R8MU & R8MUST Maintained and Non-maintained emergency bulkhead Please read instruction before commencing installation and retain for future reference. Specification: Model No. Operating mode Lamp Dimensions Insulation Supply voltage Supply current Ballast lumen factor Rated luminaire output Discharge Duration Battery Battery Life Storage temperature Operating ambient temperature Weight Case material Diffuser material Cut-out Flammability Ingress Protection R8MU R8MUST Maintained Self Test T5 8W fluorescent tube 348mm x 173mm x 77mm Class I, Must be earthed 240VAC 50Hz 0.1A 0.03A 0.24 70 Lumens >3 hours after minimum 24Hr charge 2.4V 4Ah Ni-Cd (2x1.2V cells) up to 4 years normal use -5°C ~ +60°C 5°C ~ +25°C 1.2Kg ABS Polycarbonate 280mm x 135mm Withstands 850°C Glow wire test IP40 Suitable for mounting on a normally flammable surface Green LED indicator indicates battery charging mode Safety and performance in accordance with EN60598-1, EN60598-2-22 EN50082-1, EN61000-3-2, EN61000-3-3 Suitable for Indoor use, wall or ceiling mounted Complies with EN60598 (Bs4533) Installation: ! Warning. Isolate mains supply before installing or servicing Surface mounting 1. Remove diffuser by pressing the latch on the side of the unit and sliding the cover off. 2. Using a screwdriver remove the 2 screws and pull the gear tray away from fitting. 3. Mark appropriate fixing points on wall or ceiling; check that fixings will not impinge on concealed cables of pipes before drilling holes. 4. Drill out cable entry hole and introduce supply cable. ( Normally, the emergency fitting must be powered from the lighting circuit feed) 5. Line up the keyholes in the fitting with the 2 screws in the wall 6. Push the fitting against the wall and slide down, tighten the screws making sure the fitting is secure. 7. Please proceed to stage point 8. Below. Accessories: Dropped Glass legend accessory R8MULK Information for the Product user 1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE marked with crossed out wheelie bin symbol). 2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement. 3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is important that it is separated from normal household waste and recycled in the WEEE chain 4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household waste, but should be disposed of according to local WEEE regulations The Installation must be carried out by an electrician LED Group Western Retail Park Nangor Road Dublin 12 Ireland Issue 1 161110 Tel: +353 1 7099000 Fax: +353 1 7099060 Email: info@led.ie Website: www.led.ie ISO 9001:2008 Q UAL IT Y ASSU RE D CO MPANY Page 1 Installation: Recess mounting 1. Remove diffuser by pressing the latch in the side of the fitting and sliding the cover off. 2. Using a screw driver remove the 2 screws and pull the gear tray away from the fitting. 3. Mark the appropriate cut-out for the fitting on the wall or ceiling; check that fixings will not impinge on concealed cables of pipes before drilling holes. 4. Cut-out the required area to recess the fitting into the wall or ceiling. 5. Remove the two recess covers from the sides. 6. Drill out cable entry hole and introduce supply cable. 7. Insert the fitting into the cut-out and screw the latches until tight, making sure the latches has a ferm grip to the under-side of the ceiling or wall. 8. Write installation date on battery and connect battery to the gear tray. 9. Connect wires from un-switched supply to terminals on gear tray, brown to PL (or P on non-maintained), Blue to N and green/yellow to earth: In the maintained emergency unit. 10. For lamp always on, link terminal “SL” to terminal marked “PL” for lamp switched, connect switched live wire to terminal “SL” Note: if “SL” terminal not connected, fitting works as non-maintained. 11. Fix gear tray in position again using the 2 screws 12. Insert lamp and rotate 90deg to install. 13. If a legend is required, using the clips in the diffuser insert the legend ensuring it is secure. R8MUST non-maintained procedure: 14. In order for the R8MUST to operate correctly in non-maintained operation the batteries must be fully depleted until the Yellow is on continuously. Once the Yellow LED is on the manual test button must be pressed and held for over 5 seconds. When button is released the Yellow LEDs will turn off. This process must be repeated for all R8MUST non-maintained fittings. Normal R8MUST Operation 15. During self-test or manual test mode, the fitting will the check the lamp status, once the lamp is defective or inserted incorrectly, the Red LED will be on. Change lamp or insert correctly. In order to reset the fitting after lamp failure the manual test button must be pressed and held for 5 seconds. 