PROTECTION & CONTROL Minimize Energy Let-Through — Maximize Equipment Protection. PROTECTION & CONTROL Trans-Guard™ EXT Current-Limiting Backup Fuse For 12K–40K Ratings For 100K Ratings For 65K–80K Ratings Trans-Guard EXT Current-Limiting Backup Fuse ™ Voltage Selection — Refer to Table 1. Each Trans-Guard™ EXT Current-Limiting Backup Fuse is suitable for use in both single-phase and threeIn addition to interrupting higher fault currents, the Trans-Guard™ EXT Current-Limiting phase applications where the system voltage does not exceed the Maximum System Voltage listed. For single-phase applications on delta systems, Backup Fuse serves the very important function of limiting the amount of energy one fuse is needed in each line. let-through to the source of the fault to a value below the withstand capability Current-Rating Selection — Refer to Table 2. Each Trans-Guard™ EXT Current-Limiting Backup Fuse will coordinate with any link having a of the equipment being protected. rating no greater than that listed. For types of links not listed in Table 2, please contact Thomas & Betts for assistance. For more information concerning how Trans-Guard™ EXT Current-Limiting Backup Fuses are coordinated, please consult Application Guide FS-10. Hardware Selection — Many different hardware options are available. Some options vary depending on the size of the Trans-Guard™ EXT Current- New and improved design offers you: Limiting Backup Fuse required. Please refer to Ordering Information for available options. • Smaller size and lighter weight for easier handling • Lowest energy let-through in the industry • The most complete range of ratings available Table 1 Nominal Voltage Rating (kV) 8.3 Electrical Characteristics of Trans-Guard™ EXT Current-Limiting Backup Fuse Rated Maximum Interrupting Current (kA) Peak Arc Voltage (kV) Minimum Melt I2t (A2sec) Maximum Total I2t (A2sec) 12K 26 2,700 8,000 25K 26 11,000 29,000 40K 25 26,000 72,000 Current Rating Rated Maximum Voltage (kV) 50 65K Maximum System Voltage (kV) 8.3 14.4 22 67,000 230,000 80K 22 156,000 580,000 100K 24 218,000 850,000 12K 47 2,700 9,000 49 11,000 34,000 40K 47 26,000 85,000 65K 44 67,000 230,000 25K 15.5 44 80K 17.2 50 27.6 15.5 24.9 100K 12K 25K 23.0 31 40K 23.0 65K EXPULSION FUSE OPERATION CURRENT-LIMITING FUSE OPERATION Current peak Current peak Current interruption Current interruption Fuse Current Fault Current Energy Let-Through 34.5 50 80K Table 2 Setting the Standard in System Protection 44 156,000 580,000 46 204,000 730,000 62 2,700 10,000 60 11,000 37,000 62 26,000 88,000 65 67,000 220,000 63 123,000 360,000 Trans-Guard™ EXT Current-Limiting Backup Fuse/Expulsion Fuse Link Coordination Trans-Guard EXT Fuse Rating Type K Type T Type N Type S Coordinates with links up through Type H Type D Type X Type QA Type KS 12K 12 8 20 5 8 3 2.5 15 3 25K 25 15 30 7 8 20 10 30 7 40K 40 20 50 15 8 20 15 50 15 65K 65 30 60 25 8 20 15 75 15 80K 80 50 85 40 8 20 15 100 15 100K 100 65 85 50 8 20 15 125 15 Thomas & Betts Corporation Utility Products Group 8155 T&B Blvd. Memphis, TN 38125 P: 800.888.0211 F: 800.888.0690 ©2008 Thomas & Betts Corporation. All rights reserved. Printed in the USA. PB-PC-EXT-0208 Trans-Guard™ EXT Current-Limiting Backup Fuse PROTECTION & CONTROL Application Trans-Guard™ EXT Current-Limiting