Miniature Circuit Breakers
and Residual Current Devices
SGB Series
Miniature Circuit Breaker
Technical data
Standard
Breaking capacity
Protection
Rated current In
Rated voltage
Confirming to EN / IEC60898-1
6 kA
Against overload and short circuit
0.5, 1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63A
1pole 230/400V AC 50/60Hz
2, 3, 4 pole 400V AC 50/60Hz
Rated insulation voltage Ui: 500V
Rated impulse withstand voltage Uimp: 6000V
Energy limiting class: 3
-5 °C to +40 °C pursuant to EN / IEC60898
Thermal operating limit: (1.13-1.45) x In
Magnetic operating:B: (3-5) x In
C: (5-10) x In
D: (10-20) x In
1P, 1P+N, 2P, 3P, 3P+N and 4P
Thermal / magnetic release
Lug type and Pin type
16mm2 flexible or 25mm2 rigid up to 25A ratings
25mm2 flexible or 35mm2 rigid for 32A to 63A ratings
IP20
Mounting on 35mm DIN rail
17.5mm per pole/module
Ambient temperature
Characteristic
Number of poles
Type of trip
Type of terminal
Terminal capacity
Protection degree
Installation
Width
Approvals:
B - Trip characteristics
Product code
Product name
C - Trip characteristics
Package
qty.
€/pcs.
Product code
Product name
Package
qty.
€/pcs.
3735610600
WEDIN MCB 1-POLE B 6A
12
3,20 €
3735610610
WEDIN MCB 1-POLE C 6 A
12
3,20 €
3735611000
WEDIN MCB 1-POLE B 10A
12
3,00 €
3735611010
WEDIN MCB 1-POLE C 10 A
12
3,00 €
3735611600
WEDIN MCB 1-POLE B 16 A
12
3,00 €
3735611610
WEDIN MCB 1-POLE C 16 A
12
3,00 €
3735612000
WEDIN MCB 1-POLE B 20 A
12
3,00 €
3735612010
WEDIN MCB 1-POLE C 20 A
12
3,00 €
3735612500
WEDIN MCB 1-POLE B 25 A
12
3,00 €
3735612510
WEDIN MCB 1-POLE C 25 A
12
3,00 €
3735631000
WEDIN MCB 3-POLE B 10 A
4
9,00 €
3735613210
WEDIN MCB 1-POLE C 32 A
12
3,00 €
3735631600
WEDIN MCB 3-POLE B 16 A
4
9,00 €
3735614010
WEDIN MCB 1-POLE C 40 A
12
3,00 €
3735632000
WEDIN MCB 3-POLE B 20 A
4
9,00 €
3735615010
WEDIN MCB 1-POLE C 50 A
12
3,30 €
3735632500
WEDIN MCB 3-POLE B 25 A
4
9,00 €
3735616310
WEDIN MCB 1-POLE C 63 A
12
3,30 €
3735633200
WEDIN MCB 3-POLE B 32 A
4
9,00 €
3735631010
WEDIN MCB 3-POLE C 10 A
4
9,00 €
3735631610
WEDIN MCB 3-POLE C 16 A
4
9,00 €
3735632010
WEDIN MCB 3-POLE C 20 A
4
9,00 €
3735632510
WEDIN MCB 3-POLE C 25 A
4
9,00 €
3735633210
WEDIN MCB 3-POLE C 32 A
4
9,00 €
3735634010
WEDIN MCB 3-POLE C 40 A
4
9,00 €
3735635010
WEDIN MCB 3-POLE C 50 A
4
9,60 €
3735636310
WEDIN MCB 3-POLE C 63 A
4
9,60 €
2
more than you expect
2. Endurance(operations)
Category
Operations
Operation frequency
Rated current (A)
Electrical endurance
4000
240/h
0.5~32
120/h
40~63
240/h
0.5~63
Mechanical endurance
10000
3. Please refer to the table below for temperature compensation correction
ln A
Temperature compensation coefficient under various operational temperatures
-10°C
0°C
10°C
20°C
30°C
40°C
50°C
55°C
60°C
0.5~6
1.20
1.14
1.09
1.05
1.00
0.96
0.80
0.75
0.70
10~32
1.18
1.12
1.08
1.04
1.00
0.96
0.92
0.88
0.84
40~63
1.16
1.12
1.08
1.03
1.00
0.9
0.87
0.83
0.80
4. Wiring
The suitable conductors should be used for connection, see table for relative parameters.
