SNM SUPERVISED NOTIFICATION MODULE Figure 1: Connecting 2-Wire and 4-Wire Notification Circuits J2 Jumper Header Bell Silence Switch J2 Jumper Header Bell Silence Switch Trouble and Ground Fault LED's Trouble and Ground Fault LED's Aux. Power Aux. Power Ground Panel Common Alarm In Alarm In + Bell Power In + Bell Power In - Bell Power In Style Y - Bell Power In + Bell Out A - Bell Out B Not Used Style Z + Bell Out A - Bell Out A + Bell Out B Trouble and Ground 10k Ohm EOL Resistor - Bell Out B N/C Trouble Contacts N/C Trouble Contacts N/C Trouble Contacts N/C Trouble Contacts For both 2-wire and 4-wire appliances, connect a jumper between terminals 3 and 4 and between 2 and 5 when powering the notification appliance circuit from the control panel. Description The SNM provides Style Y or Z supervision for ground faults, opens, and shorts on notification appliance circuits connected to fire alarm control panels. The SNM is suitable for use with 2 or 4-wire circuits, and provides one Trouble and one Ground Fault LED and a set of Normally Closed trouble contacts to indicate off normal conditions. The SNM also provides a Bell Silence switch for use during testing or service. You can connect a maximum 5 Amp, 12 or 24 VDC UL listed auxiliary power supply to the module to support alarm power requirements beyond the panel's alarm output capacity. Installing the SNM Module You can install the SNM module in any of the panel enclosure's 3-hole mounting locations using the plastic standoffs provided. To install the module into the enclosure, follow the steps below: 1. Mount the plastic standoffs to the enclosure using the three included Phillips head screws. 2. Insert the screws from the outside of the enclosure through the holes and into the plastic standoff which mounts on the inside of the enclosure and tighten. 3. After the standoffs have been secured onto the enclosure, snap the module onto the standoffs. Wiring Refer to Figure 1 to properly connect 2-wire and 4-wire notification circuits to the Supervised Notification Module. Specifications Operating Voltage Terminal 1: 9.6 to 14.2 VDC Operating Current Terminal 1: 26mA Idle and 85mA Alarm Terminal 3: 33mA max Maximum Alarm Current Terminal 4: 5 Amps at up to 30 VDC when using appropriate UL listed power supply. Bell Silence Switch NORMAL: For normal operation. BELL SILENCE: For testing or service use. Trouble LED Lights during an open, short, or short- to-ground on the indicating circuit. Ground Fault LED Lights during a short-to-ground on the indicating circuit. J2 Jumper ON: For no alarm output with a ground fault condition (Style W and X). OFF: For uninterrupted alarm output with a ground fault condition (Style Y and Z). Circuit Styles One 2-wire Style W or Y indicat- ing circuit, or One 4-wire Style X or Z indicating circuit. Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8900111 - REV A 5/03 PAGE 1 OF 2 SNM SUPERVISED NOTIFICATION MODULE Installing The J2 Jumper Installing the J2 jumper provides for Style W (2-wire) and Style X (4-wire) circuits. The J2 jumper also disables the alarm bell output in the event of a ground fault on either side of the notification circuit. Do not install the J2 jumper for Style Y or Z circuits. Wiring Multiple Notification Circuit Modules Refer to the wiring diagram below to properly wire multiple Notification Circuit Modules. Figure 2: Connecting Multiple Modules J11 462N Network Interface Card J12 J3 J4 Tamper Header DD, MPX Selection Headers To additional 866 Notification Circuit Modules. All modules must be installed in an approved enclosure connected to the panel by conduit. Normal/Silence Switch 865 Module 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In + 5 Bell PWR In 6 Bell Out A + 7 Bell Out A 8 Bell Out B + 9 Bell Out B 10 Bell Trouble 11 Bell Trouble J2 Output Header J10 J16 Panel Reset AC AC +B 1 2 3 -B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 13 SNM Module 14 15 Z3 GND Z4 Z5 GND Z6 16 19 17 18 20 21 Z7 GND Z8 22 23 24 Z9+ Z9- Z10+ Z10- 25 26 27 28 Install the jumper on the J2 header to disable Bell Output during ground fault conditions. 10K EOL + The 865 Module is suitable for Style Y notification circuits, as shown in this diagram, and for Style Z notification circuits. The - Power Supply Module and Power Supply Trouble Zone To additional 866 Notification Circuit Modules. Normal/Silence Switch 865 Module 1 AUX PWR 2 GND 3 Alarm In 4 Bell PWR In + 5 Bell PWR In 6 Bell Out A + 7 Bell Out A 8 Bell Out B + 9 Bell Out B 10 Bell Trouble 11 Bell Trouble SNM Module Module and Power Supply Trouble Zone PRINTED IN USA 10K EOL + - Power Supply MKT. #8900111 - REV A 5/03 PAGE 2 OF 2