Backup Fuse for 12K–40K Ratings Trans-Guard™ EXT Current-Limiting Backup Fuse for 65K–80K Ratings Designed to enhance protection on overhead distribution systems, the Trans-Guard™ EXT Current-Limiting Backup Fuse both significantly reduces energy let-through during a fault and offers very high interrupting capability to provide state-of-the-art protection against today’s ever increasing available fault currents. A A Type of Installations SOURCE SIDE CUTOUT INSTALLATION BUSHING MOUNT INSTALLATION B B Ordering Information for 12K–40K Ratings Current Rating Dimension “B” (inches) Weight (lbs) Base Catalog Number* 12K 1.5 5.2 1.0 HTDE33 (X) 065 25K 1.5 7.1 1.1 HTDE33 (X) 080 HTDE23 (X) 040 40K 2.2 6.3 2.2 HTDE34 (X) 065 HTDE24 (X) 012 12K 1.5 8.6 1.3 HTDE34 (X) 080 HTDE23 (X) 012 HTDE23 (X) 025 HTDE24 (X) 025 8.3 15.5 HTDE24 (X) 040 HTDE25 (X) 012 HTDE25 (X) 025 NOTE: The Trans-Guard™ EXT Current-Limiting Backup Fuse interrupts high-level currents and must be applied in series with LOAD SIDE CUTOUT INSTALLATION HOT-LINE/BAIL INSTALLATION Ordering Information Dimension “A” (inches) Base Catalog Number* Nominal Voltage Rating (kV) 23.0 HTDE25 (X) 040 25K 1.5 11.9 1.8 HTDE35 (X) 065 40K 2.2 10.4 3.3 HTDE35 (X) 080 12K 1.5 10.5 1.6 25K 2.2 13.4 4.0 40K 2.2 13.4 4.0 for 65K–80K Ratings Nominal Voltage Rating (kV) Current Rating Dimension “A” (inches) Dimension “B” (inches) Weight (lbs) 3.3 9.9 7.5 3.3 15.5 10.5 3.3 18.3 12.5 65K 8.3 80K 65K 15.5 80K 65K 23.0 80K *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. Hardware for 65K–80K Ratings *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. another device capable of interrupting low- to mid-level currents. 2.0" 1.9" 2.2" Hardware for 12K–40K Ratings This is most commonly a cutout expulsion fuse. When properly 3.3" coordinated, the Trans-Guard™ EXT Current-Limiting Backup Fuse always allows sufficient let-through current to cause the cutout fuse 1.1" to melt and drop open, making it easy to visually pinpoint where 1.1" 1.1" or 1.5" 1.9" the fault occurred. 1.1" for 1.5" dia. fuses .29" .29" .46" 1.5" for 2.2" dia. fuses Eyebolt Knurled Stud (Accepts #8 – 2/0) Threaded Stud Universal Adapter (1⁄2" – 13 threads) Rotatable through 180˚ .42" Hardware Code Features Superior performance Benefits/Descriptions Eyebolt Lowest total I2t let-throughs in the industry provide maximum protection for equipment by minimizing energy let-through during a fault. Higher melt I t’s on smaller fuse ratings make Knurled Stud Parallel-Groove (Accepts #8 – 2/0) Spade (Accepts #6 – 2/0) 2 fuses less susceptible to damage from current surges. 1st End Hardware 2nd End Hardware 1 Spade Knurled Stud 5 Parallel-Groove Knurled Stud 6 Parallel-Groove Spade 8 Eyebolt Knurled Stud 9 Universal Adapter Spade Extends outdoor life and includes machined brass endcaps and filament-wound epoxy, C Universal Adapter Knurled Stud centerless ground tubular bodies, ground and coated with oven-baked acrylic paint. F Eyebolt Eyebolt G Parallel-Groove Eyebolt As high as 50kA symmetrical. (see Table 1) Small physical size Shorter, lighter weight design makes fuses easy to handle and install. Integral pre-assembled hardware Reduces installation time and likelihood of joint deterioration. Broadest range of ratings available Current-limiting action Up to 100K at 