It’s tough down there. Aluminized Steel Type 2 Corrugated Steel PipE Aluminized Steel Type 2 Pipe for added durability Strength of steel, corrosion resistance of aluminum Corrugated Steel Pipe (CSP) manufactured from Aluminized Steel Type 2 offers the corrosion resistance and surface characteristics of aluminum with the strength and value of steel. The product is fabricated from steel coils that have been hot dip coated in a bath of commercially pure aluminum. The coating has uniform thickness on both sides of the sheet, with a strong metallurgical bond between the metals. The Aluminized Steel Type 2 material meets AASHTO specifications M274 and ASTM A929. The coils are then fabricated into helically corrugated pipe meeting the requirements of AASHTO specifications M36 and ASTM A760. Helically corrugated steel pipe has been a standard of the construction industry for decades. Pipe is fabricated with lock seams or welded seams depending on the job requirements, and each pipe end can be reformed to provide at least two annular re-corrugations. Excellent barrier protection Aluminum forms a passive oxide layer that adds to the service life by providing good barrier protection. This passive oxide forms rapidly and maintains better protection over a wider environmental range than zinc reaction products. The aluminum oxide is stable in both hard and soft water. The passive oxide will endure as long as the free aluminum coating layer is present. When this layer is eventually penetrated, there is an underlying hard, thick aluminum-iron alloy layer that provides further corrosion protection plus abrasion protection. 2 Pure Aluminum Coating Steel Strip Protective Atmosphere Alloy Layer Commercially pure Molten Aluminum Steel Base Metal The photomicrograph on the left shows how the thick alloy layer metallurgically bonds the aluminum coating to the steel base metal, as well as how the coating provides continuous protection to the base metal. The same coating protection is provided to both sides of the steel base metal. Based on field studies of 42 – 50 year installations, Aluminized Steel Type 2 service life is estimated to be 75 years minimum at 16 gauge in the 5 – 9 pH and ≥ 1,500 ohm•cm resistivity ranges, and 100 years in the same pH range and resistivity ranges > 5,000 ohm•cm. For a narrower pH range of 6 – 8, culvert data supports 100 year estimated service life for resistivities ≥ 1,500 ohm•cm. In some cases, the pH/resistivity ranges may be extended somewhat as is the case in arid regions where moisture availability is generally a controlling factor, and satisfactory service life may be realized at soil resistivities somewhat below the 1,500 ohm•cm lower limit. In wetter climates, satisfactory service life may be realized at soil pH values slightly below the 5.0 lower limit when resistivities are relatively high. In general, however, environments outside the recommended pH/resistivity ranges should be subjected to additional testing to see if conditions conducive to accelerated corrosion actually exist. For example, low resistivity waters and soils may contain excessive concentrations of corrosive chloride and sulfates salts. In addition, any dark or light gray, blue, or olive colored clay constituents observed in a heterogeneous soil should be isolated for pH measurement since these sometimes contain watersoluble heavy metal salts. These constituents induce strong acidification necessitating the use of a bituminous coating to ensure normal soilside corrosion behavior, or imported compliant backfill. Environments that are far outside the recommended pH/resistivity ranges should be avoided, including acid minewater, seawater, estuary brackish water, and sanitary/industrial sewage. Standard specifications 1. AASHTO M274 (Aluminized Steel Type 2 material) and ASTM A929 2. AASHTO M36 and ASTM A760 (conduit, pipe) 3. AASHTO Standard Bridge Design Specifications, Section 12 (structural design) and ASTM A796 4. ASTM A798 (installation) Aluminized Steel Type 2 75 years minimum service life. And still counting. 