16. After installation and the Yellow LED is continually on. This indicates that the battery will not hold sufficient charge and needs to be replaced. 17. The RED LED will be on when the battery is healthy but depleted after normal emergency discharge. Connect the 240V supply power to PL terminal and the fitting will reset automatically. 18. During Normal Emergency discharge, the fitting will check the lamp status, once the lamp is defective or inserted incorrectly, the Red LED is on. Once the lamp is changed or insert correctly, Connect the 240V supply power to PL terminal and the fitting will reset automatically. 19. Switch on supply: Green LED will come on indicating correct battery charging has started. The green LED will remain on until main power is lost to PL. 20. When supply to PL is lost, battery will operate lamp in emergency mode (24% normal light output). Manual testing for R8MU: The manual version emergency lighting must be inspected and tested regularly in accordance with local codes of practice: note: for safety reasons tests should be carried out during daylight hours. The minimum recommended test schedule is as follows: After installation, allow 36 hours to ensure full battery charge and then interrupt the supply; check after 3 hours that tube is still lighting. 1. Daily check that charge indicator LEDs are working 2. Monthly, interrupt mains for a short period and check tubes light 3. Six-monthly, check 1 hour duration 4. Yearly, check 3 hour duration: batteries must be replaced when they can no longer support 3 hour operation. 5. Complete record sheet on installation and retain in maintenance file. 6. Update file with ongoing test records for inspection by fire officer or other duly authorised person Important guide to use: This fitting is not suitable for installation where ambient air temperature is above 25°C. The Installation must be carried out by an electrician LED Group Western Retail Park Nangor Road Dublin 12 Ireland Tel: +353 1 7099000 Fax: +353 1 7099060 Email: info@led.ie Website: www.led.ie ISO 9001:2008 Q UAL IT Y ASSU RE D CO MPANY Page 2 Self-Test Function: The self-test version emergency lighting fuctions as following: Weekly auto test: Once a week the fitting will be placed on automatic test, the Yellow LED will fast flash, Test duration is 15 miniutes. Yearly Self test: Once a year the fitting will be placed on automatic test, the Yellow LED will fast flash, test duration is 3 hours. Manual Test: 1. Push test switch and the yellow LED will fast flash.Test duration is 15 seconds. 2. In the event that the Red LED turns on:replace lamp and press test switch to reset. LED FUNCTIONS GUIDE Green Yellow Red Status ● Normally charging mode Battery insufficient capacity ● Lamp replacement required or lamp not inserted incorrectly ● Self-test or manual test *Fast flash Normally emergency discharging *Slow flash Installation and Maintenance Record: Installer Installation Type Installation test duration & Date Month Test 1 Short 2 Short 3 Short 4 Short 5 Short 6 1Hr. 7 Short 8 Short 9 Short 10 Short 11 Short 12 1st Year Signed Date 2st Year Signed Date 1Hr. 3Hr. xxxxx xxxxx xxxxx 3st Year 4st Year 5st Year Signed Date Signed Date Signed Date xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx xxxxx The Installation must be carried out by an electrician LED Group Western Retail Park Nangor Road Dublin 12 Ireland Tel: +353 1 7099000 Fax: +353 1 7099060 Email: info@led.ie Website: www.led.ie ISO 9001:2008 Q UAL IT Y ASSU RE D CO MPANY Page 3 Installation diagram: 348mm Surface mounting 173mm 77mm from battery -B R+ Figure 1 Figure 2 Surface mounting Figure 3 Wiring Details Non-maintained Installation L N Surface mounting Figure 4 mains lighting fuse To mains lighting Tamper proof test switch To additional emergency luminaires N L Maintained or sustained installation L N non-maintained emergency luminaire mains lighting fuse Tamper proof test switch To mains lighting To additional emergency luminaires Maintained fluorscent emergency luminaire Maintained lighting control switch The Installation must be carried out by an electrician LED Group Western Retail Park Nangor Road Dublin 12 Ireland Tel: +353 1 7099000 Fax: +353 1 7099060 Email: info@led.ie Website: www.led.ie ISO 9001:2008 Q UAL IT Y ASSU RE D CO MPANY Page 4