AXIS™ 45XA Access Floor Terminal Units Application Data TABLE OF CONTENTS INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7 Benefits of UFAD System . . . . . . . . . . . . . . . . . . . . . . . . 1 • REDUCED LIFE CYCLE COST • IMPROVED COMFORT Basic Concepts of Ventilation . . . . . . . . . . . . . . . . . . . . 3 • TRADITIONAL OVERHEAD AIR DISTRIBUTION • DISPLACEMENT VENTILATION • UNDERFLOOR AIR DISTRIBUTION • TASK AMBIENT CONDITIONING UFAD System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 3 • BENEFITS OF A UFAD SYSTEM WITH ZONE MIXING BOX • APPLICATION CONSIDERATIONS • UFAD SYSTEM CHARACTERISTICS • SUSTAINABILITY (LEED™ POINTS) PRODUCT OVERVIEW. . . . . . . . . . . . . . . . . . . . . . . . . . 7, 8 Carrier UFAD System with Zone Mixing Box. . . . . . 7 • FLOOR PLENUM • DIFFUSERS • UNDERFLOOR SERIES FAN-POWERED MIXING BOX • UNDERFLOOR PERIMETER FAN COIL BOX • FAN-POWERED ZONE-MIXING BOX • CENTRAL EQUIPMENT DESIGN PROCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-17 Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Zoning Decisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 General Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Building Load Considerations. . . . . . . . . . . . . . . . . . . 10 • TWO REGIONS • LOAD ESTIMATING CONCEPTS AND FACTORS • LOAD ESTIMATING CONCERNS Central Equipment Selection . . . . . . . . . . . . . . . . . . . . 11 • FAN STATIC REQUIREMENTS • PRIMARY COOLING AIR QUANTITIES • COOLING COILS • ECONOMIZERS Room Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 • DIFFUSER SELECTION AND LAYOUT • DIFFUSER TYPES AND STLES Zone Mixing Box Selection . . . . . . . . . . . . . . . . . . . . . . 13 Distribution System Design . . . . . . . . . . . . . . . . . . . . . 14 • PLENUM DESIGN CONSIDERATIONS • RETURN AIR DESIGN • DUCTWORK DESIGN Heating System Design . . . . . . . . . . . . . . . . . . . . . . . . . 15 • CENTRAL SYSTEM VERSUS HYBRID SYSTEM FOR PERIMETER ZONES • PERIMETER FAN-COILS WITH LINEAR BAR GRILLES • HEATING INTERIORS WITH CENTRAL EQUIPMENT Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 • CONTROL DESIGN CONCEPTS FOR UFAD SYSTEMS • TYPICAL CONTROL SEQUENCES Cost Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 • INSTALLATION COSTS • ENERGY USAGE • OPERATION AND MAINTENANCE COSTS SUMMARY OF RECOMMENDATIONS. . . . . . . . . . . . 18 INTRODUCTION The concept of underfloor air distribution (UFAD) is not new, however, recent developments in office space usage, sustainable design, and indoor air quality issues have sparked new interest in this design concept. Underfloor air conditioning had its start in computer rooms, at a time when mainframe computers generated considerable heat and required complex cabling. Access floor systems allowed plenty of open space to run cabling and provided a generous pathway to supply large quantities of cooling air below the intense heat generated by the electronics. The natural convection currents of warm air rising allowed cool air to enter low, cool the equipment, and remove the warm air near the ceiling. While today’s computer rooms no longer require this type of cooling, the recent interest in access floor systems in other applications is based on the same needs that made the UFAD attractive for the old computer rooms: reduced life cycle cost and improved comfort. Benefits of UFAD System REDUCED LIFE CYCLE COST — In the computer rooms of the past, the large open floor plenum was a convenient space to run large amounts of cable for power and communications. Today, the open floor plenum can be used to meet a new need. The greatest change in office requirements over the past 15 years has been an ever-growing necessity for voice, data and power connections to every individual workstation. The open floor plenum makes it easier to provide these connections. A recent trend in office design makes use of the open space floor plan to facilitate the relocation of workers into cross-functional workgroups. The IFMA (International Facility Management Association) reported in one of its surveys that, on average, an office worker experiences a move every 51/2 months; this means that 44% of the workers move within a year. The term often used for these types of office moves is churn. The costs associated with these churn moves are some of the highest costs an owner or tenant may face, largely because of the need for cabling moves and changes to the HVAC systems. A UFAD system could greatly reduce the costs associated with churn moves and help lower total building life cycle cost. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. New Book 4 PC 201 Catalog No. 04-51450001-01 Printed in U.S.A. Form 45-1XA Pg 1 605 4-05 Replaces: New Book 3 3 4 4 Tab 6a 7a Tab 4AT1 4AT4 4AT5 IMPROVED COMFORT — The UFAD application in computer rooms was based on the principle that warm air rises. In the computer room, the warm air was generated by hot electrical equipment, but the same principle may be applied to the warm air surrounding people. The Building Owners and Managers Association (BOMA) reported in its “What Tenants Want Survey” that thermal and indoor air quality concerns are two of the top concerns and least met expectations of tenants. Traditional overhead air distribution systems are designed to do a good job of mixing the air in the space and preventing stratification, but they cannot deliver thermal comfort to every occupant and provide personal ventilation without becoming cost prohibitive. Overhead systems may require more fan energy to overcome the static losses that would result from the mixing airflow patterns required within the space. Delivery of ventilation air requires sufficient mixing to assure that the ventilation component is delivered to the occupied breathing region. By applying the principle that warm air rises, air can be provided below the occupants and discharged directly into the breathing region at relatively low velocity. As people warm the air, the air will rise toward the ceiling by natural convection. People only breathe the air in the region that extends from the floor to approximately 6 feet above. Therefore, the space above this region can be treated as a stratified air layer and the load components in this region can be treated differently. The result is that air provided underfloor can be supplied at low pressure and the energy used for space conditioning can be reduced. The ventilation air can be provided in the region where it is needed most, with pollutants moved gently toward the return. Additionally, adjustable diffusers, which discharge air to small areas in the space, may be provided as adjustable by the occupant, which would create a perceived improvement in thermal comfort. The end result is a system that is more energy efficient, comfortable, and provides better ventilation and improved indoor air quality. The application of a UFAD system requires the system designer to view the project from a different perspective than other design projects. The UFAD design process requires special consideration from the schematic stage, through load estimating, to commissioning. This document is intended to provide the designer with some basic guidelines. Further in-depth analysis of all aspects of UFAD design can be found in the ASHRAE UFAD Design Guide. A typical UFAD system is shown in Fig. 1. RETURN AIR AT CEILING STRUCTURAL SLAB UNDERFLOOR PLENUM RAISED FLOOR SWIRL DIFFUSERS PERIMETER FAN COIL PRESSURIZED PLENUM AIR PERIMETER GRILLES Fig. 1 — Typical Underfloor Air Distribution System 2 Basic Concepts of Ventilation TASK AMBIENT CONDITIONING — This system provides airflow from underfloor that is controlled at the workstation. The control is normally accomplished with a small fan that directs an air jet at the occupant within the workstation. TRADITIONAL OVERHEAD AIR DISTRIBUTION — A traditional overhead air distribution system is shown in Fig. 2. Traditional ducted systems with ceiling level supply have relatively high discharge velocities to achieve mixing in the conditioned space. The intention is to fully mix the supply air with existing air in the space. This results in pollutants being recirculated throughout the space. Ideally, this mixing will dilute pollutants in the entire volume of the space with ventilation air, so that the entire room is a uniform mixture of old space air and ventilation air, with adequate ventilation effectiveness. Ventilation effectiveness is the ability of a system to deliver fresh ventilation air into the breathing zone of the occupants. In order to achieve ventilation effectiveness, a traditional system often requires that excess ventilation air be delivered to the space. In addition, heating from overhead and the location of returns often results in less than the ideal mixing. Supply air velocity and ventilation effectiveness are two of the main design features that distinguish underfloor air distribution from a conventional overhead ducted system, as described below. There are three concepts associated with providing floor level cooling, each with distinctive characteristics. DISPLACEMENT VENTILATION — A displacement ventilation system discharges air horizontally