DS 3.230 06/00 RM, RX, RE 4Nm ROTARY ACTUATORS These Satchwell actuators have a rotary output for direct coupling to air dampers (up to approximately 0.8m2) in ventilation and air conditioning systems. The RX 7252 and RM 7652 are open/close actuators controlled by a single wire or 2-wire system. The RE 7352 is controlled by a standard 0-10Vdc signal and runs to whatever position is specified by the signal. The purpose of measuring voltage U (see wiring diagram) is to provide 0…100% electrical indication of damper position and to act as a master-slave control signal for other actuators. FEATURES • Simple direct mounting on the damper spindle by universal spindle clamp. An anti-rotation device is supplied to prevent unwanted rotation of the whole unit. • Manual operation by self-resetting push-button when necessary (the gearing is disengaged while the pushbutton is held depressed). • Adjustable angle of rotation with mechanical stops. • High functional reliability. The actuator is overload proof, needs no limit switches and halts automatically at the end stops. • Steplessly adjustable angle of rotation by integral potentiometer. Range matching of the working range and measuring signal U is performed automatically by the actuator (RE 7352 only). Notes: Using Satchwell damper actuators The actuators listed in this datasheet are intended for the operation of air dampers in HVAC systems. Torque requirements When calculating the torque required to operate dampers, it is essential to take into account all the data supplied by the damper manufacturer concerning cross sectional area, design, mounting and air flow conditions. Multi-Lingual Instructions MLI 3.230 - Installation Instructions DS 3.230 2-4 06/00 SPECIFICATIONS TYPE ACTION NOMINAL VOLTAGE NOMINAL VOLTAGE RANGE FOR WIRE SIZING POWER CONSUMPTION CONNECTING CABLE RX 7252 RE 7352 RM 7652 Open/Close actuator with single wire or two wire control Modulating actuator Open/Close actuators with single pole contact (single wire) control 24Vac 50/60Hz, 24Vdc 24Vac 50/60Hz, 24Vdc 230Vac 50/60Hz 19.2...28.8Vac, 21.6...28.8Vdc 19.2...28.8Vac, 21.6...26.4Vdc 198...264Vac 3VA 4VA 12VA 2W 2W 1W 1m long, 3 x 0.75mm2 1m long, 4 x 0.75mm2 1m long, 3 x 0.75mm2 CONTROL SIGNAL Y - 0-10Vdc @ 100kΩ input resistance - OPERATING RANGE - 2-10Vdc (for set ∠ of rotation) - MEASURING VOLTAGE U - 2-10Vdc @ ≤0.5mA (for set ∠ of rotation) - SYNCHRONISM TOLERANCE - 5% - Selected with L/R switch Selected with L/R switch (at switch position L resp. R ) Selected by L/R switch DIRECTION OF ROTATION (at Y = 0V) MANUAL OPERATION TORQUE ANGLE OF ROTATION RUNNING TIME SOUND POWER LEVEL SERVICE LIFE POSITION INDICATION PROTECTION CLASS DEGREE OF PROTECTION AMBIENT TEMP LIMITS: NON OPERATING TEMP: HUMIDITY TEST: EMC MAINTENANCE WEIGHT Pushbutton, self-resetting Pushbutton, self-resetting Pushbutton, self-resetting Min. 4Nm (at rated voltage) Min. 4Nm (at rated voltage) Min. 4Nm (at rated voltage) Max. 95° (adjustable by mechanical stops) Max. 95° (adjustable with potentiometer 20...100%) Max. 95° (adjustable by mechanical stops) 80...110s (0...4Nm) 80...110s for 95° (0...4Nm) 80...110s (0...4Nm) Max. 35dB (A) Max. 35dB (A) Max. 35dB (A) Min. 60,000 operations Min. 60,000 operations Min. 60,000 operations mechanical mechanical mechanical (safety low voltage) (safety low voltage) (all insulated) IP 54 (cable entry down) IP 54 (cable entry down) IP 54 (cable entry down) –30...+50°C –40...+80°C to EN 60335-1 –30...+50°C –40...+80°C to EN 60335-1 –30...+50°C –40...