5/5/2016 Arc Flash Assessments NFPA 70 How it affects the Maintenance and the Safety Professional Arc Flash Assessments NFPA 70 Does NFPA 70, specifically Arc Flash, belong to the Maintenance Team or the Safety Team? 1 5/5/2016 Arc Flash Assessments NFPA 70 To Understand: What is An Arc Flash Why OSHA Is Addressing This Issue Requirements In NEC & NFPA 70E Impact to Industry Benefits to completing an Arc-Flash Assessment What is an Arc Flash An Arc Flash is a Sudden Release of Heat and Energy Caused By An Electric Arc, an Additional Hazard beyond Shock 2 5/5/2016 What is an Arc Flash Every Day 7 - 10 Electricians are Severely Injured by an Arc Flash Event Effects of an Arc Flash Arcing faults in power distribution can produce intense heat - Texas in August: 105 F - Surface of the sun: 8,540 F - Arc (at mid-point): 22,940 F - Arc (at terminals): 35,540 F Injuries from arc flash refer almost exclusively to the effects of burns received 3 5/5/2016 Effects of an Arc Flash (Cont’d) Arc Blast - 6,000 lbs. force won worker’s chest from moderate fault at MCC - Pressure can cause collapsed lungs, concussion, etc. Molten copper – Vaporized copper expands 40,000x upon vaporization Shrapnel – Arc Blast can create projectiles that cause injury 2nd & 3rd Degree Burns 4 5/5/2016 Potential Causes of Arc Flash Accidental Contact - Misplaced tools - Voltage testers Equipment Failures Rodents Unsuccessful short-circuit interruptions Racking a breaker on an energized bus Removing covers Voltage checks or troubleshooting NIOSH Arc Flash Statistics 2004 - 2014 85% Industrial Facilities 9% Medical and Institutional Facilities 4% Commercial Facilities 2% Retail 5 5/5/2016 OSHA REQUIREMENTS (WHAT) OSHA 29 CFR 1910.132(d) requires employers to assess the workplace to determine if hazards are or could be present, provide the appropriate PPE for each affected employee, and requires its use. It also requires employers to inform the affected employees regarding hazards and PPE and to verify that the required assessment was performed through a written certification identifying the workplace evaluated. OSHA has determined 50-volts to ground is an electrical hazard OSHA REQUIREMENTS OSHA 29 CFR 1910.133 requires employees who are exposed to electrical shock and arc hazards to be qualified for the specific task they are performing. This involves safe work practices as well as using the appropriate PPE (TRAINING) OSHA 29 CFR 1910.335 (a)(1)(I) requires employees working with potential electrical hazards to be provided with, and use electrical PPE appropriate for the specific parts of the body to be protected and for the work to be performed. (POLICIES) 6 5/5/2016 OSHA Requirements (How) NFPA 70E and NEC were written at OHSA’s request to help employers meet the content of OSHA 1910 Subpart S. NFPA Became the Standard for Electrical Safety in the Workplaces – August 2007 OSHA REQUIREMENTS Effective August 2007 CFR 1910 will be revised that will mandate Compliance with NFPA 70E-2000 and NEC2002. SUMMARY: The Occupational Safety and Health Administration (OSHA) is revising the general industry electrical installation standard found in Subpart S of 29 CFR Part 1910. The Agency has determined that electrical hazards in the workplace pose a significant risk of injury or death to employees, and that the requirements in the revised standard, which draw heavily from the 2000 edition of the National Fire Protection Association's (NFPA) Electrical Safety Requirements for Employee Workplaces (NFPA 70E), and the 2002 edition of the National Electrical Code (NEC), are reasonably necessary to provide protection from these hazards. This final rule focuses on safety in the design and installation of electric equipment in the workplace. This revision will provide the first update of the installation requirements in the general industry electrical installation standard since 1981. OSHA is also replacing the reference to the 1971 NEC in the mandatory appendix to the general industry powered platform standard found in Subpart F of 29 CFR Part 1910 with a reference to OSHA's electrical installation standard. 