0739DB9901R11/03 June 2004 Cedar Rapids, Iowa, USA Data Bulletin International Miniature Circuit Breakers with QO® Plug-on and Bolt-on Connections Class Number 0739 Retain for future use. GENERAL DESCRIPTION The following topics are covered in this bulletin. ■ Characteristics on page 2 ■ Circuit Breaker Operating Characteristics on page 3 ■ Main Circuit Breakers on page 5 ■ QO-MBGX main circuit breakers with residual current protection on page 7 ■ Main Switch Disconnectors and Main Lugs on page 10 ■ QOE200 Main Switch with Residual Current Protection on page 12 ■ QOE Circuit Breakers on page 14 ■ QOE-RCBO Circuit Breakers with Residual Current Protection on page 17 ■ QOH-X Circuit Breakers on page 20 ■ QOH-RCDX Circuit Breakers with Residual Current Protection on page 24 ■ QOXD Circuit Breakers on page 27 In 1955 Square D Company introduced the QO® Plug-on System and revolutionized the way electrical contractors install miniature circuit breakers in the United States. Today, as part of Schneider Electric, we offer the same Plug-on System technology around the world. A full line of IEC Certified QO products are available for residential, commercial and industrial applications. © 2000-2004 Schneider Electric All Rights Reserved Table 1: International Miniature Circuit Breaker Description Circuit Breaker Description Single-phase Consumer Units Three-phase Distribution Boards QO-MBX Main circuit breakers — QO-MBGX Main circuit breakers with residual current protection — QO-M/QO-L Main switches and lugs QOE200 Main switches with residual current protection QOE Branch circuit breaker QOE-RCBO Branch circuit breaker with residual current protection QOH-X Branch circuit breaker QOH-RCDX Branch circuit breaker with residual current protection QOXD Branch circuit breaker — 1 International Miniature Circuit Breakers CHARACTERISTICS Advantages of the Plug-on System 0739DB9901R11/03 June 2004 • Circuit breakers are rated 240 Vac single-phase and 415 Vac threephase, 50/60 Hz, 3–100 A. • • Circuit breakers are available in 1-, 2- or 3-pole construction. • RCBO devices available with 10 mA, 30 mA and 100 mA residual current protection. • Trip-free handle ensures tripping even when the circuit breaker is held or locked in the ON position. • Circuit breakers are in compliance with international standards set by the International Electrotechnical Commission (IEC). • The CE marking is located on each circuit breaker in accordance with the low-voltage directive of the European Union. • The entire QO circuit breaker family provides the advantage of a plug-on connection. (Bolt-on connections also available.) • A 50% reduction on installation time compared to a lug/lug (DIN) alternative. • • • No link bars to fit and tighten. Thermal trip elements are factory calibrated to 40°C (IEC 947-2) and 30°C (IEC 898) ambient temperature. Contact jaws automatically align the circuit breakers in the equipment. High short circuits result in an increase in jaw pressure reducing the potential for hazardous arcs on the line side of the circuit breaker. Plug-on System 07393011 Figure 1: 2 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 Table 2: International Miniature Circuit Breakers Accessories QO-MBGX QOE-200 QOE QOE-RCBO Handle Tie Converts any two adjacent 120/240 Vac single-pole circuit breakers to independenttrip 2-pole. QO1HT — — — — — Clamp for holding QO single-pole circuit breaker handle in ON or OFF position. QO1LO — — — — — Clamp for holding QO either 1-, 2- or 3-pole circuit breaker handles in ON or OFF position. HLO-1 — — — Handle Clamp Handle Padlock Attachment Attaches to 1-, 2- and 3-pole circuit breaker handles (removable). QOEPLA — — Attaches to single-pole circuit breaker handles (removable). QOE-1PL — — — — For padlocking single-pole QO circuit breaker in ON or OFF position (fixed). QO1PA — — — — — For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3pole QO circuit breakers which require padlocking in either ON or OFF position (fixed). QO1PL — — — — For padlocking single-pole QO circuit breaker in ON or OFF position (removable). QOHPL — — — — For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3pole QO circuit breakers which require padlocking in either ON or OFF position (removable). QO1HPL — — — For padlocking 2-pole QO-MBGX circuit breaker in