+80°C to EN 60335-1 CE according to 89/336/EEC and 92/31/EEC CE according to 89/336/EEC and 92/31/EEC CE according to 89/336/EEC and 92/31/EEC Maintenance-free Maintenance-free Maintenance-free 650g 620g 650g OPERATION RM/RX/RE The direction of rotation of is selected by means of a switch on the actuator. RE ONLY The actuator is controlled by a standard 0-10Vdc signal and runs to whatever position is specified by the signal. The purpose of measuring voltage U (see wiring diagram) is to provide 0…100% electrical indication of damper position and to act as a master-slave control signal for other actuators. INSTALLATION See MLI 3.230. The actuator is fitted directly to the damper and the universal spindle clamp tightened securely to the damper shaft. An anti-rotation device is supplied with each actuator and must be fitted to prevent rotation during operation. The angular stroke of the actuator is mechanically limited to 95°; it will stall against end stops and is protected against overloading. 06/00 3-4 DS 3.230 CONNECTION DIAGRAMS RM 7652 To isolate from the main power supply, the system must incorporate a device which disconnects the phase conductors (with at least a 3 mm contact gap). 230Vac 230Vac RM 7652 Parallel connection of several actuators possible. Power consumption must be observed. RX 7252 Connect via safety isolating transformer 24Vac 24Vdc Parallel connection of several actuators is possible. Power consumption must be observed. RX 7252 RE 7352 24Vac 24Vdc Connect via safety isolating transformer 0-10Vdc Controller output signal 2-10Vdc Measuring voltage U for position indicating or as master-slave control signal. of set angle Reversing switch Open Closed anticlockwise-closing damper RE 7352 Parallel connection of several actuators is possible. Power consumption must be observed. WIRING PRECAUTIONS Actuator Type Wiring from Actuator to Controllera: RX RM Supply RE 24V~ supply 0-10Vdc signal a Reversing switch Open Closed clockwiseclosing damper Use an isolator with a minimum contact gap of 3mm (conforming to EN 60335-1) to isolate the RM from the mains supply. Max. length of 1.5mm² cable unscreened 100m Max. resistance per conductor 5Ω RX and RE must be connected to 24Vac via a safety transformer conforming to EN 60742. MAINTENANCE A periodic check of the control system is recommended. 100m 100m 3Ω 50Ω When wiring to BAS outstations refer to the appropriate outstation data sheet for the wiring precautions. For longer lengths of 24 Volt supply wiring, increase cable size and observe maximum resistance. Where screening is required, use either screened cable, or MICC. WARNING RM MODULES ARE AT MAINS POTENTIAL. OBSERVE LOCAL WIRING REGULATIONS, EARTHING REQUIREMENTS AND ALL USUAL SAFETY PRECAUTIONS. DS 3.230 4-4 06/00 DIMENSION DRAWING Satchwell Control Systems Limited Farnham Road Slough Berkshire SL1 4UH United Kingdom Telephone +44 (0)1753 611000 Facsimile +44 (0)1753 611001 Web site www.satchwell.com WARNINGS CERTAIN MODELS ARE AT MAINS POTENTIAL. LOCAL WIRING REGULATION AND USUAL SAFETY PRECAUTIONS MUST BE OBSERVED. NOTE EARTHING REQUIREMENTS. THESE ACTUATORS ARE NOT SAFETY DEVICES AND SHOULD NOT BE USED ON FIRE DAMPERS. Cautions • Do not apply any voltages until a qualified technician has checked the system and the commissioning procedures have been completed. • RX and RE must be connected to 24Vac via a safety transformer conforming to EN 60742. • Use an isolator with a minimum contact gap of 3mm (conforming to EN 60335-1) to isolate the RMS from the mains supply. • Ensure wires are not inadvertently crossed over. • Check torque requirements of damper (or other device) to be driven. Do not exceed rated output torque. • Interference with those parts under sealed covers renders the guarantee void. • Design and performance of Satchwell equipment are subject to continual improvement and therefore liable to alteration without notice. • Information is given for guidance only and Satchwell do not accept responsibility for the selection or installation of its products unless information has been given by the Company in writing relating to a specific applications. • A periodic system check of the control system is recommended. Please contact your local Satchwell service office for details. © 2000 Satchwell Control Systems Limited (revised June 2000) All rights reserved. Unauthorised copying of any part of the contents is prohibited. Printed in England. 06/00