DISTRIBUTION PROTECTION OVERVIEW Mike Diedesch & Kevin Damron– Avista Utilities Presented March 12, 2011 At the 29th Annual HANDS-ON Relay School Washington State University Pullman, Washington 1 Table of Contents System Overview ………………………………………………………....… 3 Distribution (3-30MVA ) Transformer Protection ………………….…..…... 14 Relay Overcurrent Curves …………………………………………..……. 22 Symmetrical Components ……………………………………………..…….. 8 Distribution Fuse Protection ………………………………………….……. 24 Conductors ………………..………..………………………………………. 28 Electromechanical Relays used on Distribution Feeders…………….…….… 31 Coordinating Time Intervals …………………………………………….… 36 Transformer Relay Settings using Electromechanical Relays ………….…… 48 IEEE Device Designations …………………………………………….…….. 51 Transformer & Feeder Protection using Microprocessor Relays ………….… 52 Transformer Differential Protection ……………………………………….… 61 Moscow 13.8kV Feeder Coordination Example ……………………………. 64 2 System Overview - Distribution Protection Objective: Protect people (company personnel and the public) and equipment by the proper application of overcurrent protective devices. Devices include: Relays operating to trip (open) circuit breakers or circuit switchers, and/or fuses blowing for the occurrence of electrical faults on the distribution system. Design tools used: 1 – Transformer and conductor damage curves, 2 - Time-current coordination curves (TCC’s), fuse curves, and relay overcurrent elements based on symmetrical components of fault current. Documentation: 1 - One-line diagrams and Schematics with standardized device designations as defined by the IEEE (Institute of Electrical and Electronics Engineers) – keeps everyone on the same page in understanding how the system works. 2 - TCC’s 3 System Overview – Inside the Substation Fence 115 kV SYSTEM MOSCOW A-172 XFMR 12/16/20 MVA 115/13.8kV HIGH LEAD LOW DELTA/WYE 13.8 kV BUS 500A, 13.8 kV FDR #515 Feeder relay Transformer relays #4 ACSR 556 ACSR PT-2A PT-1 PT-2B PT-3B 500 A FDR #2 ACSR 556 ACSR 3Ø = 3699 SLG = 3060 #2 ACSR 1 PHASE #4 ACSR PT-3A 2/0 ACSR PT-3C PT-4 3Ø = 1210 SLG = 877 3Ø = 3453 SLG = 2762 LINE RECLOSER P584 PT-5 #4 ACSR 1 PHASE #4 ACSR 13.8 kV FDR #512 3Ø = 5158 SLG = 5346 3Ø = 558 SLG = 463 3Ø = 1907 SLG = 1492 PT-6A FUSE 3-250 KVA WYE/WYE PT-6B #4 ACSR PT-6C #4 ACSR PT-8 65T 3Ø = 322 SLG = 271 4 PT-7 System Overview – Outside the Substation Fence 115 kV SYSTEM MOSCOW A-172 XFMR 12/16/20 MVA 115/13.8kV Midline recloser relay HIGH LEAD LOW DELTA/WYE 13.8 kV BUS 500A, 13.8 kV FDR #515 #4 ACSR 556 ACSR PT-2A PT-1 PT-2B PT-3B 500 A FDR #2 ACSR 556 ACSR 3Ø = 3699 SLG = 3060 #2 ACSR 1 PHASE #4 ACSR PT-3A 2/0 ACSR PT-3C PT-4 3Ø = 1210 SLG = 877 3Ø = 3453 SLG = 2762 LINE RECLOSER P584 PT-5 #4 ACSR 1 PHASE #4 ACSR 13.8 kV FDR #512 3Ø = 5158 SLG = 5346 3Ø = 558 SLG = 463 3Ø = 1907 SLG = 1492 PT-6A FUSE 3-250 KVA WYE/WYE PT-6B #4 ACSR PT-6C #4 ACSR PT-8 65T 3Ø = 322 SLG = 271 PT-7 5 115 kV SYSTEM MOSCOW System Overview – A-172 XFMR 12/16/20 MVA 115/13.8kV Each device has at least one curve plotted with current and time values on the Time Coordination Curve. HIGH LEAD LOW DELTA/WYE 13.8 kV BUS 1000 10 2 3 4 5 7 100 2 5 3 700 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 4 500 500 400 400 6 300 200 300 A. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 200 FEEDER 252 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 70 70 50 50 40 40 30 30 TRANSFORMER PROTECTION HI-SIDE CT'S 20 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 S E C O N D S 500A, 13.8 kV FDR #515 1000 #4 ACSR 556 ACSR PT-2A #2 ACSR PT-3B 2 STATION VCB 252 PROTECTION 5 PT-3C PT-4 3Ø = 1210 SLG = 877 3Ø = 3453 SLG = 2762 LINE RECLOSER P584 PT-5 5 FUSE 4 1 3 3 3. IDR 252 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 2 B 5f #4 ACSR 2 MAXIMUM FEEDER FUSE 4. 252 140T FUSE stn S&C Link140T Total clear. Ia= 5665.9A T= 0.09s MIDLINE OCR 1 .7 .5 1 FAULT DESCRIPTION: Bus Fault on: 0 IDR 252 13.8 kV 3LG .7 .5 5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s .4 .3 .2 1 PHASE #4 ACSR 2/0 ACSR 7 2. IDR 252 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s Ia= 5665.9A (35.4 sec A) T= 0.30s 4 500 A FDR #2 ACSR PT-3A 10 7 PT-2B 13.8 kV FDR #512 3Ø = 5158 SLG = 5346 556 ACSR 3Ø = 3699 SLG = 3060 20 10 PT-1 1 PHASE #4 ACSR PT-6A #4 ACSR PT-6C .3 .2 6. T FUSE S&C Link 50T Minimum melt. Ia= 5665.9A T= 0.01s .1 .1 A .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 3-250 KVA WYE/WYE PT-6B .4 MAXIMUM MIDLINE FUSE 3Ø = 558 SLG = 463 3Ø = 1907 SLG = 1492 #4 ACSR PT-8 65T 3Ø = 322 SLG = 271 PT-7 Fault I=5665.9 A .01 10 2 HORS 2010 For 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 JDH No. Date 11-25-2008 7 .01 6 System Overview – 1000 10 2 3 4 5 7 100 2 5 3 700 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 400 400 6 300 200 300 A. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 200 FEEDER 252 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 70 70 50 50 40 40 30 30 20 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 20 10 10 7 2 STATION VCB 252 PROTECTION 5 Protective Curves: - relay - fuse 5 4 1 3 3 3. IDR 252 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 2 Damage Curves: - transformer - conductor 7 2. IDR 252 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s Ia= 5665.9A (35.4 sec A) T= 0.30s 4 What are the types of curves? 700 4 500 S E C O N D S 1000 B 5f 2 So, what curve goes where? MAXIMUM FEEDER FUSE 4. 252 140T FUSE stn S&C Link140T Total clear. Ia= 5665.9A T= 0.09s MIDLINE OCR 1 .7 .5 13.8 kV 3LG .7 .5 5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s .4 .3 .2 1 FAULT DESCRIPTION: Bus Fault on: 0 IDR 252 .4 Damage curves are at the top and to the right of the TCC. .3 MAXIMUM MIDLINE FUSE .2 6. T FUSE S&C Link 50T Minimum melt. Ia= 5665.9A T= 0.01s .1 .1 A .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 Protective curves lowest and to the left on the TCC correspond to those devices farther from the substation where the fault current is less. Fault I=5665.9 A .01 10 2 HORS 2010 For 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 JDH No. Date 11-25-2008 7 .01 7 Transformer Protection - Damage Curve – ANSI/IEEE C57.109-1985 Avista has Category III size (5-30MVA) Distribution Transformers in service per the above standard. The main damage curve line shows only the thermal effect from transformer through-fault currents. It is graphed from data entered below (MVA, Base Amps, %Z ): 1000 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 1000 700 700 500 500 400 400 300 300 200 200 A. T ransf. damage c urve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. 100 The dog leg on the curve is added to allow for additional thermal and mechanical damage from (typically more than 5) through-faults over the life of a transformer serving overhead feeders. Time at 50% of the maximum per-unit through fault current = 8 seconds. 100 70 70 50 50 40 40 30 30 20 20 S 10 E C O 7 N D 5 S 4 10 7 5 4 3 3 A 2 1 1 .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 .1 .1 .07 .07 .05 Dog leg curve - 10 times base current at 2 seconds. .05 1 .04 .04 .03 .03 .02 .02 .01 Main curve - 25 times base current at 2 seconds. 2 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) T IME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 No. Comment Date .01 1. M15 CT R= By For 7 8 Conductor Damage Curves Copper Conductor Damage Curves (2/0 damage at 1500A @ 100sec.) 