CMTCS_ Trip Circuit Supervision 1MRS752363-MUM Issued: 10/1997 Version: F/23.06.2005 Data subject to change without notice Contents 1. Introduction ................................................................................................ 2 1.1 Features................................................................................................ 2 1.2 Application ............................................................................................ 2 1.3 Input description ................................................................................... 3 1.4 Output description................................................................................. 3 2. Description of operation............................................................................ 4 2.1 Configuration ........................................................................................ 4 2.2 Operation criteria .................................................................................. 4 2.3 Alarm acknowledgement....................................................................... 6 2.4 Resetting............................................................................................... 6 3. Parameters and events .............................................................................. 7 3.1 General ................................................................................................. 7 3.2 Setting values ....................................................................................... 8 3.3 3.2.1 Actual settings ............................................................................. 8 3.2.2 Control settings............................................................................ 8 Measurement values............................................................................. 9 3.3.1 Input data..................................................................................... 9 3.3.2 Output data .................................................................................. 9 3.3.3 Events.......................................................................................... 9 4. Technical data .......................................................................................... 10 CMTCS_ Distribution Automation 1. Introduction 1.1 Features • The trip coil control and measuring circuits are continuously supervised regarding interruptions, and an alarm is issued in case of an interruption • In the RED 500 Platform, two trip output relays are provided with trip circuit supervision 1.2 Application This document specifies the functions of the trip circuit supervision function blocks CMTCS1 and CMTCS2 used in products based on the RED 500 Platform. The function blocks are identical in operation. The function block does not perform the supervision itself but it is used as an aid for configuration. The functional part belongs mainly to the self-supervision tasks of the PS_ card. Table 1 . Protection diagram symbols used in the relay terminal ABB IEC ANSI CMTCS_ TCS_ TCS_ For IEC symbols used in single line diagrams, refer to the manual “Technical Descriptions of Functions, Introduction”, 1MRS750528-MUM. Figure 1. Function block symbols of CMTCS1 and CMTCS2 2 CMTCS_ Distribution Automation 1.3 1.4 Input description Name TCSSTATE Type Digital signal (BOOL, active low) Description Trip circuit supervision state from I/O-card BS Digital signal (BOOL, active high) Blocking signal of the trip circuit supervision Output description Name ALARM Type Digital signal (BOOL, active high) Description Trip circuit supervision alarm 3 CMTCS_ Distribution Automation 2. Description of operation 2.1 Configuration The trip circuit supervision status signals from the PS1 card (TCS1 and TCS2) can be connected by means of the Relay Configuration Tool. The blocking signals can also be configured by the user with the configuration tool. 2.2 Operation criteria The trip circuit supervision is based on the constant current injection principle. If the resistance of the trip circuit exceeds a certain limit, e.g. because of loose contacts or oxidation, or if the OPEN contact has welded, the voltage over the OPEN contact falls below 20 V dc and the supervision function of the trip circuit is activated. The supervision state (TCS1 or TCS2) is logical TRUE when the trip circuit condition is OK and FALSE when a trip circuit fault has occurred. The TCSSTATE input is used for monitoring the supervision state. The function block includes a delay parameter that can be defined by the user. If the fault time exceeds the delay parameter time, the ALARM output of the function block is activated along with the respective notification on the MMI. The input/output circuits are galvanically isolated from each other. The constantcurrent generator forces a 1.5 mA measuring current through the circuit-breaker trip circuit. The constant current generator is connected over the trip contact of the circuit. The current generator for the TCS1 is connected to the terminals X4.1/12-13 and the current generator for the TCS2 to the terminals X4.1/17-18 of the RE_ 54_ terminal. Under no-fault conditions, the voltage over the contact of the constant current generator must be above 20 V ac/dc. Mathematically, the operating condition can be expressed as: Uc – (Rhext + Rhint + Rs) x Ic ≥ 20 V ac/dc where 4 Uc operating voltage over the supervised trip circuit Ic measuring current through the trip circuit, approximately 1.5 mA (0.99 ... 