ampere Rating 8. Total clearing times shown include the response times of the trip unit, the .2 breaker opening, and the quenching of the arcing current. .2 Application Determines End of Curve .1 .1 .1 .05 .05 Available Flat Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .03 .03 4000 5000 3000 2000 500 600 700 800 900 1000 300 400 200 50 60 70 80 90 100 40 30 20 5 6 7 8 9 10 4 .01 3 .01 2 .02 0.5 0.6 0.7 0.8 0.9 1 .02 6000 7000 8000 9000 10,000 1 HOUR 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 6. Long Delay I4T, Short Delay Flat - Curve Number SC-6338-96, October 1997 eaton www.eaton.com 9 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Instantaneous and Override 40 50 60 70 80 90 100 30 20 5 6 7 8 9 10 4 3 10,000 2 1 2 HOURS CURRENT IN MULTIPLES OF PLUG RATING I n Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 1600A Digitrip Optim Trip Units Response: INSTANTANEOUS AND OVERRIDE 1 HOUR 5,000 Available Rating Plugs 3,000 2,000 1,000 Ampere Rating (In) Rating Plug Catalog Number Instantaneous Pickup Range 2 to 10 x In Amperes Override Amperes 1600 1600 1600 1600 1600 1600 1250 1200 1000 800 ORPL16A160 ORPL16A125 ORPL16A120 ORPL16A100 ORPL16A080 3200 -16000 2500 -12500 2400 -12000 2000 -10000 1600 - 8000 14875 -20125 14875 -20125 14875 -20125 14875 -20125 14875 -20125 Interrupting Rating 500 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 300 200 100 1 MINUTE Maximum Ampere Rating RD, CRD RDC, CRDC 125 200 65 100 50 65 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV RD, CRD RDC, CRDC Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Notes: 50 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 30 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 20 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 5 5.The instantaneous settings have conventional 100%, +/- 10% as the pickup points. 6.For additional curve tolerances contact Eaton. 3 7. Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. 2 1 2 1 Available Instantaneous Pickup Settings 2 to 10 x In ± 10% In 0.1 Increments 10 .5 .3 Available Flat Response Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .2 .2 .1 Application Determines End of Curve .05 .5 .3 .3 .1 .1 .05 AMPERES Figure 7. Instantaneous and Override, 1600 Amperes - Curve Number SC-6342-96, October 1997 eaton www.eaton.com 50,000 60,000 70,000 80,000 40,000 30,000 5000 6000 7000 8000 9000 10,000 4000 3000 2000 1000 60 70 80 90 100 50 40 30 20 6 7 8 9 10 .01 5 .01 3 .02 4 .02 2 .03 1 .03 CURRENT IN MULTIPLES OF PLUG RATING I n 10 Fixed Instantaneous Override .5 20,000 T IME IN S E C ONDS 10 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Instantaneous and Override 40 50 60 70 80 90 100 30 20 6 7 8 9 10 4 5 3 10,000 2 1 2 HOURS CURRENT IN MULTIPLES OF PLUG RATING I n Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 2000A Digitrip Optim Trip Units 1 HOUR 5,000 Response: INSTANTANEOUS AND OVERRIDE Available Rating Plugs 3,000 2,000 1,000 Maximum Ampere Rating Ampere Rating (In) Rating Plug Catalog Number Instantaneous Pickup Range 2 to 8 x In Amperes Override Amperes 2000 2000 2000 2000 2000 2000 1600 1250 1200 1000 ORPL20A200 ORPL20A160 ORPL20A125 ORPL20A120 ORPL20A100 4000 -16000 3200 -12800 2500 -10000 2400 - 9600 2000 - 8000 14875 -20125 14875 -20125 14875 -20125 14875 -20125 14875 -20125 500 Interrupting Rating 300 Breaker Type 200 RD, CRD RDC, CRDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V 1 MINUTE 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV RD, CRD RDC, CRDC 50 65 100 Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Notes: 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 30 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 20 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 5 5.The instantaneous settings have conventional 100%, +/- 10% as the pickup points. 