Série Legend Plus LGPB, LGPM, LGPBF

advertisement
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Bulletin No. LGPB/M-C
Drawing No. LP0328
Released 12/04
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
LEGEND PLUS SERIES MODEL LGPB - Four Preset Batch/Counter/Rate Indicator
MODEL LGPM - Six Preset Counter/Rate Indicator
MODEL LGPBF - Four Preset Foot-Inch Length Counter
DESCRIPTION
The Legend Plus Series consists of two models that are multi-input count and
rate indicators. The LGPB features process, batch, and total counting, as well
as a time interval rate indicator. The four available presets can be assigned to
the process counter or the rate indicator. Outputs three and four can also be
assigned to the batch or total indicator. The Legend Plus foot-inch counter
provides Process and Total count read-outs in feet and inches. A decimal point
is used to separate the foot and inch units. All Process and Total presets are also
displayed in feet and inches. The LGPM features six presets, which can be
assigned to either the rate or count display.
The Legend Plus has advanced features which allow the units to be more
closely coupled to the application. The units feature a 2 line by 8 character
alpha-numeric display, allowing the value mnemonics and programming menus
to be easily read. The units are available in single or dual color display models.
The four scroll-through indication displays can be programmed to show various
parameters and automatically scroll, if desired. On dual color models, each
indication display can be programmed for either color. The mnemonics
corresponding to the main display values (RATE, PROCESS, BATCH,
TOTAL) can be individually programmed and modified as desired. For
example, the RATE mnemonic can be reprogrammed to display the word
SPEED, so that when the rate mnemonic is to be displayed, the mnemonic
SPEED is displayed instead.
Two custom display lines are available which enable the user to specify the
number of digits of a value to be displayed on the line, along with any alphanumeric prefix or suffix. This capability allows displays such as: ‘1000 RPM’,
‘99999 Ft’, ‘PRC 9999’, etc.
The Legend Plus also features messaging capabilities that can inform the
user of output actions or other events that occur in a system. Up to ten messages
can be programmed. Messages can be requested by an output status change,
user input(s), or through serial communications. The messages can be
programmed to blink, scroll, time out, and to alternately flash between message
and indication display.
On dual color models, the message can be programmed to be displayed in
either color. This capability is very useful in drawing the operator’s attention to
particular messages.
!
2X8 TRANSMISSIVE LCD, NEGATIVE IMAGE, WITH L.E.D.
BACKLIGHTING
!
PROGRAMMABLE DISPLAY INTENSITY
!
OPTIONAL DUAL COLOR DISPLAY (Red and Green)
!
FOUR USER PROGRAMMABLE INDICATION DISPLAYS WITH
CUSTOMIZABLE MNEMONICS AND DISPLAY LINES
!
PROGRAMMABLE MESSAGE CAPABILITIES
!
ENGLISH PROGRAMMING MENUS
!
RS485 OR RS232 SERIAL COMMUNICATIONS
!
OPTIONAL PROGRAMMING SOFTWARE FOR PROGRAMMING
MULTIPLE UNITS
!
ABILITY TO LOCKOUT OPERATOR ACCESS TO PROGRAMMING
PARAMETERS
!
PROGRAMMABLE CONTROL INPUTS
!
COUNT INPUTS ARE SWITCH SELECTABLE FOR VARIOUS
SENSOR OUTPUTS
!
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
!
QUADRATURE SENSING (Up to 4 times resolution)
!
COUNT INHIBIT TERMINAL AVAILABLE FOR ALL COUNT MODES
!
ACCEPTS COUNT RATES UP TO 15 KHz
!
ALL OUTPUT(S) ASSIGNABLE TO COUNT OR RATE
!
ON & OFF DELAY FOR RATE OUTPUTS
!
SOLID STATE CURRENT SINKING OUTPUT(S)
!
RELAY OUTPUTS (LGPB only; Field Replaceable)
!
SEPARATE INPUT SCALING FOR RATE, COUNT, & TOTAL
!
115/230 VAC SWITCH SELECTABLE
!
