Connecting Loop Units Interactive fire detection systems 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21 COPYRIGHT © This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it. No information in this publication should be regarded as a warranty made by Autronica Fire and Security. The information in this publication may be updated without notice. Product names mentioned in this publication may be trademarks. They are used only for identification. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 2 Introduction Table of Contents 1. Introduction .......................................................................5 1.1 1.2 1.3 About the Handbook.......................................................................... 5 Reference Documentation................................................................. 5 The Reader ....................................................................................... 5 2. Detectors ...........................................................................6 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Connecting Detectors ........................................................................ 6 LED Connection on Detector............................................................. 6 Connection of Branch-off................................................................... 7 Detector Head / Base Alignment ....................................................... 8 Detector Label ................................................................................... 8 Detector Locking Mechanism ............................................................ 9 2.6.1 Detector Base ......................................................................... 9 2.6.2 Detector head.......................................................................... 9 2.6.3 Removing a locked detector head .......................................... 10 Detector Dust Covers ........................................................................ 11 3. Manual Callpoints .............................................................12 4. Input and Output Units .....................................................13 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 BN-180 AutroKeeper ......................................................................... 13 BN-221/01 Extinguishing Control Unit............................................... 16 BN-221/02 Monitored Output Unit, 7A Relay .................................... 17 BN-303 Single Monitored Input Unit.................................................. 18 BN-303/LS Local Alarm Delay Unit ................................................... 19 BN-304 Single Monitored Input/Output Unit ...................................... 20 BN-305 Dual Monitored Input/Output Unit ........................................ 21 BN-307 Monitored Fire Alarm Device Control Unit ........................... 22 BNB-330A Conventional Loop Interface ........................................... 23 BNB-331 Conventional Loop Interface.............................................. 24 BN-500/EX Input Unit with SelfVerify ................................................ 25 BN-500/N Input Unit with SelfVerify .................................................. 26 BN-505/EXD Input Unit with SelfVerify ............................................. 27 5. Control Units .....................................................................28 5.1 5.2 5.3 5.4 5.5 BW-200 Disable Input with Pushbuttons ........................................... 28 BW-201 Disable Input with Timer Input............................................. 29 BW-202 Day/Night Control Unit with Pushbuttons ............................ 30 BW-203 Day/Night Control Unit with Timer Input .............................. 31 BU-200 Remote Alarm Control Unit .................................................. 32 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 3 Introduction 6. Alarm Units ........................................................................33 6.1 6.2 6.3 6.4 6.5 6.6 Introduction ........................................................................................ 33 BBL-100 Beacon Indoor Addressable ............................................... 33 BBR-130 Sounder Adressable with Base ......................................... 34 BBR-230 Sounder Indoor Addressable ............................................. 35 BBQ-130 Sounder/Strobe with Base................................................. 36 BBQ-230 Sounder/Strobe Addressable ............................................ 37 7. Detectors for Special Requirements ...............................38 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 AutroFlame IR Flame Detector BG-201 ........................................... 38 AutroFlame IR Flame Detector BG-21 .............................................. 39 Fireray 5000 ...................................................................................... 40 AutroSense Nano .............................................................................. 41 AutroSense Micra 25 High Sensitivity Aspirating Detector ............... 42 AutroSense Micra 100 High Sensitivity Aspirating Detector ............. 43 AutroSense 200 High Sensitivity Aspirating Detector ....................... 44 AutroFlame X33AF Multispectrum Infrared Flame Detector ............. 45 Ex ia Approved Detectors.................................................................. 