MSAT-XEE
8.2÷30.2
new
product
Condensing unit
Cooling only
Air cooled
Outdoor installation
Capacity from 26 to 80 kW
The MSAT air-cooled condensing units have been designed for outdoor
installation and for best energy efficiency in relation to reduced size.
They may be combined with terminal units or connected to exchanger coils of
air-handling units.
The main features are:
HIGH
ENERGY EFFICIENCY, especially during operation at partial loads,
thanks to the use of two compressors of different capacity operating on a
single cooling circuit;
SELF-ADAPTING
- The evolved electronics implemented adapt the
operating parameters to the load conditions of the system it is installed in,
optimising consumption, noise and the working life of the components;
COMPACT
SIZE - The units are designed to reduce overall dimensions to a
minimum, a decisive factor to adapt to the features of any building.
functions and features
AIR
Cooling only
Air cooled
R-410A
Outdoor installation
R-410A
Hermetic Scroll
dimensions and clearances
C
AUXILIARY
B1
A2
B
B2
A
A1
CAUTION!For trouble-free operation of the unit it is essential to maintain the safety
distances indicated by the green areas.
244
Size – MSAT-XEE
A - Length
B - Width
C - Height
A1
A2
B1
B2
Operating weight
mm
mm
mm
mm
mm
mm
mm
kg
8.2
1739
721
1287
700
700
700
700
298
10.2
1739
721
1287
700
700
700
700
303
12.2
1739
721
1287
700
700
700
700
323
16.2
1967
1143
1599
700
700
700
700
456
18.2
1967
1143
1599
700
700
700
700
469
22.2
1967
1143
1599
700
700
700
700
490
26.2
2367
1141
1593
700
700
700
700
547
30.2
2367
1141
1593
700
700
700
700
561
The above mentioned data are referred to standard units for the constructive configurations indicated. For all the other configurations, refer to
the relative Technical Bulletin.
technical data
Size – MSAT-XEE
Cooling
capacity
Compressor power input
Total power input
EER
Refrigeration circuits
No. of compressors
Type of compressors
Standard airflow
Standard power supply
Sound pressure level
(1)
(1)
(1)
(1)
(2)
kW
kW
kW
Nr
Nr
l/s
V
dB(A)
8.2
25,7
8,79
6,30
2,78
1
2
SCROLL
2553
400/3/50+N
60
Notes
(1) Saturated suction temperature (SST) = 5°C; Outdoor air temperature 35°C
(2) The sound levels refer to the unit at full load, in the rated test conditions.
10.2
31,3
9,95
10,4
3,01
1
2
SCROLL
2545
400/3/50+N
60
12.2
36,0
12,4
12,9
2,80
1
2
SCROLL
2514
400/3/50+N
60
16.2
43,4
14,1
15,6
2,78
1
2
SCROLL
4965
400/3/50+N
64
18.2
51,6
16,2
17,7
2,91
1
2
SCROLL
4902
400/3/50+N
64
22.2
59,1
20,3
21,8
2,71
1
2
SCROLL
4778
400/3/50+N
65
26.2
72,3
22,6
24,2
2,99
1
2
SCROLL
7196
400/3/50+N
65
30.2
80,1
26,6
28,4
2,82
1
2
SCROLL
6971
400/3/50+N
65
The sound pressure level refers to a distance of 1m from the external surface of the units
operating in an open field.
accessories
KCX
AMRX
■• PGCEX
PM
■• ■• Connection set
Rubber antivibration mounts
Coil protection grilles outdoor air side
Phase monitor
PMX
CBRX
MEN30
MEN15
■• ■• Phase monitor
Unit with remote keypad.
Minimum external air temperature down to -30°C
Minimum external air temperature down to -15°C
Key to symbols:
Accessories separately supplied
REF-DG14B001GB-00
AUXILIARY
■•
Data contained in this document are not binding and may be changed by the Manufacturer without notice.
www.clivet.com
245