11kV - 3 Phase Star System, with Neutral Point Earthed. Theoretical Voltage Calculations and Explanation of using the Live Line Tester to measure Resultant Phase to Earth Voltage, and to determine the In Phase and Out of Phase Voltage relationships 3 Phase Star Diagram, with Neutral Point Earthed. Resultant Phase to Earth Voltage Red Phase to Phase (R-Y) = 11kV Phase to Earth (Y-E) = 11kV / √3 (√3 = 1.7320508) Ph to E (Y-E) = 11kV / 1.7320508 Ph to E (Y-E) = 6.35kV Phase to Phase (R-Y) = 11kV Cos 30 = 5.5kV / (Y-E) Ph to E (Cos 30 = 0.866) Ph to E (Y-E) = 5.5kV / 0.866 Ph to E (Y-E) = 6.35kV 11kV 120° E 90° 5.5kV 30° Yellow Blue 3 Phase Star Diagram For 11kV System Phase to Earth Voltage = 6.35kV For 6.6kV System Phase to Earth Voltage = 3.81kV 11kV Tester Showing Scale 0-15kV and Front Cover with Phasing Information The table on the front of the 11kV Tester details the In-Phase and Out of Phase Voltages expected on an 11kV System and on a 6.6kV System. From the Scale the In-Phase and Out of Phase Voltages can be easily measured Phase to Earth Fig.13- Phasing Connections The previous diagrams show how connections are made to the systems under test. Phase to Earth Current passes through the resistor rod and meter to Earth, this current is displayed on the meter as a Voltage Fig 13 – Phasing Connections The current passing through the Phasing Rod is led into the Tester on the right by means of the Phasing Lead which screws into the handle of the phasing Rod and into the back of the Tester housing (remove blanking plug). The Tester is Earthed as usual, and connected to the phases as shown. If the two lines are in phase the currents through each resistor rod are in phase, consequently twice normal current will pass through the Tester on the right. If the phasing is incorrect, the currents are 120° out of phase, the vector sum being equivalent to normal deflection between one phase and earth. Correct Phasing is thus shown on the Tester by an indication of twice the normal line/earth voltage and the Incorrect Phasing is thus shown on the Tester by an indication of normal line/earth voltage. Phase to Earth and Phase to Phase Voltages - when using a Live Line Tester Theory diagram for the LLT