Calculite® Compact Fluorescent Open Downlight 8071
Page 1 of 2
1’ x 1’ Square Aperture (2) 24/27W Twin Tube Parabolic Louver
3
6 1 5 4
2
13 1/2" Recessed Width
(343 mm)
7
13 1/4" Recessed Length
(337 mm)
3"
5 1/2"
(140 mm) (76 mm)
1" (25 mm) min.2-1/8" (54 mm) max.
5 1/2" Square
(140 mm)
11 1/8" Ceiling Opening
(283 mm)
11" (280 mm) Square
11 15/16" (303 mm) Square Flange
Ceiling Cutout: 11 1/8" (283 mm) Sq.
Reflector Trim
Frame-In Kit
Lamp
8071CLP Semi-Specular Louver, Polished Flange
8071WHW White Louver, White Flange
Q227HU
Q227HU
Q227HM120 Q227HM277 24 or 27W Twin Tube
4-Pin
Features
Electronic 4-pin
Electronic 4-pin
Magnetic 2-pin
Magnetic 2-pin
1. Parabolic Louver: Semi-specular anodized aluminum louver has low
iridescence finish. The deep four-cell louver provides 52° cutoff. Overlap
flange provides ceiling trim while eliminating need for separate mounting
frames for different ceiling types.
2.Housing: Die-formed steel painted in high reflectance white finish.
Contoured for maximum light output. Unique overhang design permits use of
13" long 24/27 watt lamps.
3. Ballast Assembly: Ease of field inspection for servicing. Cover plate is
removable without tools.
4. Mounting Brackets: 16 ga. steel. Adjust from inside of fixture. Use 3/4” or
1 1/2” lathing channel, 1/2” EMT, or optional mounting bars.
5. Retaining Springs: Precision-tooled rust proof steel springs secure reflector
to housing for quick tool-less installation. Positive tension springs hold
reflector tight to ceiling for clean finished appearance.
6. Lamp Holder: Snap-in design allows for easy relamping, center lamp
properly over louver for even illumination.
7. Access Plate: Permits wiring without opening fixture, includes two 7/8"
knockouts. Accepts most modular wiring receptacles.
Electrical
120V-277V
120V-277V 120V
277V
Options & Accessories
Louver
9 Cell Louver Consult Factory
Frame & Mounting
Emergency
Chicago Plenum
Mounting Bars
Fuse (slow blow)
Consult Factory
Consult Factory
See Sheet MBA
Add Suffix F
Labels
UL listed for damp locations, I.B.E.W.
Job Information
Type:
Job Name:
Note: For ballast electrical data and latest lamp/ballast compatibility refer to
“Ballast” specification sheet for complete electrical data.
Cat. No.:
UL listed for through branch circuit wiring with max of (8) No. 12 AWG, 90° C
supply conductors.
Lamp(s):
Notes:
Lightolier a Genlyte Thomas Company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2011 Genlyte Thomas Group LLC (Lightolier Division) • B0711
Calculite® Compact Fluorescent Open Downlight 8071
Page 2 of 2
1’ x 1’ Square Aperture (2) 24/27W Twin Tube Parabolic Louver
24W/27W
Quick Calculator
INITIAL FOOTCANDLES
80
ROOM SURFACE REFLECTANCES:
80% Ceiling; 50% Wall, 20% Floor
1800 Lumens Per Lamp
RCR= 1 (Rm. Width = 10xMtg. Ht. above work plane)
RCR= 5 (Rm. Width = 2xMtg. Ht. above work plane)
RCR=10 (Rm. Width = Mtg. Ht. above work plane)
70
60
50
40
30
20
10
25
3 4
50
5
75
100
125
150
175
AREA PER FIXTURE IN SQUARE FEET
6 7
8
9
10
11
12
200
13
14
CENTER TO CENTER DISTANCE OF FIXTURES IN FEET
This quick calculator chart determines the number and spacing of units for any
desired level of illumination.
Spacing Ratio: Parallel=1.2; Perpendicular=1.4
ITL Test Report Number: ITL 34500
COMPUTED BY: INDEPENDENT TESTING LABORATORIES, INC
PREPARED FOR: LIGHTOLIER INC.
LUMINAIRE: FABRICATED METAL HOUSING
REFLECTOR: WHITE PAINTED REFLECTOR, SEMI-SPECULAR 4 CELL PARABOLIC LOUVER
BALLAST: ONE ADVANCE CAT. NO. R-2BP27-TP
LAMPS: TWO PHILIPS PL24W/84 EACH RATED AT 1800 LUMENS.
ACROSS
45
ALONG
90
60
Angle
0
5
15
25
35
45
55
65
75
85
90
CANDELPOWER SUMMARY
0.0
45.0 90.0 135.0 180.0
999
999 999 999 999
996
1006 1015 1007 994
946
1062 1165 1072 943
857
1102 1246 1118 845
725
973 813 960 706
535
481 301 455 484
87
98
62
86
58
12
14
11
14
10
3
5
3
5
2
0
0
0
0
0
0
0
0
0
0
ZONAL LUMENS AND PERCENTAGES
Zone Lumens% Lamp
% Luminaire
0–30
896
24.9
0–40
1436
39.9
0–60
1877
52.1
0–90
1895
52.6
90–180
0
.00
0–180
1895
52.6
0
Flux
97
301
498
540
353
87
14
4
1
47.3
75.8
99.0
100.0
.00
100.0
30
**EFFICIENCY = 52.6%**
DATE: MAY, 17 1988
TESTED ACCORDING TO IES PROCEDURES. TEST DISTANCE EXCEEDS FIVE TIMES
THE GREATEST LUMINOUS OPENING OF LUMINAIRE.
Coefficients Of Utilization
ROOM CAVITY RATIO
80
1
2
3
4
5
6
7
8
9
10
50
.58
.54
.50
.46
.43
.40
.36
.33
.31
.28
30
.57
.52
.47
.43
.39
.36
.33
.30
.27
.25
10
.55
.50
.45
.41
.37
.34
.30
.28
.25
.22
% Effective Ceiling Cavity Reflectance
70
50
30
%Wall Reflectance
50 30 10 50 30 10 50 30
.57 .56 .55 .55 .54 .53 .53 .52
.53 .51 .49 .51 .50 .48 .50 .48
.49 .47 .45 .48 .46 .44 .46 .45
.46 .43 .41 .45 .42 .40 .43 .41
.42 .39 .37 .41 .39 .37 .40 .38
.39 .36 .34 .38 .35 .33 .38 .35
.36 .33 .30 .35 .32 .30 .35 .32
.33 .30 .27 .33 .30 .27 .32 .29
.30 .27 .25 .30 .27 .25 .29 .27
.28 .25 .22 .27 .24 .22 .27 .24
20% FLOOR CAVITY REFLECTANCE
10
10
.51
.47
.43
.40
.36
.33
.30
.27
.25
.22
50
.51
.48
.45
.42
.40
.37
.34
.31
.29
.27
30
.50
.47
.44
.41
.38
.35
.32
.29
.26
.24
0
10
.50
.46
.42
.39
.36
.33
.30
.27
.24
.22
0
.49
.45
.42
.38
.35
.32
.29
.26
.24
.21
Job Information
Lightolier a Genlyte Thomas Company
Type:
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2011 Genlyte Thomas Group LLC (Lightolier Division) • B0711
Download