either ON or OFF position (removable). GFI2PA — — — — For padlocking single-pole QO circuit breaker in the OFF position only (fixed). QO1PAF — — — — — For padlocking 2- and 3-pole QO circuit breakers in the OFF position only (fixed). QO2PAF — — — — — — QOXD Accessory Catalog Number QOH-RCDX Description QOH-X Accessory QO-MBX Circuit Breaker Catalog Number — — — — — — — — — — — — CIRCUIT BREAKER OPERATING CHARACTERISTICS Table 3: Main Circuit Breakers Circuit Breaker Catalog Number Prefix Plug-on Number of Poles Bolt-on Continuous Ampere Rating IEC 60947-2 Service Rating Icu (Ics) 240 V Residual Trip Current BS4293 415 V QO-MBX N/A 2 10–100 10 000 (25%) — — QO-MBGX30 N/A 2 16–63 10 000 (25%) — 30 mA Table 4: Branch Circuit Breakers Circuit Breaker Catalog Number Prefix Number of Poles Continuous Ampere IEC 898 Service Rating Icn Rating 240 V 415 V Tripping Characteristics Plug-on Bolt-on QOXD QOBXD 1, 2, 3 10–32 3 000 3 000 Type D (10–20 In) QO-EB6 N/A 1 3–63 6 000 — Type B (3–5 In) QO-EC6 N/A 1, 3 6–63 6 000 6 000 Type C (5–10 In) QO-ED6 N/A 1 6–63 6 000 — Type D (10–20 In) Type B (3–5 In) QO-EB10 N/A 1 3–63 10 000 — QO-EC10 N/A 1, 2, 3 6–63 10 000 10 000 Type C (5–10 In) QO-ED10 N/A 1, 2, 3 6–63 10 000 10 000 Type D (10–20 In) © 2000-2004 Schneider Electric All Rights Reserved 3 International Miniature Circuit Breakers Table 5: Branch Circuit Breakers Circuit Breaker Catalog Number Prefix Plug-on Bolt-on QOXD QOBXD QOH-X Table 6: Number of Poles IEC 947-2 Service Rating Icu (Ics) 415 V 1, 2, 3 10–32 3 000 (100%) 3 000 (100%) 1 40–63 3 000 (50%) — 2, 3 40–100 3 000 (50%) 3 000 (50%) 1, 2, 3 10–63 5 000 (25%) 5 000 (25%) 1, 2, 3 70–100 6 000 (25%) 6 000 (25%) 4 100 — 6 000 (25%) Residual Current Circuit Breakers Number of Poles Plug-on Bolt-on QOE-B01 N/A 1 QOE-B03 N/A 1 QOE-C01 N/A QOE-C03 QOE-C100 Continuous Ampere Rating IEC 898 Service Rating Icn Residual Trip Current BS4293 240 V 415 V 6–40 10 000 — 10 mA 6–40 10 000 — 30 mA 1 6–40 10 000 — 10 mA N/A 1 6–40 10 000 — 30 mA N/A 1 6–40 10 000 — 100 mA Residual Current Circuit Breakers Circuit Breaker Catalog Number Prefix Number of Poles Plug-on Bolt-on QOH-RCDX10 QOBH-RCDX10 1 QOH-RCDX30 QOBH-RCDX30 1 4 Continuous Ampere Rating 240 V QOBH-X Circuit Breaker Catalog Number Prefix Table 7: 0739DB9901R11/03 June 2004 Continuous Ampere Rating IEC 947-2 Service Rating Icu (Ics) 240 V 415 V 10–32 5 000 (25%) — 10–32 5 000 (25%) — © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers MAIN CIRCUIT BREAKERS QO-MBX Circuit Breaker • Compliance with International Standards: Certified to IEC 60947-2, 10 kA at 240 Vac when used as a main incomer on single-phase systems, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. 07393002 Figure 2: QO-MBX main circuit breakers are designed for use as incoming main devices for single-phase consumer unit applications. Table 8: QO-MBX Circuit Breaker Continuous Ampere Rating Circuit Breaker Catalog Number 2-Pole Circuit Breaker 16 QO216MBX 20 QO220MBX 32 QO232MBX 45 QO245MBX 63 QO263MBX 70 QO270MBX 80 QO280MBX 100 QO2100MBX • Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent red trip indicator on the front of the circuit breaker). • Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature. • Endurance (Switching Operations): — 1,500 full-load operations — 8,500 no-load operations Accessories QO-MBX Circuit Breaker Accessories 07393043 07393026 Figure 3: HLO-1 Handle Clamp 07393042 QO1HPL Removable Padlock Attachment • Mounting: Plug-on connection. • Handle Clamp (HLO-1) The handle clamp accessory fastens the handle in the ON or OFF position. This handle clamp cannot be padlocked. • Handle Padlock Attachments (QO1PL, QO1HPL) Handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: Fixed and removable. The fixed style (QO1PL) is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style (QO1HPL) is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) — Removable attachment: QO1HPL — Fixed attachment: QO1PL QO1PL Fixed Padlock Attachment © 2000-2004 Schneider Electric All Rights Reserved 5 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 Lugs 07393015 Figure 4: QO-MBX Circuit Breaker Lugs Table 9: QO-MBX Circuit Breaker Lugs Continuous Ampere Rating (1) (2) 45–63 A Lugs 10–32 A Lugs 70–100 A Lugs Wire Type Wire Size mm AWG 