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 ACSR Conductor Damage Curves (2/0 damage at 900A @ 100sec.) 2 3 4 5 7 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 1000 1000 1000 700 700 500 400 300 500 400 300 200 200 200 200 100 100 100 100 70 70 70 70 50 40 30 50 40 30 50 40 30 50 40 30 20 20 20 20 S 10 E C 7 O 5 N 4 D 3 S 10 S 10 E C 7 O 5 N 4 D 3 S 1000 1. M15-515 Phase INST INST TD=1.000 CTR=160 Pickup=7.A No inst. TP@5=0.048s 700 500 400 300 7 A. Conductor damage curve. k=0.14040 A=105500.0 cmils Conductor Copper (bare) AWG Size 2/0 2/0 Copper 5 4 3 B. Conductor damage curve. k=0.14040 A=83690.0 cmils Conductor Copper (bare) AWG Size 1/0 1/0 Copper 2 1 2 1 C. Conductor damage curve. k=0.14040 A=52630.0 cmils Conductor Copper (bare) AWG Size 2 #2 Copper .7 .5 .4 .3 .7 .5 .4 .3 D. Conductor damage curve. k=0.14040 A=33100.0 cmils Conductor Copper (bare) AWG Size 4 #4 Copper .2 .2 E. Conductor damage curve. k=0.14040 A=20820.0 cmils .1 Conductor Copper (bare) AWG Size 6 #6 Copper .07 .05 .04 .03 E D C .1 B A .07 .05 .04 .03 1 .02 .02 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) 2 3 4 5 7 10000 2 3 4 5 7 .01 Comment Copper Conductor Damage Curves By DLH No. Date 12/13/05 500 400 300 10 7 5 4 3 B. Conductor damage curve. k=0.08620 A=167800.0 cmils Conductor ACSR AWG Size 4/0 4/0 ACSR 2 C. Conductor damage curve. k=0.08620 A=105500.0 cmils Conductor ACSR AWG Size 2/0 2/0 ACSR 1 .7 1 .7 D. Conductor damage curve. k=0.08620 A=83690.0 cmils Conductor ACSR AWG Size 1/0 1/0 ACSR .5 .4 .3 .5 .4 .3 E. Conductor damage curve. k=0.08620 A=52630.0 cmils Conductor ACSR AWG Size 2 #2 ACSR .2 .2 F. Conductor damage curve. k=0.08620 A=33100.0 cmils Conductor ACSR AWG Size 4 #4 ACSR .1 .07 .05 .04 .03 F E DC A.1 B .07 .05 .04 .03 1 .02 .02 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) 2 3 4 5 7 TIME-CURRENT CURVES @Voltage 13.8 kV TIME-CURRENT CURVES @Voltage 13.8 kV For 700 A. Conductor damage curve. k=0.08620 A=355107.0 cmils Conductor ACSR 336.4 ACSR 2 .01 .01 1. M15-515 Phase INST INST TD=1.000 CTR=160 Pickup=7.A No inst. TP@5=0.048s For Comment ACSR Conductor Damage Curves 10000 2 3 4 5 By 7 .01 DLH No. Date 12/13/05 9 Conductor Ampacities Conductor at 25°C ambient taken from the Westinghouse Transmission & Distribution book. Copper Ampacity Ratings ACSR Ampacity Ratings Conductor 556 336.4 4/0 2/0 1/0 #2 #4 Rating 730 530 340 270 230 180 140 Conductor Rating 2/0 1/0 #2 #4 #6 360 310 230 170 120 10 Conductor Protection Graph 1000 10 2 3 4 5 7 100 2 700 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 1 500 500 400 400 300 300 200 200 100 100 1. Moscow 515 Kear 140T Kearney 140T Total clear. 70 70 50 50 40 30 20 20 10 10 7 7 5 5 4 4 3 3 2 2 1 1 .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 A .1 .1 .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 #4 ACSR & 140T For Comment Aspen File: HORS M15 EXP.olr 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 3 @ Voltage 13.8 kV 4 5 7 10000 Comparing a 140T fuse versus a #4 ACSR Damage curve. The 140T won’t protect the conductor below about 550 amps where the curves cross. 40 A. Conductor damage curve. k=0.08620 A=33100.0 cmils Conductor ACSR AWG Size 4 30 S E C O N D S 1000 2 3 By 4 5 Protection No. Date 3/06 7 .01 11 Transformer Protection using 115 kV Fuses 12 1000 Transformer Protection using 115 kV Fuses 10 2 3 4 5 7 100 2 3 4 700 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 2 500 500 400 400 300 300 6 A. Transf. damage curve. 7.50 MVA. Category 3 Base I=313.78 A. Z= 7.3 percent. Rockford 13.8kV - ROCKFORD115 115.kV 1 T 200 Used at smaller substations up to 7.5 MVA transformer due to low cost of protection. Other advantages are: - Low maintenance - Panel house & station battery not required 100 70 70 50 5 40 40 30 30 STATION TRANSFORMER PROTECTION 20 There are also several disadvantages to using fuses however which are: • Low interrupting rating from 1,200A (for some older models) up to 10,000A at 115 kV. By contrast a circuit switcher can have a rating of 25KAIC and our breakers have normally 40KAIC. • The fuses we generally use are rated to blow within 5 minutes at twice their nameplate rating. Thus, a 65 amp fuse will blow at 130 amps. This compromises the amount of overload we can carry in an emergency and still provide good sensitivity for faults. 200 100 50 S E C O N D S 1000 4 20 2. SMD-2B 65E VERY SLOW 176-19-065 Minimum melt. H=8.33 FEEDER VCR PROTECTION 10 10 4. LAT RP4211 51P CO-11 CO-11 TD=2.000 CTR=500/5 Pickup=3.A No inst. TP@5=0.5043s 7 5 7 5 5. LAT RP4211 51N CO-11 CO-11 TD=4.000 CTR=500/5 Pickup=2.A No inst. TP@5=1.0192s 4 3 3. LAT RP4211 50P CO-11 INST TD=1.000 CTR=500/5 Pickup=3.5A No inst. TP@5=0.048s 2 1. LAT RP4211 50N CO-11 INST TD=1.000 CTR=500/5 Pickup=2.A No inst. TP@5=0.048s 4 3 A 2 MAXIMUM FEEDER FUSE 1 1 6. LAT RP4211 FUSE S&C Link 65T Total clear. .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 .1 .1 .07 .07 .05 1 .05 3 .04 .04 .03 .03 .02 .02 .01 10 2 ROK 451R2 For 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES ROK FDR 451, BUS FAULTS: 3LG=3580A, SLG=3782A, L-L=3100A Comment ASPEN FILE: ROK NEW XFMR (2005 BASE).OLR 2 3 @ Voltage 13.8 KV 4 5 7 10000 2 3 By 4 5 JDH No. Date 2-13-07 13 7 .01 Transformer Protection using 115 kV Fuses - continued • The fuse time current characteristic (TCC) is fixed (although you can buy a standard, slow or very slow speed ratio which are different inverse curves). • The sensitivity to detect lo-side SLG faults isn’t as good as using a relay on a circuit switcher or breaker. This is because we use DELTA/WYE connected transformers so the phase current on the 115 kV is reduced by the √3 as opposed to a three phase fault. • Some fuses can be damaged and then blow later at some high load point. • When only one 115 kV fuse blows, it subjects the customer to low distribution voltages. For example the phase to neutral distribution voltages on two phases on the 13.8 kV become 50% of normal. A a 1.0 PU B 0.5 PU 0.5 PU C b c • No indication of faulted zone (transformer, bus or feeder). 14 Transformer Protection using a Circuit Switcher Showing Avista’s present standard using Microprocessor relays. 13.8kV 115kV 15 Transformer Protection using a Circuit Switcher Showing Avista’s old standard using Electromechanical relays. 16 Transformer Protection using a Circuit Switcher 1000 Some advantages to this over fuses are: • Higher interrupting. • Relays can be set to operate faster and with better sensitivity than fuses. • Three phase operation. • Provide better coordination with downstream devices. 10 2 3 4 5 7 100 2 3 700 4 5 7 1000 3 4 5 7 10000 2 3 4 5 7 500 500 400 400 200 300 A. Conductor damage curve. k=0.08620 A=133100.0 cmils Conductor ACSR AWG Size 2/0 200 FEEDER 251 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 300 70 70 50 50 40 40 30 20 S E C O N D S 1000 700 11 10 7 5 4 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33 2. IDR A-777 51G 351 SEL-VI TD=1.000 CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33 4. IDR A-777 51Q 351 SEL-EI TD=4.200 CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33 LO-SIDE CT'S 3. IDR A-777 51N 351 SEL-EI TD=5.700 CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s 30 3 5 4 9 20 10 10 7 7 5 4 1 2 3 Some disadvantages would be: • Higher cost. • Higher maintenance. • Requires a substation battery, panel house and relaying. • Transformer requires CT’s. 2 3 5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300 CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s 2 B 2 STATION VCB 251 PROTECTION 1 1 7. IDR 251 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s .7 .7 6. IDR 251 50P 351S INST TD=1.000 CTR=800/5 Pickup=7.A No inst. TP@5=0.048s .5 .5 .4 .4 9. IDR 251 51G 351S SEL-EI TD=3.900 CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s .3 .2 .3 .2 8. IDR 251 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 10. IDR 251 51Q 351S SEL-EI TD=3.500 CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s .1 A .1 .07 .07 .05 .04 MAXIMUM FEEDER FUSE MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 8 .05 6 .04 11. 251 140T FUSE stn S&C Link140T Total clear. .03 .03 .02 .02 .01 10 2 3 IDR FEEDER 251 For 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 7 .01 JDH No. Date 11-25-2008 17 Transformer Protection using a Breaker This is very similar to using a circuit switcher with a couple of advantages such as: • Higher interrupting – 40kAIC for the one shown below. • Somewhat faster tripping than a circuit switcher (3 cycles vs. 6 – 8 cycles). • Possibly less maintenance than a circuit switcher. • The CT’s would be located on the breaker so it would interrupt faults on the bus section up to the transformer plus the transformer high side bushings. 18 Relay Overcurrent Curves 1000 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 500 500 400 400 300 300 200 200 100 100 1 70 50 70 50 1. EXTREMELY INVERSE SEL-EI TD=15.000 CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s 40 40 30 20 5 5. VERY INVERSE SEL-VI TD=6.000 CTR=800/5 Pickup=6.A No inst. TP@5=1.5478s 2 10 10 7 7 5 5 2. INVERSE SEL-I TD=2.000 CTR=800/5 Pickup=6.A No inst. TP@5=0.8558s 4 The five curves shown here have the same pickup settings , but different time dial settings. 4 3 3 2 2 3 3. MODERATELY INVERSE SEL-2xx-MI TD=1.000 CTR=800/5 Pickup=6.A No inst. TP@5=0.324s 1 1 These are basically the same as various E-M relays. .7 .7 .5 .5 4 .4 .4 .3 .3 .2 .2 4. SHORT TIME INVERSE SEL-STI TD=1.000 CTR=800/5 Pickup=6.A No inst. TP@5=0.1072s .1 .1 .