75 75 years minimum service life. And still counting. years minimum service life And still counting • The condition of Aluminized Steel Type 2 pipe inverts— a critical point durability • The condition of in Aluminized design—was excellent. Steel Type 2 pipe inverts— 1952 – 53, an additional 135 composite • InThe condition of Aluminized a critical point inandurability In 1952–53, additional 135 culverts of Aluminized Steel Type 2 and Steel Type 2 pipe inverts— design—was excellent. composite culverts of Aluminized galvanized steel were installed in 20 a critical point ingalvanized durability Steel Type 2 and steel In 1952–53, an additional 135 states. Based on the current conditions design—was excellent. were installed in 20 states. Based of the pipes available, data indicates composite culverts ofthe Aluminized on the current conditions of the a minimum service life steel for In Type 1952–53, an additional 135 Steel 2100 andyear galvanized pipes available, the data indicates 16 gauge Aluminized Steel Type 2 pipe composite culverts Aluminized were installed in 20ofstates. Based a minimum 75-year service life for when installed in the recommended Steel Type 2 and galvanized steel on the current conditions of the 16 gage Aluminized Steel Type 2 environment, pHin5the – 9data with resistivities were installed 20 states. Based pipes available, indicates • ≥ 5,000 ohm cm or pH 6 – 8 with installed in the on the when current conditions of recomthe a pipe minimum 75-year service life for •cm. resistivities ≥ 1,500 ohm mended environment. pipes available, the data 16 gage Aluminized Steelindicates Type 2 a minimum 75-yearin service life for pipe when installed the recomIndependent studies Independent studies 16 gage environment. Aluminized Steel Type 2 mended Many independent have pipe when installed instudies the Independent studies have beenrecomperformed been performed that confirm Independent studies mended environment. that confirm AK Steel Corporation’s longAK Steel Corporation’s term field test. Many independent studieslong-term have field test. Independent studies Coatings for Corrugated Steelconfirm Pipe; R. M. Pyskadlo been performed that and J. P. Ewing (NYDOT); FWHA-NY-SR-87-90 Many independent studies have AK Steel Corporation’s Durability Analysis of Aluminizedlong-term Type 2 CMP; J. P. been performed thatFWHA-RD-97-140 confirm field test. Ault and J. A. Ellor (OCR); AK This SteelAluminized Corporation’s long-term Steel Type 2 fieldcorrugated test. steel � pipe was installed This Aluminized 19532 in Steel Type ThisinAluminized ElSteel Dorado, corrugated steel Type 2 This Aluminized California. It steel was pipe was installed corrugated Steel Type 2 inspected in 1982 in 1953 in in pipe was installed corrugated steel and in 1995. El in Dorado, 1953 El Dorado, pipe was installed Coupons California. It was California. Itwere was in 1953 in removed 1995 inspected in in 1982 inspected in El Dorado, forand evaluation by 1982,1995 in 1995.and California. It was the AK Steel in 2005. Coupons Coupons were inspected in 1982 werein removed in Research Center removed 1995 andfor in evaluation 1995. 1995 CALTRANS. forand evaluation by Coupons were by AK the AK Steel the Steel removed in 1995 Research Center Research Center for evaluation by and CALTRANS. and CALTRANS. the AK Steel Research Center and CALTRANS. � This close-up view shows the Aluminized Steel Type 2 pipe installed in Garland, �Maine, with the dark staining wiped away to close-up reveal theview like-new aluminum. This showsunderlying the Aluminized Steel Type 2 pipe installed in Garland, � This close-up view shows the Aluminized Maine, with the dark staining wiped away This Steel close-up Aluminized Type 2view pipe shows installedthe in Garland, Maine, to reveal the like-new underlying aluminum. the2dark staining wipedinaway to reveal Steelwith Type pipe installed Garland, the like-new aluminum Maine, with theunderlying dark staining wiped away to reveal the like-new underlying aluminum. � � AK Steel Research Center’s corrosion engineers and AK Steel Research D.O.T. AKMissouri Steel Research Center’s corrosion material engineers Center’s corrosion engineers and inspect aand 43-year engineers Missouri DOT AK Steel Research old Aluminized Missouri D.O.T. material engineers Center’s corrosion Steela Type 2 pipe material inspect 43engineers