lightning and surge protection

advertisement
LIGHTNING AND SURGE PROTECTION
FOR INDUSTRIAL, COMMERCIAL AND DOMESTIC
ELECTRICAL INSTALLATIONS
WWW.SURGEDEVICES.CO.UK
Servers
Surge Protection Devices and its
Partner Companies have been
solving problems in Lightning and
Surge Protection for over 50 years.
ISO 9001 European designed and manufactured,
state of the art products which exceed the
requirements of the latest Standards and our
competitors’ specifications.
Because we specialise in Lightning and Surge
protection we can offer you the very best, most
cost-effective solution of any company in this field.
We carry out many seminars with consultants
and specialist training organisations as well as
attending exhibitions and conferences both in the
UK and overseas where our specialist knowledge
is renowned.
Schools
Wi
nd
SPD Ltd stands for innovation, quality
and excellent customer service.
FREE technical help.
Assistance with product selection
and design.
We can carry out site surveys.
We can assist with compliance to
the latest requirement of the Wiring
Regulations.
BS7671 and BSEN62305 Lightning
Standards.
domestic
2
Surge Protection Specialists
Tu
rb
ine
s
la
r
So
An introduction to
Lightning Surge Protection
Lightning/Surge protection for electrical and
electronic systems to the new British and
European Standard BS EN 62305-4. Surge
Protection Devices Ltd offer the complete
solution to protect vital systems from damage.
Recently introduced standards put equal
importance on protecting the electrical
installation and electrical equipment as to the
building itself.
Modern micro electronic components are very
sensitive to overvoltages and because many
systems are networked they rely on each other
for the system to operate. If one part of the
system gets damaged due to lightning or surges,
the whole system will not operate.
The consequential losses suffered during such
events i.e. downtime and lost production, can be
very high.
We offer a wealth of experience in helping to
decide which product best suits your needs. Our
catalogue contains our most popular products
however we have many more products and
components to suit a range of applications.
Hospitals
MOD
New Standard BSEN62305-4 1st Sept 2008 & 17th Edition Wiring Regs Amendments 1st Jan 2012.
This new standard replaced BS6651 on the above date,
it is now mandatory to fit a lightning current arrester on
main incoming panels which are situated in buildings
with external lightning conductors or fed by an overhead
line. This type of arrester is designated as a Type 1,
we recommend a combined T1+T2+T3 arrester as this
gives additional surge protection for no added cost. The
minimum discharge capability for a T1 arrester has to be
50Ka 10/350μs.
Panels or sub-distboards feeding external circuits such as
car park lighting, CCTV etc should also have a combined
T1+T2+T3 arrester fitted as standard.
An example of a T1+T2+T3 combined arrester is
10651 LED Level 1, 100Ka 10/350μs.
For panels and sub boards in buildings without
external lightning conductors and fed by underground
cables a T2 surge arrester is sufficient. Sub-distribution
boards or local control panels more than 10 metres
from the main incomer and not feeding external circuits
then a Type 2 surge arrester can be used. An example
of a T2 surge arrester is Part no SY2-C40X.
Final sub-circuits and sensitive electronic equipment,
e.g. fire/burglar panels, PLC’s which are fitted more
than 10 metres from the last surge arrester should
have a T3 surge arrester fitted at the panel or
equipment to be protected. An example of a T3 surge
arrester is SY2-D/LED.
For further information on surge protection
recommendations please call us on 01484 851747.
3
Main Incoming Position
Sub Dist. Board Position
Socket Outlet or Final Sub
PROTECTION AGAINST
PROTECTION AGAINST
PROTECTION AGAINST
DIRECT LIGHTNING
INDIRECT LIGHTNING
SWITCHING OVERVOLTAGES
CURRENTS
EFFECTS
(SURGE ARRESTER)
(LIGHTNING CURRENT
(SURGE ARRESTER)
8/20μs
ARRESTER)
8/20μs
Type 1
Type 2
Type 3
10/350μs
General distribution
of lightning current
when a building
is hit by lightning.
LV power system
protection thanks to
cascaded 3-stage
protection.