7 5/5/2016 NFPA70E Article110.1 The employer shall implement an overall electrical safety program that directs activity appropriate to the voltage , energy level and circuit conditions. Other elements of an Electrical Safety Program should include: a) Awareness and Self-Discipline b) Electrical Safety Principles (Annex E) c) Electrical Safety Program Controls d) Electrical Procedures e) Hazard/Risk Evaluation Procedure NFPA70E Articles 120 and 130 (Cont’d) Deals with establishing an Electrically Safe Work Condition Each employee should be trained in Lockout/Tagout Procedures The Employer is responsible for the procedures Simple Lockouts vs. Complex Lockouts 8 5/5/2016 Electrical Hazards There are many hazards with electricity. Some of them are common knowledge and some we have just recently began to understand: Shock Hazard – This is the most common thought of hazard to electricity This hazard produces the most injuries and fatalities. Arc-Flash Hazard – This is the least known about hazard. This hazard can cause severe and fatal burns. The extreme heat (35,000 F) of an Arc-Flash can ignite clothing, create blast shrapnel, and dangerous pressure wave. The latest NEC and NFPA publications now have regulations to minimize the results of such a dangerous hazard. Personal Protective Equipment Voltage Rated Gloves Are REQUIRED for All Voltage Testing Above 50 Volts 500 V 1000 V 7500 V 17000 V 9 5/5/2016 Personal Protective Equipment Must be air tested daily before usage. Must be electrically tested every 6 months or replaced. Before issuance gloves may be stored for up to 1 year without being tested. OSHA Requirements (How) NFPA 70E-2015 Article 130.5 states an arc flash risk assessment shall be performed and shall (1) Determine if an arc flash hazard exist. If an arc flash exist the risk assessment shall determine: (a) Appropriate related safe work practices (b) The arc flash boundary (c) The PPE to be used within the arc flash hazard boundary. NEC 110.16 States Equipment must be marked to warn qualified persons of potential electrical arc flash hazards. 10 5/5/2016 OSHA Requirements (How) Cont’d NFPA 70E 2015 130.5(D) States serviceable equipment shall be marked with a label containing all of the following information: 1.Nominal Voltage 2.Arc Flash Boundary 3.At least one of the following: (a) Available incident energy and corresponding working distance, or arc flash PPE category but NOT BOTH. (b) Minimum arc rating of clothing (c) Site-specific level of PPE OSHA Requirements (How) Cont’d NFPA 70E 2015 130.5 (C) states there are two methods to determine the required arc flash PPE 1. Incident Energy Analysis Method - IEEE 1584 Methodology to complete the arc flash calculations 2. Arc Flash PPE Categories Method – Task Dependent Table 130.7(C)(15) – AC Voltages You cannot mix the two methods 11 5/5/2016 OSHA Requirements (How) Cont’d Table Method Task Dependent There is no Category 0 Arc Flash PPE must always be worn. User must be familiar with the Electrical System to be determine Fault Currents and OCP Device Clearing Times. Table Method Cont’d TASK ARC FLASH PPE REQUIRED Normal Operation of Switches* NO AC Systems Including voltage measurements YES Removal of Bolted Covers or Panel Covers* YES Removal of CB’s or Switches YES Reading of Panel Meters NO Preform Infrared Thermography* NO Work on Control Circuit 120V and less* NO Work on Systems with > 120V YES Work on Equipment fed from starters or Electrical Panels YES 12 5/5/2016 Incident Energy Analysis Method Table H.3(b) IEEE 1584 - states systems operating less than 240-volts fed by a transformer < 125 KVA and has a secondary fault current < 10,000-amps does not pose an Arc Flash Hazard Incident Energy Valve < 1.2 Cal/cm2 Required Arc Flash PPE Protective clothing, non-melting