3 6.For additional curve tolerances contact Eaton. 2 7. Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. 1 8 2 1 Available Instantaneous Pickup Settings 2 to 8 x In ± 10% In 0.1 Increments .5 Fixed Instantaneous Override .5 .3 Available Flat Response Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .2 .2 .1 .1 .1 Application Determines End of Curve .05 .5 .3 .3 .05 CURRENT IN MULTIPLES OF PLUG RATING I n 50,000 60,000 70,000 80,000 40,000 30,000 5000 6000 7000 8000 9000 10,000 4000 3000 2000 1000 60 70 80 90 100 50 40 30 20 6 7 8 9 10 .01 5 .01 3 .02 4 .02 2 .03 1 .03 20,000 T IME IN S E C ONDS 10 AMPERES Figure 8. Instantaneous and Override, 2000 Amperes - Curve Number SC-6343-96, October 1997 eaton www.eaton.com 11 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 1600A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only Circuit Breaker Time/Current Curves (Ground Current) Series C R - Frame Circuit Breakers Equipped With 1600A Digitrip Optim Trip Units Response: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY Available Rating Plugs 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 10,000 .2 .1 2 HOURS CURRENT IN MULTIPLES OF RATING PLUG I n 1 HOUR 5,000 3,000 Maximum Ampere Rating Ampere Rating (In) Rating Plug Catalog Number Ground Fault Pickup Range Amperes 1600 1600 1600 1600 1600 1600 1250 1200 1000 800 ORPL16A160 ORPL16A125 ORPL16A120 ORPL16A100 ORPL16A080 400 -1200 312.5 -1200 300 -1200 250 -1000 200 - 800 Interrupting Rating 2,000 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type RD, CRD RDC, CRDC 125 200 500 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 300 RD, CRD RDC, CRDC 200 Notes: 1,000 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 1 MINUTE 100 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 50 30 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 20 5.Ground fault level is electronically limited to a maximum of 1200 Amperes. 6.The ground fault settings have conventional 100%, +/- 10% as the pickup points. T IME IN S E C ONDS 10 7. For additional curve tolerances contact Eaton. Available Ground Fault Pickup Settings ±10% in 0.1 increments 5 8. Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. 3 1.0 2 .5 1 1 .2 .5 .5 .3 .5 .5 Available Flat Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .3 .3 .3 .2 .2 .1 .1 .1 I2t Slope for Ground Fault Time Settings Availaible I2 t Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .05 .03 .1 Flat Shape for Ground Fault Time Settings .05 .03 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 .2 6 7 8 9 10 5 4 3 2 .6 .7 .8 .9 1 .5 .4 .01 .3 .01 .2 .02 .1 .02 CURRENT IN MULTIPLES OF RATING PLUG I n Figure 9. Ground Fault or Ground Fault Alarm Only, 1600 Amperes - Curve Number SC-6345-96, October 1997 12 eaton www.eaton.com Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2000A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only Circuit Breaker Time/Current Curves (Ground Current) Series C R - Frame Circuit Breakers Equipped With 2000A Digitrip Optim Trip Units Response: GROUND FAULT TRIP OR GROUND FAULT ALARM ONLY Available Rating Plugs 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 10,000 .2 .1 2 HOURS CURRENT IN MULTIPLES OF RATING PLUG I n 1 HOUR 5,000 3,000 Maximum Ampere Rating Ampere Rating (In) Rating Plug Catalog Number Ground Fault Pickup Range Amperes 2000 2000 2000 2000 2000 2000 1600 1250 1200 1000 ORPL20A200 ORPL20A160 ORPL20A125 ORPL20A120 ORPL20A100 500 -1200 400 -1200 312.5 -1200 300 -1200 250 -1000 Interrupting Rating 2,000 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 1,000 RD, CRD RDC, CRDC 125 200 500 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 300 RD, CRD RDC, CRDC 200 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV Notes: Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 1 MINUTE 100 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 50 30 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 20 5.Ground fault level is electronically limited to a maximum of 1200 Amperes. 