SPD Type 1
4
SPD Type 2
Surge Protection Specialists
SPD Type 3
Type 1+2+3 Combined Lightning & Surge Arresters,
DIN Rail Mountable. Fully Compliant to EN/IEC61643-11,
BS/IS/EN62305, BS7671
LPL Level 1 100kA 10/350μs
4 Pole Data Sheet LED Indication Version
Part No. 10651 LED
TP+N
Maximum continuous operating voltage
Uc
275 V AC
Lightning impulse current (10/350)
- charge
- specific energy
Iimp
Q
W/R
25kA
12,5As
156kJ/
Total lightning current (10/350)
L1 + L2 + L3 + N - PE
Itotal
100kA
Max. discharge current (8/20) per mode
Imax
120kA
Nominal discharge current (8/20) per mode
In
50kA
Voltage protection level at Iimp
Up
<1.2kV
Response time
tA
<25ns
Temporary overvoltage (TOV)
UT
335V/5 sec.
Rec. Back-up fuse / MCCB
63A/100A
Max. Back-up fuse (“V” connection)
63AgL/gG
Short circuit withstand capability at max
back-up fuse
Ip
Weight
m
80kArms
1125g
Lifetime
min 100 000 h
Let through voltage (I) 3ka 8/20μs, short
circuit current to BS6651+1999 AppC
600V
Part No.
1065 I LED
Part No. 10651LED
LPL Level 3/4 50kA 10/350μs
2 Pole Data Sheet
Part No. 10650/LED
SP+N
Part No. 10650LED
Maximum continuous operating voltage
Uc
275 V AC
Lightning impulse current (10/350)
- charge
- specific energy
Iimp
Q
W/R
25kA
12,5As
156kJ/
Total lightning current (10/350)
L1 + N-PE 50kA
Itotal
50kA
Max. discharge current (8/20) per mode
Imax
120kA
Nominal discharge current (8/20) per mode
In
50kA
Voltage protection level at Iimp
Up
< 1.2kV
Response time
tA
< 25ns
Temporary overvoltage (TOV)
UT
335 V/5 sec.
Rec. Back-up fuse / MCCB
63A/100A
Max. Back-up fuse (“V” connection)
63AgL/gG
Short circuit withstand capability at max
back-up fuse
Ip
80kArms
Weight
m
565g
Let through voltage (I) 3ka 8/20μs, short
circuit current to BS6651+1999 AppC
600V
Part No.
10650 LED
For 2 pole level 1 100kA 10/350μs specify HS50-50 1+1LED
5
Type 1+2+3 Combined Lightning and Surge Arresters - DIN Rail Mountable.
Fully Compliant to EN/IEC61643-11, BS/EN/IEC62305, BS7671
LPL Level 1 100kA 10/350μs
4 Pole Data Sheet Window Indication Version
Part No. 383811
TP+N
Part No. 383811
64
Maximum continuous operating voltage
Uc
275 V AC
Lightning impulse current (10/350)
- charge
- specific energy
Iimp
Q
W/R
25kA
12,5As
156kJ/
Total lightning current (10/350)
L1 + L2 + L3 + N - PE
Itotal
100kA
Max. discharge current (8/20) per mode
Imax
150kA
Nominal discharge current (8/20) per mode
In
70kA
Voltage protection level at Iimp
Up
<1.5kV
Response time
tA
<25ns
Temporary overvoltage (TOV)
UT
335V/5 sec.
Rec. Back-up fuse / MCCB
63A/100A
Max. Back-up fuse (“V” connection)
63AgL/gG
Short circuit withstand capability at max
back-up fuse
Ip
80kArms
Weight
m
1125g
Lifetime
min 100 000 h
Let through voltage (I) 3ka 8/20μs, short
circuit current to BS6651+1999 AppC
600V
383811
LPL Level 3/4 50kA 10/350μs
SP+N
Part No. 383812
2 Pole Data Sheet
Part No. 383812
Maximum continuous operating voltage
Uc
275 V AC
Lightning impulse current (10/350)
- charge
- specific energy
Iimp
Q
W/R
25kA
12,5As
156kJ/
Total lightning current (10/350)
L1 + L2 + L3 + N - PE
Itotal
50kA
Max. discharge current (8/20) per mode
Imax
150kA
Nominal discharge current (8/20) per mode
In
70kA
Voltage protection level at Iimp
Up
<1.5kV
Response time
tA
<25ns
Temporary overvoltage (TOV)
UT
335V/5 sec.