year engineers andold installation. This is inspect a Steel 43-year Aluminized Type Missouri D.O.T. one of two culvert Aluminized 2old pipe installation. material engineers installations in This is one Steel Typeof 2twopipe inspect a 43-year culvert installations Carter County, installation. This is Aluminized inold Carter County, Missouri, installed one of two culvert Steel Type 2 pipe Missouri, installed in in a series containinstallations in This is ainstallation. series containing ing half Aluminized Carter County, oneAluminized of two culvert half Steel Steel Type 2 pipe Missouri, installed Type 2 pipe andinhalf installations and half galvanized in a series containgalvanized steel pipe. Carter County, ingsteel halfpipe. Aluminized Missouri, installed Steel Type 2 pipe 3 in a series containand half galvanized ing half Aluminized steel pipe. Steel Type 2 pipe and half galvanized steel pipe. � � � normal drainage project. Aluminized Steel Type 2 pipe offers a durable and economical alternate normal drainage project. Alumito reinforced concrete nized Steel Type 2 pipe pipe. offers Feaa tures include light weight, long normal drainage project. Alumidurable and economical alternate Ideal for storm sewers and joints that have nized Steel Type 2 pipe offers a tolengths, reinforced concrete pipe. Feapositive pull-apart resistance durable and economical alternate tures include light weight, long and Aluminized Steel Typeto 2 corrugated the ability adjust yielding to reinforced concrete Fea-steel lengths, andtojoints thatpipe. have pipe is an ideal material for municipal foundations. tures include light weight, long positive pull-apart resistance and storm sewers or any normal drainage Pipeand and pipe-arch are lengths, joints that have the project. ability to adjust to yielding Aluminized Steel Type 2 pipe offers available in four resistance corrugations positive pull-apart and to foundations. a 2durable1and economical alternative /3"and x to/adjust 2", 3" x 1", 125mm x (2Pipe the ability to yielding pipe-arch are reinforced concrete pipe. Features include 25mm, and Spiral Rib’s 3/4" x foundations. available in four corrugations light weight, long lengths, and joints that 3 1 / 4" x 71 /2" rib corrugation) and 2Pipe and pipe-arch are /3" xpositive /2", 3" x 1", resistance 125mm xand the (2 have pull-apart inability all standard available four corrugations toinadjust todiameters yielding /4and "x 25mm, and Spiral Rib’s 3foundations. 2 1 16 gage 10 gage. 3 1 /through / 3 " x 2 ", 3" x 1", 125mm x (2 /4" x 7 /2" rib corrugation) and 3 Long-term field testing /and 4" x 25mm, and Spiral Rib’s in all standard diameters field testing 3 Long-term 1 /4"gage x 7 /through 2" rib corrugation) 16 10 gage. and Based on extensive data from actual on extensive data from inBased all standard diameters and field installations dating back 50 actual installations datingyears, Long-term field testing 16 gagefield through 10 gage. Aluminized Steel Aluminized Type 2 is a superior back 43extensive years, Steel Based on dataand from product for storm sewer drainage Type 2 is a superior product for Long-term field testing actual fieldItinstallations datingresistance projects. has better corrosion storm sewer and drainage projects. Based on extensive data from back 43 years, Aluminized Steel than galvanized structures and displays It has better corrosion resistance actual dating Type 2field isabrasion a installations superior product for better resistance. than43 galvanized structuresprojects. and back years, Steel storm sewer andAluminized drainage abrasion resistance. Type 2better is 1953, abetter superior product for 2 Prior to Aluminized Steel Type It displays has corrosion resistance Prior to 1953, Aluminized galvanized culvertsand wereSteel storm sewer andsteel drainage projects. thanand galvanized structures Type 2 better and galvanized steel exposed incorrosion sites acrossresistance the U.S. These Itdisplays has better abrasion resistance. culverts were exposed in sites sites represented a variety of service thanPrior galvanized and to 1953,structures Aluminized Steel across the U.S. These sites repreconditions including farm field drainage, displays better abrasionsteel