6.The ground fault settings have conventional 100%, +/- 10% as the pickup points. T IME IN S E C ONDS 10 7.For additional curve tolerances contact Eaton. Available Ground Fault Pickup Settings ±10% in 0.1 increments 5 8.Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. 3 1.0 2 .5 1 1 .2 .5 .3 .5 .5 .5 Available Flat Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .3 .3 .3 .2 .2 .1 .1 .1 I2t Slope for Ground Fault Time Settings Availaible I2t Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .05 .03 .1 Flat Shape for Ground Fault Time Settings .05 .03 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 .2 6 7 8 9 10 5 4 3 2 .6 .7 .8 .9 1 .5 .4 .01 .3 .01 .2 .02 .1 .02 CURRENT IN MULTIPLES OF RATING PLUG I n Figure 10. Ground Fault or Ground Fault Alarm Only, 2000 Amperes - Curve Number SC-6346-96, October 1997 eaton www.eaton.com 13 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay I2t 1 HOUR 50 60 70 80 90 100 40 30 20 5 6 7 8 9 10 3 2 0.6 0.7 0.8 0.9 1 10,000 0.5 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Available Long Delay Pickup Settings (I r) 0.5 to 1 x In = Ir in 0.01 increments 5,000 Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 2500A Digitrip Optim Trip Units 3,000 Response: LONG DELAY I2t, SHORT DELAY I2t 2,000 Available Rating Plugs 1,000 Maximum Total Clearing Time 500 Maximum Ampere Rating Ampere Rating (In) Rating Plug Catalog Number 2500 2500 2500 2500 2000 1600 ORPL25A250 ORPL25A200 ORPL25A160 Long Delay Pickup Range 0.4 to 1 x In Amperes 1000 -2500 800 -2000 640 -1600 Short Delay Pickup Range 1.5 to 6.4 x Ir Amperes 1500 - 16000 1200 - 12800 960 - 10240 Interrupting Rating 300 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 24 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV Notes: Minimum Total Clearing Time Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A 1.For field testing primary injection methods, follow NEMA AB4 guidelines. 2.Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 7 5 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Available Long Delay Time Settings Shown @ 6 x I r 2-24 seconds +0 ⁄-30% in 0.1 second increments 10 T IME IN S E C ONDS 125 200 RD RDC 50 20 RD RDC 4 4.The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 5.This curve is shown as a multiple of the Long Delay Pick-up Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, or a Remote PC (IMPACC System). 3 2 2 Available Short Delay Pickup Settings 1.5 to 6.4 x Ir ±5% in 0.1 increments 1 .5 6.The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs above 115% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. 7.For additional curve tolerances contact Eaton. 1 8.Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. .5 .5 .3 .3 .3 .2 .2 Application Determines End of Curve .1 .1 .1 Available I2t Slope Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .05 .05 CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 11. Long Delay I2T, Short Delay I2T - Curve Number SC-6339-96, October 1997 14 eaton www.eaton.com 6000 7000 8000 9000 10,000 4000 5000 3000 2000 500 600 700 800 900 1000 300 400 200 50 60 70 80 90 100 40 30 20 5 .01 6 7 8 9 10 .01 4 .02 3 .02 2 .03 0.5 0.6 0.7 0.8 0.9 1 .03 T IME IN S E C ONDS 1 MINUT E 100 30 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 200 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I2t, Short Delay Flat 1 HOUR 40 50 60 70 80 90 100 30 20 5 6 7 8 9 10 3 2 0.5 10,000 0.6 0.7 0.8 0.9 1 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 2500A Digitrip Optim Trip Units Circuit Breaker Time/Current Curves (Phase Current) Response: LONG DELAY I 2 t, SHORT DELAY FLAT Series C R - Frame Circuit Breakers Available Long Delay Pickup Settings (Ir ) 0.5 to 1 x I n = Ir in 0.01 increments 5,000 Available Rating Plugs Equipped With 2500ARating Digitrip Optim Trip Units Maximum Ampere Plug Long Delay 3,000 Ampere Rating Catalog Pickup Range Amperes Available Rating Plugs ORPL25A250 2500 2500 2,000 Maximum Ampere Rating 1,000 2000 Ampere 1600 Rating (In) 2500 2500 2500 Maximum Total Clearing Time 500 1000 -2500 800 -2000 640 -1600 Amperes r 1500 - 16000 Long Delay 1200 - 12800 Pickup Range 960 - 10240 0.4 to 1 x In Amperes 1000 -2500 800 -2000 640 -1600 Short Delay Pickup Range 1.5 to 6.4 x Ir Amperes 1500 - 16000 1200 - 12800 960 - 10240 Interrupting Rating 200 100 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V RD RDC 125 200 65 100 50 65 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA) Breaker UL / CSA RDType RDC RD 50 Volts kA RDC Notes: 20 Plug Catalog Number n ORPL25A250 ORPL25A200 ORPL25A160 Breaker Type 30 ORPL25A200 Rating ORPL25A160 2500 2000 1600 300 1 MINUT E Short Delay Pickup Range FLAT Response: LONG DELAY I2t, SHORT Rating (I n) Number 0.4 DELAY to 1 x I 1.5 to 6.4 x I Minimum Total Clearing Time Icu Ics Icu 135 100 70 240 200 100 100 125 200 U IMP = 8kV Ics Icu Ics 25 600 13 35 50 18 Utilization65Category A 50 480 50 65 100 IEC 947-2 Volts 415 240 690 1.For field testing primary injection methods, follow NEMA AB4 guidelines. Rating I I I I I I 24 CU CS CU CU CS CS 135 70 25 RD kA 2. Calibration response in short delay 100 pickup 100 range is 50 the same for 1,13 2, or 3 poles in series. 200 35 RDC 100 50 18 U = 8kV Utilization Category A 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into IMP T IME IN S E C ONDS 10 7 5 4 Notes play if a current above the long delay pickup value exists for a time and then is cleared by the 1) For field testing primary injection methods, follow NEMA AB4-1991 publications. tripping of aindownstream device the circuit breaker itself. A subsequent overload will cause the 2) Calibration response short delay pickup range is the or same for 1, 2, or 3 poles in series. 3) There is a memory effect to that trip can act shorten thetime long delay. Thenormal. memory effect circuit breaker intoshorter than The amount of time reduction is inverse to the comes into play if a current above the long delay pickup value exists for a time and then amount timeof athat has elapsed since the previous overload. Approximately five minutes is is cleared by theof tripping downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. required between overloads to completely reset the memory. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4. end of the curve by isthe determined byof the interrupting rating of the circuit breaker. 4) TheThe end of the curve is determined interrupting rating the circuit breaker. SeeSee aboveabove tabulation. tabulation. 5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and SC-6347-96 (2500A) 6) This curvecurve is shownis as shown a multiple ofas theaLong Delay Pick-up Setting, (Ir). This I r settingPick-up is 5. This multiple of the Long Delay Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, in System). primary value amperes via a Breaker Interface Module, or OPTIMizer, or programmed a Remote PC (IMPACC 7) Theor Long Delay Pick-upPC Point(IMPACC (indicated by aSystem). flashing LED on the product) nominally occurs a Remote at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. 8) ForThe additional curve tolerances contact Cutler-Hammer. 6. Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs 9) Total clearing times shown include the response times of the trip unit, the breaker opening, above 115% ofarcing the current. Ir current, with a +/- 5% tolerance. The short delay settings have conventional and the extinction of the Available Long Delay Time Settings Shown @ 6 x I r 2-24 seconds +0 ⁄-30% in 0.1 second increments 3 2 2 100%, +/- 5% as the pickup points. Available Short Delay Pickup Settings 1.5 to 6.4 x Ir ±5% in 0.1 increments 1 .5 7.For additional curve tolerances contact Eaton. 1 8.Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. .5 .5 .3 .3 .3 .2 Application Determines End of Curve .1 .1 .1 .05 .05 Available Flat Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .03 .03 6000 7000 8000 9000 10,000 4000 5000 3000 2000 500 600 700 800 900 1000 300 400 200 50 60 70 80 90 100 40 30 20 5 6 7 8 9 10 .01 4 .01 3 .02 2 .02 0.5 0.6 0.7 0.8 0.9 1 T IME IN S E C ONDS .2 CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 12. Long Delay I2T, Short Delay Flat - Curve Number SC-6340-96, October 1997 eaton www.eaton.com 15 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Long Delay I4t, Short Delay Flat 1 HOUR 40 50 60 70 80 90 100 30 20 5 6 7 8 9 10 3 2 0.6 0.7 0.8 0.9 1 10,000 0.5 2 HOURS CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Equipped With 2500A Digitrip Optim Trip Units Circuit Breaker Time/Current Curves (Phase Current) Response: LONG DELAY I 4 t, SHORT DELAY FLAT Series C R - Frame Circuit Breakers Available Long Delay Pickup Settings (Ir ) 0.5 to 1 x I n = Ir in 0.01 increments 5,000 Available Rating Plugs Equipped With 2500A Rating Digitrip Optim Trip Units Short Delay Maximum Ampere Plug Long Delay 3,000 Ampere Rating Catalog Rating (I n) Number FLAT Response: LONG DELAY I4t, SHORT 0.4 DELAY to 1 x I 1.5 to 6.4 x I Pickup Range Amperes 2,000 Available Rating 2500 2500 Plugs Maximum Total Clearing Time 2000 1600 Ampere Maximum Ampere Rating 1,000 Plug Catalog Number Rating (In) 2500 2500 2500 ORPL25A250 ORPL25A200 ORPL25A160 Rating 2500 2000 1600 Pickup Range n 1000 -2500 800 -2000 640 -1600 Amperes r 1500 - 16000 Long Delay 1200 - 12800 960 - 10240 Pickup Range 0.4 to 1 x In Amperes ORPL25A250 ORPL25A200 ORPL25A160 1000 -2500 800 -2000 640 -1600 Short Delay Pickup Range 1.5 to 6.4 x Ir Amperes 1500 - 16000 1200 - 12800 960 - 10240 500 300 1 MINUT E 200 Interrupting Rating Minimum Total Clearing Time UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 100 RD RDC 125 200 65 100 50 65 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA) Breaker 50 Icu Ics Icu 135 100 70 240 200 100 100 125 200 U IMP = 8kV UL / CSA RD Type RDC RD Volts kA RDC Notes: IEC 947-2 Volts 30 Ics Icu Ics 25 600 13 35 50 18 Utilization65 Category A 50 480 50 65 100 415 240 690 1.For field testing primary injection methods, follow INEMA IAB4 guidelines. Rating I I I I CU CS 135 RD CU CU CS 70 CS 25 100 13 kA 2. Calibration response in short pickup 100 range is 50 the same 200 delay 100 35 for 1,182, or 3 poles in series. RDC 50 20 U IMP = 8kV Utilization Category A 3.There is a memory effect that can act to shorten the long delay. The memory effect comes into Notes play if a current above the long delay pickup value exists for a time and then is cleared by the 1) For field testing primary injection methods, follow NEMA AB4-1991 publications. tripping of aindownstream device or the circuit breaker itself. A subsequent overload will cause the 2) Calibration response short delay pickup range is the same for 1, 2, or 3 poles in series. 3) There is a memory effect that can act shorten thetime long delay. The normal. memory effect circuit breaker to trip intoshorter than The amount of time reduction is inverse to the comes into play if a current above the long delay pickup value exists for a time and then is cleared by theof tripping of athat downstream device or thesince circuit breaker itself. A amount time has elapsed the previous overload. Approximately five minutes is subsequent overload will cause the circuit breaker to trip in shorter time than normal. between to completely Therequired amount of time reduction isoverloads inverse to the amount of time that hasreset elapsedthe sincememory. the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4. of the curvebyisthe determined by thecircuit interrupting rating of the circuit breaker. 