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 SEL Various Relay Overcurrent Curves. Extremely Inverse – steepest Very Inverse Inverse Moderately Inverse Short Time Inverse – least steep 30 20 S E C O N D S 1000 700 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 Avista uses mostly extremely inverse on feeders to match the fuse curves. .01 By For No. Comment Date 19 Relay Overcurrent Curves - Pickups & Time Dials Pickup - the current at which the relay will operate to trip the breaker. - also known as “tap” from the electromechanical relay days -expressed in terms of the ratio of the current transformer (CTR) that the relay is connected to, - e.g., a relay with a CTR of 120 and a pickup (or tap) of 4 will operate to trip the breaker at 480 amps 1000 10 2 3 4 5 7 100 2 3 700 Time dial - at what time delay will the relay operate to trip the breaker - the larger time dial means more time delay - also known as “lever” from the electromechanical relay days - Instantaneous elements have a “time dial” of 1 and operate at 0.05 seconds. - Instantaneous curves are shown as a flat horizontal line starting at the left at the pickup value and plotted at 0.05 seconds. 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 500 400 400 300 200 300 A. Conductor damage curve. k=0.08620 A=133100.0 cmils Conductor ACSR AWG Size 2/0 200 FEEDER 251 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 70 70 50 50 40 30 20 S E C O N D S 1000 700 11 10 7 5 4 40 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33 2. IDR A-777 51G 351 SEL-VI TD=1.000 CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33 4. IDR A-777 51Q 351 SEL-EI TD=4.200 CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33 LO-SIDE CT'S 3. IDR A-777 51N 351 SEL-EI TD=5.700 CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s 30 3 5 4 9 20 10 10 7 7 5 4 1 2 3 3 5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300 CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s 2 B 2 STATION VCB 251 PROTECTION 1 1 7. IDR 251 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s .7 .7 6. IDR 251 50P 351S INST TD=1.000 CTR=800/5 Pickup=7.A No inst. TP@5=0.048s .5 .5 .4 .4 9. IDR 251 51G 351S SEL-EI TD=3.900 CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s .3 .2 .3 .2 8. IDR 251 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 10. IDR 251 51Q 351S SEL-EI TD=3.500 CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s .1 A .1 .07 .05 .04 .07 MAXIMUM FEEDER FUSE MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 8 .05 6 .04 11. 251 140T FUSE stn S&C Link140T Total clear. .03 .03 .02 .01 .02 10 2 3 IDR FEEDER 251 For 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 7 .01 JDH No. Date 11-25-2008 20 Relay Overcurrent Curves - Example of Different Pickup & Time Dial Settings Same Time Dial = 9 Right curve picks up at 960 Amps Left curve picks up at 320Amps 1000 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 Same Pickup = 960 Amps Top curve Time Dial = 15 Bottom curve Time Dial = 2 3 4 5 7 10 2 3 4 5 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 1000 700 700 700 500 500 500 500 400 400 400 400 300 300 300 300 200 200 200 200 100 100 70 70 50 50 40 40 30 30 20 20 1. EXT INV 1 SEL-EI TD=9.000 CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s 100 70 2. ~EXT INV 1 SEL-EI TD=9.000 CTR=800/5 Pickup=5.A No inst. TP@5=2.4431s 50 5 40 30 4 3 2 1 3. ~EXT INV 2 SEL-EI TD=9.000 CTR=800/5 Pickup=4.A No inst. TP@5=2.4431s 20 1. EXT INV 1 SEL-EI TD=15.000 CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s 10 7 5. ~EXT INV 4 SEL-EI TD=9.000 CTR=800/5 Pickup=2.A No inst. TP@5=2.4431s 5 70 2 2. ~EXT INV 1 SEL-EI TD=12.000 CTR=800/5 Pickup=6.A No inst. TP@5=3.2574s 50 3 40 30 4 3. ~EXT INV 2 SEL-EI TD=9.000 CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s 20 4. ~EXT INV 3 SEL-EI TD=6.000 CTR=800/5 Pickup=6.A No inst. TP@5=1.6287s 10 7 1000 100 1 4. ~EXT INV 3 SEL-EI TD=9.000 CTR=800/5 Pickup=3.A No inst. TP@5=2.4431s S E C O N D S 7 1000 700 5 S E C O N D S 10 10 5 7 7 5. ~EXT INV 4 SEL-EI TD=2.000 CTR=800/5 Pickup=6.A No inst. TP@5=0.5429s 5 5 4 4 4 4 3 3 3 3 2 2 2 2 1 1 1 1 .7 .7 .7 .7 .5 .5 .5 .5 .4 .4 .4 .4 .3 .3 .3 .3 .2 .2 .2 .2 .1 .1 .1 .1 .07 .07 .07 .07 .05 .05 .05 .05 .04 .04 .04 .04 .03 .03 .03 .03 .02 .02 .02 .02 .01 .01 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 10 By 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 .01 By For No. For No. Comment Date Comment Date 21 1000 10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 1000 700 A. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.4 percent. INDIAN TRAIL 12/16/20 MVA XFMR 500 400 500 400 300 300 B. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 556 kCMil AAC 200 200 100 100 70 70 50 50 TRANSFORMER PROTECTION 40 40 1 1. INT A-742 51P 351 SEL-VI TD=10.000 CTR=600/5 Pickup=0.8A No inst. TP@5=2.5797s H=8.33 30 30 20 20 Transformer relay curves 5 5. INT A-742 51G 351 SEL-VI TD=5.000 CTR=600/5 Pickup=0.8A No inst. TP@5=1.2898s H=8.33 S 10 E C 7 O N D 5 S 4 10 6 7 6. INT A-742 51Q 351 SEL-VI TD=3.000 CTR=600/5 Pickup=0.8A No inst. TP@5=0.7739s H=8.33 2 51P – phase time overcurrent 51N or 51G – ground time overcurrent 5 4 3 2 Microprocessor relays have different types of curves based on the type of fault current being measured: 3 3 STATION VCB 12F1 PROTECTION 2. INT 12F1 51P 351S SEL-VI TD=1.800 CTR=800/5 Pickup=3.A No inst. TP@5=0.4643s A 51Q – negative sequence time overcurrent 2 4 1 1 .7 .7 3. INT 12F1 51G 351S SEL-VI TD=0.900 CTR=800/5 Pickup=3.A No inst. TP@5=0.2322s .5 .5 .4 .4 .3 .3 4. INT 12F1 51Q 351S SEL-VI TD=0.500 CTR=800/5 Pickup=3.A No inst. TP@5=0.129s .2 Feeder relay curves 51P – phase time overcurrent .2 51N or 51G – ground time overcurrent .1 .1 B .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 10 INT 12F1 For 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Indian Trail feeder 12F1 in INT 2007base.olr Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 7 51Q – negative sequence time overcurrent This brings us to a brief discussion of: .01 JDH No. Date 1-29-08 22 Symmetrical Components Symmetrical Components for Power Systems Engineering, J. Lewis Blackburn, There are three sets of independent components in a three-phase system: positive, negative and zero for both current and voltage. Positive sequence voltages (Figure 1) are supplied by generators within the system and are always present. A second set of balanced phasors are also equal in magnitude and displaced 120 degrees apart, but display a counter-clockwise rotation sequence of A-C-B (Figure 2), which represents a negative sequence. The final set of balanced phasors is equal in magnitude and in phase with each other, however since there is no rotation sequence (Figure 3) this is known as a zero sequence. 23 Symmetrical Components Examples of three 13.8kV faults showing the current distribution through a Delta-Wye high-lead-low transformer bank : Three phase (3LG) fault - Positive sequence currents – for setting phase elements in relays. Phase -Phase (L-L) fault - Negative sequence currents – for setting negative sequence elements in relays. Single phase (1LG or SLG) fault - Zero sequence currents – for setting ground elements in relays. Symmetrical Components Notation: Positive Sequence current = I + = I1 Negative Sequence current = I - = I2 Zero Sequence current = I 0 = I0 Phase Current notation: IA – High side Amps Ia – Low side Amps Phasor diagram from Fault-study Software. 8.33= 115/13.8 = transformer Voltage (turns) ratio 24 Symmetrical Components – Positive Sequence, 3LG 13.8 kV Fault You have only positive sequence voltage and current since the system is balanced. A a R R B b C c IA = 619 ∠-88° Ia = 5158 ∠-118° IB = 619 ∠ 152° Ib = 5158 ∠ 122° IC = 619 ∠ 32° Ic = 5158 ∠ 2° Phase current = Sequence current That is; Ia = I+. Phase currents and voltages for the 115kV side. IA = Ia / 8.33 = 5158A / 8.33 IA = 619A 25 Symmetrical Components – Negative Sequence, L-L 13.8 kV Fault A a R R B b C c IA = 309 ∠-28° IB = 619 ∠ 152° IC = 309 ∠-28° Ia = 0 ∠ 0° Ib = 4467 ∠ 152° Ic = 4467 ∠-28° 115kV side sequence currents and voltages 3LG 13.8kV fault = 5158A, Ib=Ic=4467 A, 4467/5158 = 86.6%=√3/2 IB3LG = IBLL = 619A IA & IC = IB or Ia & Ic = Ib I2 = the phase current/√3 = 4467/√3 = 2579 Digital relays 50Q/51Q elements set using 3I2. 