near the floor at very low velocities and near laminar flow conditions. The goal is to use only the buoyancy effects to create air motion within the space and to maintain the stratification layer above the controlled region that is not mixed. While this provides excellent ventilation effectiveness in the occupied region, it is not the optimum solution for thermal comfort. The temperature variance from head to toe is much greater than the 3 to 5 degree difference that is accepted as the standard for thermal comfort. UNDERFLOOR AIR DISTRIBUTION — A traditional UFAD system uses the floor space between the structural floor and the access floor as a supply air plenum. A UFAD system uses the same buoyancy principles as displacement; however, the air is discharged into the space with adequate velocity and air pattern required to provide mixing only within the occupied region. In this system, as well as in the displacement ventilation system, the goal is to maintain the stagnant region above the breathing region. The UFAD system provides a more uniform temperature in the occupied region to stay within the comfort envelope. UFAD System Overview — The use of the underfloor plenum in the UFAD system has two major impacts on system design. First, since the air is brought in at floor level, a chance exists for a cold floor or for cold discharge temperatures near the occupant’s feet. Either condition would be objectionable, so the air must be provided at a much warmer temperature than normal air conditioning levels. The accepted level of supply air in a UFAD system is between 61 F to 65 F. This requirement affects equipment selection and operation and also impacts air distribution devices. The second issue is that the large surface area and mass of the structural slab result in a thermal mass that shifts load patterns and creates significant amounts of thermal decay to diffusers located far from the point at which supply air enters the plenum. In a UFAD system, the plenum may be configured using one of two approaches. Under the first method, air is discharged into the plenum at zero or neutral pressure and fans near the outlets draw the supply air from the plenum and discharge it to the space (Fig. 3). Neutral pressure plenums may have less leakage around floor tiles and plenum penetrations, but fan wiring and energy costs for this system negate some of the UFAD system’s inherent benefits. Using the second method, the entire underfloor plenum is pressurized to a relatively low pressure of approximately 0.10 in. wg. In the UFAD system with a pressurized plenum, conditioned air is handled using one of two methods. The first method (Fig. 4) removes the space return air near the ceiling and the entire volume is returned to the air-handler. This method requires special treatment by the air-handler to bypass the required air and condition the required supply amount without losing control of temperature and particularly humidity in the space. The Carrier system (Fig. 5) uses a mixing box located near the space to draw a portion of the return air near the ceiling and then mix it with the supply air to maintain the floor plenum pressure and temperature. Fig. 2 — Overhead Air Distribution System 3 → Fig. 3 — UFAD System with Zero Pressure Plenum → Fig. 4 — UFAD System with Pressurized Plenum and Full Return → Fig. 5 — UFAD System with Pressurized Plenum and Zone Mixing Box 605 4 adjustable pedestals, mounted on two-foot centers, that support the weight of the access floor panels and the loads on the floor above. The concrete floor panels (two-by-two, approximately 11/8 in. thick) are laid into this grid system. The structural floor below is normally sealed to provide a moisture and dust barrier. The primary use of the flooring system is to provide a service and utility space to run cabling for voice, data and power. As a result, the floors can be as little as 4 in. over the structural floor or they may be much higher, depending on the need. When the floor space is to be used as a supply plenum for air distribution, floor heights are normally at 12 to 18 inches. Access floor systems are successfully applied to many types of buildings in both new construction and renovation. However, when these floor systems are applied to retrofit situations, a few special considerations are required. Elevator lobbies and bathrooms that are built on the original structural floor must be raised to the new floor elevation or ramps must be provided to move from the structural floor heights to the raised floor height. Types of Buildings — Underfloor air systems are not an answer for every building, but may represent significant life cycle cost savings when applied to the appropriate buildings. Perimeter zones and spaces such as conference rooms present some interesting challenges for UFAD systems. These spaces have loads that vary greatly with time and that may have air requirements that cannot be handled by 65° F air. These spot cooling situations can be handled in two ways. A fan-powered box can be provided under the floor to increase airflow, or a separate unit can be provided that can use standard 55° F air. A fan coil unit located under the floor can also be used to meet cooling and heating needs. When 55° F air is supplied to zone mixing units, the system may also employ traditional methods used with overhead air distribution, to meet high load requirements. The Carrier approach uses this hybrid system (Fig. 6). Heating along the perimeter also presents challenges for UFAD systems. Terminal units are frequently added to provide the necessary heat. One very common method uses a fan coil unit that contains an electric or hot water heating coil. The fan coil unit would be placed under the floor near the perimeter and would be controlled to overcome transmission losses. BENEFITS OF UFAD SYSTEM WITH ZONE MIXING BOX — The Carrier approach employs standard air-handling equipment and uses duct supply temperatures in the normal air conditioning range, which can best handle the spot cooling requirements that arise on every project. The air is distributed in the space through a pressurized plenum with swirl style floor grilles. The plenum is supplied by a zone parallel fanpowered box with a special DDC (direct digital control) that modulates temperature and controls plenum pressure. The primary damper provides the minimum ventilation air to the zone and maintains plenum pressure. The ECM (electronically commutated motor) style fan motor in the box modulates to mix return air and primary air to maintain the required temperature. Heating and cooling requirements for specialized high load spaces and perimeter zones are handled with conventional overhead systems, underfloor series fan boxes or fan coil units. APPLICATION CONSIDERATIONS Access Flooring Systems — An access floor is a flooring system that is installed above the standard structural floor of the building. This book describes the Haworth Access Flooring System (see Fig 7). This flooring system consists of a matrix of Fig. 7 — Access Flooring System → Fig. 6 — Carrier UFAD Design Solution 5 605 New Construction — In new construction, one architectural benefit to be considered is that ceiling space could be reduced. Since large supply ducts are not required, the ceiling space can be reduced or open ceiling space can be used for lighting and sprinklers, allowing a floor-to-floor height one foot less than standard. Then for every 12 stories of building, an additional story could be added with minimal additional cost in the building shell cost. In buildings of fewer than 12 stories, the reduction in height would result in a reduction of overall building shell cost. In new construction spaces, the best applications are offices with open plan construction and buildings in which frequent office changes are anticipated. Owners can benefit from the reduced costs of moving offices and the required communications and wiring. UFAD systems may also be used successfully in other types of space with mostly internal loads and open plan construction, as found in some schools. In general, small spaces within a building are not well suited to underfloor air systems. Nor does a UFAD system make good sense in a building that has a very high ratio of perimeter to interior space, or buildings with many spaces that have highly variable loads. Retrofit Buildings — A UFAD system is a good choice in a retrofit situation where the building characteristics make overhead air distribution systems difficult to apply. Recent trends in downtown revitalization have led to the rehabilitation of old warehouses and other existing structures into offices. There may be costs associated with the relocation of elevators and plumbing connections, however, the savings and ease of providing the cabling services and air distribution under the floor may well offset those costs. In addition, the benefits of improved thermal comfort and indoor air quality may make the space even more attractive to tenants. Special Applications — Another good fit for a UFAD system is in a building with very high ceilings and no place to run overhead air distribution. Some places