4) TheThe end ofend the curve is determined interrupting rating of the breaker. See above tabulation. See above tabulation. 5) For ground fault time / current curves see SC-6345-96 (1600A), SC-6346-96 (2000A), and SC-6347-96 (2500A) 6) ThisThis curve curve is shown is as ashown multiple ofas the a Long Delay Pick-up (Ir). This I r settingPick-up is 5. multiple of Setting, the Long Delay Setting, (Ir). This Ir setting is programmed in primary value amperes via a Breaker Interface Module, or OPTIMizer, inSystem). primary value amperes via a Breaker Interface Module, or OPTIMizer, or programmed a Remote PC (IMPACC 7) The Long Delay Pick-up Point (indicated by a flashing LED on the product) nominally occurs or a Remote PC (IMPACC System). at 116% of the Ir current, with a +/- 5% tolerance. The short delay settings have conventional 100%, +/- 5% as the pickup points. 8) For additional curve tolerances contact Cutler-Hammer. 6. The Long Pick-up Point times (indicated LED on the product) nominally occurs 9) Total clearing timesDelay shown include the response of the trip by unit, a theflashing breaker opening, andabove the extinction of the 115% ofarcing thecurrent. I current, with a +/- 5% tolerance. The short delay settings have conventional 5 Available Long Delay Time Settings Shown @ 6 x I r 1-5 seconds +10 ⁄-40% in 0.1 second increments 2 r 100%, +/- 5% as the pickup points. Available Short Delay Pickup Settings 1.5 to 6.4 x Ir ±5% in 0.1 increments 1 .5 7.For additional curve tolerances contact Eaton. 1 8.Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. .5 .5 .3 .3 .2 .2 Application Determines End of Curve .1 .1 .1 .05 .05 Available Flat Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .03 .03 CURRENT IN MULTIPLES OF LONG DELAY SETTING I r Figure 13. Long Delay I4T, Short Delay Flat - Curve Number SC-6341-96, October 1997 16 eaton www.eaton.com 4000 5000 3000 2000 500 600 700 800 900 1000 300 400 200 50 60 70 80 90 100 40 30 20 5 6 7 8 9 10 4 .01 3 .01 2 .02 0.5 0.6 0.7 0.8 0.9 1 .02 T IME IN S E C ONDS 3 6000 7000 8000 9000 10,000 T IME IN S E C ONDS 10 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Instantaneous and Override 50 60 70 80 90 100 30 40 20 5 6 7 8 9 10 3 4 10,000 2 1 2 HOURS CURRENT IN MULTIPLES OF PLUG RATING I n Circuit Breaker Time/Current Curves (Phase Current) Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers Series C With R - Frame Breakers Equipped 2500A Circuit Digitrip Optim Trip Units Response: With INSTANTANEOUS AND OVERRIDE Equipped 2500A Digitrip Optim Trip Units 1 HOUR 5,000 Available Rating PlugINSTANTANEOUS AND OVERRIDE Response: 3,000 Maximum Ampere Rating (I n) Rating Plug Catalog Number Ampere Rating Plugs Available Rating Maximum 2500 Ampere Rating 2,000 2500 2500 2500 1,000 Rating Plug Ampere Catalog ORPL25A250 ORPL25A200 Number ORPL25A160 Rating 2500 2000 (I ) 1600n 2500 2000 1600 Instantaneous Override Pickup Range Amperes 2 to 6.4 x In Instantaneous Amperes Pickup Range 2 to 6.4 x I Override Amperes n -20125 14875 5000 -16000 14875 -20125 4000 -12800Amperes 14875 -20125 3200 -10240 ORPL25A250 ORPL25A200 ORPL25A160 5000 -16000 4000 -12800 3200 -10240 14875 -20125 14875 -20125 14875 -20125 Interrupting Rating 500 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type 300 RD RDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 200 50 65 Icu Ics Icu RD 135 100 70 Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA) RDC 200 100 100 Breaker UL / CSA U IMP = 8kV Notes: Type Volts 240 100 1 MINUTE 65 100 RD 50 Ics 50 50 125 kA Icu Ics 25 13 35 18 Utilization Category A 480 600 65 50 RDC 200methods, follow 100 NEMA AB4 guidelines. 