46 8. Discontinued Products.....................................................47 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 BBR-200 Programmable Electronic Sounders .................................. 47 BBR-110 Addressable Socket Sounder ............................................ 48 BN-300 Input Unit with SelfVerify ...................................................... 49 BN-310 Single Relay Output Unit ...................................................... 50 BN-201 Monitoring Input Unit ............................................................ 51 BN-320 Interface with SelfVerify ....................................................... 52 BN-320/2 Door Control Unit .............................................................. 53 BN-320/4 Monitoring and Control Unit .............................................. 54 BN-320/5 Sprinkler Control Unit ........................................................ 55 BN-330 Interface Unit for Conventional Loops.................................. 56 AutroSense 75 Aspirating Smoke Detector....................................... 57 AutroBeam 25 Infrared Beamdetector .............................................. 58 AutroBeam 100 Infrared Beamdetector System ............................... 59 9. Reader’s Comments .........................................................61 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 4 Introduction 1. Introduction 1.1 About the Handbook This document provides information on how to connect detectors and other loop units to the interactive fire detection systems Autroprime and AutroSafe. Note that some loop units can be connected to AutroSafe only (the indication “AutroSafe only” is written in the beginning of these chapters). Autronica’s interactive fire detection systems offer a wide range of fire alarm detectors, manual call points and input/output units, control units and alarm units that are developed and approved according to European directives (CPD) requiring EN 54 compliance. Both input and input/output units are also available with the SV-function. Input units can also be delivered in series 500 and 500/Ex. 1.2 Reference Documentation Detailed information for each loop unit is provided on separate data sheets. 1.3 The Reader This handbook is intended for technical personnel. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 5 Detectors 2. Detectors 2.1 Connecting Detectors I/O Unit Detector Manual Call Point BN- 320 BRANNALARM Tilpasningsenhet K N U S G LA S SE T TRYK K HER P RES S H ER E B R EA K G LA SS FIR E ALARM Interface uni t N r. Loop Driver Module No. BN- 320 BRANN ALARM Tilpasningsenhet FIRE ALARM Interface uni t Nr. No. Input Output 1 - IN 2 - OUT 3 + COMMON 4 - LED 2.2 LED Connection on Detector Input Output BU-46 + Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 6 LED Detectors 2.3 Connection of Branch-off If necessary, a branch-off can be connected to a detection loop if the existing cable layout requires this, but this is not recommended, as the safety will be reduced. To ensure a correct addressing of the detectors on a branch-off when configuring the system, there can not be more than one branch-off per detector. For safety reasons, the number of detectors on each branchoff must be kept to a minimum, as the detectors on a branch-off will not operate in case of a break or shortcircuit on the branch-off. The absolute maximum number of detectors on a branch-off (or an open loop) is 32. NOT Accepted! Accepted Branch-off Loop NOTE: Always connect a branch-off to terminal 2 (-) and 3 (+). Branch-off Loop Main Loop Input Branch-off 1 - IN 2 - OUT 3 + COMMON 4 - LED Output Branch-off + + Next detector on branch-off Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 7 Detectors 2.4 Detector Head / Base Alignment LED Alignment Location for tagname sticker LED 2.5 Detector Label AUTRONICA FIRE & SECURITY INSPECTIONSERTIFICATE REFAFS- 0842 OPTICAL DETECTORBHH320 ID 001 1998 239 0001 ID 001 1998 239 0001 EN54/7 CE Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 8 Detectors 2.6 Detector Locking Mechanism 2.6.1 Detector Base In the detector base a small locking nub will keep the springloaded tongue in an open position to prevent the detector head from being locked. If the locking nub is removed before mounting with a pair of cutting nippers or similar, the detector head will enter a locked position. Locking nub I Detector base with locking nub 2.6.2 Detector head The new springloaded tongue (figure 3) on the detector head will lock the head in a correct position if the locking nub has been removed before mounting. Springloaded tongue Detector head with springloaded tongue Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 9 Detectors 2.6.3 Removing a locked detector head To remove a locked detector head, use a suitable tool (for example a paper clip or similar) to push the springloaded tongue in, and simply turn the detector head counter-clockwise. Use this hole to access and release the locking mechanism. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 10 Detectors 2.7 Detector Dust Covers Autronica detectors are supplied with a dust cover. To avoid possible contamination of the detector chamber during installation, these should remain in place on the detector until commissioning is started. IMPORTANT: LEAVE DETECTOR DUST COVERS ON UNTIL COMMISSIONING IS STARTED Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 11 Manual Callpoints 3. Manual Callpoints I/O Unit Detector Manual Call Point BN- 320 BRANNALARM Tilpasningsenhet K N US G LAS SE T TRYK K H ER P RE SS H ER E B REA K G LASS FIRE ALARM Interface unit Nr. Loop Driver Module No. BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. 