of assembly (meeting rooms, churches, auditoriums) fit into this category. Again, open plan and internal load concentration are the factors common to successful applications. UFAD SYSTEM CHARACTERISTICS — A UFAD system offers several benefits over traditional systems. Thermal Comfort — A UFAD system provides a higher level of perceived comfort by allowing the occupant to adjust a diffuser and achieve a degree of climate control. The system also offers an increase in actual thermal comfort, since air distribution diffusers provide good head-to-toe temperature variations without disrupting the benefits of a stratification region. Ventilation Effectiveness — Fresh air supply is introduced to the space low. As the air warms, the warm air rises and carries pollutants toward the ceiling (see Fig. 8). Rather than mixing the air within the entire space, fresh air is provided to the breathing region. In ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) Standard 62, Table 6.2, ventilation efficiency of UFAD systems is listed at 100%. This ventilation method may actually result in efficiencies greater than 100%, although this has not yet been documented. In addition, the perceived indoor air quality is better. Although it is not recommended, total ventilation airflow potentially could be reduced because of the greater ventilation effectiveness of the system. Energy Usage — The lower fan static requirements of UFAD systems may provide significant energy savings when compared to overhead air systems. Economizer hours of operation may increase energy savings as well, depending on the local climate. Fig. 8 — Thermal Plume Effect Reduced Life Cycle Costs — Based on the reduction in costs associated with office churn, UFAD systems may have better total life cycle costs. In addition, the energy efficient design helps to reduce the life cycle costs. Reduced Floor-to-Floor Height — The ability to reduce the floor-to-floor height by up to one foot per floor can increase available floor space or reduce shell construction cost. The reduction in floor-to-floor height is based on reducing or eliminating ceiling plenums. Therefore, the need for ceilings to hide light fixtures or piping for sprinklers or to help improve room acoustics must be evaluated. Improved Productivity and Health — Recent studies have drawn a positive correlation between productivity and good indoor air quality and comfort. There are some characteristics of UFAD systems that must be considered when judging the suitability of the technology for a particular application. Cold Floor — One of the most sensitive points of thermal comfort on the body is the ankle. Control of floor temperature can be critical in order to avoid complaints resulting from the radiant effects of a cold floor. When considering floor diffuser placement, sensitivity to cold drafts must also be addressed. Code Issues — Although the concept is not new, UFAD technology as it is applied today is relatively new. Building code officials may not know how to interpret the codes as applied to the technology and may impose unexpected requirements for life safety components such as fire resistant materials, sprinklers, and smoke detectors. Condensation — The thermal mass effects of the plenum floor slabs can have a positive effect on sensible load swings, but care must be exercised when using control schemes that pre-cool the slab and then allow large quantities of potentially moist outdoor air to enter the underfloor plenum. Air supplied to the underfloor plenum must be kept above the dew point temperature of the floor slab. Humidity Control — The impact of local climate and part load control methodologies must be carefully evaluated. Higher supply-air temperatures have the potential to counteract the capability of the system to remove latent heat. The design analysis should evaluate the effects of part load latent control and control methodology to be sure that room relative humidity is kept below 60%. 6 requirement is for interior zones to provide individual control to at least 50% of the occupants. Since UFAD diffusers provide individual control inherently, the system again is nearly an automatic qualification for this point. The third set of points relates to thermal comfort. Since UFAD systems have been shown to provide a high degree of personal comfort with space control parameters that fall within the guidelines of the ASHRAE standard 55 comfort envelope, the system can qualify for this credit as well. The UFAD system has proven to be an excellent system to consider on projects seeking LEED certification. Remember, however, that certification is based on the total building system and the points and overall rating for a specific project are dependent on the design of that project. SUSTAINABILITY (LEED™ POINTS) — There is a nationwide trend toward constructing buildings that are more environmentally friendly to meet green building or sustainable design construction standards. The best-known green building standard is the LEED-NC Rating System® issued by the U.S. Green Building council (LEED stands for Leadership in Energy and Environmental Design). In addition, two new standards have been developed that will have an impact on HVAC design: LEED-CI Rating System® (for corporate interiors) and LEED-EB Rating System® (for existing buildings). The LEED (Leadership in Energy and Environmental Design) voluntary rating system provides standards that rate the building design in 5 categories: Indoor Environmental Quality, Energy and Atmosphere, Materials and Resources, Sustainable Site, and Water Efficiency. This standard sets green building objectives in the 5 categories listed above for which a design can accumulate up to 69 points. The rating system is based on the number of points awarded and goes from a certified level at 29 to platinum level at 52. Some prerequisites must be met for certification, but beyond that, the points may come from any of the 5 categories. Of the total points possible, HVAC related systems account for 40%. The points are based on the entire building as a system, and it is the entire building that is certified, not a particular product or system. Underfloor air systems have the potential to earn points in at least seven areas, primarily in the Indoor Environmental Quality and Energy and Atmosphere categories. The largest points area in the program is for optimizing energy performance in the category of Energy and Atmosphere. This credit varies from 1 point for exceeding the ASHRAE 90.1 energy cost budget (ECB) model by 15% to up to 10 points for a 60% reduction. In most UFAD projects the analysis would involve using the ASHRAE energy cost budget to compare the underfloor system to the energy costs of a VAV (variable air volume) reheat system. The UFAD systems may have a distinct advantage in this area since they incorporate many potential energy savings features. Lower fan static requirements as the result of low plenum pressure distribution will reduce required fan energy. Mechanical cooling requirements and hence equipment size and part load efficiency may be improved due to the use of higher discharge temperatures. Economizer usage may be extended to get more free cooling hours and help reduce part load energy requirements. In general, UFAD systems have the potential to show significant energy savings over the required base system used in the energy budget model. The UFAD system may also qualify for points under the Material and Resources category. Within this category 3 points can be earned for building reuse. If the project involves an existing building, the percentage of building shell reuse would help obtain these credits. UFAD systems lend themselves very well to certain retrofit situations where the building is being renovated to meet the requirements of new technology without destroying the current building structure. UFAD gives the architect a range of options to achieve these goals. Also, depending on the location, it is possible that the floor system used would qualify for the regional credit that requires that the project be within 200 or 500 miles of the equipment manufacturing location. In the Indoor Environmental Quality category, UFAD systems have the potential to qualify for points in 3 areas. This category is the one in which many of the existing certified projects have relied on points from UFAD systems to achieve certification. The first set of points associated with this category is in the area of ventilation effectiveness. As noted earlier, UFAD systems are not rated by ASHRAE as having any advantage in ventilation effectiveness. However, in the current LEED documentation, the UFAD system is implied to have ventilation effectiveness greater than one. As a result, the use of UFAD systems may be a qualifying point. The second set of points addresses system controllability, where the LEED PRODUCT OVERVIEW Carrier UFAD System with Zone Mixing Box FLOOR PLENUM — The space between the access floor and the structural floor is the floor plenum. Using this space as an air distribution plenum requires some special considerations. First, the floor panel seams must provide