65 1. For field testing primary injection IEC 947-2 2.Calibration response in short delay pickup range415is the same for 1, 2, or 3 poles in series. Volts 240 690 30 Rating effect that I I I I to shorten I long delay. I memory effect comes 3.There is a memory can act the The 135 long 100 70 25 for a time RD into play if a current above the delay pickup value and then is cleared 50 exists 13 kA 200 100 circuit 35 itself.18 RDC 100 or the 50 breaker by the tripping of a downstream device A subsequent overload U = 8kV Category A time than normal. The amount of time will cause the circuit breaker to Utilization trip in shorter reduction is inverse to the amount of time that has elapsed since the previous overload. Notes 1) ForApproximately field testing primary injection methods, follow NEMA AB4-1991 publications. five minutes is required between overloads to completely reset the memory. CU 20 CS CU CU CS CS IMP 2) Calibration response in short delay pickup range is the same for 1, 2, or 3 poles in series. 3) There is a memory effect that can act to shorten the long delay. The memory effect comes playof if a the current above the delay pickup value a time and thenrating of the circuit breaker. 4. Theinto end curve is long determined by exists the for interrupting is cleared by the tripping of a downstream device or the circuit breaker itself. A See above tabulation. subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to 5. The instantaneous completely reset the memory. settings have conventional 100%, +/- 10% as the pickup points. 4) The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 5) ForFor ground fault time / current curves see SC-6345-96 (1600A), Eaton. SC-6346-96 (2000A), and 6. additional curve tolerances contact SC-6347-96 (2500A) 6) The instantaneous settings have conventional 100%, +/- 10% as the pickup points. ForTotal additional curve tolerances Cutler-Hammer. 77). clearing timescontact shown include the response times of the trip unit, the breaker opening, 8) Total clearing times shown include the response times of the trip unit, the breaker opening, and the quenching of the arcing current. and the extinction of the arcing current. T IME IN S E C ONDS 10 5 3 2 1 6.4 2 1 Available Instantaneous Pickup Settings 2 to 6.4 x In ± 10% In 0.1 Increments .5 Fixed Instantaneous Override .5 .3 Available Flat Response Short Delay Time Settings 0.1 to 0.5 seconds in 0.01 second increments .2 .3 .3 .2 .1 .1 .1 Application Determines End of Curve .05 .5 .05 CURRENT IN MULTIPLES OF PLUG RATING I n 50,000 60,000 70,000 80,000 40,000 30,000 20,000 5000 6000 7000 8000 9000 10,000 4000 3000 2000 1000 50 60 70 80 90 100 30 40 20 5 .01 6 7 8 9 10 .01 3 .02 4 .02 2 .03 1 .03 AMPERES Figure 14. Instanteneous and Override - Curve NumberSC-6344-96, October 1997 eaton www.eaton.com 17 Time Current Curves TD012038EN Series C R-Frame Effective April 2014 R-Frame Circuit Breakers Equipped with 2500A Digitrip OPTIM Trip Units; Ground Fault or Ground Fault Alarm Only Circuit Breaker Time/Current Curves (Phase Current) Series C R - Frame Circuit Breakers 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 10,000 .2 .1 2 HOURS CURRENT IN MULTIPLES OF RATING PLUG I n 1 HOUR 5,000 Equipped With 2500A Digitrip Optim Trip Units Circuit Breaker Time/Current Curves (Ground Current) FAULT ALARM ONLY Response: GROUND FAULT TRIP OR GROUND Series C R - Frame Circuit Breakers Available Rating Plugs Equipped With 2500A Digitrip Optim Trip Units Response: ORPlug GROUND FAULT ALARM Rating AmpereFAULT TRIP Ground Fault ONLY Maximum GROUND Ampere Rating Available Rating Plugs Maximum Ampere 2500 Rating 3,000 Ampere Rating 2500 (I n) 2500 2500 