1 2 3 4 5 1 6 2 Manual Call Point BF-300V2 BF-510WP-H 3 4 5 6 Connector on Manual Call Point Wires on Detection Loop Wires on detection loop BF-300V2/ BF-510WP-H 1 Pos (+) in Pos (+) in 2 Pos (+) out Neg (-) in 3 Neg (-) in Pos (+) out 4 Neg (-) out Neg (-) out 5 Internal connection Internal connection 6 Internal connection Internal connection Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 12 Input and Output Units 4. Input and Output Units 4.1 BN-180 AutroKeeper The AutroKeeper is physically placed between the loop controller (BSD-310) and the detection loop and thus controlling/providing the loop controller access to the loop. Description Pin number 1 TTL COM 2 TTL IN 3 TTL OUT 4 5 6 7 8 9 10 11 12 13 14 15 16 GND 24V IN 0V IN FAILSAFE COM FAILSAFE NO OUTLOOP + OUTLOOP INLOOP + INLOOP OUT + OUT IN + IN - DIN rail conn. 1 DIN rail conn. 2 DIN rail conn. 3 DIN rail conn. 4 DIN rail conn. 5 Pin no. 1-4 5-8 24V IN 0V IN Not used Not used GND Debug port (internal use only) Debug port (internal use only) Debug port (internal use only) Power In (Green LED) Power In FailSafe Rel. (future) FailSafe Rel. (future) To “first” Loop Unit --“-To “last” Loop Unit --“-To Loop Driver’s IN + To Loop Driver’s IN To Loop Driver’s OUT+ To Loop Driver’s OUT Power In Power In Pin no. 9-12 13-16 Pin no. 1-5 (DIN rail connector) Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 13 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 14 Patented component to meet the new SOLAS requirement BN-180 as Active BN-180 as Standby Input and Output Units IN +4 -5 -2 OUT +1 Loop Driver Module BSD-310 -16 IN OUT +13 -14 +15 IN +11 -12 -10 OUT +9 AutroKeeper BN-180 Fire Alarm Control Panel BS-420 Primary System 2 1 3 3 1 2 2 1 3 3 1 2 IN -10 OUT +9 +11 - 12 IN +15 -16 -14 OUT +13 AutroKeeper BN-180 IN OUT +1 -2 +4 -5 Loop Driver Module BSD-310 1 INT 1 INT 9 CTS 10 GND 10 GND 9 CTS 7 RX 3 TX Termination Block 7 RX 3 TX Communication Module BSL-310 Page 15 15 GND Port 1 16 IE Port 1 28 IE Port 0 14 RX Port 1 13 TX Port 1 27 GND Port 0 26 RX Port 0 25 TX Port 0 AFB B’ 5 3 AFB B 9 11 AFB A’ AFB A AutroFieldBus Protocol Converter BSD-321 AFB A’ AFB A 1 2 AFB B’ 6 Termination Block 5 AFB B Fire Alarm Control Panel BS-420 Secondary System Input and Output Units Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Input and Output Units 4.2 BN-221/01 Extinguishing Control Unit The extinguishing control unit BN-221/01 is an interface unit which monitors and controls extinguishing equipment. The extinguishing equipment is powered from a separate 24 VDC supply. The interface unit is used in the AutroSafe interactive fire detection system, and it is connected directly to a detection loop. The extinguishing equipment is powered from a separate 24 VDC supply. The interface unit is used in the AutroSafe interactive fire detection system, and it is connected directly to a detection loop. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 16 Input and Output Units 4.3 BN-221/02 Monitored Output Unit, 7A Relay The monitored output unit, 7A relay (BN-221/02) is connected directly to the detection loop in the AutroSafe interactive fire detection system. It controls and monitors external equipment. Typical applications are notification devices such as horns, strobe lights, indicating light etc. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 17 Input and Output Units 4.4 BN-303 Single Monitored Input Unit The Single Monitored Input Unit BN-303 has been designed for use with Autronica’s fire detection systems, Autroprime (version 1.1.0 or newer) and AutroSafe (version 4.3.1 or newer), and includes the SelfVerify function. All connections are made to the screw terminals numbered 1-8. Screw terminal 1 2 3 4 5 6 7 8 Description AL_Com In (+) AL_Com In (-) AL_Com Out (+) AL_Com Out (-) Input (+) Input (common) Not in use Not in use Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 18 Input and Output Units 4.5 BN-303/LS Local Alarm Delay Unit The local alarm delay unit BN-303/LS enables delay of alarm routing outside the local area which the unit is connected to (Autroprime; 1 detection zone, AutroSafe; up to 10 detection zones), plus temporary stop of smoke detection in the local area. Loop in + - - + Loop out Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 19 Input and Output Units 4.6 BN-304 Single Monitored Input/Output Unit The Single Monitored Input/Output Unit BN-304 has been designed for use with Autronica’s fire detection systems Autroprime (version 1.1.0 or newer) and AutroSafe (version 4.3.1 or newer), and includes the SelfVerifyfunction. All connections are made to the screw terminals numbered 1-8 Screw terminal 1 2 3 4 5 6 7 8 Description AL_Com In (+) AL_Com In (-) AL_Com Out (+) AL_Com Out (-) Input (+) Input (common) Relay Contact Relay Contact Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 20 Input and Output Units 4.7 BN-305 Dual Monitored Input/Output Unit The Dual Monitored Input/Output Unit BN-305 has been designed for use with Autronica’s interactive fire detection systems, Autroprime and AutroSafe, and includes the SelfVerify function. All connections are made to screw terminals numbered 1-12. Terminal 1 2 3 4 5 6 7 8 9 10 11 12 Function AL_Com In (+) AL_Com In (-) AL_Com Out (+) AL_Com Out (-) Input 1 (+) Input 1 (common) Relay 1 contact Relay 1 contact Input 2 (+) Input 2 (common) Relay 2 contact Relay 2 contact LED connectors Terminal J2.1 J2.2 J2.3 J2.4 Function LED1 + (LED Activate) LED1 - (LED Activate) LED2 + (LED Fault) LED2 - (LED Fault) LED connector: A pin header enables the option to add LED indicators. The indication is a short blink at 0,5Hz period. LED activate: The input or output is in Activation condition. LED fault: There is a fault on the input or the unit itself. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 21 Input and Output Units 4.8 BN-307 Monitored Fire Alarm Device Control Unit The Monitored Fire Alarm Device Control Unit BN-307 has been designed for use with Autronica’s fire detection systems, AutroSafe and Autroprime. 7 Al_Com + in 1 2k * 8 Al_Com - in 2 Al_Com + out 3 Al_Com - out 4 BN-307 5 6 +24V DC 0V DC *End-of-line resistance 2kohm (+/- 5%) LED1 Activate LED2 Fault Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 22 Input and Output Units 4.9 BNB-330A Conventional Loop Interface The Conventional Loop Interface BNB-330A is a 2 wire interface unit for interfacing conventional detectors and manual call points onto Autronica’s interactive fire detection systems. BNB-330A replaces BNB-330 and may be used on all the same systems. AL_Com IN AL_Com OUT 9 10 11 12 + - + - 1 ALARM OUT 2 Open = normal Closed = alarm BNB-330A EN54-4 POWER SUPPLY UNIT 13 +24V 14 24V A 0V Loop Powered Conventional Detector Interface 1 + 5 32 (MAX) EOL CONV - 6 Connectors Terminal Function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Alarm Out1 Alarm Out2 N.A. N.A. Conv + Conv N.A. N.A. Loop+ Loop InLoop+ Loop Out 24V 0v N.A. N.A. Bottom connectors Terminal Function 1 2 3 4 5 24V 0V N.A. N.A. Chassis ground Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 23 Input and Output Units 4.10 BNB-331 Conventional Loop Interface The Conventional Loop Interface BNB-331 is a 2 wire interface unit for interfacing conventional detectors and manual call points onto Autronica’s interactive fire detection systems. AL_Com IN AL_Com OUT 9 FAULT RELAY 10 11 12 + - 7 PSUFlt 8 + - 1 ALARM OUT Closed = Normal Open = fault* 2 Open = normal Closed = alarm 3 BNB-331 13 EN54-4 +24V POWER SUPPLY UNIT 0V 14 24V A FAULT OUT 4 Loop Powered Conventional Detector Interface Open = normal Closed = fault 1 + 15 +24V 16 CONV. BRANCH 24V B 0V - 5 32 (MAX) 6 * Dipswitch dependent Connectors Terminal 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Function Alarm Out1 Alarm Out2 Fault Out 1 Fault Out 2 Conv + Conv PSUFlt_IN* PSUFlt_0V* Loop In + (Al_Com) Loop In - (Al_Com) Loop out + (Al_Com) Loop Out - (Al_Com) 24V A 0v A 24V B* 0v B* Bottom connectors Terminal Function 1 2 3 4 5 24V A 0V A 24V B 0V B Chassis ground Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 24 EOL unit Input and Output Units 4.11 BN-500/EX Input Unit with SelfVerify BN-500/EX is an input unit for use in hazardous area zone 0, 1, 2. It must be connected to the approved barrier BZ-500. 1 2 3 4 5 6 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 25 Input and Output Units 4.12 BN-500/N Input Unit with SelfVerify 1 2 3 4 5 6 BN-500/N 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input * EOL 2 KOHM Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 26 Input and Output Units 4.13 BN-505/EXD Input Unit with SelfVerify BN-505/EXD is an input unit for use in hazardous area zone 1 or 2. 166 145 . 120 100 BNB-300/32 1. + in 2. + out 3. - in 4. - out 5. - input 6. + input SAFE AREA Ex, ZONE-1 BSD-310 Detector Loop for smoke/heat detectors or MCP's LOOP DRIVER (for smoke/heat) BD-505/xxxEXD * CERTIFICATE NEMKO 04ATEX1406 II 2(3)G EEx d [nL IIB] IIC T6 Ta: 70 °C Exd CONNECTION AUTROSAFE Exd nL CONNECTION * BD-505/xxxEXD used as example. Can also be BN-505/EXD Ex, ZONE-2 BSD-310/N ZONE 2 Detector Loop for smoke/heat detectors or MCP's CERTIFICATE NEMKO 03ATEX217X BD-505/xxxEXD * CERTIFICATE NEMKO 04ATEX1406 II 2(3)G EEx d [nL IIB] IIC T6 Ta: 70°C NEMKO 03ATEX217X: EEx nL IIB T4 Tamb: 50°C/70°C SAFETY DATA: The ratio L/R for the loop cable shall not exceed the stated value Lo/Ro: 30µH/O Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 27 Control Units 5. Control Units 5.1 BW-200 Disable Input with Pushbuttons The Disable unit is used to disable one or a number of detection zones. The unit is connected to and powered from the detection loop. The disablement time is configurable. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM Interface unit TRYKK HER B RE AK PRE SS H ER E G LA S S Nr. Loop Driver Module No. BW-200 24V Output * 24V Input LED Steady light when disabled Flashing the last 5 min. of disablement Detection Loop Disable detection zones + + - * 1 or 2 units on each loop: More than 2 units on each loop: Enable detection zones Connect detector loop + (1), and detector loop – (3) to 24V input. Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 28 Control Units 5.2 BW-201 Disable Input with Timer Input Applies to AutroSafe only. The Disable unit is used to disable one or a number of detection zones. The unit is connected to and powered from the detection loop. An external timer controls the disablement time. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM TRYK K HER B RE AK Interface unit PRE SS H ERE G LA S S Nr. Loop Driver Module No. BW-201 External Timer 24V Output * 24V Input LED Detection Loop Connection to External timer + + - * 1 or 2 units on each loop: More than 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 29 Control Units 5.3 BW-202 Day/Night Control Unit with Pushbuttons Applies to AutroSafe only. The Day/Night Control Unit is used for remote operation of the Disable/Enable ‘Immediate Output Action’ commands. The unit is connected to and powered from the detection loop. BN- 320 BRANNALARM Tilpasningsenhet K N U S G L A S SE T FIRE ALARM TRYK K HE R B REAK Interface unit Loop Driver Module PRES S HER E G LA S S Nr. No. BW-202 24V Output * 24V Input LED Detection Loop Day Mode + + - Night Mode - * 1 or 2 units on each loop: More than 2 units on each loop: Connect detector loop + (1), and detector loop – (3) to 24V input. Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 30 Control Units 5.4 BW-203 Day/Night Control Unit with Timer Input Applies to AutroSafe only. The Day/Night Control Unit is used for remote operation of the Disable/Enable ‘Immediate Output Action’ commands. The unit is connected to and powered from the detection loop. An external timer controls the monitored input. BN- 320 BR ANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE AL ARM TRYK K HE R B R E AK Interface unit Loop Driver Module P RE SS H ER E G LA S S Nr. No. BW-203 External Timer 24V Output * 24V Input LED Detection Loop * 1 or 2 units on each loop: More than 2 units on each loop: Connection to External timer Connect detector loop + (1), and detector loop – (3) to 24V input. Use external 24V supply Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 31 Control Units 5.5 BU-200 Remote Alarm Control Unit Applies to AutroSafe only. The Remote Alarm Control Unit is used for remote / local alarm handling from predefined areas / zones. The main purpose of the unit is to facilitate alarm handling without disturbance of people and unnecessary calls to rescue services, for example, the fire brigade. The unit can send acknowledgement and reset to the Fire Alarm Control Panel. The Remote Alarm Unit is connected to the detection loop. Each loop unit can be connected to one Operation Zone. An Operation Zone can have one or more units, but requires separate 24V DC power. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA SSE T FIRE ALARM Interface unit TRYK K HER B RE AK Nr. Loop Driver Module No. 24VDC BU-200 BW-200 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 32 PRESS HERE G LA S S Alarm Units 6. Alarm Units 6.1 Introduction This chapter deals only with alarm units connected to the detection loop, not the ones that are connected to alarm outputs. 6.2 BBL-100 Beacon Indoor Addressable Compact beacon for indoor use enclosed in an IP32C plastic casing. Reliable in operation and robust design. Simple mounting in all relevant directions. - + - Out + Out - + - In + In Detection Loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 33 Alarm Units 6.3 BBR-130 Sounder Adressable with Base BBR-130 is a combined detector base and addressable sounder that is connected directly to the detection loop. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 34 Alarm Units 6.4 BBR-230 Sounder Indoor Addressable BBR-230 is an addressable sounder that is connected directly to the detection loop. - + - Out + Out - + - In + In Detection Loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 35 Alarm Units 6.5 BBQ-130 Sounder/Strobe with Base BBQ-130 is a combined detector base and addressable sounder/strobe that is connected directly to the detection loop. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 36 Alarm Units 6.6 BBQ-230 Sounder/Strobe Addressable BBQ-230 is an addressable sounder/strobe that is connected to the detection loop. - + - Out + Out - + - In + In Detection Loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 37 Detectors for Special Requirements 7. Detectors for Special Requirements 7.1 AutroFlame IR Flame Detector BG-201 The detector is provided with a pluggable terminal block for ease of connection. Wire: Max. 2,5 mm2 / 14 AWG Interactive detection loop connection: 1 + - 2 3 4 Output + Input Terminal: 1 2 3 4 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 38 Detectors for Special Requirements 7.2 AutroFlame IR Flame Detector BG-21 NOTE: For use with conventional fire alarm systems only. Connection to the first/ between detectors: Connection to the last/single detector: Terminal Connection Terminal Connection 1 + in 1 + in 2 - in / out 2 - in / EOL 3 +out / alarm resistor 3 alarm resistor / EOL 4 alarm resistor 4 alarm resistor The above connection between detectors on a conventional loop will secure a fault activation at the panel if one of the connectors are unplugged. 1 2 3 4 1 LOO 2 I + CONVEN IN/OUT + TIONA 3 4 OU + R ALARM RESISTOR J J LOOP STANDAR LEGAC HIGH CONV LOW SENS. Manufacturer label J5 J Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 39 Detectors for Special Requirements 7.3 Fireray 5000 The FireRay® 5000 is a motorised infrared optical beam smoke detector. The detector requires the use of the Single Input Monitoring Unit BN303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for the detector. Function A is used (Alarm condition signalling input). BN 303 BN-303 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 40 Detectors for Special Requirements 7.4 AutroSense Nano The AutroSense Nano High Sensitivity Aspirating Detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense Nano. Function A is used (Alarm condition signalling input). BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SSE SE T TRYKK HER PRESS HER E AK G LA S S B RE REAK SS FIRE ALARM Interface unit Nr. No. Loop Driver Module BN-303 BN-300 BN- 35 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit N r. No. 24V DC AutroSense Nano Detection loop Out + Detection loop In + BN-303 AutroSense Nano 910 FIRE 0V Earth 24V 2K + PRE ALARM FAULT 5 24V 6 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 41 Detectors for Special Requirements 7.5 AutroSense Micra 25 High Sensitivity Aspirating Detector The AutroSense Micra 25 High Sensitivity Aspirating Detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense Micra 25. Function A is used (Alarm condition signalling input, non-latching). BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SET FIRE ALARM TRYK K HER B RE AK Interface unit Nr. No. Loop Driver Module BN-303 BN-300 BN- 35 BRA NNALAR M Tilpasningsenhet FIRE ALARM Interface unit N r. No. 24 V DC AutroSense Micra 25 Detection loop Out + Detection loop In + BN-303 AutroSense Micra 25 1 + 2K 2 3 4 + - - 910 + 24V Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 42 PRESS HERE G LA S S Detectors for Special Requirements 7.6 AutroSense Micra 100 High Sensitivity Aspirating Detector The AutroSense Micra 100 detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN303 unit selects the relevant function for AutroSense Micra 100. Function A is used (Alarm condition signalling input). BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S S E T FIRE ALARM TRYKK HER B RE AK Interface unit Nr. No. Loop Driver Module BN-303 BN-300 BN- 35 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit N r. No. 24 V DC AutroSense Micra 100 Detection loop Out + Detection loop In + BN-303 AutroSense AutroSense Micra Micra100 25 1 + 2K 2 3 4 + - - 910 + 24V Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 43 PRESS HER E G LA S S Detectors for Special Requirements 7.7 AutroSense 200 High Sensitivity Aspirating Detector The AutroSense 200 detector requires the use of the Single Input Monitoring Unit BN-303. The internal DIP switch S1 on the BN-303 unit selects the relevant function for AutroSense 200. Function F is used (Fault, Pre Alarm and Alarm condition signaling input, non-latching). BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. Loop Driver Module BN-303 BN-320 BN- 35 B R A N N A LA R M Tilpasningsenhet FIRE ALARM Interface unit N r. No. 24 V DC AutroSense 200 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 44 K NU S G LA S SE T TRYKK HER PRESS HER E B RE AK G LA S S Detectors for Special Requirements 7.8 AutroFlame X33AF Multispectrum Infrared Flame Detector BN- 320 BR AN NALAR M Tilpasningsenhet K NU S G LA S SE T FIRE AL ARM Int erf ace unit N r. Loop Driver Module N o. BN-304 24 VDC BN-320 BN- 320 B RA NNA LA RM Tilpasningsenhet FIRE AL ARM Interface unit Nr. No. Alarm signal Power AutroFlame AutroFlameX33AF X33/1 The relay output is required only if the 24V supply for flame detectors needs to be controlled (e.g. latching alarms/faults). In this case BN-304 must be set to function G. If the 24V supply is to be permanently connected to X33AF, it is possible to use BN-303 function A, or BN-304 function A or G. Detection Loop Out + - Detection + Loop In oi TEST 3 (optional) + - 24V DC BN-304 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 45 TRYKK HER B RE AK PRESS HERE G LA S S Detectors for Special Requirements 7.9 Ex ia Approved Detectors Ex ia-approved detectors can be connected to the system. The Ex-Barrier Unit (BZ-500) is used to separate the safe area from the hazardous (Ex) area. A maximum of 20 Ex ia-approved detectors can be mounted as a branch-off from the Ex-Interface Unit on the loop. Detector BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface uni t 2 Loop Driver Module KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS Nr. No. 24VDC Ex Ex-Interface Unit Safe Area Hazardous Area Ex ia-approved detectors Detector on main loop Input + Output 24 V + - Branch-off - BZ-500 Note: The Ex-Barrier Unit BZ-500 is shown upside down on the drawing. 12 10 8 10 Safe Area 7 BARRIER P&F 1.54 6 5 4 3 2 1 3 - BZB-500 EX TERMINALS 11 2 DIN RAIL + 9 11 - 12 NON EX TERMINALS + + 1 Ex-Area + - Ex-Branch for Ex ia-approved Detectors Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 46 Discontinued Products 8. Discontinued Products 8.1 BBR-200 Programmable Electronic Sounders SUBSTITUTE PRODUCT: BBR-230 The Electronic Sounder (BBR-200) has its own address / interface board and can be connected directly to a detection loop. The unit is powered from the detection loop. No external power supply is required. BN- 320 BRANNALARM Tilpasningsenhet FIR E ALARM Interface uni t Nr. Loop Driver Module No. Electronic Sounder w/address/interface board BBR-200 Detection loop out Detection loop in Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 47 K N U S G LA S SE T TRYK K H ER P RE S S H ER E B R EAK G LASS Discontinued Products 8.2 BBR-110 Addressable Socket Sounder SUBSTITUTE PRODUCT: BBR-130 The Socket Sounder (BBR-110) is a combined detector base and addressable sounder. The unit is powered from the detection loop. No external power supply is required. BN- 320 BRANNALARM Tilpasningsenhet KNUS GLASSET FIRE ALARM Interface unit TRYKK HER PRESS HERE BREAK GLASS Nr. Loop Driver Module No. Socket Sounder BBR-110 Detection Detector loop in in Detection Detectorloop loopout out - In: - Out: Common (+ In and + Out): External LED: Terminal connection 1 Terminal connection - out on circuit board Terminal connection 3 Terminal connection 4 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 48 Discontinued Products 8.3 BN-300 Input Unit with SelfVerify SUBSTITUTE PRODUCT: BN-303 BN-300 input unit is used to interface different types of signal devices of ON/OFF-type (for fire alarms) onto the detection loop. BN- 320 BRANNALARM Tilpasningsenhet FIRE AL ARM Interface unit Nr. No. Loop Driver Module BN-300 BN- 35 B R AN N A L A R M Tilpasningsenhet FIRE ALARM Interface unit N r. No. 1 2 3 4 5 6 BNB-300/32 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 49 K NU N U S G LA SSET SSET TRYKK HER PRESS H ERE BR RE E AK G LA S S Discontinued Products 8.4 BN-310 Single Relay Output Unit SUBSTITUTE PRODUCT: BN-304 BN-310 single relay output unit contains a potential free change-over contact which can be activated from a detector or a combination of several detectors in alarm. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM Interface unit Nr. No. Loop Driver Module BN-310 BN- 35 B RANNA LARM Tilpasningsenhet FIRE ALARM Interface unit N r. No. 11 10 1.Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 9 8 7 6 5 1 2 3 4 5. N.A 6. N.A Loop 7. N.A 8. N.A 9. Normally open 10. Normally closed 11. Common Not for use. Relay contact Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 50 TRYKK HER B RE AK PRE SS H ER E G LA S S Discontinued Products 8.5 BN-201 Monitoring Input Unit SUBSTITUTE PRODUCT: BN-303 The Monitoring Input Unit is used for monitoring of fault or other signal contacts from external equipment (technical alarms). BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM Interface unit TRYK K HER B RE AK PRESS H ER E G LA S S Nr. No. Loop Driver Module BN-201 BN- 35 BR A NN A LA R M Tilpasningsenhet FIRE ALARM Interface unit N r. No. 11 2 3 4 5 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input 6. (+) Input 6 BNB-200/01 Four different classes can be configured in order to be able to monitor different setups of the fault contact (s). Each class can be set to latching or non-latching operation. C lass 1 5 6 N .O . 2KO hm 910 O hm C lass 2 5 6 N .C . 2KO hm 910 O hm C lass 3 5 N .O . 2KO hm 6 C lass 4 N .C . 5 2KO hm 6 Class 1: Normal Open contact with ‘activate’ resistor, fault monitored for open and short circuit. Class 2: Normal Closed contact with ‘activate’ resistor, fault monitored for open and short circuit. Class 3: Normal Open contact without ‘activate’ resistor, fault monitored for open circuit. Class 4: Normal Closed contact without ‘activate’ resistor, fault monitored for short circuit. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 51 Discontinued Products 8.6 BN-320 Interface with SelfVerify SUBSTITUTE PRODUCT: BN-304/BN-305 The I/O unit BN-320 is connected to the detector loop to control, monitor or identify external equipment. Typical applications are: Interface for AutroFlame detectors Interface for AutroBeam 25 11 10 9 8 7 1 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 6 2 3 5 4 5. (+) input A 6. (-) input A Loop 7. (+) input B 8. (-) input B 9. Normally open 10. Normally closed 11. Common Relay contact Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 52 Discontinued Products 8.7 BN-320/2 Door Control Unit SUBSTITUTE PRODUCT: BN-305 The Door Control unit controls and monitors fire doors. The unit is connected to the detection loop, and powered from an external 24V DC power supply. BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit K N U S G LA S SE T TRYK K HER PRESS H ERE B R E A K G LA S S Nr. Loop Driver Module No. 24 VDC BN-320/2 BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Int erface unit Nr. No. Output CLOSING OF FIRE DOORS Input A Input B Trigging of electromagnetic doorholder FIRE DOOR Normally closed output. Switch 1 Switch 2 Status Closed Open Door Open Open Open Door in transition Open Closed Door Closed Closed Closed Illegal (fault) Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 53 Discontinued Products 8.8 BN-320/4 Monitoring and Control Unit SUBSTITUTE PRODUCT: BN-305 The Monitoring and Control Unit monitors and/or controls various external equipment such as control of fire dampers, ventilation valves, fans, lifts, plus fire and smoke hatches. The unit is connected to and powered from the detection loop. External equipment must have separate power supply. BN - 320 BRANNALAR M Tilpasningsenhet FIRE ALARM KNUS GLASSET TRYKK HER Interface unit Nr. Loop Driver Module No. BN-320/4 BN - 320 BRANNALAR M Tilpasningsenhet FIRE ALARM Interface unit Nr. No. Output Input A Input B External Equipment External Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 54 PRESS HERE BREAK GLASS Discontinued Products 8.9 BN-320/5 Sprinkler Control Unit SUBSTITUTE PRODUCT: BN-303 The Sprinkler Control Unit is used for monitoring and control of sprinkler systems The unit is connected to and powered from the detection loop. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM Interface unit TRYK K HER B RE AK Nr. Loop Driver Module No. BN-320/5 BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. Input A Sprinkler Flow Switch Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 55 PRE SS H ER E G LA S S Discontinued Products 8.10 BN-330 Interface Unit for Conventional Loops SUBSTITUTE PRODUCT: BNB-331 Applies to AutroSafe only. The Interface Unit for Conventional Loops BN-330 consists of a BNB-330 module* mounted on a DIN-rail inside a PCM-box. The conventional detectors are connected to a two-wire sub loop. The sub loop is monitored for broken line by an end-of line unit BNY-330. The interface unit must have a separate 24V supply. BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SE T FIRE ALARM TRYKK HER Interface unit Loop Driver Module Nr. No. BN-330 24VDC + - Conventional Loop End-of line unit BNY-330 K NU S G LA S SE T T RY KK HER P RE SS H ER E B RE AK G LA S S * Variant: The internal Conventional Loop Interface Module BNB-330 is mounted on a DIN-rail onto other internal modules inside the Fire Alarm Control Panel / Controller where it is powered with 24VDC. + BNB-330 Module Conventional Loop End-of line unit BNY-330 K N U S G LA S SE T TRY KK HE R B RE AK PRES S H ER E G LA S S Terminal Signal 1 + AL-Com in 2 - AL_Com in 3 4 + AL-Com out - AL_Com out 5 + 24V Input 6 0V 7 Conventional loop 15V/24V select 8 9 T-output / Open collector + conventional loop 10 - conventional loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 56 B RE AK PRESS HERE G LA S S Discontinued Products 8.11 AutroSense 75 Aspirating Smoke Detector BN- 320 BRANNALARM Tilpasningsenhet K NU S G LAS SE T TRYK K HER P RE S S H ER E BR EA K G LA SS FIRE ALA RM Interface unit Nr. Loop Driver Module No. 24 VDC AutroSense 75 (BW-75/AUT) Loop Connection AutroSense 75 (BW-75/AUT) 1+ Loop 2+ 3 4 - + 24 V DC - + Loop in + 24 V DC 0V 0V (to next detector) Connection to 24V DC 24V DC in + - 1+ Loop 2+ 3 - 24V DC out + 4 + 24 V DC + 24 V DC 0V 0V Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 57 - Discontinued Products 8.12 AutroBeam 25 Infrared Beamdetector BN- 320 BRANNALARM Tilpasningsenhet K NU S G LA S SET FIRE ALARM TRYKK HER PRESS HERE B RE AK GLA SS Interface unit Nr. Loop Driver Module No. 24 VDC BN-320 BN- 320 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. Alarm signal Reflector AutroBeam 25 AutroBeam 25 24V 1 2 3 4 5 6 7 8 + - + 24VDC - 3 4 ALARM RELAY 5 2k 910 6 7 8 FAULT RELAY 2k C 11 NC NO - + - + 10 8 7 6 5 1 + 2 + 3 - 4 - 9 BN-320 Main loop in + Main - + - loop out Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 58 Discontinued Products 8.13 AutroBeam 100 Infrared Beamdetector System SUBSTITUTE PRODUCT: FIRERAY 5000 BN- 320 BRANNALARM Tilpasningsenhet K NUS G LASSET FIRE ALARM Interface unit Nr. Loop Driver Module No. 24 VDC BN-40A/3 Alarm signal AutroBeam 100 AutroBeam 100 Transmitter AutroBeam 100 AutroBeam 100 Receiver Fire Alarm Control Panel Power (Drawing No. bs-1160) Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 59 TRYKK HER PRESS HERE B REAK G LA SS Discontinued Products Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Page 60 Reader’s Comments 9. Reader’s Comments Please help us to improve the quality of our documentation by returning your comments on this manual: Title: Connecting Loop Units, Interactive Fire Detection Systems, Ref. No.: 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21 Your information on any inaccuracies or omissions (with page reference): Please turn the page Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Reader’s Comments Suggestions for improvements Thank you! We will investigate your comments promptly. Would you like a written reply? Yes No Name: ------------------------------------------------------------------------------------------------ Title: ------------------------------------------------------------------------------------------------ Company: ------------------------------------------------------------------------------------------------ Address: ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- Telephone: ------------------------------------------------------------------------------------------------ Fax: ------------------------------------------------------------------------------------------------ Date: ------------------------------------------------------------------------------------------------ Please send this form to: Autronica Fire and Security AS N-7483 Trondheim Norway Tel: + 47 73 58 25 00 Fax: + 47 73 58 25 01 www.autronicafire.com Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Reader’s Comments Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB, rev. D, 2013-02-21, Autronica Fire and Security AS Autronica Fire and Security is an international company, headquartered in Trondheim, one of the largest cities in Norway. The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing, manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions, including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm systems, public address systems, emergency light systems, plus suppression systems. All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide. The company's strategy and philosophy is plainly manifested in the business idea: Protecting life, environment and property. Quality Assurance Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our products are CE marked and developed for worldwide standards and regulations, and conform with the CEN regulation EN54. Our quality system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression, integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring and control. Autronica Fire and Security AS Headquarters, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Head Office Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Division Oil & Gas, Oslo, Norway. Phone: + 47 23 17 50 50, Fax: + 47 23 17 50 51 Division Oil & Gas, PO Box 416, Farnborough GU14 4AT, UK. Phone: + 47 51 84 09 00, Fax: + 44 84 52 80 20 55 Division Maritime, Suppression/New Build Detection & Alarm. Norway. Phone: + 47 31 29 55 00, Fax: + 47 31 29 55 01 Division Maritime, After Sales/Service Detection & Alarm, Norway. Phone: +47-73 58 25 00, Fax: +47-73 58 25 01 Visit Autronica Fire and Security's Web site: www.autronicafire.com