or untreated cotton, long sleeves, Safety Glasses, Hearing Protection >1.2 Cal/cm2 – 12 Cal/cm2 Arc Rated Clothing, Arc Rated Face Shield, Balaclava, Safety Glasses, Hearing Protection > 12 Cal/cm2 Arc Rated Clothing Arc Rated Hood, Safety Glasses, Hearing Protection NFPA 70E does not recognize incident energy levels greater than 40 cal/cm2. This is a very dangerous condition. No work should be completed on or near this equipment. PPE Examples < 1.2 cal/cm2 > 1.2 - 12 cal/cm2 > 12 cal/cm2 13 5/5/2016 OSHA Methods of Enforcement The General Duty Clause – Requires workplaces to be free from recognized hazards (shock, electrical burn) The General Duty clause also requires employees to comply rules pursuant to the act The Specific Duty Clause – Requires the employer to comply with OSHA standards OSHA’s Use of NFPA 70E General Duty Clause - Employer must provide a safe work place - 70E is considered and “Industry Best Practice” - 70E is a consensus ANSI standard Specific Duty Clause - Employer must follow specific OSHA rules - OSHA may refer to specific provisions of 70E Historically, NFPA 70E has been cited for “Remediation or “Abatement 14 5/5/2016 Definition Qualified Person Qualified Person: “One who has received training in and has demonstrated skills and knowledge in the construction and operation of electrical equipment and installations and has received safety training to identify and avoid the hazards involved.” How to Be Compliant Turn it off!!!! OSHA expects it to be locked and tagged before any work begins. OSHA 1910.133 states “Live parts to which an employee may be exposed shall be de-energized before the employee works on or near them.” Exception: Unless de-energization creates a greater hazard or introduces a additional hazard or is infeasible 15 5/5/2016 How to Be Compliant Train your employees Electrical Workers must meet the OHSA’s definition of qualified. Skills and knowledge, safety training, the use of PPE Conduct job briefings (toolbox meetings) How to Be Compliant Assess the Hazards OSHA 1910.132 (d)(1) states “The employer shall assess the workplace to determine if hazards are present, or likely to be present, which necessitate the use of PPE. If such hazards are present, or likely to be present, the employer shall Select and have each affected employee use, the types of PPE that will protect the affected employee from the hazards identified in the hazard assessment.” 16 5/5/2016 Arc Flash Analysis Benefits •Anticipated Benefits: •Employee Safety – Primarily improving associate and contractor safety while interacting with electrical systems, this includes: •Reducing the exposure from arc flash •Matching the PPE requirements to the need, thus reducing PPE cost •Establish a means to properly label and rate over current protection. •Potentially lowers insurance premiums • Enables easy changes and upgrades • Drastically lessens your chances of having to make a very unpleasant visit to survivors Arc Flash Analysis Benefits •System Reliability: •Improve system capabilities and overall system balance, again improving up time and performance. •Allows Reliability community to focus predictive/preventive resources more effectively, thus improving TRS. •Asset Conservation: Improved reliability of the system reduces the probability of significant fire events and resulting property damage and business interruption. •Transfer of Best Practice: •System design features •System maintenance approaches •Over current and grounding strategies •Employee training and overall competence 17 5/5/2016 Final Thought WHEN YOU THINK YOU HAVE THIS ELECTRICAL SAFETY PROBLEM LICKED, YOU WILL BE IN YOUR MOST VULERNABLE POSITION. YOU START TO LET YOUR GUARD DOWN. ELECTRICITY IS VERY PATIENT AND WILL WAIT A LONG, LONG TIME FOR SOMEONE TO LET THEIR GUARD DOWN, AND IT WILL STRIKE SWIFTLY AND WITH NO WARNING. YOU MUST NEVER THINK YOU HAVE FINISHED YOUR WORK ON ELECTRICAL SAFETY Thomas D. Sterner May 19, 1988 18