3I2 = Ib x √3 = 4467 x 1.732 = 7737, 13.8kV side sequence currents and voltages 26 Symmetrical Components – Zero Sequence, 1LG 13.8 kV Fault A a R R B b C c IA = 370 ∠-118° Ia=3I0=5346 ∠-118° IB = 0 ∠ 0° Ib = 0 ∠ 0° IC = 370 ∠ 62° Ic = 0 ∠ 0° Ia = 3Va/(Z1 + Z2 + Z0) 115kV side sequence currents and voltages 3I0 is the sum of the 3 phase currents and since Ib & Ic = 0, then 3I0 = Ia. This means the phase and ground overcurrent relays on the feeder breaker see the same amount of current. 5346/(8.33*√3) = 370 amps. So the high side phase current is the √3 less as compared to the 3Ø fault. Digital relays ground elements set using 3I0. 13.8kV side sequence currents and voltages 27 Symmetrical Components - Summary of 13.8 kV Faults If you have a Delta-Wye transformer bank, and you know the voltage ratio and secondary phase current values for 13.8kV 3LG (5158) and SLG (5346) faults, you can find the rest: 3LG – positive sequence current IA = 619 Ia = 5158 IB = 619 Ib = 5158 IC = 619 Ic = 5158 5158 / 8.33 = 619 L-L – negative sequence current IA = 309 Ia = 0 5158 x √3/2 = 4467 IB = 619 Ib = 4467 4467/(8.33x √3) = 309 IC = 309 Ic = 4467 309 x 2 = 619 Ia = 5158 = I1 Ib x √3 = 7737 = 3I2 SLG – zero sequence current IA = 370 Ia=5346 IB = 0 Ib = 0 IC = 370 Ic = 0 5346/(8.33x√3) = 370 Ia = 5346 = 3I0 28 Symmetrical Components - Summary of 13.8 kV Faults You’ve heard of a Line-to-Line fault, how about an “Antler-to-Antler” fault? 29 Electromechanical Relays used on Distribution Feeders Avista’s standard distribution relay package (until the mid-1990’s) included the following: 3 phase 50/51 CO-11 relays, 1 reclosing relay 1 ground 50/51 CO-11 relay . 30 1000 Electromechanical Relays used on Distribution Feeders 10 2 3 4 5 7 100 2 3 4 5 7 700 1000 2 3 4 5 7 10000 2 3 4 5 7 700 1 500 500 400 400 300 300 6 200 Objectives: − Protect the feeder conductor − Detect as low a fault current as possible (PU = 50% EOL fault amps) − Other than 51P, set pickup and time dial as low as possible and still have minimum Coordinating Time Interval (CTI) to next device. CTI is minimum time between operation of adjacent devices. − Carry normal maximum load (phase overcurrent only). − Pickup the feeder in a cold load condition (≅ 2 times maximum normal load) or pickup ½ of the next feeder load· 200 100 100 A. Transf. damage curve. 7.50 MVA. Category 3 Base I=313.78 A. Z= 6.9 percent. Latah Jct 13.8kV - LATAHJCT115 115.kV T 70 70 50 50 40 40 B. Conductor damage curve. k=0.08620 A=105500.0 cmils Conductor ACSR AWG Size 1/0 30 30 5 TRANSFORMER PROTECTION 20 20 1. SMD-2B 65E VERY SLOW 176-19-065 Minimum melt. H=8.33 S E C O N D S 1000 10 3 10 FEEDER VCB PROTECTION 3. LAT421 51P CO-9 CO-9 TD=1.900 CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s 7 5 7 5 5. LAT421 51N CO-9 CO-9 TD=3.000 CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s 4 3 4 3 2. LAT421 50P CO-9 INST TD=1.000 CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s A 2 2 4. LAT421 50N CO-9 INST TD=1.000 CTR=600/5 Pickup=3.A No inst. TP@5=0.048s 1 1 MAXIMUM FEEDER FUSE .7 .7 6. LAT421 FUSE S&C Link100T Total clear. .5 .5 .4 .4 .3 .3 .2 .2 B .1 .1 .07 .07 .05 4 .05 2 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 3 @ Voltage 13.8 KV 4 5 7 10000 2 3 4 5 By For No. Comment Date 31 7 .01 Electromechanical Relays used on Distribution Feeders Pickup setting criteria of 2/1 ratio of “end of line” fault duty / pickup - ensures that the relay will “see” the fault and operate when needed. FEEDER SETTINGS 51P = 2000 / 2 = 1000 A 51N = 1000 / 2 = 500 A 13 kV BUS MIN FAULT 3LG = 2000 A 1LG = 1000 A 32 Electromechanical Relays used on Distribution Feeders FEEDER SETTINGS 51P = 2000 / 2 = 1000 A 51N = 1000 / 2 = 500 A MIDLINE SETTINGS 51P = 1000 / 2 = 500 A 51N = 500 / 2 = 250 A 13 kV BUS FAULT at MIDLINE 3LG = 2000 A 1LG = 1000 A MIN FAULT at END OF LINE 3LG = 1000 A 1LG = 500 A 33 Electromechanical Relays used on Distribution Feeders 500A FEEDER SETTINGS 51P = 960 A 51N = 480 A 13 kV BUS SECTION LOAD = 500 A 34 Electromechanical Relays used on Distribution Feeders 500A FEEDER SETTINGS 51P = 960 A 51N = 480 A N.O. 13 kV BUS SECTION LOAD = 500 A SECTION LOAD = 250 A SECTION LOAD = 250 A 35 Electromechanical Relays used on Distribution Feeders Reclosing • Most overhead feeders also use reclosing capability to automatically re-energize the feeder for temporary faults. Most distribution reclosing relays have the capability of providing up to three or four recloses. -- Avista uses either one fast or one fast and one time delayed reclose to lockout. • The reclosing relay also provides a reset time generally adjustable from about 10 seconds to three minutes. This means if we run through the reclosing sequence and trip again within the reset time, the reclosing relay will lockout and the breaker will have to be closed by manual means. The time to reset from the lockout position is 3 to 6 seconds for EM reclosing relays. -- Avista uses reset times ranging from 90 to 180 seconds. • Lockout only for faults within the protected zone. That is; won’t lockout for faults beyond fuses, line reclosers etc. • Most distribution reclosing relays also have the capability of blocking instantaneous tripping. -- Avista normally blocks the INST tripping after the first trip to provide for a Fuse Protecting Scheme. 36 Electromechanical Relays used on Distribution Feeders Reclosing – Sequence shown for a permanent fault 13 kV BUS RECLOSING SEQUENCE Closed Open 0.5" 12" LOCKOUT RESET = 120" (INST Blocked during Reset Time) 37 Distribution Fusing – Fuse Protection/Saving Scheme 1000 10 2 3 4 5 7 100 2 3 700 Fault on fused lateral on an overhead feeder: - Station or midline 51 element back up fuse. - Station or midline 50 element protects fuse. During fault: • Trip and clear the fault at the station (or line recloser) by the instantaneous trip before the fuse is damaged for a lateral fault. • Reclose the breaker. That way if the fault were temporary the feeder is completely re-energized and back to normal. • During the reclose the reclosing relay has to block the instantaneous trip from tripping again. That way, if the fault still exists you force the time delay trip and the fuse will blow before you trip the feeder again thus isolating the fault and re-energizing most of the customers. • Of course if the fault were on the main trunk the breaker will trip to lockout. 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 500 400 400 300 300 200 200 100 100 70 70 50 S E C O N D S 1000 700 2 50 1 40 40 30 30 20 20 10 10 7 7 5 5 4 4 3 3 2 2 STATION FEEDER RELAYING 1 1 1. M15 515 GND TIME CO-11 TD=4.000 CTR=160 Pickup=3.A No inst. TP@5=1.0192s .7 .7 3. M15 50N CO-11 INST TD=1.000 CTR=160 Pickup=3.A No inst. TP@5=0.048s .5 .5 .4 .4 MAXIMUM FEEDER FUSE .3 .3 2. Moscow 515 Kear 140T Kearney 140T Total clear. .2 .2 .1 .1 .07 .07 .05 .05 3 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 M15 515 51N to 140T For Comment Aspen File: HORS M15 EXP.olr 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 Protection No. Date 3/06 38 7 .01 Distribution Fusing – Fuse Protection for Temporary Faults 1000 10 2 3 4 5 7 100 2 700 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 1 500 500 400 400 2 300 S E C O N D S 1000 3 300 200 200 100 100 70 70 50 50 40 40 30 30 20 20 1. BR1 S&C 140T S&C Link140T Minimum melt. 10 10 7 7 5 5 3. M15 515 S&C 80T S&C Link 80T Minimum melt. 4 4 3 3 2 2 2. ENDTAP S&C 40T S&C Link 40T Minimum melt. 1 1 .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 .1 .1 .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 Shows the maximum fault current for which S&C type T fuses can still be protected by a recloser/breaker instantaneous trip for temporary faults (minimum melt curve at 0.1 seconds): 6T – 120 amps 8T – 160 amps 10T – 225 amps 12T – 300 amps 15T – 390 amps 20T – 500 amps 25T – 640 amps 30T – 800 amps 40T – 1040 amps 50T – 1300 amps 65T – 1650 amps 80T – 2050 amps 100T – 2650 amps 140T – 3500 amps 200T – 5500 amps .01 By For No. Comment Date 39 Distribution Fusing – Fuse to Fuse Coordination NOTE: These values were taken from the S&C data bulletin 350-170 of March 28, 1988 based on no preloading and then preloading of the source side fuse link. Preloading is defined as the source side fuse carrying load amps equal to it’s rating prior to the fault. This means there was prior heating of that fuse so it doesn’t take as long to blow for a given fault. 