a tight seal to prevent air leakage from the plenum into the space. In some cases ductwork is run through the space to special variable load areas. Also, the space may need partitioning for life safety or thermal zoning. A typical underfloor plenum is between 12 and 18 inches in height. DIFFUSERS — Room air distribution is accomplished through one of two types of floor diffusers. Interior spaces are controlled through a system of adjustable passive floor mounted diffusers. The Carrier 35BF-R diffuser consists of an adjustable swirl plate located in a mounting basket (Fig. 9). The diffuser is mounted through a hole cut in the concrete floor panel. The basket catches any dirt or spilled liquids and prevents contamination of the space below the floor. The adjustable swirl plate allows the occupants to adjust their diffusers to a comfortable level in their space. The diffusers are designed to achieve mixing of the approximately 65 F degree supply air within a very tight radius of the diffuser and at very low velocity. Typical diffuser airflow is about 60 to 100 cfm per diffuser. A second type of diffuser is used with underfloor series fanpowered mixing boxes and perimeter fan coil units. The Carrier 35BF-D rectangular grille is used to provide an air curtain that washes exterior surfaces with warm or cold air (Fig. 10). These grilles depend on much higher velocities and can be used in various lengths to match the airflow requirements of the mixing box or fan coil unit. A deflection blade of either 0 or 15 degrees can be used to provide the required throw pattern. A version of the rectangular grille can also be installed in a plenum that has a control damper to provide variable volume control to selected spaces. The rectangular grilles can also be used to allow return air from above the floor back down to the underfloor mixing boxes if desired. If used directly in the pressurized plenum, a standard balancing damper can be added to adjust airflow. Fig. 9 — Swirl Plate Style Diffuser — 35BF-R 7 FAN-POWERED ZONE MIXING BOX (45XC) — The 45XC is a parallel fan powered box with a standard Carrier DDC controller (Fig. 13). One box is used for each zone and is mounted in a closet or utility space to control the airflow to the underfloor plenum. The controller is configured for UFAD to control the temperature and pressure of the zone. The box uses standard 55 F supply air from the air handler and blends the air with return air from the zone to provide the 63 F discharge air required in the underfloor plenum. The ECM motor in the box varies fan speed as required to control plenum temperature by varying the amount of recirculated air introduced into the plenum, while the primary air damper simultaneously maintains the plenum pressure by controlling the amount of primary air introduced into the plenum. Minimum damper position stops assure that ventilation air is always provided to the underfloor plenum. Plenum pressure is maintained at approximately 0.1 in. wg. CENTRAL EQUIPMENT — Since Carrier’s UFAD system uses a zone mixing concept and air is supplied to the zone mixing box at normal unit design conditions, special air-handling equipment is not required. Mixing boxes may be used with air handlers in chilled water or direct expansion type systems or with many types of packaged VAV equipment as well. Careful psychrometric analysis should be made of coil entering conditions to be sure the coil will meet the specific leaving air conditions for entering sensible heat factors that may be higher than normal. Part load operating conditions in terms of coil control or staging should be evaluated to be sure room humidity levels can be maintained below 60% relative humidity. Economizers should be used with all system types where local climate permits and should use an integrated differential enthalpy type control. Because of low static pressure requirements, fan sizes may be lower than conventional overhead systems. Due to varying air volumes to the zones, the use of variable frequency drive (VFD) is recommended; the VFD will also improve system efficiency. The use of high-quality filtration is recommended since a prime consideration of the UFAD system is good indoor air quality. Fig. 10 — Rectangular Grille with Plenum — 35BF-D UNDERFLOOR SERIES FAN-POWERED MIXING BOX (45UC) — The 45UC unit is designed to fit underfloor in the space between pedestals and the grids of the access flooring system (Fig. 11). Sizes range from 280 cfm to 1200 cfm. These units are used for perimeter spaces, conference rooms and other spaces with a highly variable load pattern. Typically, these fan-powered boxes use supply air from the floor plenum and increase the volume delivered to the room to meet the variable needs. The same style box can be used when ducted primary air is required to meet high thermal load requirements. Heating can be provided with either hot water coils or electric heaters. UNDERFLOOR PERIMETER FAN COIL BOX (42KC) — The 42KC fan coil box can be used for spaces with variable load patterns and are well suited to addressing heating requirements of perimeter zones (Fig. 12). Available in sizes from 325 to 2800 cfm, these fan coil units also fit underfloor in the space between pedestals and the grids of the access flooring system. Heating can be provided with either hot water or electric heat coils. Fig. 11 — Underfloor Series Fan-Powered Mixing Box — 45UC Fig. 13 — Fan-Powered Zone Mixing Box — 45XC Fig. 12 — Underfloor Perimeter Fan Coils — 42KC 8 DESIGN PROCESS • Perimeter zone size may be restricted by ASHRAE 90.1 requirements for exposure zoning and limits of 50 ft of linear wall per exposure. • Zone-mixing terminals should be located in vertical equipment closets. This approach will occupy some useable floor space, but is a better choice than locating the units within the plenum. Locating the terminals outside of the plenum makes maintenance easier and minimizes obstructions within the plenum. • Zones that include conference rooms and rooms with plants, process or large equipment or solar loads may have high cooling or humidity loads. The designer should condition these spaces with traditional VAV terminals using lower temperature primary air (50 to 55 F). The Carrier hybrid system design will require smaller air handling equipment and ductwork. Design Considerations — When designing a UFAD system, it is important to keep in mind certain differences between the UFAD system and a traditional overhead mixing system. Following are key concepts to be considered to avoid incorporating elements of a traditional system that are not desirable in a UFAD system. • Underfloor systems work best when a stratification layer is established at 6 feet above the access floor. This creates a partial displacement ventilation effect within the room and improves ventilation effectiveness, contaminant control, heat capture, and reduces loads within the space, transferring them directly to the return air. • Airflows must be closely matched to the loads within the occupied region so that design requirements do not “over air” the space, which would disrupt the partial displacement ventilation effect. • Mixing occurs only within the occupied region and occurs so efficiently that a 3º to 5º F temperature gradient is typical, meeting ASHRAE 55 comfort limit. • Supply airflow should not include excessive safety factors; this will lead to “over airing” the system, resulting in many occupant discomfort complaints and the loss of the stratification layer. General Layout — In terms of general layout, a UFAD system may be thought of as an inverted conventional overhead system. A UFAD system is similar to a traditional system in the following ways: • Central cooling and heating equipment, as well as ductwork mains and branches to zone mixing terminals, can be nearly identical to traditional overhead systems. • Zoning occurs in much the same way as with other systems, but because of the duct mains above and zoned distribution below, multiple vertical duct drops and equipment chases must be strategically located around the floor plate. The following layout considerations are unique to the UFAD system design: • When using zone fan powered mixing boxes above the access floor, the chases must provide adequate room to locate the terminal as well as provide required service clearances (Fig. 14). • Diffusers are located in the access floor, much closer to the occupants, so special care must be used in their layout. Since the UFAD system is a non-ducted system, relocation of diffusers can be accomplished simply by swapping floor panels. Since UFAD systems work best with uniformly loaded thermal areas, high load zones and variable load zones should be managed with traditional systems, creating an overall hybrid system that utilizes the best features of both types of systems (Fig. 15.) Zoning Decisions — The underfloor air supply plenum used in a UFAD system requires that the following factors be considered when making zoning decisions. • Thermal decay refers to the increase in cooling supply air temperature resulting from heat transfer to the floor slab and access flooring. Zone