10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36 10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36 45–63 Al/Cu (1) 10–25 (1) #8–#2 75°C 5 45 70–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50 2 Temperature Rating Torque Value N•m lb-in Dimensions QO-MBX Circuit Breaker Dimensions Dim. A: 3.0 in. (76 mm), 10–32 A Dim. B: 3.125 in. (79 mm), 45–63 A Dim. C: 3.5 in. (89 mm), 70–100 A 0.94 (24) 3° 26° Dim. B Dim. A 0.75 (19) 6 Dim. C ° 22 2 1° Re set 0.16 (4) ON 1.34 (34) 0.53 (13) Tripped 1.48 (38) OF F 07393030 Figure 5: 0.25 (6) 2.92 (74) 2.91 (74) 2.31 (59) 2.75 (70) Dual Dimensions: in. (mm) © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers QO-MBGX MAIN CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION QO-MBGX Circuit Breaker 07393009 Figure 6: Table 10: QO-MBGX Circuit Breakers Continuous Ampere Rating Circuit Breaker Catalog Number Residual Trip Current 30 mA 2-Pole 16 QO216MBGX30 20 QO220MBGX30 32 QO232MBGX30 45 QO245MBGX30 63 QO263MBGX30 QO-MBGX main circuit breakers with residual current protection are designed for use as incoming main devices for single-phase consumer unit applications. • Compliance with International Standards: Certified to IEC 61009-1 10 kA at 240 Vac when used as a main incomer on single-phase systems, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload, short circuit or residual current ground fault is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker). • Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface. • • Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature Residual Current Protection: Residual ground-fault trip currents are factory set at 30 mA. • Endurance (Switching Operations): — 1,500 full-load operations — 8,500 no-load operations • Mounting: Plug-on connection. • Handle Clamp (HLO-1) The handle clamp accessory fastens the handle in the ON or OFF position. This handle clamp cannot be padlocked. • Handle Padlock Attachments (GFI2PA, QO1HPL) Handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed (GFI2PA) and removable (QO1HPL). The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) Accessories QO-MBGX Circuit Breaker Accessories 07393026 Figure 7: 07393043 07393042 HLO-1 Handle Clamp GFI2PA Fixed Padlock Attachment QO1HPL Removable Padlock Attachment © 2000-2004 Schneider Electric All Rights Reserved 7 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 Lugs QO-MBGX Circuit Breaker Lug 07393016 Figure 8: Table 11: QO-MBGX Circuit Breaker Lug Continuous Ampere Rating Wire Type 16–63 Al/Cu Lug Wire Size mm2 AWG (1) 2.5-16 (1) #14–#6 Temperature Rating 75°C Torque Value N•m lb-in 5 45 16–63 A Lug Dimensions QO-MBGX Circuit Breaker Dimensions 0.94 (24) 3° 07393031 Figure 9: 21 ° Re set OF F ON 22 ° Tripped 26° 2.91 (74) 2.31 (59) 1.49 (38) 8 4.12 (103) Dual Dimensions: in. (mm) © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Connections 07393029 Figure 10: QO-MBGX Circuit Breaker Connections in 240 Vac Single-phase Consumer Unit Branch Circuit Breakers 240 Vac Source L N 240 V Load Load 240 V QO-MBGX Main Circuit Breaker Load S/N GND © 2000-2004 Schneider Electric All Rights Reserved 9 International Miniature Circuit Breakers MAIN SWITCH DISCONNECTORS AND MAIN LUGS QO-M Main Switch Disconnector QO-M main switch disconnectors and QO-L main lugs are designed for use as incoming main devices in single-phase consumer unit and three-phase distribution panelboard applications. • 07303008 Figure 11: 0739DB9901R11/03 June 2004 Compliance with International Standards: QO-M switches are certified to IEC 60947-3 at 240 Vac single phase and 415 Vac three phase, 50/60 Hz, CE marked. — Duty category AC21-A (125 A) and AC22-B (100 A). Figure 12: • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Over-center toggle mechanism. ON-OFF isolator switch disconnector. • • Mounting: Plug-on connection. Accessories: A padlocking feature is incorporated into the design of the switch disconnector. QO-L Main Lug 07303014 Table 12: QO-M/QO-L Main Switch Disconnect and Main Lug Ampere Rating Catalog Number Main Switch Units 1-Pole 2-Pole 3-Pole 100 N/A QO1100M — — 125 N/A N/A QO3100M — 125 (4-pole) N/A N/A QO4100M QO4100M 125 (4-pole with solid neutral) N/A N/A QO4100MN QO4100MN 100 QO1100L N/A N/A — 125 N/A N/A QO3100L — 125 (4-pole) N/A N/A QO4100L QO4100L 4-Pole Main Lug Units Lug