resistance. Type 2 and galvanized fresh water swamps, alkali soils, and sented a of service condiPriorwere tovariety 1953, Aluminized Steel culverts exposed in sites erosive applications. Test installations tions2including farm sites field drainage, Type andU.S. galvanized steel across the These reprewerewater sampled after 8 years andsoils, again fresh swamps, alkali culverts were exposed in sites sented a24 variety of service condiafter years. Weight loss data analyzed andincluding erosive Test across the U.S.applications. These sitesdrainage, repretions farm field at all sites indicate Aluminized Steel installations were sampled afterType 2 sented a variety of service condifresh water swamps, alkali soils, provided significant additional corrosion eight yearsapplications. and again tions including farm fieldafter drainage, and erosive Test 24 resistance. years. Weight data fresh water swamps, alkalianalyzed soils, installations wereloss sampled after at all sites indicate Aluminized and applications. Test eight years and 24andSteel Inerosive addition to theagain careful after sampling Type 2 provided significant addiinstallations were after years. Weight losssampled dataduring analyzed evaluation accomplished this 24 tional corrosion resistance. eight years andsimple again after 24 Steel year program, visual inspection at all sites indicate Aluminized In addition to the revealed that: loss years. datacareful analyzed Type 2Weight provided significant addisampling and evaluation accomat all sites indicate Aluminized Steel tional corrosion resistance. plished during this 24-year pro• T he appearance of Aluminized Steel Type provided In 2addition to significant the careful addiType 2 was clearly superior to that gram, simple visual inspection tional corrosion resistance. sampling and evaluation accom- of conventional metallic coating. revealed that:to In addition the careful plished during this 24-year pro• The condition of Aluminized Steel sampling and evaluation accomgram, simple visual inspection • The appearance Type 2 pipe inverts,ofa Aluminized critical point in plished during this 24-year prorevealed that: Steel Typedesign, 2 was clearly superior durability was excellent. gram, simple visual inspection to that of conventional metallic • The appearance of Aluminized revealed that: coating. Steel Type 2 was clearly superior • to Thethat appearance of Aluminized of conventional metallic Steel Type 2 was clearly superior coating. to that of conventional metallic coating. 3 3 Performance proven by 50 year field test 50 year old Aluminized Steel Type 2 coupons taken from pipe inverts around the United States Marshall County, IA Installed 1952 Inspected 2003 Lafayette County, MO Installed 1952 Inspected 2003 Greene County, IL Installed 1953 Inspected 2003 Morgan County, IL Installed 1952 Inspected 2003 Bernalillo County, NM Installed 1952 Inspected 2005 Carter County, MO Installed 1953 Inspected 2003 San Benito County, CA Installed 1952 Inspected 2005 Decatur County, KS Installed 1953 Inspected 2003 Pratt County, KS Installed 1953 Inspected 2003 Dickenson County, KS Installed 1953 Inspected 2003 San Juan County, WA Installed 1953 Inspected 2005 Eldorado County, CA Installed in 1952 Inspected 2005 AK Steel has inspected many more pipe sites around the United States, and these field research studies indicate a minimum 75 year service life for Aluminized Steel Type 2 Corrugated Steel Pipe installed in the recommended environment. AK Steel Corporation 9227 Centre Pointe Drive West Chester, OH 45069 800.331.5050 www.aksteel.com 4 The information and data in this bulletin are accurate to the best of our knowledge and belief, but are intended for general information only. Applications suggested for the materials are described only to help readers make their own evaluations and are neither guarantees nor to be construed as express or implied warranties of suitability for these or other applications. AK Steel and the AK Steel logo are registered trademarks of AK Steel Corporation. Revision 06.17.12 The product, engineering and research information in this literature is applicable exclusively to AK Steel Aluminized Steel Type 2. Aluminized Steel Type 2