1000 10 2 3 4 5 7 100 2 700 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 500 400 400 300 300 1 200 200 100 100 1. T FUSE S&C Link100T Minimum melt. 70 70 2. 251 140T FUSE stn S&C Link140T Total clear. 50 S E C O N D S 1000 700 2 50 40 40 30 30 20 20 10 10 7 7 5 5 4 4 3 3 2 2 1 1 .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 .1 .1 .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 .01 By For No. Comment Date 40 Distribution Fusing – S&C T-Fuse Current Ratings Typical continuous and 8 hour emergency rating of the S&C T rated silver fuse links plus the 140T and 200T. 1000 10 2 3 4 5 7 100 2 700 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 500 400 400 300 300 200 200 100 100 70 70 50 50 40 40 30 30 20 20 1. BR1 S&C 140T S&C Link140T Minimum melt. S 10 E C O 7 N D 5 S 4 General Rule: Fuse Blows at 2X Rating in 5 Minutes 1000 700 1 10 7 5 4 3 3 2 2 1 1 .7 .7 .5 .5 .4 .4 .3 .3 .2 .2 .1 .1 .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) T IME-CURRENT CURVES 2 @ Voltage 3 4 5 7 10000 2 3 4 5 7 By For No. Comment Date 41 .01 1000 Coordinating Time Intervals 10 2 3 4 5 7 100 2 5 3 700 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 4 500 500 400 400 6 200 300 A. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 200 FEEDER 252 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 300 70 70 50 50 40 40 30 20 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. S E C O N D S 1000 30 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 20 10 10 7 2 STATION VCB 252 PROTECTION 5 7 5 2. IDR 252 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s Ia= 5665.9A (35.4 sec A) T= 0.30s 4 4 1 3 3 3. IDR 252 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 2 B 5f 2 MAXIMUM FEEDER FUSE 4. 252 140T FUSE stn S&C Link140T Total clear. Ia= 5665.9A T= 0.09s MIDLINE OCR 1 DEVICES: CTI (Sec.) Relay – Fuse Total Clear 0.2 Relay – Series Trip Recloser 0.4 Relay – Relayed Line Recloser 0.3 Lo Side Xfmr Relay – Feeder Relay 0.4 Hi Side Xfmr Relay – Feeder Relay 0.4 Xfmr Fuse Min Melt – Feeder Relay 0.4 .7 .5 13.8 kV 3LG .7 .5 5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s .4 .3 .2 1 FAULT DESCRIPTION: Bus Fault on: 0 IDR 252 .4 .3 MAXIMUM MIDLINE FUSE .2 6. T FUSE S&C Link 50T Minimum melt. Ia= 5665.9A T= 0.01s .1 .1 A .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 Fault I=5665.9 A .01 10 2 HORS 2010 For 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 7 JDH No. Date 11-25-2008 42 .01 1000 Coordinating Time Intervals 10 2 3 4 5 7 100 2 5 3 700 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 4 500 500 400 400 6 200 300 A. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC 200 FEEDER 252 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 300 70 70 50 50 40 40 30 20 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. S E C O N D S 1000 30 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s Ia= 679.8A (5.7 sec A) T= 0.78s H=8.33 20 10 10 7 2 STATION VCB 252 PROTECTION 5 7 5 2. IDR 252 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s Ia= 5665.9A (35.4 sec A) T= 0.30s 4 4 1 3 3 3. IDR 252 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 3Io= 0.0A (0.0 sec A) T=9999s 2 B 5f 2 MAXIMUM FEEDER FUSE 4. 252 140T FUSE stn S&C Link140T Total clear. Ia= 5665.9A T= 0.09s MIDLINE OCR 1 DEVICES: CTI (Sec.) Relay – Fuse Total Clear 0.2 Relay – Series Trip Recloser 0.4 Relay – Relayed Line Recloser 0.3 Lo Side Xfmr Relay – Feeder Relay 0.4 Hi Side Xfmr Relay – Feeder Relay 0.4 Xfmr Fuse Min Melt – Feeder Relay 0.4 .7 .5 13.8 kV 3LG .7 .5 5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s .4 .3 .2 1 FAULT DESCRIPTION: Bus Fault on: 0 IDR 252 .4 .3 MAXIMUM MIDLINE FUSE .2 6. T FUSE S&C Link 50T Minimum melt. Ia= 5665.9A T= 0.01s .1 .1 A .07 .07 .05 .05 .04 .04 .03 .03 .02 .02 Fault I=5665.9 A .01 10 2 HORS 2010 For 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 7 JDH No. Date 11-25-2008 43 .01 1000 10 2 3 4 5 7 100 2 3 4 5 700 Coordinating Time Intervals 7 1000 2 3 4 5 7 10000 2 3 4 5 7 500 400 RATHDRUM FDR 231 PROTECTION 19. RAT 231 51P CO-11 CO-11 TD=1.800 17 300 CTR=800/5 Pickup=6.A No inst. TP@5=0.4533s 500 400 B. Conductor damage curve. k=0.06710 A=556000.0 cmils Conductor AAC MIDLINE C390 FED FROM HUE 142 - MINIMUM CONDUCTOR TO PROTECT 18 300 16. RAT 231 50P CO-11 INST TD=1.000 CTR=800/5 Pickup=7.A No inst. TP@5=0.048s 200 200 15. RAT 231 51N CO-11 CO-11 TD=5.000 CTR=800/5 Pickup=3.A No inst. TP@5=1.3192s 100 100 13 14. RAT 231 50N CO-11 INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 70 1000 700 A. Conductor damage curve. k=0.08620 A=133100.0 cmils Conductor ACSR AWG Size 2/0 MIDLINE C390 FED FROM RAT 231 - MINIMUM CONDUCTOR TO PROTECT 70 15 50 50 40 HUETTER FDR 142 PROTECTION RECLOSE IS 1SEC, 12 SEC, LO, 180 SEC RESET 20 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. S E C O N D S 1 4 10 8 19 11 20 10. HUE 142 51N 251 SEL-EI TD=4.000 CTR=160 Pickup=3.A No inst. TP@5=1.0858s 10 10 6 9. HUE 142 50N 251 INST TD=1.000 CTR=160 Pickup=3.A No inst. TP@5=0.048s 7 7 5 5 11. HUE 142 51Q 251 SEL-EI TD=4.000 CTR=160 Pickup=5.2A No inst. TP@5=1.0858s 4 4 3 3 HUE 142 MID C270R PROTECTION CALLED "HUE 142 LINE" IN POWERBASE 2 RECLOSE IS 1SEC, 12SEC, LO, 120 SEC RESET 2 8. HUE ML C270R 51P CO-11 TD=1.500 CTR=400/5 Pickup=7.A No inst. TP@5=0.3766s 7. HUE ML C270R 50P INST TD=1.000 CTR=400/5 Pickup=8.1A No inst. TP@5=0.048s 1 CTI (Sec.) Relay – Fuse Total Clear 0.2 Relay – Series Trip Recloser 0.4 Relay – Relayed Line Recloser 0.3 Lo Side Xfmr Relay – Feeder Relay 0.4 Hi Side Xfmr Relay – Feeder Relay 0.4 Xfmr Fuse Min Melt – Feeder Relay 0.4 30 5. HUE 142 50P 251 INST TD=1.000 CTR=160 Pickup=7.A No inst. TP@5=0.048s .7 DEVICES: 40 6. HUE 142 51P 251 SEL-EI TD=1.500 CTR=160 Pickup=6.A No inst. TP@5=0.4072s 30 1 .7 13. HUE ML C270R 51N CO-11 TD=7.000 CTR=400/5 Pickup=3.A No inst. TP@5=1.8052s .5 .4 .5 .4 12. HUE ML C270R 50N INST TD=1.000 CTR=400/5 Pickup=3.A No inst. TP@5=0.048s .3 .3 MIDLINE 390R PROTECTION 1. C390R MID 51P CO-9 CO-9 TD=2.500 CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s .2 .2 2. C390R MID 50P CO-9 INST TD=1.000 CTR=300/5 Pickup=6.A No inst. TP@5=0.048s .1 A .1 B 4. C390R MID 51N CO-9 CO-9 TD=2.500 CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s .07 .05 .07 12 3 2 3. C390R MID 50N CO-9 INST TD=1.000 CTR=300/5 Pickup=5.A No inst. TP@5=0.048s .04 9 14 7 .05 5 16 .04 .03 .03 LARGEST DOWNSTREAM FUSE FROM 390R MIDLINE 17. HUE 142 FUSE S&C Link 65T .02 Total clear. .02 18. RAT 231 FUSE S&C Link100T Total clear. .01 10 2 3 RAT 231 MID C390R For 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) 2 TIME-CURRENT CURVES @ Voltage 13.8 kV Huetter feeder 142 (2008) Rat feeder 231 (2009+) Midline Recloser C390R Comment Saved in: HUE142-RAT231 MID C390R 2007base.olr 3 4 5 7 10000 2 3 By 4 5 JDH No. Date 2-25-08 44 7 .01 1000 10 2 3 4 5 7 100 2 3 700 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 700 11 500 500 Coordinating Time Intervals 200 300 A. Conductor damage curve. k=0.08620 A=133100.0 cmils Conductor ACSR AWG Size 2/0 200 FEEDER 251 SMALLEST CONDUCTOR TO PROTECT 100 B. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.2 percent. IDAHO RD 12/16/20 MVA XFMR 100 300 70 70 50 50 40 40 30 20 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. 400 400 S E C O N D S 10 7 5 4 TRANSFORMER PROTECTION HI-SIDE CT'S 1. IDR A-777 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33 2. IDR A-777 51G 351 SEL-VI TD=1.000 CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33 4. IDR A-777 51Q 351 SEL-EI TD=4.200 CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33 LO-SIDE CT'S 3. IDR A-777 51N 351 SEL-EI TD=5.700 CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s CTI (Sec.) Relay – Fuse Total Clear 0.2 Relay – Series Trip Recloser 0.4 Relay – Relayed Line Recloser 0.3 Lo Side Xfmr Relay – Feeder Relay 0.4 Hi Side Xfmr Relay – Feeder Relay 0.4 Xfmr Fuse Min Melt – Feeder Relay 0.4 30 3 5 4 9 20 10 10 7 7 5 4 1 2 3 3 5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300 CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s 2 B 2 STATION VCB 251 PROTECTION 1 1 7. IDR 251 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s .7 DEVICES: 1000 .7 6. IDR 251 50P 351S INST TD=1.000 CTR=800/5 Pickup=7.A No inst. TP@5=0.048s .5 .5 .4 .4 9. IDR 251 51G 351S SEL-EI TD=3.900 CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s .3 .2 .3 .2 8. IDR 251 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 10. IDR 251 51Q 351S SEL-EI TD=3.500 CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s .1 A .1 .07 .05 .04 .07 MAXIMUM FEEDER FUSE MINIMUM FAULT TO DETECT: 3LG=2460A, SLG=1833A, L-L=2130A 8 .05 6 .04 11. 