QO-M/QO-L Lug 07393020 Figure 13: Table 13: Table 11: QO-M/QO-L Lug Continuous Ampere Rating Wire Type 100–125 Al/Cu Lug Wire Size mm2 AWG (1) 10–50 (1) #12–#2/0 Temperature Rating 75°C Torque Value N•m lb-in 6 50 100–125 A Lug 10 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Dimensions QO-M Main Switch Disconnector Dimensions 2.25 (57) 07393032 Figure 14: 0.25 (6.3) 1.62 (41) 0.34 (8.7) 0.20 (5) 60° 0.29 (7.5) 0.56 (39) 0.25 (6.3) 0.43 (11) 3.20 (81) 3.0 (76) 2.25 (57) 1.50 (38) 0.75 (19) 3.36 (85) 0.55 (14) Dual Dimensions: © 2000-2004 Schneider Electric All Rights Reserved in. (mm) 11 International Miniature Circuit Breakers QOE200 MAIN SWITCH WITH RESIDUAL CURRENT PROTECTION QOE200 Main Switch 07393004 Figure 15: 0739DB9901R11/03 June 2004 QOE200 main switches with residual current protection are designed for use as incoming main devices in single-phase consumer unit applications. • Compliance with International Standards: Certified to BS 4293 at 240 Vac single-phase, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on residual current ground fault is by location of the handle in the OFF position. The circuit breaker is also equipped with a red trip indicator on the front of the device. • Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface. • Residual Current Protection: Residual ground-fault trip currents are factory set at 30 mA, 100 mA or 300 mA. They are sensitive to ac currents. • Mounting: Plug-on connection. Continuous Ampere Rating Circuit Breaker Catalog Number (2-Pole) Residual Trip Current 30 mA 63 QOE200R30 100 QOE20030 Residual Trip Current 100 mA 63 QOE200R100 100 QOE200100 100 with time delay QOE200100S Residual Trip Current 300 mA Accessory 07393023 Figure 16: 12 63 QOE200R300 100 QOE200300 Handle Padlock Attachment (QOEPLA) QOEPLA Handle Padlock Attachment The handle padlock attachment allows padlocking of the main switch handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Lug QOE200 Circuit Breaker Lug Table 14: 07393019 Figure 17: QOE200 Circuit Breaker Lug Continuous Ampere Rating Wire Type 63–100 Cu Lug Wire Size mm2 AWG (1) 10–50 (1) #8–#1/0 Temperature Rating 75°C Torque Value N•m lb-in 3.5 32 63–100 A Lug Dimensions Figure 18: QOE200 Circuit Breaker Dimensions 07393033 1.45 (37) 1.40 (35) 0.49 (12) 0.45 (11) 0.19 (5) 4.13 105 2.68 (68) 0.35 (8.8) 85° 0.19 (5) Dual Dimensions: in. (mm) Connections 07393040 Figure 19: QOE200 Circuit Breaker Connections Line Power Load Switches QOE-200 2-pole Circuit Breaker L N 240 V Load Power Load 1 Load 2 240 V Load Neutral Load 3 S/N GND © 2000-2004 Schneider Electric All Rights Reserved 13 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 QOE CIRCUIT BREAKERS QOE current-limiting branch circuit breakers are designed for use in singlephase consumer unit and three-phase distribution panelboard applications. Figure 20: • Compliance with International Standards: Certified to IEC 60898, 6 kA and 10 kA at 240 Vac single-phase and 415 Vac three-phase, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the handle of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle that ensures tripping even when held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position. • Thermal Trip Element: Thermal trip elements are factory calibrated at 30°C ambient temperature (50°C calibration available: Contact your local sales office). Instantaneous-trip level types B, C and D: — Type B—(3–5 In) Overcurrent protection for sensitive equipment 07393077 QOE 1-Pole Circuit Breaker QOE 3-Pole Circuit Breaker 07393005 Figure 21: • Accessory Handle Padlock Attachment (QOEPLA) Mounting: Plug-on connection. Handle Padlock Attachment (QOEPLA) The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) 07393023 Figure 22: — Type C—(5–10 In) Overcurrent protection for all application types — Type D—(10–14 In) Overcurrent protection for loads with high inrush currents Lugs 07393017 3–25 A Lug 14 QOE Circuit Breaker Lugs 07393018 Figure 23: Table 15: QOE Circuit Breaker Lugs Continuous Ampere Rating Wire Type 3–25 32–63 Lug Wire Size Temperature Rating Torque Value mm2 AWG N•m lb-in Cu 1–25 (1) #18–#14 75°C 3.5 32 Cu 2.5–35 (1) #14–#2 75°C 3.5 32 32–63 A Lug © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Thermal-magnetic Plug-on Circuit Breakers 240/415 Vac, 10–63 A, Certified to IEC 898 