Rated current In(A)
Nominal cross section area (mm2)
Tightening torque (Nm)
0.5~6
10
1
2
1.5
2
13, 16, 20
2.5
2
25
4
2
32
6
2
40, 50
10
2
63
16
2
5. Overall and mounting dimensions
3
SGR Series
Residual Current Circuit Breaker
Technical data
Standard
Rated conditional short-circuit current, Inc
Protection
Rated current, In
Number of poles
Rated sensitivity currents, I△n
Charasteristic
Rated residual non-operating current
Rated impulse withstand voltage Uimp
Rated voltages
2-pole
4-pole
Ambient temperature
Residual current off-time at I △n
Rated residual current making & breaking
capacity, I△m
Type of terminal
Terminal capacity
Protection degree
Width
Installation
Confirming to EN / IEC61008-1
6 kA
Ground fault
16, 25, 32, 40, 63, 80, 100, 125A
2(1+N), 4(3+N)
10, 30, 100, 300 mA
A-type
0.5 X I △n
6000V
230VAC
230/400VAC
-25°C~+45°C, Max. 95% humidity
≤ 0.1s
500A for In=16, 25, 32, 40A
630A for In=63, 80, 100, 125A
Lug type and Pin type
Cables up to 35mm2
IP20
2 or 4 modules
35mm DIN rail
Approvals:
Product code
Product name
Package qty.
€/pcs.
4735624000
4735644000
WEDIN RCCB 2-POLE 40 A, 30 mA
1
26,45 €
WEDIN RCCB 4-POLE 40 A, 30 mA
1
32,00 €
4
more than you expect
1. Life
Operating cycles
In
Operating frequency
(operations/h)
On-load operating cycles
Off-load operating cycles
16, 25, 32
2000
2000
240
40, 63, 80, 100, 125
2000
1000
120
2. Breaking time of residual current
Breaking time of residual current
In (A)
IΔn(A)
IΔn
2IΔn
5IΔn
5A, 10A, 20A, 50A
100A, 200A, 500A
16, 25, 32, 40, 63, 80, 100, 125
0.01, 0.03, 0.1, 0.3
0.1s
0.08s
0.04s
0.04s
Max.Breaking time
3. Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
2
Rated current ln (A)
Nominal cross section area of lead (mm )
Tightening torque (Nm)
16
2.5
2.5
25
4
2.5
32
6
2.5
40
10
2.5
63
16
2.5
80
25
2.5
100
35
2.5
125
35
2.5
4. Overall and mounting dimensions
SGR
5
SGRM Series
Residual Current Operated Circuit Breaker (RCBO)
Technical data
EN / IEC 61009 -1
6 kA
Ground fault, overcurrent and short circuit
3, 6, 10, 16, 20, 25, 32, 40A
10, 30, 100, 300 mA
B-, C-curve; A type
500A
Standard
Breaking capacity
Protection
Rated current, In
Operating, I△n
Characteristic
Rated residual current operated making &
breaking capacity I△m
Rated residual non-operated current I△no
Rated impulse withstand voltage Uimp
Number of poles
Rated voltage
Ambient temperature
Residual current off-time
Protection degree
Terminal capacity
Installation
Width
Type of terminal
0.5 I△n
4000V
1P+N
230VAC
-25°C~+45oC, Max. 95% humidity
≤ 0.1 sec.
IP20
10mm2 flexible/16mm2 rigid
35mm DIN rail
2 modules
Lug type and Pin type
Approvals:
Product code
Product name
Package qty.
€/pcs.
5735621000
5735621600
WEDIN RCBO MAGN. 2-POLE B 10 A, 30 mA
1
33,30 €
WEDIN RCBO MAGN. 2-POLE B 16 A, 30 mA
1
33,30 €
5735621010
WEDIN RCBO MAGN. 2-POLE C 10 A, 30 mA
1
33,30 €
5735621610
WEDIN RCBO MAGN. 2-POLE C 16 A, 30 mA
1
33,30 €
6
more than you expect
1. Curves
2. Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
Rated current In (A)
Cross section area S (mm2)
Tightening torque (Nm)
3~6
1
2
10
1.5
2
16~20
2.5
2
25
4
2
32
6
2
40
10
2
3. Types
Type A :For which tripping is ensued for residual sinusoidal alternating currents and residual pulsating direct currents,
whether suddenly applied or slowly rising.
