Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. Analysis of a three-limb core power transformer under earth fault M. A. Tsili S. A. Papathanassiou Laboratory of Electric Machines and Power Electronics Electric Power Division, School of Electrical & Computer Engineering National Technical University of Athens (NTUA) 9, Iroon Polytechneiou Street, 15780 Athens, Greece tel: (+30)-210-7723658, fax: (+30)-210-7723593, e-mail: st@power.ece.ntua.gr ZL Abstract —In this paper, the zero sequence equivalent circuit is derived for three-limb core (“core-type”) YNyn0 3-phase power transformers, to take proper account of the low zerosequence magnetizing reactance and neutral earthing arrangements of the transformer. Subsequently the sequence component theory is applied to calculate the expected sequence and phase currents and voltages for a variety of unbalanced conditions, including single and double phase-toearth faults and open conductor situations. The results can provide the basis for the detection of zero-sequence flux conditions in the transformer, that may appear under certain unbalanced faults which remain undetected by the standard transformer protections. I. NOMENCLATURE Φk, k=a,b,c ep0 : Limb magnetic flux, phase k, : primary winding zero sequence internal EMF, es0 : secondary winding zero sequence internal EMF, Ip0 : primary winding zero sequence current, Is0 : secondary winding zero seq. current, Φlpk, k=a,b,c : leakage flux of primary winding phase k, Φlsk, k=a,b,c : leakage flux of sec. winding phase k, ZGP : primary neutral earthing impedance, ZGS : secondary neutral earthing impedance, ZG : substation earthing system impedance (resistance) to infinite earth, R lpk , k=a,b,c : reluctance of leakage flux path for phase k of primary winding, R lsk , k=a,b,c : reluctance of leakage flux path for phase k of secondary winding, : reluctance of phase k limb of the R k , k=a,b,c: magnetic core, : reluctance of zero-sequence flux (3Φ0) R0 path external to the core, Zp : primary series (short-circuit) impedance, Zs : secondary series (short-circuit) impedance., : zero-sequence magnetizing reactance, Z m0 N Up0 Us0 Rp Rs ZS ZTL ZT : : : : : : primary/secondary winding turns ratio, primary zero sequence terminal voltage secondary zero sequence terminal voltage primary winding resistance secondary winding resistance positive/negative sequence impedance of the system upstream the fault position, : positive/negative sequence impedance of the transmission line (fault to substation), : series (short-circuit) impedance of the transformer (positive sequence), ZS0 ZTL0 ZPO ZSO ZMO ZL0 Z Z0 : Positive/negative sequence impedance of the load (MV side), : zero sequence impedance of the system upstream the fault position, : zero sequence impedance of the transmission line (fault to substation), : primary series impedance of the zero sequence transformer equivalent circuit, : secondary series impedance of the zero sequence transformer equivalent circuit, : shunt impedance of the zero sequence transformer equivalent circuit, : zero sequence load impedance (MV side), : ZTL+ZT+ZL : ZTL0+ZT0+ZL0 II. INTRODUCTION Large high to medium voltage power transformers are vital and expensive components in electric power systems and accordingly high demands are imposed on the study of their behaviour and the implementation of suitable protections. Correct representation of the transformer under unbalanced operating conditions is crucial for the accurate calculation of fault currents, as well as for the selection and setting of appropriate transformer and network protection schemes. Although sequence transformer equivalents are widely available in the literature, these models do not always pay due attention to the type of the transformer magnetic core, which affects critically its apparent impedance in zerosequence conditions, [1,2]. It is a known fact that in coretype 3-phase power transformers, a high reluctance return path exists for zero-sequence flux, via the transformer tank surrounding the core, which results in low values of the zero-sequence magnetizing impedance, typically of the order of 50-150%. In the present paper, the zero sequence equivalent circuit