Table 16: QOE Circuit Breakers (10 kA) and QOE Circuit Breakers (6 kA) QOE Circuit Breakers (10 kA) QOE Circuit Breakers (6 kA) Ampere Rating Circuit Breaker Catalog Number Ampere Rating Circuit Breaker Catalog Number Type B Instantaneous Trip Circuit Breakers 1-Pole 2-Pole 3-Pole Type B Instantaneous Trip Circuit Breakers 1-Pole 2-Pole 3-Pole 3 QO103EB10 N/A N/A 3 QO103EB6 N/A N/A 6 QO106EB10 N/A N/A 6 QO106EB6 N/A N/A 10 QO110EB10 N/A N/A 10 QO110EB6 N/A N/A 16 QO116EB10 N/A N/A 16 QO116EB6 N/A N/A 20 QO120EB10 N/A N/A 20 QO120EB6 N/A N/A 25 QO125EB10 N/A N/A 25 QO125EB6 N/A N/A 32 QO132EB10 N/A N/A 32 QO132EB6 N/A N/A 40 QO140EB10 N/A N/A 40 QO140EB6 N/A N/A 50 QO150EB10 N/A N/A 50 QO150EB6 N/A N/A 63 QO163EB10 N/A N/A 63 QO163EB6 N/A N/A Type C Instantaneous-trip Circuit Breakers Type C Instantaneous-trip Circuit Breakers 6 QO106EC10 QO206EC10 QO306EC10 6 QO106EC6 N/A QO306EC6 10 QO110EC10 QO210EC10 QO310EC10 10 QO110EC6 N/A QO310EC6 16 QO116EC10 QO216EC10 QO316EC10 16 QO116EC6 N/A QO316EC6 20 QO120EC10 QO220EC10 QO320EC10 20 QO120EC6 N/A QO320EC6 25 QO125EC10 QO225EC10 QO325EC10 25 QO125EC6 N/A QO325EC6 32 QO132EC10 QO232EC10 QO332EC10 32 QO132EC6 N/A QO332EC6 40 QO140EC10 QO240EC10 QO340EC10 40 QO140EC6 N/A QO340EC6 50 QO150EC10 QO250EC10 QO350EC10 50 QO150EC6 N/A QO350EC6 63 QO163EC10 QO263EC10 QO363EC10 63 QO163EC6 N/A QO363EC6 Type D Instantaneous-trip Circuit Breakers Type D Instantaneous-trip Circuit Breakers 6 QO106ED10 QO206ED10 QO306ED10 6 QO106ED6 N/A N/A 10 QO110ED10 QO210ED10 QO310ED10 10 QO110ED6 N/A N/A 16 QO116ED10 QO216ED10 QO316ED10 16 QO116ED6 N/A N/A 20 QO120ED10 QO220ED10 QO320ED10 20 QO120ED6 N/A N/A 25 QO125ED10 QO225ED10 QO325ED10 25 QO125ED6 N/A N/A 32 QO132ED10 QO232ED10 QO332ED10 32 QO132ED6 N/A N/A 40 QO140ED10 QO240ED10 QO340ED10 40 QO140ED6 N/A N/A 50 QO150ED10 QO250ED10 QO350ED10 50 QO150ED6 N/A N/A 63 QO163ED10 QO263ED10 QO363ED10 63 QO163ED6 N/A N/A © 2000-2004 Schneider Electric All Rights Reserved 15 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 Dimensions QOE Circuit Breaker Dimensions 3.20 81 07393034 Figure 24: 2.24 (57) 0.5 (14) 82° 0.11 (2.8) 2.03 (51) 3.2 (81) 2.21 (56) 1.47 (37) 0.73 (18) 2.91 (74) 2.31 (59) Dual Dimensions: 16 in. (mm) © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 QOE-RCBO CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION QOE-RCBO Circuit Breaker 07393013 Figure 25: International Miniature Circuit Breakers QOE-RCBO branch circuit breakers with residual current protection and integral overcurrent protection are designed for use in single-phase consumer unit and three-phase distribution panelboard applications. • Compliance with International Standards: Certified to IEC 60898 and BS4293, 10 kA at 240 Vac, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position. Indication of a tripped circuit breaker on residual current ground fault is by location of the handle in an intermediate position. • Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface. • Thermal Trip Element: Thermal trip elements are factory calibrated at 30°C ambient temperature. • Instantaneous trip level types B and C: — Type B—(3–5 In) Overcurrent protection for sensitive equipment — Type C—(5–10 In) Overcurrent protection for all application types © 2000-2004 Schneider Electric All Rights Reserved • Residual Current Protection: Residual ground-fault trip currents are factory set at 10 mA, 30 mA or 100 mA: Type A. • Trip Mechanism: Device will trip on loss of neutral. Device is sensitive to both ac and pulsating dc fault current. Device will trip on voltage between neutral and earth greater than 50 Vac. • Mounting: Plug-on connection. 17 International Miniature Circuit Breakers Table 17: 0739DB9901R11/03 June 2004 QOE-RCBO Circuit Breakers with Instantaneous Trip and Residual Trip Current Type B Type D Type C Ampere Rating Circuit Breaker Catalog Number Ampere Rating Circuit Breaker Catalog Number Ampere Rating Circuit Breaker Catalog Number 10 mA 1-Pole 10 mA 1-Pole 10mA 1-Pole 6 QOE106B01 6 QOE106C01 10 QOE110B01 10 QOE110C01 16 QOE116B01 16 QOE116C01 20 QOE120B01 20 QOE120C01 32 QOE132B01 32 QOE132C01 40 QOE140B01 40 QOE140C01 30 mA 30 mA 30 mA 6 QOE106B03 6 QOE106C03 6 QOE106D03 10 QOE110B03 10 QOE110C03 10 QOE110D03 16 QOE116B03 16 QOE116C03 16 QOE116D03 20 QOE120B03 20 QOE120C03 