8.3kV and 15.5kV; up to 80K at 23kV. Improves power quality by reducing voltage dip time during a fault and reduces flame discharge and noise associated with the operation of the series-connected cutout fuse. Multiple hardware options for 12K–40K Ratings Hardware Code (X) High fault interrupting capability Durable design Hardware Code Wide variety of mounting and connection options for greater flexibility in installation. H Eyebolt Spade J Eyebolt Universal Adapter Z Parallel-Groove Universal Adapter for 65K–80K Ratings Hardware Code (X) 1st End Hardware 2nd End Hardware A Threaded Stud Threaded Stud E Eyebolt Knurled Stud F Eyebolt Eyebolt U Eyebolt Universal Adapter 3.3" Trans-Guard™ EXT Current-Limiting Backup Fuse for 100K Ratings .29" C 1.8" Eyebolt A .46" (Accepts #8 – 2/0) Universal Adapter Rotatable through 180˚ B Ordering Information for 100K Ratings Nominal Voltage Rating (kV) Current Rating HTDE23E100 8.3 100K 4.9 14.0 11.9 7.5 HTDE24E100 15.5 100K 4.9 19.4 17.5 10.5 Catalog Number Dimension “A” (inches) Dimension “B” (inches) Dimension “C” (inches) Weight (lbs) PROTECTION & CONTROL Application Trans-Guard™ EXT Current-Limiting Backup Fuse for 12K–40K Ratings Trans-Guard™ EXT Current-Limiting Backup Fuse for 65K–80K Ratings Designed to enhance protection on overhead distribution systems, the Trans-Guard™ EXT Current-Limiting Backup Fuse both significantly reduces energy let-through during a fault and offers very high interrupting capability to provide state-of-the-art protection against today’s ever increasing available fault currents. A A Type of Installations SOURCE SIDE CUTOUT INSTALLATION BUSHING MOUNT INSTALLATION B B Ordering Information for 12K–40K Ratings Current Rating Dimension “B” (inches) Weight (lbs) Base Catalog Number* 12K 1.5 5.2 1.0 HTDE33 (X) 065 25K 1.5 7.1 1.1 HTDE33 (X) 080 HTDE23 (X) 040 40K 2.2 6.3 2.2 HTDE34 (X) 065 HTDE24 (X) 012 12K 1.5 8.6 1.3 HTDE34 (X) 080 HTDE23 (X) 012 HTDE23 (X) 025 HTDE24 (X) 025 8.3 15.5 HTDE24 (X) 040 HTDE25 (X) 012 HTDE25 (X) 025 NOTE: The Trans-Guard™ EXT Current-Limiting Backup Fuse interrupts high-level currents and must be applied in series with LOAD SIDE CUTOUT INSTALLATION HOT-LINE/BAIL INSTALLATION Ordering Information Dimension “A” (inches) Base Catalog Number* Nominal Voltage Rating (kV) 23.0 HTDE25 (X) 040 25K 1.5 11.9 1.8 HTDE35 (X) 065 40K 2.2 10.4 3.3 HTDE35 (X) 080 12K 1.5 10.5 1.6 25K 2.2 13.4 4.0 40K 2.2 13.4 4.0 for 65K–80K Ratings Nominal Voltage Rating (kV) Current Rating Dimension “A” (inches) Dimension “B” (inches) Weight (lbs) 3.3 9.9 7.5 3.3 15.5 10.5 3.3 18.3 12.5 65K 8.3 80K 65K 15.5 80K 65K 23.0 80K *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. Hardware for 65K–80K Ratings *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. another device capable of interrupting low- to mid-level currents. 2.0" 1.9" 2.2" Hardware for 12K–40K Ratings This is most commonly a cutout expulsion fuse. When properly 3.3" coordinated, the Trans-Guard™ EXT Current-Limiting Backup Fuse always allows sufficient let-through current to cause the cutout fuse 1.1" to melt and drop open, making it easy to visually pinpoint where 1.1" 1.1" or 1.5" 1.9" the fault occurred. 