Rec. Back-up fuse / MCCB
63A/100A
Max. Back-up fuse (“V” connection)
63AgL/gG
Short circuit withstand capability at max
back-up fuse
Ip
80kArms
Weight
m
565g
Lifetime
min 100 000 h
Let through voltage (I) 3ka 8/20μs, short
circuit current to BS6651+1999 AppC
600V
383812
For 2 pole level 1 100kA 10/350μs specify HS50-50 1+1LED
6
Surge Protection Specialists
Lightning and Surge Protection for Industrial,
Commercial and Domestic Electric Installations
Type 1 + 2 + 3 Combined arresters in enclosures
383811 ENC
TP+N
• Type 1 + 2 + 3 combined direct
lightning and surge arrester TP+N
• Complete in high quality IP65
Polycarbonate enclosure
• Meets level 1, 2, 3 + 4 100KA
10/350μs
• Conforms to BSEN62305
EN61643-11, BS7671 Amendment
Wiring Regs.
• Use where building have external
lightning protection or fed by
overhead lines
Dimensions (CM) : H20 x W26 x D11
383812 ENC
SP+N
• Visual and remote indication as
standard
• Low through voltage
• Available with 63AMP backup
MCB (add ‘M’ to part number - e.g.
383811 ENC M)
• Each pole individually replaceable
• SP+N version 50KA 10/350μs.
Level 3-4 if 100KA needed then
please ask for HS 50-50 1+1 ENC
100KA 10/350μs version
• Use 63/100 AMP backup fuse or
MCB
• Cable size to be 25mm² min.
Dimensions (CM) : H20 x W20 x D11
7
Type 1 + 2 + 3 Combined Lightning/Surge
Arresters for DIN Rail Mounting
Part No. 10020
Part No. 10020/4
8
Surge Protection Specialists
Maximum continuous operating voltage
Uc
275 V AC
Lightning impulse current (10/350)
- charge
- specific energy
1mp
Q
W/R
25kA
12,5As
39kJ/
Max. discharge current
Imax
100kA
Nominal discharge current (8/20)
In
20kA
Temporary overvoltage (TOV)
UT
335V/5 sec.
Voltage protection level at Iimp
Up
<1.2kV
Response time
tA
<25ns
Rec. Back-up fuse / MCCB
63 AMPS
Lifetime
min. 100 000h
Short circuit withstand capability at max
back-up fuse
Ip
60kA rms
Weight
m
140g
Let through voltage (I) 3ka 8/20μs, short
circuit current to BS6651+1999 AppC
App C = 600V
Part No. 1 Pole
10020
Part No. 2 Pole
10020/2
Part No. 4 Pole
10020/4
Type 1 + 2 + 3 Combined Lightning/Surge
Arresters in Complete Enclosures
Part No. 10020/4 ENC
TP+N
• Type 1 + 2 + 3 Level 3/4 50KA
10/350μs
• Very low let-through voltage
(less than 600v)
• Fast response time less than
<25ns
• For LPL Zones 0-3
• IP65 Polycarbonate enclosure
H20cm W20cm D11cm
• With or without backup
63AMP MCB
• Follow currents completely
eliminated
Part No. 10020/4 ENCM
TP+N + MCB
• Visual and remote monitoring
as standard
• Enhanced protection to BSEN
62305
• 1st Amendment, 17th Edition
Wiring Regs. Compliant
9
Type 1 + Type 2 +Type 3 Combined
Lightning/Surge Arrester for DIN Rail Mounting
4 Pole Lightning/Surge Arrester
TP+N
Max. continuous operating voltage
Uc
275 V AC
Lightning impulse current
- charge
- specific energy
Iimp
Q
W/R
12,5 kA
6,25 As
39 KJ/Ω
Total lightning current (10/350)
L1 + L2 + L3 + N → PE
Itotal
50 kA
Nominal discharge current (80/20)
In
20 kA
Voltage protection level
Up
< 1,2 kV
Temporary overvoltage (TOV)
UT
335 V / 5 sec
Response time
tA
< 25ns
Max. backup fuse
Short-circuit withstand capability at max.
back-up fuse
160 AgL/gG
Ip
Lifetime
Part No. 16057
•
•
•
•
•
•
•
•
•
Arrester Type 1 + Type 2 + Type 3
4-pole arrester pluggable
3-phase power supply network TN-C-S
LPZ 0-1
LPL III, IV Itotal 50kA 10/350μs
Very low let-through voltage
Visual indication of status
Remote signal contacts
Recomended back-up fuse/MCB Min 63
AMPS
• Cable size 16mm² to 25mm²
10
Surge Protection Specialists
Weight
60 kArms
min. 100 000 h
m
560g
Part no
16057
Part no spare module
16058
Type 2/3 DIN Rail Mountable
Surge Arresters
Protect sensitive electronic equipment with high quality surge arresters.