20 QOE120D03 32 QOE132B03 32 QOE132C03 32 QOE132D03 40 QOE140B03 40 QOE140C03 100 mA 100 mA 100 mA 6 QOE106C100 6 QOE106D10 10 QOE110C100 10 QOE110D10 16 QOE116C100 16 QOE116D10 20 QOE120C100 20 QOE120D10 32 QOE132C100 32 QOE132D10 Accessory QOE1PL Handle Padlock Attachment 07393023 Figure 26: Handle Padlock Attachment (QOE1PL) The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) Lugs 07393021 Figure 27: QOE-RCBO Circuit Breaker Lug Table 17: QOE-RCBO Circuit Breaker Lug Continuous Ampere Rating Wire Type Lug Wire Size mm2 AWG 6–40 Cu (1) 1–10 (1) #18–#8 Temperature Rating Torque Value N•m lb-in 75°C 1.0 9 6–40 A Lug 18 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Dimensions Figure 28: QOE-RCBO Circuit Breaker Dimensions 0.17 (4.5) 07393035 0.68 (17) 0.19 (5) 0.73 (18) 0.34 (8.8) 0.27 (7) 60° 0.37 (9.5) 60° 0.35 (9) 4.36 (110) 2.53 (64) 0.15 (4) 0.59 (5) 0.29 (7.3) Dual Dimensions: in. (mm) Connections Figure 29: QOE-RCBO Circuit Breaker Connections 07393041 A—Load Power Line Power N QOE-RCBO 1-pole Circuit Breaker B—Load Neutral C—Panel Neutral Wire Blue L D—Panel Earth Wire Yellow/Green A B Load 1 C Load 2 D © 2000-2004 Schneider Electric All Rights Reserved 19 International Miniature Circuit Breakers QOH-X CIRCUIT BREAKERS QOH-X 1-Pole Circuit Breaker QOH-X branch circuit breakers are designed for use in single-phase consumer unit and three-phase distribution panelboard applications. • Compliance with International Standards: Certified to IEC 60947-2, 5 kA (10–63 A) and 6 kA (70–100 A) at 240 Vac single-phase and 415 Vac three-phase, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker). Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature. 07393006 Figure 30: 0739DB9901R11/03 June 2004 Figure 31: QOH-X 4-Pole Circuit Breaker • 07393007 • Endurance (Switching Operations): — 1,500 full-load operations — 8,500 no-load operations • QOH-X and QOBH-X Circuit Breakers Table 18: Mounting: Plug-on and bolt-on connection available. Thermal-magnetic, 240/415 Vac, 10–63 A Certified to IEC 947-2 at 5 kA, 70–100 A Certified to IEC 947-2 at 6 kA QOH-X and QOBH-X Circuit Breakers QOH-X Plug-on Circuit Breakers QOBH-X Bolt-on Circuit Breakers Circuit Breaker Catalog Number Continuous Ampere Rating 1-Pole 2-Pole 3-Pole Circuit Breaker Catalog Number Continuous Ampere Rating 1-Pole 2-Pole 3-Pole 10 QOH110X QOH210X QOH310X 10 QOBH110X QOBH210X QOBH310X 16 QOH116X QOH216X QOH316X 16 QOBH116X QOBH216X QOBH316X 20 QOH120X QOH220X QOH320X 20 QOBH120X QOBH220X QOBH320X 32 QOH132X QOH232X QOH332X 32 QOBH132X QOBH232X QOBH332X 45 QOH145X QOH245X QOH345X 45 QOBH145X QOBH245X QOBH345X 63 QOH163X QOH263X QOH363X 63 QOBH163X QOBH263X QOBH363X 70 QOH170X QOH270X QOH370X 70 QOBH170X QOBH270X QOBH370X 80 QOH180X QOH280X QOH380X 80 QOBH180X QOBH280X QOBH380X 100 QOH1100X QOH2100X QOH3100X 100 QOBH1100X QOBH2100X QOBH3100X 100 (4-pole) N/A N/A QOH4100X 100 (4-pole) N/A N/A QOBH4100X 20 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Accessories • Handle Tie (QO1HT) The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip, multi-pole circuit breaker. • Handle Clamps (QO1LO and HLO-1) The handle clamp accessories fasten the circuit breaker handle in the ON or OFF position. These handle clamps cannot be padlocked. QOH-X Circuit Breaker 07393027 07393025 Figure 32: — 1-pole circuit breaker handle clamp: QO1LO QO1HT Handle Tie QO1PA Fixed Padlock Attachment — 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1 • 07393043 07393028 QO1LO Handle Clamp QO1HPL Removable Padlock Attachment Handle Padlock Attachments (QOHPL, QO1PA, QO1PL and QO1HPL) The handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. Padlock is not included. 07393026 — 1-pole circuit breaker removable attachment: QOHPL — 1-pole circuit breaker fixed attachment: QO1PA — 2- and 3-pole removable attachment: QO1HPL — 2- and 3-pole fixed attachment: QO1PL 07393044 07393042 HLO-1 Handle Clamp QO1PL Fixed Padlock Attachment QOHPL Removable Padlock Attachment Lugs QOH-X Circuit Breaker Lugs (1) (2) 10–32 A Lugs Table 19: Continuous Ampere Rating 07393016 07393022 Figure 33: 45–100 A Lug © 2000-2004 Schneider Electric All Rights Reserved Table 19: QOH-X Circuit Breaker Lugs Wire Type Lug Wire Size mm2 AWG Temperature Rating Torque Value N•m lb-in 10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36 10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36 45–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50 21 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 Dimensions QOH-X Circuit Breaker Dimensions 07393036 Figure 34: NOTE: QOBH-X circuit breaker dimensions are the same as the QOH-X circuit breaker dimensions except as shown Dim. A: 3.5 in. (88.9 mm), 45–100 A for 1-, 2- and 3-pole Dim. B: 3.00 in. (76.2 mm), 10–32 A for 1-, 2- and 3-pole Dim. A 2.25 (57) Dim. B 0.73 0.18 (19) (4) 0.59 (15) 0.38 (10) 2.23 (57) 2.09 (53) 0.53 (13) 22° 0.16 (4) ON 1.48 (38) 1.34 (34) 0.53 (13) 3° 26° Tripped OF F Re set 0.94 24 21° 0.25 (6) 2.91 (74) 2.31 (59) 0.94 24 0.94 24 2.75 (70) Dual Dimensions: 22 2.92 (74) in. (mm) © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 QOBH-X Circuit Breaker Dimensions 07393036 Figure 35: International Miniature Circuit Breakers 0.38 (10) 0.75 (19) 0.75 (19) 0.75 (19) 2.94 (75) Dual Dimensions: © 2000-2004 Schneider Electric All Rights Reserved in. (mm) 23 International Miniature Circuit Breakers QOH-RCDX CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION QOH-RCDX Circuit Breaker 07393001 Figure 36: 0739DB9901R11/03 June 2004 QOH-RCDX branch circuit breakers with residual current protection and integral overcurrent protection are designed for use in consumer unit and three-phase distribution panelboard applications. • Compliance with International Standards: Certified to IEC 60947-2 and BS4293, 5 kA at 240 Vac, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload, short circuit or residual current ground fault is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker). • Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface. Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature. • Residual Current Protection: Residual ground-fault trip currents are factory set at 10 or 30 mA. • Endurance (Switching Operation): — 1,500 full-load operations — 8,500 no-load operations Table 20: QOH-RCDX and QOBH-RCDX Circuit Breakers with Instantaneous Trip and Residual Trip Current QOH-RCDX Circuit Breaker Continuous Ampere Rating QOBH-RCDX Circuit Breaker Circuit Breaker Catalog Number (1-Pole) Residual Trip Current 10 mA Continuous Ampere Rating Circuit Breaker Catalog Number (1-Pole) Residual Trip Current 10 mA 10 QOH110RCDX10 10 QOBH110RCDX10 16 QOH116RCDX10 16 QOBH116RCDX10 20 QOH120RCDX10 20 QOBH120RCDX10 32 QOH132RCDX10 32 QOBH132RCDX10 Residual Trip Current 30 mA Residual Trip Current 30 mA 10 QOH110RCDX30 10 QOBH110RCDX30 16 QOH116RCDX30 16 QOBH116RCDX30 20 QOH120RCDX30 20 QOBH120RCDX30 32 QOH132RCDX30 32 QOBH132RCDX30 24 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Accessories 07393025 QOH-RCDX Circuit Breaker Figure 37: Accessories 07393026 07393027 QO1HT Handle Tie QO1LO Handle Clamp QO1PA Fixed Padlock Attachment 07393022 • • Handle Clamps (HLO-1 and QO1LO) • Handle Padlock Attachments (QO1PA and QOHPL) The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. Padlock is not included. Handle Tie (QO1HT) The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip, multi-pole circuit breaker. The handle clamp accessories fasten the handle in the ON or OFF position. These handle clamps cannot be padlocked. — Removable padlock attachment: QOHPL QOHPL Removable Padlock Attachment Lugs Figure 38: Mounting: Plug-on and bolt-on connections available. — Fixed padlock attachment: QO1PA 07393044 07393028 HLO-1 Handle Clamp • • • Table 21: QOH-RCDX Circuit Breaker Lugs QOH-RCDX Circuit Breaker Lugs (1) Continuous Ampere Rating mm2 AWG Torque Temperature Value Rating N•m lb-in Lug Wire Size Wire Type 10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36 10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36 (2) 10–32 A Lugs © 2000-2004 Schneider Electric All Rights Reserved 25 International Miniature Circuit Breakers 0739DB9901R11/03 June 2004 Dimensions QOH-RCDX Circuit Breaker Dimensions 07393037 Figure 39: 3° 26° 22° OF F Re set ON Tripped 21° 2.91 (74) 2.31 (59) 4.12 (108) 0.74 (19) Dual Dimensions: in. (mm) Connections 07393039 Figure 40: QOH-RCDX Circuit Breaker Connections 240 Vac Source L N Load Power 250 V Duplex Receptacle 240 Vac 240 V Load Neutral S/N GND 26 Equipment Ground © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers QOXD CIRCUIT BREAKERS QOXD Circuit Breaker • Compliance with International Standards: Certified to IEC 947-2 (3 kA [10–63 A]) and IEC 898 (3 kA [10–32 A]) at 240 Vac single phase and 415 Vac three phase, 50/60 Hz, CE marked. • ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings. • Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position. • Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker). • Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient (IEC 947-2) and 30°C ambient (IEC 898) temperature. • Endurance (Switching Operations): 07393010 Figure 41: QOXD branch circuit breakers are designed for use in single-phase consumer unit and three-phase distribution panelboard applications. — IEC 947-2: 1,500 full-load operations — IEC 947-2: 8,500 no-load operations — IEC 898: 4,000 full-load operations Table 21: Thermal-Magnetic Circuit Breakers QOXD Plug-on Circuit Breakers QOBXD Bolt-on Circuit Breakers Continuous Ampere Rating Circuit Breaker Catalog Number Circuit Breaker Catalog Number 1-Pole 2-Pole 3-Pole Continuous Ampere Rating 1-Pole 2-Pole 3-Pole 10 QOXD110 QOXD210 QOXD310 10 QOBXD110 QOBXD210 QOBXD310 16 QOXD116 QOXD216 QOXD316 16 QOBXD116 QOBXD216 QOBXD316 20 QOXD120 QOXD220 QOXD320 20 QOBXD120 QOBXD220 QOBXD320 25 QOXD125 QOXD225 QOXD325 25 QOBXD125 QOBXD225 QOBXD325 32 QOXD132 QOXD232 QOXD332 32 QOBXD132 QOBXD232 QOBXD332 40 QOXD140 QOXD240 QOXD340 40 QOBXD140 QOBXD240 QOBXD340 45 QOXD145 QOXD245 QOXD345 45 QOBXD145 QOBXD245 QOBXD345 50 QOXD150 QOXD250 QOXD350 50 QOBXD150 QOBXD250 QOBXD350 63 QOXD163 QOXD263 QOXD363 63 QOBXD163 QOBXD263 QOBXD363 70 — QOXD270 QOXD370 70 — QOBXD270 QOBXD370 80 — QOXD280 QOXD380 80 — QOBXD280 QOBXD380 100 — QOXD2100 QOXD3100 100 — QOBXD2100 QOBXD3100 © 2000-2004 Schneider Electric All Rights Reserved 27 International Miniature Circuit Breakers Accessories 0739DB9901R11/03 June 2004 Mounting: Plug-on and bolt-on connection available. 07393025 QOXD Circuit Breaker Figure 42: Accessories • Handle Tie (QO1HT) The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip multi-pole circuit breaker. • Handle Clamps (HLO-1 and QO1LO) The handle clamp accessories fasten the circuit breaker handle in the ON or OFF position. These handle clamps cannot be padlocked. — 1-pole circuit breaker handle clamp: QO1LO QO1HT Handle Tie 07393027 07393026 — 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1 HLO-1 Handle Clamp • 07393044 07393028 QO1LO Handle Clamp Handle Padlock Attachments (QOHPL, QO1PA, QO1HPL and QO1PL) The handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.) — 1-pole circuit breaker removable attachment: QOHPL QOHPL Removable Padlock Attachment QO1PA Fixed Padlock Attachment — 2- and 3-pole removable attachment: QO1HPL — 2- and 3-pole fixed attachment: QO1PL 07393042 07393043 QO1HPL Removable Padlock Attachment — 1-pole circuit breaker fixed attachment: QO1PA QO1PL Fixed Padlock Attachment Lugs (1) QOXD Circuit Breaker Lug 07393016 07393022 Figure 43: (2) 10–32 A Lugs 28 45–100 A Lug Table 23: QOXD Circuit Breaker Lugs Continuous Ampere Rating Wire Type Lug Wire Size mm2 Temperature Rating Torque Value AWG N•m lb-in 10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36 10–32 Cu (only) 45–100 Al/Cu (2) 2.5–6 (2) #14–#10 60–75°C 4 36 (1) 25–50 (1) #4–#2/0 75°C 6 50 © 2000-2004 Schneider Electric All Rights Reserved 0739DB9901R11/03 June 2004 International Miniature Circuit Breakers Dimensions Figure 44: NOTE: QOBX-D circuit breaker dimensions are the same as the QOXD circuit breaker dimensions except as shown. QOXD Circuit Breaker Dimensions 07393036 Dim. A: 3.5 in. (89 mm), 70–100 A for 1-, 2- and 3-pole Dim. B: 3.125 in. (79 mm), 45–63 A for 1-, 2- and 3-pole Dim. C: 3.0 in. (76 mm), 10–32 A for 1-, 2- and 3-pole 2.25 (57) 3.00 (76) 0.94 (24) 0.53 (13) 0.59 (15) 0.38 (10) 0.16 (24) 22° Tripped 0.73 (19) 1.48 (38) 1.34 (34) 0.53 (13) ON 2.23 (57) 2.09 (53) 3° 26° F Re set Dim. C OF Dim. A Dim. B 21 ° 0.25 (6) 2.91 (74) 2.31 (59) 0.75 (19) 0.75 (19) 0.75 (19) 2.75 (70) Dual Dimensions: © 2000-2004 Schneider Electric All Rights Reserved 2.92 (74) in. (mm) 29 International Miniature Circuit Breakers QOBX-D Circuit Breaker Dimensions 07393036 Figure 45: 0739DB9901R11/03 June 2004 0.38 (10) 0.75 (19) 0.75 (19) 0.75 (19) 2.94 (75) Dual Dimensions: 30 in. (mm) © 2000-2004 Schneider Electric All Rights Reserved