1.1" for 1.5" dia. fuses .29" .29" .46" 1.5" for 2.2" dia. fuses Eyebolt Knurled Stud (Accepts #8 – 2/0) Threaded Stud Universal Adapter (1⁄2" – 13 threads) Rotatable through 180˚ .42" Hardware Code Features Superior performance Benefits/Descriptions Eyebolt Lowest total I2t let-throughs in the industry provide maximum protection for equipment by minimizing energy let-through during a fault. Higher melt I t’s on smaller fuse ratings make Knurled Stud Parallel-Groove (Accepts #8 – 2/0) Spade (Accepts #6 – 2/0) 2 fuses less susceptible to damage from current surges. 1st End Hardware 2nd End Hardware 1 Spade Knurled Stud 5 Parallel-Groove Knurled Stud 6 Parallel-Groove Spade 8 Eyebolt Knurled Stud 9 Universal Adapter Spade Extends outdoor life and includes machined brass endcaps and filament-wound epoxy, C Universal Adapter Knurled Stud centerless ground tubular bodies, ground and coated with oven-baked acrylic paint. F Eyebolt Eyebolt G Parallel-Groove Eyebolt As high as 50kA symmetrical. (see Table 1) Small physical size Shorter, lighter weight design makes fuses easy to handle and install. Integral pre-assembled hardware Reduces installation time and likelihood of joint deterioration. Broadest range of ratings available Current-limiting action Up to 100K at 8.3kV and 15.5kV; up to 80K at 23kV. Improves power quality by reducing voltage dip time during a fault and reduces flame discharge and noise associated with the operation of the series-connected cutout fuse. Multiple hardware options for 12K–40K Ratings Hardware Code (X) High fault interrupting capability Durable design Hardware Code Wide variety of mounting and connection options for greater flexibility in installation. H Eyebolt Spade J Eyebolt Universal Adapter Z Parallel-Groove Universal Adapter for 65K–80K Ratings Hardware Code (X) 1st End Hardware 2nd End Hardware A Threaded Stud Threaded Stud E Eyebolt Knurled Stud F Eyebolt Eyebolt U Eyebolt Universal Adapter 3.3" Trans-Guard™ EXT Current-Limiting Backup Fuse for 100K Ratings .29" C 1.8" Eyebolt A .46" (Accepts #8 – 2/0) Universal Adapter Rotatable through 180˚ B Ordering Information for 100K Ratings Nominal Voltage Rating (kV) Current Rating HTDE23E100 8.3 100K 4.9 14.0 11.9 7.5 HTDE24E100 15.5 100K 4.9 19.4 17.5 10.5 Catalog Number Dimension “A” (inches) Dimension “B” (inches) Dimension “C” (inches) Weight (lbs) PROTECTION & CONTROL Application Trans-Guard™ EXT Current-Limiting Backup Fuse for 12K–40K Ratings Trans-Guard™ EXT Current-Limiting Backup Fuse for 65K–80K Ratings Designed to enhance protection on overhead distribution systems, the Trans-Guard™ EXT Current-Limiting Backup Fuse both significantly reduces energy let-through during a fault and offers very high interrupting capability to provide state-of-the-art protection against today’s ever increasing available fault currents. A A Type of Installations SOURCE SIDE CUTOUT INSTALLATION BUSHING MOUNT INSTALLATION B B Ordering Information for 12K–40K Ratings Current Rating Dimension “B” (inches) Weight (lbs) Base Catalog Number* 12K 1.5 5.2 1.0 HTDE33 (X) 065 25K 1.5 7.1 1.1 HTDE33 (X) 080 HTDE23 (X) 040 40K 2.2 6.3 2.2 HTDE34 (X) 065 HTDE24 (X) 012 12K 1.5 8.6 1.3 HTDE34 (X) 080 HTDE23 (X) 012 HTDE23 (X) 025 HTDE24 (X) 025 8.3 15.5 HTDE24 (X) 040 HTDE25 (X) 012 HTDE25 (X) 025 NOTE: The Trans-Guard™ EXT Current-Limiting Backup Fuse interrupts high-level currents and must be applied in series with LOAD SIDE CUTOUT INSTALLATION HOT-LINE/BAIL INSTALLATION Ordering Information Dimension “A” (inches) Base Catalog Number* Nominal Voltage Rating (kV) 23.0 HTDE25 (X) 040 25K 1.5 11.9 1.8 HTDE35 (X) 065 40K 2.2 10.4 3.3 HTDE35 (X) 080 12K 1.5 10.5 1.6 25K 2.2 13.4 4.0 40K 2.2 13.4 4.0 for 65K–80K Ratings Nominal Voltage Rating (kV) Current Rating Dimension “A” (inches) Dimension “B” (inches) Weight (lbs) 3.3 9.9 7.5 3.3 15.5 10.5 3.3 18.3 12.5 65K 8.3 80K 65K 15.5 80K 65K 23.0 80K *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. Hardware for 65K–80K Ratings *When ordering, replace the (X) in the Base Catalog Number with the appropriate hardware code from the chart below. another device capable of interrupting low- to mid-level currents. 2.0" 1.9" 2.2" Hardware for 12K–40K Ratings This is most commonly a cutout expulsion fuse. When properly 3.3" coordinated, the Trans-Guard™ EXT Current-Limiting Backup Fuse always allows sufficient let-through current to cause the cutout fuse 1.1" to melt and drop open, making it easy to visually pinpoint where 1.1" 1.1" or 1.5" 1.9" the fault occurred. 1.1" for 1.5" dia. fuses .29" .29" .46" 1.5" for 2.2" dia. fuses Eyebolt Knurled Stud (Accepts #8 – 2/0) Threaded Stud Universal Adapter (1⁄2" – 13 threads) Rotatable through 180˚ .42" Hardware Code Features Superior performance Benefits/Descriptions Eyebolt Lowest total I2t let-throughs in the industry provide maximum protection for equipment by minimizing energy let-through during a fault. Higher melt I t’s on smaller fuse ratings make Knurled Stud Parallel-Groove (Accepts #8 – 2/0) Spade (Accepts #6 – 2/0) 2 fuses less susceptible to damage from current surges. 1st End Hardware 2nd End Hardware 1 Spade Knurled Stud 5 Parallel-Groove Knurled Stud 6 Parallel-Groove Spade 8 Eyebolt Knurled Stud 9 Universal Adapter Spade Extends outdoor life and includes machined brass endcaps and filament-wound epoxy, C Universal Adapter Knurled Stud centerless ground tubular bodies, ground and coated with oven-baked acrylic paint. F Eyebolt Eyebolt G Parallel-Groove Eyebolt As high as 50kA symmetrical. (see Table 1) Small physical size Shorter, lighter weight design makes fuses easy to handle and install. Integral pre-assembled hardware Reduces installation time and likelihood of joint deterioration. Broadest range of ratings available Current-limiting action Up to 100K at 8.3kV and 15.5kV; up to 80K at 23kV. Improves power quality by reducing voltage dip time during a fault and reduces flame discharge and noise associated with the operation of the series-connected cutout fuse. Multiple hardware options for 12K–40K Ratings Hardware Code (X) High fault interrupting capability Durable design Hardware Code Wide variety of mounting and connection options for greater flexibility in installation. H Eyebolt Spade J Eyebolt Universal Adapter Z Parallel-Groove Universal Adapter for 65K–80K Ratings Hardware Code (X) 1st End Hardware 2nd End Hardware A Threaded Stud Threaded Stud E Eyebolt Knurled Stud F Eyebolt Eyebolt U Eyebolt Universal Adapter 3.3" Trans-Guard™ EXT Current-Limiting Backup Fuse for 100K Ratings .29" C 1.8" Eyebolt A .46" (Accepts #8 – 2/0) Universal Adapter Rotatable through 180˚ B Ordering Information for 100K Ratings Nominal Voltage Rating (kV) Current Rating HTDE23E100 8.3 100K 4.9 14.0 11.9 7.5 HTDE24E100 15.5 100K 4.9 19.4 17.5 10.5 Catalog Number Dimension “A” (inches) Dimension “B” (inches) Dimension “C” (inches) Weight (lbs) PROTECTION & CONTROL Minimize Energy Let-Through — Maximize Equipment Protection. PROTECTION & CONTROL Trans-Guard™ EXT Current-Limiting Backup Fuse For 12K–40K Ratings For 100K Ratings For 65K–80K Ratings Trans-Guard EXT Current-Limiting Backup Fuse ™ Voltage Selection — Refer to Table 1. Each Trans-Guard™ EXT Current-Limiting Backup Fuse is suitable for use in both single-phase and threeIn addition to interrupting higher fault currents, the Trans-Guard™ EXT Current-Limiting phase applications where the system voltage does not exceed the Maximum System Voltage listed. For single-phase applications on delta systems, Backup Fuse serves the very important function of limiting the amount of energy one fuse is needed in each line. let-through to the source of the fault to a value below the withstand capability Current-Rating Selection — Refer to Table 2. Each Trans-Guard™ EXT Current-Limiting Backup Fuse will coordinate with any link having a of the equipment being protected. rating no greater than that listed. For types of links not listed in Table 2, please contact Thomas & Betts for assistance. For more information concerning how Trans-Guard™ EXT Current-Limiting Backup Fuses are coordinated, please consult Application Guide FS-10. Hardware Selection — Many different hardware options are available. Some options vary depending on the size of the Trans-Guard™ EXT Current- New and improved design offers you: Limiting Backup Fuse required. Please refer to Ordering Information for available options. • Smaller size and lighter weight for easier handling • Lowest energy let-through in the industry • The most complete range of ratings available Table 1 Nominal Voltage Rating (kV) 8.3 Electrical Characteristics of Trans-Guard™ EXT Current-Limiting Backup Fuse Rated Maximum Interrupting Current (kA) Peak Arc Voltage (kV) Minimum Melt I2t (A2sec) Maximum Total I2t (A2sec) 12K 26 2,700 8,000 25K 26 11,000 29,000 40K 25 26,000 72,000 Current Rating Rated Maximum Voltage (kV) 50 65K Maximum System Voltage (kV) 8.3 14.4 22 67,000 230,000 80K 22 156,000 580,000 100K 24 218,000 850,000 12K 47 2,700 9,000 49 11,000 34,000 40K 47 26,000 85,000 65K 44 67,000 230,000 25K 15.5 44 80K 17.2 50 27.6 15.5 24.9 100K 12K 25K 23.0 31 40K 23.0 65K EXPULSION FUSE OPERATION CURRENT-LIMITING FUSE OPERATION Current peak Current peak Current interruption Current interruption Fuse Current Fault Current Energy Let-Through 34.5 50 80K Table 2 Setting the Standard in System Protection 44 156,000 580,000 46 204,000 730,000 62 2,700 10,000 60 11,000 37,000 62 26,000 88,000 65 67,000 220,000 63 123,000 360,000 Trans-Guard™ EXT Current-Limiting Backup Fuse/Expulsion Fuse Link Coordination Trans-Guard EXT Fuse Rating Type K Type T Type N Type S Coordinates with links up through Type H Type D Type X Type QA Type KS 12K 12 8 20 5 8 3 2.5 15 3 25K 25 15 30 7 8 20 10 30 7 40K 40 20 50 15 8 20 15 50 15 65K 65 30 60 25 8 20 15 75 15 80K 80 50 85 40 8 20 15 100 15 100K 100 65 85 50 8 20 15 125 15 Thomas & Betts Corporation Utility Products Group 8155 T&B Blvd. Memphis, TN 38125 P: 800.888.0211 F: 800.888.0690 ©2008 Thomas & Betts Corporation. All rights reserved. Printed in the USA. PB-PC-EXT-0208 Trans-Guard™ EXT Current-Limiting Backup Fuse PROTECTION & CONTROL Minimize Energy Let-Through — Maximize Equipment Protection. PROTECTION & CONTROL Trans-Guard™ EXT Current-Limiting Backup Fuse For 12K–40K Ratings For 100K Ratings For 65K–80K Ratings Trans-Guard EXT Current-Limiting Backup Fuse ™ Voltage Selection — Refer to Table 1. Each Trans-Guard™ EXT Current-Limiting Backup Fuse is suitable for use in both single-phase and threeIn addition to interrupting higher fault currents, the Trans-Guard™ EXT Current-Limiting phase applications where the system voltage does not exceed the Maximum System Voltage listed. For single-phase applications on delta systems, Backup Fuse serves the very important function of limiting the amount of energy one fuse is needed in each line. let-through to the source of the fault to a value below the withstand capability Current-Rating Selection — Refer to Table 2. Each Trans-Guard™ EXT Current-Limiting Backup Fuse will coordinate with any link having a of the equipment being protected. rating no greater than that listed. For types of links not listed in Table 2, please contact Thomas & Betts for assistance. For more information concerning how Trans-Guard™ EXT Current-Limiting Backup Fuses are coordinated, please consult Application Guide FS-10. Hardware Selection — Many different hardware options are available. Some options vary depending on the size of the Trans-Guard™ EXT Current- New and improved design offers you: Limiting Backup Fuse required. Please refer to Ordering Information for available options. • Smaller size and lighter weight for easier handling • Lowest energy let-through in the industry • The most complete range of ratings available Table 1 Nominal Voltage Rating (kV) 8.3 Electrical Characteristics of Trans-Guard™ EXT Current-Limiting Backup Fuse Rated Maximum Interrupting Current (kA) Peak Arc Voltage (kV) Minimum Melt I2t (A2sec) Maximum Total I2t (A2sec) 12K 26 2,700 8,000 25K 26 11,000 29,000 40K 25 26,000 72,000 Current Rating Rated Maximum Voltage (kV) 50 65K Maximum System Voltage (kV) 8.3 14.4 22 67,000 230,000 80K 22 156,000 580,000 100K 24 218,000 850,000 12K 47 2,700 9,000 49 11,000 34,000 40K 47 26,000 85,000 65K 44 67,000 230,000 25K 15.5 44 80K 17.2 50 27.6 15.5 24.9 100K 12K 25K 23.0 31 40K 23.0 65K EXPULSION FUSE OPERATION CURRENT-LIMITING FUSE OPERATION Current peak Current peak Current interruption Current interruption Fuse Current Fault Current Energy Let-Through 34.5 50 80K Table 2 Setting the Standard in System Protection 44 156,000 580,000 46 204,000 730,000 62 2,700 10,000 60 11,000 37,000 62 26,000 88,000 65 67,000 220,000 63 123,000 360,000 Trans-Guard™ EXT Current-Limiting Backup Fuse/Expulsion Fuse Link Coordination Trans-Guard EXT Fuse Rating Type K Type T Type N Type S Coordinates with links up through Type H Type D Type X Type QA Type KS 12K 12 8 20 5 8 3 2.5 15 3 25K 25 15 30 7 8 20 10 30 7 40K 40 20 50 15 8 20 15 50 15 65K 65 30 60 25 8 20 15 75 15 80K 80 50 85 40 8 20 15 100 15 100K 100 65 85 50 8 20 15 125 15 Thomas & Betts Corporation Utility Products Group 8155 T&B Blvd. Memphis, TN 38125 P: 800.888.0211 F: 800.888.0690 ©2008 Thomas & Betts Corporation. All rights reserved. Printed in the USA. PB-PC-EXT-0208 Trans-Guard™ EXT Current-Limiting Backup Fuse