Today’s highly sensitive electronics require a higher level of protection; you can achieve this by using the following
Lightning/Surge Arresters from Surge Protection Devices Ltd. They are quick and easy to install and are high-tech
products at competitive prices compared with other brands.
Type 2/3 Enhanced Pluggable
Surge Arresters
SPD According to
IEC61643-1 EN61643-11 Type 2/3
Maximum continuous operating voltage
UcV
(350V DC)
275 VAC
Voltage protection level In Up
Voltage protection level at 5kA Up
Voltage protection level at 3kA Up
≤ 1.3kV
< 0.9kV
< 0.6kV
Nominal discharge current
In (8/20μs)kA
20kA
Nominal discharge current
Imax (8/20μs)kA
40kA
Withstand
Short Circuit
50kA
RMS
Response time in ns
<25ns
Dimensions
W 72mm H 90mm D 66mm
Din-rail mountable
Enclosure material
Yellow/Grey
UL94 V-O
Degree of protection
IP20
Recommended backup MCB/fuse
Terminal capacity
Visual indication of status
Part No. SY1-C 40X
Part No. SY2-C 40X
SP+N
TP+N
Type 2/3 Enhanced Surge Arrester
2 pole (SP+N)
Part No. SY2-D
Pluggable version
Part No. SY2-D LED
LED version
SP+N
SP+N
32A to 63A
Phase line Neutral line - 2.5~35mm²
Earth Line - 4.0~35mm²
Signal Line - 1.0mm²
Remote Alarm Contact
Green OK
Red Replace Module
Contact closes if any part of the
device fails
SPD According to
IEC61643-1 EN61643-11 Type 2/3
Maximum continuous operating voltage
UCV
275 V
Voltage protection level Up
3kA (8/20μs)kA
< 0.6kV
Nominal discharge current
In (8/20μs)kA
5kA
Maximum discharge current
Imax (8/20μs)kA
10kA
Response time
< 25ns
Dimensions
W 18mm H 90mm D 66mm
Enclosure material
Grey UL94 V-O
Degree of protection
IP20
Recommended backup MCB/fuse
32A or less
Terminal capacity
1.5~4mm²
Visual indication of status
Black OK
Red Replace Module
DIN rail mountable
Yes
11
Type 2/3 Enhanced Pluggable Surge Arresters
in Enclosures
SY2-C40X ENC
TP+N
• Type 2/3 Enhanced TP+N
Pluggable Surge Arrester
• Complete in high quality IP65
Polycarbonate enclosure
• High surge capacity 40,000 AMPS
per pole
• Conforms to BSEN62305,
EN61643-11 and BS7671 1st
Amendment Wiring Regs.
• Use where there is no external
lightning protection and no
overhead lines
• Also use on sub-dist boards
to protect sensitive electronic
equipment
Dimensions (CM) : H20 x W12 x D11
SY1-C40X ENC
SP+N
• Connection in parallel means no
current limitations
• Visual and remote indication as
standard
• Low let through voltage
• Available with 63AMP backup MCB
(add ‘M’ to part number - e.g.
SY2-C40X ENCM)
• Each pole individually replaceable
• Use 32A to 63A backup MCB
• Cable size 6mm² - 16mm²
Dimensions (CM) : H20 x W12 x D11
12
Surge Protection Specialists
Surge Arrester Type 2/3 Compact Type
LED Indication
P-3k is a three-phase surge arrester type 2/3 according to EN61643-11 and IEC 61643-1 suitable for use in TNS,
TNC and TT systems. These are parallel devices intended for protection of electronic appliances against impulse
surge. All varistors are fitted with thermal fuses to prevent short and also permanent overloading.
These units are to be connected as near to the protected appliance as possible, e.g. local control panel, dist board.
The right function of P-3k230 devices is indicated by target disconnection of mechanical thermal fuses which react to
varistors overheating above c. 120˚C.
