International Miniature Circuit Breakers

advertisement
0739DB9901R11/03
June 2004
Cedar Rapids, Iowa, USA
Data Bulletin
International Miniature Circuit Breakers
with QO® Plug-on and Bolt-on Connections
Class Number 0739
Retain for future use.
GENERAL DESCRIPTION
The following topics are covered in this bulletin.
■
Characteristics on page 2
■
Circuit Breaker Operating Characteristics on page 3
■
Main Circuit Breakers on page 5
■
QO-MBGX main circuit breakers with residual current protection on
page 7
■
Main Switch Disconnectors and Main Lugs on page 10
■
QOE200 Main Switch with Residual Current Protection on page 12
■
QOE Circuit Breakers on page 14
■
QOE-RCBO Circuit Breakers with Residual Current Protection on
page 17
■
QOH-X Circuit Breakers on page 20
■
QOH-RCDX Circuit Breakers with Residual Current Protection on
page 24
■
QOXD Circuit Breakers on page 27
In 1955 Square D Company introduced the QO® Plug-on System and
revolutionized the way electrical contractors install miniature circuit breakers
in the United States. Today, as part of Schneider Electric, we offer the same
Plug-on System technology around the world. A full line of IEC Certified QO
products are available for residential, commercial and industrial
applications.
© 2000-2004 Schneider Electric All Rights Reserved
Table 1:
International Miniature Circuit Breaker Description
Circuit
Breaker
Description
Single-phase
Consumer
Units
Three-phase
Distribution
Boards
QO-MBX
Main circuit breakers
—
QO-MBGX
Main circuit breakers with residual
current protection
—
QO-M/QO-L
Main switches and lugs
QOE200
Main switches with residual current
protection
QOE
Branch circuit breaker
QOE-RCBO
Branch circuit breaker with residual
current protection
QOH-X
Branch circuit breaker
QOH-RCDX
Branch circuit breaker with residual
current protection
QOXD
Branch circuit breaker
—
1
International Miniature Circuit Breakers
CHARACTERISTICS
Advantages of the Plug-on System
0739DB9901R11/03
June 2004
•
Circuit breakers are rated 240 Vac single-phase and 415 Vac threephase, 50/60 Hz, 3–100 A.
•
•
Circuit breakers are available in 1-, 2- or 3-pole construction.
•
RCBO devices available with 10 mA, 30 mA and 100 mA residual
current protection.
•
Trip-free handle ensures tripping even when the circuit breaker is held or
locked in the ON position.
•
Circuit breakers are in compliance with international standards set by
the International Electrotechnical Commission (IEC).
•
The CE marking is located on each circuit breaker in accordance with
the low-voltage directive of the European Union.
•
The entire QO circuit breaker family provides the advantage of a plug-on
connection. (Bolt-on connections also available.)
•
A 50% reduction on installation time compared to a lug/lug (DIN)
alternative.
•
•
•
No link bars to fit and tighten.
Thermal trip elements are factory calibrated to 40°C (IEC 947-2) and
30°C (IEC 898) ambient temperature.
Contact jaws automatically align the circuit breakers in the equipment.
High short circuits result in an increase in jaw pressure reducing the
potential for hazardous arcs on the line side of the circuit breaker.
Plug-on System
07393011
Figure 1:
2
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
Table 2:
International Miniature Circuit Breakers
Accessories
QO-MBGX
QOE-200
QOE
QOE-RCBO
Handle Tie
Converts any two adjacent 120/240 Vac single-pole circuit breakers to independenttrip 2-pole.
QO1HT
—
—
—
—
—
Clamp for holding QO single-pole circuit breaker handle in ON or OFF position.
QO1LO
—
—
—
—
—
Clamp for holding QO either 1-, 2- or 3-pole circuit breaker handles in ON or OFF
position.
HLO-1
—
—
—
Handle
Clamp
Handle
Padlock
Attachment
Attaches to 1-, 2- and 3-pole circuit breaker handles (removable).
QOEPLA
—
—
Attaches to single-pole circuit breaker handles (removable).
QOE-1PL
—
—
—
—
For padlocking single-pole QO circuit breaker in ON or OFF position (fixed).
QO1PA
—
—
—
—
—
For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3pole QO circuit breakers which require padlocking in either ON or OFF position
(fixed).
QO1PL
—
—
—
—
For padlocking single-pole QO circuit breaker in ON or OFF position (removable).
QOHPL
—
—
—
—
For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3pole QO circuit breakers which require padlocking in either ON or OFF position
(removable).
QO1HPL
—
—
—
For padlocking 2-pole QO-MBGX circuit breaker in either ON or OFF position
(removable).
GFI2PA
—
—
—
—
For padlocking single-pole QO circuit breaker in the OFF position only (fixed).
QO1PAF
—
—
—
—
—
For padlocking 2- and 3-pole QO circuit breakers in the OFF position only (fixed).