is derived for a three-limb core YNyn0 3-phase power transformer, to take proper account of the low zerosequence magnetizing reactance, as well as of the neutral earthing arrangements. Subsequently the sequence component theory is applied to calculate the expected sequence and phase currents and voltages for a variety of unbalanced conditions, including single and double phaseto-earth faults and open conductor situations. Special emphasis is placed on the developed zero-sequence flux in the transformer. The results can provide the basis for the detection of zero-sequence flux conditions, that may appear under certain unbalanced faults which remain undetected by the standard transformer protections. The motivation for this work has been provided by a case of Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. severe transformer tank heating, following a permanent earth fault on the transmission line near the substation, which went undetected by the existing protections. III. DESCRIPTION OF THE STUDY-CASE SYSTEM A simplified single-line diagram of the studied system is shown in Fig. 1. It comprises a 150/21 kV YNyn0 transformer fed by an overhead 150 kV transmission line. Near the substation, one phase of the 150 kV line has been interrupted and the transformer side conductor has fallen on the ground, creating thus a combined phase-to-earth and open conductor fault. The event remained undetected by the transmission line and transformer protections, resulting in severe tank heating of the transformer, which was eventually tripped by the tank temperature protection. The system and transformer winding connections and earthing arrangements are shown in Fig. 1. The transformer under study is a 150/21 kV, 40/50 MVA (ONAN/ONAF), 3-limb core unit, shown in the pictures of Fig. 2. Both windings are Y-connected with neutrals grounded to the substation grounding system, directly at the HV side and via a 12 Ω/1000 A neutral resistor at the MV side. The distribution transformers (20/0.4 kV) connected to the 20 kV distribution network downstream the power transformer are all delta-connected at the 20 kV side (vector group Dyn11). Figure 2. The 150/20 kV, 40/50 MVA, “core-type” transformer. The main transformer protection relays are indicated in Fig. 1. Basic transformer protection is the differential protection (87T), trigerred by the difference of primary and secondary winding phase currents. A time over-current 400/150 kV autotransformer protection relay (51) serves as back up protection for the HV side. The MV side includes the secondary winding differential protection (Restricted Earth Fault-87REF), as well as low-set and high-set ground over-current relays (resp. EFL and EFH). Time-delayed over-current protection (51, 51N) is also used for the secondary breaker. IV. ZERO SEQUENCE EQUIVALENT CIRCUIT In the case of 5-limb core (“shell-type”) YY-connected transformers, zero sequence excitation in one winding results in negligible current, if the other winding is open circuited with respect to this sequence, due to the high magnetizing reactance of the iron core. However, 3-limb core (“core-type”) units differ fundamentally in this respect. The resulting zero-sequence flux path is now external to the core, via the insulating medium (oil), the tank and metallic connections other than the core, as shown schematically in Fig. 3. Due to the high reluctance of this path, the resulting zero-sequence magnetizing reactance of the transformer is low and therefore a significant zero-sequence current may result in the excited winding. To properly account for such situations, a proper zero-sequence equivalent circuit is required, which should also take into account the transformer and substation grounding arrangements. To derive such a circuit, the transformer representation of Fig. 3 is used, along with the respective magnetic equivalent circuit of Fig. 4. Zero sequence voltages are applied at the terminals of the primary winding, resulting in a zero sequence flux Φ0 per core limb. From the circuit of Fig.4 the following relations hold: N p i p0 − N s i s0 = φ0R a + 3φ0R 0 (1) N p i p0 = φlpaR a (2) N s is0 = −φlsaR a (3) Considering that the reluctance of the