Nominal voltage
UN
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal discharge current In(8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N, L/PE)
10 kV (N/PE)
Voltage protection level at Uoc
Up
<1,2 V (L/N)
<1,2 kV (L/PE)
<1,2 kV (N/PE)
c. 3VA / 0,1 VA
Power loss at winding temp. 20˚C
Response time
tA
<25ns (L/N)
<100ns (L/PE, N/PE)
Recommended backup fuse
16A
Lifetime
min. 100.000 h
Weight
Part no
m
140/205g
30 105
Part No. 30 105
Recommended connection of 30105
Basic circuit diagram of 30105
13
Type 3 Surge Arrester
For electrical installation systems
Surge protection device for electrical installation systems
Type 3 to EN61643-11
Nominal voltage
Un
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal discharge current In (8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N)
10 kV (N/PE)
Voltage protection level at Uoc
Up
1 kV (L/N)
<1 kV (L/PE)
<1,2 kV (N/PE)
0,5 W
Power loss at winding temp. 20˚C
Response time
32006 is surge arrester type 3 according to EN
61643-11 dsigned for installation into electrical
installation systems, e.g.: cable ducts, flushmounted sockets or fire alarm panels as an
additional protection measure.
Recommended backup fuse
32006 contains an acoustic fault indicator (buzzer)
and is earth leakage free.
Weight
Temporary overvoltage (TOV)
<25 ns (L/N)
<100 ns (L/PE, N/PE)
16A
UT
335V/5 s (L/N)
1200V + U0/200 ms (L/PE)
Lifetime
Min. 100.000 h
Failure indication 32006
inbuilt piezosiren
Part No.
Basic circuit diagram of 32006
Recommended connection of 32006
14
TA
Surge Protection Specialists
m
20/30g
32006
Surge Arresters - Varistor and EMC/EMI Filter
Type 3
PI-k and PI-k16 are type 3 single phase surge arresters with a high frequency filter according to EN61643-11
and IEC 61643-1. They are produced for nominal current within the range of 8, 16, 25, 32 for mounting on DIN
rail 35mm. For protection of single-phase electronic appliances in L.V. supply systems against impulse surge
and high-frequency disturbance.
Nominal voltage
UN
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal current
IN
8A
Nominal discharge current In(8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N, L/PE)
10 kV (N/PE)
Voltage protection level at Uoc
Up
<850 V (L/N)
<1,5 kV (L/PE)
<1,2 kV (N/PE)
Asymmetrical attenuation of filter
(band-stop filter)
Filters constraints
min. 80dB at 4MHz
min. 40dB (0,15 - 30MHz)
Cx
Cy
L
<2,2 W
Power loss at winding temp. 20˚C
Response time
Part No. 30 080
tA
<25ns (L/N)
<100ns (L/PE, N/PE)
Recommended backup fuse
6A
Lifetime
min. 100.000 h
Weight
m
Part no
130g
30 080
Nominal voltage
UN
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal current
IN
16A
Nominal discharge current In(8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N, L/PE)
10 kV (N/PE)
Voltage protection level at Uoc
Up
<850 V (L/N)
<1,5 kV (L/PE)
<1,2 kV (N/PE)
Asymmetrical attenuation of filter
(band-stop filter)
Filters constraints
Part No. 30 004
150 nF
22 nF
1,2 mH
min. 80dB at 4MHz
min. 40dB (0,15 - 30MHz)
Cx
Cy
L
<3,5 W
Power loss at winding temp. 20˚C
Response time
220 nF
22 nF
1,8 mH
tA
<25ns (L/N)