QO2PAF
—
—
—
—
—
—
QOXD
Accessory
Catalog
Number
QOH-RCDX
Description
QOH-X
Accessory
QO-MBX
Circuit Breaker Catalog Number
—
—
—
—
—
—
—
—
—
—
—
—
CIRCUIT BREAKER OPERATING
CHARACTERISTICS
Table 3:
Main Circuit Breakers
Circuit Breaker
Catalog Number Prefix
Plug-on
Number of Poles
Bolt-on
Continuous
Ampere
Rating
IEC 60947-2 Service Rating Icu (Ics)
240 V
Residual Trip
Current BS4293
415 V
QO-MBX
N/A
2
10–100
10 000 (25%)
—
—
QO-MBGX30
N/A
2
16–63
10 000 (25%)
—
30 mA
Table 4:
Branch Circuit Breakers
Circuit Breaker
Catalog Number Prefix
Number of
Poles
Continuous Ampere IEC 898 Service Rating Icn
Rating
240 V
415 V
Tripping
Characteristics
Plug-on
Bolt-on
QOXD
QOBXD
1, 2, 3
10–32
3 000
3 000
Type D (10–20 In)
QO-EB6
N/A
1
3–63
6 000
—
Type B (3–5 In)
QO-EC6
N/A
1, 3
6–63
6 000
6 000
Type C (5–10 In)
QO-ED6
N/A
1
6–63
6 000
—
Type D (10–20 In)
Type B (3–5 In)
QO-EB10
N/A
1
3–63
10 000
—
QO-EC10
N/A
1, 2, 3
6–63
10 000
10 000
Type C (5–10 In)
QO-ED10
N/A
1, 2, 3
6–63
10 000
10 000
Type D (10–20 In)
© 2000-2004 Schneider Electric All Rights Reserved
3
International Miniature Circuit Breakers
Table 5:
Branch Circuit Breakers
Circuit Breaker
Catalog Number Prefix
Plug-on
Bolt-on
QOXD
QOBXD
QOH-X
Table 6:
Number of Poles
IEC 947-2 Service Rating Icu (Ics)
415 V
1, 2, 3
10–32
3 000 (100%)
3 000 (100%)
1
40–63
3 000 (50%)
—
2, 3
40–100
3 000 (50%)
3 000 (50%)
1, 2, 3
10–63
5 000 (25%)
5 000 (25%)
1, 2, 3
70–100
6 000 (25%)
6 000 (25%)
4
100
—
6 000 (25%)
Residual Current Circuit Breakers
Number
of Poles
Plug-on
Bolt-on
QOE-B01
N/A
1
QOE-B03
N/A
1
QOE-C01
N/A
QOE-C03
QOE-C100
Continuous
Ampere
Rating
IEC 898 Service
Rating Icn
Residual Trip
Current
BS4293
240 V
415 V
6–40
10 000
—
10 mA
6–40
10 000
—
30 mA
1
6–40
10 000
—
10 mA
N/A
1
6–40
10 000
—
30 mA
N/A
1
6–40
10 000
—
100 mA
Residual Current Circuit Breakers
Circuit Breaker
Catalog Number Prefix
Number
of Poles
Plug-on
Bolt-on
QOH-RCDX10
QOBH-RCDX10
1
QOH-RCDX30
QOBH-RCDX30
1
4
Continuous Ampere
Rating
240 V
QOBH-X
Circuit Breaker
Catalog Number Prefix
Table 7:
0739DB9901R11/03
June 2004
Continuous Ampere
Rating
IEC 947-2 Service
Rating Icu (Ics)
240 V
415 V
10–32
5 000 (25%)
—
10–32
5 000 (25%)
—
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
MAIN CIRCUIT BREAKERS
QO-MBX Circuit Breaker
•
Compliance with International Standards: Certified to IEC 60947-2,
10 kA at 240 Vac when used as a main incomer on single-phase
systems, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
07393002
Figure 2:
QO-MBX main circuit breakers are designed for use as incoming main
devices for single-phase consumer unit applications.
Table 8:
QO-MBX Circuit Breaker
Continuous Ampere Rating
Circuit Breaker
Catalog Number
2-Pole Circuit Breaker
16
QO216MBX
20
QO220MBX
32
QO232MBX
45
QO245MBX
63
QO263MBX
70
QO270MBX
80
QO280MBX
100
QO2100MBX
•
Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent red trip indicator on the front of the circuit breaker).
•
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature.
•
Endurance (Switching Operations):
— 1,500 full-load operations
— 8,500 no-load operations
Accessories
QO-MBX Circuit Breaker
Accessories
07393043
07393026
Figure 3:
HLO-1 Handle Clamp
07393042
QO1HPL Removable
Padlock Attachment
•
Mounting: Plug-on connection.
•
Handle Clamp (HLO-1)
The handle clamp accessory fastens the handle in the ON or OFF
position. This handle clamp cannot be padlocked.
•
Handle Padlock Attachments (QO1PL, QO1HPL)
Handle padlock attachments allow padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
Fixed and removable. The fixed style (QO1PL) is intended to be a
permanent device. The padlock can be removed to resume normal
operation. The removable style (QO1HPL) is intended to be a temporary
device and must be removed to resume normal operation. (Padlock is
not included.)
— Removable attachment: QO1HPL
— Fixed attachment: QO1PL
QO1PL Fixed
Padlock Attachment
© 2000-2004 Schneider Electric All Rights Reserved
5
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
Lugs
07393015
Figure 4:
QO-MBX Circuit Breaker Lugs
Table 9:
QO-MBX Circuit Breaker Lugs
Continuous
Ampere
Rating
(1)
(2)
45–63 A Lugs
10–32 A Lugs
70–100 A Lugs
Wire
Type
Wire Size
mm
AWG
10–32
Al/Cu
(1) 2.5–6
(1) #14–#8
60–75°C
4
36
10–32
Cu (only)
(2) 2.5–6
(2) #14–#10
60–75°C
4
36
45–63
Al/Cu
(1) 10–25
(1) #8–#2
75°C
5
45
70–100
Al/Cu
(1) 25–50
(1) #4–#2/0
75°C
6
50
2
Temperature
Rating
Torque Value
N•m
lb-in
Dimensions
QO-MBX Circuit Breaker Dimensions
Dim. A: 3.0 in. (76 mm), 10–32 A
Dim. B: 3.125 in. (79 mm), 45–63 A
Dim. C: 3.5 in. (89 mm), 70–100 A
0.94
(24)
3°
26°
Dim.
B
Dim.
A
0.75
(19)
6
Dim.
C
°
22
2 1°
Re
set
0.16
(4)
ON
1.34
(34)
0.53
(13)
Tripped
1.48
(38)
OF
F
07393030
Figure 5:
0.25
(6) 2.92
(74)
2.91
(74)
2.31
(59)
2.75
(70)
Dual Dimensions:
in.