251 140T FUSE stn S&C Link140T Total clear. .03 .03 .02 .01 .02 10 2 3 IDR FEEDER 251 For 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A 2 3 @ Voltage 13.8 kV 4 5 7 10000 2 3 By 4 5 JDH No. Date 11-25-2008 45 7 .01 1000 10 2 3 4 5 7 100 2 3 4 5 7 700 Coordinating Time Intervals 1000 2 3 4 5 7 10000 2 3 4 5 7 700 1 500 500 400 400 300 300 6 200 200 100 100 A. Transf. damage curve. 7.50 MVA. Category 3 Base I=313.78 A. Z= 6.9 percent. Latah Jct 13.8kV - LATAHJCT115 115.kV T 70 50 40 40 B. Conductor damage curve. k=0.08620 A=105500.0 cmils Conductor ACSR AWG Size 1/0 30 5 TRANSFORMER PROTECTION 20 20 1. SMD-2B 65E VERY SLOW 176-19-065 Minimum melt. H=8.33 Typical Coordinating Time Intervals (CTI) that Avista generally uses between protective devices. Other utilities may use different times. 70 50 30 S E C O N D S 10 3 10 FEEDER VCB PROTECTION 3. LAT421 51P CO-9 CO-9 TD=1.900 CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s 7 5 7 5 5. LAT421 51N CO-9 CO-9 TD=3.000 CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s 4 3 4 3 2. LAT421 50P CO-9 INST TD=1.000 CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s A 2 2 4. LAT421 50N CO-9 INST TD=1.000 CTR=600/5 Pickup=3.A No inst. TP@5=0.048s 1 DEVICES: CTI (Sec.) Relay – Fuse Total Clear 0.2 Relay – Series Trip Recloser 0.4 Relay – Relayed Line Recloser 0.3 Lo Side Xfmr Relay – Feeder Relay 0.4 Hi Side Xfmr Relay – Feeder Relay 0.4 Xfmr Fuse Min Melt – Feeder Relay 0.4 1000 1 MAXIMUM FEEDER FUSE .7 .7 6. LAT421 FUSE S&C Link100T Total clear. .5 .5 .4 .4 .3 .3 .2 .2 B .1 .1 .07 .07 .05 4 .05 2 .04 .04 .03 .03 .02 .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) TIME-CURRENT CURVES 2 3 @ Voltage 13.8 KV 4 5 7 10000 2 3 4 5 By For No. Comment Date 46 7 .01 1000 10 2 3 4 5 7 100 2 1 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7 Coordinating Time Intervals 500 400 300 1. Moscow515 Kear 140T Kearney140T Minimummelt. I= 5158.1A T= 0.10s 500 400 300 200 2. M15-515 Phase Time CO-11 TD=1.500 CTR=160 Pickup=6.A No inst. TP@5=0.3766s I= 5158.1A (32.2 sec A) T= 0.33s 200 3. M15 A-172 Phase CO- 9 TD=1.500 CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605s I= 619.0A (5.2 sec A) T= 1.03s H=8.33 70 100 70 3LG Fault Coordination Example: Top – Ckt Swr w/ Phase E-M relay ----- 0.4 sec. -----Middle - E-M Phase relay for a 500 Amp Feeder ----- 0.2 sec. -----Bottom – 140T Feeder Fuse (Total Clear) 1000 700 700 50 40 30 100 50 40 30 20 20 2 S 10 E C 7 O 5 N 4 D 3 S 10 3 7 5 4 3 2 2 1 1 .7 .7 .5 .4 .3 .5 .4 .3 .2 .2 .1 .1 .07 .07 .05 .04 .03 FAULT DESCRIPTION: Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 3LG .02 .05 .04 .03 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) .02 2 3 4 5 7 TIME-CURRENT CURVES @Voltage 13.8 kV For M15 A-172 CS with fdr 515 with Kearney140T Fuse Comment Three Phase Fault 10000 2 3 4 5 By 7 DLH No. Date 12/12/05 47 .01 1000 10 2 3 4 5 7 100 2 1 3 4 5 7 700 Coordinating Time Intervals 70 ----- 0.4 sec. -----Middle - E-M relays (Phase & Ground) for a 500 Amp Feeder ----- 0.2 sec. -----Bottom – 140T Feeder Fuse (Total Clear) 3 4 5 7 10000 2 3 4 5 7 50 40 30 2 4 1000 700 500 400 300 2. M15 515 GND TIME CO-11 TD=4.000 CTR=160 Pickup=3.A No inst. TP@5=1.0192s I= 5346.5A (33.4 sec A) T= 0.29s 3. M15-515 Phase Time CO-11 TD=1.500 CTR=160 Pickup=6.A No inst. TP@5=0.3766s I= 5346.4A (33.4 sec A) T= 0.31s 100 Top – Ckt Swr w/ E-M Phase relay 2 1. Moscow 515 Kear 140T Kearney140T Minimummelt. I=5346.4A T= 0.09s 500 400 300 200 SLG Fault Coordination Example: 1000 200 100 70 50 40 30 4. M15 A-172 GND TIME CO-11 TD=4.000 CTR=240 Pickup=4.A No inst. TP@5=1.0192s I= 5346.5A (22.3 sec A) T= 0.83s 20 20 3 10 S 10 E C 7 O 5 N 4 D 3 S 7 5 4 3 2 2 1 1 .7 .7 .5 .4 .3 .5 .4 .3 .2 .2 .1 .1 .07 .07 .05 .04 .03 .05 .04 .03 .02 FAULT DESCRIPTION: Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 1LG Type=A .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) 2 3 4 5 7 TIME-CURRENT CURVES @Voltage 13.8 kV For MoscowCS with fdr 515 with 140T fuses Comment Single Line to Ground Fault 10000 2 3 4 5 By 7 DLH No. Date 12/12/05 48 .01 1000 10 2 3 4 5 7 100 2 1 3 4 5 700 Coordinating Time Intervals 1000 2 3 4 5 7 10000 2 3 4 5 7 500 400 300 2. M15-515 Phase Time CO-11 TD=1.500 CTR=160 Pickup=6.A No inst. TP@5=0.3766s I= 4467.0A (27.9 sec A) T= 0.43s 200 3. M15 A-172 Phase CO- 9 TD=1.500 CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605s I= 619.0A (5.2 sec A) T= 1.03s H=8.33 100 70 1000 700 1. Moscow515 Kear 140T Kearney140T Minimummelt. I= 4467.0A T= 0.12s 500 400 300 200 L-L Fault Coordination Example: 7 100 70 50 40 30 50 40 30 20 20 2 Top – Ckt Swr w/ E-M relay ----- 0.4 sec. -----Middle - E-M (Phase) relay for a 500 Amp Feeder ----- 0.2 sec. -----Bottom – 140T Feeder Fuse (Total Clear) S 10 E C 7 O 5 N 4 D 3 S 10 3 7 5 4 3 2 2 1 1 .7 .7 .5 .4 .3 .5 .4 .3 .2 .2 .1 .1 .07 .07 .05 .04 .03 .05 .04 .03 FAULT DESCRIPTION: .02 Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L LL Type=B-C .02 .01 10 2 3 4 5 7 100 2 3 4 5 7 1000 CURRENT (A) 2 3 4 5 7 TIME-CURRENT CURVES @Voltage 13.8 kV For MoscowCS A-172 with fdr 515 with 140T Fuse Comment Line to Line Fault 10000 2 3 4 5 By DLH No. Date 49 7 .01 The Final Product 1000 10 2 3 4 5 7 100 2 700 3 17 4 5 7 1000 2 3 An example of a completed 13.8kV Feeder Coordination Study with 20 Time-Current Curves representing: 1. INT A-742 51P 351 SEL-VI TD=1.200 CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33 200 2. INT A-742 51G 351 SEL-VI TD=1.000 CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33 Two Fuses 40 5 7 B. Conductor damage curve. k=0.14040 A=52630.0 cmils Conductor Copper (bare) AWG Size 2 NORTH BRANCH SMALLEST TRUNK CONDUCTOR 300 400 D. Conductor damage curve. k=0.08620 A=105500.0 cmils Conductor ACSR AWG Size 2/0 WEST BRANCH SMALLEST TRUNK CONDUCTOR 100 70 50 40 30 7. INT 12F2 51P 351S SEL-EI TD=1.500 CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s 20 6. INT 12F2 50P 351S INST TD=1.000 CTR=800/5 Pickup=7.A No inst. TP@5=0.048s 30 3 15 9 9& 15 11 11 4 &4 16 10 20 13 10 8. INT 12F2 50G 351S INST TD=1.000 CTR=800/5 Pickup=3.A No inst. TP@5=0.048s 7 10 7 7 10. INT 12F2 51Q 351S SEL-EI TD=3.500 CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s 5 5 4 4 1 2 12F2 MIDLINE 466R PROTECTION 3 3 13. F2 MID 466R 51P 351R SEL-EI TD=2.300 CTR=500/1 Pickup=1.44A No inst. TP@5=0.6243s A 2 2 12. F2 MID 466R 50P 351R INST TD=1.000 CTR=500/1 Pickup=1.68A No inst. TP@5=0.048s 1 15. F2 MID 466R 51G 351R SEL-EI TD=4.200 CTR=500/1 Pickup=0.89A No inst. TP@5=1.1401s 1 .7 14. F2 MID 466R 50G 351R INST TD=1.000 CTR=500/1 Pickup=0.89A No inst. TP@5=0.048s .7 .5 .5 16. F2 MID 466R 51Q 351R SEL-EI TD=3.800 CTR=500/1 Pickup=1.54A No inst. TP@5=1.0315s .4 .3 .3 .2 .2 EAST BRANCH - FEEDER MAXIMUM FUSE FAULT DUTY AT 150E; 3LG=2318, LL=2008, SLG=1684 5. INT F2 150E FUSE SMU-20_150E Total clear. .1 B D C .1 .07 Three Conductor Damage Curves 1000 500 STATION VCB 12F2 PROTECTION .4 Transformer Damage Curve 4 200 9. INT 12F2 51G 351S SEL-EI TD=3.900 CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s S E C O N D S 3 11. INT A-742 51Q 587 W2 SEL-EI TD=4.300 CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s 50 Instantaneous & Time-Delay Curves for the: - Transformer high side protection, - Transformer low side protection, - Station feeder breaker protection, - Midline feeder breaker protection. 2 A. Transf. damage curve. 12.00 MVA. Category 3 Base I=502.00 A. Z= 8.4 percent. INDIAN TRAIL 12/16/20 MVA XFMR 3. INT A-742 51N 351 SEL-EI TD=5.600 CTR=1200/5 Pickup=3.A No inst. TP@5=1.5201s 70 10000 C. Conductor damage curve. k=0.04704 A=350000.0 cmils Cable XLPE 90C/250C EAST BRANCH SMALLEST TRUNK CONDUCTOR - 350 CN15 4. INT A-742 51Q 351 SEL-EI TD=4.200 CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33 100 7 700 TRANSFORMER PROTECTION 300 5 5 500 400 4 .07 WEST OR NORTH BRANCH - FEEDER MAXIMUM FUSE FAULT DUTY AT 140T - WHEN FED FROM WEST MID 466R 3LG=2093, LL=1813, SLG=1520 .05 .04 148 12 .05 6 FAULT DUTY AT 140T - WHEN FED FROM NORTH (N.O. PT) 3LG=1932, LL=1673, SLG=1388 .03 .04 .03 17. INT F2 140T FUSE stn S&C Link140T Total clear. .02 .01 .02 10 2 3 4 5 7 100 INT 12F2 & MID 466R For 2 3 5 7 1000 CURRENT (A) TIME-CURRENT CURVES @ Voltage 13.8 kV Indian Trail feeder 12F2 and 12F2 Midline 466R in INT 2007base.olr Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A 4 2 3 4 5 7 10000 2 3 By 4 5 7 JDH No. Date 1-29-08 50 .01 IEEE Device Designations commonly used in Distribution Protection Avista sometimes adds letters to these such as F for feeders, T for transformers, B for bus and BF for breaker failure. 