4. Tripping sensitivity data
RCD with a rated residual current of maximum 30 mA are used for personnel,material and fire protection, as well as for protection
against direct contact.
RCD with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults.
RCD with a rated residual current of 100 mA co-ordinated with the earth system according to the formula IΔn<50/R, to provide
protection again indirect contacts.
5. Overall and mounting dimensions
7
SGBR Series (electronic)
Residual Current Operated Circuit Breaker (RCBO)
Technical data
Standard
Breaking Capacity
Number of poles
Rated currents
Rated voltage
Rated Tripping Current
Residual current off time
Characteristic
Electrical endurance
Mechanical endurance
Ambient temperature
Connection terminal
EN / IEC61009
6 kA
1P+N(1 module)
6, 10, 16, 20, 25, 32, 40, 50A
230VAC
10mA, 30mA, 100mA
≤0.1s
B-, C-curve; A-type
10000
20000
-25°C~+45°C, Max. 95% humidity
Flexible conductor 16mm2
Rigid conductor 25mm2
Lug type and Pin type
17.8mm /module
Type of terminal
Width
Approvals:
Product code
Product name
Package qty.
€/pcs.
5735621011
WEDIN RCBO EL. 2-POLE, C 10 A, 30 mA
1
31,45 €
5735621611
WEDIN RCBO EL. 2-POLE, C 16 A, 30 mA
1
31,45 €
8
more than you expect
1. Curves
2. Breaking time of residual current
In (A)
IΔn (A)
6~50
0.01,0.03,0.1
Max. Breaking times
IΔn
2IΔn
5IΔn
5A, 10A, 20A, 50A, 100A, 200A, 500A
0.1s
0.08s
0.04s
0.04s
3. Wiring
The suitable conductors should be used for connection,see table below for relative parameters.
Rated current In (A)
Cross section area S (mm2)
Tightening torque (Nm)
6
1
2
10
1.5
2
16~20
2.5
2
25
4
2
32
6
2
40
10
2
50
16
2
4. Overall and mounting dimensions
SGBR6K
9
SGI series
Isolating switch
Technical data
Standard
EN / IEC60947-3
Number of poles
1P, 2P, 3P, 4P
Rated currents
16, 20, 25, 32, 40, 50, 63, 80, 100, 125A
Rated voltage
1pole 230/400V AC 50/60Hz
2, 3, 4 pole 400V AC 50/60Hz
Utilization category
AC-22A
Icw
12le, t=0.1s
Rated short-circuit making capacity Icn
20le, t=0.1s
Rated making & breaking capacity
3le, 1.05Ue, COSφ=0.65
Rated insulation voltage Ui
690V
Rated impulse withstand voltage Uimp
4000V
Electrical endurance
1500
Mechanical endurance
10000
Type of terminal
Lug type and Pin type
Terminal capacity
Cables up to 50mm2
Ambient temperature (°C)
-25~+45, Max.95% humidity
-40~+75
Storage temperature (°C)
Max. 2,000
Altitude (meters)
Protection degree
IP20
Installation
Mounting on 35mm DIN rail
Width
17.8mm per pole/module
Approvals:
Product code
Product name
Package qty.
€/pcs.
6735613200
WEDIN MODULAR ISOLATING SWITCH 1-POLE 32 A
12
2,90 €
6735633200
WEDIN MODULAR ISOLATING SWITCH 3-POLE 32 A
4
8,70 €
6735636300
WEDIN MODULAR ISOLATING SWITCH 3-POLE 63 A
4
9,30 €
6735631000
WEDIN MODULAR ISOLATING SWITCH 3-POLE 100 A
4
9,90 €
10
more than you expect
1. Endurance(operations)
Category
Operations
Operation frequency
Rated current
Electric endurance
1500
120/h
16~125A
Mechanical endurance
10000
120/h
16~125A
2. Wiring
The suitable conductors should be used for connection, see table below for relative parameters.
