installation instructions

advertisement
INSTALLATION INSTRUCTIONS
MultiForm
2x2 Recessed Exam Light
Series: MLF340/440
11500 Melrose Avenue
Franklin Park, Illinois 60131 Phone: 800-576-2135 Fax: 800-576-2136
www.vistalighting.com
CAUTION! – READ THIS FIRST --- IMPORTANT SAFETY INSTRUCTIONS
*
* This fixture may employ a grounded receptacle and is not intended for connection to a two-wire, ungrounded source supply.
* Carefully read the instructions pertaining to your fixture. IF YOU HAVE ANY QUESTIONS REGARDING THE PROPER INSTALLATION OR LOCAL CODES, CONSULT A QUALIFIED ELECTRICIAN.
Injury to persons and damage to the fixture
and/or mounting surface may result if the fixture is pulled from the surface. To reduce the
likelihood of such injury or damage, mount only on a surface that is mechanically sound.
2-Wire Component
(Hot & Neutral)
Disconnect conductors
before servicing
Ballast, Power Supply or Filter
*
To avoid shock hazard, do not work with live
electrical wires.
*
Install the fixture in only dry, indoor applications.
*
Do not install outdoors or in applications other than the intended use.
*
Install and wire the fixture in locations in accordance with all national, state and local codes.
*
For 277V installations, disconnect the orange safety disconnect plug(s) (located in the wireway
compartment) to fully disconnect power to the fixture before servicing. (See Figure 1)
3-Wire Component
(2 Hot, Neutral)
Disconnect conductors
before servicing
To branch circuit
outside fixture
Ballast, Power Supply or Filter
Fixture Ground
Typical wiring compartment
(cover removed)
To branch circuit
outside fixture
Fixture Ground
Typical wiring compartment
(cover removed)
Figure 1
WARNING: THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTIONS AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: RISK OF FIRE, MINIMUM OF 90°C SUPPLY CONDUCTOR. CONSULT A QUALIFIED ELECTRICIAN TO ENSURE CORRECT BRANCH CIRCUIT CONDUCTOR.
WARNING: TO AVOID SHOCK HAZARD, DISCONNECT THE POWER AT THE PANEL BOARD (CIRCUIT
BREAKER BOX) BEFORE BEGINNING INSTALLATION.
OVERVIEW
Read through the entire Installation Instructions prior to beginning the installation.
A. GRID INSTALLATION
The MultiForm luminaire is designed to install into standard suspended grid
ceilings with a 1" or 1½" high grid. The weight of the luminaire is supported by
the grid and supplemented with direct connection to the building structure. The
steps for installation are as follows:
1.Inspect the ceiling grid to make sure it is supported from the building structure as recommended by the ceiling grid manufacturer’s instructions. 2.Angle the fixture up through the opening in the grid. Once through the
opening, lower the luminaire so that its flanges are supported on the ceiling grid.
3.The luminaire is to be connected directly to the building structure, independent of the ceiling grid. Locate the hanger support tab at each corner of the luminaire housing and bend the tab. Use a hanger wire at all four corners to tie the luminaire to the building structure. Use 12 gauge minimum hanger wire rated for such application. In addition, follow local building codes regarding required additional support of luminaires.
4.Proceed to section “C. Making Electrical Connections”. B. FLANGE INSTALLATION
The MultiForm luminaire can
be installed into a drywall (i.e.
gypsum board, sheetrock)
ceiling with the addition of the
flange kit option. The steps for
installation are as follows:
1.A flange installation requires a clean and accurate opening of 24¼" x 24¼" to be cut into the ceiling surface Typical Corner Detail
where the luminaire is to be installed. Openings need to
be cut square and accurate. It is recommended that the opening should be cut into whole pieces of ceiling material to minimize seams Figure 3
and joints intersecting the cut opening. This limits stress on taped joints and ensures a better fit of the fixture flange against the ceiling surface.
2.Assemble the flange kit by sliding the (snap-lock) corner angles into side and end rails as shown in Figure 2.
3.Place assembled frame into ceiling opening and wire support (at four corners as shown in Figure 2) from main floor/ceiling structure.
4.Angle the fixture up through the opening in the frame. Once through the opening, lower the luminaire so that the fixture flanges are supported on the flanges of the flange kit.
5.Proceed to section “C. Making Electrical Connections.
#12 ga. mild steel support wire
(by others)
INSID
E
Marked side of end
and side rails to face
frame opening
INSID
E
Typical coupling detail
for continuous rows
Thumb
screw
Thumb
screw
C. MAKING ELECTRICAL CONNECTIONS
Figure 2
Note: The circuit should be shut-off at the breaker before
beginning this step.
1.Open the door by fully loosening the two thumbscrews. Allow the door to swing open.
Figure 3
2.Remove the reflector plate by removing the four (4) screws. The fixture wiring should be exposed at this point.
3.Locate the knockouts on the back of the housing. Remove one of the knockouts.
4.Secure the flexible metal conduit (FMC) with the incoming power at the location of the removed knockout with the appropriate conduit connector. Locate the leads for the exam load. (These leads are tagged for easy identification.) There may be an additional set of leads for the nightlight option.
5.Make the electrical connections by connecting the building hot to the black lead, the building neutral to the white lead and the building ground to the ground lead.
reflector
plate
D. INSTALLING LAMPS
1.Exam Compartment
a.Hand loosen the two (2) thumb screws for the exam compartment door. Allow door to hang open from the fixture.
b.Angle the lamp so that it fits into the fixture housing. Begin inserting the lamp’s socket into the lampholder from the side of the lampholder so that the 4 pins on
the lamp align with the pin holes on the lampholder. Begin to move the tip of the lamp horizontally until
the lamp’s socket aligns with the lampholder. Gently push the lamp into the lampholder until it fully engages. Once in place, push the tip of the lamp over
the lamp support clip.
c.Repeat this same step for the other lamps in this compartment.
d.Close the exam compartment door and hand tighten the two (2) thumbscrews.
Figure 3
lamp
lamp
lamp
Figure 4
CUSTOMER SUPPORT
If you require additional information regarding this light fixture we invite you to call us at Philips Vista. Our business hours are:
Monday - Friday (except holidays), 8:00am to 4:30pm Central time. Phone: 800-576-2135 Fax: 800-576-2136
REPLACEMENT PARTS
Contact Philips Vista directly for information on replacement parts. When calling, be prepared to provide the model number and
date of manufacture of the fixture. This information is indicated on labels located on the product.
.075.0401 03/12 MLF340/440 Series
Some luminaires use fluorescent or high intensity discharge (HID) lamps that contain small amounts of mercury. Such lamps are
labeled “Contains Mercury” and/or with the symbol “Hg.” Lamps that contain mercury must be disposed of in accordance with local
requirements. Information regarding lamp recycling and disposal can be found at www.lamprecycle.org
3