flux path external to the core is much higher than the reluctance of the core iron ( R 0 >> R a ), eq. (1) can be reduced to: N p i p0 − N s is0 = 3φ0R 0 (4) 150/20 kV substation DP LEGEND Transmission line fault 150 kV busbars O/C O/C EFH Voltage transformer Current transformer Circuit breaker (CB) Protection relay DP: Distance protection O/C: Over-current DIF: Differential REF: Restricted earth fault EFH: Earth fault - High EFL: Earth fault - Low Measurement C/B trip command EFL REF DIF Figure 1. Single line diagram of the system, including the main transformer protections. Alarm 20 kV busbars Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. 3φ0 Core Z GP 3(i p0-i s0 ) 3i p0 e+p0 3i s0 e+s0 φ0 φ0 i p0 - U Tank φ0 so ′ = -[Z ′ + 3N 2 Z − 3N(N − 1)Z ]I ′ s Gs G s0 ′ φlpa φlpb φlpc φlsa φlsb φlsc + (Z m0 + 3NZ G )(I p0 − I s0 ) i s0 - where Z s′ = Z GS ZG ⎛ N 2 ⎞⎟ ⎜ s + ω R j ⎟ is the secondary s R 2 ⎜ ⎜ N lsa ⎟ ⎠ ⎝ 1 winding series impedance referred to the primary turns. I p0 Figure 3. Three-phase core-type YNyn transformer under zero sequence conditions. Ra (9) φb φa φc Rb U p0 3φ0 Z P0 Rlpa Npipo Rlpb Npipo Nsiso Rlsa Nsiso Rlsb Nsiso Figure 5. Zero-sequence T equivalent circuit of a “core-type” YY connected transformer, referred to the primary winding. Rlpc Ro From eqs. (7) and (9), the zero-sequence equivalent circuit of Fig. 5 is readily derived. Its parameters are: (10) Z P0 = Z p + 3ZGP − 3( N − 1)Z G Rlsc 2 Z S0 = Z s + 3N Z GS Figure 4. Magnetic equivalent circuit for transformer of Fig. 3. With reference to Fig. 3, the voltage equation for phase a of the primary winding is the following, where capital letters are used for phasor notation in the following: U p0 = I p0 R p + E p0 + 3Z GP I p0 +3Z G (I p0 − I s0 ) (5) Using eqs. (1) and (4), the zero sequence voltage, Ep0, induced in the primary can be expressed as: d(φ0 + φlpa ) e po = N p ⇒ dt ⎡ N p I p0 − N s I s0 N p I po ⎤ E po = jωN p ⎢ + (6) ⎥ 3R 0 R lpa ⎥⎦ ⎢⎣ Combining eqs. (5) and (6), referring current Is0 to the primary winding turns and rearranging terms, it is eventually obtained: U = [ Z p + 3Ζ GP − 3(N − 1)Ζ G ]I p0 po ′ (7) + (Ζ m0 + 3NΖ G )(I p0 − I s0 ) where Zp= R + jω p U s0 Z M0 Rc Npipo N I s0 Z S0 2 p R lpa is the primary resistance plus N leakage impedance and Zm0= jω 2 p 3R 0 the zero-sequence magnetizing impedance. For the secondary winding, using the voltage equation: U s0 = I s0 Z s + E s0 − 3Z GS I s0 −3Z G (I p0 − I s0 ) (8) and working in the same way as for eq. (7), it is deduced: Z M0 − 3N(N − 1)ZG = Zm0 + 3NZG (11) (12) where the neutral and substation grounding impedances have been properly incorporated. Eqs. (7) and (9), along with the equivalent circuit of Fig. 5, can be per-unitized with the use of the primary and secondary winding base quantities. In case of transformers with on-load tap changers or fixed off-load tap positions, the OLTC position or the off-nominal turns ratio (ONR) must be taken into account ([3,4]). V. ANALYSIS OF UNBALANCED FAULTS To quantitatively analyse the fault conditions of the study-case system of Fig. 1, the sequence component theory can be applied, utilizing the established sequence equivalent circuits of the various system elements ([1,2,5]). In Fig. 6 the connection of the sequence equivalents is shown for the combined earth fault and open conductor situation, described in Section III. The various impedances are defined in Section I. Solving the sequence network equations permits the calculation of the voltages and currents at the various points of the network. For instance, the following expression is derived for the zero sequence voltage Uf0 at the point of the fault: U fo = − 3(Z + Z f )Z Es 0 [(Z + Z s )(3Z f + Z0 ) + (Z + Z f )(6Z0 + 4Zs0 ) (13) + 2Zs0 (Z0 + Z f ) + 2Z(Z0 + Z s )] Hence, the voltage along the shunt impedance, ZM0, which provides a measure of the zero-sequence flux in the transformer, is given by: Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. If Is1 Zs Is1 Zs If IT1 ZTL ZT Es 1:1 ZL IT2 Uf1 Es Is2 Zs ZTL ZT Zs0 Is0 ZTL ZP0 1:1 ZM0 ZL0 Figure 6. Connection of the sequence circuits for the study case fault (combined earth fault and open conductor conditions), [2]. f0 Z M0 Z m0 ⋅ Z 0 Z M0 (14) Es ZP0 ZS0 ZL0 ZM0 Z0 Es 2(Z 0 + Z s0 ) + (Z + Z s ) Interruption of two phases Z0 Es U fo = (Z 0 + Z s0 ) + 2(Z + Z s ) Single phase to ground fault Z ⋅ ( Z s0 //Z 0 ) Es U fo = (Z + Z )(Z s //Z + Z s0 //Z 0 + 3Z f ) + ZZ s U fo = ZT Is2 Zs IT2 ZL ZTL ZT Uf2 Is0 Zs0 ZTL IT0 Uf0 ZL ZP0 ZM0 ZS0 ZL0 (15) Figure 8. Connection of the sequence circuits for two open conductors (phases b and c). (16) VI. (17) s Double phase to ground fault ⎤ ⎡ ⎞ Z //Z 1 ⎛⎜ s0 0 ⎟ ⎥ ⎢ Z s ⎜ Z //Z + 3Z ⎟ ⎥ Es ⎢ s0 0 f ⎠ ⎝ =⎢ ⎥ 1 1 1 ⎥ ⎢ + + Z (Z//Z s ) //(Z0 //Z s0 + 3Z f ) ⎥ ⎢Z s ⎦ ⎣ IT1 ZTL Uf1 Interruption of one phase fo ZTL Connection of the sequence circuits for one open conductor (phase a). Is1 Zs To estimate the zero-sequence flux developed in the transformer under other possible unbalanced conditions, the same analysis has been conducted for other types of unsymmetrical faults, occurring at the same position along the HV in-feed line. Such are the single-phase and doublephase-to-ground faults and the interruption of one or two phases. The respective connections of the sequence equivalent circuits are shown in Figs. 7 to 10 and the relations for Uf0 are the following: U Zs0 Uf0 Figure 7. U m0 = U ZT ZL IT0 Uf0 ZS0 IT0 ZTL IT2 3Zf Uf2 If Is0 ZL Uf2 1:1 ZL ZT Uf1 If Is2 Zs IT1 ZTL (18) Eq. (14) can then be used to evaluate the zero sequence voltage and hence flux along the transformer shunt reactance. RESULTS AND DISCUSSION Eqs. (13) and (15)-(18) can be further simplified to derive practical rules of thumb regarding the expected zero sequence voltage magnitude. For the typical parameter values encountered in HV power systems, it holds in general that Zs<<ZTL<<ZT<<ZL and Zs0<<ZTL0<<ZT0<<ZL0. Hence, eq. (13) can be reduced to: Es (19) U fo = − 3 For typical HV/MV transformer parameters and fault position relatively close to the substation (small ZTL0), eq. (14) yields Umo ≈ 0.9Ufo. Therefore, in the case of the combined earth fault and open conductor situation, the zero sequence voltage along the transformer magnetizing impedance is approximately equal to 0.3 p.u., which is also a rough indication of the zero sequence flux per limb. Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. If Is1 Zs IT1 ZTL ZT Uf1 Es Typically Zs0 ≈ k Zs, with k=3÷6. For a mean value of k=4.5, Umo is eventually found ≈0.6 p.u. In the case of the double phase to ground fault, eq. (18) is reduced to: 0.5Z s0 Es (23) U fo = Z s0 + 0.5Z s If ZL If Is2 Zs IT2 ZTL ZT Uf2 Is0 Zs0 3Zf ZL If ZTL ZP0 ZS0 IT0 Uf0 ZL0 ZM0 which results in Umo approximately equal to 0.4 p.u. More accurate results regarding the currents and voltages in the system are easily derived by solving the sequence networks for each fault. For instance, for the combined earth fault and open conductor situation of Section III, the results are shown in Fig. 11, where the phasors of HV and MV side voltages and currents are illustrated. Initially the transformer operates with a 30 MVA, 0.9 ind. p.f. load. The calculated magnetizing branch zero sequence voltage Um0 is equal to 26.95 kV. Notable, the approximate solution of the previous Section resulted in Um0 ≈0.3 p.u. i.e. 0.3⋅(150/√3)=26 kV, very close to the actual value. Figure 9. Connection of the sequence circuits for a single phase to ground fault. If Is1 Zs If IT1 ZTL ZT Uf1 Es Is2 Zs ZL IT2 ZTL ZT Uf2 Is0 ZL Zs0 ZTL ZP0 3Zf ZS0 IT0 Uf0 ZM0 ZL0 Figure 10. Connection of the sequence circuits for a double phase to ground fault. Following a similar line of reasoning, the simplified equation for Ufo, in case of interruption of one phase, is: Z0 (20) U fo = Es 2Z + Z 0 Taking into account that Z ≈ Z0, Ufo is then approximately equal to 0.33 p.u. and Um0 approximately equal to 0.3 p.u. For two open conductors, Ufo is given by: Z0 (21) U fo = Es Z + 2Z 0 which also results in Um0 ≈ 0.3 p.u. For the single phase to ground fault, eq. (17) can be reduced to: Z s0 Es (22) U fo = 2Z s + Z s0 Figure 11. Phasor diagram of the phase voltages (in kV) and currents (in kA) after the occurrence of the fault. The results of Fig. 11 correspond to distance of the fault from the substation equal to 0.5 km. In order to examine the impact of the fault distance on Um0 and