Rated current In (A)
Cross section area S (mm2)
Tightening torque (Nm)
16
2.5
2.5
20
2.5
2.5
25
4
2.5
32
6
2.5
40
10
2.5
50
10
2.5
63
16
2.5
80
35
3.5
100
35
3.5
125
50
3.5
3. Overall and mounting dimensions
SGI
11
SGBA series
Auxiliary contacts
Technical data
Standard
Confirming to EN / IEC 60947-5-1
Rated insulation voltage
Ui 500V
Rated voltage
230 VAC, 400 VAC, 24 VDC, 48 VDC
Rated frequency(Hz)
50/60Hz
Utilization catagory
AC14, AC15
Ambient temperature(°)
-5°...+40° Max 95% humidity
Storage temprature(°)
-40°...+75°
Electric endurance
30000
Mechanical endurance
40000
Dielectric strength
2000V/1min
Protection degree
IP20
Approvals:
+
Product code
Product name
3735000010
+
+
+
Package qty.
€/pcs.
WEDIN OF AUXILIARY CONTACT
17
3,90 €
3735000020
WEDIN SD ALARM CONTACT
17
4,45 €
3735000030
WEDIN MX SHUNT TRIP
9
8,75 €
3735000040
WEDIN MN VOLTAGE TRIP
9
8,75 €
12
more than you expect
Application
Applicable to MCB model SGB,used to control remote signaling device.
+
+
Combination scheme
OF
SGB
OF
OF
SGB
MX
OF Auxiliary Contact
OF
Rated voltage (V)
Rated current (A)
230 AC
6
400 AC
3
24 DC
6
48 DC
2
Electro-mechanical endurance: ≥5000
Mounted on the left side of the MCB SGB6K, indicating "ON", "OFF"
status of combined MCB.
MX Shunt Tripper
MX
Rated insulating voltage(Ui):500V
Operate voltage range: 70~100% Us
Contact capacity: AC:3A/400V, AC:6A/230V, AC:9A/125V
Electro-mechanical endurance: ≥4000
Mounting on the right side of MCB, used to trip the MCB by
remote controlling device.
13
Application
Applicable to MCB model SGB6K, used to control remote signaling device.
+
+
Combination scheme
SD
SGB
SD
SD
SGB MN
SD Alarm Switch
SD
Rated voltage (V)
Rated current (A)
230 AC
6
400 AC
3
24 DC
6
48 DC
2
Rated insulating voltage (Ui): 500V
Operate voltage range: 70~100% Us
Electro-mechanical endurance: ≥4000
Is used to connect ON/OFF auxiliary contact, work as circuit breaker
ON/OFF indicator in case of faulty (tripping)
MN Over-voltage/Under-voltage Tripper
Rated voltage (V)
MN
230 AC
Rated insulating voltage (Ui): 500V
Over-voltage tripping range: 280V± 5%
Under-voltage tripping range: 170V± 5%
Electro-mechanical endurance: ≥4000
Mounted on the right side of circuit breaker, actuate the combined device to
trip in case of under-voltage or over-voltage, effectively prevent the device
from closing operation under abnormal power voltage condition.
14
more than you expect
Accessories
Technical data
Standard
Confirming to IEC664
Rated insulation
500V
Electric ratings
32A, 63A, 80A, 100A, 125A
Type of terminal
Pin type and Fork type
Number of poles
1P, 1P+N, 2P, 3P, 4P
Approvals:
Product code
Product name
Package qty.
€/pcs.
3735116310
WEDIN INSUL. BUS BAR NEEDLE 1-p. 63A 1m
10
6,85 €
3735136310
3735216310
WEDIN INSUL. BUS BAR NEEDLE 3-p. 63A 1m
6
20,60 €
WEDIN INSULATED BUS BAR, U-MODE, 1-p. 63 A, 1m
10
9,45 €
3735236310
WEDIN INSULATED BUS BAR, U-MODE, 3-p. 63 A, 1m
6
20,90 €
15
more than you expect
Mechanical and electronics products
also available for purchase from
Würth Elektronik oy
Würth Elektronik Oy • Karhutie 4 • 01900 Nurmijärvi, Finland • Tel +358 10 308 4700 • Fax +358 10 308 4701
myynti@wurthelektronik.fi
16• www.wurthelektronik.fi
Related documents
Download