<100ns (L/PE, N/PE)
Recommended backup fuse
16A
Lifetime
min. 100.000 h
Weight
Part no
m
170/224g
30 004
15
2-Stage MOV Surge Arrester and EMC / EMI Filter
Nominal voltage
UN
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal current
IN
25A
Nominal discharge current In(8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N, L/PE)
10 kV (N/PE)
Voltage protection level at Uoc
Up
<850 V (L/N)
<1,5 kV (L/PE)
<1,2 kV (N/PE)
Asymmetrical attenuation of filter
(band-stop filter)
Filters constraints
Part No. 30 017
min. 80dB at 4MHz
min. 40dB (0,15 - 30MHz)
Cx
Cy
L
<3,5 W
Power loss at winding temp. 20˚C
Response time
tA
25A
Lifetime
min. 100.000 h
m
Part no
Nominal voltage
UN
230 V AC
Max. continuous operating voltage
Uc
275 V AC
Nominal current
IN
32A
Nominal discharge current In(8/20)
In
3 kA (L/N, L/PE)
5 kA (N/PE)
Combined impulse
Uoc
6 kV (L/N, L/PE)
10 kV (N/PE)
Voltage protection level at Uoc
Up
<850 V (L/N)
<1,5 kV (L/PE)
<1,2 kV (N/PE)
Filters constraints
min. 80dB at 4MHz
min. 40dB (0,15 - 30MHz)
Cx
Cy
L
Response time
220 nF
22 nF
2,3 mH
<4 W
Power loss at winding temp. 20˚C
tA
<25ns (L/N)
<100ns (L/PE, N/PE)
Recommended backup fuse
32A
Lifetime
min. 100.000 h
Weight
Part no
Surge Protection Specialists
240g
30 017
Asymmetrical attenuation of filter
(band-stop filter)
16
<25ns (L/N)
<100ns (L/PE, N/PE)
Recommended backup fuse
Weight
Part No. 30 005
220 nF
22 nF
2,3 mH
m
240g
30 005
Telephone/Fax/Modem
Surge Arrester
For BT Type Sockets. Test category
D+C+B to BSEN 61643-21
Technical Data
Part No. DTB2/ART
Can also be used on ISDN Fast
Transmission Lines
Number of protected pairs
2
Nominal voltage
Un
170v
Max. continuous operating voltage
Uc
204v
Nominal current
IN
100mA
C2 Max. discharge current (8/20)
1MAX
2kA
Nominal discharge current (8/20)
IN
1kV
Voltage protection level at 1kV/μs
Up
520v
Response time
TA
<30ns
Data rate
10MBit/s
Series impedance per line
1,5-10 Ω
Parasitic capacitance
C
1,5nF
Operating temperature change
ϑ
-40°C ÷ + 80°C
Category tested acc. to IEC 61643:21-2000
A2, B2, C2, C3, D1
Single or 10 Pair Telephone Surge Arrester for Installation into Krone
LSA Disconnections Strips, Test Category D+C+B to BSEN 61643-21
Part No. DP1 LSA180
Part No. DP10LSA180
Part No. TELCO/EB
Technical Data
Nomincal direct voltage
110V=
Max. continuous operating direct voltage (Uc)
180v=
Max. continuous operating alternating voltage (Uc)
180~
Residual voltage at 1kV/μs
<250V
Nominal operating current at 25°C
145mA
C2 nominal discharge current (8/20μs) In
5kA
Max. impulse discharge current (8/20μs) (Imax)
10kA
Protection level at In (Up)
220V
Response time (tA)
<1ns
Thermal response time at 230V/23 A ac and ambient
temp. 25°C (TA)
<2s
Capacitance wire-earth (C)
<0.1nF
Series inductance at 25°C (L)
47μH
Series resistance per line at 25°C (R)
3-6 Ω
Max. transmission frequency (fg)
≤1.2MHz
Operating temperature range
-40°C to + 80°C
Enclosure material / colour
Thermoplastic, grey or yellow
Dimensions (L x W x H)
110 x 2.25 x 40mm
Net weight / pc
90g
17
Data Signal Line
Arresters/CCTV
SP-30 SP-48
DATA SIGNAL ARRESTER 2 POLE
Part No.