1.72 mA) Rhext external shunt resistor value Rhint internal shunt resistor value, 1 kΩ Rs trip coil resistance value CMTCS_ Distribution Automation The resistor Rhext must be so calculated that the trip circuit supervision current through the resistor is low enough not to influence the trip coil of the circuit breaker. On the other hand, the voltage drop over the resistor Rhext must be low enough not to jeopardize the operating condition presented in the formula above. The following values are recommended for the resistor Rhext in Figure 2 below: Operating voltage Uc 48 V dc Shunt resistor Rhext 1.2 kΩ, 5 W 60 V dc 5.6 kΩ, 5 W 110 V dc 22 kΩ, 5 W 220 V dc 33 kΩ, 5 W - Uc + TCS_ Ic 20 V Rh int 1 kW CMTCS_ A L M R A TCSSTATE ALARM BS Rh ext Rs TCSfunc Figure 2. Operating principle of the trip circuit supervision (TCS) function To avoid unnecessary alarms, the trip circuit supervision can be blocked by the BS signal, which makes it possible to disable the supervision output when the circuit breaker is withdrawn, i.e. when the four-pole status of both the circuit breaker and the circuit breaker truck is undefined. Moreover, to avoid unnecessary alarms, CMTCS_ should be blocked by the BS signal when a trip signal initiated by a protection function block is activated. The event E3 is not sent if the object is blocked in the initial condition (after reset). 5 CMTCS_ 2.3 Distribution Automation Alarm acknowledgement The ALARM output will reset automatically when the fault disappears or when the BS signal is activated. The user cannot reset the output without disabling the function. 2.4 Resetting The operation indications of the function block can be reset via the general parameter F001V011 or the push-button C on the front panel of the MMI, which both affect all function blocks. 6 CMTCS_ Distribution Automation 3. Parameters and events 3.1 General • Each function block has a specific channel number for serial communication parameters and events. The channel for CMTCS1 is 191 and that for CMTCS2 192. • The data direction of the parameters defines the use of each parameter as follows: Data direction R, R/M Description Read only W Write only R/W Read and write • The different event mask parameters (see section “Control settings”) affect the visibility of events on the MMI or on serial communication (LON or SPA) as follows: Event mask 1 (FxxxV101/102) SPA / MMI (LON) Event mask 2 (FxxxV103/104) LON Event mask 3 (FxxxV105/106) LON Event mask 4 (FxxxV107/108) LON For example, if only the events E3, E4 and E5 are to be seen on the MMI of the relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask 1” parameter (FxxxV101). In case a function block includes more than 32 events, there are two parameters instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A” (FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events 32...63. 7 CMTCS_ Distribution Automation 3.2 Setting values 3.2.1 Actual settings Parameter Code Values Unit Default Data Explanation direction Alarm delay S1 0...300.000 s 3 R/W Alarm delay Activation S2 0 or 1 1) 1 R/W Activation of TCS function Default Data Explanation 1) 3.2.2 Activation - 0 = Inactive; 1 = Active Control settings Parameter Code Values Unit direction Event mask 1 V101 0...15 - 10 R/W Event mask 1 for event transmission (E0 ... E3) Event mask 2 V103 0...15 - 10 R/W Event mask 2 for event transmission (E0 ... E3) Event mask 3 V105 0...15 - 10 R/W Event mask 3 for event transmission (E0 ... E3) Event mask 4 V107 0...15 - 10 R/W Event mask 4 for event transmission (E0 ... E3) 8 CMTCS_ Distribution Automation 3.3 Measurement values 3.3.1 Input data Parameter Code Values Unit Default Data Explanation direction BS state 1) 3.3.2 I2 Blocking signal 0 or 1 1) - 0 R/M Blocking signal state Data Explanation 0 = Inactive; 1 = Active Output data Parameter Code Values Unit Default direction Alarm state 1) 3.3.3 O1 Alarm state 0 or 1 1) - 0 R/M Alarm state 0 = Inactive; 1 = Active Events Code Weighting Default coefficient mask Event reason Event state E0 1 0 Trip circuit superv. 1 or 2 alarm Reset E1 2 1 Trip circuit superv. 1 or 2 alarm Activated E2 4 0 Trip circuit superv. 1 or 2 block Inactive E3 8 1 Trip circuit superv. 1 or 2 block Active 9 CMTCS_ 4. Distribution Automation Technical data Alarm delay accuracy The accuracy depends on the function block execution interval (that can be selected) and the setting value (whether the setting value is a multiple of the execution interval or not). The symbol “Tex” denotes the execution interval in ms. Alarm pulse delay: ± 2 % of set value or ±10 ms (if the delay is a multiple of the execution interval) ± 2 % of set value or 0...Tex±10 ms (if the delay is not a multiple of the execution interval) Configuration data Task execution interval (Relay Configuration Tool): 100 ms at the rated frequency fn = 50 Hz Technical revision history 10 Technical revision Change A - B -