maximum travel distance is measured from the terminal discharge into the plenum to the farthest diffuser. Thermal decay will limit the zone maximum travel distance to 50 to 60 ft. This means that from a typical core location, the maximum zone size would be 120 ft by 60 ft, or 7200 sq ft or less. • Open area zones that have loading differences are hard to “isolate” from one another without the use of plenum barriers beneath the access floor. However, too many barriers will limit accessibility and reduce the ease with which rezoning and utility changes may be made in the future. • Zones with high heating loads, such as exterior walls with glazing, may benefit from the use of ducted linear bar diffusers that deliver the conditioned air to the load point without significant thermal decay. Ductwork should be insulated to prevent loss of cooling capacity. Fig. 14 — UFAD with Zone Mixing Box 9 Fig. 15 — Carrier UFAD Design Solution Building Load Considerations TWO REGIONS — The UFAD system depends on establishing two regions: The occupied region and the stratification region (Fig. 16). Tests have shown that loads that occur in the upper stratified layer do not affect the occupied region, however, there is no computerized load-estimating program that can model this condition. The designer must take into account these two regions when assigning loads. Using too many safety factors in the occupied region or being overly conservative in assigning loads may prevent the system from achieving the benefit of a reduction in airflow requirements for the space. LOAD ESTIMATING CONCEPTS AND FACTORS — The following items address those areas that require either manual output adjustment or computer program input modifications to allow designers to more closely model UFAD systems and correctly assign loads and set zone airflows. • For stratification to benefit cooling loads, floor diffusers should mix the air within a tight radius and the throw should not exceed 4 to 5 feet, so that that it will not affect the height of the stratification layer, which typically starts at 6 feet. • Lighting energy is predominantly radiant energy, so only 1/ of total watts should be assigned directly to the upper, 3 unoccupied region. When return air is taken through the light troffers, a greater portion of the total watts used (up to 50%) can be assigned to the unoccupied region. • Exterior wall conductive load is still transferred into the zone as predominantly radiant (often over 60%), so only 1/ of the unoccupied wall area load should be assigned 3 to the unoccupied region. NOTE: Lowering the zone ceiling height to the midpoint value of the unoccupied region would allow most computerized load programs to automatically assign the loads addressed above to the return air. • Transmitted solar loading comes into the space as 100% radiant, unless inside shading is used. Since manually adjusted shades cannot be counted on when sizing equipment or setting airflows, do not assign any transmitted solar load to the unoccupied region. Fig. 16 — UFAD Design Load Concepts • Absorbed solar loading becomes over 1/3 convective, so an appreciable portion of this amount can be manually assigned to the upper stratified layer, especially if wall-washing linear bar supply registers and overhead perimeter return are used in the room air distribution design. • People load should always be assigned 100% to the occupied region. • Equipment loading should not be assigned to the unoccupied region unless specific return register placement is used to capture a portion of that load with the return air, or it is believed that aggressive thermal plumes will develop and carry a substantial portion of the load through the stratification layer. • Infiltration loads always remain within the occupied region and ventilation loads always remain a part of the central equipment coil loading. 10 When the loads have been run and certain manual adjustments made, the designer should be able to define two regions: QOCCUPIED for the lower mixed region, and QUNOCCUPIED for the region above, which is the stratification layer. With these loads the designer can then calculate the following required design parameters: 1. Solve for CFM required in the occupied region. (This is the air supply that must be supplied by the underfloor supply diffusers and zone mixing box total air flow.) CFMRoom = QOccupied/(1.1(TRoom –TPlenum–Supply)) Equation 1 TRoom is the thermostat set point for the space TPlenum-Supply is assumed discharge air temperature in the plenum 2. Solve for CFM primary air required. (This is the air supply from the air handler and is used in zone box selection.) CFMzone–Box = QOccupied/(1.1(TRoom –TAHU–Supply)) Equation 2 TRoom is the thermostat set point for the space TAHU-Supply is assumed primary air temperature into the zone-mixing box 3. Solve for TRETURN in the stratified, or unoccupied region. (This is the return air temperature to the zone mixing unit and the AHU before outdoor air mixing occurs.) TReturn = QUnoccupied/(1.1xCFMRoom) + TRoom Equation 3 TRoom is the thermostat set point for the space LOAD ESTIMATING CONCERNS Airflow — Be careful not to “over air” the space. When working with Equation 1, the space set point temperature, TRoom, can be increased to be closer to the temperature at the stratification layer; this will help to more accurately determine the actual minimum airflow required to meet the occupied region load. Similarly, in Equation 3, TRoom can be adjusted to the higher value at the stratification layer, remembering that with UFAD systems and the partial displacement effect, return air temperatures are quite a bit higher than the zone set point temperature. Floor panel temperature will be midway between room set point and plenum temperature, creating both a radiant cooling effect and convective heat transfer into the plenum, lowering the required room airflow. Leakage — Leakage is another concern that should be addressed during the design process. Following are leakage sources that should be considered: • Supply air leakage out of the pressurized plenum into unconditioned spaces through construction gaps • Supply air leakage between the floor tiles into the occupied region • Radiant and convective cooling by the lower-temperature floor panels Leakage into the occupied region and radiant and convective cooling from floor panels may result in overcooling the conditioned space. Core vs Perimeter — UFAD systems work best with core areas, open perimeters with limited glass, and similar spaces that have low load variations. These zones tend to be larger and constant volume designs will provide the most cost effective installations with superior IAQ. When load concentrations increase and/or high load variability is present, the requirements for airflow delivery to the space can increase significantly, since UFAD systems are typicaly designed to provide supply air at a higher than usual temperature (65 F) in order to provide a more uniform temperature for the occupants. Adding variable volume equipment would increase system cost. Therefore, perimeter offices with high glazing areas, conference rooms, and areas with large equipment loads are examples of zones where use of dedicated traditional systems make the most sense. The resulting hybrid design makes the most of both traditional mixing ventilation systems with lower cooling supply air temperatures and UFAD benefits of the base design. Central Equipment Selection — While a UFAD system is thought of primarily as a variation in air distribution design, there are many particulars that may affect central equipment selection: FAN STATIC REQUIREMENTS — Central fan energy should be less than required in a traditional system because of the low plenum pressure and reduction in ductwork downstream from the air terminal. Reduced external static pressure on the central equipment is an advantage of a UFAD system. Supply ductwork runs and air pressure drops on the zone terminals leading to the plenums are little different than conventional systems. The same is the case with return ducts, but there is always less than 0.10 in. wg pressure requirement on the plenum and diffusers downstream from the zone terminals. While this savings of 0.25 to 0.50 in. wg appears small, when added to the overall reduction in CFM associated with UFAD’s partial displacement effect, the result is a significant reduction in fan motor horsepower. PRIMARY COOLING AIR QUANTITIES — These quantities can be reduced when potential load credits are realized from the stratification layer partial displacement ventilation effect. COOLING COILS — Temperature and humidity conditions entering the cooling coil should be checked to be sure that the cooling coil selected will be able to achieve the required ADP and bypass factor. In some cases, this may require the use of larger coils, more coil rows, or lower face velocities. Part load loss of humidity control can be a significant issue. A part load analysis should be done to determine if the coil control methodology being used or the refrigeration staging will provide sufficient latent heat removal at part load operation. ECONOMIZERS — Air or water economizers should be used whenever possible for the local climate. The use of an integrated differential enthalpy type is recommend. Use care in setting up the economizer changeover temperature to be sure that the 60% maximum space dew point will not be exceeded. At 75 F room design, this would be an upper limit of 59 F dew point temperature. Room Air Distribution DIFFUSER SELECTION AND LAYOUT — Since the supply air is introduced into the occupied region, it must be warmer than traditional systems. The temperature of the supply air should be approximately 61 to 65 F, or only 8º to 13º F below the usual room cooling set point. In addition, since the occupant is much closer to the diffuser in a UFAD system, the diffuser must be a high induction design to quickly even out the surrounding space temperature and avoid drafts and occupant complaints. The air must mix quickly into the room and not project outside the occupied region so that the stratification layer remains intact. Tests have shown an ideal airflow of 0.6 cfm/sf for good mixing while maintaining the stratification height at 6 feet and keeping the room temperature gradient below 5º F (see Fig. 17). Assuming similar zone loads, the higher supply air temperature of a UFAD system means that larger quantities of air are needed, resulting in greater numbers of diffusers located in the access floor. Since the diffusers have low pressure drops and plenum pressure is very uniform, UFAD designs can be considered self-balancing at the diffuser. 11 To select a passive diffuser, determine the required room CFM with Equation 1 above and divide it by the tabulated airflow for the diffuser at the pressure maintained in the plenum. This will be the approximate number of diffusers required. Adjustments may be made to be sure all spaces receive adequate coverage. # Diffusers=CFMRoom/(Diffuser_CFMat_Plenum_Pressure) Equation 4 Table 1 — Application of Passive Diffusers PASSIVE DIFFUSER STYLE Swirl Floor grilles UNIFORM LOADING Core — open areas & offices Perimeter — open areas Large equip. loads, few people VARIABLE LOADING Base loading Base loading UFAD Systems will create a high degree of personal comfort when designed with floor diffusers that provide a well-mixed region in the lower portion of the room. Warm return air travels upward through natural convection and is carried back to the HVAC system. If the diffusers are not designed properly, the distance the air travels from the diffuser into the space could be excessive, causing stratified air to circulate back into the occupied space. Improper system design could result in poor temperature control and the inability to manage building loads. The 35BF-R Swirl diffuser throw is a function of both airflow and ∆T. Quite often, space loads are over estimated. The difference in estimated and actual space load results from a combination of factors. The first factor is that the listed amp draw of equipment located in the space (such as computers and copy machines) is used to estimate the load. This estimate may vary from the actual heat generated by this equipment when used. The second factor is variable occupancy. Early UFAD systems were designed around 100 cfm/person at a 10° F ∆T from room to discharge air temperature. System analysis proved that with many projects, the airflow (cfm) was too great, which caused over-cooling. This overcooling, combined with the 10° F ∆T, made it difficult to control humidity. As a result of this analysis, many current project designs have elected to reduce the supply temperature in the underfloor plenum from 66° F to 62° F and the supply airflow rate from 1cfm/ft2 to 0.8 cfm/ft2 or less. The optimal airflow/delivery rate of the 35BF-R is 15° F ∆T and 80 cfm per diffuser. This tested performance ensures the ideal throw of 4 to 6 ft within the occupied region. Temperature and velocity profiles for the 35BF-R are shown in Fig. 18. Fig. 17 — UFAD Room Temperature Gradient DIFFUSER TYPES AND STYLES — The Carrier UFAD system uses passive type diffusers that are designed for use in pressurized plenum systems. The two styles, described in the Product Overview section, page 7 are the swirl diffuser (35BF-R) and the floor grille (35BF-D). Each passive style is able to move required air quantities at low plenum pressures (0.05 to 0.10 in. wg) and has very low noise generation values, usually under NC 20. In fact, a white noise generation system within the plenum is often recommended for proper acoustic privacy in open office situations. Table 1 summarizes the application recommendations for passive diffusers. Passive type diffusers have an advantage over active type diffusers in that passive diffusers can be rearranged easily by just moving floor panels; active types require moving fan units, power and control wiring and possibly ductwork. The UFAD diffusers should not be used where liquid spillage potential is high, even though they have a catch basin for incidental spills, and they should not be placed in traffic areas where high rolling loads are expected. 12 8’ 8’ 7’ 7’ 77.0-78.0 76.0-77.0 6’ 6’ 75.0-76.0 74.0-75.0 73.0-74.0 5’ 5’ Distance Above Floor 4’ 72.0-73.0 71.0-72.0 70.0-71.0 4’ 69.0-70.0 68.0-69.0 3’ 3’ 2’ 2’ 1’ Distance From Diffuser Centerline 36" left 18" left 12" left 6" left Center 6" right 12" right 18" right 36" right 36" left 18" left 12" left 6" left Center 6" right 12" right 36"right 18" right 1’ Distance From Diffuser Center Air Speed, FPM 8’ 8’ 175-200 150-175 125-150 7’ 7’ 100-125 75-100 50-75 6’ 6’ 25-50 Distance From Diffuser Center 36"left 18" left 12" left 6" left 9" left 1’ 3" left 1’ Center 2’ 3" right 2’ 6" right 3’ 9" right 3’ 12" right Distance Above 4’ Floor 18" right 5’ Distance Above 4’ Floor 36" right 5’ 36"left 18" left 12" left 9" left 6" left 3" left Center 3" right 6" right 9" right 12" right 18" right 36" right 0-25 Distance From Diffuser Center Fig. 18 — 35BF-R Diffuser Temperature and Velocity Profiles Zone Mixing Box Selection — Each zone (thermostat) will require a dedicated air terminal to satisfy that zone and supply cooling and heating airflow to those areas covered by the zone. Larger, more uniformly loaded open office interior zones can be supplied by parallel fan-powered mixing boxes (PFPMB) all the way up to 3,700 cfm primary airflow (5,800 cfm mixed airflow). Smaller perimeter zones and partitioned interior zones can be handled with the same equipment down to 500 cfm primary airflow. Once cooling loads have been determined, basic terminal selection can occur, using traditional manual or software methods. The designer should keep in mind the following items when selecting units for UFAD systems: • Primary airflow can be supplied by a traditional temperature source (approximately 50 to 55 F) or even from a low-temperature central system, keeping supply ductwork mains and branches small. • Primary airflow is the airflow determined with equation 2 (page 11) and is based on the AHU supply-air temperature. Total airflow is the amount calculated by equation 1 (page 11). • Care must be exercised in the selection of the zone mixing unit to be sure it will provide the total mixed airflow based on calculated entering conditions to the zone mixing unit. The use of selection software is recommended. • Although the units are installed closer to the occupied space, acoustic values should not be a problem if inlet duct pressure levels are kept low. Acoustic attenuation options are also available. • Optional filters on the recirculated air opening are advisable, removing particulate from the return air stream before it mixes with the primary air. Control options that meet the sequences of operation will be required. Control schemes tend to be more complex with UFAD, making a DDC system a logical choice. 