NEMA 4X/IP65 SEALED FRONT PANEL BEZEL
UL Recognized Component,
File # E137808
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 3.0" (76.2)H x 4.0" (101.6)W.
1
PANEL CUT-OUT
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
DESCRIPTION (Cont’d)
SPECIFICATIONS
The program disable DIP switch, the code value, and an external user input
selected for Program Disable can be utilized to provide multi-level protection
against unwanted changes to data values and unit configuration.
The Legend Plus features enhanced serial communications. The serial port
can be configured for connection to RS485 or RS232 devices. It can be used for
data retrieval and for programming various data values.
Optional Legend Plus Programming Software for IBM compatible PCs is
available to program all the Legend configuration parameters, such as
messages, count modes, etc. The software allows unit configurations to be
created, uploaded, downloaded and saved to a file for rapid programming of the
Legend unit.
The six programmable User Inputs can be configured to provide a variety of
functions. Four user inputs are located on the upper rear terminal block and the
other two inputs are front panel function keys. The User Inputs can be
configured to provide functions such as:
1. DISPLAY: 2x8, 0.3" (7 mm) high characters, negative image transmissive
LCD, with Single (green or red) or Dual Color (green and red) LED
backlighting.
2. POWER:
AC Operation: 115/230 VAC ±10%, 50/60 Hz, 10 VA, switch selectable.
DC Operation: +12 VDC ±20% @ 250 mA max.
3. MEMORY: Non-volatile memory retains all programming information.
Count and Preset values are written to non-volatile memory when power is
interrupted. All other programming parameters are written to memory when
programming mode is exited. If power is removed while in the programming
menu’s the parameters are stored to previously saved settings.
Data Retention: 10 yr. min.
Message/Mnemonics Memory:
792 (LGPB) / 804 (LGPM) bytes available (with factory settings loaded).
4. SENSOR POWER: +12 VDC ±25% @ 100 mA.
5. INPUTS A and B: DIP Switch selectable to accept count pulses from a
variety of sources including switch contacts, outputs from CMOS or TTL
circuits, magnetic pickups and all standard RLC sensors.
LOGIC: Input trigger levels VIL = 1.5 VMAX; VIH = 3.75 VMIN.
Current sinking: Internal 7.8 KΩ pull up to +12 VDC, IMAX = 1.9 mA.
Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mAMAX @ 28 VDC.
Debounce: Damping capacitor provided for switch contact bounce.
Limits count speed to 50 Hz and input pulse widths to 10 msec min.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak.
Hysteresis: 100 mV.
Input impedance: 3.9 KΩ @ 60 Hz.
Maximum input voltage: ±50 Vp
Note: For magnetic pickup input, the sink/source DIP switch must be in the
SRC position.
6. RATE ACCURACY: ±0.01%
7. RATE MINIMUM INPUT FREQUENCY: 0.01Hz.
8. MAXIMUM COUNT RATE IN KHz:
Count Inhibit
Message Request
Output Activation
Program Disable
Print Request
Reset
Message Cancellation
Output Deactivation
View/Freeze Display
Skip Presets(outputs)
The units offer a choice of seven programmable counting modes for use in
applications requiring Bi-directional, Anti-coincidence, and Quadrature
counting. The count inhibit function can be utilized with all of these input
response modes by programming User Input 4 for the Inhibit Count function.
The input circuitry is switch selectable to accept signals from a variety of
sources. In the Anti-coincidence mode both inputs are monitored
simultaneously, so that no counts are missed, and the final count can be chosen
as the sum or difference of the two inputs.
Rate, Process and Total displays have separate scaling and decimal point
placement, for readouts in different units. The Counter Load feature enables the
operator to modify the count value. This is useful when flawed material has
been counted and it is necessary to adjust the count value accordingly.
The rate operates in the time interval method (1/tau) to calculate the rate
value. This method insures high resolution at all input rates. Averaging can be
accomplished by programming the Minimum and Maximum Update Time for
the desired response. Extensive scaling capabilities allow practically any
reading at very slow input rates.
The construction of the Legend Plus unit is a lightweight, high impact plastic
case with a clear viewing window. The sealed front panel with silicone rubber
keypad meets NEMA 4X/IP65 specifications for wash-down and/or dusty
environments, when properly installed. Plug-in style terminal blocks simplify
installation and wiring change-outs.