2 – Time delay relay. 27 – Undervoltage relay. 43 – Manual transfer or selective device. We use these for cutting in and out instantaneous overcurrent relays, reclosing relays etc. 50 (or 50P) – Instantaneous overcurrent phase relay. 50N (or 50G) – Instantaneous overcurrent ground (or neutral) relay. 50Q – Instantaneous Negative Sequence overcurrent relay. 51 (or 51P) – Time delay overcurrent phase relay. 51N (or 51G) – Time delay overcurrent ground (or neutral) relay. 51Q – Time delay Negative Sequence overcurrent relay. 52 – AC circuit breaker. 52/a – Circuit breaker auxiliary switch closed when the breaker is closed. 52/b – Circuit breaker auxiliary switch closed when the breaker is open. 59 – Overvoltage relay. 62 – Time Delay relay 63 – Sudden pressure relay. 79 – AC Reclosing relay. 81 – Frequency relay. 86 – Lock out relay which has several contacts. Avista uses 86T for a transformer lockout, 86B for a bus lockout etc. 87 – Differential relay. 94 – Auxiliary tripping relay. 51 Mike’s Turn 52 Distribution Transformer Electromechanical Relays Criteria (for outdoor bus arrangement, not switchgear) Protect the Transformer from thermal damage - Refer to Damage Curves Backup feeder protection (as much as possible) - Sensitivity is limited because load is higher Coordinate with downstream devices (feeder relays) Carry normal maximum load (phase only) Pick up Cold Load after outages 53 Distribution Transformer Electromechanical Relays - Setting Criteria Relays: 3 High Side Phase Overcurrent (with time and instantaneous elements) 1 Low Side Ground Overcurrent (with time and instantaneous elements) Sudden Pressure Relay 54 Distribution Transformer Electromechanical Relays - Setting Criteria Phase Overcurrent Settings – Current measured on 115kV side 51P Pickup (time overcurrent) Don’t trip for load or cold load pickup (use 2.4 * highest MVA rating) Ends up being higher than the feeder phase element pickup Example: 12/16/20 MVA unit would use 2.4*20*5 = 240 amps (1940A low side) 51P Time Lever (time dial) Coordinate with feeder relays for maximum fault (close in feeder fault) CTI is 0.4 seconds Worst coordination case: Ø-Ø on low side (discrepancy due to delta/wye conn.) Multiple feeder load can make the transformer relay operate faster 50P Pickup (instantaneous overcurrent) Must not trip for feeder faults Æ set at 170% of low side bus fault Accounts for DC offset 55 Distribution Transformer Electromechanical Relays - Setting Criteria Ground Overcurrent Settings – Current measured on 13.8 kV side 51N Pickup (time overcurrent) Set to same sensitivity as feeder phase relay (in case the feeder ground relay is failed) This setting is higher than the feeder ground, so we lose some sensitivity for backup 51N Time Lever (time dial) Coordinate with feeder relays for ground faults CTI is 0.4 seconds 50N Pickup (instantaneous overcurrent) DO NOT USE!!!! 56 Distribution Transformer & Feeder Protection with Microprocessor Relays Advantages: More precise TAP settings More Relay Elements Programmable Logic / Buttons Lower burden to CT Event Reports!!!!!!!!! Remote Communications Coordinate with like elements (faster) More Settings Microprocessor Relay 57 Distribution Transformer & Feeder Protection with Microprocessor Relays Elements We Set: 51P 50P 50P2 (FTB) 51G 50G (115kV) 51N (13.8kV) 50N1 (FTB) FTB = Fast Trip Block (feeder relays must be Microprocessor) 58 Distribution Transformer & Feeder Protection with Microprocessor Relays Transformer Phase Overcurrent Settings - Current measured on 115kV Side 51P - Phase Time Overcurrent Pickup Set to 240% of nameplate (same as EM relay) 51P Time Dial Set to coordinate with feeder’s fastest element for each fault CTI is still 0.4 seconds 50P1 – Phase instantaneous #1 Pickup Direct Trip Set to 130% of max 13.8 kV fault (vs. 170% with EM relay) 50P2 – Phase instantaneous pickup for Fast Trip Block scheme Set above transformer inrush 4 Cycle time delay Blocked if any feeder overcurrent elements are picked up 59 Distribution Transformer & Feeder Protection with Microprocessor Relays Transformer Ground Overcurrent Settings - Current calculated from 115kV CTs 51G - Ground Time Overcurrent Pickup 51GTime Dial Set very low (will not see low side ground faults due to transformer connection). Usually 120 Amps. Set very low 50G1 – Ground Instantaneous #1 Pickup Set very low. Usually 120 Amps. Symmetrical Components! 60 Distribution Transformer & Feeder Protection with Microprocessor Relays Transformer Neutral Overcurrent Settings - Current measured by neutral CT or calculated from 13.8kV CTs. 51N - Ground Time Overcurrent Pickup Set slightly higher than feeder ground pickup (about 1.3 times) 51NTime Dial Set to coordinate with feeder ground CTI is 0.4 seconds 50N1 – Ground Instantaneous for Fast Trip Block Set slightly above the feeder ground instantaneous pickup Time Delay by 4 cycles Blocked if Feeder overcurrent elements are picked up 61 Distribution Transformer & Feeder Protection with Microprocessor Relays Inrush – The current seen when energizing a transformer. Need to account for inrush when using instantaneous elements (regular or FTB). Inrush can be approximately 8 times the nameplate of a transformer. Note that the microprocessor relay only responds to the 60 HZ fundamental and that this fundamental portion of inrush current is ≅ 60% of the total. So to calculate a setting, we could use the 8 times rule of thumb along with the 60% value. For a 12/16/20 MVA transformer, the expected inrush would be 8*12*5*0.6 = 288 amps. We set a little above this number (360 Amps). 62 Distribution Transformer & Feeder Protection with Microprocessor Relays Transformer inrush UNFILTERED current. The peak current is about 1800 amps. Transformer inrush FILTERED current (filtered by digital filters to show basically only 60 HZ). Peak is about 700 amps. 63 Distribution Transformer & Feeder Protection with Microprocessor Relays Microprocessor Feeder Relay Overcurrent Reclosing Fast Trip Block Output Breaker Failure Output Elements We Set: 51P 50P 51G 50G 51Q 64 Distribution Transformer & Feeder Protection with Microprocessor Relays Feeder Phase Overcurrent Settings 51P - Phase Time Overcurrent Pickup Set above load and cold load (960 Amps for 500 Amp feeder) Same as EM pickup 51P Time Dial Same as EM relay (coordinate with downstream protection with CTI) Select a curve 50P – Phase instantaneous Pickup Set the same as the 51P pickup (960 Amps) 65 Distribution Transformer & Feeder Protection with Microprocessor Relays Feeder Ground Overcurrent Settings 51G - Phase Time Overcurrent Pickup Same as EM pickup which is 480 Amps 51G Time Dial Same as EM relay (coordinate with downstream protection) Select a curve 50G – Phase instantaneous Pickup Set the same as the 51G pickup 66 Distribution Transformer & Feeder Protection with Microprocessor Relays Feeder Negative Sequence Overcurrent Settings 51Q - Negative Sequence Time Overcurrent Pickup Set with equivalent sensitivity as the ground element (not affected by load) Coordinate with downstream protection 51Q Time Dial Same as EM relay (coordinate with downstream protection) Select a curve 50Q – Negative Sequence instantaneous Pickup DON’T USE!!!!! Contributions from motors during external faults could trip this 67 Transformer Differential Protection • The differential relay is connected to both the high and low side transformer BCT’s. • EM Differential Relay Since the distribution transformer is connected delta – wye the transformer CT’s have to be set wye – delta to compensate for the phase shift. 