(mm)
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
QO-MBGX MAIN CIRCUIT BREAKERS
WITH RESIDUAL CURRENT
PROTECTION
QO-MBGX Circuit Breaker
07393009
Figure 6:
Table 10:
QO-MBGX Circuit Breakers
Continuous
Ampere Rating
Circuit Breaker
Catalog Number
Residual Trip
Current 30 mA
2-Pole
16
QO216MBGX30
20
QO220MBGX30
32
QO232MBGX30
45
QO245MBGX30
63
QO263MBGX30
QO-MBGX main circuit breakers with residual current protection are
designed for use as incoming main devices for single-phase consumer unit
applications.
•
Compliance with International Standards: Certified to IEC 61009-1
10 kA at 240 Vac when used as a main incomer on single-phase
systems, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload, short
circuit or residual current ground fault is by location of the handle in the
center position. The circuit breaker is also equipped with the Square D
exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the
front of the circuit breaker).
•
Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
•
•
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature
Residual Current Protection: Residual ground-fault trip currents are
factory set at 30 mA.
•
Endurance (Switching Operations):
— 1,500 full-load operations
— 8,500 no-load operations
•
Mounting: Plug-on connection.
•
Handle Clamp (HLO-1)
The handle clamp accessory fastens the handle in the ON or OFF
position. This handle clamp cannot be padlocked.
•
Handle Padlock Attachments (GFI2PA, QO1HPL)
Handle padlock attachments allow padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
fixed (GFI2PA) and removable (QO1HPL). The fixed style is intended to
be a permanent device. The padlock can be removed to resume normal
operation. The removable style is intended to be a temporary device and
must be removed to resume normal operation. (Padlock is not included.)
Accessories
QO-MBGX Circuit Breaker
Accessories
07393026
Figure 7:
07393043
07393042
HLO-1 Handle Clamp
GFI2PA Fixed
Padlock Attachment
QO1HPL Removable
Padlock Attachment
© 2000-2004 Schneider Electric All Rights Reserved
7
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
Lugs
QO-MBGX Circuit Breaker Lug
07393016
Figure 8:
Table 11:
QO-MBGX Circuit Breaker Lug
Continuous
Ampere
Rating
Wire
Type
16–63
Al/Cu
Lug Wire Size
mm2
AWG
(1) 2.5-16
(1) #14–#6
Temperature
Rating
75°C
Torque Value
N•m
lb-in
5
45
16–63 A Lug
Dimensions
QO-MBGX Circuit Breaker Dimensions
0.94
(24)
3°
07393031
Figure 9:
21
°
Re
set
OF
F
ON
22 °
Tripped
26°
2.91
(74)
2.31
(59)
1.49
(38)
8
4.12
(103)
Dual Dimensions:
in.
(mm)
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Connections
07393029
Figure 10:
QO-MBGX Circuit Breaker Connections in 240 Vac Single-phase Consumer Unit
Branch Circuit Breakers
240 Vac Source
L
N
240 V
Load
Load
240 V
QO-MBGX
Main Circuit Breaker
Load
S/N
GND
© 2000-2004 Schneider Electric All Rights Reserved
9
International Miniature Circuit Breakers
MAIN SWITCH DISCONNECTORS AND
MAIN LUGS
QO-M Main Switch Disconnector
QO-M main switch disconnectors and QO-L main lugs are designed for use
as incoming main devices in single-phase consumer unit and three-phase
distribution panelboard applications.
•
07303008
Figure 11:
0739DB9901R11/03
June 2004
Compliance with International Standards: QO-M switches are
certified to IEC 60947-3 at 240 Vac single phase and 415 Vac three
phase, 50/60 Hz, CE marked.
— Duty category AC21-A (125 A) and AC22-B (100 A).
Figure 12:
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Over-center toggle mechanism. ON-OFF isolator
switch disconnector.
•
•
Mounting: Plug-on connection.
Accessories: A padlocking feature is incorporated into the design of the
switch disconnector.
QO-L Main Lug
07303014
Table 12:
QO-M/QO-L Main Switch Disconnect and Main Lug
Ampere
Rating
Catalog Number
Main Switch
Units
1-Pole
2-Pole
3-Pole
100
N/A
QO1100M
—
—
125
N/A
N/A
QO3100M
—
125 (4-pole)
N/A
N/A
QO4100M
QO4100M
125 (4-pole
with solid
neutral)
N/A
N/A
QO4100MN
QO4100MN
100
QO1100L
N/A
N/A
—
125
N/A
N/A
QO3100L
—
125 (4-pole)
N/A
N/A
QO4100L
QO4100L
4-Pole
Main Lug
Units
Lug
QO-M/QO-L Lug
07393020
Figure 13:
Table 13:
Table 11: QO-M/QO-L Lug
Continuous
Ampere
Rating
Wire
Type
100–125
Al/Cu
Lug Wire Size
mm2
AWG
(1) 10–50
(1) #12–#2/0
Temperature
Rating
75°C
Torque Value
N•m
lb-in
6
50
100–125 A Lug
10
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Dimensions
QO-M Main Switch Disconnector Dimensions
2.25
(57)
07393032
Figure 14:
0.25
(6.3)
1.62
(41)
0.34
(8.7)
0.20
(5)
60°
0.29
(7.5)
0.56
(39)
0.25
(6.3)
0.43
(11)
3.20
(81)
3.0
(76)
2.25
(57)
1.50
(38)
0.75
(19)
3.36
(85)
0.55
(14)
Dual Dimensions:
© 2000-2004 Schneider Electric All Rights Reserved
in.
(mm)
11
International Miniature Circuit Breakers
QOE200 MAIN SWITCH WITH RESIDUAL
CURRENT PROTECTION
QOE200 Main Switch
07393004
Figure 15:
0739DB9901R11/03
June 2004
QOE200 main switches with residual current protection are designed for
use as incoming main devices in single-phase consumer unit applications.
•
Compliance with International Standards: Certified to BS 4293 at 240
Vac single-phase, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on residual
current ground fault is by location of the handle in the OFF position. The
circuit breaker is also equipped with a red trip indicator on the front of the
device.
•
Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
•
Residual Current Protection: Residual ground-fault trip currents are
factory set at 30 mA, 100 mA or 300 mA. They are sensitive to ac
currents.
•
Mounting: Plug-on connection.
Continuous
Ampere Rating
Circuit Breaker
Catalog Number (2-Pole)
Residual Trip Current 30 mA
63
QOE200R30
100
QOE20030
Residual Trip Current 100 mA
63
QOE200R100
100
QOE200100
100 with time delay
QOE200100S
Residual Trip Current 300 mA
Accessory
07393023
Figure 16:
12
63
QOE200R300
100
QOE200300
Handle Padlock Attachment (QOEPLA)
QOEPLA Handle Padlock
Attachment
The handle padlock attachment allows padlocking of the main switch
handles in the ON or OFF position. The padlock attachment is intended to
be a temporary device and must be removed to resume normal operation.
(Padlock is not included.)
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Lug
QOE200 Circuit Breaker Lug
Table 14:
07393019
Figure 17:
QOE200 Circuit Breaker Lug
Continuous
Ampere
Rating
Wire
Type
63–100
Cu
Lug Wire Size
mm2
AWG
(1) 10–50
(1) #8–#1/0
Temperature
Rating
75°C
Torque Value
N•m
lb-in
3.5
32
63–100 A Lug
Dimensions
Figure 18:
QOE200 Circuit Breaker Dimensions
07393033
1.45
(37)
1.40
(35)
0.49
(12)
0.45
(11)
0.19
(5)
4.13
105
2.68
(68)
0.35
(8.8)
85°
0.19
(5)
Dual Dimensions:
in.
(mm)
Connections
07393040
Figure 19:
QOE200 Circuit Breaker Connections
Line Power
Load Switches
QOE-200
2-pole Circuit Breaker
L
N
240 V
Load Power
Load 1
Load 2
240 V
Load Neutral
Load 3
S/N
GND
© 2000-2004 Schneider Electric All Rights Reserved
13
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
QOE CIRCUIT BREAKERS
QOE current-limiting branch circuit breakers are designed for use in singlephase consumer unit and three-phase distribution panelboard applications.
Figure 20:
•
Compliance with International Standards: Certified to IEC 60898,
6 kA and 10 kA at 240 Vac single-phase and 415 Vac three-phase,
50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the handle of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle that ensures tripping even when
held or locked in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the OFF position.
•
Thermal Trip Element: Thermal trip elements are factory calibrated at
30°C ambient temperature (50°C calibration available: Contact your
local sales office).
Instantaneous-trip level types B, C and D:
— Type B—(3–5 In) Overcurrent protection for sensitive equipment
07393077
QOE 1-Pole Circuit Breaker
QOE 3-Pole Circuit Breaker
07393005
Figure 21:
•
Accessory
Handle Padlock Attachment
(QOEPLA)
Mounting: Plug-on connection.
Handle Padlock Attachment (QOEPLA)
The handle padlock attachment allows padlocking the circuit breaker
handles in the ON or OFF position. The padlock attachment is intended to
be a temporary device and must be removed to resume normal operation.
(Padlock is not included.)
07393023
Figure 22:
— Type C—(5–10 In) Overcurrent protection for all application types
— Type D—(10–14 In) Overcurrent protection for loads with high inrush
currents
Lugs
07393017
3–25 A Lug
14
QOE Circuit Breaker Lugs
07393018
Figure 23:
Table 15:
QOE Circuit Breaker Lugs
Continuous
Ampere
Rating
Wire
Type
3–25
32–63
Lug Wire Size
Temperature
Rating
Torque
Value
mm2
AWG
N•m
lb-in
Cu
1–25
(1) #18–#14
75°C
3.5
32
Cu
2.5–35
(1) #14–#2
75°C
3.5
32
32–63 A Lug
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Thermal-magnetic Plug-on Circuit
Breakers 240/415 Vac, 10–63 A, Certified
to IEC 898
Table 16:
QOE Circuit Breakers (10 kA) and QOE Circuit Breakers (6 kA)
QOE Circuit Breakers (10 kA)
QOE Circuit Breakers (6 kA)
Ampere Rating
Circuit Breaker Catalog Number
Ampere Rating
Circuit Breaker Catalog Number
Type B
Instantaneous Trip
Circuit Breakers
1-Pole
2-Pole
3-Pole
Type B
Instantaneous Trip
Circuit Breakers
1-Pole
2-Pole
3-Pole
3
QO103EB10
N/A
N/A
3
QO103EB6
N/A
N/A
6
QO106EB10
N/A
N/A
6
QO106EB6
N/A
N/A
10
QO110EB10
N/A
N/A
10
QO110EB6
N/A
N/A
16
QO116EB10
N/A
N/A
16
QO116EB6
N/A
N/A
20
QO120EB10
N/A
N/A
20
QO120EB6
N/A
N/A
25
QO125EB10
N/A
N/A
25
QO125EB6
N/A
N/A
32
QO132EB10
N/A
N/A
32
QO132EB6
N/A
N/A
40
QO140EB10
N/A
N/A
40
QO140EB6
N/A
N/A
50
QO150EB10
N/A
N/A
50
QO150EB6
N/A
N/A
63
QO163EB10
N/A
N/A
63
QO163EB6
N/A
N/A
Type C Instantaneous-trip Circuit Breakers
Type C Instantaneous-trip Circuit Breakers
6
QO106EC10
QO206EC10
QO306EC10
6
QO106EC6
N/A
QO306EC6
10
QO110EC10
QO210EC10
QO310EC10
10
QO110EC6
N/A
QO310EC6
16
QO116EC10
QO216EC10
QO316EC10
16
QO116EC6
N/A
QO316EC6
20
QO120EC10
QO220EC10
QO320EC10
20
QO120EC6
N/A
QO320EC6
25
QO125EC10
QO225EC10
QO325EC10
25
QO125EC6
N/A
QO325EC6
32
QO132EC10
QO232EC10
QO332EC10
32
QO132EC6
N/A
QO332EC6
40
QO140EC10
QO240EC10
QO340EC10
40
QO140EC6
N/A
QO340EC6
50
QO150EC10
QO250EC10
QO350EC10
50
QO150EC6
N/A
QO350EC6
63
QO163EC10
QO263EC10
QO363EC10
63
QO163EC6
N/A
QO363EC6
Type D Instantaneous-trip Circuit Breakers
Type D Instantaneous-trip Circuit Breakers
6
QO106ED10
QO206ED10
QO306ED10
6
QO106ED6
N/A
N/A
10
QO110ED10
QO210ED10
QO310ED10
10
QO110ED6
N/A
N/A
16
QO116ED10
QO216ED10
QO316ED10
16
QO116ED6
N/A
N/A
20
QO120ED10
QO220ED10
QO320ED10
20
QO120ED6
N/A
N/A
25
QO125ED10
QO225ED10
QO325ED10
25
QO125ED6
N/A
N/A
32
QO132ED10
QO232ED10
QO332ED10
32
QO132ED6
N/A
N/A
40
QO140ED10
QO240ED10
QO340ED10
40
QO140ED6
N/A
N/A
50
QO150ED10
QO250ED10
QO350ED10
50
QO150ED6
N/A
N/A
63
QO163ED10
QO263ED10
QO363ED10
63
QO163ED6
N/A
N/A
© 2000-2004 Schneider Electric All Rights Reserved
15
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
Dimensions
QOE Circuit Breaker Dimensions
3.20
81
07393034
Figure 24:
2.24
(57)
0.5
(14)
82°
0.11
(2.8)
2.03
(51)
3.2
(81)
2.21
(56)
1.47
(37)
0.73
(18)
2.91
(74)
2.31
(59)
Dual Dimensions:
16
in.
(mm)
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
QOE-RCBO CIRCUIT BREAKERS WITH
RESIDUAL CURRENT PROTECTION
QOE-RCBO Circuit Breaker
07393013
Figure 25:
International Miniature Circuit Breakers
QOE-RCBO branch circuit breakers with residual current protection and
integral overcurrent protection are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
•
Compliance with International Standards: Certified to IEC 60898 and
BS4293, 10 kA at 240 Vac, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the OFF position. Indication of
a tripped circuit breaker on residual current ground fault is by location of
the handle in an intermediate position.
•
Push-to-test Function: A yellow push-to-test button is positioned on
the front of the device for testing the residual current electronic trip
circuit and mechanical tripping interface.
•
Thermal Trip Element: Thermal trip elements are factory calibrated at
30°C ambient temperature.
•
Instantaneous trip level types B and C:
— Type B—(3–5 In) Overcurrent protection for sensitive equipment
— Type C—(5–10 In) Overcurrent protection for all application types
© 2000-2004 Schneider Electric All Rights Reserved
•
Residual Current Protection: Residual ground-fault trip currents are
factory set at 10 mA, 30 mA or 100 mA: Type A.
•
Trip Mechanism: Device will trip on loss of neutral. Device is sensitive
to both ac and pulsating dc fault current. Device will trip on voltage
between neutral and earth greater than 50 Vac.
•
Mounting: Plug-on connection.
17
International Miniature Circuit Breakers
Table 17:
0739DB9901R11/03
June 2004
QOE-RCBO Circuit Breakers with Instantaneous Trip and Residual Trip Current
Type B
Type D
Type C
Ampere
Rating
Circuit Breaker
Catalog
Number
Ampere
Rating
Circuit Breaker
Catalog
Number
Ampere
Rating
Circuit Breaker
Catalog
Number
10 mA
1-Pole
10 mA
1-Pole
10mA
1-Pole
6
QOE106B01
6
QOE106C01
10
QOE110B01
10
QOE110C01
16
QOE116B01
16
QOE116C01
20
QOE120B01
20
QOE120C01
32
QOE132B01
32
QOE132C01
40
QOE140B01
40
QOE140C01
30 mA
30 mA
30 mA
6
QOE106B03
6
QOE106C03
6
QOE106D03
10
QOE110B03
10
QOE110C03
10
QOE110D03
16
QOE116B03
16
QOE116C03
16
QOE116D03
20
QOE120B03
20
QOE120C03
20
QOE120D03
32
QOE132B03
32
QOE132C03
32
QOE132D03
40
QOE140B03
40
QOE140C03
100 mA
100 mA
100 mA
6
QOE106C100
6
QOE106D10
10
QOE110C100
10
QOE110D10
16
QOE116C100
16
QOE116D10
20
QOE120C100
20
QOE120D10
32
QOE132C100
32
QOE132D10
Accessory
QOE1PL Handle Padlock
Attachment
07393023
Figure 26:
Handle Padlock Attachment (QOE1PL)
The handle padlock attachment allows padlocking the circuit breaker
handles in the ON or OFF position. The padlock attachment is intended to
be a temporary device and must be removed to resume normal operation.
(Padlock is not included.)
Lugs
07393021
Figure 27:
QOE-RCBO Circuit Breaker Lug
Table 17: QOE-RCBO Circuit Breaker Lug
Continuous
Ampere
Rating
Wire
Type
Lug Wire Size
mm2
AWG
6–40
Cu
(1) 1–10
(1) #18–#8
Temperature
Rating
Torque Value
N•m
lb-in
75°C
1.0
9
6–40 A Lug
18
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Dimensions
Figure 28:
QOE-RCBO Circuit Breaker Dimensions
0.17
(4.5)
07393035
0.68
(17)
0.19
(5)
0.73
(18)
0.34
(8.8)
0.27
(7)
60°
0.37
(9.5)
60°
0.35
(9)
4.36
(110)
2.53
(64)
0.15
(4)
0.59
(5)
0.29
(7.3)
Dual Dimensions:
in.
(mm)
Connections
Figure 29:
QOE-RCBO Circuit Breaker Connections
07393041
A—Load Power
Line Power
N
QOE-RCBO 1-pole Circuit Breaker
B—Load Neutral
C—Panel Neutral Wire Blue
L
D—Panel Earth Wire Yellow/Green
A
B
Load 1
C
Load 2
D
© 2000-2004 Schneider Electric All Rights Reserved
19
International Miniature Circuit Breakers
QOH-X CIRCUIT BREAKERS
QOH-X 1-Pole Circuit Breaker
QOH-X branch circuit breakers are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
•
Compliance with International Standards: Certified to IEC 60947-2, 5
kA (10–63 A) and 6 kA (70–100 A) at 240 Vac single-phase and 415 Vac
three-phase, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent, red trip indicator on the front of the circuit breaker).
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature.
07393006
Figure 30:
0739DB9901R11/03
June 2004
Figure 31:
QOH-X 4-Pole Circuit Breaker
•
07393007
•
Endurance (Switching Operations):
— 1,500 full-load operations
— 8,500 no-load operations
•
QOH-X and QOBH-X Circuit Breakers
Table 18:
Mounting: Plug-on and bolt-on connection available.
Thermal-magnetic, 240/415 Vac, 10–63 A Certified to IEC 947-2 at 5 kA,
70–100 A Certified to IEC 947-2 at 6 kA
QOH-X and QOBH-X Circuit Breakers
QOH-X Plug-on Circuit Breakers
QOBH-X Bolt-on Circuit Breakers
Circuit Breaker Catalog Number
Continuous
Ampere Rating 1-Pole
2-Pole
3-Pole
Circuit Breaker Catalog Number
Continuous
Ampere Rating 1-Pole
2-Pole
3-Pole
10
QOH110X
QOH210X
QOH310X
10
QOBH110X
QOBH210X
QOBH310X
16
QOH116X
QOH216X
QOH316X
16
QOBH116X
QOBH216X
QOBH316X
20
QOH120X
QOH220X
QOH320X
20
QOBH120X
QOBH220X
QOBH320X
32
QOH132X
QOH232X
QOH332X
32
QOBH132X
QOBH232X
QOBH332X
45
QOH145X
QOH245X
QOH345X
45
QOBH145X
QOBH245X
QOBH345X
63
QOH163X
QOH263X
QOH363X
63
QOBH163X
QOBH263X
QOBH363X
70
QOH170X
QOH270X
QOH370X
70
QOBH170X
QOBH270X
QOBH370X
80
QOH180X
QOH280X
QOH380X
80
QOBH180X
QOBH280X
QOBH380X
100
QOH1100X
QOH2100X
QOH3100X
100
QOBH1100X
QOBH2100X
QOBH3100X
100 (4-pole)
N/A
N/A
QOH4100X
100 (4-pole)
N/A
N/A
QOBH4100X
20
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Accessories
•
Handle Tie (QO1HT)
The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip, multi-pole circuit breaker.
•
Handle Clamps (QO1LO and HLO-1)
The handle clamp accessories fasten the circuit breaker handle in the
ON or OFF position. These handle clamps cannot be padlocked.
QOH-X Circuit Breaker
07393027
07393025
Figure 32:
— 1-pole circuit breaker handle clamp: QO1LO
QO1HT Handle Tie
QO1PA Fixed
Padlock Attachment
— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1
•
07393043
07393028
QO1LO Handle Clamp
QO1HPL Removable
Padlock Attachment
Handle Padlock Attachments
(QOHPL, QO1PA, QO1PL and QO1HPL)
The handle padlock attachments allow padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
fixed and removable. The fixed style is intended to be a permanent
device. The padlock can be removed to resume normal operation. The
removable style is intended to be a temporary device and must be
removed to resume normal operation. Padlock is not included.
07393026
— 1-pole circuit breaker removable attachment: QOHPL
— 1-pole circuit breaker fixed attachment: QO1PA
— 2- and 3-pole removable attachment: QO1HPL
— 2- and 3-pole fixed attachment: QO1PL
07393044
07393042
HLO-1 Handle Clamp
QO1PL Fixed
Padlock Attachment
QOHPL Removable
Padlock Attachment
Lugs
QOH-X Circuit Breaker Lugs
(1)
(2)
10–32 A Lugs
Table 19:
Continuous
Ampere
Rating
07393016
07393022
Figure 33:
45–100 A Lug
© 2000-2004 Schneider Electric All Rights Reserved
Table 19: QOH-X Circuit Breaker Lugs
Wire
Type
Lug Wire Size
mm2
AWG
Temperature
Rating
Torque Value
N•m
lb-in
10–32
Al/Cu
(1) 2.5–6
(1) #14–#8
60–75°C
4
36
10–32
Cu (only)
(2) 2.5–6
(2) #14–#10
60–75°C
4
36
45–100
Al/Cu
(1) 25–50
(1) #4–#2/0
75°C
6
50
21
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
Dimensions
QOH-X Circuit Breaker Dimensions
07393036
Figure 34:
NOTE: QOBH-X circuit breaker dimensions are the same as the QOH-X
circuit breaker dimensions except as shown
Dim. A: 3.5 in. (88.9 mm), 45–100 A for 1-, 2- and 3-pole
Dim. B: 3.00 in. (76.2 mm), 10–32 A for 1-, 2- and 3-pole
Dim. A
2.25
(57)
Dim. B
0.73 0.18
(19) (4)
0.59
(15)
0.38
(10)
2.23
(57)
2.09
(53)
0.53
(13)
22°
0.16
(4)
ON
1.48
(38)
1.34
(34)
0.53
(13)
3°
26°
Tripped
OF
F
Re
set
0.94
24
21°
0.25
(6)
2.91
(74)
2.31
(59)
0.94
24
0.94
24
2.75
(70)
Dual Dimensions:
22
2.92
(74)
in.
(mm)
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
QOBH-X Circuit Breaker Dimensions
07393036
Figure 35:
International Miniature Circuit Breakers
0.38
(10)
0.75
(19)
0.75
(19)
0.75
(19)
2.94
(75)
Dual Dimensions:
© 2000-2004 Schneider Electric All Rights Reserved
in.
(mm)
23
International Miniature Circuit Breakers
QOH-RCDX CIRCUIT BREAKERS WITH
RESIDUAL CURRENT PROTECTION
QOH-RCDX Circuit Breaker
07393001
Figure 36:
0739DB9901R11/03
June 2004
QOH-RCDX branch circuit breakers with residual current protection and
integral overcurrent protection are designed for use in consumer unit and
three-phase distribution panelboard applications.
•
Compliance with International Standards: Certified to IEC 60947-2
and BS4293, 5 kA at 240 Vac, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload, short
circuit or residual current ground fault is by location of the handle in the
center position. The circuit breaker is also equipped with the Square D
exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the
front of the circuit breaker).
•
Push-to-test Function: A yellow push-to-test button is positioned on the
front of the device for testing the residual current electronic trip circuit
and mechanical tripping interface.
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient temperature.
•
Residual Current Protection: Residual ground-fault trip currents are
factory set at 10 or 30 mA.
•
Endurance (Switching Operation):
— 1,500 full-load operations
— 8,500 no-load operations
Table 20:
QOH-RCDX and QOBH-RCDX Circuit Breakers with Instantaneous Trip and Residual Trip Current
QOH-RCDX Circuit Breaker
Continuous
Ampere
Rating
QOBH-RCDX Circuit Breaker
Circuit Breaker
Catalog Number
(1-Pole)
Residual Trip Current
10 mA
Continuous
Ampere
Rating
Circuit Breaker
Catalog Number
(1-Pole)
Residual Trip Current
10 mA
10
QOH110RCDX10
10
QOBH110RCDX10
16
QOH116RCDX10
16
QOBH116RCDX10
20
QOH120RCDX10
20
QOBH120RCDX10
32
QOH132RCDX10
32
QOBH132RCDX10
Residual Trip Current
30 mA
Residual Trip Current
30 mA
10
QOH110RCDX30
10
QOBH110RCDX30
16
QOH116RCDX30
16
QOBH116RCDX30
20
QOH120RCDX30
20
QOBH120RCDX30
32
QOH132RCDX30
32
QOBH132RCDX30
24
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Accessories
07393025
QOH-RCDX Circuit Breaker
Figure 37: Accessories
07393026
07393027
QO1HT Handle Tie
QO1LO Handle Clamp
QO1PA Fixed
Padlock Attachment
07393022
•
•
Handle Clamps (HLO-1 and QO1LO)
•
Handle Padlock Attachments (QO1PA and QOHPL)
The handle padlock attachment allows padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
fixed and removable. The fixed style is intended to be a permanent
device. The padlock can be removed to resume normal operation. The
removable style is intended to be a temporary device and must be
removed to resume normal operation. Padlock is not included.
Handle Tie (QO1HT)
The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip, multi-pole circuit breaker.
The handle clamp accessories fasten the handle in the ON or OFF
position. These handle clamps cannot be padlocked.
— Removable padlock attachment: QOHPL
QOHPL Removable
Padlock Attachment
Lugs
Figure 38:
Mounting: Plug-on and bolt-on connections available.
— Fixed padlock attachment: QO1PA
07393044
07393028
HLO-1 Handle Clamp
•
•
•
Table 21: QOH-RCDX Circuit Breaker Lugs
QOH-RCDX Circuit Breaker Lugs
(1)
Continuous
Ampere
Rating
mm2
AWG
Torque
Temperature Value
Rating
N•m lb-in
Lug Wire Size
Wire Type
10–32
Al/Cu
(1) 2.5–6
(1) #14–#8
60–75°C
4
36
10–32
Cu (only)
(2) 2.5–6
(2) #14–#10
60–75°C
4
36
(2)
10–32 A Lugs
© 2000-2004 Schneider Electric All Rights Reserved
25
International Miniature Circuit Breakers
0739DB9901R11/03
June 2004
Dimensions
QOH-RCDX Circuit Breaker Dimensions
07393037
Figure 39:
3°
26°
22°
OF
F
Re
set
ON
Tripped
21°
2.91
(74)
2.31
(59)
4.12
(108)
0.74
(19)
Dual Dimensions:
in.
(mm)
Connections
07393039
Figure 40:
QOH-RCDX Circuit Breaker Connections
240 Vac Source
L
N
Load Power
250 V Duplex
Receptacle
240
Vac
240 V
Load Neutral
S/N
GND
26
Equipment Ground
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
QOXD CIRCUIT BREAKERS
QOXD Circuit Breaker
•
Compliance with International Standards: Certified to IEC
947-2 (3 kA [10–63 A]) and IEC 898 (3 kA [10–32 A]) at 240 Vac single
phase and 415 Vac three phase, 50/60 Hz, CE marked.
•
ON/OFF Indication: ON/OFF markings are on the face of the circuit
breaker along with the international I/O markings.
•
Handle Operation: Trip-free handle through an over-center toggle
mechanism that ensures tripping even when the handle is held or locked
in the ON position.
•
Trip Indication: Indication of a tripped circuit breaker on overload or
short circuit is by location of the handle in the center position. The circuit
breaker is also equipped with the Square D exclusive Visi-Trip® indicator
(a luminescent, red trip indicator on the front of the circuit breaker).
•
Thermal Trip Element: Thermal trip elements are factory calibrated at
40°C ambient (IEC 947-2) and 30°C ambient (IEC 898) temperature.
•
Endurance (Switching Operations):
07393010
Figure 41:
QOXD branch circuit breakers are designed for use in single-phase
consumer unit and three-phase distribution panelboard applications.
— IEC 947-2: 1,500 full-load operations
— IEC 947-2: 8,500 no-load operations
— IEC 898: 4,000 full-load operations
Table 21:
Thermal-Magnetic Circuit Breakers
QOXD Plug-on Circuit Breakers
QOBXD Bolt-on Circuit Breakers
Continuous
Ampere
Rating
Circuit Breaker Catalog Number
Circuit Breaker Catalog Number
1-Pole
2-Pole
3-Pole
Continuous
Ampere
Rating
1-Pole
2-Pole
3-Pole
10
QOXD110
QOXD210
QOXD310
10
QOBXD110
QOBXD210
QOBXD310
16
QOXD116
QOXD216
QOXD316
16
QOBXD116
QOBXD216
QOBXD316
20
QOXD120
QOXD220
QOXD320
20
QOBXD120
QOBXD220
QOBXD320
25
QOXD125
QOXD225
QOXD325
25
QOBXD125
QOBXD225
QOBXD325
32
QOXD132
QOXD232
QOXD332
32
QOBXD132
QOBXD232
QOBXD332
40
QOXD140
QOXD240
QOXD340
40
QOBXD140
QOBXD240
QOBXD340
45
QOXD145
QOXD245
QOXD345
45
QOBXD145
QOBXD245
QOBXD345
50
QOXD150
QOXD250
QOXD350
50
QOBXD150
QOBXD250
QOBXD350
63
QOXD163
QOXD263
QOXD363
63
QOBXD163
QOBXD263
QOBXD363
70
—
QOXD270
QOXD370
70
—
QOBXD270
QOBXD370
80
—
QOXD280
QOXD380
80
—
QOBXD280
QOBXD380
100
—
QOXD2100
QOXD3100
100
—
QOBXD2100
QOBXD3100
© 2000-2004 Schneider Electric All Rights Reserved
27
International Miniature Circuit Breakers
Accessories
0739DB9901R11/03
June 2004
Mounting: Plug-on and bolt-on connection available.
07393025
QOXD Circuit Breaker
Figure 42: Accessories
•
Handle Tie (QO1HT)
The handle tie accessory converts any adjacent 1-pole QO circuit
breaker to one independent-trip multi-pole circuit breaker.
•
Handle Clamps (HLO-1 and QO1LO)
The handle clamp accessories fasten the circuit breaker handle in the
ON or OFF position. These handle clamps cannot be padlocked.
— 1-pole circuit breaker handle clamp: QO1LO
QO1HT Handle Tie
07393027
07393026
— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1
HLO-1 Handle Clamp
•
07393044
07393028
QO1LO Handle Clamp
Handle Padlock Attachments
(QOHPL, QO1PA, QO1HPL and QO1PL)
The handle padlock attachments allow padlocking the circuit breaker
handles in the ON or OFF position. They are available in two styles:
fixed and removable. The fixed style is intended to be a permanent
device. The padlock can be removed to resume normal operation. The
removable style is intended to be a temporary device and must be
removed to resume normal operation. (Padlock is not included.)
— 1-pole circuit breaker removable attachment: QOHPL
QOHPL Removable
Padlock Attachment
QO1PA Fixed
Padlock Attachment
— 2- and 3-pole removable attachment: QO1HPL
— 2- and 3-pole fixed attachment: QO1PL
07393042
07393043
QO1HPL Removable
Padlock Attachment
— 1-pole circuit breaker fixed attachment: QO1PA
QO1PL Fixed
Padlock Attachment
Lugs
(1)
QOXD Circuit Breaker Lug
07393016
07393022
Figure 43:
(2)
10–32 A Lugs
28
45–100 A Lug
Table 23: QOXD Circuit Breaker Lugs
Continuous
Ampere
Rating
Wire
Type
Lug Wire Size
mm2
Temperature
Rating
Torque Value
AWG
N•m
lb-in
10–32
Al/Cu
(1) 2.5–6
(1) #14–#8
60–75°C
4
36
10–32
Cu (only)
45–100
Al/Cu
(2) 2.5–6
(2) #14–#10
60–75°C
4
36
(1) 25–50
(1) #4–#2/0
75°C
6
50
© 2000-2004 Schneider Electric All Rights Reserved
0739DB9901R11/03
June 2004
International Miniature Circuit Breakers
Dimensions
Figure 44:
NOTE: QOBX-D circuit breaker dimensions are the same as the QOXD
circuit breaker dimensions except as shown.
QOXD Circuit Breaker Dimensions
07393036
Dim. A: 3.5 in. (89 mm), 70–100 A for 1-, 2- and 3-pole
Dim. B: 3.125 in. (79 mm), 45–63 A for 1-, 2- and 3-pole
Dim. C: 3.0 in. (76 mm), 10–32 A for 1-, 2- and 3-pole
2.25
(57)
3.00
(76)
0.94
(24)
0.53
(13)
0.59
(15)
0.38
(10)
0.16
(24)
22°
Tripped
0.73
(19)
1.48
(38)
1.34
(34)
0.53
(13)
ON
2.23
(57)
2.09
(53)
3°
26°
F
Re
set
Dim. C
OF
Dim. A
Dim. B
21
°
0.25
(6)
2.91
(74)
2.31
(59)
0.75
(19)
0.75
(19)
0.75
(19)
2.75
(70)
Dual Dimensions:
© 2000-2004 Schneider Electric All Rights Reserved
2.92
(74)
in.
(mm)
29
International Miniature Circuit Breakers
QOBX-D Circuit Breaker Dimensions
07393036
Figure 45:
0739DB9901R11/03
June 2004
0.38
(10)
0.75
(19)
0.75
(19)
0.75
(19)
2.94
(75)
Dual Dimensions:
30
in.
(mm)
© 2000-2004 Schneider Electric All Rights Reserved