CNT + DIR
LGPB (Batch)
LGPM (Six Preset)
LGPBF (Foot-Inch)
X1
15
13
15
X2
7
6
7
QUAD
X1
7
6
7
X2
5.5
5
5.5
X4
3
2.5
3
ADD/ADD
ADD/SUB
X1*
14
12
15
X1*
7
6
7
Notes:
1. Maximum count rates given are for Process counter set for Auto reset with
the auto cycle preset set to an equivalent of 100 count pulses or greater.
With auto cycle presets less than 100 counts the maximum count rates may
be lower. The actual Preset value for 100 count pulses, with Count
SF=0.5000 and Count Scale Multiplier=X1, would be 50.
2. Maximum count rate given for X2 & X4 count modes are given for 50%
duty cycle signals and Quad signals with 90° phase shift.
*Inputs A & B count rates summed.
9. MAXIMUM COUNT CAPACITY:
Process or Count: 9 digits internal (non-scaled), 6 digits displayable (scaled)
Batch Count: 6 digits
Total Count: 11 digits internal (non-scaled), 8 digits displayable (scaled)
10. CONTROL INPUTS:
Programmable user inputs (4):
USR INP 1 to 3: Internal 10 KΩ pull-up to +5 VDC, VIL = 1.5 VMAX; VIH
= 3.5 VMIN, response time = 30 msec typical, 100 msec max. (count rate
dependent).
USR INP 4/INH: Internal 10 KΩ pull-up to +5 VDC, VIL = 1.5 VMAX,
VIH = 3.0 VMIN, response time = 30 msec typical, 100 msec max. (count
rate dependent).
INHIBIT Response time = 50 µsec max.
User Inputs Programmed for Binary Message Request: Debounce =
100 msec. (Binary message request inputs must be stable for 100 msec
before a message is requested).
11. SERIAL COMMUNICATIONS:
Type: Jumper selectable RS485 or RS232.
Can connect up to 32 units when using RS485 interface.
Baud Rate: Programmable from 1200 to 9600.
Maximum Addresses: Programmable from 00 to 99. (Actual number on a
line is limited by hardware specifications)
Transmit Delay: Programmable for 0.002 or 0.100 second.
Data Format: 10 Bit Frame; 1 start bit, 7 or 8 data bits, 1 or no parity bit,
and 1 stop bit. Parity is programmable for ODD (7 data bits), EVEN (7
data bits), or NO Parity (8 data bits).
12. OUTPUT(S):
Solid-State: Current sinking NPN open collector transistor.
VCE = 1.1 VSAT @ 100 mA max. VOH = 30 VDC max.
(Internal Zener Diode Protection).
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.
MODEL - LGPB
The process counter is used to monitor the count within the batch. Presets 1
through 4 can be assigned to the process counter or the rate indicator. Presets 3
and 4 can also be assigned to either the batch counter or totalizer.
Presets 1 and 2 can activate relay outputs 1 and 2 respectively. Presets 3 and
4 can activate the NPN open collector outputs O3-SNK and O4-SNK
respectively.
MODEL - LGPM
The Multi Preset unit has 6 presets which can control NPN open collector
outputs 01-SNK to 06-SNK respectively. Presets 1 through 6 can be assigned to
either the rate or count display.
STANDARD INDICATION DISPLAYS
& PRESETS FOR EACH MODEL
LGPB & LGPBF
RATE
PEAK
VALLEY
PROCESS
BATCH
TOTAL
(4 Presets)
MODEL
LGPM
RATE
PEAK
VALLEY
COUNT
(6 Presets)
2
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
12. OUTPUT(S): (Cont’d)
Relay(s): Mounted on field-replaceable P.C. board. Form C contacts rated at
5 amps @ 120 VAC/240 VAC or 28 VDC (resistive load), 1/8 H.P. @ 120
VAC (inductive load). The operate time is 5 msec nominal and the release
time is 3 msec nominal.
Programmable Timed Output(s): Programmable time ranges from 0.01 to
99.99 seconds, ±0.05% - 11 msec max.
Output Time Required To Request Message: 50 msec.
13. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 70°C
Operating and Storage Humidity: 85% max. (non-condensing) from 0°C
to 50°C.
Altitude: Up to 2000 meters
14. CERTIFICATIONS AND COMPLIANCES:
UL Recognized Component, File # E137808, UL508, CSA22.2 No. 14
Recognized to U. S and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
Type 4X Indoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #UL1581-176645/USA,
CB Scheme Test Report #97ME50052-081391
Issued by Underwriters Laboratories, Inc.
IEC 1010- 1, EN 61010- 1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 Kv contact
Level 3; 8 Kv air
Electromagnetic RF fields
EN 61000-4-3 Level 3; 10 V/m
80 MHz - 1 GHz
Fast transients (burst)
EN 61000-4-4 Level 4; 2 Kv I/O1
Level 3; 2 Kv power
RF conducted interference
EN 61000-4-6 Level 3; 10 V/rms 1
150 KHz - 80 MHz
Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m
Emissions to EN 50081-2
RF interference
EN 55011
Enclosure class A
Power mains class A
Note:
1. When the unit is DC powered from terminal TBA pin 5 (common) and
terminal TBA pin 3 (DC OUT/ IN) a power line filter was installed, RLC
#LFIL0000 or equivalent, so as not to impair the function of the unit.
Refer to the EMC Installation Guidelines section of the manual for
additional information.
15. CONSTRUCTION: High impact plastic case with clear viewing window.
The front panel meets NEMA 4X/IP65 requirements for indoor use when
properly installed. Installation Category II, Pollution Degree 2. (Panel
gasket, mounting clips, nut fasteners and screws included with unit.)
16. WEIGHT: 1.5 lbs. (0.68 Kg)
PROGRAMMABLE FUNCTIONS
PRESET(S)
Ranges from -99999 to 999999
Counter Load ranges from -99999 to 999999
SCALE FACTORS (RATE, COUNT & TOTAL)
Ranges from 0.0001 to 5.9999. The internal count value is multiplied by the
count scale factor and the count scale multiplier to provide the process count
display value. The total count is scaled by the count scale factor and the count
scale multiplier, and is additionally scaled by the total scale factor. The number
of negative edges is multiplied by the rate scale factor, the rate scale multiplier,
and the rate conversion factor to calculate the rate value.
COUNT SCALE MULTIPLIER
Multiplies the contents of the 9-digit internal counter or the 11-digit internal
totalizer by a factor of 1, 0.1, 0.01 or 0.001 to view the desired number of
significant digits on the 6-digit Counter display or the 8-digit Totalizer display.
DECIMAL POINT
Separate decimal point location for Count, Rate, and Total displays.
0
0.0
0.00
0.000
0.0000
0.00000
PROGRAMMING
The Legend Plus Series provides an easy to use, menu driven programming
interface. The English prompts, the front panel keypad, and the flashing display
aid the operator during programming. In the normal operating mode, the main
display loop allows the user to scroll through the four programmable indication
displays using the direction keys. From the main loop, presets and scale factors
can be accessed directly. All other parameters are accessed through the
programming loop, which can be set to require an access code number to enter
the loop. In the programming loop, parameters can be viewed or changed and
the operator can exit anywhere in the loop. The drawing above shows the main
display loop and part of the programming loop of a Legend Plus unit. Also
shown above right are four different views of the indication displays.
RATE SCALE MULTIPLIERS
Multiplies the contents of the actual internal rate, pulses per second (PPS),
by a factor of 0.01, 0.1, 1, 10, 100, or 1000 to view the desired number of
significant digits on the 6-digit Rate display. The desired time units for the rate
can be programmed as per Second (x1), per Minute (x60), or per Hour (x3600).
3
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
PROGRAMMABLE FUNCTIONS (Cont’d)
Program Disable:
Can be used alone, or in conjunction with the program disable DIP switch, to
provide a variety of program security modes. (External User Input only)
Inhibit Count:
Prevents pulses from being counted on Inputs A and B. (User Input 4 only).
The rate input is not affected by the inhibit setting and continues to display the
rate of the signal at Input A.
UPDATE TIME
The Rate Minimum and Maximum Update Times range from 0.1 to 99.9
seconds. This provides averaging capability for non-consistent pulse spacing.
Note: The maximum update time must be larger than the minimum update time.
COUNTING MODES
Count with Direction
Count with Direction (X2)
Quadrature
Quadrature (X2)
Quadrature (X4)
2-Input Anti-coincidence Add/Subtract
2-Input Anti-coincidence Add/Add
A separate Inhibit input is available for all count modes.
OUTPUT(S)
Output Assignment:
The LGPB can have outputs 1 through 4 assigned to the process or the rate.
Outputs 3 and 4 can also be assigned to the batch or total.
The LGPM can have outputs 1 through 6 assigned to either count or rate.
Phase:
Each output can have its active logic state set for positive phase (normally
off) or negative phase (normally on).
Output Activation Mode:
Latched
Boundary
Timed - 0.01 to 99.99 seconds
Hi/Lo Acting:
This mode is used in conjunction with all Rate modes and the Boundary
count modes. A Lo acting output would perform the Output action when the
count/rate is lower than the preset. A Hi acting output would perform the
Output action when the count/rate is higher than or equal to the preset.
Rate Output On/Off Delay:
Used to prevent output chatter. Output condition must be satisfied for a
period of time longer than delay period for output state to change.
On Delay: Prevents activation of output(s) for the amount of time
programmed.
Off Delay: Prevents deactivation of output(s) for the amount of time
programmed.
On & Off Delay: This mode prevents output state change for specified delay
period when turning on or off.
Output Reset Mode:
Outputs 1 & 2 Only:
End Output 1 @ Output 2 Start
End Output 1 @ Timed Output 2 End
End Output 2 @ Output 1 Start
End Output 2 @ Timed Output 1 End
Output(s) Power Up or Power Down State:
The Output’s state can be set to be Off (Inactive) @ power up.
OR
The Output’s state can be saved @ power down and restored at power-up.
OR
The Output’s state can be set to be ON (Active) @ power up.
Note: Power down state for Latched Mode Only.
Reset Output when Count is Reset:
This feature can be enabled or disabled.
Request Message:
Each output can be programmed to request a specific message when the
output conditions are satisfied.
RESET MODES
Manual Reset
Automatic Reset at Preset
Reset at Beginning Of Output 1
Reset at End Of Timed Output 1
Reset at Beginning Of Output 2
Reset at End Of Timed Output 2
Reset at Beginning Of Output 1 or Output 2
Reset at End Of Timed Output 1 or Output 2
MODEL LGPB ONLY
Reset at Beginning Of Output 3
Reset at End Of Timed Output 3
Reset at Beginning Of Output 4
Reset at End Of Timed Output 4
Reset at Beginning Of Output 3 or Output 4
Reset at End Of Timed Output 3 or Output 4
RESET ACTION
Reset to Zero: Count display value returns to zero when reset. Output activates,
if programmed, when the count equals the preset value.
Reset to Preset: Count display value returns to preset value when reset. Output
assigned to the specified preset activates, if programmed, when the count
equals zero.
Reset to Counter Load: Count display value returns to counter load value when
reset. Output activates, if programmed, when count equals the preset value.
USER INPUTS
There are four external user inputs and two front panel Function keys that are
programmable. When activated, each user input can be programmed to perform
one of the following functions:
Maintained Reset or Momentary Reset:
Can reset Rate, Peak, Valley, Process*, Batch*, Total*, or Count* display
values and/or any output associated with that display.
* On Models with these available display options.
Reset Output(s):
Places the output(s) in their inactive state. (Momentary action)
Set Output(s):
Places the output(s) in their active state. (Momentary action)
View Display 1-4:
Causes the selected indication display (1, 2, 3, or 4) to be displayed and held
from anywhere in the main display loop. The current display value is frozen
(not updated) while the display is held.
Change Display:
Causes the indication display to toggle to the next indication display.
Request Message:
Requests a specific programmed message to activate.
Clear Message:
Causes the displayed message to be canceled. (Maintained action)
Skip Preset:
Keeps the output from activating and automatic reset from occurring, if
programmed, when the count value equals the preset value.
Counter Load:
Places the counter load value into the count display and operates from that
value. (Maintained action)
Print Request:
Transmits the values specified in the Program Print Options module over the
serial port. (Maintained action)
INDICATION DISPLAYS
Each of the four indication displays is programmed individually. Each line of
each indication display can be programmed to show a value mnemonic, a
numeric value, the output status, a preset value, the counter load value, or a
custom display line. The mnemonics are factory set to; RATE, PEAK,
VALLEY, COUNT*, PROCESS*, BATCH*, TOTAL*, and OVERFLOW.
Each mnemonic can be individually changed to a mnemonic tailored to a
specific application. The first character of the full mnemonic is displayed to the
left of the appropriate numeric value if the other line is not programmed to
display the full mnemonic. Each of the 4 indication displays can be programmed
to be green or red on dual color models.
* On Models with these available display options.
Scroll Speed:
None
2.5 Seconds
5.0 Seconds
Display Intensity:
The brightness of the display can be adjusted from 1 to 5, with 5 as the
brightest. There is a separate adjustment for each color.
4
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
PROGRAMMABLE FUNCTIONS (Cont’d)
Message Cancellation:
The displayed message is canceled when:
A message of equal or higher priority is requested.
Message times out (Timed) and input/output is deactivated.
User input or output is deactivated (Til End).
User input programmed for clear message is activated.
Message Time:
Ranges from 1 to 599 Seconds.
Message Color: (Dual Color Option only)
Green or Red
INDICATION DISPLAYS (Cont’d)
Custom Display Line:
The Legend Plus has two Custom Display Lines which allow the user to
specify the number of digits to be displayed on the line, along with any alphanumeric prefix or suffix.
Program Mnemonic:
Allows the user to modify the mnemonics (RATE, PROCESS, BATCH, etc.)
to a mnemonic of your choice. For example, RATE can be changed to read
SPEED.
MESSAGES
There are ten messages that can be programmed in the Legend. The following
attributes can be set for each message.
Message Text:
Standard Characters - Lower/Upper case letters, numbers, punctuation
symbols
Extended Characters (Including most European characters)
Message Priority:
1 to 8 (1 = highest priority)
Message Type:
1 line block - message scrolls in block fashion on the top line of the display,
bottom line contains programmed indication display.
2 line block - message scrolls in block fashion on both lines of the display
1 line scroll - message scrolls right to left on the top line of the display,
bottom line contains programmed indication display
2 line scroll - Top line scrolls right to left, bottom line is blanked
Maintained/Momentary Request:
A Maintained Request setting enables messages to be restored or
redisplayed, when the display is available if the input/output action
requesting the message is still active.
A Momentary Message setting will allow only one request per message
requesting input/output action. Lower priority messages will be canceled by
higher priority messages.
Blinking Message:
Enables the message to blink when displayed. Only available with 1 or 2 line
block messages.
Multiplex:
Setting this parameter to yes will cause the unit to display the message for 2
seconds, then display the programmed display for 2 seconds. Only available
with 1 or 2 line block messages.
COMMUNICATION PORT
Jumper selectable for RS-485 or RS-232
Baud Rate - 1200 to 9600
Parity - Odd (7 data bits), Even (7 data bits), or No parity (8 data bits)
Unit Address - 00 to 99
Transmit Delay - 0.002 or 0.100 seconds
PRINT OPTIONS
The programmable print options specify which values are transmitted when
a print request is issued. The available options are; Rate, Peak, Valley, Count*,
Process*, Batch*, Total*, Scale Factors, Preset(s), Counter Load values, and
Message 0.
* On Models with these available display options.
The unit can be programmed to transmit or NOT to transmit mnemonics (unit
address & value identifiers). The mnemonic transmitted is the first three
characters of the programmed display mnemonic. For total, only the first
character is transmitted. A transmit and reset count capability allows the
selected count values to automatically reset after the value is printed
(transmitted).
OPERATOR ACCESS TO FRONT PANEL
There are several program disable modes that can be used to limit the
operator from programming the parameter values via the front panel keypad.
The Program Disable DIP switch can be used alone or in conjunction with a
User Input, programmed for the program disable function and a programmable
code value, to provide the desired level of security.
MODEL LGPB APPLICATION
A local canning plant wishes to improve the display and control capabilities
of its nine process lines. There is a requirement to add message interaction for
the operators during process operation. The following application facts and
requirements have been specified by the plant engineer.
1. The cans are sensed by a photo-electric device specially suited for can
manufacturing. The device produces one pulse per can.
2. The can count for the process of boxing the cans is the first requirement.
The can count is never changed, there are always 24 cans to each box. An
output is required at 20 cans to slow the line temporarily until the second
output is turned on. The second output changes the gate direction to begin
the next grouping of 24. The second output has a time delay output of 2
seconds. After the time delay, both outputs are reset and ready for the next
process cycle.
3. A count of the number of batches is required for each 8-hour shift. This
count is recorded and reset by the manufacturing computer.
4. A total count of cans produced per 24-hour period is required. This count is
also transmitted to the manufacturing computer, and reset as required via
the communication link.
5. A display of cans per minute is required with minimum and maximum
speed limits. Output 3 activates below 100 counts per minute and Output 4
activates above 500 counts per minute.
6. The four desired displays are process, batch, total, and rate. These are to be
scrolled via the front panel.
7. The customer also wants the following messages displayed when the listed
events occur:
Output 3 - Line #4 Slow
Output 4 - Overspd STOP! (Wants this display to stand out and have top
priority)
Proximity 1 - Check Label Glue
Proximity 2 - Check Top Supply
Proximity 3 - System Fault! Stop Line #4! (Wants this display to stand out
and have top priority)
8. Once the unit is set up, the only front panel access should be for a reset of
the process count and viewing of the displays.
The following page is a chart of the necessary programming for the Legend
Plus unit.
5
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
LEGEND PLUS PROGRAM SHEET
RATE
SCALING
COUNT SF
RATE SF
TOT SF
CNT. SCM
CNT. D.P.
RATE SCM
RATE PER
RATE D.P.
TOT D.P.
CHG. CNT
MIN. TIME
MAX. TIME
1.0000
1.0000
1.0000
X1.0
0
X1.0
MINUTE
0
0
YES
MESSAGE
1.0
5.0
COUNTER
CNT. INPUT
PRC. RST.
P AUTO. RS
BAT. RST.
B AUTO. RS
TOT. RST.
CT+DIRX1
TO ZERO
OUT2
TO ZERO
DISABLED
TO ZERO
USER INPUTS
BIN. MSG.REQ.NONE
USER INP. 1
REQMSG#5
USER INP. 3
REQMSG#4
USER F1
NO MODE
USER INP. 2
USER INP. 4
USER F2
REQMSG#6
CLRMSG
MNT.RST
PRC-YES
OUTPUT 3
ASSIGNED
PHASE
TYPE
ACT/TIME
OFF @ P.
RST/C
REQ MSG #
TO PRC
+
LATCHED
@OUT2END
OFF@P.UP
EN
TO RATE
+
BOUNDARY
LO ACT
OFF@P.UP
EN
2
OUTPUT 2
ASSIGNED
PHASE
TYPE
ACT/TIME
OUTPUT END
OFF @ P.
RST/C
REQ MSG #
OUTPUT 4
ASSIGNED
PHASE
TYPE
ACT/TIME
OFF @ P.
RST/C
REQ MSG #
TO PRC
+
TIMED
2.00
DISABLED
OFF@P.UP
EN
NO
NO
NO
NO
NO
NO
PRESETS
P1
P2
P3
P4
CL
PRIORITY
TYPE
BLINKING
MULTIPLEX
CANCEL
TIME SEC.
COLOR
8
2L BLOCK
NO
NO
TIL END
MSG. #2
TEXT
2
LINE #4
SLOW
7
2L BLOCK
YES
YES
TIL END
MSG. #3
TEXT
PRIORITY
TYPE
BLINKING
MULTIPLEX
CANCEL
TIME SEC.
COLOR
TO RATE
+
BOUNDARY
HI ACT
OFF@P.UP
EN
3
GREEN
GREEN
3
OVERSPD
STOP
5
2L BLOCK
YES
YES
TIL END
RED
MSG. #4
4
TEXT
SYSTEM
STOP LINE #4
FAULT
PRIORITY
5
TYPE
2L BLOCK
BLINKING
YES
MULTIPLEX
NO
CANCEL
TIMED
TIME SEC.
1
COLOR
RED
MSG. #5
TEXT
5
CHECK LABEL
GLUE
PRIORITY
6
TYPE
1L SCROL
BLINKING
MULTIPLEX
CANCEL
TIMED
TIME SEC.
1
COLOR
GREEN
MSG. #6
TEXT
6
CHECK TOP
SUPPLY
PRIORITY
6
TYPE
1L SCROL
BLINKING
MULTIPLEX
CANCEL
TIMED
TIME SEC.
1
COLOR
GREEN
DISPLAY
OPTIONS
ACCESS
P1
P2
P3
P4
CTLD.
SF’S
1
GATE CHANGE
PRIORITY
TYPE
BLINKING
MULTIPLEX
CANCEL
TIME SEC.
COLOR
OUTPUTS
OUTPUT 1
ASSIGNED
PHASE
TYPE
ACT/TIME
OUTPUT END
OFF @ P.
RST/C
REQ MSG #
MSG. #1
TEXT
20
24
100
500
0
DISPLY 1
D1 LINE 1
D1 LINE 2
D1 COLOR
CUSTOM 2
OUTPUTS
GREEN
DISPLY 2
D2 LINE 1
D2 LINE 2
D2 COLOR
BAT-MNE
BAT-VAL
GREEN
DISPLY 3
D3 LINE 1
D3 LINE 2
D3 COLOR
CUSTOM 1
CUSTOM 2
GREEN
DISPLY 4
D4 LINE 1
D4 LINE 2
D4 COLOR
TOT-MNE
TOT-VAL
GREEN
MNEMONIC
RATE
PEAK
VALLEY
PROC/CNT
BATCH
TOTAL
OVERFLOW
SPEED
P
V
CANS
CASES
TOT.CANS
OVERFLOW
SCRO. SPD
NONE
DSP. LEVEL G 10
R 10
CUST. DSP.
CUST.DSP.1
PRESET TRACKING
P1 TRACK
NONE
P2 TRACK
NONE
P3 TRACK
NONE
P4 TRACK
NONE
PRO. CODE
33
CUST. DPS.2
VAL-RATE
-CPM
VAL-PRC
-CANS
ORDERING INFORMATION
MODEL NO.
LGPB
LGPM
LGPBF
SFLGP
PART NUMBER
115/230 VAC
& +12VDC
DESCRIPTION
Four Preset Batch Legend Plus w/Grn Backlighting
Four Preset Batch Legend Plus w/Red Backlighting
Four Preset Batch Legend Plus w/Dual Color Backlighting
Multi-Preset (6) Legend Plus w/Grn Backlighting
Multi-Preset (6) Legend Plus w/Red Backlighting
Multi-Preset (6) Legend Plus w/Dual Color Backlighting
Four Preset Foot-Inch Counter w/Red Backlighting
Legend Plus Programming Software, 3 1/2", 1.44 M Disk
Dual Relay Board (Model LGPBs only)
6
LGPB0000
LGPB0100
LGPB0200
LGPM0001
LGPM0101
LGPM0201
LGPBF100
SFLGP
RLYLG002
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
7
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to one year from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls AP
Red Lion Controls
20 Willow Springs Circle
Red Lion Controls BV
Basicweg 11b
31, Kaki Bukit Road 3,
#06-04/05 TechLink
York PA 17402
NL - 3821 BR Amersfoort
Singapore 417818
Tel +1 (717) 767-6511
Tel +31 (0) 334 723 225
Tel +65 6744-6613
Fax +1 (717) 764-0839
Fax +31 (0) 334 893 793
Fax +65 6743-3360
Download