68 Transformer Differential Protection – External Fault PRI I SEC I CURRENT FLOW THROUGH AN E/M 87 DIFFERENTIAL RELAY FOR AN INTERNAL AND EXTERNAL FAULT CT POLARITY MARK BCT'S 87 R1 EXTERNAL FAULT THE SECONDARY CURRENTS FLOW THROUGH BOTH RESTRAINT COILS IN THE SAME DIRECTION AND THEN CIRCULATE BACK THROUGH THE CT'S. THEY DO NOT FLOW THROUGH THE OPERATE COIL 87 OP 87 R2 BCT'S PRI I SEC I 69 Transformer Differential Protection – Internal Fault PRI I SEC I CT POLARITY MARK 87 R1 BCT'S 87 OP 87 R2 INTERNAL FAULT THE SECONDARY CURRENTS FLOW THROUGH BOTH RESTRAINT COILS IN OPPOSITE DIRECTIONS, ADD AND THEN FLOW THROUGH THE OPERATE COIL AND BACK TO THE RESPECTIVE CT'S BCT'S SEC I PRI I 70 HANDOUT MOSCOW FEEDER 515 PROTECTION EXAMPLE • Where do we start the protection design? – Gather Information: • The feeder rating is 500 Amps. • The fault duty at the bus is 5,188 for a 3Ø fault and 5,346 for a SLG 71 Where do we start (Cont’d) • What other information do we have/need? – This feeder already has a line recloser and the Field Engineer wants to keep the same location. Reason for coordination was replacing the older recloser with a newer relayed recloser. – We then have to run feeder fault studies (normally done by a Distribution Engineer) and look at the feeder configuration so we know what fusing and relay settings to use. – We then generally start near the end of the feeder and work back towards the substation. A lot of times though we have to go back and forth because our first choice of a fuse size may not work correctly when we figure out the protection towards the substation and we have to make compromises. 72 How do we proceed? • At each coordination point – Temporary Faults - From Table 1 • What can a fuse be protected up to – Fuse-to-Fuse Coordination - From Table 2 • What will coordinate with the downstream device – Fuse Loading – From Table 3 • Are we above the fuse rating – Conductor Protection - From Table 7 • minimum conductor that can be protected by the feeder settings or fuse – Fault Detection • Can we detect the fault by our 2:1 margin 73 Begin at the END • NOTE: The actual Moscow feeder 515 does not look exactly like this even though the substation and line recloser settings we will arrive at are the actual settings. • POINT 8: This is a customers load and we are using 3-250 KVA transformers to serve the load. The full load of this size of bank is 31.4 amps. The Avista transformer fusing standard says to use a 65T on this transformer so that’s what we’ll choose. • POINT 7: This is the end of a 3Ø lateral and the fault duty is: 3Ø = 322 amps and SLG = 271 amps 74 POINT 6B: • What we know: – 3Ø lateral feeding to a 65T at the end – #4 ACSR exists. • Coordination: – Temporary Faults - From Table 1 we see that an 80T fuse can be protected up to 2,050 amps for temporary faults and the 3Ø fault is 1,907 amps so we could choose an 80T or higher from that standpoint – Fuse-to-Fuse Coordination – From Table 2, we see that we need an 80T, or larger, fuse to coordinate with the downstream 65T fuses (at fault duties < 1400A w/preload) – Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a 100T or smaller fuse – Fault Detection - Under the Relay Setting Criteria we want to detect the minimum end fault with a 2:1 margin. The SLG is 463 so the maximum fuse we could use would be: 463/2 (2:1 margin) = 231 amps so the largest fuse we could use is 231/2 (blows at twice the rating) = 115 so we could use a 100T or smaller fuse for this criteria – Loading – Assume the load at the end is all there is so no need to worry 75 Point 6B - So what fuse size should we use? • 80T 76 POINT 5 – Midline Recloser: • What we know: – 3Ø line of #4 ACSR feeding to point 6 – 3LG = 3453 A, 1LG = 2762 A • Coordination: – Temporary Faults - The fault duties at the recloser are: 3Ø = 3,453 amps and SLG = 2,762. We will assume we have a fused lateral just beyond the line recloser and we want to protect it for temporary faults. From Table 1 we see that we can protect a 100T fuse up to 2,650 and a 140T up to 3,500 amps. Therefore, from this standpoint we could use a 140T fuse beyond the recloser – Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a 100T or smaller fuse. That means that we won’t be able to set the line recloser to coordinate with a 140T and still protect the conductor. Therefore, we have to compromise and we will sacrifice the fuse protection for temporary faults in order to gain protection for the conductor. NOTE: This normally isn’t too bad because most faults are SLG and are somewhat less than the calculated value because of fault resistance and distance to the fault out on the lateral – Coordination – We will try and coordinate with a 100T fuse and still protect the #4 ACSR conductor. Once we determine the overcurrent pickup values, we will choose a Time Lever to provide 0.2 seconds (see Table 6) coordination with the 77 fuse and then will recheck to determine if we are satisfied with the conductor protection POINT 5 (Cont’d): 1. Fault Detection & Loading - The loading information we obtained from the Distribution Group is 84 amps normal and cold load ≅ 2 times = 168 amps. Therefore, we can set the phase PU at? • • 2. 3. 4. 200 amps which would carry the load and pick it up cold load. However, #4 ACSR can carry around 140 amps (see Table 4) so we would probably want to set about 300 amps to allow for load growth. NOTE: We do not set the phase overcurrent to protect the conductor from normal or emergency loading The Ø-Ø fault at point 6 is 0.866*1907 = 1,651 so our margin to detect that fault would be 1651/300 = 5.5:1 so no problem with the 300 amps Ø PU from that standpoint (used Ø-Ø because it’s the minimum multi phase fault) SLG Fault Detection – The SLG at point 6 is 1,492 so we could set the ground up to 1492/2 = 745 amps and still detect the fault. However, our criteria says to set as low as possible and still coordinate with the largest downstream device and from above we’re trying to use a 100T. Again this is 300 amps so in this case the ground PU will be set the same as the phase Instantaneous Units – The phase instantaneous will be set at 350 A and the ground instantaneous unit will be set at 300 A. Note that they can’t reach all the way to point 7 so they can’t protect the point 6C fuse from temporary faults occurring near the end of the lateral 78 POINT 3C: • What we know: – – • The fault duty at point 3 is: 3Ø = 3,699 amps and the SLG is 3,060 #4 ACSR 3Ø trunk feeding to the line recloser with a SLG of 2,762 amps Coordination: 1. 2. 3. 4. Temporary Faults - From Table 1 we see that a 140T fuse can be protected up to 3,500 amps for temporary faults and the 3Ø fault is 3,699 amps. This again appears to indicate we would want to use a 200T fuse Coordination – We set the line recloser up to coordinate with a 100T fuse so we wouldn’t be able to coordinate with the recloser by using a 140T so this would indicate we need a 200T Conductor Protection - From Table 7 we see that #4 ACSR requires a 100T fuse or smaller to be protected. OOPS The above coordination and conductor protection dilemma means that we can’t solve this problem by fusing this lateral. We also can’t remove the fuse because the substation setting of 960 A can’t protect the conductor either. 79 Point 3C - Solutions? • Move Recloser • Reconductor 80 POINT 1: • • What we know: – This is a 500 amp feeder so must set to carry load. NOTE: The load is 325 amps and cold load 650 – – The fault duty at point 1 is: 3Ø = 5,158 amps and SLG = 5,346 We want a Fuse Protection Scheme. Coordination: 1. 2. 3. Temporary Faults – We have decided that a 140T fuse is the maximum fuse we will use on the feeder even though it can’t be protected at the maximum fault duties. Coordination – We will coordinate with a 140T fuse at the maximum SLG fault duty of 5,346 amps with 0.2 seconds coordination time per Table 6. We will also coordinate with the line recloser settings with 0.3 seconds coordination time again per Table 6 Conductor Protection – The main trunk is 556 ACSR and from Table 7 a 500 amp feeder setting of 960 A can protect 1/0 ACSR or higher so no problem since all laterals are fused. 81 POINT 1 (Cont’d): 4. Fault Detection & Loading – We will set the phase pickup to carry 500 amps normally plus pick up cold load so will set at 960 amps. • The Ø-Ø fault at point 5 is 0.866*3453 = 2990 so our margin to detect that fault would be 2990/960 = 3.1:1 so no problem • SLG Fault Detection – Again per our criteria we will set as low as possible and still coordinate with the maximum downstream devices with the same coordination times as above • The SLG at point 5 is 2,762 so our margin to detect that fault is: 2762/480 = 5.7:1 so no problem • Instantaneous Units – The phase instantaneous will be set at 1,120A and the ground instantaneous unit will be set at 480 A 82 Questions? 83