Chapter 9: Dimming actuators/control units 9.5 Control unit, 3-gang Control unit 1-10 V REG-K, 3-gang Art. No. 647129 Control unit 1-10 V REG-K, 3-gangChapter 9:Dimming actuators/control unitsArt. No.647129As at 01/019.5Control unit, 3-gang Control unit 1-10 V REG-K, 3-gang 1. Function The control unit is used for the brightness control of 3 lighting circuits. The following devices can be controlled: – Electronic ballasts with 1-10 V interface – Electronic LV halogen transformers with 1-10 V interface. A floating switch contact is used for switching off the connected devices. The switch outputs can also be used to switch additional lighting circuits. Article No. 647129 auto uell man 3 2 EIB bus insta it 1-10V ® inhe uere fach Ste -K / 3G RE 29 647150 Hz AC 1 230V "Auto/manual" selector switch: Table of Contents 1. Function 1 2. Commissioning 1 3. Technical Data 2 4. Settings in the EIB Tool Software (ETS) 3 5. Application overview 3 In the "Auto" position, the outputs are controlled by the assigned sensors via the bus cable. In the "Manual" position, the outputs can be switched via the operator buttons on the device. 2. Commissioning – Connect the power supply AC 230 V and bus voltage Connect the outputs – Check the function of the outputs: Set the selector switch to the "Manual" position. Switch the loads by pressing the operator buttons | Dimming is not possible via the operator butNote: tons on the device. – Check the bus connection: Set the selector switch to the "Auto" position. If the bus voltage fails, all the status displays flash. – Define the functional characteristics by assigning parameters and downloading the associated application software with the help of ETS. Notes about the programming: Assigning the physical address: – Set the selector switch to the "Auto" position to assign the physical address. – Press all 3 operator buttons simultaneously. The LED at output 1 flashes to indicate that the device is ready for programming. As at 01/01 1 Chapter 9: Dimming actuators/control units 9.5 Control unit, 3-gang Control unit 1-10 V REG-K, 3-gang Art. No. 647129 Circuit diagram: 3. Technical Data Electrical data Power supply: A AC 230 V, 50 Hz and INSTABUS EIB, DC 24 V (+ 6 / - 3 V) 5 VA maximum 10 W 10 A, cos ϕ = 0.6 Power consumption: Leakage loss: Nominal current: Operating data Control outputs 1-10 V: max. 50 mA current sink Contact rating: 16 A, cos ϕ = 1, 250 V (180,000 switching cycles) Contact endurance: 125,000 switching cycles At the following loads: Incandescent lamps: 2000 W LV halogen lamps with 2600 W electronic transformer: Fluorescent lamps with electronic ballast: 60 x 18 W 30 x 36 W 18 x 58 W Contact endurance: 100,000 switching cycles At the following load: Halogen lamps 230 V: 1600 W Environment Operation: 0 °C to +45 °C Storage: -20 °C to +70 °C Connection Cage clamp terminals: flexible: 1 mm2 to 6 mm2 solid: 1.5 mm2 to 10 mm2 Dimensions Size: 6 modules (approx. 108 mm) As at 01/01 230 V 50 Hz L N B C D L 1 3 9 11 13 15 17 19 auto K N EVG 1-10 V + manuell - instabusEIB ® E Steuereinheit 1-10V REG-K / 3-fach 1 6471 29 2 3 AC 230V 50 Hz F 10 12 14 16 18 20 - + I INSTABUS EIB - + - + H G J A Make contact, output 1 B Make contact, output 2 C Make contact, output 3 D Connection of an electronic ballast E Status display F Operator buttons: Manual operation of the outputs in the "Manual" position of the selector switch (only ON and OFF) G 1-10 V, output 3 H 1-10 V, output 2 I 1-10 V, output 1 J Further connection K Selector switch – top/"Auto": normal mode – bottom/"Manual": manual operation via operator buttons 2 Chapter 9: Dimming actuators/control units 9.5 Control unit, 3-gang Control unit 1-10 V REG-K, 3-gang Art. No. 647129 4. Settings in the EIB Tool Software (ETS) Selection in the product database Manufacturer: Product family: Product type: Program name: Media type: Product name: Order number: Merten 4.7 Control unit 1-10 V 4.7.01 DIN rail mounted REG-K Dimming 3271/1 Twisted Pair Control unit 1-10 V REG-K, 3-gang 647129 5. Application overview The following application can be selected: Application Vers. Function Dimming 3271/1 1 Behaviour on bus voltage recovery Switching – with adjustable starting behaviour – Memory function (last brightness value) – Status feedback of the relay state via separate status feedback object Dimming – with variable dimming speed Scenes – 4 scenes for the 3 outputs As at 01/01 3