2500 2,000 Catalog Number Rating (In) 2000 1600 2500 500 -1200 400 -1200 ORPL25A200 ORPL25A160 2000 UL/CSA rms Sym. kA, 50/60 Hz 240V 480V 600V Breaker Type RD RDC 125 200 Breaker Type IEC 60947-2 rms Sym. kA, 50/60 Hz 240V 415V 690V 500 300 65 100 50 65 Icu Ics Icu 135 100 70 200 100 100 U IMP = 8kV RD RDC 200 Ground Fault Pickup Range 625 -1200 Amperes 500 -1200 400 625 -1200 -1200 ORPL25A200 ORPL25A160 ORPL25A250 1600 Interrupting Rating 1,000 Pickup Range Amperes Rating Plug Catalog ORPL25A250 Number Notes: Ics 50 50 Icu Ics 25 13 35 18 Utilization Category A Interrupting Rating @ 50/60 Hz RMS Sym. Amperes (kA) 1. For field testing primary injection methods, follow NEMA AB4 guidelines. Breaker UL / CSA 1 MINUTE 100 Type Volts 240 pickup range 480is the same for 6001, 2, or 3 poles in series. 2. Calibration response in short delay RD 30 kA RDC 65 50 CU CS CU CS CU CS 200 100 100 50 35 18 4.The end of the Ucurve is determined byCategory the interrupting rating of the circuit breaker. = 8kV Utilization A See above tabulation. 20 IMP Notes 1) For field testing primary injection methods, follow NEMA AB4-1991 publications. 2)5. Calibration response range is the same for 1, 2,to or a 3 maximum poles in series. of 1200 Amperes. Ground faultin short leveldelay is pickup electronically limited 3) There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device orconventional the circuit breaker itself. A +/- 10% as the pickup points. 6. The ground fault settings have 100%, subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to 7. For additional curve tolerances contact Eaton. completely reset the memory. 4) The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 8. Total clearing times shown include the response times of the trip unit, the breaker 5) Ground fault level is electronically limited to a maximum of 1200 Amperes. quenching of the arcing current. 6) For and phase the current curves, see SC-6336-96, SC-6337-96, SC-6338-96, SC-6339-96, SC-6340-96, SC-6341-96, SC-6342-96, SC-6343-96, and SC-6344-96. 7) The ground fault settings have conventional 100%, +/- 10% as the pickup points. 8) For additional curve tolerances contact Cutler-Hammer. 9) Total clearing times shown include the response times of the trip unit, the breaker opening, and the extinction of the arcing current. 10 T IME IN S E C ONDS 125 kA RDC 200 act to shorten 100the long delay. 65The memory effect comes 3. There is a memory effect that can into play if a current IEC 947-2 above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload 415 0 690 will cause theVolts circuit breaker to24trip in shorter time than normal. The amount of time Rating I I since the I time Ithat hasI elapsed I reduction is inverse to the amount of previous overload. is required overloads to completely reset the memory. 70 25 RD Approximately five minutes135 100 between 50 13 50 Available Ground Fault Pickup Settings ±10% in 0.01 increments 5 3 1.0 2 1 1 .2 .5 .5 .5 .5 Available Flat Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .3 .3 .2 .2 .1 .1 .1 I2 t Slope for Ground Fault Time Settings .1 Availaible I2 t Response Ground Fault Time Settings 0.1 to 0.5 seconds in 0.01 second increments .05 .03 Flat Shape for Ground Fault Time Settings .03 Figure 15. Ground Fault or Ground Fault Alarm Only - Curve Number SC-6347-96, October 1997 eaton www.eaton.com 6 7 8 9 10 4 5 3 2 .6 .7 .8 .9 1 .4 .5 .3 .2 6 7 8 9 10 5 4 3 2 .6 .7 .8 .9 1 .5 .4 .01 .3 .01 .2 .02 .1 .02 CURRENT IN MULTIPLES OF RATING PLUG I n 18 .05 opening, Series C R-Frame Time Current Curves TD012038EN Effective April 2014 eaton www.eaton.com 19 Time Current Curves TD012038EN Effective April 2014 Series C R-Frame Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. TD012038EN / KDC April 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners.