Vintage Cutler-Hammer panelboards and switchboards

Renewal Parts RP01400003E
Effective February 2009
Supersedes February 2000
PB, PH, PH-L, FNB, EE, EP, ES,
CDP, MP40, MP200, NFB, MP100,
MP2, M50 Trim Locks and Trim
Clamps
Vintage Cutler-Hammer
panelboards and switchboards
PB
PH
PH-L
Description
EP
EE
MP40
MP100
Page
Vintage Cutler-Hammer姞 panelboards and switchboards
Procedure for identifying renewal parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Procedure for identifying panelboard type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PB panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PH panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PH-L panelboards and NFB panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
EP panelboards ES switchboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EE panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Type EE filler plates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
CDP, MP40, and NFB panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MP40 panelboards, CDP and NFB, MP2 switchboard chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
MP40 panelboards, MP2 switchboard chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
MP100 panelboards, MP2 switchboard chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Breaker cross-reference chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Panelboard trim clamps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Panelboard trim locks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Procedure for identifying renewal parts
Distributor ordering instructions
1. Identify the type of panelboard (PB, PH, PM-L, EE, EP, MP40,
MP100, MP200, CDP, CHP/CHB, NFB) from the data found on
the nameplate. Critical information includes:
• Type of panelboard
1. Specify the item by catalog or part number.
2. Refer to Price List PL01400003E for pricing information.
Discount Symbol CE9 applies.
3. Enter the order on Vista entry point SUM or Q49.
•
Ampere rating of the main
•
Ampere rating of the neutral
•
Voltage
•
Type of service (phase/number of wires)
•
General order number
•
In the event that the nameplate is missing or unreadable, follow
the procedure on page 3.
or
Note: For MP40 retrofit kits shown on page 30, enter the catalog number, list
price, standard multiplier, and location SUM or Q49.
When ordering a new circuit breaker to add to an MP40 panelboard,
the following options are available:
2. Refer to the listing below and turn to the proper section
in this renewal parts data to identify standard parts and
components.
Description
3. This book identifies those replacement parts which are most
frequently ordered and which are readily available from
stock. These parts can be ordered by style, part or catalog
number to speed up processing and delivery.
EATON CORPORATION www.eaton.com
Select the correct breaker retrofit kit on page 30 which includes
the breaker and connector kit in one package—one shipment and
one invoice from the Sumter plant.
4. Selling Policy 25-000 applies.
Page
PB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PH-L, NFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
EP, ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CDP, MP40, MP2, NFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
MP100, MP2, M50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Breaker cross-reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Trim locks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Trim clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2
•
Take the required breaker from your stock (or order from W34)
and order the connector kit on page 30 from the Sumter plant.
5. If additional assistance is required, contact the Panelboard
and Switchboard Aftermarket Product Center in Sumter, SC
at 1-803-481-6843.
Sumter plant services
All the parts and kits shown in this renewal parts will come from
the Sumter plant. To extend the life of your existing equipment,
the Sumter plant will:
•
Provide all new components
•
Manufacture per original specifications
•
Follow all UL姞 procedures
•
Provide full Cutler-Hammer warranty
Services offered include:
•
Parts and kits for MP40 and MP100 panelboards
•
Retrofit kits for MP2 switchboard distribution sections
•
Connector kits for MP2 switchboard distribution sections
•
Upgrades to meet changing system
•
Requirements such as higher fault current and increased load
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Procedure for identifying panelboard type
The nameplate could be located on the front or back of the deadfront cover. In the event that the nameplate is missing, it may still
be possible to identify the panel type by the enclosure width, the
ampere rating of the main device, and the branch devices from
Table 1 below.
Table 1. Procedure for Identifying Panelboard Type—
Dimensions in Inches (mm)
Enclosure
Width in
Inches
Main Lug
or Device
Rating
Branch Breakers or Fusible
Switches
Panelboard
Type
15.00
(381.0)
Up to 225A
maximum
Are in two vertical cutouts
measuring 7.00 inches (177.8 mm)
from side to side and have either
tan or gray breaker handles.
PB
21.00
(533.4)
Up to 400A
maximum
Are in two vertical rows measuring 7.00 inches (177.8 mm) from
side to side and have either tan
or gray breaker handles.
PB
Up to 600A
maximum
Are CH, CHB, F and C-Frames and
are in a single cutout measuring
14.25 inches (362.0 mm) across.
PH
6–9
Up to 225A
maximum
Are in two vertical cutouts measuring 14.25 inches (362.0 mm)
across, are F-Frame, and have
breakers with black handles.
PH-L
NFB 10, 11
Up to 800A
maximum
Are CH, CHB, F and C-Frames and
are in a single cutout measuring
14.25 inches (362.0 mm) across.
PH
6–9
26.00
(660.4)
See
Page
4, 5
Circuit Breaker Unit for EP Panelboards
4, 5
Fusible Switch Unit for EP Panelboards
30.00
(762.0),
42.00
(1066.8)
or 48.00
(1219.2)
Up to 1200A
main breaker
Circuit breakers or fusible
switches do not have metal side
flanges. Circuit breaker covers are
attached to the trim.
EP
ES
12–19
or 800A main
fusible switch
or 1200A
MLO
Circuit breakers or fusible
switches have sheet metal side
flanges. Circuit breaker covers are
attached to the breaker.
EE
20–25
30.00
(762.0),
38.00
(965.2)
Up to 1200A
main breaker
or fusible
switch or
1600A MLO
F-Frame through L-Frame are
twin-mounted horizontal with
center cover between breakers.
NFB CDP
MP40
26–29
Fusible switches are labeled M50
30 through 1200A.
MP100
30–32
21.00-inch (533.4 mm) width.
26.50-inch (673.1 mm)–36.00-inch (914.4 mm) width.
Circuit Breaker Unit for EE Panelboards
Fusible Switch Unit for EE Panelboards
EATON CORPORATION www.eaton.com
3
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
PB panelboards
Trim
Neutral
Box
Deadfront
Cover
Main Lugs
UL Label
Label
(Panelboard
Type)
Trim Lock
Branch Breakers
CH or CHB
Circuit Breaker
Directories
Ground Bar
PB Panelboards
Table 2. Type PB Panelboard Trims and Deadfront Covers—Dimensions in Inches (mm)
Maximum
Pole Space
Main
Amperes
Indoor 15.00 (381.0) Wide
Indoor 21.00 (533.4) Wide
Box
Height
Trim (S or F)
Catalog Number
Deadfront Cover
Kit Part Number
Box
Height
Trim (S or F)
Catalog Number
Deadfront
Cover Kit Part
Number
29.00 (736.6)
34.00 (863.6)
38.00 (965.2)
—
PB29T(S/F)
PB34T(S/F)
PB38T(S/F)
—
99-3613-5
99-3613-20
—
30.00 (762.0)
34.00 (863.6)
38.00 (965.2)
54.00 (1371.6)
PW30T(S/F)
PW34T(S/F)
PW38T(S/F)
PW54T(S/F)
PW30KT1NB
PW34KT1NB
PW38KT1NB
99-3613-9
34.00 (863.6)
42.00 (1066.8)
42.00 (1066.8)
48.00 (1219.2)
—
PB34T(S/F)
PB42T(S/F)
PB42T(S/F)
PB48T(S/F)
—
99-3613-22
99-3613-8
99-3613-8
39-3613-16
—
34.00 (863.6)
42.00 (1066.8)
42.00 (1066.8)
50.00 (1270.0)
63.00 (1600.2)
PW34T(S/F)
PW42T(S/F)
PW42T(S/F)
PW50T(S/F)
PW63T(S/F)
PW34KT2NB
PW42KT1NB
PW42KT1NB
PW50KT1NB
99-3613-29
29.00 (736.6)
29.00 (736.6)
34.00 (863.6)
38.00 (965.2)
—
PB29T(S/F)
PB29T(S/F)
PB34T(S/F)
PB38T(S/F)
—
99-3613-11
99-3613-17
39-3613-27
—
30.00 (762.0)
30.00 (762.0)
34.00 (863.6)
38.00 (965.2)
54.00 (1371.6)
PW30T(S/F)
PW30T(S/F)
PW34T(S/F)
PW38T(S/F)
PW54T(S/F)
PW30KT1NB
PW30KT3NB
PW34KT1NB
PW38KT1NB
99-3613-4
34.00 (863.6)
34.00 (863.6)
42.00 (1066.8)
42.00 (1066.8)
48.00 (1219.2)
—
PB34T(S/F)
PB34T(S/F)
PB42T(S/F)
PB42T(S/F)
PB48T(S/F)
—
99-3613-13
99-3613-30
99-3613-8
99-3613-3
39-3613-16
—
34.00 (863.6)
34.00 (863.6)
42.00 (1066.8)
42.00 (1066.8)
50.00 (1270.0)
63.00 (1600.2)
PW34T(S/F)
PW34T(S/F)
PW42T(S/F)
PW42T(S/F)
PW50T(S/F)
PW63T(S/F)
PW34KT1NB
PW34KT1NB
PW42KT1NB
PW42KT1NB
PW50KT1NB
99-3613-28
Main Lugs Only—Single-Phase, 3-Wire
18
30
42
42
125
225
225
400
Main Breaker—Single-Phase, 3-Wire
18
30
30
42
42
100
150
255
225
400
Main Lugs Only—Three-Phase, 4-Wire
18
30
30
42
42
125
125
225
225
400
Main Breaker—Three-Phase, 4-Wire
18
24
30
30
42
42
100
100
150
225
225
400
Contact the Aftermarket Product Center in Sumter, SC at 1-800-556-4569.
4
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Ground bar Al/Cu
Filler plate
Filler Plate
Ground Bar Al/Cu
Table 6. Filler Plate
Table 3. Ground Bar Al/Cu
Description
Catalog Number
225A Al/Cu
CH9GP21
400A Al/Cu
CH9GB04A2
Description
Catalog Number
Filler Plate
CH9CP
400A neutral bar
125 and 225A neutral bar
400A Neutral Bar
Table 7. 400A Neutral Bar
125 and 225A Neutral Bar
Description
Catalog Number
Neutral Bar
PB42SN400
Sub-Feed Lugs
Table 4. 125 and 225A Neutral Bar
Description
Catalog Number
125A
PB24SN125
225A
PB42SN225
Corner Grounded Adapter Kit
Sub-Feed Lugs
Table 8. Sub-Feed Lugs
Description
Catalog Number
225A
PB225SF3
400A
PB400SF3
Deadfront covers
Corner Grounded Adapter Kit
Table 5. Corner Grounded Adapter Kit
Panel Ampere Rating
Type of Main
Catalog Number
125
225
400
Main Lug
Main Lug
Main Lug
PBGRDB125ML
PBHGRDB225ML
PBHGRDB400ML
100
225 400
Main Breaker
Main Breaker
Main Breaker
PBGRDB100MB
PBGRDB225MB
PBGRDB400MB
For 225A CHH main breaker for top feed only, order PBGRDB225CHH.
Deadfront Covers
Note: Refer to Table 2 for catalog numbers.
Branch breakers
To order branch circuit breakers, identify the breaker (CH or CHB),
the number of poles (1, 2, 3), and the ampere rating (10 through
100A). Contact your local distributor.
EATON CORPORATION www.eaton.com
5
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
PH panelboards
Trim
Box
Neutral
Ground
Bar
Branch
Breakers
Breaker
Cover
Plates
Trim Lock
Circuit
Breaker
Directory
Branch
Breakers
Blank Filler
Plates
Label
(Panelboard
Type)
Circuit
Breaker
Directory
Main Breaker
UL Label
Deadfront
Covers
PH Panelboards
6
EATON CORPORATION www.eaton.com
Trim Lock
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Must specify in notes whether this is for a single-phase panel or a
three-phase panel.
“B” space increments
Type PH panelboards are divided vertically into “B” space increments each occupying four (4) normal pole spaces for single-phase
panels or six (6) pole spaces in a three-phase panel. All circuit
breakers mounted in one “B” space must be in the same family
type (EHD, F-Frame, and CC, CCH, CHH). Each kit consists of a
breaker, connectors, installation instructions and a deadfront panel
cover plate to mount all breakers in a single “B” space increment.
Order one retrofit kit for each “B” space increment or a filler plate
to cover unused “B” spaces. Refer to page 10 for filler plates.
EHD, F-Frame retrofit kit
Each kit includes one breaker, copper connectors for twin mounting,
covers, mounting brackets, hardware and installation instructions.
PH breaker retrofit kits
A retrofit kit includes one breaker and all the associated parts
required for mounting on a PH panel chassis.
Table 9. PH Panelboards
Frame Ampere
Rating
Breaker
Frame
Number of
Poles
Trip Range
Mounting
Type
CC, CCH, CHH single unit retrofit kit
240 Vac Maximum
225
EHD, F-Frame Retrofit Kit
CC
CC
CCH
CCH
CHH
2, 3
2, 3
2, 3
2, 3
2, 3
100–225
100–225
100–225
100–225
60–225
Single
Twin Single
Twin Single
Each kit includes one breaker, copper connectors, covers, mounting
brackets, hardware, and installation instructions.
277 Vac Maximum
100
EHD
FDB
FD
HFD
1
1
1
1
15–100
15–100
15–100
15–100
Twin
Twin
Twin
Twin
2, 3
15–100
Twin
480 Vac Maximum
100
EHD
600 Vac Maximum
100
FDB
FD
HFD
2, 3
2, 3
2. 3
15–100
15–100
15–100
Twin
Twin
Twin
150
FDB
FD
HFD
2, 3
2, 3
2, 3
15–150
15–150
15–150
Twin
Twin
Twin
CC, CCH, CHH Single Unit Retrofit Kit
CC, CCH double unit retrofit kit
Each kit includes one breaker, copper connectors for twin mounting,
covers, mounting brackets, hardware, and installation instructions.
For three-phase panelboards only.
How to create a retrofit kit catalog number
Use “KPH” prefix and add the catalog number of the specific breaker as shown in Table 10.
Twin mounting indicates that only one set of connectors is required
to mount two breakers (of similar frames) opposite one another.
A RETROFIT KIT INCLUDES ONE BREAKER ONLY, FOR EITHER
SINGLE OR TWIN MOUNTED APPLICATIONS. If a second breaker
is required for a twin mounting application, it must be specified as a
separate item.
Example: The retrofit kit catalog number for a 3-pole, 100A, FDB
breaker is:
CC, CCH Double Unit Retrofit Kit
Table 10. Catalog Numbering System
KPH FDB 3 100 T
Designates PH
Retrofit Kit
T = Twin
S = Single
Breaker Frame
Ampere Rating
Number of Poles
2 = 2-Pole
3 = 3-Pole
EATON CORPORATION www.eaton.com
7
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EHD, F-frame connector/mounting kit
Table 11. Connector/Mounting Kits—for Branch Breakers
Branch
Breaker
Type
Volts
Maximum
Amperes
Each “B” Space
Increment Breaker
Loading
Number
of Poles
Catalog
Number
Single-Phase Panel
Three-Phase Shown
CC, CCH, CHH connector/mounting kit
EHD and
F-Frame
600
100
Any combination of
1-pole or 2-pole breakers up to maximum of
4-poles.
4
PH4E-1
CC, CCH,
CHH
240
225
Occupies all 4-pole
spaces.
2
PH2CC1
Three-Phase Panel
EHD and
F-Frame 600
150
Any combination of
1-pole, 2-pole or 3-pole
breakers up to maximum of 6-poles.
6
PH6E-3
CC, CCH,
CHH
240
225
Occupies all 6 pole
spaces.
3
PH3CC3
CC, CCH 240
225
One 3-pole each side.
6
PH6C-3
CH, CHB connector kits are no longer available. Use F-Frame retrofit kits as listed on page 7.
Maximum amperes per breaker not to exceed 150A, and maximum amperes connected to any one
connector not to exceed 200A. (50A–150A.)
Dual CC, CCH mounting in 21.00-inch (533.4 mm) wide box limits wire size to 4/0.
Note: Each kit includes copper connectors, mounting brackets, covers,
hardware and installation instructions.
Three-Phase Shown
CC, CCH, CHH dual unit connector/mounting kit
Three-Phase Shown
8
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Table 12. PH Panelboard Trims and Deadfront Covers—Dimensions in Inches (mm)
21.00 (533.4) Wide
Maximum
Pole Space
26.00 (660.4) Wide
Main
Amperes
21.00 (533.4) and 26.00
(660.4) Wide
Box
Height
Trim (S or F)
Catalog Number
Box
Height
Trim (S or F)
Catalog Number
Deadfront Cover Kits
Part Number
42.00 (1066.8)
50.00 (1270.0)
54.00 (1371.6)
63.00 (1600.2)
54.00 (1371.6)
63.00 (1600.2)
—
—
PW42T(S/F)
PW50T(S/F)
PW54T(S/F)
PW63T(S/F)
PW54T(S/F)
PW63T(S/F)
—
—
42.00 (1066.8)
50.00 (1270.0)
54.00 (1371.6)
63.00 (1600.2)
54.00 (1371.6)
63.00 (1600.2)
59.00 (1498.6)
67.00 (1701.8)
PWW42T(S/F)
PWW50T(S/F)
PWW54T(S/F)
PWW63T(S/F)
PWW54T(S/F)
PWW63T(S/F)
PWW59T(S/F)
PWW67T(S/F)
59.00 (1498.6)
67.00 (1701.8)
67.00 (1701.8)
75.00 (1905.0)
67.00 (1701.8)
75.00 (1905.0)
PW59T(S/F)
PW67T(S/F)
PW67T(S/F)
PW75T(S/F)
PW67T(S/F)
PW75T(S/F)
59.00 (1498.6)
67.00 (1701.8)
67.00 (1701.8)
75.00 (1905.0)
67.00 (1701.8)
75.00 (1905.0)
PWW59T(S/F)
PWW67T(S/F)
PWW67T(S/F)
PWW75T(S/F)
PWW67T(S/F)
PWW75T(S/F)
34.00 (863.6)
42.00 (1066.8)
50.00 (1270.0)
54.00 (1371.6)
63.00 (1600.2)
54.00 (1371.6)
63.00 (1600.2)
—
—
PW34T(S/F)
PW42T(S/F)
PW50T(S/F)
PW54T(S/F)
PW63T(S/F)
PW54T(S/F)
PW63T(S/F)
—
—
—
42.00 (1066.8)
50.00 (1270.0)
54.00 (1371.6)
63.00 (1600.2)
54.00 (1371.6)
63.00 (1600.2)
59.00 (1498.6)
67.00 (1701.8)
—
PWW42T(S/F)
PWW50T(S/F)
PWW54T(S/F)
PWW63T(S/F)
PWW54T(S/F)
PWW63T(S/F)
PWW59T(S/F)
PWW67T(S/F)
99-3613-2
99-3613-7
99-3613-6
99-3613-15
99-3613
99-3613-18
99-3613-10
50.00 (1270.0)
59.00 (1498.6)
67.00 (1701.8)
67.00 (1701.8)
75.00 (1905.0)
67.00 (1701.8)
75.00 (1905.0)
PW50T(S/F)
PW59T(S/F)
PW67T(S/F)
PW67T(S/F)
PW75T(S/F)
PW67T(S/F)
PW75T(S/F)
50.00 (1270.0)
59.00 (1498.6)
67.00 (1701.8)
67.00 (1701.8)
75.00 (1905.0)
67.00 (1701.8)
75.00 (1905.0)
PWW50T(S/F)
PWW59T(S/F)
PWW67T(S/F)
PWW67T(S/F)
PWW75T(S/F)
PWW67T(S/F)
PWW75T(S/F)
Main Lugs Only—Single-Phase, 3-Wire
28
40
28
40
28
40
28
40
225
225
400
400
600
600
800
800
99-3613-14
99-3613-31
99-3613-24
99-3613-21
Main Breaker—Single-Phase, 3-Wire
28
40
28
40
28
40
225
225
400
400
600
600
Main Lugs Only—Three-Phase, 4-Wire
18
30
42
30
42
30
42
30
42
225
225
225
400
400
600
600
800
800
Main Breaker—Three-Phase, 4-Wire
18
30
42
30
42
30
42
225
225
225
400
400
600
600
Contact the Aftermarket Product Center in Sumter, SC at 1-800-556-4569.
EATON CORPORATION www.eaton.com
9
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
600/800A neutral bar
Ground bar Al/Cu
600/800A Neutral Bar
Ground Bar Al/Cu
Table 16. 600/800A Neutral Bar
Table 13. Ground Bar Al/Cu
Description
Catalog Number
225A Al/Cu
400A Al/Cu
400A Copper
CH9GP21
CH9GB04A2
CH9GB04C2
600A Al/Cu
600A Copper
800A Al/Cu
800A Copper
PHGB06A2
PHGB06C2
EPGB12A2
EPGB12C2
Description
Part Number
600A
99-2085-2
800A
99-2085-3
Deadfront covers
Refer to Table 12 for part numbers.
225A neutral bar
225A Neutral Bar
Table 14. 225A Neutral Bar
Description
Catalog Number
Neutral Bar
PB42SN225
400A neutral bar
Deadfront Covers
Blank filler plate
400A Neutral Bar
Table 15. 400A Neutral Bar
Blank Filler Plate
Table 17. Blank Filler Plate
Description
Part Number
Description
Catalog Number
Neutral Bar
99-2086-2
Single-Phase
PH4CP
Three-Phase
PH6CP
10
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Table 20. Breaker Cover Plate
Breaker cover plate
For CH and CHB breakers.
Description
Part Number
Single-Phase
47-28007
Three-Phase
47-28008
Corner grounded adapter kit
Breaker Cover Plate
Table 18. Breaker Cover Plate
Description
Catalog Number
Breaker Cover Plate
CH9CP
Breaker cover plate
For F- and C-Frame breakers.
Corner Grounded Adapter Kit
Table 21. Corner Grounded Adapter Kit
Breaker Cover Plate
Table 19. Breaker Cover Plate
Description
Part Number
Breaker Cover Plate
47-28266
Panel Ampere Rating
Type of Main
Catalog Number
225
400
600
Main Lug
Main Lug
Main Lug
PBHGRDB225ML
PBHGRDB400ML
PHGRDB600ML
225
400
600
Main Breaker
Main Breaker
Main Breaker
PHGRDB225MB
PHGRDB400MB
PHGRDB600MB
Breaker cover plate
Breaker Cover Plate
EATON CORPORATION www.eaton.com
11
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
PH-L panelboards and NFB panelboards 21.00 inches (533.4 mm) wide
Box
Trim
Deadfront
Cover
Blank Filler
Plates
Trim
Lock
Circuit
Breaker
Directory
Branch
Breakers
Branch
Breakers
Trim
Lock
Main Lugs
Ul Label
Ground
Bar
Neutral
PH-L Panelboards and NFB Panelboards 21.00 Inches (533.4 mm) Wide
Table 22. PH-L Panelboard Trims—Dimensions in Inches (mm)
Maximum Pole
Spaces
Main
Amperes
Box
Height
Trim (S or F)
Catalog Number
Main Lugs Only—Three-Phase, 4-Wire
18
30
42
225
225
225
34.00 (863.6)
42.00 (1066.8)
50.00 (1270.0)
PW34T(S/F)
PW42T(S/F)
PW50T(S/F)
50.00 (1270.0)
59.00 (1498.6)
67.00 (1701.8)
PW50T(S/F)
PW59T(S/F)
PW67T(S/F)
Main Breaker—Three-Phase, 4-Wire
18
30
42
12
225
225
225
EATON CORPORATION www.eaton.com
PH-L and PH panelboards have the following common parts:
•
Ground bar
•
Neutral bars
•
Corner grounded adapter kits
Refer to page 9 for the applicable style and part numbers.
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
PH-L breaker retrofit kits
Deadfront cover
A retrofit kit includes one breaker and all the associated parts
required for mounting on a PH-L panel chassis.
Note: The below PH-L retrofit kits and blank filler plate will fit a 21.00-inch
(533.4 mm) wide NFB panelboard.
Table 23. PH-L Breaker Retrofit Kits
Frame Ampere
Rating
Breaker
Frame
Number of
Poles
Trip Range
Mounting
Type
1
1
1
1
15–100
15–100
15–100
15–100
Twin
Twin
Twin
Twin
2, 3
15–100
Twin
277 Vac Maximum
100
EHD
FDB
FD
HFD
480 Vac Maximum
100
EHD
600 Vac Maximum
100
FDB
FD
HFD
2, 3
2, 3
2, 3
15–100
15–100
15–100
Twin
Twin
Twin
150 FDB
FD
HFD
2, 3
2, 3
2, 3
15–150
15–150
15–150
Twin
Twin
Twin
Kit contains A, B and C phase connectors, hardware and instructions to twin mount two 3-pole
above listed frame breakers. Maximum amperes per breaker not to exceed 150A and maximum
amperes connected to any one connector not to exceed 200A (50–150A).
Deadfront Cover
How to create a retrofit kit catalog number
Use “KPH-L” prefix and add the catalog number of the specific
breaker as shown in Table 24.
Contact the Aftermarket Product Center in Sumter, SC at
1-800-556-4569.
Twin mounting indicates that only one set of connectors is required
to mount two breakers (of similar frames) opposite one another.
A RETROFIT KIT INCLUDES ONE BREAKER ONLY. FOR TWIN
MOUNTED APPLICATIONS. If a second breaker is required for a
twin mounting application, it must be specified as a separate item.
EHD and F-Frame retrofit kit
Each kit includes one breaker, copper connectors for twin mounting,
hardware, mounting brackets and instructions. Blank filler plates are
not included.
Important: The retrofit kit catalog number for a 3-pole, 100A, FDB
breaker is:
Table 24. Catalog Numbering System
KPH-L FDB 3 100 T
Designates PH-L
Retrofit Kit
T = Twin
Ampere Rating
Breaker Frame
Number of Poles
2 = 2-Pole
3 = 3-Pole
EHD and F-Frame Retrofit Kit
PH-L and NFB 21.00-inch (533.4 mm) wide blank filler plate
PH-L and NFB 21.00-Inch (533.4 mm) Wide Blank Filler Plate
Table 25. PH-L and NFB 21.00-Inch (533.4 mm) Wide Blank
Filler Plate
Description
Part Number
21.00-Inch (533.4 mm)
Wide Blank Filler Plate
47-15718-2
EATON CORPORATION www.eaton.com
13
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EP panelboards and ES switchboards
Box
Single Width
Circuit Breaker
Unit
Single Width
Fusible Switch
Unit
Dual Mounted
Unit with 2
Circuit Breakers
Single Width
Circuit Breaker
Unit
EP Panelboard
Nameplate
Breaker
Filler
Plate
Single Width
Fusible Switch
Unit
Double Width
Fusible Switch
Unit
Lug Unit
Neutral
Ground Bar
Trim
EP Panelboards
14
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Branch circuit selection of EE2 units
Step 1: Select the correct branch circuit device.
When selecting, you need to know the following:
•
Amperage
•
System voltage
•
Available short circuit rating
•
Number of poles
•
Size and number of wires per phase
•
X space required 1X = 1.38 inches (35.1 mm)
Step 2: Refer to the EP panelboard layout on page 14 to verify the
amount of X space available.
Step 3: Create an EE2 Unit catalog number, or order by
description, by following the instructions on page 15.
Step 4: Determine if extra filler covers are required. Additional filler
covers may be necessary to fill the unused space. Refer to
page 20 for filler plate information.
Table 26. Electrical Characteristics and X Space Requirements of Branch Circuit Breakers and Fusible Switches
Circuit
Breaker
Ampere
Rating
Number of
Poles
Maximum
Vac
UL Listed Interrupting Capacities—kA Symmetrical Amperes
DC Rating Volts AC Rating Volts
X Space
Required
240
277
480
600
125
250
EHD
15–100
15–100
1
2, 3
277
480
—
18
14
14
—
—
—
—
10
—
—
10
FDB
FD
FDC
15–225
15–225
15–225
15–225
15–225
15–225
2, 3
1
2, 3
1
2, 3
2, 3
600
277
600
277
600
600
18
—
65
—
100
200
–—
25
—
—
—
—
14
—
25
65
65
100
14
—
18
—
25
35
—
10
—
10
—
—
10
—
10
—
22
22
ED
EDH
EDC
100–225
100–225
100–225
2, 3
2, 3
2, 3
240
240
240
65
100
200
—
—
—
—
—
—
—
—
—
10
10
10
—
—
—
JD, JDB
HJD
JDC
70–250
70–250
70–250
2, 3
2, 3
2, 3
600
600
600
65
100
200
—
—
—
35
65
100
18
25
35
—
—
—
10
22
22
DK
KD, KDB
HKD
KDC
250–400
100–400
100–400
100–400
2, 3
2, 3
2, 3
2, 3
240
600
600
600
65
65
100
200
—
—
—
—
—
35
65
100
—
25
35
50
—
—
—
—
10
10 22 22 4X
LCL
LD, LDB
HLD
LDC
100–400
125–400
300–600
300–600
2, 3
2, 3
2, 3
2, 3
600
600
600
600
200
65
100
200
—
—
—
—
200
35
65
100
—
25
35
50
—
—
—
—
—
22 25 25 6X
MDL
HMDL
ND
HND
NDC
300–600
300–800
600–1200
600–1200
600–1200
2, 3
2, 3
2, 3
2, 3
2, 3
600
600
600
600
600
65
100
65
100
200
—
—
—
—
—
50
65
35
65
100
25
35
25
35
50
—
—
—
—
—
22 25 —
—
—
12X HFD
3X
Fusible Switches
Fusible Switches are not available. Replace with circuit breaker units from above.
WARNING: Circuit breaker units will not fit across from a fusible switch or lug unit.
DC ratings apply to substantially non-inductive circuits.
DC ratings not available with electronic trip.
12X space requires a double bus panel only.
EATON CORPORATION www.eaton.com
15
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EP panelboards
“X” unit layout of circuit breaker and fusible switch units
Note: For current circuit breaker offering, refer to the cross-reference Table 50 on page 33.
Note: Switch and breaker units may be combined without transition space in the same panel, but not horizontally opposed in double-bus interiors.
1X = 1.38 inches (35.1 mm).
42.00 (1066.8)
10.00 (254.0)
10.00 (254.0)
3X
3-Pole
JS, JH, JL
3X
Filler Plate
➃
3X
10X
Blank Wireway ① 3X
7X
2- or 3-Pole
6X
LSB, LHB, LLB, LC
200A
Branch Switch
600V, J-T Fuse ➃
6X
100A
Branch Switch ➃
6X
6X
12X
800A MS, MH, MC, HMC
Branch Breaker
6X
8X
6X
12X
1200A NS, NH, NC, HNC
Main or Branch Breaker ➁
6X
10X
10.00
(254.0)
10.00
(254.0)
10.00 (254.0)
14X
200A Branch Switch Unit
600V, R Fuse ➂
7X
12X
800A MS, MH, MC
Main Breaker ➁
6X
20X
400A–600A Main or
Branch Switch Unit ➁
Blank Filler ➃
Load
3-Pole
FS, FH,
CC, CCH
3-Pole
CHH
7X
10X
Load
3X
3-Pole
FS, FH,
CC, CCH
3-Pole
CHH
7X
7X
400A–600A
Branch Switch
Lug Unit
Load
Blank Wireway ①
7.00
(177.8)
8X
30A–60A ➃
Branch Switch
Load
3X
14X
400A–600A Main or
Branch Lug Unit ➁
7X
2X
Line/Load Line/Load
2-P FS, FH, 2-P FS, FH,
CC, CCH
CC, CCH
Blank Wireway ① 2X
FS, FH, 2-P FS, FH,
Blank Wireway ① 2-P
CC, CCH
CC, CCH 2X
2X 2-Pole CHH 2-Pole CHH Blank Wireway ① 2X
2X
7X
3-Pole FS, FH, FL,
3X
CC, CCH, CHH
14X
800A–1200A Main or
Branch Lug Unit ➁
5X
800A Main
or Branch
Lug Unit ➃
Load
3-Pole FS, FH, FL,
CC, CCH, CHH
2X
8X
Load
3X
2-Pole FS, FH, FL
CC, CCH, CHH
Line/Load
2-Pole FS, FH, FL
CC, CCH, CHH
Neutral ñ No ì Xî Factor
Top or Bottom
7.00
(177.8)
Load
2X
7.00
(177.8)
Line
Neutral ñ No ì Xî Factor
Top or Bottom
Load
7.00
(177.8)
42.00 (1066.8)
10X
20X
800A Main or Branch
Switch Unit ➁
10.00
(254.0)
10.00
(254.0)
10.00 (254.0)
48.00 (1219.2)
48.00 (1219.2)
Figure 1. Double-Bus Interior Mounted in 42.00-Inch (1066.8 mm) or 48.00-Inch (1219.2 mm) Wide Enclosure—
Dimensions in Inches (mm)
Blank wireway fillers are required opposite any dual breaker unit or adapter.
Main device must be mounted at the neutral end of double-bus panel.
Single plug-on connector provided opposite the load end of wide switch unit may require staggering to balance double-bus loading.
May be used in 30.00-inch (762.0 mm) wide single bus interiors.
Table 27. EP-Line Box Sizes and Maximum Component Unit Sizes—Dimensions in Inches (mm)
Box Width
and Bus
Type
Total “X”
Factor
Box
Height
Maximum Ampere of Plug-on Components
30.00 (762.0)
Wide
Single-Bus
24X
32X
40X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
800
42.00 (1066.8)
Wide
Double-Bus
48X
64X
80X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
1200 48.00 (1219.2)
Wide
Double-Bus
48X
64X
80X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
1200 Main
Lugs
Branch
Lugs
Branch
Breaker
Main
witch
Branch Fusible
Switch
600
600
—
100A
600V
R Fuse
1200 Twin
400 Single
800 600
600 600
1200 Twin
600 Single
1200 800
800 800
600
Main
Breaker
200A
600V
J or T Fuse
200A
240V
R Fuse
Mains must be twin-mount types (over 8X space factor), and must be mounted on the neutral end of the panel. Smaller 4X or 6X breakers may be used as the main breaker when a 1200A lug unit is used to
tie across the double-bus. The 1200A lug unit must be mounted at the neutral end with the main breaker adjacent to the lug unit.
16
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Table 29. How to Create an EE2 Circuit Breaker Plug-on Unit
Catalog Number
EP panelboards and ES switchboards
EE2 circuit breaker plug-on units
A plug-on unit is a complete assembly with a circuit breaker and
mounting adapter to mount on an EP panelboard.
Single indicates units that may be mounted in a single or double
bus panel, and twin indicates double bus panels only.
Breaker
Frame
Trip
Range
Mounting
Type
Space Required
Inches
(mm)
X Space
EHD
EHD
FDB
FDB
FD
FD
HFD
HFD
FDC
FDC
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
4.13 (104.9)
FDB
FD
HFD
FDC
110–225
110–225
110–225
110–225
Single
Single
Single
Single
4.13 (104.9)
ED
EDH
EDC
JD
HJD
JDC
100–225
100–225
100–225
70–225
70–225
70–225
Single
Single
Single
Single
Single
Single
250
JD
HJD
JDC
250
250
250
Single
Single
Single
4.13 (104.9)
3X
400
KD
HKD
KDC
100–400
100–400
100–400
Single
Single
Single
5.50 (139.7)
4X
LCL
125–400
Single
8.25 (209.6)
6X
600
LD
HLD
LDC
300–600
300–600
300–600
Single
Single
Single
8.25 (209.6)
6X
800
MDL
HMDL
400–800
400–800
Twin
Twin
8.25 (209.6)
12X
1200
ND
HND
NDC
600–1200
600–1200
600–1200
Twin
Twin
Twin
8.25 (209.6)
12X
100
225
Model
Type of Unit
2 indicates EP
Panelboard or ES
Switchboards
Circuit Breaker
Type
Table 28. EE2 Circuit Breaker Plug-on Units
Frame
Ampere
Rating
EE EHD 2 2 0015 S B 2
3X
M = Main
B = Branch
C = Combination
Phasing
AC = 2
ABC = 3
ABL or BCR = 4
BCL or ABR = 5
T = Twin
S = Single
Volts
1 = 120V
2 = 240V
3 = 277V or 300V
4= 480V
6= 600V
Amperes
Use all 4 characters
(i.e., 15A = 0015)
3X
Type EE2 single plug-on unit
Each single plug-on unit comes as a complete assembly with one
circuit breaker mounted to an adapter. Also included is a breaker
cover plate, hardware and installation instructions.
Type EE2 Single Plug-on Unit
EATON CORPORATION www.eaton.com
17
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EP panelboards and ES switchboards
Type ED dual plug-on units
Each dual plug-on unit comes as a complete assembly with one
or two circuit breakers mounted to an adapter. Also included is a
breaker cover plate, hardware and installation instructions. A blank
wire way filler plate is required when a unit is mounted in a double
bus panel.
ED dual plug-on units are ordered by description.
Specify:
•
The number of 3-pole breakers to be mounted on each unit
(maximum 2).
•
The breaker frame with current rating and the operating voltage.
•
The available frame ratings are listed in Table 30.
Type ED Dual Plug-on Units
Table 30. Type ED Dual Plug-on Units
Frame Ampere Rating
Breaker Frame
Inches (mm)
X Space
100
EHD
EHD
FDB
FDB
FD
FD
HFD
HFD
FDC
FDC
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
4.13 (104.9)
3X
225
FDB
FD
HFD
FDC
100–225
100–225
100–225
100–225
Single
Single
Single
Single
4.13 (104.9)
3X
ED
EDH
EDC
100–225
100–225
100–225
Single
Single
Single
18
Trip Range
EATON CORPORATION www.eaton.com
Mounting Type
Space Required
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Table 31. Neutral Assembly
EP panelboards
Incoming Number of Cables and Wire Size
Neutral assembly
Catalog Number
Neutral Assemblies with Lugs
(4) 250–500 Kcmil Aluminum/Copper
(4) 250–500 Kcmil Copper Neutral
EPN08A
EPN08C
Neutral Lugs (Lugs Only)
(1) 1/0–750 Kcmil or (2) 1/0–300 Kcmil Aluminum/Copper
(2) 250–500 Kcmil Aluminum/Copper
(3) 3/0–750 Kcmil Aluminum/Copper
(4) 3/0–750 Kcmil Aluminum/Copper
EPN400L
EPN600L
EPN800L
EPN1200L
Type EE2 plug-on lug units are used as main lug only or sub-feed
lugs on EP panelboards. The plug-on unit comes as a complete
assembly with lugs mounted to an adapter. Also included is a cover
plate, hardware and installation instructions.
Table 32. Type EE2 Plug-on Lug Units
Neutral Assembly
EP panelboards and ES switchboards
Type EE2 plug-on lug units
Branch lug units require overcurrent protection per NECT
Article #240-21.
Maximum
Amperes
“X”
Factor
Number of Cables/Phase and Wire Size
Aluminum/Copper
Catalog Number
400 600 800
600
1200
8X
8X
8X
14X
14X
(1) 1/0–500 Kcmil or (2) 1/0–250 Kcmil
(2) #4–500 Kcmil
(2) #2–500 Kcmil or (3) #4–400 Kcmil
(2) #4–500 Kcmil
(4) #4–500 Kcmil
EELUG360400SC2
EELUG360600SC2
EELUG360800SC2
EELUG360600TC2
EELUG361200TC2
400A lug unit can also be used as a branch feeder in all panels and all box widths.
600A lug unit can be used as a branch feeder only in the 30.00-inch (762.0 mm) and
48.00-inch (1219.2 mm) wide boxes.
Table 33. Grounding Kits
Description
Catalog Number
Equipment Ground Bar Kit
(2) #6–300 Kcmil, (8) #14–1/0 and (23) #14–#6
EPGB12A2
Ground Conductor Lug Only
Type EE2 Plug-on Lug Units
(2) #6–250 Kcmil
EPGL2
Grounding kits (for aluminum/copper wire)
Grounding Kits
EATON CORPORATION www.eaton.com
19
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EP panelboards and ES switchboards
Table 34. Type EE2 Breaker Filler Plates
Full width plate for use with double
bus interiors in 42.00-inch (1066.8
mm) and 48.00-inch (1219.2 mm)
wide enclosures. “X” Factor
Catalog Number
1X
2X
3X
4X
5X
6X
8X
10X
12X
—
EEFPB2T2
—
EEFPB4T2
—
EEFBP6T2
EEFPB8T2
EEFBP10T2
EEFPB12T2
Single width for use with single bus
width interiors and across from circuit
breakers in wide panels.
Single width blank wireway to cover the
bus across from a dual-mount adapter
kit in a bus interior. Also used opposite
breakers with accessories.
Single width blank bus cover and trim
fillers for use across from breakers for
six disconnect rule (SUSE) applications.
EEFPB1S1
EEFPB2S1
EEFPB3S1
EEFPB4S1
EEFPB5S1
EEFPB6S1
—
—
—
—
EEFPB2S2W
EEFPB3S2W
EEFPB4S2W
EEFPB5S2W
EEFPB6S2W
—
—
—
—
EEFPB2S2N
EEFPB3S2N
EEFPB4S2N
EEFPB5S2N
EEFPB6S2N
—
—
—
Full width for use with
double width interiors. With wiring trays for use with fusible
switches with accessories.
Single width bus covers and trim fillers
for use across from fusible switches for
six disconnect rule (SUSE) applications
—
EEFPB2T2
—
EEFPB4T2
—
EEFPB6T2
—
EEFPB8T2
EEFPB10T2
EEFPB12T2
—
EEFPS2S2W
EEFPS3S2W
EEFPS4S2W
EEFPS5S2W
EEFPS6S2W
—
—
—
—
—
EEFPS2S2N
EEFPS3S2N
EEFPS4S2N
EEFPS5S2N
EEFPS6S2N
—
—
—
—
2X filler is a 1X filler covering the left side and right side of a double bus interior.
Table 35. Type EE2 Fusible Switch Filler Plates
For use across from single width fusible switches in double bus panels.
“X” Factor
Catalog Number
1X
2X
3X
4X
5X
6X
7X
8X
10X
12X
EEFPS1S2
EEFPS2S2
EEFPS3S2
EEFPS4S2
EEFPS5S2
EEFPS6S2
EEFPS7S2
EEFPS8S2
—
—
2X filler is a 1X filler covering the left side and right side of a double bus interior.
20
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EP panelboards
Table 36. Type EP Door Kits and Three-Piece Trims Main
Amperes
Box Height in
Inches (mm)
Catalog Number
Door Kit
Three Piece Trim
Single Bus Panel—30.00-Inch (762.0 mm) Wide Box
800
800
800
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
EPT24SDC
EPT32SDC
EPT40SDC
EPT2430S
EPT3230S
EPT4030S
Double Bus Panel—42.00-Inch (1066.8 mm) Wide Box
1200
1200
1200
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
EPT24TDC
EPT32TDC
EPT40TDC
EPT2442S
EPT3242S
EPT4042S
Double Bus Panel—48.00-Inch (1219.2 mm) Wide Box
1200
1200
1200
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
EPT24TDC
EPT32TDC
EPT40TDC
EPT2448S
EPT3248S
EPT4048S
Door Kit
Three-Piece Trim
EATON CORPORATION www.eaton.com
21
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EE panelboards
Box
Trim
EE Panelboard
Nameplate
Blank Filler
Plate
Main Breaker
Single Width
Circuit
Breaker Unit
Double Width
Fusible
Switch Unit
Trim
EE Panelboards
22
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Branch circuit selection of EE units
Step 1: Select the correct branch circuit device.
When selecting, you need to know the following:
Step 2: Refer to the EE panelboard layout on page 22 to verify the
amount of X space available.
Step 3: Create an EE unit catalog number by following the
instructions on page 23.
Step 4: Determine if extra filler covers are required. Additional filler
covers may be necessary to fill the unused space. Refer
to page 27 for filler plate information.
•
Amperage
•
System voltage
•
Available short circuit rating
•
Number of poles
•
Size and number of wires per phase
•
X space required 1X = 1.38 inches (35.1 mm)
Table 37. Electrical Characteristics and X Space Requirements of Branch Circuit Breakers and Fusible Switches
Circuit
Breaker
Ampere
Rating
Number
of Poles
Maximum
Vac
UL Listed Interrupting Capacities — kA Symmetrical Amperes
DC Rating Volts AC Rating Volts
240
277
480
600
125
250
X Space
Required
EHD
15–100
15–100
1
2, 3
277
480
—
18
14
14
—
—
—
—
10
—
—
10
FDB
FD
FDC
15–225
15–225
15–225
15–225
15–225
15–225
2, 3
1
2, 3
1
2, 3
2, 3
600
277
600
277
600
600
18
—
65
—
100
200
—
25
—
—
—
—
14
—
25
65
65
100
14
—
18
—
25
35
—
10
—
10
—
—
10
—
10
—
22
22
ED
EDH
EDC
100–225
100–225
100–225
2, 3
2, 3
2, 3
240
240
240
65
100
200
—
—
—
—
—
—
—
—
—
10
10
10
—
—
—
JD, JDB
HJD
JDC
70–250
70–250
70–250
2, 3
2, 3
2, 3
600
600
600
65
100
200
—
—
—
35
65
100
18
25
35
—
—
—
10
22
22
DK
KD, KDB
HKD
KDC
250–400
100–400
100–400
100–400
2, 3
2, 3
2, 3
2, 3
240
600
600
600
65
65
100
200
—
—
—
—
—
35
65
100
—
25
35
50
—
—
—
—
10
10 22 22 4X
LCL
LD, LDB
HLD
LDC
100–400
125–400
300–600
300–600
2, 3
2, 3
2, 3
2, 3
600
600
600
600
200
65
100
200
—
—
—
—
200
35
65
100
—
25
35
50
—
—
—
—
—
22 25 25 6X
MDL
HMDL
ND
HND
NDC
300–600
300–800
600–1200
600–1200
600–1200
2, 3
2, 3
2, 3
2, 3
2, 3
600
600
600
600
600
65
100
65
100
200
—
—
—
—
—
50
65
35
65
100
25
35
25
35
50
—
—
—
—
—
22 25 —
—
—
12X HFD
3X
Fusible switches
Fusible switches are not available. Replace with circuit breaker units from above.
WARNING: Circuit breaker units will not fit across from a fusible switch or lug unit.
DC ratings apply to substantially non-inductive circuits.
DC ratings not available with electronic trip.
12X space requires a double bus panel only.
EATON CORPORATION www.eaton.com
23
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
“X” unit layout of circuit breaker and fusible switch units
1X = 1.38 inches (35.1 mm).
48.00 (1219.2)
42.00 (1066.8)
7.00
(177.8)
7.00
(177.8)
10" Gutter
Neutral – No "X" Factor
(May be at Bottom)
20X
10X 400A–600 A Main Switch
400A–600 A Branch Switch
10X
7X
14X
1200A Lug Unit
200A Branch Switch (600V with R Fusing)
7X
10X
20X
800A Main Switch
800A Branch Switch
10X
8X
600A
Branch
Lug Unit
6X
12X
MS, MH Branch Breaker
NS, NH Main Breaker
600A
Branch
Lug Unit
LS, LH
Breaker
6X
LS, LH
Breaker
200A Branch Switch
8X
6X
6X
600V – T Fuse Only
400A
Branch
Lug Unit
8X
100A
Branch
Switch
30A, 60A
Branch
Switch
5X
7X 240V – R & T Fuse
6X
CC, CCH, CCH
3X FS, FH, JS, JH, JL
4X
CC, CCH, CCH
FS, FH, JS, JH, JL 3X
KS, KH
Breaker
6X
KS, KH
Breaker
12X
MS, MH Main Breaker
4X
6X
10.00 (254.0) Gutter
10.00
(254.0)
10.00
(254.0)
Figure 2. “X” Unit Layout of Circuit Breaker and Fusible Switch Units—Dimensions in Inches (mm)
Main device must be mounted at the neutral end of double bus panel.
May be used in 30.00-inch (762.0 mm) wide single bus interiors.
Table 38. EE-Line Box Sizes and Maximum Component Unit Sizes—Dimensions in Inches (mm)
Box Width
and Bus
Type
Total “X”
Factor
Box
Height
Maximum Ampere of Plug-on Components
30.00 (762.0)
Wide
Single-Bus
24X
32X
40X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
800
42.00 (1066.8)
Wide
Double-Bus
48X
64X
80X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
1200 48.00 (1219.2)
Wide
Double-Bus
48X
64X
80X
64.00 (1625.6)
75.00 (1905.0)
86.00 (2184.4)
1200 Main Lugs
Branch Lugs
Branch
Breaker
Main Switch
Branch Fusible Switch
600
600
—
100A
600V
R Fuse
1200 Twin
400 Single
800 600
600 600
1200 Twin
600 Single
1200 800
800 800
600
Main
Breaker
200A
600V
J or T Fuse
200A
240V
R Fuse
Mains must be twin-mount types (over 8X space factor), and must be mounted on the neutral end of the panel. Smaller 4X or 6X breakers may be used as the main breaker when a 1200A lug unit is used to
tie across the double bus. The 1200A lug unit must be mounted at the neutral end with the main breaker adjacent to the lug unit.
24
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EE circuit breaker plug-on units
Type EE single plug-on unit
A plug-on unit for an EE panelboard is a complete assembly with a
circuit breaker and mounting adapter to mount on an EE panelboard.
Each single plug-on unit comes as a complete assembly with one
circuit breaker mounted to an adapter. Also included is the installation instructions.
Table 39. EE Circuit Breaker Plug-on Units
Frame
Ampere
Rating
Breaker
Frame
Trip Range
Mounting
Type
Space Required
Inches
(mm)
X Space
100
EHD
EHD
FDB
FDB
FD
FD
HFD
HFD
FDC
FDC
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
4.13 (104.9)
3X
225
FDB
FD
HFD
FDC
110–225
110–225
110–225
110–225
Single
Single
Single
Single
4.13 (104.9)
3X
ED
EDH
EDC
JD
HJD
JDC
100–225
100–225
100–225
70–225
70–225
70–225
Single
Single
Single
Single
Single
Single
250
JD
HJD
JDC
250
250
250
Single
Single
Single
4.13 (104.9)
3X
400
KD
HKD
KDC
100–400
100–400
100–400
Single
Single
Single
5.50 (139.7)
4X
LCL
125–400
Single
8.25 (209.6)
6X
600
LD
HLD
LDC
300–600
300–600
300–600
Single
Single
Single
8.25 (209.6)
6X
800
MDL
HMDL
400–800
400–800
Twin
Twin
8.25 (209.6)
12X
1200
ND
HND
NDC
600–1200
600–1200
600–1200
Twin
Twin
Twin
8.25 (209.6)
12X
Type EE Single Plug-on Unit
Table 40. How to Create an EE Circuit Breaker Plug-on Unit
Catalog Number
EE HNC 3 6 1200 A
Model
Type of Unit
A indicates EE
panelboard
Circuit Breaker
Type
Amperes
Number of Poles
Volts
Use all 4 characters
(i.e., 1200A = 1200)
2 = 240V
3 = 277V
4= 480V
6= 600V
EATON CORPORATION www.eaton.com
25
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Table 41. Neutral Assembly
Neutral assembly
Incoming Number of Cables and Wire Size
Catalog Number
Neutral Assemblies with Lugs
(4) 250–500 Kcmil Aluminum/Copper
(4) 250–500 Kcmil Copper Neutral
EEN08A
EEN08C
Neutral Lugs (Lugs only)
(4) 3/0–750 Kcmil Aluminum/Copper
EEN1200L
Type EE plug-on lug units are used as main lug only or sub-feed lugs
on EE panelboards. The plug-on unit comes as a complete assembly with lugs mounted to an adapter. Also included is a cover plate,
hardware, and installation instructions.
Table 42. Type EE Plug-on Lug Units
Neutral Assembly
Type EE plug-on lug units
Note: Branch Lug Units require overcurrent protection per NEC Article
#240-21.
Maximum
Amperes
“X”
Factor
Number of Cables/Phase and Wire
Size Aluminum/Copper
Catalog
Number
400 600 800
8X
8X
8X
(1) 1/0–500 Kcmil or (2) 1/0–250 Kcmil
(2) #4–500 Kcmil
(2) #2–500 Kcmil or (3) #4–400 Kcmil
EEL400S
EEL600S
EEL800S
(4) #4–500 Kcmil
EEL12T
Double Bus Panel
400–1200
14X
400A lug unit can also be used as a branch feeder in all panels and all box widths.
600A lug unit can be used as a branch feeder only in the 30.00-inch (762.0 mm) and 48.00-inch
(1219.2 mm) wide boxes.
Table 43. Grounding Kits
Description
Catalog Number
Equipment Ground Bar Kit
(2) #6–300 Kcmil, (8) #14–1/0 and (23) #14–#6
EEG12B
Ground Conductor Lug Only
(2) #6–250 Kcmil
Type EE Plug-on Lug Units
Grounding kits (for aluminum/copper wire)
Grounding Kits
26
EATON CORPORATION www.eaton.com
EEG12L
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Type EE filler plates
Table 44. Type EE Filler Plates
Blank filler for use opposite a fusible switch, lug unit or blank space.
“X” Factor
Catalog Number
1X
2X
3X
4X
5X
6X
EEP1S
EEP2S
EEP3S
EEP4S
—
EEP6S
Blank filler for use opposite a circuit breaker.
—
—
EEP3B
EEP4B
—
EEP6B
Two single bus filler plates are required for a double bus width opening.
EATON CORPORATION www.eaton.com
27
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
CDP, MP40, and NFB
26.50–36.00-inch (673.1–914.4 mm) wide panelboards
Chassis Rail
Chassis Bus
Breaker Mounting
Bracket
Breaker Mounting
Bracket
Copper Connectors
Upgraded Series C姞
Breaker
Original F-Frame
Breaker
Filler Plate
Filler Cover Mounting
Bracket
Filler Cover
Nameplate
MP40 Panelboard
28
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Branch circuit breaker selection
Step 2: Use the chart on page 30 to determine the space required.
Step 1: Select the correct breaker.
Step 3: Create the retrofit kit catalog number by following the
instructions on page 30.
When selecting a breaker, you need to know the following:
•
Amperage
•
System voltage
•
Available short circuit rating
•
Number of poles
•
Size and number of wires per phase
Step 4: Determine if extra filler covers are required. Additional filler
covers may be necessary to fill the unused space.
Table 45. Electrical Characteristics of Branch Circuit Breakers
Circuit Breaker
Type
Continuous
Ampere Rating
Number of
Poles
Vac
UL Listed Interrupting Capacities — kA Symmetrical Amperes
DC Rating Volts AC Rating Volts
240
277
480
600
125
250
FDC
15–100
15–100
100–225
100–225
15–225
15–225
15–225
15–225
15–225
15–225
15–225
1
2, 3
2, 3
2, 3
2, 3
2, 3
1
2, 3
1
2, 3
2, 3
277
480
240
240
240
600
277
600
277
600
600
—
18
65
100
200
18
—
65
—
100
200
14
—
—
—
—
—
25
—
65
—
—
—
14
—
—
—
14
—
25
—
65
100
—
—
—
—
—
14
—
18
—
25
35
10
—
—
—
—
—
10
—
10
—
—
—
10
10
10
10
10
—
10
—
22
22
CC CCH CHH 100–225
100–225
60–225
2, 3
2, 3
2, 3
240
240
240
10
25
100
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
JD, JDB
HJD
JDC
70–250
70–250
70–250
2, 3
2, 3
2, 3
600
600
600
65
100
200
—
—
—
35
65
100
18
25
35
—
—
—
10
22
22
DK
KD, KDB
HKD
KDC
250–400
100–400
100–400
100–400
2, 3
2, 3
2, 3
2, 3
600
600
600
600
65
65
100
200
—
—
—
—
—
35
65
100
—
25
35
50
—
—
—
—
10
10 22 22 LCL
125–400
2, 3
480
200
—
200
—
—
—
LD
HLD
LDC
300–600
300–600
300–600
2, 3
2, 3
2, 3
600
600
600
65
100
200
—
—
—
35
65
100
25
35
50
—
—
—
22 25 25 MDL
HMDL
300–800
300–800
2, 3
2, 3
600
600
65
100
—
—
50
65
25
35
—
—
22 25 ND
HND
NDC
600–1200
600–1200
600–1200
2, 3
2, 3
2, 3
600
600
600
65
100
200
—
—
—
35
65
100
25
35
50
—
—
—
—
—
—
EHD
ED
EDH
EDC
FDB
FD
HFD
DC ratings apply to substantially non-inductive circuits.
Not recommended for motor loads.
DC ratings not available with electronic trip.
EATON CORPORATION www.eaton.com
29
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
MP40 panelboards, CDP and NFB 26.50–
36.00 inches (673.1–914.4 mm) wide, MP2
switchboard chassis
Mounting
Type
Space Required
Inches
(mm)
X Space
Example: The retrofit kit catalog number for a 3-pole, 400A, KD
breaker is:
3X
Table 47. Catalog Numbering System
Table 46. MP40 Breaker Retrofit Kits
Breaker
Frame
Trip Range
EHD
EHD
FDB
FDB
FD
FD
HFD
HFD
FDC
FDC
FCL
FB-P
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
15–60
70–100
15–100
15–100
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
4.13 (104.9)
FDB
FD
HFD
FDC
110–225
110–225
110–225
110–225
Twin
Twin
Twin
Twin
4.13 (104.9)
225
ED
EDH
EDC
125–225
125–225
125–225
Twin
Twin
Twin
4.13 (104.9)
3X
250
JD
JD
HJD
HJD
JDC
JDC
70–225
250
70–225
250
70–225
250
Twin
Twin
Twin
Twin
Twin
Twin
4.13 (104.9)
3X
400
KD
HKD
KDC
100–400
100–400
100–400
Twin
Twin
Twin
5.50 (139.7)
4X
600
LD
HLD
LDC
300–600
300–600
300–600
Twin
Twin
Twin
8.25 (209.6)
6X
800
MDL
HMDL
400–800
400–800
Single
Single
8.25 (209.6)
6X
1200
ND
HND
NDC
600–1200
600–1200
600–1200
Single
Single
Single
8.25 (209.6)
6X
100
150
30
Use “KMP40” prefix and add the catalog number of the specific
breaker as shown in Table 47.
Twin mounting indicates that only one set of connectors is required
to mount two breakers (of similar frames) opposite one another.
A RETROFIT KIT INCLUDES ONE BREAKER ONLY, FOR EITHER
SINGLE OR TWIN MOUNTED APPLICATIONS. If a second breaker
is required for a twin mounting application, it must be specified as a
separate item.
A retrofit kit includes one breaker and all the associated parts
required for mounting on a MP40 or CDP panel chassis.
Frame
Ampere
Rating
How to create a retrofit kit catalog number
KMP40 KD 3 400
Designates MP40
Connector Kit
Ampere Rating
Breaker Frame
Number of
Poles
2 = 2-Pole
3 = 3-Pole
3X
MP40 retrofit kit
EATON CORPORATION www.eaton.com
Each kit includes one breaker, copper connectors, mounting brackets, covers, hardware, and instructions.
MP40 Retrofit Kit
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
MP40 panelboards, MP2 switchboard
chassis
A connector kit consists of copper connectors, mounting bracket
covers, hardware and instructions for mounting breaker(s) on a
MP40 or MP200 SWBD chassis. If breaker is also required, see
retrofit kits shown on page 30.
Connector kit
Each kit includes copper connectors, mounting brackets, covers,
hardware and instructions.
Table 48. MP40 Breaker Connector Kits
Maximum
Amperes
100
225
Breaker
Frames
Number
of
Poles
Mounting
Type
Space Required
Inches
(mm)
X
Space
EHD,
FDB, FD,
HFD, FDC
2
Twin
2.75
(69.9)
2X
MP40KF100-2
3
Twin
4.13
(104.9)
3X
MP40KF100-3
FDB, FD,
HFD,
FDC, ED,
EHD,
EDC
2
Twin
2.75
(69.9)
2X
MP40KF225-2
3
Twin
4.13
(104.9)
3X
MP40KF225-3
CC, CCH
2
Twin
2.75
(69.9)
2X
MP40KC225-2
3
Twin
4.13
(104.9)
3X
MP40KC225-3
2
Twin
2.75
(69.9)
2X
MP40KCHH225-2
3
Twin
4.13
(104.9)
3X
MP40KCHH225-3
CHH
Connector
Kit Catalog
Numbers
250
JD, JDB,
HJD,
JDC
3
Twin
4.13
(104.9)
3X
MP40KJ225-3
400
DK, KD,
KDB,
HKD,
KDC
3
Twin
5.50
(139.7)
4X
MP40KK400-3
600
LD, HLD,
LDC
3
Twin
8.25
(209.6)
6X
MP40KL600-3
400
LCL
3
Single
8.25
(209.6)
6X
MP40KLL400-3
800
MDL,
HMDL
3
Single
8.25
(209.6)
6X
MP40KM800-3
ND, HND,
NDC
3
Single
8.25
(209.6)
6X
1200
Connector Kit
Hardware kit
Each kit includes mounting bracket(s), filler plates and mounting
hardware ONLY. Use the appropriate connector kit catalog number
and add an “H” to designate hardware only.
Example: MP40KF100-3H
Hardware Kit
MP40 filler covers
Filler covers are available in any increment of 1X 1.38 inches (35.1
mm). Catalog number is: MP40FC-_ X. Fill in the blank with the size.
Included are cover, mounting brackets, and hardware.
MP40KN1200-3
Connector kits are not rated for 100 percent breakers.
MP40 Filler Covers
EATON CORPORATION www.eaton.com
31
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
MP100 panelboards, MP2 switchboard chassis
Nameplate
Extension Wings
Extension Wings
Copper
Connectors
Chassis Rail
Chassis Bus
Filter Cover
MP100 Panelboard
32
EATON CORPORATION www.eaton.com
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Branch M50 switch selection
MP100 filler covers
Step 1: Once you know the amperage and system voltage,
choose the retrofit kit catalog number from Table 49.
Filler covers are available in any increment of 1X 1.38 inches (35.1
mm). Catalog number is: MP100FC-_ X. Fill in the blank with the
size. Included are cover, mounting brackets and hardware.
Step 2: Check for space requirements from Table 49.
Step 3: Determine if extra filler covers are required. Additional filler
covers may be necessary to fill the unused space.
M50 Retrofit Kit
Each kit includes one switch, copper connectors, covers, hardware
and instructions.
MP100 Filler Covers
“Picture frame”
To permit installation of circuit breakers in a FDP panel, a “picture
frame” is required. Add 2X to the breaker size for transition.
Contact the Sumter plant for technical assistance and pricing
at 1-803-481-6843.
M50 Retrofit Kit
A retrofit kit includes one switch and all hardware to mount the
switch as branch devices only. For main switches, contact the
Aftermarket Product Center in Sumter, SC at 1-803-481-6843.
Switches through 600A are designed for use with rejection type
fuses. For other fuse applications, contact the Sumter Aftermarket
plant. Switches rated 800 and 1200A are designed for use with
Class L fuses. Fuses are not included.
Table 49. M50 Retrofit Kits
Switch
Ampere
Rating
Mounting
Type
Space Required
Catalog Number
Inches
(mm)
250
Volts
600
Volts
30/30
60/60
100/100
100/100
Twin
Twin
Twin
Twin
5.50 (139.7)
5.50 (139.7)
5.50 (139.7)
6.88 (174.8)
4X
4X
4X
5X
M50ATW3211R
M50ATW3222R
M50ATW3233R
—
M50ATW3611R
M50ATW3622R
—
M50ATW3633R
200
400
Single
Single
8.25 (209.6)
12.38 (314.5)
6X
9X
M50ASB324R
M50ASW325R
M50ASB364R
M50ASW365R
600
800 1200 Single
Single
Single
15.13 (384.3)
24.75 (628.7)
26.13 (663.7)
11X
18X
19X
M50ASW326R
Use 600V Kit
Use 600V Kit
M50ASW366R
M50ASW367_
M50ASW368_
X
Space
“Picture Frame”
800 and 1200A switches must be vertically mounted and located at the top or bottom of the
panelboard. Enter a “T” in the catalog number for top mounted or a “B” for bottom mounted.
EATON CORPORATION www.eaton.com
33
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
Breaker cross-reference chart
Panelboard trim locks
Table 50. Breaker Cross-Reference Chart
As panelboard trims have been redesigned over the years, so have
trim locks. Contact the Aftermarket Product Center in Sumter, SC for
availability on the styles listed below in Table 52 at 1-800-556-4569.
Obsolete Cutler-Hammer Circuit
Breaker Frame
Series C Replacement Circuit
Breaker Frame
EC
EHC
FS
FC
FH
EHD
FD
FD
FD
HFD
FL
JS
JH
JL
KS (A) 1
FDC
JD, JDB
HJD
JDC
KD, KDB
KH (A) 1
KS (D)
KH (D)
LS (A)
LS (E)
KD
KD, KDB
KD
LD
LD
LH (A)
LH (E)
LL (E)
LSB (E)
LH (E)
LD
LD
LDC
LD
HLD
MS
NS
MH
NH
MDL
ND
HMDL
ND
Table 52. Panelboard Trim Locks
Description
Catalog Number
For use on left-handed door (hinged on left side) WEN 1 key.
For use on right-handed door (hinged on right side) WEN 1 key.
K80522
K80133
T-Handle lock. At one time used on all trims over 48.00 inches (1219.2
mm) in height. Also used on outdoor (N3R) trims. WEM 1 key.
K80429
Used on lighting and small power panels as standard. WEM 2 key.
Used on lighting and small panels as standard.
1A32258H03
52-2751
K80522
K80429
K80133
The Series C K-Frame family of breakers requires a TAD3 adaptor kit when mounting a KD frame
breaker onto existing KS (A) connectors. This adaptor kit may be purchased separately for use with
existing LB or KS (A) connectors.
National Electrical Code and NEC are registered trademarks of the
National Fire Protection Association, Quincy, Mass. UL is a federally
registered trademark of Underwriters Laboratories Inc.
Panelboard trim clamps
Panelboard trims clamps. Contact the Aftermarket Product Center in
Sumter, SC for availability on styles listed below at 1-800-556-4569.
Table 51. Panelboard Trim Clamps
Description
Catalog Number
Used on MP40, PWW and all Door-on-Door trims.
Used on PB and PW trims.
99-970
99-1016
52-2751
99-970
99-1016
34
EATON CORPORATION www.eaton.com
1A32258H03
Vintage Cutler-Hammer
panelboards and switchboards
Renewal Parts RP01400003E
Effective February 2009
EATON CORPORATION www.eaton.com
35
Renewal Parts RP01400003E
Effective February 2009
Vintage Cutler-Hammer
panelboards and switchboards
Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2009 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. RP01400003E /Z8180
February 2009
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.