Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Voltage Dips and Short Interruption Immunity Test Generator As per IEC 61000 – 4 – 11 Sneha Bhavsar¹, Prof. Varsha A Shah 2, Mr. Vinod Gupta 3 1, 2 : Department of Electrical Engg., SVNIT, Surat, India. 3 Electrical Research and Development Association, ERDA Road, Makarpura GIDC, Vadodara-390010, India E-mail: s_bhavsar132@yahoo.co.in Abstract-- This paper presents Voltage Dips and Short Interruption Immunity Test Generator, to check the immunity of equipment against the voltage dips and short interruption, which occurs widely in low voltage mains and interface with electrical and electronics equipment connected to the mains. The output voltage waveforms of the immunity test generator are in full compliance with the standard IEC 61000 – 4 – 11. IEC 61000 – 4 – 11 is a common reference used to evaluate immunity of equipment while subjected to voltage dips or short interruptions. The 3 phase generator is designed for immunity testing of equipment operating at low voltage (not exceeding 240 V) and power frequency (50 Hz). Current rating of the generator is 32 amps. Generator is having user interface facility – HMI (human machine interface) using which user can generate the voltage dips or short interruption of any level and duration defined in IEC 61000 – 4 – 11. Experiment towards energy meter has been done to testify the equipment’s feasibility. The resulting waveform can show that generator can work properly. The reason is that the modern electricity utilizing equipment either in its own design or due to the incorporated control feature has become more sensitive to the voltage dips. There is a need of increase awareness of phenomenon among the supplier and user of electricity and manufacturer of equipment using electricity. System inconvenience can be reduced by proper cooperation of the supplier and user. Voltage mitigation is the one of the means for the solution of the voltage dips problem. Another solution is to increase the voltage dips immunity of the equipment. Using standards and a voltage dips and short interruption immunity test generator, it is fairly easy to modify a piece of industrial or commercial equipment to increase its immunity to voltage dips. Also proper mitigation can be carried out. The modifications are almost always simple and inexpensive. Consequently generator for testing the voltage dips and short interruption immunity of equipment is presented in this paper which is in full compliance with IEC – 61000 – 4 – 11. So far prototypical generator specified in the EMC standards involves waveform oscillator with power amplifier (WOPA), motorized variac with multi tapping transformer and throw over switches. From three strategies we have implemented the second one. Index Terms: Voltage dips, Short Interruption, Voltage dips and short interruption immunity testing I. INTRODUCTION: A voltage dips is a short-term reduction in or complete loss of, RMS voltage. It is specified in terms of duration and retained voltage, usually expressed as the percentage of nominal RMS voltage remaining at the lowest point during the dips. Voltage dips and short interruptions can be expected at any place at any time and at any level involving virtually zero voltage and duration up to and above 1 second. The frequency of their occurrence and the probability of their occurrence is at any level is highly variable both from place to place and one year to another. So voltage dips is being an in strict feature of public electricity supply. In recent decades they have become increasingly troublesome disturbance giving rise to inconveniency and even considerable economic loss. II. A. VOLTAGE DIPS AND SHORT INTERRUPTION Voltage Dips: The definition of a voltage dips is not unambiguous and often set only by two parameters depth/magnitude and duration. Different sources however present different alternatives how these parameters are interpreted. In this paper, the voltage dips magnitude is ranged from 80% to 0% of nominal voltage and with duration from half a cycle to 250 cycles. 137 Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 IEC 61000-2-8 definition [18]: included the significant source of stored energy, preventing voltage from reaching to zero during a very short interruption. Furthermore the most severe voltage dips implies the zero voltage. Such a voltage dips is effectively interruption although the connection to the voltage source remains. Thus there can be difficulty for measurement instrument to distinguish between voltage dips and shore interruption. For these reason in measuring it is necessary to adopt a boundary voltage greater than zero in order to distinguish between voltage dips and short interruption. In the event in which voltage falls below this boundary voltage is to be considered as short interruption or else voltage dips. “According to the IEC 61000 4 11 voltage less than the 20% of the rated voltage is to be considered as the short interruption.” A sudden reduction of the voltage at particular point of electricity supply below a specified dips threshold followed by its recovery after a brief interval associated with electromagnetic disturbances. Vrms 100% 40% Td Ts Tr Fig. 1. RMS Plot of Voltage Dips Of 40 % Where, Td= Delay Time Tr= Rise Time Ts = Time of reduced voltage. It is the two dimensional electromagnetic disturbance. The level is defined by both voltage amplitude and time. Notes: 1 Typically a dips is associated with the occurrence and termination of a short circuit or other extreme current increase on the system or installations connected to it. 2 A voltage dips is a two dimensional electromagnetic disturbance, the level of which is determined by both voltage and time (duration).” B. D. Need of Voltage Dips and Short Interruption Immunity Testing: Equipment on-site is becoming more sensitive to disturbances that it often self generates. The disturbances generated by electronic equipment, and its sensitivity to disturbances, is a factor that should be included in equipment specifications, and entered into commercial discussions. A survey conducted by European Copper Institute in 2001 asked facility and building managers at 1400 sites in 8 countries about the problems they experience. It showed that any of the problems listed in figure below is experienced by 25% of sites. The real incidence rate may be higher, for lack of awareness of the problem, or being unable to diagnose it as a PQ problem. Short Interruption [18]: A sudden reduction of the voltage on all phases at a particular point of electricity supply below specified interruption threshold followed by its recovery after a brief interval. Vrms 100% 0% Td Ts Tr Fig. 2. RMS Plot of Short Interruption. C. Distinguishing Between Voltage Dips and Short Interruption [18]: A short interruption implies complete disconnection form all the sources of supply and there for zero voltage. In practice the disconnected source can be Fig. 3. Incidence rate for typical power quality problems 138 Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Above survey presents the need of proper action to be taken care for the problem of supply voltage dips or short interruption. One can go for either proper mitigation technique or to use equipment already having the enough immunity level. For implying mitigating method you should know the level till which equipment can withstand the voltage dip or short interruption without any malfunction. But again that is costlier solution of the proper. New trend is to make the system or the equipment of the higher immunity. After manufacturing the equipment needs to be checked out for the designed immunity level. For above stated requirement that is either for designing equipment with higher immunity or for applying mitigation we need some reference which can check the immunity of the equipment and that reference is Voltage dips and short interruption immunity test generator. III. variac is used to set the system voltage at the rated voltage specified by the user. Position of variac is changed using the increment and decrement relay which are driven by the signal generated by PIC. Multi tapping transformer is connected to the load via bidirectional switches connected in series. SK60GM123 bidirectional IGBT is used as a switch. PIC generates the gate driving signals for the static switches. Amplitude of the gate driving signal is increased using M56962L driver IC. PIC and HMI are interacting with each other via RS 232 cable. PIC will control the system according to the condition specified by the user through the HMI. How the all modules are connected to each other that is shown in the figure given below. VOLTAGE DIPS AND SHORT INTERRUPTION IMMUNITY TEST GENERATOR: IEC 61000 – 4 – 11 describes three distinct methodologies of voltage dips and short interruption immunity test generator. First is Waveform Oscillator with Power Amplifier, second is Throw over Switch and third is Motorized Variac With Multi Tapping Transformer. First method can be proved costly for higher current rating. One can opt for second or third method but in this paper we have opted for third that is Motorized Variac with Multi Tapping Transformer because of isolation provision. Block diagram of selected methodology is shown below. 100% Vrated Fig. 5. Block diagram of the generator RESULTS: In order to validate the generator the wavefroms has been carried out which are shown below. 80% 70% 40% Fig. 4. Methodology of the generator IV. HARDWARE IMPLEMENTATION: Test generator is divided in two modules, one is power circuit module and another one is control card module. Motorized variac, transformer, switching devices, driver card are part of the power module. Control module consists of the PIC controller which is mainly responsible for generation of voltage dips. It also consists of HMI (Human Machine Interface) facility for user to enter the test specifications. Motorized Fig. 6. Waveform of gate pulse for class 2 of IEC 6100 4 11 standard 139 Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Fig. 10: Waveform of Class 3 voltage dip: 0% for 1.5 cycles, 40% for 10 cycles 70% for 25 cycles, 80% for 250 cycles. Fig. 7. Waveform of gate pulse for class 3 of IEC 6100 – 4 - 11 standard V. CONCLUSION: This paper presents the voltage dips and short interruption immunity test generator which is in full compliance with the IEC 61000 – 4 – 11. The term 'Power Quality' refers to the degree with which an electric power supply deviates from its nominal, sinusoidal waveform, steady state voltage condition; a larger deviation denoting poorer power quality. It must first be recognized that unlike other power quality problems, when there is a voltage dip, there is a momentary and at times substantial loss of power. This is also true, and even more so, for voltage short interruptions. It is clear that voltage dips cause widespread and serious operational and economic problems to a very wide range of industrial, commercial and service operations. Over the last few years, it has become widely recognized that power quality is compatibility issue between the supply system and the load. In other words, it is the tolerance or sensitivity of electrical loads compared to the quality that the supply system has to offer. Solution to voltage dips and short interruption is either to use proper mitigation method or to increase immunity of system. To implement any of the above solution we first need to check the voltage dips and short interruption immunity of the equipment. Fig. 8. Waveform of short interruption for 1 sec performed for 3 times REFERENCES: [1] YU Shying, LIU Guangbin, WU Hong, “Development of generator for voltage dips, short interruption and voltage variation immunity test” [2] R. Mienski, R. Pawelek, I. Wasiak ,” A Simulation Method for Estimating Supply Voltage Dips in Electrical Power Networks ” [3] Giinther BRAUNER, Christian HENNERBICHLER, “VOLTAGE DIPS AND SENSITIVITY OF CONSUMERS IN LOW VOLTAGENETWORKS” [4] Andreas Eberhard, Vice President of Technical Services, “New Developments in Power Quality Immunity and Voltage Sag Fig. 9: Waveform of Class 2 voltage dip: 0% for 1.5 cycles, 70% for 25 cycles. 140 Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Standards:Hands-on Applications in North America, Asia, and Europe” [5]Kjell Sand, Knut Samdal, Helge Seljeseth SINTEF Energy Research, “QUALITY OF SUPPLY REGULATION – STATUS AND TREND” [6]ITI (CBEMA) curve application note,[Online document], Available at http://www.itic.org [7]Power quality application guide,[Online document], Available at http://www.itic.org [8] Bhattacharya, K., Bollen, M. and Daalder, J. (2001) “Operation of Restructured Power Systems”. Kluwer’s Power Electronics and Power Systems Series, Kluwer Academic Publishers. [9] Heydt, G. (1999). “Electric Power Quality”. Start in a Circle Publications, West LaFayette, Indiana 1991. [10] Dugan, R., McGranaghan, F. and Wayne H. (1996) “Electrical Power Systems Quality”. McGraw-Hill New York, 1996. [11] GABRIEL OLGUIN: Thesis for the degree of doctor of philosophy: “Voltage Dip (Sag) Estimation in Power Systems based on Stochastic Assessment and Optimal Monitoring” [12] Davenport, F. (1991). “Voltage Dips and Short Interruptions in Medium Voltage Public Electricity Supply” Systems”. Electricity Association, London. Group of Experts: F. W. T. Davenport (Chairman), D. Bose, U. Grape, M. Kasztler, J. N. Luttjehuizen, H. Seljeseth, M. Silvestri, D. J. Start, J-P Tete, J. Votsmeier, R. Tonon. [13] Dorr, D.S. (1992). “National Power Laboratory Power Quality Study Results Based on 600 Site-months”. Telecommunications Energy 14th International Conference, 1992. INTELEC '92. 1992 [14] Dorr, D.S. et al (1996) M. “Interpreting Recent Power Quality Surveys to Define the Electrical Environment”. Conference Record of the 1996 IEEE Industry Applications Conference. Thirty-first IAS Annual Meeting. [15] Wagner, C.F., Evans, R.D. (1933). “Symmetrical Components; As applied to the Analysis of Unbalanced Electrical Circuits”, First Edition, McGraw-Hill Book Inc., New York 1933. [16] Koval, D.O. and Hughes, B.M. (1996). “Frequency of Voltage Sags At Industrial and Commercial Sites in Canada”. Canadian Conference on Electrical and Computer Engineering, CCEC’96, Canada 1996. Reference Standards: [17] IEC 61000 – 2 – 8: Environment - on public electric power supply system with statistical measurement results. [18] IEC 61000 – 4 – 11: Testing and measurement technique. Voltage dips, short interruption and immunity test. [19] IEEE Std. 1100 (1999): “Recommended Practice for Powering and Grounding Electronic Equipment”. [Revision of IEEE Std 1100- 1992]. BIO-DATA OF AUTHOR(S): Sneha D Bhavsar is pursuing M Tech in Electrical (Industrial Electronics) from SVNIT, Surat & obtained B.E. in Electrical from VNSGU in May-June 2004. She has presented paper in national conference on current trends in technology. Shri Vinod Gupta obtained Master of Engineering in Electrical engineering from M.S. University Vadodara in December 2003 & B.E. in Power Electronics from L.E. college, Morvi in 1993. He has more than 13 years of experience in R&D of Power Electronics & Instrumentation. 141