thus on the zero sequence flux, the calculations have been repeated for greater lengths of the transmission line Paper presented at the 16th International Conference on Electrical Machines, ICEM 2004, Cracow, Poland, September 5-8, 2004. between the fault position and the substation. Fig. 12 illustrates the calculated variation of Umo with respect to the fault-to-substation distance, for the five cases of unbalanced conditions examined in the previous Section. In Tables I and II, the resulting voltages Ufo and Umo are presented for the loaded and unloaded transformer, again for the same five types of unsymmetrical conditions. TABLE I TRANSFORMER ZERO SEQUENCE VOLTAGE FOR DIFFERENT TYPES OF UNSYMMETRICAL CONDITIONS (LOAD 30 MVA, PF=0.9 IND.) Fault Uf0 (kV) Um0 (kV) Earth fault and one open phase One open phase Two open phases Phase to ground fault Double phase to ground fault 29.26 29.55 26.67 63.62 40.9 26.95 27.23 24.53 58.61 37.68 Umo (kV) TABLE II TRANSFORMER ZERO SEQUENCE VOLTAGE FOR DIFFERENT TYPES OF UNSYMMETRICAL CONDITIONS (UNLOADED TRANSFORMER) Fault Uf0 (kV) Um0 (kV) Earth fault and one open phase One open phase Two open phases Phase to ground fault Double phase to ground fault 29.45 0.24 0.12 63.87 41.11 27.14 0.22 0.11 58.84 37.87 [2] [3] [4] [5] 20 40 60 80 CONCLUSIONS In this paper, the zero sequence equivalent circuit of a core-type 3-phase YNyn power transformer is derived, taking into account the core structure and the winding earthing arrangements. The equivalent circuit is then applied for the analysis of various unsymmetrical operating conditions. The analysis was prompted by an incident where an unbalanced fault, which remained undetected by the system and transformer protections, resulted in severe tank heating of the transformer due to the zero sequence flux circulating through the tank. The analysis is focused on the zero sequence voltage and hence flux in the transformer and can serve as the basis for the elaboration and implementation of a suitable protection. [1] REFERENCES P. M. Anderson, Analysis of Faulted Power Systems. IEEE Press, 1995 Electrical Transmission and Distribution Reference Book, Westinghouse Electric Corporation, 1964. S. A. Papathanassiou, “Modeling Transformers with OffNominal Ratios for Unbalanced Conditions,” IEEE Power Eng. Review, pp. 50-52, Feb. 2002. L. V. Barboza, H. H. Zurn, R. Salgado, “Load Tap Change Transformers: A Modeling Reminder,” IEEE Power Eng. Review, pp. 51-52, Feb. 2001. P. Kundur, Power System Stability and Control. McGraw Hill, 1994. 100 Distance of substation from the postion of the fault (km) earth fault and one open phase one open phase two open phases phase to ground fault double phase to ground fault Figure 12. Variation of Umo with the fault-to-substation distance for various types of unsymmetrical conditions. Comparing the results shown in Tables I and II leads to the following conclusions: ii) VII. VIII. 65 60 55 50 45 40 35 30 25 20 15 0 i) provide a low reluctance return path for the flux. When significant load exists, the closed secondary winding forces the zero sequence flux to partially follow paths external to the core. The Umo magnitudes for the other kinds of faults are similar as for the case of the loaded transformer. iii) The values of Table I (loaded transformer) are very close to the simplified estimations of Um0 provided in Section V. For a loaded transformer, the greatest values of Umo occur in the case of single and double phase to ground faults. Open conductors result in similar and relatively lower values. Under low load conditions, zero sequence voltage and therefore flux in the transformer is negligible in case of single- or two-phase supply. This is expected because the core limbs of the interrupted phases IX. APPENDIX: PARAMETER VALUES The system short-circuit capacity at the point of the fault is 3200 MVA and the X/R ratio is equal to 7. The distance from the substation to the point of the fault is 0.5 km. The other parameters of the study case system have the following values: 0Ω ZGP = ZGS = 12 Ω ZG = 0.5 Ω Zm0 = 540j Ω ZS = 0.994+6.961j Ω ZTL = 0.097+0.391j Ω/km ZT = 90j Ω ZL = 675+326.92j Ω ZS0 = 5.779+34.678j Ω ZTL0 = 0.497+2.349j Ω/km