GNSD SERIES Fully Recessed Emergency Light FRONT PANEL DIAGNOSTIC DISPLAY Hi Charge – Red Float / Full Charge – Green • • Diagnostic Functions 2 Battery Failure – Red Flash 5 Lamp Failure – Red Flash 1 Transfer Failure – Red Flash 3 Charger Failure – Red Flash 4 Door Failure – Red Flash •• Insufficient Charge – Red/Green In Test – Green Flash • Fully self-contained emergency light that can be recessed into walls or ceilings • Virtually invisible during normal lighting conditions eliminating unattractive surface mounted emergency lights and battery packs • Exterior trim can be painted or wall-papered to match any color or décor • Advanced microprocessor self-diagnostics standard on ALL units • Fully adjustable long-life, 2000 hour MR16 Halogen lamps (up to 75 Watts) 9 ISOLITE GENIE SERIES – FULLY RECESSED EMERGENCY LIGHT Dimensions Computerized Electronic Circuitry Batteries 16" Transformer Back Box AC Input 7 7/8" 1 Lamp Head INTERNAL COMPONENTS with Back Box Rear Cover Removed Specifications 13 /2" Rough in Opening 6 3/4" Rough in Opening BACK BOX and Mounting Dimensions Construction • Unique, fully recessed, self-contained emergency light • F ully automatic operation suitable for wall or ceiling mount applications • Two flat panel doors lay flush with the trim and mounting surface • Compact, universal (wall or ceiling) recessed backbox is provided with fully adjustable mounting hardware to suit virtually all mounting applications • Self-adjusting frame and door assembly with no external mounting screws • Modular assembly and quick connector wiring allows for easy and fast installation Approvals • UL listed by Underwriters Laboratories to UL924 standard • Chicago Plenum Listed Battery • Option of lead calcium or nickel cadmium • Optional extended run times or remote capacity • 120 or 277 VAC field-selectable input Lamps • Fully adjustable long life, 2000 hour MR16 Halogen lamps up to 75 Watts each • Soft start lamp circuit ensuring extended lamp life 14 7/16" Universal, Adjustible Mounting Rails 2 per unit 13 1/2" to 30" Lamp sockets can be adjusted to optimize light pattern for wall or ceiling mounting MOUNTED DIMENSIONS (doors open) Features • Pre-Ship Back box • Self-Test/Self-Diagnostic • Advanced microprocessor self-diagnostics standard on ALL units • Discreet, automatic monthly self-testing • Self-diagnostics monitors: lamp load transfer circuit, battery capacity, door operation and motor drive • Optional infra-red remote transmitter with selectable 30 seconds or 90 minute tests • LED indicator and push-to-test button Electronics • Reliable, continuous cam, precision DC motor drive • No gears, cogs, limit switches or sensitive solenoid setting to jam or fail • Solid state microprocessor controlled circuitry • Line latch prevents unnecessary discharge of battery during installation • Brownout protection • Battery LVCO Warranty • General Warranty and Obligations in Isolite manual • Lamps not warranted Ordering Information Series Lamp Wattage Battery TypeOperation MountingOptions GNSD = 12 = 2 x 12 Watt LC = Lead Calcium 90 = 90 Minutes UN= Universal CP = Chicago Plenum Listed Genie w/ 20 = 2 x 20 Watt NC = NiCad 2H = 2 Hours (ceiling + wall) RI = Remote Indicator Display self-diagnostics 35 = 2 x 35 Watt 3H = 3 Hours SM= Surface mount RM = Fused Remote Output Leads 50 = 2 x 50 Watt 4H = 4 Hours (consult factory) RT = Infra-red Remote Testing 75 = 2 x 75 Watt TD = 15 Min Retransfer Delay (90 minutes only) TLRT = Infra-red Remote Transmitter (order separately) DL = Damp Location CC = Custom Color (specify) Example: GN-SD-20-NC-2H-U-RM 10 Headquarters: 31 Waterloo Avenue • Berwyn, PA 19312 • 800-888-5483 • 610-647-8200 • 610-296-8952 Fax www.isolite.com Western Office: 3563 Sueldo, Suite M • San Luis Obispo, CA 93401 • 800-799-5343 • 805-546-9669 • 805-546-9564 Fax