SP5
SP12
SP15
SP24
SP30
SP48
SP60
SP110
Nominal voltage: Un
5V-
12V-
15V-
24V-
30V-
48V-
60V-
110V-
Max. continuous voltage DC.Uc
6V-
14.5V-
17.8V-
26.8V-
34.8V-
55.1V-
65V-
170V-
Max. continuous voltage: AC.Uc
4.2V
10.2V
12.5V
18.9V
24.5V
38.9V
50V
130V
Nominal current: In
1A
C2 Total Nominal Discharge Current In (8/20μs) 20kA
D1 Total Lightning Impulse Current (10/350μs) Iimp 20kA
Voltage protective
level: Upin
Voltage protective
level: Up 1kc/μS
Core/Core
≤50V
≤70V
≤85V
≤100V
≤130V
≤200V
≤240V
≤730V
Core/PE
≤45V
≤60V
≤70V
≤80V
≤80V
≤120V
≤150V
≤400V
Core/Core
≤16V
≤38V
≤50V
≤70V
≤95V
≤150V
≤180V
≤520V
Core/PE
≤8V
≤19V
≤25V
≤35V
≤50V
≤75V
≤90V
≤260V
1.5 Ω
1.6 Ω
1.8 Ω
1.8 Ω
1.8 Ω
1.8 Ω
Response time: tA
≤1ns
Resistance
1Ω
≤25ns
Insertion loss
≤0.3dB
Working frequency
≤0.3MHz
Degree of protection
IP20
Dimensions
90H x 14W x 65D mm
Enclosure material
Polyamide PA6.6
Connector
Screw terminals
Signal Surge Protection Device. REP-SP Series
Co-Axial BNC C.C.T.V Arrester
Surge arresters for coaxial ethernet network systems
protection. Protects against surges at the boundaries
from lightning protection zone 0 3
•
•
•
•
•
•
18
Data network protector in accordance with IEC614321.
Limit the transients with gas discharge tubes and
transzorb diodes.
Two-stage protection circuit in aluminium housing.
BNC connector for ethernet systems.
Simple installation.
Also application for the protection of video signals,
cameras and/or TV systems
Surge Protection Specialists
Model No.
D-24/BNC
Nominal voltage (V) Un
24
Max. continuous voltage (V) Uc
24/28
C2 nominal discharge current (8/20μs) per line In
5kA
C2 nominal discharge current (8/20μs) shield-PG In
10kA
Voltage protection level
(8/20μs, V) Up
Line-Shield
≤300
Shield-Ground
≤700
Voltage protection level
(1KVμs, V) Up
Line-Shield
≤50
Shield-Ground
≤600
Transmission Speed (bps) Vs
10Mbps
Series impedence per line (Ohm)
3Ohm
Inerstion loss (dB)
0.5@10MHz
Response time Ta
1ns
Type of connection IN/OUT
BNC Female/Male
Dimensions (mm)
70x25x25
Environment Temperature °C
-25~+70
Protection of
PHOTOVOLTAIC/SOLAR SYSTEMS
Surge protection devices for the protection of the DC side before inverter
Type 2 to EN61643-11
• Fault indication
• Remote signal contact optional
• Pluggable and replaceable modules
Part No. SPD PV1000
SPD According to
IEC61643-1 EN61643-11 Type 2
Maximum continuous operating voltage UcV
1060v DC
Voltage protection level In Up
4kv
Nominal discharge current In (8/20μs) kA
20kA
Maximum discharge current In (8/20μs) kA
40kA
Withstand short circuit
50kA
RMS
Response time ns
<25ns
Dimensions
W 54 x H 90 x D 66mm
Din-rail mountable
Enclosure material
Grey
UL94 V-O
Degree of protection
IP20
Recommended backup MCB/fuse
32A to 63A
Terminal capacity
Phase line Neutral line
2.5~35mm²
Earth line
4.0~35mm²
Signal line
1mm²
Visual indication status
Green - OK Red - Replace Module
Din rail mountable
Yes
Type 2 to EN61643-11
SPD According to
IEC61643-1 EN61643-11 Type 2
Maximum continuous operating voltage UcV
640v
Voltage protection level Up
2.2kv
Nominal discharge current In (8/20μs) kA
20kA
Maximum discharge current In (8/20μs) kA
40kA
Response time
<25ns
Dimensions
W 36 x H 90 x D 66mm
Enclosure material
Grey
UL94 V-O
Degree of protection
IP20
Recommended backup MCB/fuse
32A to 63A
Terminal capacity
• Fault indication
• Remote signal contact optional
• Pluggable and replaceable modules
Phase line Neutral line
2.5~35mm²
Earth line
4.0~35mm²
Signal line
1mm²
Visual indication status
Green - OK Red - Replace Module
Din rail mountable
Yes
Part No. SPD PV600
Type 1 + 2 Available - Please Contact The Sales Office
19
Lightning and Surge Protection
for Industrial, Commercial and
Domestic Electrical Insrtallations
•
•
•
We offer free technical help and assistance
with product selection and design.
We can carry out site surveys.
We can assist with compliance to the latest
requirement of the Wiring Regulations
BS7671 and BSEN62305 Lightning Standards.