13 Distribution System Design — As stated earlier in the General layout section, in a UFAD system the ductwork from the air handler to the zones is essentially the same as any other all-air system. However, since the air delivery occurs underfloor, there are routing and design requirements that are quite different than in a conventional system. One of the major differences to take into account when designing the air distribution system is that air diffusion occurs within the occupied region (up to 6 feet above the finished floor). PLENUM DESIGN CONSIDERATIONS — The following guidelines can be used in developing a pressurized plenum design for HVAC use with passive and active diffusers. • Common plenum depths are 12 to 18 in. from top of slab to top of floor panel, with most panels being ≤ 2 in. thick. Practical minimum plenum depth is 8 in. and plenums deeper than 24 in. offer no HVAC advantages. • Airflow leakage must be minimized with superior construction sealing of all joints, including overlapping joints when laying down carpet squares. (Fig. 19.) If carpet is not used, the floor manufacturer can provide a sealing strip to use between the floor panels. • Sealing of concrete floor slabs reduces particulate generation, although heavier dirt accumulation within the plenum will not be entrained by the low velocity airflows. • Plenum exterior surfaces, both floor and sidewall, should be insulated to minimize thermal losses, which can affect the temperature of the supply air delivered to the furthest diffusers. • Obstructions within the plenum should be kept to less than 50% of the plenum depth to avoid affecting airflow. This is more important with shallow plenums. • Plenum dividers (available as part of a manufactured access flooring system) should be provided when zoning is critical, as part of an architecturally determined smoke barrier, and to separate the perimeter from the core when a hybrid solution is used. • For good acoustic privacy between offices, the floor panels should weigh at least 10 lb/ft2. Placing a physical barrier in the plenum along the common wall line provides additional attenuation. RETURN AIR DESIGN Maintaining Displacement Benefits — When designing the return side of the air distribution system, keep in mind that there are two key elements of the UFAD system that the return air design should support. The first is to help create the partial displacement ventilation effect and the second is to more directly remove local high cooling loading conditions. Placing the return registers on the ceiling or high sidewall will combine with the stratification layer created by the short throw supply diffusers in the floor to achieve the desired overall upward vertical flow of the air within the room. When a space has high cooling loads, such as a copier or a cluster of data terminals, placing the return directly above the area may capture a large portion of the heat, depending on the height of the ceiling and nature of the supply airflow in the immediate area. Recirculating Return Air — Variations in return airflow occur when space humidity control is critical. To control the supply air moisture content during humid summer conditions, cooling coil leaving air temperatures must be lower than the supply air temperatures used with UFAD diffusers. To reheat the air leaving the cooling coil, return air is routed back into the supply airstream, at the zone air terminal. For the zone terminal design to work, warm air is usually ducted back from a ceiling return plenum. Placing ceiling return registers along the exterior walls brings an added benefit of pulling in any thermal plumes that develop under high solar loading conditions, reducing zone cooling load in the summer, and increasing the first stage heating effectiveness in the winter. Fig. 19 — Carpet Used to Prevent Plenum Leakage DUCTWORK DESIGN — One of the main benefits of a UFAD system is the elimination of the requirement for ductwork downstream of the zone terminals. An airflow plenum underneath a raised access flooring system provides low-pressure distribution to the room diffusers. All the ductwork from the air-handling unit to the zone terminals is laid out and sized using the same methods used on traditional mixing ventilation systems. This applies to both supply and return ducts, as well as the outdoor air ductwork. Vertical Drops — One way in which a UFAD system differs from a traditional system is in the vertical drop from the ceiling plenum down into the access floor plenum. Due to the thermal decay of the supply-air temperature within the plenum, travel distance must be limited to 50 to 60 ft from the plenum entry to the furthest diffuser. This will require multiple entry points on all but the smallest system. If shallower plenums are used and frequent obstructions are possibilities, more than the usual number of plenum entry points should be included in the duct design. Figure 20 shows a floor plate of a typical large office building with multiple drops supplying each zone mixing box. Air Highways — One plenum distribution technique used with UFAD systems is an air highway. Air highways are installed within the plenum to distribute zone supply air to multiple points within the plenum. These are typically provided by the access floor installing contractor and must be sized in the same way as normal ductwork. Airflow velocity should be limited to a range of 1,200 to 1,500 fpm in the main duct and to a range of 800 to 1,000 fpm in dampered branch outlets. Diffusers should not be installed in the floor panels above an air highway. Although air highways may serve a useful purpose, they obstruct the placement of electric, communication and data cables under the raised access floors, and may also interfere with other supply air entry points into the plenum. Future rearrangement of furniture and partitions above the floor may require air highway adjustments under the floor, which negates the efficiency and savings possible with a raised floor system. Smoke Partitions and Fire Walls — Whenever plenum areas become too large, they inevitably cross over partitions or walls that, in order to meet life safety code requirements, must extend down through the plenum to the floor slab. The HVAC zoning design should take into account these lines and avoid crossing them. If air must be transferred over the partitions, a hard duct sleeve with the appropriate smoke and/or fire damper installed per code should be used. 14 Fig. 20 — Floor Plan Chase Locations Heating System Design that switches to full heating from the central HVAC equipment during the peak heating times. When the system switches from cooling to heating, normal control strategies for the zone terminals will control mixing of the warmer primary air with recirculated plenum air and adjust terminal fan speed to control plenum pressure. Passive diffusers that had been operating in the cooling mode will operate properly as heating diffusers. CENTRAL SYSTEM VERSUS HYBRID SYSTEM FOR PERIMETER ZONES — The heating method chosen to heat the perimeter zones depends primarily on the magnitude of the load and whether or not simultaneous heating and cooling is required. The need for continuous cooling in many interior zones makes it difficult to switch the central equipment over to heating. If the wintertime temperatures drop below 40 F and the building perimeter has more than 25% glass area, increased supply-air temperatures will be required to counteract the high heating loads and downdrafts along the outside walls. In either of these cases, it is recommended that a separate heating system be designed for the perimeter zones, creating a hybrid system with UFAD heating being reserved for the interior. PERIMETER FAN-COILS WITH LINEAR BAR GRILLES — High heating loads along the outside walls often require higher supply-air temperatures than interior spaces need for morning warm-up or offsetting roof loads. The use of zone fan-coils located in the perimeter plenums is an ideal solution. Using either hot water or electric heating coils allows local boosting of the zone supply air temperatures above those temperatures obtained by recirculating ceiling plenum air that is traditionally single-stage heating for light load conditions. Use of a linear bar grille style diffuser (such as Carrier’s 35BF-CT) is recommended to spread the air out along the perimeter wall and offset the downdrafts that develop. During summer cooling this style of grille is also beneficial in treating the higher cooling loads that are typical along the perimeter of most buildings. HEATING INTERIORS WITH CENTRAL EQUIPMENT — Smaller single-story buildings that do not require simultaneous heating and cooling are often able to use a system Control Systems CONTROL DESIGN CONCEPTS FOR UFAD SYSTEMS — UFAD systems rely on proper design and operation of the controls, as do all systems. Listed below are concepts that should be incorporated into the design to maintain the stratification layer and its many benefits: • Most UFAD systems use pressurized plenums and passive diffusers, requiring some type of pressurization control on either the zone mixing box or central equipment. • Perimeter zone control with passive diffusers requires adjustment of the supply air temperature at the air terminal. This is best accomplished using Perimeter Fan Powered Mixing Boxes (PFPMB) connected to the zone ceiling plenum to mix return air with primary air. • Resetting supply air temperature higher when loads are light allows additional hours of outdoor air economizer cooling, especially in drier climates. However, when economizer cooling is used, special care must be taken not to exceed the relative humidity level of 60% in the space. Also keep in mind that economizer cooling may not meet the spot cooling requirements of high load spaces. 15 • Nighttime pre-cooling, when performed correctly so that condensation does not form on the plenum surfaces, can offset or delay thermal decay of the zone supply air temperature. • Thermostat mounting heights are often being set lower because of ADA (Americans with Disabilities Act), from 48 to 54 inches above the access floor. The lower height is actually a benefit for UFAD systems, because thermostats that are mounted too high will sense the higher temperatures near the stratification layer, requiring that the set point be adjusted upwards to compensate. • Systems that use Parallel Fan Powered Mixing Boxes to control the zone primary airflow for ventilation requirements can use Demand Controlled Ventilation (DCV) to reduce primary airflow in lower occupancy periods, resulting in additional energy savings. • Control requirements of ASHRAE Standard 90.1 should be followed, including setback requirements and optimum start requirements. TYPICAL CONTROL SEQUENCES — Plenum mixing boxes with variable speed fans can provide pressure and temperature control for plenums that serve interior zones and for exterior zones that use a separate perimeter heating system. Typical operating sequences are shown in Fig. 21 and 22. The sequences show basic VAV control of the primary air. The fan provides plenum temperature control by varying the amount of recirculated air introduced into the plenum, while the primary air damper simultaneously maintains the plenum pressure by controlling the amount of primary air introduced into the plenum. A wall-mounted space temperature sensor located in the zone will sense load requirements. As the zone’s cooling load decreases, the fan speed increases, which increases the amount of recirculated air drawn in from the ceiling plenum. Simultaneously, the amount of primary air is reduced to maintain a constant plenum pressure. The terminal fan will operate whenever the primary air source is operating. System Start-up 1. Points 1 to 2 from Fig. 21 indicate that maximum cooling airflow is established by the user-defined maximum cooling plenum pressure set point until the zone comes under control at Point 2. The fan operates at minimum speed. 2. From Point 2, the primary airflow is slowed to reduce plenum pressure until the minimum cooling plenum pressure set point is reached at Point 3. Normal Operation (Cooling — Fig.21) 1. Point 3 indicates that the zone temperature is above the control (heating) set point; the plenum pressure is maintained at the user-defined minimum cooling plenum pressure set point. 2. At Point 4 in Fig. 21, the zone temperature decreases. Increasing the fan speed to introduce more recirculated air, while simultaneously reducing the primary airflow, will increase the plenum temperature. The plenum pressure remains constant at the user-defined minimum cooling plenum pressure set point. 3. As indicated by Points 4 to 5, if the zone temperature continues to fall, the primary air damper will close. Primary airflow will not fall below the user defined minimum ventilation set point at 5. (The minimum ventilation set point may be set to zero.) The fan will provide recirculated air to maintain the plenum pressure set point. Normal Operation (Heating — Fig. 22) 1. Upon receiving a heating signal from the air handler controller, the heating mode will be in effect automatically. 2. If the zone temperature is above the occupied heating set point, the primary air damper modulates to maintain the minimum heating plenum pressure set point at Point 4′. The fan operates at minimum speed. 3. If the zone temperature falls, the plenum pressure will increase until it reaches the user-defined maximum heating plenum pressure set point at Point 5′. The control may be configured to provide constant volume heating for a constant supply of heated air to the zone. Cost Considerations INSTALLATION COSTS — Many owners and developers have found that raised floor systems with UFAD significantly reduce costs associated with space reconfiguration. With the national churn rate now approaching 50%, it is not unexpected to find that many new office buildings use raised flooring. Buildings using UFAD systems have certain cost components that make them more expensive than buildings using traditional systems. There are compensating cost components that lower the overall price premium that currently exists for this application. Since recent job costs show that raised floor can represent a cost increase of from $3 to $5 per square foot, a few of these other cost components should be examined. • The raised floor system is the component with the single largest cost increase. The cost should be justified based on the benefits to the entire service delivery system (HVAC, power, voice and data) and should not be evaluated based on the UFAD system alone. • Local building and fire inspectors may require sprinkler protection if plenum depth exceeds 18 in. and often require smoke detectors within the plenum. • Generally, HVAC costs for central cooling and heating equipment and ductwork mains are no different for UFAD systems than for traditional overhead systems. • Diffuser costs are dependent on the types of diffuser chosen for the majority of air delivery requirements. • If a relatively open underfloor plenum can be used, significant ductwork savings can be realized compared to the typical overhead air distribution system. • Controls costs should be similar to traditional systems with the same zoning requirements. • Raised floor systems have the potential to reduce slab-toslab heights by as much as 6 to 12 in. per floor. This reduction is particularly beneficial in mid-rise and highrise markets with zoning code height limitations. • Testing and balancing savings can be realized from pressurized plenum designs, which are essentially selfbalancing. ENERGY USAGE — UFAD systems have the potential to save energy in comparison to traditional designs. The bulk of these savings come from reduced fan energy associated with lower static pressures and overall cfm reductions created by the stratification layer partial displacement ventilation effect. Documented energy costs savings remain difficult to predict because to date there is no energy simulation software that accurately models UFAD system performance. OPERATION AND MAINTENANCE COSTS — Office building UFAD systems are quite new, making it difficult to get actual owning and maintenance cost data to compare against traditional HVAC systems. Operations and maintenance costs are primarily replacement costs for equipment and labor expenses associated with maintaining the HVAC system and responding to occupant complaints. While many engineers believe that UFAD may prove to be more costly to service, research suggests that the frequency of occupant complaints will be reduced when occupants are given some individual control of their local environment. 16 Plenum Pressure (Maximum Cooling) PLENUM PRESSURE 2 PRIMARY AIRFLOW 5 Maximum Fan Airflow Warmer 1 4 3 Plenum Pressure (Minimum Cooling) PLENUM TEMPERATURE Cool Minimum Ventilation 5 FAN 4 Minimum Fan Airflow OCCUPIED CONTROL SETPOINT OCCUPIED COOLING SETPOINT (HEATING & MORNING WARM-UP) LEGEND ----------- Air Source Supplying Heated Air Air Source Supplying Cool Air Fig. 21 — Carrier UFAD Control Sequence — Equipment Cooling Plenum Pressure (Maximum Heating) 5’ Maximum Heating Airflow Warm PLENUM TEMPERATURE PRIMARY AIRFLOW Minimum Heating Airflow 4’ Plenum Pressure (Minimum Heating) PLENUM PRESSURE FAN Minimum Fan Airflow OCCUPIED CONTROL SETPOINT OCCUPIED COOLING SETPOINT (HEATING & MORNING WARM-UP) LEGEND ----------- Air Source Supplying Heated Air Air Source Supplying Cool Air Fig. 22 — Carrier UFAD Control Sequence — Equipment Heating 17 SUMMARY OF RECOMMENDATIONS 1. Do not eliminate the suspended ceiling. Reduce the depth of the ceiling plenum and use it as a return air plenum, gaining additional airflow benefits from assigning greater amounts of cooling load directly to the return air. 2. Keep plenum depths below 18 in. to avoid potential requirement for sprinklers. 3. Do not use too many zoning barriers in the plenum; zoning barriers will restrict the ease of future rezoning and running of service utilities to various points of use. 4. Use multiple vertical drops to avoid the need for air highways. 5. Limit the underfloor air travel distance from the supply air discharge to the most remote diffuser to a maximum of 60 ft. 6. Do not include excess safety factors; airflow rates should closely match load requirements within the occupied region to avoid “over airing” the system. The ideal airflow 0.6 cfm/sq ft. This will provide good mixing in 7. 8. 9. 10. 11. 18 the occupied regions, maintain the stratification height at 6 ft and keep the room temperature gradient below 5° F. Carefully run loads for both Qoccupied and Qunoccupied, and determine if load credits can be taken; equipment size reduction will benefit the job costs. Select diffusers so that throws are 4 to 5 ft so that the stratification layer is preserved. Use passive swirls in the interior and uniformly loaded large perimeter spaces. Use a hybrid designs in high load/variable load situations. Combining the UFAD system with a conventional VAV system will maximize the benefits of the lower supply air temperatures of the air-handling unit and keep summertime humidity concerns under control. Place return air inlets over heat producing equipment and/ or at the outside wall when high solar loads exist. This strategy will maximize benefit of the partial displacement ventilation effect. DDC controls should be considered basis of design for realizing true UFAD benefits. Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. New Book 4 PC 201 Catalog No. 04-51450001-01 Printed in U.S.A. Form 45-1XA Pg 20 605 4-05 Replaces: New Book 3 3 4 4 Tab 6a 7a Tab 4AT1 4AT4 4AT5